Professional Documents
Culture Documents
Display
rollFLEX PX6
roll printing machine
Copyright
Drawings, installation plans and operating instructions as well as designs,
catalogues, brochures, diagrams etc. are the intellectual property of Starlinger.
Duplication, reproduction, dissemination and distribution to third parties are
prohibited. Moreover, they must not be used to produce or have produced
machines or machine components.
Great care was taken in the creation of this documentation. However, Starlinger
reserves the right to make changes and improvements to the documentation.
Information
This document describes how to use the central operating and control unit and is
part of the documentation series on the rollFLEX PX6 roll printing machine. This
documentation series comprises the following documents:
• General safety instructions
• Technical manual
• Display user manual
• Manufacturer's documentation
The documentation series is intended for use by technically qualified and trained
personnel who are responsible for the installation, operation, servicing and
maintenance of the machine. It contains all of the information needed to work on
or with the machine safely and properly and must therefore be observed
precisely. Compliance with the stated instructions and guidelines will also
increase the service life and optimise the performance of the machine.
NOTE!
The documentation series must always be at hand where the
machine is used and must be read and used by everyone who
works on or with the machine.
Notation
This document uses the following notation:
Multi-step instructions
In this document, multi-step instructions are presented as follows:
1. Step 1
2. Step 2
- Subtask
3. Step 3
Result
Lists
In this document, lists are presented as follows:
• List item 1
• List item 2
- Sub-item / Subtask
• List item 3
Result
Steps which do not have a particular defined order are also presented in the form
of lists. In such cases, the lists may have subtasks and results.
Indicator words
The following table provides an overview of the indicator words used and their
meaning:
Pictograms
This document contains pictograms with the following meaning:
Important information
Figures
The diagrams used in this document are example images in English, which may
deviate from your machine slightly, depending on the particular application. All
controls are governed by the specifications of the respective customer.
1 AREA OF APPLICATION
1.1 Function
The display is the central operating and control unit for the rollFLEX PX6 roll
printing machine. It consists of a control panel with a touch-sensitive screen
(touchscreen), the corresponding software with a graphical user interface and a
programmable control unit with several bus systems.
The display makes it possible to perform the following actions:
• Set and view parameters
• View status information
• Monitor production processes and functions
• Activate and deactivate individual components
• Control parts of the machine manually
• Confirm alarms
• Report and recipe management
Ethernet Customer
Control unit
network
X2X or ethernet
POWERLINK
Bus coupling
I/O modules
Sensors /
Actuators
2.3 Software
The operating system and control software which are displayed on the control
panel are installed on the control unit.
NOTE!
A malfunction may be caused by third-party software.
Third-party software can impair the function of the control
software, resulting in control faults.
Do not install third-party software!
4.1.1 Switching on
Switching the machine on (see the rollFLEX PX6 technical manual) automatically
puts the control panel into operation.
Starting up the control panel comprises the following steps:
1. Boot process
2. Loading of the operating system
3. Launching of the control software
Fig. 4967/4001
Fig. 4967/4002
Button Function
Change sign
Decimal point
Fig. 4967/4003
Button Function
Button Function
Not assigned
Highlight entry
Fig. 4967/4004
Fig. 4967/4005
Ready to take
Blue
screenshot
Button is being
Yellow Screenshot
touched
Screenshot is
Green
being saved
Authorisation level 2
Green Displayed
Additional information
Red Hidden
4.3.5 Calculator
Many menu screens have a calculator, which is opened as follows:
• Tap the [Calculator] button
The calculator opens.
Calculator
4.3.6 Screensaver
The screensaver is displayed automatically when the control panel has not being
used for a period of 30 min.
Fig. 4967/4006
4.4 Controls
The graphical user interface (see Chapter 4.1.1, Fig. 4967/4001) contains various
controls with the following functions:
• Enter and display parameters
• Display operating modes
• Activate and deactivate functions
Input field
White/Black Set value
with/without focus
4.4.2 Buttons
Tapping the buttons in the graphical user interface allows you to execute the
following user actions:
• Change statuses
• Execute processes
Sunken Active
Precise information on the individual buttons can be found in the description for
the respective menu.
