Professional Documents
Culture Documents
Transformer Relay
Instruction Manual
Preface
Introduction
This guide and the relevant operating or service manual documentation for the equipment provide
full information on safe handling, commissioning and testing of this equipment.
Documentation for equipment ordered from NR is dispatched separately from manufactured goods
and may not be received at the same time. Therefore, this guide is provided to ensure that printed
information normally present on equipment is fully understood by the recipient.
Before carrying out any work on the equipment, the user should be familiar with the contents of
this manual, and read relevant chapter carefully.
This chapter describes the safety precautions recommended when using the equipment. Before
installing and using the equipment, this chapter must be thoroughly read and understood.
When electrical equipment is in operation, dangerous voltages will be present in certain parts of
the equipment. Failure to observe warning notices, incorrect use, or improper use may endanger
personnel and equipment and cause personal injury or physical damage.
Before working in the terminal strip area, the equipment must be isolated.
Proper and safe operation of the equipment depends on appropriate shipping and handling,
proper storage, installation and commissioning, and on careful operation, maintenance and
servicing. For this reason, only qualified personnel may work on or operate the equipment.
Are familiar with the installation, commissioning, and operation of the equipment and of the
system to which it is being connected;
Are able to safely perform switching operations in accordance with accepted safety
engineering practices and are authorized to energize and de-energize equipment and to
isolate, ground, and label it;
Are trained in the care and use of safety apparatus in accordance with safety engineering
practices;
Date: 2015-07-29
Preface
DANGER! means that death, severe personal injury and considerable equipment damage
will occur if safety precautions are disregarded.
WARNING! means that death, severe personal and considerable equipment damage
could occur if safety precautions are disregarded.
CAUTION! means that light personal injury or equipment damage may occur if safe ty
precautions are disregarded.
NOTICE! is particularly applies to damage to device and to resulting damage of the protected
equipment.
DANGER!
NEVER allow a open current transformer (CT) secondary circuit connected to this
device while the primary system is live. Open CT circuit will produce a dangerously high
voltage that cause death.
WARNING!
ONLY qualified personnel should work on or in the vicinity of this device. This personnel
MUST be familiar with all safety regulations and service procedures described in this
manual. During operating of electrical device, certain part of the device is under high
voltage. Severe personal injury and significant device damage could result from
improper behavior.
WARNING!
Do NOT touch the exposed terminals of this device while the power supply is on. The
generated high voltage causes death, injury, and device damage.
WARNING!
Thirty seconds is NECESSARY for discharging the voltage. Hazardous voltage can be
present in the DC circuit just after switching off the DC power supply.
CAUTION!
Earthing
Operating environment
ONLY use the device within the range of ambient environment and in an
environment free of abnormal vibration.
Ratings
Date: 2015-07-29
Preface
Check the input ratings BEFORE applying AC voltage/current and power supply to
the device.
Do NOT attach or remove printed circuit board if the device is powered on.
External circuit
Check the supply voltage used when connecting the device output contacts to
external circuits, in order to prevent overheating.
Connection cable
NOTICE!
We reserve all rights to this document and to the information contained herein. Improper use in particular reproduction and dissemination
to third parties is strictly forbidden except where expressly authorized.
The information in this manual is carefully checked periodically, and necessary corrections will be included in future editions. If
nevertheless any errors are detected, suggestions for correction or improvement are greatly appreciated.
Date: 2015-07-29
Preface
Documentation Structure
The manual provides a functional and technical description of this relay and a comprehensive set
of instructions for the relay’s use and application.
1 Introduction
Briefly introduce the application, functions and features about this relay.
2 Technical Data
Introduce the technical data about this relay, such as electrical specifications, mechanical
specifications, ambient temperature and humidity range, communication port parameters, type
tests, setting ranges and accuracy limits and the certifications that our products have passed.
3 Operation Theory
Introduce a comprehensive and detailed functional description of all protective elements.
4 Supervision
Introduce the automatic self-supervision function of this relay.
5 Management
Introduce the management function (measurment and recording) of this relay.
6 Hardware
Introduce the main function carried out by each plug-in module of this relay and providing the
definition of pins of each plug-in module, typical wiring is provided.
7 Settings
List settings including system settings, communication settings and etc.
9 Configurable Function
Brief introduction of configurable functions and configuration software.
10 Communication
Introduce the communication port and protocol which this relay can support, IEC60970 -5-103,
IEC61850 and DNP3.0 protocols are introduced in details.
11 Installation
Date: 2015-07-29
Preface
12 Commissioning
Introduce how to commission this relay, comprising checks on the calibration and functionality of
this relay.
13 Maintenance
A general maintenance policy for this relay is outlined.
Deviations may be permitted in drawings and tables when the type of designator can be obviously
derived from the illustration.
&
AND gate
≥1
OR gate
Comparator
Date: 2015-07-29
Preface
Timer
t
Time (optional definite-time or inverse-time characteristic)
t
10ms 2ms
Timer [delay pickup (10ms), delay dropoff (2ms), non-settable]
[XXX] 0ms
Timer (delay pickup, settable)
0ms [XXX]
Timer (delay drop off, settable)
[XXX] [XXX]
Timer (delay pickup, delay drop off, settable)
IDMT
Timer (inverse-time characteristic)
Basic Example
A, B, C L1, L2, L3 Ia, Ib, Ic, I0 IL1, IL2, IL3, IN
AN, BN, CN L1N, L2N, L3N Ua, Ub, Uc VL1, VL2, VL3
ABC L123 Uab, Ubc, Uca VL12, VL23, VL31
U (voltage) V U0, U1, U2 VN, V1, V2
Date: 2015-07-29
1 Introduction
1 Introduction
Table of Contents
1.1 Application.....................................................................................................................1-1
1.2 Functions .......................................................................................................................1-2
1.3 Features..........................................................................................................................1-5
List of Figures
List of Tables
Date: 2015-07-29
1 Introduction
Date: 2015-07-29
1 Introduction
1.1 Application
PCS-985TE provides up to 36 analog input channels including current and voltage inputs. The
transformer protections are configurable. Ancillary functions of fault diagnostic, disturbance
records, event records and communication function are integrated in the device.
NOTICE!
Current transformers (CT) used for differential protection may be DIFFERENT from
those for backup protection.
Busbar 1
Busbar 2 50BF PCS-985TE
Busbar VT MR 49 62PD 21 27P,59P
50F
CB VT
Cal
3I0
l n abcn
*
Main 24 50P,51P 50G,51G 50Q,51Q 51PALM 59G 59GAlm
Transformer 87T 64REF
81
VT
abc
*
Conventional CT
*
Big-ratio CT
*
* *
* *
Step-down
Transformer
VT VT
abc
abc
Date: 2015-07-29
1 Introduction
Busbar 1
Busbar 2
Busbar VT
CB VT
l n abcn
*
Main
Transformer
PCS-985TE
VT
abc
*
Conventional CT
*
Big-ratio CT
*
* * Cal
3I0
* *
Step-down
Transformer
MR 87T 64REF 64REF 50P, 51P 50G,51G 51PALM
VT VT
abc
abc
59G 59GAlm
Busbar 1
Busbar 2 50BF PCS-985TE
Busbar VT
62PD
MR
CB VT Cal
3I0
l n abcn
*
Start up/stand by *
Transformer
87T 64REF 24 50P, 51P 50G,51G 51PALM 59G 59GAlm
* *
* * * * 64REF 64REF
VT VT VT VT
1.2 Functions
Protective Functions
Date: 2015-07-29
1 Introduction
The protective functions listed in following table are available for PCS-985TE; the functions can be
configured according to user’s requirement.
Miscellaneous functions
Miscellaneous functions are listed in the following table, such as measurement, self-supervision
and oscillography, communication functions, and etc.
Miscellaneous functions
Date: 2015-07-29
1 Introduction
Miscellaneous functions
Serial port
Ports type Electrical Ethernet port
Optical Ethernet port
Rear
IEC 60870-5-103 (Ethernet port or serial port)
communication
IEC 61850-8-1 (Ethernet port)
ports to host
Protocol type Modbus (Serial port)
DNP 3.0 (Ethernet port)
(Specified when ordering)
Date: 2015-07-29
1 Introduction
Miscellaneous functions
1.3 Features
Configurable Function
Modules of the device adopt intelligent design, amount of input and output modules and module
slot position are configurable. User can increase or decrease the amount of AC input module,
binary input module and binary output module, and terminals of those modules can be defined
according to actual requirement. Besides, configurability is also reflected in software design of
device, which means that user can hide the protective element not used or add new protective
module not in standard configuration.
The hardware of the device comprises a 32-bit microprocessor and two 32-bit digital signal
processors (DSP). Those processors can operate in parallel companied by fast A/D converter. The
32-bit microprocessor performs logic calculation and the DSP performs the protection calculation.
High performance hardware ensures real time calculation of all protection relays within a sampling
interval.
On the premise of 24 samples per cycle, all data measurement, calculation and logic
discrimination could be done within one sampling period. The event recording and protection logic
calculation are completed simultaneously.
Independent fault detectors in fault detector DSP module for connecting power supply of output
relays. The relay can drive a tripping output only when protection element on protection DSP
module operates with the fault detector in the fault detector DSP modu le operating simultaneously.
This kind of independent supervision of tripping outputs using fault detectors can avoid any
mal-operation possibly caused by any hardware component failure. This highly increases the
security. Please refer to Chapter 6 for details.
Date: 2015-07-29
1 Introduction
The tripping output contacts can be configured by tripping matrix and suitable to any mode of
tripping.
Event records include 1024 binary input events and 1024 alarm events. Disturbance records
including 64 fault reports, and 64 disturbance waveforms, and file format of waveform is
compatible with international COMTRADE91 and COMTRADE99 file. Analog inputs and binary
inputs can be recorded, and three oscillography triggering mode are supported, which are
protection pickup triggering, manual triggering on keypad of device, and remote triggering through
PCS-Explorer software.
Powerful PC tool software (PCS-Explorer) can fulfill protection function configuration, modify
setting and waveform analysis.
Main and backup protection are integrated in one set of protection device. Protection information
is shared by all parts. The device can record all relevant waveforms of any fault.
DPFC (deviation of power frequency component) biased current differential protection element is
regardless of the load current and is sensitive to small internal fault current within the transformer.
Its performance against current transformer saturation is also good.
Based on the operation sequence of DPFC restraint current element and DPFC differential current
element of differential protection, external fault with CT saturation or internal fault can be
distinguished correctly.
Date: 2015-07-29
2 Technical Data
2 Technical Data
Table of Contents
2.6 Certifications.................................................................................................................2-6
2.7 Terminals........................................................................................................................2-6
Date: 2015-07-29
2 Technical Data
Date: 2015-07-29
2 Technical Data
Date: 2015-07-29
2 Technical Data
1. Tripping contact
2. Signal contact
Date: 2015-07-29
2 Technical Data
0.65A@48Vdc
0.35A@110Vdc
Breaking capacity (L/R=40ms) 0.30A@125Vdc
0.20A@220Vdc
0.15A@250Vdc
Burden 400mW
380Vac
Ma ximal system voltage
250Vdc
Test voltage across open contact 1200V RMS for 1min
12A@3s
15A@1s
Short duration current
20A@0.5s
30A@0.2s
Durability (Loaded contact) 10,000 operations minimum
Number Up to 33 signal output according to various hardware configurations
NOTICE!
Tripping output contacts are not connected to trip circuit breakers directly. They are
connected to interposing relays or lockout relays contacts which are connected to trip
circuit breakers.
Date: 2015-07-29
2 Technical Data
Altitude <3000m
Ma ximal capacity 32
Transmission distance <500m
Safety le vel Isolation to ELV level
Twisted pair Screened twisted pair cable
Type RS-232
Baud Rate 4.8kbit/s, 9.6kbit/s, 19.2kbit/s, 38.4kbit/s, 57.6kbit/s, 115.2kbit/s
Printer type EPSON ® 300K printer
Safety le vel Isolation to ELV level
Type RS-485
Transmission distance <500m
Ma ximal capacity 32
Timing standard PPS, IRIG-B
Date: 2015-07-29
2 Technical Data
IEC 60255-22-1:2007
1MHz burst disturbance test Common mode: class Ⅲ 2.5kV
Differential mode: class Ⅲ 1.0kV
IEC60255-22-2:2008 class Ⅳ
Electrostatic discharge test For contact discharge: 8kV
For air discharge: 15kV
IEC 60255-22-3:2007 class Ⅲ
Frequency sweep
Radiated amplitude-modulated
10V/m (rms), f=80~1000MHz
Radio frequency interference tests Spot frequency
Radiated amplitude-modulated
10V/m (rms), f=80MHz/160MH z/450MH z/900 MHz
Radiated pulse-modulated
10V/m (rms), f=900MHz
IEC 60255-22-4:2008
Fast transient disturbance tests Power supply, I/O, Earth: class Ⅳ, 4kV, 2.5kH z, 5/50ns
Communication terminals: class Ⅳ, 2kV, 5kHz, 5/50ns
IEC 60255-22-5:2008
Surge immunity test
Power supply, AC input, I/O port: class Ⅳ, 1.2/50us
Date: 2015-07-29
2 Technical Data
2.6 Certifications
ISO9001: 2008
ISO14001:2004
OHSAS18001: 2007
ISO10012:2003
CMMI L5
2.7 Terminals
Connection Type Wire Size
2 2
Crimp terminals, 1.5mm ~4.0mm lead
AC current If using 4.0mm 2 lead, only dedicated terminal cable lug provided by NR
can be adopted.
AC voltage Crimp terminals, 1.0mm 2~2.5mm 2 lead
Power supply Crimp terminals, 1.0mm 2~2.5mm 2 lead
Contact I/O Crimp terminals, 1.0mm 2~2.5mm 2 lead
Grounding (Earthing) Connection BVR type, 2.5mm²~6.0mm 2 lead
Date: 2015-07-29
2 Technical Data
Ma ximum duration 2048 sampled points (24 sampled points per cycle)
Recording position 3 cycles before pickup of trigger element
There are some symbols mentioned in the following sections and the meaning of them is given
here.
pu – per-unit value
Date: 2015-07-29
2 Technical Data
Tolerance of operating current ≤5% of operating current or 0.02 pu, whichever is greater
Tolerance of definite-time time delay ≤1% of setting +40ms (at 2 times current s etting)
Operating time of inverse-time overcurrent ≤2.5% operating time or 40ms, whichever is greater(for current
element between 1.2 and 20 multiples of pickup)
Date: 2015-07-29
2 Technical Data
Tolerance of definite-time time delay ≤1% of setting +40ms (at 2 times current setting)
Operating time of inverse-time overcurrent ≤2.5% operating time or 40ms, whichever is greater(for current
element between 1.2 and 20 multiples of pickup)
Tolerance of definite-time time delay ≤1% of setting +40ms (at 2 times current setting)
Operating time of inverse-time overcurrent ≤2.5% operating time or 40ms, whichever is greater(for current
element between 1.2 and 20 multiples of pickup)
Date: 2015-07-29
2 Technical Data
Tolerance of definite-time time delay ≤1% of setting +40ms (at 1.2 times voltage setting)
Operating time of inverse-time overvoltage ≤2.5% operating time or 40ms, whichever is greater (for voltage
element between 1.2 and 2 multiples of pickup)
Date: 2015-07-29
2 Technical Data
Tolerance of time delay ≤1% of setting +40ms (at 2 times current setting)
Date: 2015-07-29
2 Technical Data
Tolerance of time setting ≤1% of setting +40ms (at 2 times current setting)
Date: 2015-07-29
3 Operation Theory
3 Operation Theory
Table of Contents
Date: 2015-07-29
3 Operation Theory
Date: 2015-07-29
3 Operation Theory
Date: 2015-07-29
3 Operation Theory
3.14.6 Settings.......................................................................................................................3-112
3.15.2 Function......................................................................................................................3-114
3.15.4 Logic...........................................................................................................................3-115
3.15.6 Settings.......................................................................................................................3-117
Date: 2015-07-29
3 Operation Theory
Date: 2015-07-29
3 Operation Theory
List of Figures
Date: 2015-07-29
3 Operation Theory
Figure 3.2-4 Logic diagram of startup of transformer current differential protection ...... 3-18
Figure 3.2-5 Logic diagram of steady-state current differential element of transformer.. 3-19
Figure 3.2-6 Logic diagram of DPFC current differential element of main transformer ... 3-20
Figure 3.2-7 Function block diagram of transformer current differential protection ........ 3-21
Figure 3.3-1 Operation characteristic curve of restricted earth fault protection .............. 3-29
Figure 3.3-2 Logic diagram of restricted earth fault protection ......................................... 3-33
Figure 3.3-3 Function block diagram of restricted earth fault protection.......................... 3-34
Figure 3.4-1 Logic diagram of negative -sequence overcurrent protection (x=1 or 2) ...... 3-40
Figure 3.4-2 Function block diagram of negative-sequence overcurrent protection ....... 3-40
Figure 3.6-1 Function diagram of main transformer phase overcurrent protection ......... 3-50
Figure 3.6-3 Direction characteristic of main transformer phase overcurrent protection 3-54
Figure 3.6-4 Logic diagram of main transformer phase overcurrent protection (x=1,2,3) 3-57
Figure 3.6-5 Logic diagram of phase -to-phase VCE of main transformer phase overcurrent
protection .............................................................................................................................. 3-57
Figure 3.6-7 Logic diagram of direction element of main transformer phase overcurrent
protection .............................................................................................................................. 3-58
Figure 3.6-9 Function block diagram of main transformer phase overcurrent protection 3-59
Figure 3.7-1 Logic diagram of phase overcurrent alarm elements (x=1, 2, 3) ................... 3-64
Figure 3.7-2 Function block diagram of phase overcurrent alarm elements .................... 3-65
Date: 2015-07-29
3 Operation Theory
Figure 3.8-4 Logic diagram of main transformer ground overcurrent protection (x=1,2,3)
............................................................................................................................................... 3-72
Figure 3.8-5 Logic diagram of direction element of main transformer ground overcurrent
protection .............................................................................................................................. 3-72
Figure 3.8-7 Function block diagram of main transformer ground overcurrent protection
............................................................................................................................................... 3-73
Figure 3.11-2 Function block diagram of residual overvoltage protection ....................... 3-89
Figure 3.12-2 Logic diagram of stage 1 of overfrequency band accumulate protection .. 3-94
Figure 3.12-3 Logic diagram of stage 4 of overfrequency band accumulate protection .. 3-94
Figure 3.13-1 Logic diagram of stage x of underfrequency protection (x=1~4) .............. 3-101
Figure 3.14-2 Function block diagram of rate -of-frequency-change protection ............. 3-110
Figure 3.15-2 Function block diagram of thermal overload protection ........................... 3-116
Figure 3.16-2 Operating characteristic of phase -to-phase impedance relay .................. 3-120
Date: 2015-07-29
3 Operation Theory
Figure 3.16-4 Logic diagram of FD PSBR (takes HV side as an example) ....................... 3-123
Figure 3.17-2 Function block diagram of breaker failure protection ............................... 3-131
Figure 3.19-2 Function block diagram of breaker flashover protection .......................... 3-140
Figure 3.20-2 Function block diagram of mechanical protection (x=1, 2) ....................... 3-143
Figure 3.21-2 Function block diagram of interconnection status element ...................... 3-148
Figure 3.23-2 Function block diagram of three-phase current element .......................... 3-153
Figure 3.24-2 Function block diagram of three-phase voltage element .......................... 3-157
Figure 3.25-1 Function block diagram of residual current element ................................. 3-161
List of Tables
Table 3.2-1 Phase shift matrix for phase compensation ...................................................... 3-5
Table 3.2-2 Input signals of transformer current differential protection ........................... 3-21
Table 3.2-3 Output signals of transformer current differential protection ........................ 3-21
Table 3.2-4 Output signals of transformer current differential protection (event recorder)
............................................................................................................................................... 3-21
Date: 2015-07-29
3 Operation Theory
Table 3.2-6 Settings list of transformer current differential protection ............................. 3-23
Table 3.3-1 Input signals of restricted earth fault protection ............................................. 3-34
Table 3.3-2 Output signals of restricted earth fault protection .......................................... 3-34
Table 3.3-3 Output signals of restricted earth fault protection (event recorder) .............. 3-34
Table 3.3-4 Output signals of restricted earth fault protection (measurements) .............. 3-35
Table 3.3-5 Settings list of restricted earth fault protection ............................................... 3-36
Table 3.6-2 Input signals of main transformer phase overcurrent protection................... 3-59
Table 3.6-3 Output signals of main transformer phase overcurrent protection................ 3-59
Table 3.6-4 Output signals of main transformer phase overcurrent protection (event
recorder)................................................................................................................................ 3-60
Table 3.6-6 Settings list of main transformer phase overcurrent protection .................... 3-61
Table 3.7-1 Input signals of phase overcurrent alarm elements ........................................ 3-65
Table 3.7-2 Output signals of phase overcurrent alarm elements ..................................... 3-65
Table 3.7-3 Output signals of phase overcurrent alarm elements (event recorder) ......... 3-65
Date: 2015-07-29
3 Operation Theory
Table 3.8-2 Input signals of main transformer ground overcurrent protection................. 3-73
Table 3.8-3 Output signals of main transformer ground overcurrent protection.............. 3-74
Table 3.8-4 Output signals of main transformer ground overcurrent protection (event
recorder)................................................................................................................................ 3-74
Table 3.8-6 Settings list of main transformer ground overcurrent protection .................. 3-75
Table 3.9-3 Output signals of phase overvoltage protection (event recorder).................. 3-80
Table 3.9-4 Output signals of phase overvoltage protection (measurements) ................. 3-81
Table 3.10-3 Output signals of phase undervoltage protection (event recorder) ............. 3-85
Table 3.10-4 Output signals of phase undervoltage protection (measurements) ............. 3-86
Table 3.11-3 Output signals of residual overvoltage protection (event recorder) ............ 3-90
Table 3.11-4 Output signals of residual overvoltage protection (measurements) ............ 3-90
Table 3.12-3 Output signals of overfrequency protection (event recorder) ...................... 3-96
Date: 2015-07-29
3 Operation Theory
Table 3.13-3 Output signals of underfrequency protection (event recorder) .................. 3-104
Table 3.15-3 Output signals of thermal overload protection (event recorder) ................ 3-117
Table 3.15-4 Output signals of thermal overload protection (measurements) ................ 3-117
Table 3.16-3 Output signals of impedance protection (event recorder) .......................... 3-125
Table 3.17-3 Output signals of breaker failure protection (event recorder) .................... 3-131
Table 3.18-3 Output signals of pole disagreement protection (event recorder) ............. 3-135
Table 3.19-3 Output signals of breaker flashover protection (event recorder) ............... 3-140
Date: 2015-07-29
3 Operation Theory
Table 3.20-3 Output signals of mechanical protection (event recorder) (x=1, 2) ............ 3-143
Table 3.21-3 Output signals of interconnection status element (measurements) .......... 3-148
Table 3.23-3 Output signals of three-phase current element (event recorder) ............... 3-153
Table 3.23-4 Output signals of three-phase current element (measurements) ............... 3-153
Table 3.24-3 Output signals of three-phase voltage element (event recorder) ............... 3-158
Table 3.24-4 Output signals of three-phase voltage element (measurements) ............... 3-158
Table 3.25-1 Input signals of single current element with filter ....................................... 3-161
Table 3.25-3 Output signals of residual current element (measurements) ..................... 3-161
Table 3.26-3 Output signals of residual voltage element (measurements) ..................... 3-162
Date: 2015-07-29
3 Operation Theory
Date: 2015-07-29
3 Operation Theory
3.1 Overview
The device has 2 plug-in modules (protection DSP module and fault detector DSP module) for
protection calculation. Protection DSP module is responsible for calculation of protection elements,
and fault detector DSP module is responsible for calculation of general fault detector element to
determine fault appearance on the protected power system. General fault detector picks up to
provide positive supply to output relays. The output relays can only operate when both a protection
element and the corresponding general fault detector operate simultaneously. Otherwise, the
output relays would not operate. An alarm message will be issued with blocking output if a
protection element operates while the corresponding general fault detector does not operate.
