You are on page 1of 2

May 21, 2021 Coordinaide™ - The S&C Protection & 1

Coordination Assistant
System Settings
Frequency Voltage Available Fault Current
60 Hz 300 kV 3000 A

2.Power Fuse
Curve Property Value
Power Fuse Manufacturer S&C
Type Liquid
Speed Slow
kV Range 7.5 - 23
Ampere Rating 10E
Preload Amps 0
Ambient Temp. Adjustment 25

4.Transformer (Damage Curve)


Curve Property Value
Transformer (Damage Curve) Connection: Delta-Grd.Y
3-Phase Secondary kV 0.48
3-Phase Rating kVA 2500
Impedance 5
Display Magnetizing Inrush true
Points?
@ 0.01 second 25
Magnetizing Inrush 120.275
@ 0.1 second 12
Magnetizing Inrush 57.732
@ 1 second 6
Cold-Load Pickup Inrush 28.866
@ 10 second 3
Cold-Load Pickup Inrush 14.433
@ 900 second 2
Cold-Load Pickup Inrush 9.622
Primary_kV/Full Load Amps 300.0/4.811
Secondary_kV/Full Load 0.48/3007.033
Amps

May 21, 2021 Coordinaide™ - The S&C Protection & 2


Coordination Assistant