Fig. 4967/4007
No symbol Deselected
Print variant
System time
Language selection
Changing units
1. Select authorisation level 3 (see Chapter 4.5.2)
2. Tap the [Change units] button
The button changes depending on the state.
The selected measuring system is accepted.
The lower the brightness value is set, the longer the service life of
the screen.
Green Displayed
Shift settings
Grey Hidden
Machine settings
Factory settings
0 55
1 152
3 193
4 135
All settings are saved by the control unit and remain active until they are
amended (after the required authorisation level is selected). Authorisation levels
2 - 4 are only valid for 10 min. After this time, authorisation level 1 is selected
automatically. After the machine is switched on, authorisation level 0 is selected
automatically.
Authorisation level 2
This menu screen allows you to check or modify all connection data and
configure settings for emergency operation.
Fig. 4967/4010
Green Extended
Format cylinder
Blue Retracted
Green Active
Cyclic operation of the
hydraulic unit
Grey Not active
Fig. 4967/4008
This menu screen shows the course of travel of the fabric for the selected print
variant.
Fig. 4967/4009
These menu pages show the factory settings which were configured by Starlinger
technicians. Some settings can also be configured by the customer, if
authorisation level 4 is selected.
Fig. 4967/4011
The machine's most important parameters can be checked and modified on this
menu screen.
Fig. 4967/5001
Corona pre-treatment
Discharge
unit
5.7
5.3
Winder
5.8
Infeed
5.4
Information
5.10
Alarm management
Pressure 5.11
5.5 Basic settings
4.5
All of the relevant unwinder parameters can be checked and changed in this
menu.
Fig. 4967/5002
Brake status
An angle measurement sensor measures the position of the rocker arm (15), and
uses this measurement to control the brake (4).
Ramp status
Green Switched on
Water cooler
Blue Switched off
All of the relevant parameters for the corona pre-treatment unit can be checked
and changed on this menu screen.
Fig. 4967/5003
Corona status
Green Started
Corona
Blue Stopped
This menu displays the fault and status messages of the corona pre-treatment
unit.
Fig. 4967/5004
1 Fault 3 Outputs
2 Status messages
Display status
Green
messages
All of the relevant infeed parameters can be checked and changed in this menu.
Fig. 4967/5005
1 Infeed status
Speed 5 Production speed (set/actual)
2
(set calculated/actual)
3 Infeed drive utilisation (actual) 6 Production speed indicator
Motor temperature (actual)
4 Ramp status 7
and [Servo drives] button
The set values can be changed with authorisation level 2 selected.
Ramp status
Infeed status
Green Raised
Pressure roller
Blue Lowered
Servo drives
All of the parameters for the machine's printing area can be checked and
changed in this menu.
Fig. 4967/5006
Ramp status
All of the relevant printing unit parameters are checked and changed on this
menu screen.
Fig. 4967/5007
Green Switched on
Measuring probe or valve
Blue Switched off
Green Switched on
Drying system
Blue Switched off
Representatio
Button Status Name / Function
n
Green Switched on
Raster drum
Blue Switched off
If the direction change has not been carried out properly for the
printing unit in question, the machine cannot be started!
Fig. 4967/5008
All of the relevant drying system parameters can be checked and changed in this
menu.
Fig. 4967/5009
Ramp status
Green Switched on
Drying system
Blue Switched off
All of the relevant parameters for the discharge can be checked and changed in
this menu.
Fig. 4967/5010
Discharge speed
1 Production speed (set/actual) 5
(set calculated/actual)
Discharge drive utilisation
2 Production speed indicator 6
(actual)
3 Motor temperature (actual) 7 Ramp status
4 Discharge status 8 [Production speed] button
Ramp status
Drive status
Green Raised
Pressure roller
Blue Lowered
Servo drives
All of the relevant winder parameters can be checked and changed in this menu.
Fig. 4967/5011
Oscillator status
Ensures the regular composition of the fabric roll. The winder is regulated by
motor, within the set traversing range.