The fault detector of fault detector DSP module consists of several independent fault detector
elements, which can monitor corresponding protection elements without influence to other
protection elements. For example, biased current differential protection will not release tripping
command until both protection element of protection DSP module and the corresponding fault
detector of fault detector DSP module operate simultaneously. Furthermore, if there is a hardware
fault on one DSP module or the differential current is at the trip boundary, the inconsistent pickup
of fault detectors of biased current differential protection on two DSP modules will occur.
NOTICE!
In Section 3.2, the prefix “Y” in settings (such as [Y.87T.I_Biased]) and input/output
signals (such as [Y.87T.Op_Biased]) can be Tr. Details of the prefix are:
3.2.1 Application
Transformer current differential protection is the main protection for the internal short -circuit fault of
transformer winding. Current differential protection can operate quickly to clear the internal fault to
avoid the transformer from damages or reduce the maintenance cost as low as possible.
For Y-Y, △→△, △→Y and Y→△ connection, all possible vector combinations have been taken
into account, so it is very flexible.
Optional inrush current distinguished principles and inrush current blocking method, which
can avoid the inrush current reliably, and it can also ensure the operation speed when a fault
happens during normal operation.
Date: 2015-07-29
3 Operation Theory
Biased current differential element with initial restraint slope is adopted, it consists of sensitive
and conventional biased differential elements as well as independent CT saturation criterion.
DPFC current differential element can fully reflect the change of differential current and
restraint current, and it is not affected by the load current and is sensitive to small internal fault
current within the transformer. Its performance against CT saturation is also good.
For internal serious fault, once the differential current is larger than the current setting of
instantaneous differential element, the current differential protection will operate to cut off the
fault quickly.
Voltage is also used to judge the abnormality of differential CT circuit, multi-phase CT circuit
failure, multi-side CT circuit failure and short-circuit condition can be detected.
3.2.3.1 Overview
Current differential protection includes three operation elements: biased differential element,
unrestrained differential element and DPFC current differential element. When the differential
current is larger than the corresponding current threshold and no larger harmonic is detected,
current differential protection will operate, and it will drop off if the fault current disappears.
Sensitive biased differential element is variable slope differential element with initial restraint slope.
Conventional biased differential element is differential element with two broken lines. Unrestrained
differential element is used to cut off the serious fault quickly and there is no any blocking element
for it. Main transformer DPFC differential element adopts the current change to calculate, it is very
sensitive to slight fault under heavy loading condition. The three differential elements coordinate
with each other, so quick and high sensitive differential protection can be realized.
Generally, the magnitudes of secondary current of each side of transformer are different due to the
difference of voltage level and CT ratio. The current value difference between each side shall be
eliminated before calculation for current differential protection by amplitude compensation .
The nameplate parameters of the transformer (includes the rated apparent power and the rated
voltage of each side) and the primary and secondary data of CT of each side of the transformer
should be input to the device. The device will calculate the rated current of each side and the
differential adjust coefficient automatically according to the parameters.
Date: 2015-07-29
3 Operation Theory
Sn
I 1bBrm Equation 3.2-1
3 U 1 nBrm
Where:
I 1bBrm
I 2 bBrm Equation 3.2-2
CT Brm
Where:
k B a se 1
I 2 b B a se
k B rm
I 2 b B rm Equation 3.2-3
( I 2 b B a se / I 2 n B a se )
32
( I 2 b B rm / I 2 n B rm )
Where:
Date: 2015-07-29
3 Operation Theory
Via the setting [Y.87T.Opt_BaseSide], the referenced side for transformer current differential
protection can be selected, main transformer LV side (step-down transformer HV side) is the
default referenced side. If Equation 3.2-3 is not met, the setting error alarm signals
[Y.87T.Fail_Settings] will be issued and displayed on LCD and the protective device will be
blocked.
For the connection mode of transformer each side winding is different, different vector group will
be generated, the vector group will lead the phase shift of secondary currents of each side, which
should be adjusted via the phase compensation of the software.
2) The secondary current channel of CT will be connected to the protection device directly.
Phase compensation is carried out from each side to the referenced side. The referenced side is 0
or 12 o’clock. Other sides are n o’clock (n=0~11) relative to the referenced side. If the referenced
side is △ connection, then it does not need to be compensated, other sides need to shift for n
o’clock. If the referenced side is Y connection, then the referenced side is 1 o’clock to eliminate the
effects of zero-sequence current, other sides need to shift for n+1 o’clock.
For example:
The vector group of a transformer is Y0/Δ11, the setting [Tr_HVS.WdgConn] should be set as
“Wye”, the setting [Tr_LVS.WdgConn] should be set as “Delta”, and the setting
[Tr_LVS.Clk_WRT_HVS] should be set as “11”.
1) If LV side is set as the referenced side, it is 1 o'clock for HV side relative to LV side, so the
phase shift matrix corresponds to 1 o’clock is adopted to compensate HV side current. The LV
side is △ connection, so it does not need to be compensated.
2) If HV side is set as the referenced side, the HV side is Y connection, so the phase shift matrix
corresponds to 1 o’clock is adopted to compensate HV side current. It is 11 o'clock for LV side
relative to HV side, so the phase shift matrix corresponds to 12 (or 0, 11+1=12) o’clock is
adopted to compensate LV side current.
Date: 2015-07-29
3 Operation Theory
1 0 0
0
0 1 0
(No phase shit)
0 0 1
1 1 0
1 1
0 1 1
(Shift 30°leading)
3
1 0 1
0 1 0
2
0 0 1
(shift 60°leading)
1 0 0
0 1 1
3 1
1 0 1
(Shit 90°leading)
3
1 1 0
0 0 1
4
1 0 0
(Shit 120°leading)
0 1 0
1 0 1
5 1
1 1 0
(Shift 150°leading)
3
0 1 1
1 0 0
6
0 1 0
(Shift 180°leading)
0 0 1
1 1 0
7 1
0 1 1
(Shift 150°lagging) 3
1 0 1
0 1 0
8
0 0 1
(Shift 120°lagging)
1 0 0
0 1 1
S9 1
1 0 1
(Shift 90°lagging)
3
1 1 0
Date: 2015-07-29
3 Operation Theory
0 0 1
10
1 0 0
(Shift 60°lagging)
0 1 0
1 0 1
11 1
1 1 0
(Shift 30°lagging)
3
0 1 1
NOTICE!
For Y-y and D-d connection the vector group can ONLY BE even number, (i.e. Y-y4,
D-d8), for Y-d and D-y connection the vector group can ONLY BE odd number, (i.e.
Y-d11, D-y5), if the two conditions can not be met, the setting error alarm signal
[Y.87T.Fail_Settings] will be issued and displayed on LCD and the protective device will
be blocked.
I dA I A 1 I A 2 I A 3 I A 4 I A 5 I A 6
I dB I B 1 I B 2 I B 3 I B 4 I B 5 I B 6 Equation 3.2-5
I dC I C 1 I C 2 I C 3 I C 4 I C 5 I C 6
Where:
I Am , I Bm , I Cm in the equation are the secondary current vectors of side m (m=1, 2, 3, 4, 5, 6).
M 1, M 2 , M 3 , M 4 , M 5 , M 6 are phase shift matrixes of each side of transformer respectively. Its value is
Date: 2015-07-29
3 Operation Theory
decided according to the vector group of transformer and please refers to Section 3.2.3.3 for
details.
I 2 bBr 1 , I 2 bBr 2 , I 2 bBr 3 , I 2 bBr 4 , I 2 bBr 5 , I 2 bBr 6 are rated secondary values of each side of transformer
respectively.
1
I rA I A1 I A 2 I A 3 I A 4 I A 5 I A 6
2
1
I rB I B1 I B 2 I B 3 I B 4 I B 5 I B 6 Equation 3.2-6
2
1
I rC I C 1 I C 2 I C 3 I C 4 I C 5 I C 6
2
Where:
Current compensation process is shown in the flowing figure (takes two-winding transformer as an
example). The symbol “*” represents the polarity of CT. If current flowing into the polarity side of CT,
the current direction is defined as positive direction. In an ideal situation, the differential current
(i.e. I d I _ H I _ L )should be zero during the normal operation of the transformer or an
external fault occurring.
Ip_H Ip_L
* * *
* * *
HV side LV side
I_H I_L
PCS-985TI
Phase shift/zero sequence Phase shift/zero sequence
current elimination (*M1) current elimination (*M2)
I'_H I'_L
In above figure:
I’_H, I’_L are secondary corrected current vectors of HV and LV side respectively.
Date: 2015-07-29
3 Operation Theory
To clarify the principle, in an ideal situation, three important operation conditions are considered.
The direction of I’_H is reverse to that of I’_L, but the amplitude of I’_H is equal to that of I’_L,
i.e. I’_H=–I’_L, |I’_H|=|I’_L|.
Id=|I’_H+I’_L|=|I’_H–I’_H|=0;
Ir=(|I’_H|+|I’_L|)/2=(|I’_H|+|I’_H|)/2=|I’_H|
No differential current (Id=0), restraint current (Ir) is one time of the through-flowing current,
and current differential protection will not operate.
2. Internal short-circuit fault, e.g. the fed currents of two sides are equal:
Id=|I’_H+I’_L|=|I’_H+I’_H|=2|I’_H|;
Ir=(|I’_H|+|I’_L|)/2=(|I’_H|+|I’_H|)/2=|I’_H|
Differential current (Id) is two times of restraint current (Ir) and it corresponds to the total fault
current, current differential protection operates sensitively.
The above results show that Id = 2Ir during an internal fault. I.e. the operation characteristic of
current differential protection for internal fault is a straight line with a slope of 2.
Assuming I’_L=0
Id=|I’_H+I’_L|=|I’_H+0|=|I’_H|;
Ir=(|I’_H|+|I’_L|)/2=(|I’_H|+|0|)/2=|I’_H|/2
Differential current (Id) is two times of restraint current (Ir) and it corresponds to fault current of
single side, current differential protection operates sensitively.
The above results show that Id = 2Ir during an internal fault. I.e. the operation characteristic of
current differential protection for internal fault is a straight line with a slope of 2.
Date: 2015-07-29
3 Operation Theory
m
1
Ir Ii
2 i 1
m
I
d
Ii
i 1
Where:
K b1
is the restraint coefficient of biased differential element.
K b1r
is the restraint coefficient increment of biased differential element.
K bl1 is the initial slope setting of biased differential element, it takes 0.10 generally
[Y.87T.Slope1].
K bl 2 is the maximum slope setting of biased differential element, it takes 0.70 generally
[Y.87T.Slope2].
n is the restraint current multiple when the restraint coefficient reach to the maximum value. This
internal value is set as 6 fixedly.
Conventional biased differential element with higher pickup current and higher restraint coefficient
comparing with sensitive biased differential element is equipped. Its biased restraint characteristic
can make the differential element not operate due to CT transient and steady-state saturation
Date: 2015-07-29
3 Operation Theory
during external fault, and it can operate reliably even the CT is seriously saturated during internal
fault. Operation criterion of conventional biased differential element is:
I d 1 .2 I e
Id Ir Equation 3.2-8
Where:
NOTICE!
The related parameters of conventional biased differential element are set FIXEDLY in
the device. Therefore, the slope and the knee point with constant values do not need to
be set by user.
Where:
If internal slight fault occurs in main transformer, sensitive and conventional biased differential
element may not response sensitively due to the influence of load current. DPFC (Deviation of
Power Frequency Component) biased differential element of main transformer is equipped with
the device for that and it can significantly improve the sensitivity of the protection during small
current internal fault of main transformer. It can be enabled or disabled conveniently by the
corresponding logic setting.
I d 1 . 25 * I dt I dth
I d 0 .6 * I r Ir 2 Ie Equation 3.2-10
I 0 . 75 * I 0 . 3 * I Ir 2Ie
d r e
Date: 2015-07-29
3 Operation Theory
Ir I m
i 1
Id I m
i 1
Where:
I dt is the floating threshold varied with the change of differential current. Take its multiple as
1.25 can ensure the threshold value always a bit higher than the unbalance current. So that
unwanted operation of the device can be avoided during power swing or frequency deviation
condition.
。 。
I r is the DPFC restraint current, the maximum value of three-phase DPFC current of all sides
NOTICE!
If the above criteria are met, CT circuit failure detection (optional), inrush current detection and
overexcitation detection are also adopted to control transformer DPFC differential element.
For the restraint coefficient of transformer DPFC differential element can take a higher value, so it
has high ability to eliminate the effect of transient and steady-state CT saturation during an
external fault. Transformer DPFC differential element improves the sensitivity for detecting
transformer internal slight fault.
Date: 2015-07-29
3 Operation Theory
Id (Ie)
differential Tripping area of
current instantaneous diff.
2
K=
[Y.87T.I_Inst]
ff.
di
.0 ed f
K bia a o
l re
=1 s
na a
tio ing
of iff.
en pp
ea d
ar ed
nv ri
co T
ng a s
2]
pi e bi
pe
p
o
i
Sl
Tr itiv
T.
ns
7
.8
se
[Y
1.2Ie
pe1]
T.Slo
[Y.87
[Y.87T.I_Biased]
restraint current
0 1Ie 1.2Ie nIe Ir (Ie)
△ Id
m
K=
K=0.75
1.2Ie
K=0.6
[Tr.87T.I_Biased]
2Ie
△ Ir
Figure 3.2-3 Operation characteristic curve of DPFC differential element of main transformer
Current differential protection carries out the fault discrimination according to the current of each
phase. If the current criteria are met and no related blocking element(s) operate, differential
Date: 2015-07-29
3 Operation Theory
1) Sensitive biased differential element will send tripping signal monitored by CT saturation,
overexcitation, inrush current and CT circuit failure (optional). It can ensure the sensitivity of
differential protection and avoid the unwanted operation when CT is saturated during an
external fault. Its operation area is the tint shadow area in the figure above.
2) Conventional biased differential element will send tripping signal monitored by inrush current
and CT circuit failure (optional). It eliminates the influence of transient and steady -state
saturations of CT during an external fault and ensures differential protection can operate
reliably even if CT is saturated during an internal fault by means of its biased characteristic. Its
operation area is the deeper shadow area in the figure above.
3) Unrestrained instantaneous differential element will send tripping signal without any blocking
element if differential current of any phase is larger than corresponding current setting.
Unrestrained instantaneous differential element is used to cut off the internal serious fault
quickly. Its operation area is over the above two areas with the deepest dark shadow.
The logic setting [Y.87T.Opt_Inrush_Ident] is provided for users to select the inrush current
detection principle. If the logic setting is set as “Waveform”, discrimination by waveform distortion
is enabled, and if it is set as “Hm2”, discrimination by second harmonics is enabled .
The logic setting [Y.87T.Opt_BlkMode_Inrush] is provided for users to select the inrush current
blocking mode, synthetic blocking mode, cross blocking mode and phase blocking mode can be
selected.
The ratio between second harmonic and fundamental component of three-phase differential
current is used to distinguish inrush current. Its criteria are:
I 2 nd K 2 xb * I 1 st Equation 3.2-11
Where:
[Y.87T.K_Hm2_Inrush]=0.15 is recommended.
Users can select the second harmonic criterion or wave distortion criterion (see following section)
to distinguish inrush current.
Date: 2015-07-29
3 Operation Theory
After the transmission of current transformer, the differential current is basically the fundamental
sinusoidal wave during an internal fault. When the transformer is energized, plentiful harmonics
will appear, the waveform will be distorted, the waveform is interrupted and unsymmetrical.
S K b * S
Equation 3.2-12
S St
Where:
S is the full-cycle integral value of (differential current instantaneous value+ differential current
K b is a fixed coefficient.
S t * I d 0 .1 I e Equation 3.2-13
Where:
is a ratio coefficient.
When inrush current appears, the above waveform distinguish expression is not met, current
differential protection will not mal-operate.
Users can select the inrush current blocking mode by the logic setting
[Y.87T.Opt_BlkMode_Inrush].
If the following criterion is met, the three-phase differential protection will be blocked.
M a x { I a 2 n d , I b 2 n d , I c 2 n d } [ Y .8 7 T . K _ H m 2 _ In r u s h ] M a x ( I a 1 n d , I b 1 n d , I c 1 n d ) Equation 3.2-14
If the following criterion is met, the three-phase differential protection will be blocked.