Green Active
Oscillator
Shift statistics
“Winder diagnostics”
Green
menu screen is open
Winder diagnostics
“Winder diagnostics”
Grey menu screen is not
open
On this menu screen, you can reference and manually move the winder.
Fig. 4967/5012
Oscillator status
Sensor status
Starting referencing
1. Select authorisation level 2
2. Tap the [Start referencing] button
Referencing is started.
Starting referencing
Cancelling referencing
1. Select authorisation level 2
2. Tap the [Cancel referencing] button
Referencing is reset.
Cancel referencing
Green Automatic
Operating mode
Blue Manual
This menu displays the shift statistics – provided that shift data has been
registered (see Chapter 4.5.1).
Fig. 4967/5013
In this menu you can set the winder's working parameters, based on the roll
diameter.
Fig. 4967/5029
5.9.1 Overview
Fig. 4967/5014
YES NO
Opening a file
1. Select authorisation level 2
2. Open the folder containing the file to be opened by tapping the relevant
button
3. Select the file in the folder by tapping the button [Move one item
upwards] or [Move one item downwards]
The line of the selected file is highlighted.
4. Tap the [Open file] button
The "Display data" menu screen opens (see Chapter 5.9.2), and the
contents of the file is displayed.
Open a file
3. Select the file in the folder by tapping the button [Move one item
upwards] or [Move one item downwards]
The line of the selected file is highlighted.
4. Tap the [Send file by e-mail] button
The file is sent by e-mail to the recipients listed in the fields
“e-mail address recipient 1 / 2” (see Chapter 4.5.3,
Fig. 4967/4010 (8)).
Importing a file
A file is imported from a USB stick onto the memory card as follows:
1. Select authorisation level 2
2. Connect the USB stick to the USB port on the switching cabinet of the
operating unit (see the rollFLEX PX6 technical manual)
3. Open the folder by tapping the [USB stick folder] button
4. Select the file in the folder by tapping the button [Move one item
upwards] or [Move one item downwards]
The line of the selected file is highlighted.
5. Tap the [Import file] button
The file is saved to the control unit's memory card.
If a recipe has been imported:
The “Recipes” folder contains the imported file.
If a text file has been imported:
The “Production report” folder contains the imported file.
Import a file
Exporting a file
A file is exported from the memory card onto a USB stick as follows:
1. Select authorisation level 2
2. Connect the USB stick to the USB port on the switching cabinet of the
operating unit (see the rollFLEX PX6 technical manual)
Export a file
Delete a file
Fig. 4967/5015
Fig. 4967/5016
A setup report consists of a list of the machine settings and additional information
entered by the user. This menu screen is used to generate the setup report and
save it to a file.
Fig. 4967/5017
1 User name
3 Report preview
2 Comment
This menu screen is used to generate the safety system report and save it to a
file.
Fig. 4967/5018
1 User name
3 Report preview
2 Comment
This menu screen is used to display control unit data, battery status and machine
operating hours.
Fig. 4967/5019
Battery status
The indicator (3) provides information about the status of the battery. If it is red,
the battery must be changed (see Chapter 6.3).
Ping
To open, tap the [Control unit logbook] button on the "Control unit"
menu screen in the "Information"
submenu
This menu screen displays the logbook for the control unit, allowing you to
analyse faults with the bus system and control unit crashes.
Fig. 4967/5020
Exporting data
1. Connect the USB stick to the "USB1" port of the control panel
(see the manufacturer's documentation)
2. Tap the [Export data] button
The button changes depending on the state.
The data is saved to the USB stick.
Data is being
Green
exported
Exporting data
Available for
Blue
selection
This menu screen allows you to check the hardware and software data for the
control unit.
Fig. 4967/5021
Update
Fig. 4967/5022
Fig. 4967/5023
SafeLogic commissioning
Fig. 4967/5024
This menu screen shows the alarm history of the selected frequency converter.
Fig. 4967/5025
Alarm status
In this menu, you can check user actions and alarms and reset alarms, and
export them to a USB stick if required.
Fig. 4967/5026
Alarm status
Alarm procedure
All problems which occur during operation are immediately displayed in the status
area (see Chapter 4.3.1, Fig. 4967/4005 (8)) in the form of alarms, and are
logged in the "Alarm management" screen.