Date: 2015-07-29
3 Operation Theory
I a 2 n d [ Y .8 7 T . K _ H m 2 _ In r u s h ] I a 1 n d
or
I b 2 n d [ Y .8 7 T . K _ H m 2 _ In r u s h ] I b 1 n d
I a 2 n d [ Y .8 7 T . K _ H m 2 _ In r u s h ] I a 1 n d
or Equation 3.2-15
I c 2 n d [ Y .8 7 T . K _ H m 2 _ In r u s h ] I c 1 n d
I c 2 n d [ Y .8 7 T . K _ H m 2 _ In r u s h ] I c 1 n d
I b 2 n d [ Y .8 7 T . K _ H m 2 _ In r u s h ] I b 1 n d
If one of the following criteria is met, only the corresponding phase differential protection will be
blocked.
I a 2 n d [ Y .8 7 T . K _ H m 2 _ In r u s h ] I a 1 n d
I b 2 n d [ Y .8 7 T . K _ H m 2 _ In r u s h ] I b 1 n d Equation 3.2-16
I c 2 n d [ Y .8 7 T . K _ H m 2 _ In r u s h ] I c 1 n d
The synthetic blocking mode is strongly recommended to be selected in the actual application.
Operating experience indicating that the synthetic blocking mode can guarantee the differential
protection not operate under most inrush current situation, and ensure the differential protection
can operate sensitively when the excitation is no-load energized on to a fault.
When an transformer external fault happens, great through-fault current will flowing through the CT,
if the saturation degree of LV side CT is inconsistent with that of HV side CT, great unbalance
differential current will generate in the differential circuit, which will lead to the mal-operation of
differential protection. So the CT saturation detection function is required for transformer
differential protection.
There is a certain time before the CT falling into saturated state, so the changing characteristic of
differential current and restraint current within the initial time of the fault can be used to judge
whether it is an external fault. For an external fault, the deviation of power frequency component
(DPFC) of restraint current appears before the appearance of DPFC of differential current; for an
internal fault, DPFC of restraint current and differential current appear almost simultaneously. If
external fault is detected, CT saturation blocking criterion is enabled.
I _ 2 nd K sat _ 2 xb I _ 1 st
Equation 3.2-17
I K sat I
_ 3 rd _ 3 xb _ 1 st
Where:
Date: 2015-07-29
3 Operation Theory
If any harmonic of one phase differential current meets the above equation, it will be considered
that it is CT saturation to cause this phase differential current and sensitive biased differential
element will be blocked. The criterion is only enabled when the transformer is in service.
When a transformer is overexcited, the exciting current will increase sharply which may result in
unwanted operation of differential protection. Therefore the overexcitation shall be discriminated to
block differential protection. If overexcitation is detected, then sensitive biased differential element
will be blocked.
I 5 th k 5 xb * I 1 st Equation 3.2-18
Where:
If the transformer differential current of any phase meets the following criteria and corresponding
differential element is enabled, the transformer differential current abnormality alarm
[Y.87T.Alm_Diff] with a time delay of 300ms, this alarm signal will not block the differential element.
The signal will reset if the differential current disappears with a time delay of 10s.
I d [Y . 8 7 T . I _ A l m ]
Equation 3.2-19
Id k * Ir
Date: 2015-07-29
3 Operation Theory
Criteria
If any one of following four conditions is satisfied after the fault detector of biased differential
current picks up, it will be determined as fault and differential protection is released, otherwise it
will be determined that the fault detector of biased differential current picks up due to differential
CT circuit failure or short-circuit.
Any phase current of any side increases after the fault detector picks up.
The maximum phase current is larger than 1.2Ie after the fault detector picks up.
Among all the current channels, any three phases of the current decrease after fault
detector picks up.
If none of above four conditions is satisfied within 40ms after the fault detector of biased
differential current picks up, it will be determined as differential CT circuit failure and CT circuit
failure alarm will be issued. Then if the logic setting [Y.87T.En_CTS_Blk] is set as “1”, sensitive
and conventional biased differential element will be blocked, if the logic setting
[Y.87T.En_CTS_Blk] is set as “0”, sensitive and conventional biased differential element will not be
blocked. Transformer unrestrained instantaneous differential element will not be blocked during
CT circuit failure.
Before the transformer is connected to the power grid, CT circuit failure alarming and blocking
function will quit automatically.
The above conditions contain the voltage criteria and current criteria, which realizes the high
accuracy and sensitivity of the CT circuit failure detection.
The CT circuit failure alarm is latched once issued, it can be reset only after the failure is cleared
and the device is reset (i.e. the binary input [BI_RstTarg] is energized).
No matter whether the abnormality alarm signal makes the differential protection picks up, there
must be some problems in the differential circuit. For example, when the differential circuit fails,
the differential protection will not pick up for light-loaded condition, but the differential current
abnormality alarm signal will be issued. If the abnormality is treated in time, the mal-operation of
differential protection due to increase of load or external fau lt can be avoided (if the logic setting
[Y.87T.En_CTS_Blk] is set as “0”).
Once the differential CT circuit failure alarm is issued, the CT circuit should be check carefully, only
if the fault is cleared, the reset operation can be conducted.
3.2.4 Logic
For transformer current differential protection, if following three conditions are met, the protection
Date: 2015-07-29
3 Operation Theory
will be enabled.
(2) The protection function enabling inputs [Y.87T.En1], [Y.87T.En2] are “1”
If transformer differential protection is disabled, all the related output signals will be reset. If no
external input is configured to [Y.87T.En1] ([Y.87T.En2]), the default initial value of [Y.87T.En1]
([Y.87T.En2]) is “1”; if no external input is configured to [Y.87T.Blk], the default initial value of
[Y.87T.Blk] is “0”.
En [Y.87T.En_Biased] & ≥1
SIG Idmax>[Y.87T.I_Biased]
En [Tr.87T.En_DPFC] &
SIG ΔId>1.25ΔIdt+Idth
Where:
Date: 2015-07-29
3 Operation Theory
EN [Y.87T.En_Inst]
SIG [Y.87T.En1] &
&
SIG [Y.87T.En2]
[Y.87T.Op_Inst]
SIG [Y.87T.Blk]
SIG Idmax>[Y.87T.I_Inst]
0ms 500ms
SIG Y.87T.FD_Inst
EN [Y.87T.En_Biased]
SIG [Y.87T.En1] &
SIG &
[Y.87T.En2]
SIG [Y.87T.Blk]
SIG Flg_Inrush_ConvBiasDiff
SET [Y.87T.En_CTS_Blk] ≥1
[Y.87T.Op_Biased]
SIG Y.87T.FD_Biased 0ms 500ms
EN [Y.87T.En_Biased]
SIG [Y.87T.En1] &
SIG [Y.87T.En2]
SIG [Y.87T.Blk]
&
SIG Flg_SensBiasDiff
SIG Flg_CTSaturation
SET [Y.87T.En_CTS_Blk]
SET [Y.87T.En_OvExc_Blk]
0ms 500ms
SIG Y.87T.FD_Biased
Where:
Flg_ConvBiasDiff is the internal flag indicating that the operation criteria of conventional biased
differential element are satisfied.
Flg_SensBiasDiff is the internal flag indicating that operation criteria of sensitive biased differential
element are satisfied.
Flg_CTS is the internal flag indicating that differential CT circuit failure is detected.
Flg_Inrush_ConvBiasDiff is the internal flag indicating that inrush current is detected for
conventional biased differential element.
Flg_Inrush_SensBiasDiff is the internal flag indicating inrush current is detected for sensitive
Date: 2015-07-29
3 Operation Theory
Y.87T.FD_Inst is the signal indicating that the fault detector of unrestrained instantaneous
differential element picks up (the fault detector of fault detector DSP module).
Y.87T.FD_Biased is the signal indicating that the fault detector of biased differential element picks
up (the fault detector of fault detector DSP module).
EN [Tr.87T.En_DPFC]
SIG [Tr.87T.En1] &
SIG [Tr.87T.En2]
SIG [Tr.87T.Blk]
&
SIG Flg_DPFC_Diff [Tr.87T.Op_DPFC]
SET [Tr.87T.En_CTS_Blk]
SET [Tr.87T.En_OvExc_Blk
Figure 3.2-6 Logic diagram of DPFC current differential element of main transformer
Where:
Flg_DPFC_Diff is the internal flag indicating that the operation criteria of DPFC differential element
are satisfied.
Flg_Inrush_DPFC is the internal flag indicating inrush current is detected for DPFC differential
element.
Flg_CTS is the internal flag indicating that differential CT circuit failure is detected.
Tr.87T.FD_DPFC is the signal indicating that the fault detector of DPFC differential element picks
up (the fault detector of fault detector DSP module).
Date: 2015-07-29
3 Operation Theory
87T
Y.87T.I3P1 Y.87T.St
Y.87T.I3P2 Y.87T.Op_Biased
Y.87T.I3P3 Y.87T.Op_Inst
Y.87T.I3P4 Tr.87T.Op_DPFC
Y.87T.I3P5 Y.87T.Alm_CTS
Y.87T.I3P6
Y.87T.Alm_Diff
Y.87T.En1
Y.87T.En2
Y.87T.Blk
Above input and output signals can be used for programmable logic, and following output signals
are only for LCD display and waveform recording function of the device.
Table 3.2-4 Output signals of transformer current differential protection (event recorder)
Tripping reports
Date: 2015-07-29
3 Operation Theory
Start signals
Alarm signals
Waveform recording
Tr.87T.Ida
Three-phase differential current amplitude of main
1 Tr.87T.Idb pu
transformer.
Tr.87T.Idc
Tr.87T.Ira
Three-phase restraint current amplitude of main
2 Tr.87T.Irb pu
transformer.
Tr.87T.Irc
Tr.87T.Ia_Cr_Brm
Three-phase corrected current of each side that used for
3 Tr.87T.Ib_Cr_Brm pu
main transformer differential protection (m=1~6).
Tr.87T.Ic_Cr_Brm
Access path:
Main menu -> Measurements -> Measurements1-> Tr Values-> Tr Diff Values
Main menu -> Measurements -> Measurements2-> Tr Values-> Tr Diff Values
Access path:
Main menu -> Measurements -> Measurements2-> Phase Angle-> Tr PhaseAngle Values
Date: 2015-07-29
3 Operation Theory
Access path:
Main menu -> Measurements -> Measurements2-> Cal Param Display-> Sec Rated Curr Values
Access path:
Main menu -> Measurements -> Measurements2-> Cal Param Display-> Diff Corr Coef Values
Y.87T.Ida
7 Y.87T.Idb Three-phase differential current amplitude of transformer. pu
Y.87T.Idc
Y.87T.Ira
9 Y.87T.Irb Three-phase restraint current amplitude of transformer. pu
Y.87T.Irc
Y.87T.Ia_Th_Biased_L
Three-phase current threshold of transformer sensitive
10 Y.87T.Ib_Th_Biased_L pu
biased differential current protection.
Y.87T.Ic_Th_Biased_L
Y.87T.Ia_Th_Biased_H
Three-phase current threshold of transformer conventional
11 Y.87T.Ib_Th_Biased_H pu
biased differential current protection.
Y.87T.Ic_Th_Biased_H
Y.87T.Ida_Hm2
Second harmonic amplitude of three-phase differential
12 Y.87T.Idb_Hm2 pu
current of transformer.
Y.87T.Idc_Hm2
Y.87T.Ida_Hm3
Third harmonic amplitude of three-phase differential current
13 Y.87T.Idb_Hm3 pu
of transformer.
Y.87T.Idc_Hm3
Y.87T.Ida_Hm5
Fifth harmonic amplitude of three-phase differential current
14 Y.87T.Idb_Hm5 pu
of transformer.
Y.87T.Idc_Hm5
Access path:
Main menu -> Measurements -> Measurements2-> Prot Values-> Tr Diff Prot Values
3.2.6 Settings
Date: 2015-07-29
3 Operation Theory
Date: 2015-07-29
3 Operation Theory
NOTICE!
[Y.87T.OutMap]
The tripping logic setting is used to specify which breaker(s) will be tripped when correspond ing
protection element operates. This logic setting comprises 32 binary bits as follows and is
expressed by a hexadecimal number of 8 digits from 0H to 3FFFFFFFH. The tripping logic setting
of the device is specified as follows:
bit 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
TrpOutput15
TrpOutput14
TrpOutput13
TrpOutput12
TrpOutput11
TrpOutput10
TrpOutput09
TrpOutput08
TrpOutput07
TrpOutput06
TrpOutput05
TrpOutput04
TrpOutput03
TrpOutput02
TrpOutput01
Enable trip
Function
matrix
bit 31 30 29 28 27 26 25 24 23 22 21 20 19 18 17 16
TrpOutput016
TrpOutput29
TrpOutput28
TrpOutput27
TrpOutput26
TrpOutput25
TrpOutput24
TrpOutput23
TrpOutput22
TrpOutput21
TrpOutput20
TrpOutput19
TrpOutput18
TrpOutput17
Function
Spare
Spare
“TrpOutput01” just means to drive tripping output channel 1. Set bit0 as “1” means this protection
element can operate to trip breaker(s). The bit corresponding to the breaker to be tripped shall be
set as “1” and other bits shall be “0”. For example, if transformer differential protection is defined to
trip breaker 3 (tripping output channel 3) and breaker 5 (tripping output channel 5), the bit0, bit3
and bit5 shall be set as “1” and other bits shall be set as “0”. Then a hexadecimal number
00000029H is formed as the tripping output logic setting of transformer differential protection.
Please note that tripping output logic settings of the equipment have to be set on basis of
application-specific drawings.
All the tripping logic settings mentioned below should be defined with the same method.
NOTICE!
Date: 2015-07-29
3 Operation Theory
In Section 3.3, the prefix “Y” in settings (such as [Y.64REF.I_Biased]) and input/output
signals (such as [Y.64REF.Op_Biased]) can be Tr_HVS and Tr_MVS. Details of the
prefix are as:
Tr_HVS.64REF Corresponds to restricted earth fault protection of main transformer high voltage side.
Tr_MVS.64REF Corresponds to restricted earth fault protection of main transformer medium voltage side.
3.3.1 Application
Transformer restricted earth fault protection is the main protection for the internal earth fault of
transformer winding. Transformer restricted earth fault protection can operate quickly to clear the
internal earth fault to avoid the transformer from damages or reduce the maintenance cost as low
as possible.
3.3.2 Function
The biased differential element with restraint characteristic is adopted, it consists of sensitive and
conventional biased differential elements as well as independent CT saturation criterion .
3.3.3.1 Overview
Transformer restricted earth fault protection includes one operation element: biased differential
element. When the residual differential current is larger than the corresponding current threshold
and no larger harmonic is detected, restricted earth fault protection will operate, and it will drop off
if the fault current disappears.
Generally, the magnitudes of secondary current of each side of transformer are different due to the
difference of CT ratio. The current value difference between each side shall be adjusted before
calculation for restricted earth fault protection by amplitude compensation. The residual differential
adjust current of each side should be converted to In (In is the secondary rated current, 1A or 5A).
The primary and secondary data of CT of each side of transformer restricted earth fault protection
should be input to the device. The device will calculate the differential adjust coefficient of each
side automatically according to the parameters.
Date: 2015-07-29
3 Operation Theory
k Base 1
I 1 n Brm
k Brm
I 1 n Base Equation 3.3-1
( I 1 n Brm )
16
( I 1 n Base )
Where:
I 1 n Brm , I 1 n Base are primary rated current of calculated side and referenced side of transformer.
Via the setting [Y.64REF.Opt_BaseSide], the referenced side for transformer current differential
protection can be selected, transformer neutral point measured CT is the default referenced side.
If Equation 3.3-1 is not met, the setting error alarm signals [Y.64REF.Fail_Settings] will be issued
and displayed on LCD and the protective device will be blocked.
3 I 0 d 3 I 0 1 K B r1 3 I 0 2 K B r 2 3 I 0 3 K B r 3 3 I 0 4 K B a s e
Equation 3.3-2
3 I 0 d 3 I 0 1 3 I 0 2 3 I 0 3 3 I 0 4
Where:
3 I 0 1 , 3 I 0 2 , 3 I 0 3 in the equation are the residual current vectors of each side, and 3 I 0 4 is the
K B r1 ,K Br 2 ,K B r3 ,K B ase are the adjust coefficients of each side and neutral point side.
3 I ' 0 1 , 3 I ' 0 2 , 3 I ' 0 3 are the corrected residual current vectors of each side, and 3 I 0 4 is the
Date: 2015-07-29
3 Operation Theory
3I 0r m a x 3 I 0 1, 3 I 0 2 , 3 I 0 3 , 3 I 0 4 Equation 3.3-3
Where:
3 I 0 d K b l 3 I 0 r
3 I 0 d I D iff . P ic k u p
Equation 3.3-4
3 I 0 d 3 I 0 1 3 I 0 2 3 I 0 3 3 I 0 4
3 I 0 r m a x 3 I 0 1, 3 I 0 2 , 3 I 0 3 , 3 I 0 4
Where:
3 I ' 0 1 , 3 I ' 0 2 , 3 I ' 0 3 are the corrected residual current vectors of each side, and 3 I 0 4 is the
Conventional biased differential element with higher pickup current and higher restraint coefficient
comparing with sensitive biased differential element is equipped. Its biased restraint characteristic
can make the differential element not operate due to CT transient and steady-state saturation
during external fault, and it can operate reliably even the CT is seriously saturated during internal
fault. Operation criterion of conventional biased differential element is:
3 I 0 d 1 .2 I n
3I0d 3I0r Equation 3.3-5
Where:
Date: 2015-07-29
3 Operation Theory
NOTICE!
The related parameters of conventional biased differential element are set FIXEDLY in
the device. Therefore, the slope and the knee point with constant values do not need to
be set by user.
3I0d
Tripping area of
区
conventional biased diff. f .
作
a o diff
动
动
e
ar ed ]
差
率
.0
=1
ng ias lope
比
K
值
i
p b F.S
ip 低
Tr itive 4RE
ns [Y.6
se
1.2In
[Y.64REF.I_Biased]
0
1.2In 3I0r
Current differential protection carries out the fault discrimination according to the current of each
phase. If the current criteria are met and no related blocking element(s) operate, differential
protection will operate to trip.
1) Sensitive biased differential element will send tripping signal monitored by neutral point CT
saturation discrimination, differential current harmonic discrimination and three-phase
unbalance discrimination. It can ensure the sensitivity of differential protection and avoid the
unwanted operation when CT is saturated during an external fault. Its operation area is the tint
shadow area in the figure above.
2) Conventional biased differential element will send tripping signal monitored b y differential
current second harmonic. It eliminates the influence of CT saturation during an external fault
and ensures differential protection can operate reliably even if CT is saturated during an
internal fault by means of its biased characteristic. Its operation area is the deeper shadow
area in the figure above.
When an transformer external fault happens, great through -fault current will flowing through the
Date: 2015-07-29
3 Operation Theory
neutral point measuring residual CT, generally the CT ratio of the neutral point measuring residual
CT is small and it is easy to be saturated, great unbalance differential current will generate in the
differential circuit, which will lead to the mal-operation of differential protection. So the CT
saturation detection function is required for restricted earth fault protection.
I _ 2 nd K sat _ 2 xb I _ 1 st
Equation 3.3-6
I K sat I
_ 3 rd _ 3 xb _ 1 st
Where:
If neutral point measured residual current meets the above equation, it will be considered that it is
CT saturation to cause residual differential current and sensitive biased differential element will be
blocked. The criterion is only enabled when the transformer is in service and it will also be
controlled by the logic setting [Y.64REF.En_NPCurr].
3 I 0 d _ 2 n d K 2 x b 3 I 0 d _ 1 s t
Equation 3.3-7
3 I 0 d _ 3 r d K 3 x b 3 I 0 d _ 1 s t
Where:
Date: 2015-07-29
3 Operation Theory
If residual differential current meets the above equation, it will be considered that it is CT
saturation to cause residual differential current and sensitive biased differential element will be
blocked. The criterion is only enabled when the transformer is in service.
Under some conditions such as a maximum three-phase short-circuit fault happens or inrush
current and etc., the wrong differential circuit residual current caused by CT transient state
characteristic difference and CT saturation etc. will affect the restricted earth fault protection, so
the device adopts the blocking criterion using positive-sequence current, i.e. when the residual
current of each side of restricted earth fault protection is greater than 0 times of positive
sequence current of corresponding side, it is identified that residual current is caused by a fault
and restricted earth fault protection will be released.
3 I 0 0 I1 Equation 3.3-8
Where:
0 is a proportional constant.
Once the neutral point measured residual current is larger than the threshold value, it is identified
that an earth fault happens, then positive-sequence current blocking criterion of each side will be
enabled fixedly.
If the differential current meets the following criteria and corresponding differential element is
enabled, the differential current abnormality alarm [Y.64REF.Alm_Diff] will be issued with a time
delay of 300ms, this alarm signal will not block the differential element. The signal will reset if the
differential current disappears with a time delay of 10s.
In order to consider both of sensitivity and reliability, percentage restraint differential current alarm
criteria is adopted:
3 I 0 d [ Y .6 4 R E F . I _ A lm ]
Equation 3.3-9
3I0d k * 3I0r
Date: 2015-07-29
3 Operation Theory
No matter whether the abnormality alarm signal makes the restricted earth fault protection picks
up, there must be some problems in the differential circuit or the settings are wrong. For example,
when the differential circuit fails, the restricted earth fault protection will not pick up for light-loaded
condition, but the differential current abnormality alarm signal will be issued. If the abnormality is
treated in time, the mal-operation of differential protection due to increase of load or external fault
can be avoided.
3.3.4 Logic
For restricted earth fault protection, if following three conditions are met, the protection will be
enabled.
(2) The protection function enabling inputs [Y.64REF.En1], [Y.64REF.En2] are “1”.
If restricted earth fault protection is disabled, all the related output signals will be reset. If no
external input is configured to [Y.64REF.En1] ([Y.64REF.En2]), the default initial value of
[Y.64REF.En1] ([Y.64REF.En2]) is “1”; if no external input is configured to [Y.64REF.Blk], the
default initial value of [Y.64REF.Blk] is “0”.
Date: 2015-07-29
3 Operation Theory
EN [Y.64REF.En_Biased]
SIG [Y.64REF.En1] &
SIG &
[Y.64REF.En2]
SIG [Y.64REF.Blk]
&
SIG Flg_ConvBiasedDiff
SIG Flg_2nd_Harm
≥1
EN [Y.64REF.En_Biased]
SIG [Y.64REF.En1] &
SIG [Y.64REF.En2]
SIG [Y.64REF.Blk]
&
SIG Flg_SensBiasedDiff
SIG Flg_2nd_Harm
SIG Flg_Blk_PosSeq
SET [Y.64REF.En_NPCurr]
0ms 500ms
SIG FD_BiasedDiff
En [Y.64REF.En_Biased] &
SIG 3I0d>[Y.64REF.I_Biased]
Where:
Flg_ConvBiasedDiff is the internal flag indicating that operation criteria of conventional biased
differential element are met.
Flg_SensBiasedDiff is the internal flag indicating that operation criteria of sensitive biased
differential element are met.
Flg_2nd_Harm is the internal flag indicating that the second harmonic current blocking condition is
met.
Flg_3rd_Harm is the internal flag indicating that the third harmonic current blocking condition is
met.
FD_BiasedDiff is the signal indicating that the fault detector of restricted earth fault protection
picks up.
Flg_CTSaturation_Neu is the internal flag indicating that the neutral point CT is saturated.
Date: 2015-07-29
3 Operation Theory
64REF
Y.64REF.I3P1 Y.64REF.St
Y.64REF.I3P2 Y.64REF.Op_Biased
Y.64REF.I3P3 Y.64REF.Alm_Diff
Y.64REF.I1P
Y.64REF.En1
Y.64REF.En2
Y.64REF.Blk
Above input and output signals can be used for programmable logic, and f ollowing output signals
are only for LCD display and waveform recording function of the device.
Table 3.3-3 Output signals of restricted earth fault protection (event recorder)
Tripping reports
Start signals
Alarm signals
Waveform recording
Date: 2015-07-29
3 Operation Theory
recording.
Access path:
Main menu -> Measurements -> Measurements1-> Tr Values-> Tr REF Values
Main menu -> Measurements -> Measurements2-> Tr Values-> Tr REF Values
Access path:
Main menu -> Measurements -> Measurements2-> Phase Angle-> Tr PhaseAngle Values
Access path:
Main menu -> Measurements -> Measurements2-> Cal Param Display-> Diff Corr Coef Values
Date: 2015-07-29
3 Operation Theory
Access path:
Main menu -> Measurements -> Measurements2-> Prot Status-> Tr REF Prot Values
3.3.6 Settings
Date: 2015-07-29
3 Operation Theory
Access path:
Settings-> Prot Settings -> TrHVS REF Settings
Settings-> Prot Settings -> TrMVS REF Settings
NOTICE!
In Section 3.4, the prefix “Y” in settings (such as [Y.50/51Q1.I2_Set]) and input/output
signals (such as [Y.50/51Q1.Op]) can be Tr_HVS and Tr_MVS. Details of the prefix are
as:
3.4.1 Application
Negative-sequence overcurrent protection is applied as the backup protection for ge nerator. When
an unsymmetrical short-circuit fault happens or the three-phase loads are unbalance,
negative-sequence current will be generated. Negative-sequence current protection is mainly
used to detect the unbalanced load of three-phase induction motor (generator or electric motor),
negative-sequence current of stator winding will generate a magnetic field rotating in reverse
direction, the frequency of the magnetic field is twice relative to the frequency of the rotor. The
double-frequency magnetic field will generate eddy current on the surface of the rotor, which will
lead to the local over-heating of the end of the rotor, damping stripe and slot-wedge.
The negative-sequence overcurrent protection can also be applied to detect the single-phase and
two-phase fault when the fault current is low than the load current, the negative-sequence
overcurrent has higher sensitivity relative to phase overcurrent. Besides, the negative-sequence
overcurrent protection can also be applied to detect the open, fault or polarity error of the CT
circuit.
3.4.2 Function
Date: 2015-07-29
3 Operation Theory
Where:
If negative-sequence current is greater than the negative-sequence current setting of the enabled
stage of negative-sequence overcurrent protection, the stage of protection will operate after a time
delay. Each stage of negative-sequence overcurrent protection will drop off instantaneously after
fault current disappears.
K
t(I) C TP Equation 3.4-2
I2
( ) 1
I
set
Where:
,
K ,C are inverse-time constants of inverse-time curve.
The user can select the operating characteristic from various inverse-time characteristic curves by
the setting [Y.50/51Q2.Opt_Curve], and parameters of available characteristics for selection are
shown in the following table.
Date: 2015-07-29
3 Operation Theory
0 Definite time
13 Programmable user-defined
If all available curves do not comply with user application, user can configure
[Y.50/51Q2.Opt_Curve] as “13” to customize the inverse-time curve characteristic (by configuring
the three inverse-time curve constants K , and C ).
In order to improve the sensitivity of negative-sequence overcurrent protection, via the setting
[Y.50/51Qx.En_VCE], voltage controlled element of negative-sequence overcurrent protection can
be enabled or disabled. Please refer to Section 3.6.3.4 for details. Voltage controlled element of
negative-sequence overcurrent protection can be configured through the software PCS-Explorer.
3.4.4 Logic
For stage x of negative-sequence overcurrent protection, if following three conditions are met,
stage x of negative-sequence overcurrent protection is enabled.
(2) The protection function enabling inputs [Y.50/51Qx.En1], [Y.50/51Qx.En2] are “1”
If negative-sequence overcurrent protection is disabled, all the related output signals will be reset.
Date: 2015-07-29
3 Operation Theory
EN [Y.50/51Qx.En]
SIG [Y.50/51Qx.En1] &
SIG [Y.50/51Qx.En2]
SIG [Y.50/51Qx.Blk]
SIG [Y.50/51Qx.I3P]
& &
[Y.50/51Qx.St]
SET [Y.50/51Qx.I2_Set]
SIG Y.50/51Q.VCE.Op ≥1
Timer
t
SET [Y.50/51Qx.En_VCE] [Y.50/51Qx.Op]
t
0ms 500ms
SIG Y.50/51Qx.FD Inverse-time only for
stage 2
Where:
[Y.50/51Q.VCE.Op] is the signal indicating that the voltage controlled element operates.
Y.50/51Qx.FD is the internal signal indicating that stage x of negative -sequence overcurrent
protection picks up (the fault detector of fault detector DSP module).
50/51Q
Y.50/51Qx.I3P Y.50/51Qx.St
Y.50/51Qx.VCE Y.50/51Qx.Op
Y.50/51Qx.En1
Y.50/51Qx.En2
Y.50/51Qx.Blk
Date: 2015-07-29
3 Operation Theory
Above input and output signals can be used for programmable logic, and following output signals
are only for LCD display and waveform recording function of the device.
Tripping reports
Start signals
Waveform recording
Access Path:
Main menu -> Measurements -> Measurements2-> Prot Status->Tr HVS PPF Prot Values
Main menu -> Measurements -> Measurements2-> Prot Status->Tr MVS PPF Prot Values
3.4.6 Settings
Date: 2015-07-29
3 Operation Theory
Date: 2015-07-29
3 Operation Theory
3.5.1 Application
Overexcitation protection is used to check the over-flux phenomenon during operation of the
transformer. Especially for the transformer of generator-transformer unit wiring, the over-flux
phenomenon will occur more easily. Abnormal voltage increase and abnormal frequency decline
will lead to the increase of flux density. When the flux density increase quickly over the rated flux
density, it will cause core saturation and resulting in great eddy current, then it will lead to severe
heating, the insulation of the equipment will be damaged.
The ratio of voltage and frequency is adopted to check overexcitation, for the ratio is
proportional to the flux density (B) of the protected object
RMS of three phase-to-phase voltages is used to calculate the overexcitation multiple, which
is not affected by frequency fluctuation.
One stage definite-time overexcitation protection for tripping and one stage definite-time
overexcitation protection for alarm are equipped (with respective overexcitation multiple
setting and time delay).
n U * / f* Equation 3.5-1
Where:
The reference value for calculating per unit value of voltage is secondary rated voltage of some
side of transformer, and the reference value for calculating per unit value of frequency is rated
frequency. During normal operation, n = 1.
Date: 2015-07-29
3 Operation Theory
voltage is:
[T r_ H V S .U 1 n _ P la te ] [T r_ H V S .U 2 n ] 525 100
6 0 .6 2 V
3 [T r_ H V S .U 1 n ] 3 500
The device will calculate the voltage reference value automatically according to the above settings,
so the primary voltage of the protected equipment, the primary and secondary voltage of the
voltage transformer should be set correctly.
Tripping stage
For Definite-time overexcitation protection tripping stage, the operation equation is:
U *
/ f * >[24.DT.K] Equation 3.5-2
Where:
U *
/ f * is the overexcitation multiples.
Alarm stage
For Definite-time overexcitation protection alarm stage, the operation equation is:
U *
/ f * >[24.K_Alm] Equation 3.5-3
Where:
U *
/ f * is the overexcitation multiple.
Users can set eight groups of overexcitation multiple and tripping time to simulate the inverse-time
operation characteristics curve and it can satisfy the overexcitation requirement of various
transformer. For the overexcitation multiple between two overexcitation multiple settings, the
corresponding tripping time can be calculated via the internal piece-wise linear interpolation
method.
Date: 2015-07-29
3 Operation Theory
U*/f*
K0
K1
K2
K3
K4
K5
K6
K7
t0 t1 t2 t3 t4 t5 t6 t7 t(s)
The main harm of transformer overexcitation is overheat, inverse-time characteristic curve can
roughly simulate the heat accumulation and dissipation process for transformer overexcitation.
Once the transformer overexcitation multiple over the lower limit of inverse-time overexcitation
multiple [24.IDMT.K7], the time will be accumulated. When accumulated time delay is larger than
the tripping time of overexcitation protection, a tripping command will be issued by the device.
Once the transformer overexcitation multiple is less than the lower limit of inverse-time
overexcitation multiple [24.IDMT.K7], the inverse-time dissipation process starts. If the transformer
overexcitation multiple is always less than the lower limit of inverse-time overexcitation multiple,,
the accumulated value will decrease to “0” gradually.
The eight groups of settings of inverse-time characteristic curve must meet following conditions:
K0≥K1 ≥ K2 ≥ K3 ≥ K4 ≥ K5 ≥ K6 ≥ K7
t0 ≤t1 ≤ t2 ≤ t3 ≤ t4 ≤ t5 ≤ t6 ≤ t7
3.5.4 Logic
For each tripping stage of overexcitation protection, if following three conditions are met, the
protection will be enabled.
If overexcitation protection is disabled, all the related output signals will be reset. If no external
input is configured to [24.En1] ([24.En2]), the default initial value of [24.En1] ([24.En2]) is “1”; if no
external input is configured to [24.Blk], the default initial value of [24.Blk] is “0”.
For the alarm stage of overexcitation protection, once the setting [ 24.En] is set as “1”, the alarm
function is enabled.
Date: 2015-07-29
3 Operation Theory
EN [24.En]
SIG [24.En1] &
SIG U*/f*>[24.DT.K]
>=1
≥1
0ms 500ms
SIG 24.DT.FD
[24.St]
EN [24.En]
SIG [24.En1] &
SIG U*/f*>[24.IDMT.K7]
0ms 500ms
SIG 24.IDMT.FD
Where:
U *
/ f * is the overexcitation multiple.
24.DT.FD is the internal signal indicating that the definite-time overexcitation protection picks up
(the fault detector of fault detector DSP module).
24.IDMT.FD is the internal signal indicating that the inverse-time overexcitation protection picks up
(the fault detector of fault detector DSP module).
24
24.U3P 24.St
f 24.DT.Op
24.En1 24.IDMT.Op
24.En2 24.Alm
24.Blk
Date: 2015-07-29
3 Operation Theory
Above input and output signals can be used for programmable logic, and following output signals
are only for LCD display and waveform recording function of the device.
Tripping reports
Start signals
Alarm signals
4 24.Alm The alarm stage of overexcitation protection operates to issue alarm signal
Waveform recording
1 f System frequency. Hz
Access path:
Main menu -> Measurements -> Measurements1-> Tr Values-> Tr Volt Values
Main menu -> Measurements -> Measurements2-> Tr Values-> Tr Volt Values
Date: 2015-07-29
3 Operation Theory
3.5.6 Settings
Date: 2015-07-29
3 Operation Theory
NOTICE!
In Section 3.6, the prefix “Y” in settings (such as [Y.50/51P1.I_Set]) and input/output
signals (such as [Y.50/51P1.Op]) can be Tr_HVS, Tr_MVS, and Tr_LVS. Details of the
prefix are as:
Tr_HVS.50/51P Corresponds to phase overcurrent protection of main transformer high voltage side.
Tr_MVS.50/51P Corresponds to phase overcurrent protection of main transformer medium voltage side.
Tr_LVS.50/51P Corresponds to phase overcurrent protection of main transformer low voltage side.
3.6.1 Application
When a fault occurs in power system, the current increases and phase overcurrent protection
operates to avoid damages to protected equipment. Voltage controlled element can be selected to
improve the sensitivity of phase overcurrent protection and direction element can be selected to
improve the selectivity of the protection. In order to prevent the phase overcurrent protection from
mal-operation when energizing a transformer without load, harmonic blocking element can be
applied to phase overcurrent protection (harmonic blocking element is not available for main
transformer low voltage side phase overcurrent protection).
An external fault will result in transformer overload, it will lead to damage of transformer if the fault
can not be cut off quickly, and in this case phase overcurrent protection can operate to trip
transformer circuit breaker to avoid physical damage. For small-scale transformer, phase
overcurrent protection can protect main transformer from internal fault, for large-scale transformer,
phase overcurrent protection is applied as the backup protection of transformer differential
protection.
Three-stage phase overcurrent protection with independent logic, current and time delay
settings.
Stage 1 and stage 2 are definite-time characteristic, stage 3 can be selected as definite-time
or inverse-time characteristic. The inverse-time characteristic is selectable among IEC and
Date: 2015-07-29
3 Operation Theory
Voltage controlled element can be selected to control each stage of phase overcurrent
protection.
Direction element can be selected to control each stage of phase overcurrent protection with
three options: no direction, forward direction and reverse direction.
Second harmonic blocking element can be enabled or disabled for each stage of phase
overcurrent protection (harmonic blocking element is not available for main transformer low
voltage side phase overcurrent protection).
3.6.3.1 Overview
Phase overcurrent element: each stage is equipped with one independent overcurrent
element.
Voltage controlled element: one voltage controlled element shared by all phase overcurrent
elements.
Direction element: one direction element shared by all phase overcurrent elements.
U3P
Stage 1
[Alm_VTS] Direction Direction signal St
Element
Overcurrent Op
Element
voltage signal
Voltage Stage 2
Control St
Element Overcurrent Op
Element
I3P
Stage 3
Harmonic St
Blocking Overcurrent Op
Harmonic restraint
Element Element
signal
The operation criterion of each stage of main transformer phase overcurrent protection is:
Date: 2015-07-29
3 Operation Theory
Where:
If any phase current is larger than the current setting of any enabled stage of phase overcurrent
protection, voltage controlled element operates (or voltage controlled element is disabled),
direction element operates (or direction element is disabled), and harmonic blocking element is
released (or harmonic blocking element is disabled), the stage of phase overcurrent protection will
operate after a time delay. The stage phase overcurrent protection will drop off instantaneously
after fault current disappears.
Main transformer phase overcurrent protection stage 1 and stage 2 are definite-time characteristic
and each stage can perform instantaneous operation if the corresponding time delay setting is set
as “0”. Stage 3 can be selected as definite-time or inverse-time characteristic, and inverse-time
operating time curve is as follows.
K
t(I) C TP Equation 3.6-2
I
( ) 1
I set
Where:
I set is the base current setting, corresponds to the setting [Y.50/51P3.Ib_Set]. The maximum
operating current of the circuit should be taken into account, it should not pick up for overload.
,
K ,C are inverse-time constants of inverse-time curve.
The user can select the operating characteristic from various inverse-time characteristic curves by
the setting [Y.50/51P3.Opt_Curve], and parameters of available characteristics for selection are
shown in the following table.
Date: 2015-07-29
3 Operation Theory
Table 3.6-1 Inverse-time curve parameters of stage 3 of main transformer phase overcurrent protection
0 Definite time
13 Programmable user-defined
If all available curves do not comply with user application, user can configure
[Y.50/51P3.Opt_Curve] as “13” to customize the inverse-time curve characteristic (by configuring
the three inverse-time curve constants K , and C ).
Main transformer phase overcurrent protection is equipped as the backup protection of main
transformer and adjacent power equipment, and voltage element is usually used to control phase
overcurrent protection to improve sensitivity of the protection. Unsymmetrical fault will result in
unsymmetrical sequence voltages and symmetrical fault will lead to low three phase voltages at
relay location. If voltage element is enabled, phase overcurrent protection can operate if the
sequence voltage is larger than a setting or phase-to-phase voltage is lower than a setting, so
current settings of phase overcurrent protection can be set lower with high sensitivity.
The voltage controlled element picks up if phase-to-phase voltage is lower than its setting or
negative-sequence voltage is larger than its setting.
Criteria:
Date: 2015-07-29
3 Operation Theory
U
< [Y.50/51P.Upp_VCE] or U 2
[Y.50/51P.U2_VCE] Equation 3.2-3
Where:
U 2
is the negative-sequence voltage.
Voltage of any side can be used as the input of voltage controlled element through the software
PCS-Explorer.
Effect of VT Circuit
The logic setting [Y.50/51P.En_VTS_Blk] is used to control the voltage controlled element of phase
overcurrent protection during VT circuit failure. When VT circuit fails, if setting
[Y.50/51P.En_VTS_Blk] is set as “1”, the voltage controlled element will not pick up when VT circuit
fails; if the setting is set as “0”, and voltage controlled element meet the criterion, voltage
controlled element will pick up.
Direction element can be selected to control main transformer phase overcurrent protection to
coordinate with other protections of power grid. If the element is select ed for phase overcurrent
protection, then the protection becomes directional overcurrent protection.