As soon as an operational condition is re-established (for example, when the
motor has reached a normal temperature), the alarm disappears from the list of
active alarms. However, it is still visible in the Alarm history list (see Chapter
5.11.3).
User actions
Alarm history
All of the user actions (starting the machine, changing set values, etc.) are logged
in the User actions list. This is used to diagnose faults and monitor production.
User actions are displayed on this menu screen.
Fig. 4967/5027
Active alarms
Alarm history
This menu screen displays alarms that occurred in the past, and allows you to
export them onto a USB stick.
Fig. 4967/5028
Alarm status
Filtering alarms
1. Tap the [Alarm type] button
The list of alarm types opens.
2. Tap an alarm type in the list
The list of alarm types closes and the list of alarms is filtered
depending on the alarm type selected.
Alarm type
Exporting alarms
1. Connect the USB stick to the USB1 port (see the manufacturer's
documentation)
2. Select authorisation level 2
3. Tap the [Export alarms] button
The alarms are saved to the USB stick.
Active alarms
User actions
5.1;00
Main menu
5.1
4.5.1;200 4.5.3;201
Basic settings
4.5
4.5.5;0
6.1;0
Cleaning the
touchscreen
6.1
6.2;0
Calibrating the
touchscreen
6.2
5.2;10
Unwinder
5.2
5.3.1;60 5.3.2;65
Corona pre-
treatment unit
5.3
5.4;20
Infeed
5.4
5.1;00
Main menu
5.1
5.6;50
Drying system
5.6
5.7;40
Discharge
5.7
5.8.1;80
Winder
5.8
5.8.2;85
5.8.3;90
5.8.4;81
5.11.1;140 5.11.2;150
Alarm
management
5.11
5.11.3;145
5.1;00
Main menu
5.1
5.9.3;131
5.9.4;135
5.9.5;137
5.10.1;112 5.10.2;115
Information
5.10
5.10.3;240
5.10.7;119
6 MAINTENANCE
CAUTION!
Malfunctions can be caused by accidentally triggering commands!
Only clean the touchscreen when the cleaning screen is selected
or when the unit is switched off!
NOTE!
The control panel may be damaged by improper cleaning!
Never spray cleaning agent directly onto the touchscreen!
Only use the following cleaning agents:
• Screen cleaner
• Alcohol
• Water and washing-up liquid
Cleaning screen
Fig. 4967/6001
Fig. 4967/6002
Once the cleaning time has elapsed, the main menu opens
automatically.
Closing the cleaning screen before the cleaning time has elapsed
• Touch the [Close cleaning screen] button for 5 sec
The main menu opens.
Calibration screen
Fig. 4967/6003
• Tap the crosshairs which appear in the corners, one after another
The touchscreen is calibrated.
NOTE!
Risk of data loss!
Perform a backup of your data before changing the memory card!
CAUTION!
Risk of electric shock!
• Only change the memory card when the machine is de-
energised!
• Only change the memory card according to the instructions of
a Starlinger technician!
Fig. 4967/6004
NOTE!
Risk of data loss!
Perform a backup of your data before carrying out a software
update!
7 TROUBLESHOOTING
When contacting our Customer Service Center, please have the following
information to hand:
• Serial number of the machine
• General description of the problem
• Precise wording of the alarm text AND the alarm number, as displayed
in the Alarm management screen (see Chapter 5.11)
• Fault codes shown on the screens for the affected drives
• As precise details as possible about when and under what
circumstances the fault occurred
• If you have already carried out tests, as precise details as possible
about the results obtained
• Name of the person familiar with the problem
• Your phone number and e-mail address
The new roll of fabric did not move during • Pay attention to the feed diagram (see
the roll change due to the fabric the rollFLEX PX6 technical manual)
preparation. • Prepare the fabric accordingly
Roll 1 diameter for automatic roll change too large ({RollDia1} >
04-057
{ChgDia})
Roll 2 diameter for automatic roll change too large ({RollDia2} >
04-058
{ChgDia})
Cause Remedy
• Check the adjustment of the winder
shaft used
A web break occurred before the min. • Select winder shaft size for the roll
diameter for the roll change was reached. being changed to
• Use a roll of fabric without winding
defects
Fig. 4967/7001
Procedure
1. Note down or export the number and text of active and historical
X2X link bus alarms (see Chapter 5.11)
2. Switch machine off and back on again after 30 seconds
3. Start the machine and observe its operating behaviour
4. Check status LEDs on the X2X link module (type X20 BR 9300)
(see the manufacturer's documentation)
- "r" lights up green: X2X link module is OK
- "r" flashes: X2X link module is faulty
- "r" does not light up: X2X link module no supply
- "X" lights up orange: X2X link communication OK
- "X" does not light up: no X2X link communication
5. Check the status LEDs on the X20 module
- "r" lights up green: X20 module is OK
- "r" flashes: X20 module is faulty
- "r" does not light up: X20 link module no supply
6. Check X2X link addressing and hardware number (addresses can only
be assigned once)
7. On the relevant menu screens, check the protocol counter and observe
the fault counter (CycleCount, BreakCount)
8. Check on the back of the X2X link module that the bus modules (5) and
(6) are properly connected
9. Check X2X link cable connection
10. Check the earthing of the machine or check it by having an earthing
measurement carried out on your premises by an authorised electrical
contractor
11. Check shielding
- Check shield connection and cable ties
- Check the shielding braid and wire for corrosion
- Check that the motor cable is shielded on both sides and that the
shielding is fully tightened (check the shield connection points for
electrical conductivity)
- Check top-hat rail for earth connection
- Check that the earth connection and the X2X link bus are attached
to the shielding plate of the frequency converter
- Check that the connections are made properly (pay attention to the
electrical conductivity of the shield connection points)
- Check analogue signal on one side (via the control module is best)
Procedure
1. Note down or export the number and text of active and historical EPL
bus alarms (see Chapter 5.11)
2. Switch machine off and back on again after 30 seconds
3. Start the machine and observe its operating behaviour
4. Check the status LED on the bus controller
- Lights up green: bus controller is OK
- Lights up red: bus controller is faulty
5. Check EPL addressing and hardware number (addresses can only be
assigned once)
6. Check the status of the EPL module on the corresponding menu
screens
7. Check on the back of the X20 I/O system that all EPL modules are
properly connected
8. Check the ethernet cable connection (min. CAT 5/6 with metal on the
connector)
9. Check the earthing of the machine or check it by having an earthing
measurement carried out on your premises by an authorised electrical
contractor
10. Check shielding
- Check shield connection and cable ties
- Check the shielding braid and wire for corrosion
- Check that the motor cable is shielded on both sides and that the
shielding is fully tightened (check the shield connection points for
electrical conductivity)
7.12 Sensors
Procedure
1. Check sensor for mechanical damage
2. Check the switching distance (see the manufacturer's documentation)
3. Reposition the sensor if necessary
- Unplug connector
- Undo nut (sensor is freed)
- Set the distance between the sensor and the object with a feeler
gauge
- Check the connector
Procedure
1. Check the sensor for mechanical damage, particularly the diaphragm
2. Check power supply
3. Measure the output signals and check the value on the display
4. Check parameters or DIP switch setting (addressing) (see the Circuit
diagram)
5. Check wiring
6. Check the plug connections
7. If necessary, replace the sensor
- If the new sensor does not function, replace the input card
Procedure
1. Check sensor for mechanical damage
2. Adjust the spring on the bayonet coupling so that the sensor is pushed
against the surface being monitored
3. Check and tighten terminal connections where required, observe
polarity
4. Check wiring
5. Check sensor:
- For sensors with a connecting head, disconnect and twist the
connection line
- For potted sensors, connect a new sensor or a twisted
compensating line to the input
The ambient temperature is displayed on the screen:
The sensor is faulty.
The ambient temperature is not displayed on the screen:
The control unit input is faulty.
6. If necessary, replace the sensor
- If the new sensor does not function, replace the temperature control
or input card
Procedure
1. Clean sensor
2. Check sensor for mechanical damage
3. Position the sensor
The red measurement point must not be interrupted by machine
parts.