When a fault occurs at forward direction, the angle between polarizing voltage U ref and fault
U ref
k arg Equation 3.6-3
I dir
U ref
k arg 180 Equation 3.6-4
I dir
k
Date: 2015-07-29
3 Operation Theory
the angle polarizing voltage leading fault current, in order to ensure the direction element can
operate reliably, the angle range of the forward direction is:
U
sen sen
ref
90 arg 90 Equation 3.6-5
I dir
If VT and CT are connected as following figure, i.e. positive polarity of CT is at busbar side, points
to the protected object, then the operation zone of forward and reverse direction element are
shown in Figure 3.6-3 (Wherein the hatched portion is the operation zone of forward direction
Reverse Forward
CT
Protected
Object
VT
Direction
Element
Reverse
Uref(U1)
Φsen
Φsen+180°
Idir(Ip)
Forward
Effect of VT Circuit
The logic setting [Y.50/51P.En_VTS_Blk] is used to control the direction element of phase
overcurrent protection during VT circuit failure. When VT circuit fails, if setting
[Y.50/51P.En_VTS_Blk] is set as “1”, the direction element will not pick up when VT circuit fails; if
the setting is set as “0”, and direction element meet the criterion, direction element will pick up.
Date: 2015-07-29
3 Operation Theory
NOTICE!
This element is ONLY available for the main transformer HV side and MV side phase
overcurrent protection; it is not available for main transformer LV side phase
overcurrent protection.
When phase overcurrent protection is used to protect main transformer during main transformer
energization, in order to prevent the mal-operation of phase overcurrent protection that caused by
inrush current, harmonic blocking function can be selected for each stage. Users can select the
harmonic blocking mode (synthetic blocking mode, synthetic blocking mode or phase blocking
mode) by the logic setting [Y.50/51P.Opt_Hm_Blk].
The device adopts the ratio between second harmonic and fundamental component of
three-phase current to realize inrush current blocking criterion, the equation is:
Operation criterion:
I p _ 2 n d [5 0 / 5 1 P . K _ H m 2 ] I p Equation 3.6-6
Where:
Harmonic releasing
If any phase current is larger than the harmonic releasing current setting [Y.50/51P.I_Rls_HmBlk],
the harmonic blocking element will be released immediately even though the harmonic blocking
condition is met.
If the following criterion is met, the three-phase differential protection will be blocked.
M a x { I a 2 n d , I b 2 n d , I c 2 n d } [ Y .5 0 / 5 1 P . K _ H m 2 ] M a x ( I a 1 n d , I b 1 n d , I c 1 n d ) Equation 3.6-7
If the following criterion is met, the three-phase differential protection will be blocked.
Date: 2015-07-29
3 Operation Theory
I a 2 n d [Y . 5 0 / 5 1 P . K _ H m 2 ] I a 1 n d
or
I b 2 n d [Y . 5 0 / 5 1 P . K _ H m 2 ] I b 1 n d
I a 2 n d [Y . 5 0 / 5 1 P . K _ H m 2 ] I a 1 n d
or Equation 3.6-8
I c 2 n d [Y . 5 0 / 5 1 P . K _ H m 2 ] I c 1 n d
I c 2 n d [Y . 5 0 / 5 1 P . K _ H m 2 ] I c 1 n d
I b 2 n d [Y . 5 0 / 5 1 P . K _ H m 2 ] I b 1 n d
If one of the following criteria is met, only the corresponding phase differential protection will be
blocked.
I a 2 n d [Y . 5 0 / 5 1 P . K _ H m 2 ] I a 1 n d
I b 2 n d [Y . 5 0 / 5 1 P . K _ H m 2 ] I b 1 n d Equation 3.6-9
I c 2 n d [Y . 5 0 / 5 1 P . K _ H m 2 ] I c 1 n d
3.6.4 Logic
Logic diagram of main transformer phase overcurrent is shown in the following figure, including
phase overcurrent element, voltage controlled element and direction element, harmonic blocking
element and enabling and blocking logic of the protection.
For stage x of phase overcurrent protection, if following three conditions are met, stage x of phase
overcurrent protection is enabled.
(2) The protection function enabling inputs [Y.50/51Px.En1], [Y.50/51Px.En2] are “1”
If main transformer phase overcurrent protection is disabled, all the related output signals will be
reset. If no external input is configured to [Y.50/51Px.En1] ([Y.50/51Px.En2]), the default initial
value of [Y.50/51Px.En1] ([Y.50/51Px.En2]) is “1”; if no external input is configured to
[Y.50/51Px.Blk], the default initial value of [Y.50/51Px.Blk] is “0”.
Date: 2015-07-29
3 Operation Theory
EN [Y.50/51Px.En]
SIG [Y.50/51Px.En1] &
SIG [Y.50/51Px.En2]
SIG [Y.50/51Px.Blk]
SIG [Y.50/51P.I3P]
& &
SET [Y.50/51Px.I_Set] [Y.50/51Px.St]
SIG [Y.50/51P.VCE.Op] ≥1
Timer
SET [Y.50/51Px.En_VCE] t
[Y.50/51Px.Op]
t
SIG [Y.50/51P.DIR.Op] ≥1
Inverse-time only for
SET [Y.50/51Px.En_Dir] stage 3
SIG [Y.50/51P.HMB.Op] ≥1
SET [Y.50/51Px.En_Hm2_Blk]
0ms 500ms
SIG Y.50/51Px.FD
Figure 3.6-4 Logic diagram of main transformer phase overcurrent protection (x=1,2,3)
Where:
[Y.50/51P.VCE.Op] is the signal indicating that the voltage controlled element operates.
[Y.50/51P.HMB.Op] is the signal indicating that the harmonic blocking element is released.
Y.50/51Px.FD is the internal signal indicating that stage x of main transformer phase overcurrent
protection picks up (the fault detector of fault detector DSP module).
EN [Y.50/51P.En_VTS_Blk]
Figure 3.6-5 Logic diagram of phase-to-phase VCE of main transformer phase overcurrent protection
Date: 2015-07-29
3 Operation Theory
EN [Y.50/51P.En_VTS_Blk]
Figure 3.6-6 Logic diagram of negative-sequence VCE of main transformer phase overcurrent protection
Where:
EN [Y.50/51P.En] &
Fwd/Rev
SET [Y.50/51P.Opt_Dir]
EN [Y.50/51P.En_VTS_Blk]
Figure 3.6-7 Logic diagram of direction element of main transformer phase overcurrent protection
Where:
[Y.50/51P.DIR.Op] is the internal signal indicating that the direction element operates.
Date: 2015-07-29
3 Operation Theory
SIG Ip>0.04In ≥1
&
SIG Ip>[Y.50/51P.I_Rls_HmBlk] [Y.50/51P.HMB.Op]
SIG [Y.50/51P.Blk]
[Y.50/51P.HMB.Op] is the signal indicating that the harmonic blocking element is released.
50/51P
Y.50/51Px.I3P Y.50/51Px.St
Y.50/51Px.U3P Y.50/51Px.Op
Y.50/51Px.En1
Y.50/51Px.En2
Y.50/51Px.Blk
Y.50/51Px.VCE
Figure 3.6-9 Function block diagram of main transformer phase overcurrent protection
Date: 2015-07-29
3 Operation Theory
Above input and output signals can be used for programmable logic, and following output signals
are only for LCD display and waveform recording function of the device.
Table 3.6-4 Output signals of main transformer phase overcurrent protection (event recorder)
Tripping reports
Start signals
Waveform recording
Table 3.6-5 Output signals of main transformer phase overcurrent protection (measurements)
Date: 2015-07-29
3 Operation Theory
Access Path:
Main menu -> Measurements -> Measurements2-> Prot Values-> Tr HVS PPF Prot Values
Main menu -> Measurements -> Measurements2-> Prot Values-> Tr MVS PPF Prot Values
Main menu -> Measurements -> Measurements2-> Prot Values-> Tr LVS Bak Prot Values
3.6.6 Settings
Date: 2015-07-29
3 Operation Theory
Date: 2015-07-29
3 Operation Theory
NOTICE!
In Section 3.7, the prefix “Y” in settings (such as [Y.51PAlm1.I_Set]) and input/output
signals (such as [Y.51PAlm1.Alm]) can be Tr_HVS and Tr_MVS. Details of the prefix
are as:
3.7.1 Application
During overload operation of a power transformer, great current results in greater heat will lead to
temperature increase of transformer, if the temperature reaches a too high value, the equipment
might be damaged, the insulation of the transformer will be forced ageing.
The phase overcurrent alarm elements are equipped to monitor the load of transformer winding,
and when load current exceeds the transformer limit load current, phase overcurrent alarm
Date: 2015-07-29
3 Operation Theory
Besides, during overload of transformer, it is needed to initiate cooling system (such as cooling fan)
and blocking on-load-tap-changing (OLTC) function of the tap of transformer. Therefore phase
overcurrent alarm elements can also be applied to initiate cooling system and blocking OLTC
function.
3.7.2 Function
Phase overcurrent alarm elements has following functions:
Three stages of definite-time phase overcurrent alarm elements with independent logic,
Drop off coefficient of each stage of phase overcurrent alarm element is settable.
Operation criterion:
Where:
I p is phase current.
[Y.51PAlmx.I_Set] is the current setting of stage x (x=1~3) of phase overcurrent alarm element.
If any phase current is greater than the setting of any enabled stage of phase overcurrent alarm
element, the stage of phase overcurrent alarm element will operate after a settable time delay and
the stage protection will drop off if the overload current is lower than the drop off current value.
3.7.4 Logic
EN [Y.51PAlmx.En]
SIG [Y.51PAlmx.En1] &
SIG [Y.51PAlmx.En2]
SIG [Y.51PAlmx.Blk] &
[Y.51PAlmx.St]
SIG [Y.51PAlmx.I3P]
[Y.51PAlmx.t_Op] 0ms
SET [Y.51PAlmx.I_Set] [Y.51PAlmx.Alm]
Date: 2015-07-29
3 Operation Theory
51PAlm
Y.51PAlmx.I3P Y.51PAlmx.St
Y.51PAlmx.En1 Y.51PAlmx.Op
Y.51PAlmx.En2
Y.51PAlmx.Blk
Above input and output signals can be used for programmable logic, and following output signals
are only for LCD display and waveform recording function of the device.
Table 3.7-3 Output signals of phase overcurrent alarm elements (event recorder)
Alarm signal
Start signals
Date: 2015-07-29
3 Operation Theory
3.7.6 Settings
x=1, 2 and 3
NOTICE!
In Section 3.8, the prefix “Y” in settings (such as [Y.50/51G1.3I0_Set]) and input/output
signals (such as [Y.50/51G1.Op]) can be Tr_HVS and Tr_MVS. Details of the prefix are
as:
Tr_HVS.50/51G Corresponds to ground overcurrent protection of main transformer high voltage side.
Tr_MVS.50/51G Corresponds to ground overcurrent protection of main transformer medium voltage side.
3.8.1 Application
If earth fault happens to a big-current earthing system, great residual current will generate,
whereas the great residual current is not exist during normal operation of the system, therefore
residual current is adopted for earth fault.
In order to improve the selectivity of ground overcurrent protection in power grid with two or
multiple power sources, directional element can be selected to control ground overcurrent
protection. In order to avoid the effect of transformer inrush current, second harmonic blocking
element can be applied to ground overcurrent protection.
3.8.2 Function
Three-stage ground overcurrent protection with independent logic, current and time delay
settings.
Date: 2015-07-29
3 Operation Theory
Stage 1 and stage 2 are definite-time characteristic, stage 3 can be selected as definite-time
or inverse-time characteristic. The inverse-time characteristic is selectable among IEC and
ANSI standard inverse-time characteristics and a user-defined inverse-time curve.
Residual voltage can be selected to control each stage of ground overcurrent protection.
Direction element can be selected to control each stage of ground overcurrent protection
with three options: no direction, forward direction and reverse direction.
Second harmonic blocking element can be enabled or disabled for each stage of ground
overcurrent protection.
Measured residual current or calculated residual current can be selected for the calculation
of ground overcurrent protection.
3.8.3.1 Overview
Residual overcurrent element: each stage is equipped with one independent residual
overcurrent element.
Where:
Date: 2015-07-29
3 Operation Theory
3 I 0 is measured residual current or calculated residual current, which is selected by user through
If residual current is larger than the current setting of any enabled stage of ground overcurrent
protection, residual voltage controlled element operates (or voltage controlled element is disabled),
direction element operates (or direction element is disabled), and harmonic blocking element is
released (or harmonic blocking element is disabled), the stage of ground overcurrent protection
will operate after a time delay. The stage of ground overcurrent protection will drop off
instantaneously after fault current disappears.
Main transformer ground overcurrent protection stage 1 and stage 2 are definite-time
characteristic and each stage can perform instantaneous operation if the corresponding time delay
setting is set as “0”. Stage 3 can be selected as definite-time or inverse-time characteristic, and
inverse-time operating time curve is as follows.
K
t(I) C TP Equation 3.8-2
3I0
( ) 1
I
set
Where:
The user can select the operating characteristic from various inverse-time characteristic curves by
the setting [Y.50/51G3.Opt_Curve], and parameters of available characteristics for selection are
shown in the following table.
Table 3.8-1 Inverse-time curve parameters of stage 3 of main transformer ground overcurrent protection
0 Definite time
Date: 2015-07-29
3 Operation Theory
13 Programmable user-defined
If all available curves do not comply with user application, user can configure
[Y.50/51G3.Opt_Curve] as “13” to customize the inverse-time curve characteristic (by configuring
the three inverse-time curve constants K , and C ).
Residual voltage controlled element is applied to ensure the reliability of the ground overcurrent
protection. Users can enable the element by setting [Y.50/51Gx.En_VCE]. If the setting is set as
“1”, the start signal or operation signal of residual overvoltage protection can be configured to
control ground overcurrent protection.
The calculated residual voltage (3U0) is adopted as the polarizing quantity (i.e. polarizing voltage)
of residual directional element. When the measured residual current (IN) is selected for the
calculation of ground overcurrent, the measured residual current is the operating quantity (i.e. fault
current). When the calculated residual current (3I0) is selected for the calculation of ground
overcurrent, the calculated residual current is the operating quantity.
When a fault occurs at forward direction, the angle polarizing voltage U ref leading fault current
I dir is:
U ref
k arg Equation 3.8-3
I dir
Date: 2015-07-29
3 Operation Theory
U ref
k arg 180 Equation 3.8-4
I dir
k
Relay characteristic angle sen (i.e. the setting [Y.50/51G.RCA]), in order to make sure the
residual direction element can operate reliably, the operating phase range for forward direction is:
U
sen sen
ref
90 arg 90 Equation 3.8-5
I dir
If VT and CT are connected as following figure, i.e. positive polarity of CT is at busbar side, points
to the protected object, then the operation zone of forward and reverse direction element are
shown in Figure 3.8-3 (Wherein the hatched portion is the operation zone of forward direction
element). Symbol “*” represents the polarity of current transformer.
VT
Dir
Reverse
Direction
CT Element
Forward
Protected
Object
Forward
Idir(3I0 or IN)
Uref(3U0)
Φsen Φsen-180°
Reverse
Effect of VT Circuit
The logic setting [Y.50/51G.En_VTS_Blk] is used to control the direction element of ground
overcurrent protection during VT circuit failure. When VT circuit fails, if the setting
[Y.50/51G.En_VTS_Blk] is set as “1”, the direction element will not pick up when VT circuit fails; if
the setting is set as “0”, and direction element meet the criterion, direction element will pick up.
Date: 2015-07-29
3 Operation Theory
In order to prevent the mal-operation of ground overcurrent protection that caused by inrush
current, harmonic blocking function can be selected for each stage. If the setting
[Y.50/51Gx.En_Hm2_Blk] is set as “1” and the ratio between second harmonic and fundamental
component of residual current is larger than the second harmonic restraint coefficient, the
harmonic blocking element of ground overcurrent protection will operate. Via the setting
[Y.50/51Gx.En_Hm2_Blk], users can select which stage(s) of ground overcurrent protection will be
controlled by harmonic blocking element.
If the fundamental component of residual current is larger than the harmonic releasing residual
current setting [Y.50/51G.3I0_Rls_HmBlk], the harmonic blocking element will be released
immediately even though the harmonic blocking condition is met.
3 I 0 _ 2 n d [ Y .5 0 / 5 1G . K _ H m 2 ] 3 I 0 Equation 3.8-6
Where:
If the fundamental component of residual current is lower than the minimum operating current (the
typical value is 0.1In) of harmonic blocking element, the harmonic blocking element will out of
service.
3.8.4 Logic
Logic diagram of main transformer ground overcurrent is shown in the following figure, including
ground overcurrent element, residual voltage controlled element and direction element, harmonic
blocking element and enabling and blocking logic of the protection.
For stage x of ground overcurrent protection, if following three conditions are met, stage x of
ground overcurrent protection is enabled.
(2) The protection function enabling inputs [Y.50/51Gx.En1], [Y.50/51Gx.En2] are “1”
If main transformer ground overcurrent protection is disabled, all the related output signals will be
reset. If no external input is configured to [Y.50/51Gx.En1] ([Y.50/51Gx.En2]), the default initial
value of [Y.50/51Gx.En1] ([Y.50/51Gx.En2]) is “1”; if no external input is configured to
[Y.50/51Gx.Blk], the default initial value of [Y.50/51Gx.Blk] is “0”.
Date: 2015-07-29
3 Operation Theory
EN [Y.50/51Gx.En]
SIG [Y.50/51Gx.En1] &
SIG [Y.50/51Gx.En2]
SIG [Y.50/51Gx.Blk]
SIG 3I0 or IN
& &
SET [Y.50/51Gx.I_Set] [Y.50/51Gx.St]
SIG [Y.50/51G.VCE.Op] ≥1
Timer
SET [Y.50/51Gx.En_VCE] t
[Y.50/51Gx.Op]
t
SIG [Y.50/51Gx.DIR.Op] ≥1
Inverse-time only for
SET [Y.50/51Gx.En_Dir] stage 3
SIG [Y.50/51Gx.HMB.Op] ≥1
SET [Y.50/51Gx.En_Hm2_Blk]
0ms 500ms
SIG Y.50/51Gx.FD
Figure 3.8-4 Logic diagram of main transformer ground overcurrent protection (x=1,2,3)
Where:
[Y.50/51G.VCE.Op] is the signal indicating that the residual voltage controlled element operates.
3I0 or IN means calculated residual current (3I0) or measured residual current (IN).
[Y.50/51Gx.HMB.Op] is the signal indicating that the harmonic blocking element is released.
Y.50/51Gx.FD is the internal signal indicating that stage x of main transformer ground overcurrent
protection picks up (the fault detector of fault detector DSP module).
EN [Y.50/51Gx.En] &
Fwd/Rev
SET [Y.50/51G.Opt_Dir]
EN [Y.50/51G.En_VTS_Blk]
Figure 3.8-5 Logic diagram of direction element of main transformer ground overcurrent protection
Where:
Date: 2015-07-29
3 Operation Theory
SIG 3I0_1>0.1In ≥1
&
SIG 3I0>[Y.50/51G.3I0_Rls_HmBlk] [Y.50/51Gx.HMB.Op]
SIG [Y.50/51Gx.Blk]
[Y.50/51Gx.HMB.Op] is the signal indicating that the harmonic blocking element of stage x of
ground overcurrent protection is released.
50/51G
Y.50/51Gx.I3P Y.50/51Gx.St
Y.50/51Gx.I1P Y.50/51Gx.Op
Y.50/51Gx.En1
Y.50/51Gx.En2
Y.50/51Gx.Blk
Y.50/51Gx.VCE
Figure 3.8-7 Function block diagram of main transformer ground overcurrent protection
Date: 2015-07-29
3 Operation Theory
Above input and output signals can be used for programmable logic, and following output signals
are only for LCD display and waveform recording function of the device.
Table 3.8-4 Output signals of main transformer ground overcurrent protection (e vent recorder)
Tripping reports
Start signals
Waveform recording
Table 3.8-5 Output signals of main transformer ground overcurrent protection (measurements)
Date: 2015-07-29
3 Operation Theory
Access Path:
Main menu -> Measurements -> Measurements2-> Prot Status->Tr HVS EF Prot Values
Main menu -> Measurements -> Measurements2-> Prot Status->Tr MVS EF Prot Values
3.8.6 Settings
Date: 2015-07-29
3 Operation Theory
Date: 2015-07-29
3 Operation Theory
NOTICE!
In Section 3.9, the prefix “Y” in settings (such as [Y.59P1.Upp_Set]) and input/output
signals (such as [Y.59P1.Op]) can be Tr_HVS and Tr_MVS. Details of the prefix are as:
Tr_HVS.59P Corresponds to phase overvoltage protection of main transformer high voltage side.