The sensor must be positioned such that the material being detected
(e.g. fabric) is located in the centre of the detection area.
4. Remove any obstacles from the detection area of the sensor
5. Check power supply
6. Measure output signals
7. If necessary, replace the cable
8. If necessary, replace the sensor
- If the new sensor does not function, replace the input card
Procedure
1. Check the transmitter and receiver or reflector for mechanical damage
2. Clean the transmitter and receiver or reflector
3. Check power supply
4. Measure output signal
5. Check the alignment of the transmitter to the receiver or reflector
6. Replace the reflector with another of the same type
7. If necessary, replace the cable
8. If necessary, replace the transmitter and receiver or reflector
- If the new transmitter or receiver does not function, replace the input
card.
Procedure
1. Clean the fan filter and replace if necessary (only with filter material of
the same properties)
2. Check the circulation of the fan
The cold air must be taken in by the fan unimpeded, passed through
an air filter, and blown into the switching cabinet.
The hot air must be able to escape unimpeded through the air filter
at the air outlet.
3. Inspect the fan in the switching cabinet and replace if necessary
4. Close the switching cabinet door
NOTE!
The water supply line and return line must not be mixed up during
installation!
The condensate drain must be installed in accordance with the
manufacturer's documentation.
NOTE!
Possibility of damage to the electronic components through
condensation!
• Keep the switching cabinet doors closed at all times!
• Keep the seals in the proper condition!
• Check condensate drain on a monthly basis for blockage and
clean as necessary
The switching cabinets are provided with seals to prevent the
discharged hot air from one getting in another switching cabinet.
The moisture in the discharged hot air results in increased
condensation during cooling. If a large amount of condensate
collects in the drop pan, it could be taken up by the fan, and result
in serious damage to electronic components.
Procedure
1. Close the switching cabinet door
2. Open the cooling water line
3. Clean the filter in the cooling line
4. Check the supply temperature at the cooling unit input, and reduce if
necessary
5. Inspect the cooling unit, if necessary set the temperature to 35°C
6. Inspect the fan in the switching cabinet and replace if necessary
7. Inspect the valve in the cooling unit and replace if necessary
8. Increase the flow volume on the water distributor
9. Reduce the ambient temperature
7.14 DC drives
Procedure
1. Allow motor to cool down
2. Check mechanism for ease of movement
3. Check gearbox and maintain as necessary
- Check the oil level
- Check the bearing
Procedure
1. Compare set current value on the triggering device with the value on the
motor type plate
2. Check power supply
3. Check cable connection
4. Check motor temperature
5. Check mechanism for ease of movement
6. Check gearbox and maintain as necessary
- Check the oil level
- Check the bearing
7. Check direction of rotation
8. Check the motor for short-circuit/short-circuit to earth and other
malfunctions
9. Perform maintenance (see the manufacturer's documentation)
Procedure
1. Note down the alarm number and reset the alarm (see Chapter 5.11)
This activates the reset input on the frequency converter.