Tr_MVS.59P Corresponds to phase overvoltage protection of main transformer medium voltage side.
3.9.1 Application
In the power system, there many causes will lead to overvoltage, such as mal-operation of the
excitation system, fault of voltage automatic adjustment device, load shedding due to full load of
generator, disconnection between generator and the system or isolated operation of the generator.
Overvoltage protection is provided to protect the operating equipment against the risk due to
abnormal rise of voltage.
Date: 2015-07-29
3 Operation Theory
Two-stage phase overvoltage protection for tripping and one-stage phase overvoltage
protection for alarm are available (with respective voltage setting, time delay and logic
setting).
Stage 1 of phase overvoltage protection for tripping and the phase overvoltage protection for
alarm are definite-time overvoltage protection fixedly, stage 2 of phase overvoltage
protection for tripping can be configured as inverse-time overvoltage protection (IDMT) or
definite-time overvoltage protection by the setting [Y.59P2.Opt_Curve] (0: definite-time
characteristic, 1: inverse-time characteristic).
U _ R M S > [Y.59Px.Upp_Set]
Equation 3.9-1
and U _ m in >0.95* [Y.59Px.Upp_Set]
Where:
Stage 1 of phase overvoltage protection for tripping and the phase overvoltage protection for alarm
are definite-time overvoltage protection fixedly.
Stage 2 of phase overvoltage protection for tripping can be configured as inverse-time overvoltage
Date: 2015-07-29
3 Operation Theory
TP
t
U Equation 3.9-2
1
U set
Where:
U set
is inverse-time overvoltage pick-up setting, corresponds to the setting [Y.59P2.Upp_Set].
3.9.4 Logic
For each stage of phase overvoltage protection, if following three conditions are met,
corresponding stage of phase overvoltage protection will be enabled.
(2) The protection function enabling inputs [Y.59Px.En1], [Y.59Px.En2] are “1”
If overvoltage protection is disabled, all the related output signals will be reset. If no external input
is configured to [Y.59Px.En1] ([Y.59Px.En2]), the default initial value of [Y.59Px.En1] ([Y.59Px.En2])
is “1”; if no external input is configured to [Y.59Px.Blk], the default initial value of [Y.59Px.Blk] is “0”.
&
SIG [Y.59PAlm.U3P]
[Y.59PAlm.St]
SET [Y.59PAlm.Upp_Set]
Timer
EN [Y.59Pn.En] Y.59PAlm.t_Op
[Y.59PAlm.Alm]
SIG [Y.59Pn.En1] &
SIG [Y.59Pn.En2]
SIG [Y.59Pn.Blk]
Where:
[Y.59Px.U3P] is the three-phase voltage input for alarm or tripping stage of phase overvoltage
protection.
Y.59Px.FD is the signal to indicate that the fault detector of overvoltage protection picks up (the
fault detector of fault detector DSP module).
Date: 2015-07-29
3 Operation Theory
Y.59Pn.En2 Y.59PAlm.En2
Y.59Pn.Blk Y.59PAlm.Blk
Above input and output signals can be used for programmable logic, and following output signals
are only for LCD display and waveform recording function of the device.
Tripping reports
3 Y.59PAlm.Alm Phase overvoltage protection alarm stage operates to issue alarm signal.
Start signals
Waveform recording
Date: 2015-07-29
3 Operation Theory
Access Path:
Main menu -> Measurements -> Measurements2-> Prot Values-> Tr HVS PPF Prot Values
Main menu -> Measurements -> Measurements2-> Prot Values-> Tr MVS PPF Prot Values
3.9.6 Settings
Date: 2015-07-29
3 Operation Theory
NOTICE!
In Section 3.10, the prefix “Y” in settings (such as [Y.27P1.Upp_Set]) and input/output
signals (such as [Y.27P1.Op]) can be Tr_HVS and Tr_MVS. Details of the prefix are as:
3.10.1 Application
Undervoltage protection is used to detect the voltage decline of the operating motor, so to avoid
the impermissible operating conditions and the possible loss of stability. When the system voltage
decline to a certain degree so that the system stability will be affected, undervoltage protection can
be used as the operation criterion of load shedding.
One-stage phase undervoltage protection for tripping and one-stage phase undervoltage
protection for alarm are available (with respective voltage setting, time delay and logic
setting).
The phase undervoltage protection for alarm is definite-time undervoltage protection fixedly,
the phase undervoltage protection for tripping can be configured as inverse-time undervoltage
protection (IDMT) or definite-time undervoltage protection by the setting [Y.27P.Opt_Curve] (0:
definite-time characteristic, 1: inverse-time characteristic).
Date: 2015-07-29
3 Operation Theory
When phase-to-phase voltage is lower than corresponding voltage setting and the auxiliary
criterion is also met, corresponding stage of undervoltage protection will pick up and operate with
a settable time delay.
Where:
Up p_Set is the phase-to-phase voltage setting of undervoltage protection (tripping stage or alarm
stage).
The phase undervoltage protection for alarm is definite-time undervoltage protection fixedly.
The phase undervoltage protection for tripping can be configured as inverse-time undervoltage
protection (IDMT) or definite-time undervoltage protection by the setting [Y.27P.Opt_Curve] (0:
definite-time characteristic, 1: inverse-time characteristic), the equation of inverse-time
characteristic is:
TP
t
U Equation 3.10-2
1
U set
Where:
U set
is inverse-time undervoltage pick-up setting, corresponds to the setting [Y.27P.Upp_Set].
Undervoltage protection can be blocked by the normally open auxiliary contact of the circuit
breaker [Flg_52a]. If [Flg_52a] is “0”, undervoltage protection is blocked. Besides, the normally
Date: 2015-07-29
3 Operation Theory
open auxiliary contact of the circuit breaker can be replaced by the internal signal that indicating
the generator is connected with the system.
The undervoltage protection is also controlled by the load current, only if any phase current is
larger than 0.04In (the signal [Z.Flg_Onload]=1. Z=Y.27PAlm or Y.27P), the undervoltage
protection can be enabled.
When a fault happens at the secondary circuit of VT, the undervoltage protection tripping stage
can be blocked by a binary input signal (such as VT MCB auxiliary contact and etc.). The output
signal of VT circuit supervision function can also be adopted to block the undervoltage protection.
[Flg_52a], [Z.Flg_Onload] (Z=Y.27PAlm or Y.27P) and the VT abnormal binary input (or signal) can
be configured by the software PCS-Explorer.
3.10.4 Logic
For each stage of phase undervoltage protection, if following three conditions are met,
corresponding stage of phase undervoltage protection will be enabled.
(2) The protection function enabling inputs [Z.En1], [Z.En2] are “1”.
If undervoltage protection is disabled, all the related output signals will be reset. If no external input
is configured to [Z.En1] ([Z.En2]), the default initial value of [Z.En1] ([Z.En2]) is “1”; if no external
input is configured to [Z.Blk], the default initial value of [Z.Blk] is “0”.
EN [Y.27PAlm.En]
SIG [Y.27PAlm.En1] &
SIG [Y.27PAlm.En2]
&
SIG [Y.27PAlm.Blk]
[Y.27PAlm.St]
SET UΦΦ_max<[Y.27PAlm.Upp_Set]
Timer
Y.27PAlm.t_Op
[Y.27PAlm.Alm]
EN [Y.27P.En]
SIG [Y.27P.En1] &
SET UΦΦ_max<[Y.27P.Upp_Set]
Timer
SIG Y.27P.FD 0ms 500ms t
[Y.27P.Op]
t
Where:
Y.27P.FD is the internal signal to indicate that tripping stage of undervoltage protection picks up
(the fault detector of fault detector DSP module).
Date: 2015-07-29
3 Operation Theory
27P 27PAlm
Y.27P.En2 Y.27PAlm.En2
Y.27P.Blk Y.27PAlm.Blk
Flg_52a Flg_52a
Y.27P.Flg_Onload Y.27PAlm.Flg_Onload
Above input and output signals can be used for programmable logic, and following output signals
are only for LCD display and waveform recording function of the device.
Tripping reports
2 Y.27PAlm.Alm Phase undervoltage protection alarm stage operates to issue alarm signal.
Start signals
Waveform recording
Date: 2015-07-29
3 Operation Theory
5 Y.27P.TrigDFR Phase undervoltage protection tripping stage operates to trigger waveform recording.
Access Path:
Main menu -> Measurements -> Measurements2-> Prot Values-> Tr HVS PPF Prot Values
Main menu -> Measurements -> Measurements2-> Prot Values-> Tr MVS PPF Prot Values
3.10.6 Settings
Date: 2015-07-29
3 Operation Theory
NOTICE!
In Section 3.11, the prefix “Y” in settings (such as [Y.59G.3U0_Set]) and input/output
signals (such as [Y.59G.Op]) can be Tr_HVS, Tr_MVS and Tr_LVS. Details of the prefix
are as:
Tr_HVS.59G Corresponds to residual overvoltage protection of main transformer high voltage side.
Tr_MVS.59G Corresponds to residual overvoltage protection of main transformer medium voltage side.
Tr_LVS.59G Corresponds to residual overvoltage protection of main transformer low voltage side.
3.11.1 Application
Residual overvoltage protection is used to detect the earth fault of the system, generally it is used
for ungrounded system, high resistance grounded system or Peterson coil grounded system. For
directly grounded system or small resistance grounded system, generally ground overcurrent
protection is used to detect the earth fault.
3.11.2 Function
Residual overvoltage protection has following functions
One-stage residual overvoltage protection for tripping and one-stage residual overvoltage
protection for alarm are available (with respective residual voltage setting, time delay and
logic setting).
The residual overvoltage protection for alarm is definite-time residual overvoltage protection
fixedly, the residual overvoltage protection for tripping can be configured as inverse-time
residual overvoltage protection (IDMT) or definite-time residual overvoltage protection by the
setting [Y.59G.Opt_Curve] (0: definite-time characteristic, 1: inverse-time characteristic).
The VT broken-delta residual voltage or the calculated residual voltage can be selected for
the calculation of residual overvoltage protection.
For any stage of residual overvoltage protection, the operation equation is:
3U 0
> [3U0_Set] Equation 3.11-1
Date: 2015-07-29
3 Operation Theory
Where:
3U 0
is VT broken-delta residual voltage or calculated residual voltage, which is selected by user
3U0_Set is the residual voltage setting of residual overvoltage protection (tripping stage or alarm
stage).
If residual voltage is greater than the setting of any enabled stage of residual overvoltage
protection, the stage of residual overvoltage protection will operate after a time delay and the
protection will drop off instantaneously after the fault disappears.
The residual overvoltage protection for alarm is definite-time residual overvoltage protection
fixedly.
The residual overvoltage protection for tripping can be configured as inverse-time residual
overvoltage protection (IDMT) or definite-time residual overvoltage protection by the setting
[Y.59G.Opt_Curve] (0: definite-time characteristic, 1: inverse-time characteristic), the equation of
inverse-time characteristic is:
TP
t
U Equation 3.11-2
1
U set
Where:
U set
is inverse-time residual voltage pick-up setting, corresponds to the setting [Y.59G.3U0_Set].
3.11.4 Logic
For each stage of residual overvoltage protection, if following three conditions are met,
corresponding stage of residual overvoltage protection will be enabled.
(2) The protection function enabling inputs [Z.En1], [Z.En2] are “1”.
If residual overvoltage protection is disabled, all the related output signals will be reset. If no
external input is configured to [Z.En1] ([Z.En2]), the default initial value of [Z.En1] ([Z.En2]) is “1”; if
no external input is configured to [Z.Blk], the default initial value of [Z.Blk] is “0”.
Date: 2015-07-29
3 Operation Theory
EN [Y.59GAlm.En]
SIG [Y.59GAlm.En1] &
SIG [Y.59GAlm.En2]
SIG [Y.59GAlm.Blk] &
SIG 3U0 [Y.59GAlm.St]
SET [Y.59GAlm.3U0_Set]
Timer
Y.59GAlm.t_Op
EN [Y.59G.En] [Y.59GAlm.Alm]
SIG [Y.59G.En2]
SIG [Y.59G.Blk]
Where:
3U 0
is VT broken-delta residual voltage or calculated residual voltage.
Y.59G.FD is the internal signal to indicate that tripping stage of residual overvoltage protection
picks up (the fault detector of fault detector DSP module).
59G 59GAlm
Y.59G.En1 Y.59GAlm.En1
Y.59G.En2 Y.59GAlm.En2
Y.59G.Blk Y.59GAlm.Blk
Date: 2015-07-29
3 Operation Theory
Above input and output signals can be used for programmable logic, and following output signals
are only for LCD display and waveform recording function of the de vice.
Tripping reports
2 Y.59GAlm.Alm Residual overvoltage protection alarm stage operates to issue alarm signal.
Start signals
Waveform recording
5 Y.59G.TrigDFR Residual overvoltage protection tripping stage operates to trigger waveform recording.
Access Path:
Main menu -> Measurements -> Measurements2-> Prot Status->Tr HVS EF Prot Values
Main menu -> Measurements -> Measurements2-> Prot Status->Tr MVS EF Prot Values
Main menu -> Measurements -> Measurements2-> Prot Status->Tr LVS Bak Prot Values
3.11.6 Settings
Date: 2015-07-29
3 Operation Theory
3.12.1 Application
When active power surplus happens to the power system or the speed regulating system of
generator is in abnormal operation, the frequency of the power system will rise, so overfrequency
protection can be used to detect the above abnormal over-frequency conditions. If the frequency is
larger than the overfrequency protection setting, overfrequency protection will operate to issue
Date: 2015-07-29
3 Operation Theory
Steam-turbine generator is able to withstand the frequency shifting, but this will leads to the
vibration of the turbine blade which will eventually cause the metal fatigue damage of the blade.
This kind of damage is a process of accumulation and it is irreversible, therefore, when t he
frequency protection is applied for steam-turbine generator, a feature of frequency accumulation is
required.
Four stages of overfrequency protection (with respective frequency setting, time delay and
logic setting) are available. Each stage can be configured to issue alarm signal or trip.
Four stages of overfrequency band accumulate protection are available and each stage has
respective frequency upper limit setting, lower limit frequency setting, accumulated time
setting and logic setting. Each stage can be configured to issue alarm signal or trip.
3.12.3.1 Overview
When the system frequency is larger than the overfrequency setting, the protection picks up, after
a time delay determined by the time delay setting, the overfrequency protection will operate to
issue alarm signal or trip. If the frequency accumulation function is enabled, i.e. the logic setting
[81O.OFx.En_Alm_Accu] or [81O.OFx.En_Trp_Accu] (x=1~4) is set as “1”, the relay will
accumulate the time that the system frequency falling into the corresponding overfrequency band,
if the accumulated time is larger than the corresponding time delay setting, the overfrequency
band accumulate protection will operate to issue alarm signal or trip.
The positive voltage is used to calculate the system frequency, after a filtering process, the
measurement of system frequency will not be affected by the harmonic component.
Where:
f is system frequency.
Date: 2015-07-29
3 Operation Theory
Where:
f is system frequency.
[81O.OFx.f_Set] is the lower limit frequency setting of stage x (x=1~4) of overfrequency band
accumulate protection.
[81U.UFx’.f_Set] is the upper limit frequency setting of stage x (x=1~4) of overfrequency band
accumulate protection.
If x=1~3, x’=x+1.
3.12.4 Logic
For overfrequency protection, when following three conditions are met, the protection is enabled.
(2) The protection function enabling binary inputs [81O.En1] and [81O.En2] are “1”
If overfrequency protection is disabled, all the related output signals will be reset. If no external
input is configured to [81O.En1] ([81O.En2]), the default initial value of [81O.En1] ([81O.En2]) is
“1”; if no external input is configured to [81O.Blk], the default initial value of [81O.Blk] is “0”.
EN [81O.En] &
& [81O.OFx.t_Op] 0s
[81O.OFx.Alm]
EN [81O.OFx.En_Alm] &
& [81O.St]
& [81O.OFx.t_Op] 0s
EN [81O.OFx.En_Trp] &
[81O.OFx.Op]
SIG f > [81O.OFx.f_Set]
0 500ms
SIG 81O.FD
Date: 2015-07-29
3 Operation Theory
EN [81O.En]
SIG [81O.Flg_OnLoad]
&
[81O.OF1.t_Accu] 0s
& [81O.OF1.Alm_Accu]
EN [81O.OF1.En_Alm_Accu] &
SIG [81O.OF2.f_Set]>f>[81O.OF1.f_Set]
& [81O.St]
& [81O.OF1.t_Accu] 0s
EN [81O.OF1.En_Trp_Accu] &
[81O.OF1.Op_Accu]
SIG [81O.OF2.f_Set]>f>[81O.OF1.f_Set]
0 500ms
SIG 81O.FD
The stage 2 and stage 3 of overfrequency band accumulate protection are similar to stage 1 of
overfrequency band accumulate protection.
EN [81O.En]
SIG [81O.Flg_OnLoad]
&
[81O.OF4.t_Accu] 0s
& [81O.OF4.Alm_Accu]
EN [81O.OF4.En_Alm_Accu] &
SIG f>[81O.OF4.f_Set]
& [81O.St]
& [81O.OF4.t_Accu] 0s
EN [81O.OF4.En_Trp_Accu] &
[81O.OF4.Op_Accu]
SIG f>[81O.OF4.f_Set]
0 500ms
SIG 81O.FD
Where:
f is system frequency.
81O.FD is the internal signal to indicate that overfrequency protection picks up (the fault detector
of fault detector DSP module).
Date: 2015-07-29
3 Operation Theory
81O
f 81O.St
81O.En1 81O.OF1.Op
81O.En2 81O.OF2.Op
81O.Blk 81O.OF3.Op
81O.Flg_OnLoad 81O.OF4.Op
Flg_52a 81O.OF1.Op_Accu
81O.OF2.Op_Accu
81O.OF3.Op_Accu
81O.OF4.Op_Accu
81O.OF1.Alm
81O.OF2.Alm
81O.OF3.Alm
81O.OF4.Alm
81O.OF1.Alm_Accu
81O.OF2.Alm_Accu
81O.OF3.Alm_Accu
81O.OF4.Alm_Accu
Date: 2015-07-29
3 Operation Theory
Above input and output signals can be used for programmable logic, and following output signals
are only for LCD display and waveform recording function of the device.
Tripping reports
Start signals
Alarm signals
Waveform recording
Date: 2015-07-29
3 Operation Theory
IO events
Access Path:
Main menu -> Measurements -> Measurements2-> Prot Values-> Freq Prot Values
3.12.6 Settings
Date: 2015-07-29
3 Operation Theory
Date: 2015-07-29
3 Operation Theory
3.13.1 Application
When the power system requires more active power or the speed regulating system of generator
is in abnormal operation, the frequency of the power system will decline, so underfrequency
protection can be used to detect the above abnormal low-frequency conditions. If the frequency is
lower than the underfrequency protection setting, underfrequency protection will operate to issue
alarm signal or trip with a time delay.
Steam-turbine generator is able to withstand the frequency shifting, but this will leads to the
vibration of the turbine blade which will eventually cause the metal fatigue damage of the blade.
This kind of damage is a process of accumulation and it is irreversible, therefore, when the
frequency protection is applied for steam-turbine generator, a feature of frequency accumulation is
Date: 2015-07-29
3 Operation Theory
required.
Four stages of underfrequency protection (with respective frequency setting, time delay and
logic setting) are available. Each stage can be configured to issue alarm signal or trip.
Four stages of underfrequency band accumulate protection are available and each stage has
respective frequency upper limit setting, lower limit frequency setting, accumulated time
setting and logic setting. Each stage can be configured to issue alarm signal or trip.
3.13.3.1 Overview
When the system frequency is smaller than the underfrequency setting, the protection picks up,
after a time delay determined by the time delay setting, the underfrequency protection will operate
to issue alarm signal or trip. If the frequency accumulation function is enabled, i.e. the logic setting
[81U.UFx.En_Alm_Accu] or [81U.UFx.En_Trp_Accu] (x=1~4) is set as “1”, the relay will
accumulate the time that the system frequency falling into the corresponding underfrequency band,
if the accumulated time is larger than the corresponding time delay setting, the underfrequency
band accumulate protection will operate to issue alarm signal or trip.
The positive voltage is used to calculate the system frequency, after a filtering process, the
measurement of system frequency will not be affected by the harmonic component.
Where:
f is system frequency.