2. Check the diagnostics menu for of the drive
3. Check power supply
4. Check wiring
5. Look-up the fault displayed on the frequency converter in the
manufacturer's documentation
6. Switch machine off and back on again after 30 seconds
Procedure
1. Allow motor to cool down
2. Check mechanism for ease of movement
Procedure
1. Check the power supply on the stepper motor module and on the bus
node in question (see Chapter 7.18.5)
2. Check cable connections for the stepper motor and stepper motor
module against the Circuit diagram
3. Check that the models installed correspond to those listed in the Circuit
diagram
4. If necessary, replace the stepper motor module
Procedure
1. Check the stepper motor module
2. Check that the models installed correspond to those listed in the Circuit
diagram
3. Check mechanical components
4. Move the stepper motor manually
5. Re-reference the stepper motor module
Procedure
1. Check temperature of the servo converter
2. Reset the alarm (see Chapter 5.11)
3. Ensure that there is an adequate airflow across the heat sink
4. Check the heat sink for dirt (dust) and clean as necessary
5. Check the cooler fan for proper functioning (noise)
6. Check switching cabinet air-conditioning (see Chapter 7.13)
7. Check drive components for ease of movement
Procedure
1. Allow motor to cool down
2. Check mechanism for ease of movement
3. Check gearbox and maintain as necessary
- Check the oil level
- Check the bearing
4. If the motor is soiled, clean the following parts:
- cooling fins
- if applicable, the filter
Procedure
1. Check the machine for jams
2. Note down the alarm number and alarm text incl. the following fault
numbers of the servo drive and reset the alarm (see Chapter 5.11)
3. Run machine until empty
4. Switch machine off and back on again after 30 seconds
5. Check mains supply
6. Check fuse, motor cable, rotary encoder cable and bus cable
Procedure
1. Note down the alarm number and alarm text, and reset the alarm (see
Chapter 5.11)
2. Check drive elements for ease of movement (if necessary, eliminate
jams and check brakes)
3. Check mains supply
4. Run machine until empty
5. Switch machine off and back on again after 30 seconds
6. Check the plugged connections for the motor cable and rotary encoder
7. Replace the motor cable or rotary encoder cable
8. Uncouple the load (disconnect the coupling) and test in idle operation
9. Check the motor for short-circuit/short-circuit to earth and other
malfunctions
Procedure
1. Check mains supply
2. Test fuses
3. If applicable, check the contactor
4. Check wiring
5. Check servo converter (see Chapter 7.16.3)
Procedure
1. Note down the alarm number and alarm text, and reset the alarm (see
Chapter 5.11)
2. Check cable connection
3. Remove the plugged connections in a de-energised state and reconnect
4. Press the <EMERGENCY STOP> push button
5. Turn the motor by hand and observe the status LEDs on the expansion
card of the servo inverter (see the manufacturer's documentation),
depending on the direction of rotation a certain status LED must light
up.
6. Check shielding
- Check shield connection and cable ties
- Check the shielding braid and wire for corrosion
- Check that the motor cable is shielded on both sides and that the
shielding is fully tightened (check the shield connection points for
electrical conductivity)
- Check top-hat rail for earth connection
- Check that the earth connection is attached to the shielding plate of
the frequency converter
- Check that the connections are made properly (pay attention to the
electrical conductivity of the shield connection points)
7. If necessary, replace the cable of the rotary encoder
8. If necessary, replace the expansion card
9. If necessary, replace the motor
Procedure
1. Check the machine for jams or material fragments
2. Check the machine components for ease of movement
3. Reset the alarm (see Chapter 5.11)
4. Run machine until empty
5. Switch machine off and back on again after 30 seconds
6. On the menu screen of the drive in question, observe the rocker arm
position
7. Check the drive for rotary encoder faults (see Chapter 7.16.6)
DANGER!
Risk to life from the failure of the safety system!
Have the condition and function of all components and functions
of the safety system checked once a month by an electrician.
Fig. 4967/7002
DANGER!
Risk to life from the failure of one of the modules in the safety
system ("F A I L" LEDs are permanently lit).
Replace the defective module immediately and initiate all of the
necessary repair measures straight away.
Testing LEDs
1. Set <Select> switch to "TEST"
2. Press the <Confirm> button
All LEDs of the safety processor (left-hand and centre module of the
SafeLOGIC) remain lit while the respective button is being pressed.
On releases < 1.4, the "SKEY" LED does not light up for this test.
DANGER!
Danger to life from electric current!
Work on the safety system must only be carried out by trained
electricians! Safety measures for work on electrical components
must be adhered to!
DANGER!
Risk of life from the failure of the safety system after the SafeKEY
is removed!
Pulling out the SafeKEY during operation causes the SafeLOGIC
to restart, switches off all safety-related actuators, and may result
in the destruction of the data on the SafeKEY.
The SafeKEY must not be pulled out during operation!
NOTE!
Possible damage to property due to the use of non-original
replacement parts!
Only a SafeKEY from the original manufacturer may be used.
DANGER!
Danger to life from electric current!
Work on the safety system must only be carried out by trained
electricians! Safety measures for work on electrical components
must be adhered to!
NOTE!