Where:
f is system frequency.
[81U.UFx.f_Set] is the upper limit frequency setting of stage x (x=1~4) of underfrequency band
accumulate protection.
Date: 2015-07-29
3 Operation Theory
[81U.UFx’.f_Set] is the lower limit frequency setting of stage x (x=1~4) of underfrequency band
accumulate protection.
3.13.4 Logic
For underfrequency protection, when following three conditions are met, the protection is enabled.
(2) The protection function enabling binary inputs [81U.En1] and [81U.En2] are “1”
If underfrequency protection is disabled, all the related output signals will be reset. If no external
input is configured to [81U.En1] ([81U.En2]), the default initial value of [81U.En1] ([81U.En2]) is “1”;
if no external input is configured to [81U.Blk], the default initial value of [81U.Blk] is “0”.
EN [81U.En]
SIG [81U.Flg_OnLoad]
&
& [81U.UFx.t_Op] 0s
EN [81U.UFx.En_Alm] & [81U.UFx.Alm]
SIG f < [81U.UFx.f_Set]
& [81U.St]
& [81U.UFx.t_Op] 0s
EN [81U.UFx.En_Trp] &
[81U.UFx.Op]
SIG f < [81U.UFx.f_Set]
0 500ms
SIG 81U.FD
Date: 2015-07-29
3 Operation Theory
EN [81U.En]
SIG [81U.Flg_OnLoad]
&
&
& [81U.UF1.t_Accu] 0s
EN [81U.UF1.En_Alm_Accu] [81U.UF1.Alm_Accu]
SIG [81U.UF2.f_Set]<f< [81U.UF1.f_Set]
& [81U.St]
& [81U.UF1.t_Accu] 0s
EN [81U.UF1.En_Trp_Accu] &
[81U.UF1.Op_Accu]
SIG [81U.UF2.f_Set]<f< [81U.UF1.f_Set]
0 500ms
SIG 81U.FD
The stage 2 and stage 3 of underfrequency band accumulate protection are similar to stage 1 of
underfrequency band accumulate protection.
EN [81U.En]
SIG [81U.Flg_OnLoad]
&
& [81U.UF4.t_Accu] 0s
EN [81U.UF4.En_Alm_Accu] & [81U.UF4.Alm_Accu]
SIG 0<f< [81U.UF4.f_Set]
& [81U.St]
& [81U.UF4.t_Accu] 0s
EN [81U.UF4.En_Trp_Accu] &
[81U.UF4.Op_Accu]
SIG 0<f< [81U.UF4.f_Set]
0 500ms
SIG 81U.FD
Where:
f is system frequency.
81U.FD is the internal signal to indicate that underfrequency protection picks up (the fault detector
of fault detector DSP module).
Date: 2015-07-29
3 Operation Theory
81U
f 81U.St
81U.En1 81U.UF1.Op
81U.En2 81U.UF2.Op
81U.Blk 81U.UF3.Op
81U.Flg_OnLoad 81U.UF4.Op
Flg_52a 81U.UF1.Op_Accu
81U.UF2.Op_Accu
81U.UF3.Op_Accu
81U.UF4.Op_Accu
81U.UF1.Alm
81U.UF2.Alm
81U.UF3.Alm
81U.UF4.Alm
81U.UF1.Alm_Accu
81U.UF2.Alm_Accu
81U.UF3.Alm_Accu
81U.UF4.Alm_Accu
Date: 2015-07-29
3 Operation Theory
Above input and output signals can be used for programmable logic, and following output signals
are only for LCD display and waveform recording function of the device.
Tripping reports
Start signals
Alarm signals
Date: 2015-07-29
3 Operation Theory
Waveform recording
IO events
Access Path:
Main menu -> Measurements -> Measurements2-> Prot Values-> Freq Prot Values
3.13.6 Settings
Date: 2015-07-29
3 Operation Theory
Date: 2015-07-29
3 Operation Theory
3.14.1 Application
The rate-of-frequency-change protection is applied to quickly detect the frequency change of
system. If system frequency has a decreasing trend or an increasing trend, the protection can
detect it and operate to issue an alarm signal or a trip command. When active power demand and
active power supply can not keep the balance, the system frequency will change. The system
frequency decrease demands for loss of load of system, and the system frequency increase
demands for reduction of output and even generator shutdown.
Date: 2015-07-29
3 Operation Theory
3.14.2 Function
3.14.3.1 Overview
The relay consistently monitoring the rate-of-frequency-change, if the rate-of-change for frequency
increase or decrease is greater than the pre-configured setting, a timer has been started, if the
duration exceeds the set time delay, the protection will operate to alarm or trip.
3.14.3.2 Measurement
The relay will use positive voltage to calculate the frequency value, the average value of the
frequency can be got via frequency smoothing calculation. The time period is configurable (the
default value is 5 cycles), within which the frequency change can be got. The ratio between the
frequency change and the time period is the corresponding rate-of-frequency-change. It can be a
positive value or a negative one.
To prevent the mal-operation of the protection, the low voltage blocking function is available for
rate-of-frequency-change protection, the low voltage blocking can be enabled or disabled, and the
low voltage blocking setting is settable. If the positive-sequence voltage is lower than the low
voltage blocking setting, the system frequency can not be accurately calculated from the voltage
signal, so the rate-of-frequency-change protection will be disabled automatically.
3.14.3.4 Criteria
Four stages of rate-of-frequency-change protection are available, the protection can operate to
alarm or trip.
Date: 2015-07-29
3 Operation Theory
df
[81R.RFx.df/dt_Set] Equation 3.14-1
dt
Where:
df
is the calculated rate-of-frequency-change.
dt
df
-[81R.RFx.df/dt_Set] Equation 3.14-2
dt
Where:
df
is the calculated rate-of-frequency-change.
dt
3.14.4 Logic
For rate-of-frequency-change protection, when following three conditions are met, the
rate-of-frequency-change protection is enabled.
(2) The protection function enabling inputs [81R.En1], [81R.En2] are “1”.
If rate-of-frequency-change protection is disabled, all the related output signals will be reset. If no
external input is configured to [81R.En1] ([81R.En2]), the default initial value of [81R.En1]
([81R.En2]) is “1”; if no external input is configured to [81R.Blk], the default initial value of [81R.Blk]
is “0”.
Logics of rate-of-frequency-change protection is shown in following figure (takes the logic scheme
of stage 1 of rate-of-frequency-change protection as an example, the logic scheme of other stages
are the same).
Date: 2015-07-29
3 Operation Theory
Set 81R.RF1.En_Alm
Set 81R.En_UV_Blk ≥1
Sig f<[81R.RF1.f_Pkp]
&
Sig df/dt<-[81R.RF1.df/dt_Set]
≥1
Set [81R.RF1.Opt_Trend] 0/increase &
1/decrease [81R.RF1.t_Op] 0ms
& [81R.RF1.Alm]
Sig df/dt>[81R.RF1.df/dt_Set]
&
Sig f>[81R.RF1.f_Pkp]
SIG 81R.En2
SIG 81R.Blk
Set 81R.RF1.En_Trp
0 500ms
Sig 81R.FD
Where:
f is system frequency.
df
is the calculated system rate-of-frequency-change.
dt
81R.FD is the operation flag of the fault detector of rate-of-frequency-change protection (the fault
detector of fault detector DSP module).
81R
f 81R.St
81R.U3P 81R.RF1.Op
81R.En1 81R.RF2.Op
81R.En2 81R.RF3.Op
81R.Blk 81R.RF4.Op
Flg_52a 81R.RF1.Alm
81R.Flg_Onload 81R.RF2.Alm
81R.RF3.Alm
81R.RF4.Alm
Date: 2015-07-29
3 Operation Theory
Above input and output signals can be used for programmable logic, and following output signals
are only for LCD display and waveform recording function of the device.
Tripping reports
Start signals
Alarm signals
Waveform recording
Date: 2015-07-29
3 Operation Theory
3.14.6 Settings
Date: 2015-07-29
3 Operation Theory
Date: 2015-07-29
3 Operation Theory
NOTICE!
In Section 3.15, the prefix “Y” in settings (such as [Y.49.Ib_Set]) and input/output
signals (such as [Y.49.Op]) can be Tr_HVS and Tr_MVS. Details of the prefix are as:
Tr_HVS.49 Corresponds to thermal overload protection of main transformer high voltage side.
Tr_MVS.49 Corresponds to thermal overload protection of main transformer medium voltage side.
3.15.1 Application
Thermal overload protection can reflect the average heating condition of transformer winding, and
it can prevent the transformer from overheating caused by overload and asymmetric overload. The
thermal overload model is based on IEC 60255-8 standard, transformer load current is used to
calculate the thermal accumulation.
3.15.2 Function
Thermal overload protection can operate to trip or alarm (with independent setting and logic
setting).
One binary input signal can be used to clear the thermal accumulation.
Thermal overload protection reflects the overheating condition of transformer three-phase winding,
the thermal accumulation meets the demand of IEC 60255-8 standard. For any phase of
transformer winding, the operation time meets the following equation:
Date: 2015-07-29
3 Operation Theory
2 2
I eq I p
t ln Equation 3.15-1
2 2
I eq ( k I B )
Where:
three-phase currrent.
I p is the steady-state current before the thermal overload element pick-up, for cooling start
characteristic, I p is zero.
ln is natural logarithm.
If the thermal accumulation exceeds 100%, the device will operate to alarm or trip according to the
value of corresponding logic settings.
If the current disappears or is lower than the thermal overload base current, the heat dissipation
starts, the thermal accumulation will decline. One binary input signal can be used to clear the
thermal accumulation.
3.15.4 Logic
For thermal overload protection, when following three conditions are met, the thermal overload
protection is enabled.
(2) The protection function enabling inputs [Y.49.En1], [Y.49.En2] are “1”.
If thermal overload protection is disabled, all the related output signals will be reset. If no external
input is configured to [Y.49.En1] ([Y.49.En2]), the default initial value of [Y.49.En1] ([Y.49.En2]) is
“1”; if no external input is configured to [Y.49.Blk], the default initial value of [Y.49.Blk] is “0”.
Date: 2015-07-29
3 Operation Theory
EN [Y.49.En]
SIG [Y.49.En1] &
SIG [Y.49.En2]
SIG [Y.49.Blk]
&
IDMT [Y.49.Alm]
EN [Y.49.En_Alm]
SIG I>[Y.49.Ib_Set]
EN [Y.49.En]
SIG [Y.49.En1] &
[Y.49.St]
SIG [Y.49.En2] &
SIG [Y.49.Blk] IDMT [Y.49.Op]
EN [Y.49.En_Trp]
SIG I>[Y.49.Ib_Set]
0ms 500ms
SIG Y.49.FD
Where:
Y.49.FD is the operation flag of the fault detector of thermal overload protection (the fault detector
of fault detector DSP module).
49
Y.49.I3P Y.49.St
Y.49.Clear Y.49.Op
Y.49.En1 Y.49.Alm
Y.49.En2
Y.49.Blk
Above input and output signals can be used for programmable logic, and following output signals
Date: 2015-07-29
3 Operation Theory
are only for LCD display and waveform recording function of the device.
Tripping report
Start signal
Alarm signal
Waveform recording
Access path:
Main menu -> Measurements -> Measurements2-> Prot Status->Tr HVS PPF Prot Values
Main menu -> Measurements -> Measurements2-> Prot Status->Tr MVS PPF Prot Values
3.15.6 Settings
Date: 2015-07-29
3 Operation Theory
NOTICE!
In Section 3.16, the prefix “Y” in settings (such as [Y.21M1.I_PSBR]) and input/output
signals (such as [Y.21M1.ZP.Op]) can be Tr_HVS and Tr_MVS. Details of the prefix are
as:
3.16.1 Application
When phase overcurrent protection and ground overcurrent protection cannot meet the sensitivity
requirement of transformer backup protection, impedance protection can be configured. The
operation mode of power system has little effect on impedance protection, so impedance
protection can coordinate with protections of adjacent equipment easily.
Two stage phase-to-phase impedance protection elements with respective impedance setting,
time delay setting and logic setting.
Two stage phase-to-earth impedance protection elements with respective impedance setting,
time delay setting and logic setting.
3.16.3.1 Overview
The fault detector of impedance protection includes the DPFC phase-to-phase current fault
detector and the negative-sequence current fault detector. The fault detector output signal will last
for 500ms after the corresponding fault detector picks up, if phase-to-phase or phase-to-earth
impedance relay operates within the 500ms, the fault detector output signal will be kept.
Date: 2015-07-29
3 Operation Theory
I 1 . 25 I t I th Equation 3.16-1
Where:
I t is the floating threshold value which will arise automatically and gradually according to
increasing of the current changing. The coefficient takes 1.25 in order to ensure the threshold
current is always slightly larger than the unbalance output, so the protection will not mal-operate
under power swing and frequency shifting condition.
Where:
If VT and CT are connected as following figure, i.e. the positive polarity of CT is at busbar side,
points to the protected object, then the setting [Y.21Mx.ZP.Opt_Dir] and [Y.21Mx.ZG.Opt_Dir]
should be set as “1”. Otherwise [Y.21Mx.ZP.Opt_Dir] and [Y.21Mx.ZG.Opt_Dir] should be set as “0”.
Date: 2015-07-29
3 Operation Theory
Reverse Forward
CT
Protected
Object
VT
Direction
Element
Following figure shows operating characteristic of phase-to-phase impedance relay, the setting
[Y.21Mx.RCA] (x=1 or 2) is impedance characteristic angle (i.e. m shown in the following figure,
it is also called reach angle). In the figure, if the setting [Y.21Mx.ZP.Opt_Dir] is “1”, Zn is the
reverse impedance setting [Y.21Mx.ZP.Z_Rev] and Zp is the forward impedance setting
[Y.21Mx.ZP.Z_Fwd]. If the setting [Y.21Mx.ZP.Opt_Dir] is “0”, Zn is the forward impedance setting
[Y.21Mx.ZP.Z_Fwd] and Zp is the reverse impedance setting [Y.21Mx.ZP.Z_Rev].
jx
IZp
U IZp
U
m
R
IZn U IZn
(U I Z P )
90 Arg
270 Equation 3.16-3
(U I Z n )
Where:
Date: 2015-07-29
3 Operation Theory
NOTICE!
Following figure shows operating characteristic of phase-to-earth impedance relay, the setting
[Y.21Mx.RCA] (x=1 or 2) is impedance characteristic angle (i.e. m shown in the following figure,
it is also called reach angle). In the figure, If the setting [Y.21Mx.ZG.Opt_Dir] is “1”, Zn is the
reverse impedance setting [Y.21Mx.ZG.Z_Rev] and ZG is the forward impedance setting
[Y.21Mx.ZG.Z_Fwd]. If the setting [Y.21Mx.ZG.Opt_Dir] is “0”, Zn is the forward impedance setting
[Y.21Mx.ZG.Z_Fwd] and ZG is the reverse impedance setting [Y.21Mx.ZG.Z_Rev].
jx
(I k 3I 0 )ZG
U (I k 3I 0 )ZG
U
m
R
-(I k 3 I 0 )Zn U (I k 3I 0 )Zn
U (I k 3 I 0 )Z G
90 A rg
270 Equation 3.16-4
U (I k 3 I 0 )Z n
Where:
Date: 2015-07-29
3 Operation Theory
z 0 z1
k is the zero-sequence compensated coefficient of stage x of phase-to-earth
3 z1
impedance protection [Y.21Mx.K0], the setting range is 0~2. If the ground impedance points to the
busbar of local side, it takes 0.6 generally; If the ground impedance points to the transformer, it
takes 0~0.1 generally.
NOTICE!
The logic setting [Y.21Mx.En_PSBR] is used to enable or disable PSBR function. If it is set as “1”,
the PSBR function is enabled. Otherwise, it is disabled.
If the time delay of impedance protection is more than 1.5s, PSBR function is not needed for the
impedance protection.
Power swing blocking for impedance relay will be released if any of the following PSBR elements
operate.
At the moment that any impedance protection fault detector picks up, if positive-sequence
overcurrent element does not operate or the operating duration is less then 10ms, FD PSBR will
operate for 160ms.
I1 is positive-sequence current.
[Y.21Mx.I_PSBR] (x=1 or 2) is the current setting of FD PSBR, which is set larger than the
maximum load current of transformer.
Date: 2015-07-29
3 Operation Theory
10ms 0
SIG I1>[Y.21Mx.I_PSBR] ≥1
&
0 160ms
SIG I1≤[Y.21Mx.I_PSBR] Flg_Pkp_FDPSBR
SIG Y.21M.FD
When an internal unsymmetrical fault happens, power swing blocking for impedance relay can be
released by following element:
I0 I2 m I1 Equation 3.16-6
Where:
“m” is an internal fixed coefficient with a certain margin which can ensure UF PSBR operate during
power swing with internal unsymmetrical fault, while not operate during power swing or power
swing with external fault.
respectively.
When fault detector operates and after 160ms, or during the power swing, if a three-phase fault
occurs, both of FD PSBR and UF PSBR can not operate to release the impedance protection.
Thus, SF PSBR is provided for this case specially. This detection is based on measuring the
voltage of power swing center:
U OS
U 1 cos Equation 3.16-7
Where:
1) When 0 . 03 U N
U OS
0 . 08 U N , the SF PSBR element will operate with a time delay
150ms.
2) When 0 . 1U N
U OS
0 . 25 U N , the SF PSBR element will operate with a time delay
500ms.
Date: 2015-07-29
3 Operation Theory
3.16.4 Logic
The logic of phase-to-earth impedance protection is same to that of phase-to phase impedance
protection, and stage 1 of phase-to-phase impendence protection of HV side is taken as an
example as shown below.
For each stage of impedance protection, if following three conditions are met, the corresponding
stage of impedance protection is enabled.
(2) The protection function enabling inputs [Tr_HVS.21M1.En1], [Tr_HVS.21M1.En2] are “1”.
If impedance protection is disabled, all the related output signals will be reset. If no external input
is configured to [Tr_HVS.21M1.En1] ([Tr_HVS.21M1.En2]), the default initial value of
[Tr_HVS.21M1.En1] ([Tr_HVS.21M1.En2]) is “1”; if no external input is configured to
[Tr_HVS.21M1.Blk], the default initial value of [Tr_HVS.21M1.Blk] is “0”.
EN Flg_Pkp_UFPSBR
≥1
EN Flg_Pkp_SFPSBR Flg_Pkp_PSBR
SIG Flg_Pkp_FDPSBR
SIG Flg_Pkp_PSBR ≥1
SIG [Tr_HVS.21M1.En_PSBR]
SIG Flg_Op_ZP1
&
SET [Tr_HVS.21M1.En]
&
SIG [Tr_HVS.21M1.En1] &
[Tr_HVS.21M1.ZP.St]
SIG [Tr_HVS.21M1.En2]
[Tr_HVS.21M1.ZP.t_Op] 0s [Tr_HVS.21M1.ZP.Op]
SIG [Tr_HVS.21M1.Blk]
SIG [Tr_HVS.21M1.En_VTS_Blk]
0ms 500ms
SIG Tr_HVS.21M1.FD
Where:
Flg_Pkp_UFPSBR is the internal flag indicating that unsymmetrical fault PSBR element picks up.
Flg_Pkp_SFPSBR is the internal flag indicating that symmetrical fault PSBR element picks up.
Flg_Pkp_FDPSBR is the internal flag indicating that fault detector PSBR element picks up.
Tr_HVS.21M1.FD is the operation flag of the fault detector of DPFC phase-to-phase current or
that of negative-sequence current (the fault detector of fault detector DSP module).
Date: 2015-07-29
3 Operation Theory
Flg_Pkp_PSBR is the internal flag indicating that power swing blocking releasing element picks
up.
Flg_Op_ZP1 is the internal flag indicating that the operation criterion of stage 1 of phase-to-phase
impedance relay (i.e. Equation 3.16-3) is met.
21
Y.21Mx.U3P Y.21Mx.St
Y.21Mx.I3P Y.21Mx.ZP.Op
Y.21Mx.En1 Y.21Mx.ZG.Op
Y.21Mx.En2
Y.21Mx.Blk
x=1 and 2.
Above input and output signals can be used for programmable logic, and following output signals
are only for LCD display and waveform recording function of the device.