Possible damage to property due to the use of non-original
replacement parts!
Only a SafeIO module or a SafeLOGIC safety control from the
original manufacturer may be used.
The SafeLOGIC automatically detects the replacement of safe modules. After the
module change, the overall system (SafeLOGIC, openSAFETY) automatically
ensures that the module is operated again with the correct parameters and that
incompatible module types are rejected. Therefore after the module replacement
the following potential faults remain:
• Transposing the terminals between the different modules
• Wiring fault
• Transposing SafeIO modules
Procedure
1. Switch off the machine
2. Pull the terminals out of the defective modules
3. Remove the modules (see the manufacturer's documentation)
4. Install new modules
5. Connect the terminals
6. If more than 1 module or the SafeLOGIC is replaced: test wiring
7. Switch on the machine and wait until it is ready for operation
8. Confirm replacement on the SafeLOGIC: Select the "Module
replacement" function (position acc.to number of modules replaced)
and confirm
9. Check all functions of the safety system
Replacement of the modules is complete.
DANGER!
The safety switch of safety devices may never be bypassed in
order to get rid of an alarm!
Procedure
• Check if one or more safety doors are open, and if necessary close
• Check settings (switching distance) of the safety switches
• Check parallelism, height and lateral offset
• Check proper functioning of safety switch
• Check wiring of the safety switch for damage
• Check if the wiring to the safety control is broken
• Check LED for the safety circuit
Procedure
• Properly close the safety door
• Check the status of the safety control and of the respective input card
(depending on the switch type, one or both channels of the safety door
circuit must logic “1” for a closed safety door, and logic “0” for an open
safety door (see the Circuit diagram))
• Check the switching distance of the safety switch
• Lateral and height offset: adjust active areas of the safety switch and
actuator so that they are parallel and opposite one another
• Check the safety switch (see Chapter 7.17.2)
• Check wiring for damage and check against the Circuit diagram
• Perform a functional test of the safety doors
Procedure
• Check the status of the safety control and the respective input card
• Check wiring for damage and check against the Circuit diagram
• Perform a functional test of the safety doors
Procedure
1. Check wiring against the Circuit diagram
2. Check the safety switch (see Chapter 7.17.2)
3. Check the safety components
4. Contact the Customer-Service Center
Procedure
1. Check <Stop> push button for mechanical damage
2. Check cables of the Stop loop against the Circuit diagram
<Stop> push buttons are normally not actuated when closed.
3. If necessary, replace the <Stop> push button
Procedure
• Check the movement of the unwinder with the manual adjustment
movement
• Activate the web edge control
• Perform material alignment
• Check settings against the Circuit diagram, correct if necessary
• Read the display of the control unit in question (see the manufacturer's
documentation)
• Carry out the colour comparison again (see the rollFLEX PX6 technical
manual)
• Check the sensors (see the manufacturer's documentation)
Procedure
1. Measure voltage at the power supply unit
- Typical tolerance range: 23 - 25 V DC
- For deviations from the tolerance range: Check the size of the input
voltage, if necessary adjust the power supply unit
2. Check the LED on the power supply unit
- Lights up red: Defect or short-circuit
3. Check the functional ability of the buffer module and replace if
necessary
4. Check the line safety switch in the switching cabinet against the Circuit
diagram
5. Check the consumers individually:
- Switch off all consumers with the 24V line safety switch
- Measure voltage at the power supply unit
- Switch the consumers back on again one at a time, until the voltage
fails again
- On the line safety switch in question: Check the consumer against
the Circuit diagram, replace defective consumers
NOTES
.................................................................................................................................
.................................................................................................................................
.................................................................................................................................
.................................................................................................................................
.................................................................................................................................
.................................................................................................................................
.................................................................................................................................
.................................................................................................................................
.................................................................................................................................
.................................................................................................................................
.................................................................................................................................
.................................................................................................................................
.................................................................................................................................
.................................................................................................................................
.................................................................................................................................
.................................................................................................................................
.................................................................................................................................
.................................................................................................................................
.................................................................................................................................
.................................................................................................................................
.................................................................................................................................
.................................................................................................................................
.................................................................................................................................