Tripping reports
Date: 2015-07-29
3 Operation Theory
Start signals
Waveform recording
19 Y.21Mx.Ang(Uab-Iab) Phase angle between phase-AB voltage and phase-AB current deg
20 Y.21Mx.Ang(Ubc-Ibc) Phase angle between phase-BC voltage and phase-BC current deg
21 Y.21Mx.Ang(Uca-Ica) Phase angle between phase-CA voltage and phase-CA current deg
22 Y.21Mx.Ang(Ua-Ia) Phase angle between phase-A voltage and phase-A current deg
23 Y.21Mx.Ang(Ub-Ib) Phase angle between phase-B voltage and phase-B current deg
24 Y.21Mx.Ang(Uc-Ic) Phase angle between phase-C voltage and phase-C current deg
Date: 2015-07-29
3 Operation Theory
Access path:
Main menu -> Measurements -> Measurements2-> Prot Values->Tr HVS Impedance Prot Values
Main menu -> Measurements -> Measurements2-> Prot Values->Tr MVS Impedance Prot Values
3.16.6 Settings
x=1 or 2;
Date: 2015-07-29
3 Operation Theory
impedance protection.
Tripping logic setting of stage x of
15 Y.21Mx.ZG.OutMap 0~3FFFFFFF
phase-to-earth impedance protection.
0: disable Logic setting of enabling/disabling stage x of
16 Y.21Mx.ZG.En 1
1: enable phase-to-earth impedance protection.
Logic setting of enabling/disabling VT circuit
0: disable
17 Y.21Mx.En_ VTS_Blk 1 failure block element of stage x of impedance
1: enable
protection.
0: disable Logic setting of enabling/disabling the PSBR
18 Y.21Mx.En_PSBR 1
1: enable element of stage x of impedance protection.
Access path:
Settings-> Prot Settings -> TrHVS Impedance Settings
Settings-> Prot Settings -> TrMVS Impedance Settings
NOTICE!
In Section 3.17, the prefix “Y” in settings (such as [Y.50BF.I2_Set]) and input/output
signals (such as [Y.50BF.Op]) can be Tr_HVS and Tr_MVS. Details of the prefix are as:
Tr_HVS.50BF Corresponds to breaker failure protection of main transformer high voltage side.
Tr_MVS.50BF Corresponds to breaker failure protection of main transformer medium voltage side.
3.17.1 Application
Breaker failure protection is applied to monitor the circuit breaker state to ensure that the circuit
breaker is correctly opened. When a tripping command is issued from the protection device, but
the circuit breaker have not been tripped within a certain time delay, so that the fault can not be cut
off, then the circuit breaker of upper stream will be initiated to trip.
After the tripping command been issued, the device will check whether the phase current and
negative-sequence current are larger than corresponding setting.
The protection will use the auxiliary contact of the circuit breaker to judge whether the circuit
breaker is correctly tripped. As under certain circumstances, the criteria of current are not
applicable, like frequency protection, voltage protection and overexcitation protection etc.
The internal logic between above two criteria can be “And” or “Or”. If the setting
[Y.50BF.Opt_Mode] is set as “0”, the internal logic between current criterion and circuit breaker
auxiliary contact criterion is “Or”; if the setting [Y.50BF.Opt_Mode] is set as “1”, the internal logic
between current criterion and circuit breaker auxiliary contact criterion is “And”. Current criterion
Date: 2015-07-29
3 Operation Theory
and circuit breaker auxiliary contact criterion can be enabled or disabled separately, so that there
are four possible combinational logics for breaker failure protection:
3.17.3.1 Overview
The breaker failure protection has two independent tripping stages and is controlled by the input
signal [Y.50BF.Init], which can be an internal protection tripping signal or an external protection
operating binary input.
Current criteria include phase current criterion and negative-sequence current criterion. If any
current criterion is satisfied, current element of breaker failure protection picks up.
Where:
Where:
Where:
Date: 2015-07-29
3 Operation Theory
3.17.4 Logic
For breaker failure protection, when following three conditions are met, the breaker failure
protection is enabled.
(2) The protection function enabling inputs [Y.50BF.En1], [Y.50BF.En2] are “1”.
If breaker failure protection is disabled, all the related output signals will be reset. If no exte rnal
input is configured to [Y.50BF.En1] ([Y.50BF.En2]), the default initial value of [Y.50BF.En1]
([Y.50BF.En2]) is “1”; if no external input is configured to [Y.50BF.Blk], the default initial value of
[Y.50BF.Blk] is “0”.
Logics of breaker failure protection (with two time delays) is shown in following figure.
Sig IΦ_max>[Y.50BF.Ip_set]
1 A AND B
Set [Y.50BF.En_3I0] & B
Sig 3I0>[Y.50BF.3I0_Set]
Sig [BI_52b]
OR/AND
&
Set [Y.50BF.Opt_Mode] [Y.50BF.St]
[Y.50BF.t1_Op] 0ms
En [Y.50BF.En] [Y.50BF.Op_t1]
&
SIG [Y.50BF.En1] [Y.50BF.t2_Op] 0ms
[Y.50BF.Op_t2]
SIG [Y.50BF.En2]
SIG [Y.50BF.Blk]
Sig [Y.50BF.Init]
0ms 500ms
Sig Y.50BF.FD
Where:
50BF.FD is the operation flag of the fault detector of breaker failure protection (the fault detector of
fault detector DSP module).
Date: 2015-07-29
3 Operation Theory
50BF
Y.50BF.I3P Y.50BF.St
Y.50BF.Init Y.50BF.Op_t1
Y.50BF.En1 Y.50BF.Op_t2
Y.50BF.En2
Y.50BF.Blk
BI_52b
Above input and output signals can be used for programmable logic, and following output signals
are only for LCD display and waveform recording function of the device.
Tripping reports
Start signals
Waveform recording
Date: 2015-07-29
3 Operation Theory
3.17.6 Settings
NOTICE!
In Section 3.18, the prefix “Y” in settings (such as [Y.62PD.I2_Set]) and input/output
signals (such as [Y.62PD.Op]) can be Tr_HVS and Tr_MVS. Details of the prefix are as:
Tr_HVS.62PD Corresponds to pole disagreement protection of main transformer high voltage side.
Date: 2015-07-29
3 Operation Theory
Tr_MVS.62PD Corresponds to pole disagreement protection of main transformer medium voltage side.
3.18.1 Application
If the voltage level of some side of transformer is high, usually phase -segregated circuit breaker is
equipped. If three-phase can not closing or tripping simultaneously due to mal-operation or
mechanical reason, or some phase trip suddenly (mal-trip) during normal operation, all of these
will lead to three-phase unbalance of the system and damage of power equipment. So that if a
pole disagreement fault is detected, after a settable time delay, pole disagreement protection will
issue a trip command to trip three-phase circuit breaker.
3.18.2 Function
There are two current criteria for pole disagreement protection: residual current criterion and
negative-sequence current criterion. The two current criteria can be enabled or disabled
independently.
3.18.3.1 Overview
The device will detect the pole disagreement position input signal [Y.62PD.In_PD_CB], if the input
signal is “1”, pole disagreement protection is initiated. If the pole disagreement position input
signal is “1” for a long time, pole disagreement position contact abnormality alarm will be issued.
If any current criterion is enabled, the protection will also detect whether the residual current or
negative-sequence current is larger than the corresponding current setting.
Current criteria include residual current criterion and negative-sequence current criterion. If any
current criterion is met, current element of pole disagreement protection will pick up.
Where:
Where:
Date: 2015-07-29
3 Operation Theory
3.18.4 Logic
For pole disagreement protection, when following three conditions are met, the pole disagreement
protection is enabled.
(2) The protection function enabling inputs [Y.62PD.En1], [Y.62PD.En2] are “1”.
If pole disagreement protection is disabled, all the related output signals will be reset. If no
external input is configured to [Y.62PD.En1] ([Y.62PD.En2]), the default initial value of
[Y.62PD.En1] ([Y.62PD.En2]) is “1”; if no external input is configured to [Y.62PD.Blk], the default
initial value of [Y.62PD.Blk] is “0”.
BI Y.62PD.In_PD_CB
Set Y.62PD.En_3I0
≥1 ≥1
&
[Y.62PD.St]
Set Y.62PD.En_I2 & [Y.62PD.t_Op] 0ms
[Y.62PD.Op]
Sig I2>[Y.62PD.I2_Set]
En Y.62PD.En
&
SIG Y.62PD.En1
SIG Y.62PD.En2
SIG Y.62PD.Blk
0ms 500ms
Sig Y.62PD.FD
[Y.62PD.t_Alm] 0ms
BI Y.62PD.In_PD_CB [Y.62PD.Alm]
Where:
Y.62PD.FD is the operation flag of the fault detector of pole disagreement protection (the fault
detector of fault detector DSP module).
Date: 2015-07-29
3 Operation Theory
62PD
Y.62PD.I3P Y.62PD.St
Y.62PD.In_PD_CB Y.62PD.Op
Y.62PD.En1 Y.62PD.Alm
Y.62PD.En2
Y.62PD.Blk
Above input and output signals can be used for programmable logic, and following output signals
are only for LCD display and waveform recording function of the device.
Tripping reports
Start signals
Alarm signals
Waveform recording
Date: 2015-07-29
3 Operation Theory
3.18.6 Settings
In Section 3.19, the prefix “Y” in settings (such as [Y.50F.I2_Set]) and input/output
signals (such as [Y.50F.Op_t1]) can be Tr_HVS and Tr_MVS. Details of the prefix are
as:
Tr_HVS.50F Corresponds to breaker flashover protection of main transformer high voltage side.
Tr_MVS.50F Corresponds to breaker flashover protection of main transformer medium voltage side.
3.19.1 Application
For the large-scale generator-transformer unit in higher voltage level system, during the process of
preparation synchronization or just out of operation, flashover in circuit breaker is possible when
phase angle difference between the voltages of two sides of the circuit breaker is around 180°.
Flashover in circuit breaker will damage the circuit breaker, and it also maybe cause the trouble to
extend, then the stable operation of the system will be destroyed. Usually flashover in circuit
breaker is one phase and two-phase flashover, it will generate torque which will act on the
generator, on the other hand it will generate negative-sequence current which will cause additional
loss to the rotor, and then the safety of the generator will be threatened. If the device detect the
Date: 2015-07-29
3 Operation Theory
flashover fault, breaker flashover protection will operate to start de-excitation of the generator and
initiate the circuit breaker failure protection with a settable time delay.
3.19.2 Function
Breaker flashover protection includes following two criteria:
Circuit breaker position auxiliary contact criterion. The circuit breaker is open when flashover
happens, users can select to only judge circuit breaker normally closed contact or judge both
of circuit breaker normally open contact and normally closed contact.
Current criteria: negative-sequence current criterion, phase current criterion and residual
current criterion.
The internal logic between the above two criteria is “And”. Negative-sequence current criterion is
enabled fixedly; phase current criterion and residual current criterion can be enabled or disabled
independently.
3.19.3.1 Overview
When the circuit breaker is open, and the negative-sequence current or phase current or residual
current is larger than the corresponding setting, breaker flashover protection will operate to trip.
Two independent time delays are available for breaker flashover protection, breaker flashover
protection with time delay 1 can operate to trip generator circuit breaker or de-excitation circuit
breaker, breaker flashover protection with time delay 2 can operate to initiate the circuit breaker
failure protection.
If the setting [Y.50F.Opt_Mode] is set as “0”, the protection will only judge the circuit breaker
normally closed auxiliary contact, if the normally closed auxiliary contact [BI_52b] is “1”, it means
the circuit breaker is open. If the setting [Y.50F.Opt_Mode] is set as “1”, the protection will judge
the circuit breaker normally closed auxiliary contact and normally open auxiliary contact, if the
normally closed auxiliary contact [BI_52b] is “1” and the normally open auxiliary contact [BI_52a] is
“0”, it means the circuit breaker is open.
When the setting [Y.50F.Opt_Mode] is set as “0”, if the normally closed auxiliary contact [BI_52b] is
“1” for a long time and current is detected, circuit breaker contact abnormality alarm [Y.50F.Alm]
will be issued. When the setting [Y.50F.Opt_Mode] is set as “1”, if the state of both of normally
closed auxiliary contact [BI_52b] and normally open auxiliary contact [BI_52a] are the same, circuit
breaker contact abnormality alarm [Y.50F.Alm] will also be issued.
Current criteria include negative-sequence current criterion, residual current criterion, and phase
current criterion. If any current criterion is met, current element of breaker flashover protection
picks up.
Date: 2015-07-29
3 Operation Theory
Where:
Where:
Where:
[Y.50F.Ip_Set] is the phase current setting of breaker flashover protection of corresponding side.
3.19.4 Logic
For breaker flashover protection, when following three conditions are met, the breaker flashover
protection is enabled.
(2) The protection function enabling inputs [Y.50F.En1], [Y.50F.En2] are “1”.
If breaker flashover protection is disabled, all the related outp ut signals will be reset. If no external
input is configured to [Y.50F.En1] ([Y.50F.En2]), the default initial value of [Y.50F.En1] ([Y.50F.En2])
is “1”; if no external input is configured to [Y.50F.Blk], the default initial value of [Y.50F.Blk] is “0”.
Logics of breaker flashover protection (with two time delays) is shown in following figure.
Date: 2015-07-29
3 Operation Theory
Sig IΦ_max>[Y.50F.Ip_Set]
Sig 3I0>[Y.50F.3I0_Set]
Sig I2>[Y.50F.I2_Set]
&
Sig BI_52b
≥1
&
Set Y.50F.Opt_Mode &
&
[Y.50F.St]
Sig BI_52a
[Y.50F.t1_Op] 0ms [Y.50F.Op_t1]
Sig Y.50F.Alm
[Y.50F.t2_Op] 0ms [Y.50F.Op_t2]
En Y.50F.En
&
SIG Y.50F.En1
SIG Y.50F.En2
SIG Y.50F.Blk
0ms 500ms
Sig Y.50F.FD
Set Y.50F.Opt_Mode
≥1
[Y.50F.t_Alm] 0ms [Y.50F.Alm]
Sig BI_52b =1
Set Y.50F.Opt_Mode
Where:
Y.50F.FD is the operation flag of the fault detector of breaker flashover protection (the fault
detector of fault detector DSP module).
Date: 2015-07-29
3 Operation Theory
Y.50F.I3P Y.50F.St
BI_52b Y.50F.Op_t1
BI_52a Y.50F.Op_t2
Y.50F.En1 Y.50F.Alm
Y.50F.En2
Y.50F.Blk
Above input and output signals can be used for programmable logic, and following output signals
are only for LCD display and waveform recording function of the device.
Tripping reports
Start signals
Alarm signals
Waveform recording
Date: 2015-07-29
3 Operation Theory
3.19.6 Settings
3.20.1 Application
Any operation signal from the transformer body protection or other external device can be coupled
to the microprocessor-based protection device via the binary input signal. Transformer mechanical
protection can repeat these binary input signals to send alarm signals, tripping directly or tripping
with a time delay. By this way the output signal of some mechanical protection (such as gas
protection and etc.) can be coupled to the microprocessor-based protection device, and then
Date: 2015-07-29
3 Operation Theory
these signals can be repeated through high-power relays to improve the anti-inference ability of
the protection.
Each module provides 4 mechanical signal input channels for trip or alarm.
3.20.4 Logic
For mechanical protection, if following three conditions are met, the protection will be enabled.
(2) The protection function enabling inputs [MRx.En1], [MRx.En2] are “1”
If mechanical protection is disabled, all the related output signals will be reset. If no external input
is configured to [MRx.En1] ([MRx.En2]), the default initial value of [MRx.En1] ([MRx.En2]) is “1”; if
no external input is configured to [MRx.Blk], the default initial value of [MRx.Blk] is “0”.
Here takes channel 1 of mechanical protection 1 as an example. The logics of channel 2, 3 and 4
are similar with that of channel 1.
EN [MR1.En] &
EN [MR1.En_1] [MR1.Sig1]
SIG [MR1.Input1]
EN [MR1.En_1] &
SIG [MR1.Input1]
SET [MR1.OutMap_1] (bit0=1)
Date: 2015-07-29
3 Operation Theory
MRx
MRx.Input1 MRx.St
MRx.Input2 MRx.Op1
MRx.Input3 MRx.Op2
MRx.Input4 MRx.Op3
MRx.En1 MRx.Op4
MRx.En2 MRx.Sig1
MRx.Blk MRx.Sig2
MRx.Sig3
MRx.Sig4
Above input and output signals can be used for programmable logic, and following output signals
are only for LCD display and waveform recording function of the device.
Tripping reports
Date: 2015-07-29
3 Operation Theory
Start signals
Waveform recording
IO events
3.20.6 Settings
Date: 2015-07-29
3 Operation Theory
3.21.1 Application
Date: 2015-07-29
3 Operation Theory
after the interconnection status. The device will detect the position of main transformer HV side or
MV side circuit breaker and the current of the CT at the outlet of the circuit breaker, then
comprehensively judge whether the main transformer or the generator-transformer unit is during
interconnection status, the interconnection status flag can be output for the user to implement logic
programming.
Four circuit breaker auxiliary contact inputs, the auxiliary contact of main transformer HV
side or MV side circuit breaker can be connected to the device.
Four groups of current inputs respectively correspond to the CTs at the outlet of the four
circuit breakers.
If the setting [Num_CB_MVS_Tr] is set as “0”, it means there is no circuit breaker on main
transformer MV side. If the setting [Num_CB_MVS_Tr] is set as “1”, it means there is one circuit
breaker on main transformer MV side, then the auxiliary contact of main transformer MV side
circuit breaker and the current of the CT at the outlet of main transformer MV side circuit breaker
should be input. If the setting [Num_CB_MVS_Tr] is set as “2”, it means there are two circuit
breakers on main transformer MV side (it is also called 3/2 breakers wiring), then the auxiliary
contacts of the two circuit breakers of main transformer MV side and the currents of the CTs at the
outlet of the two circuit breakers should be input.
The device will detect the position of main transformer HV side or MV side circuit breaker and the
current of the CT at the outlet of the circuit breaker, then comprehensively judge whether the main
transformer or the generator-transformer unit is during interconnection status, the interconnection
status flag can be output for the user to implement logic programming.
3.21.4 Logic
Date: 2015-07-29
3 Operation Theory
SIG BI_52b_CB1 ≥1
&
&
SIG [Num_CB_HVS_Tr]=2
[Flg_52a]
SIG [Num_CB_MVS_Tr]=0
SIG [Num_CB_MVS_Tr]=2
SIG Imax1>0.04In
SIG Imax2>0.04In ≥1
[TrCBStatus.Flg_OnLoad]
SIG Imax3>0.04In
SIG Imax4>0.04In
Where:
Date: 2015-07-29
3 Operation Theory
TrCBStatus
TrCBStatus.I3P1
TrCBStatus.I3P2
TrCBStatus.I3P3
TrCBStatus.I3P4 Flg_52a
BI_52b_CB1 TrCBStatus.Flg_OnLoad
BI_52b_CB2
BI_52b_CB3
BI_52b_CB4
Above input and output signals can be used for programmable logic, and following output signals
are only for LCD display and waveform recording function of the device.
The signal indicating that current of the CT at the outlet of the circuit
2 TrCBStatus.Flg_OnLoad
breaker is detected.
Date: 2015-07-29
3 Operation Theory
Access path:
Main menu -> Measurements -> Measurements2-> Prot Values-> Misc Prot Values
3.21.6 Settings
3.22.1 Application
Current sum element is used to synthesize several channels of three-phase current as one
channel of three-phase current, so it can be convenient for protection logic calculation.
3.22.3 Principle
If one side of the protected object has several branches, sometimes the current sum of the several
branches is needed. The CT ratio of the several branches can be different, the CT ratio of the first
channel of current is taken as the referenced CT ratio, the currents of other channel(s) will be
converted to the first channel firstly, and then the current sum is calculated.
3.22.4 Logic
EN [Y.CurrSum.En] &
[Y.CurrSum.I3P]
SIG [Y.CurrSum.I3P1]
SIG [Y.CurrSum.I3P2]
SIG [Y.CurrSum.I3P3]
Date: 2015-07-29
3 Operation Theory
Y.CurrSum
Y.CurrSum.I3P1 Y.CurrSum.I3P
Y.CurrSum.I3P2 Y.CurrSum.Ang(Ia)
Y.CurrSum.I3P3 Y.CurrSum.Ang(Ib)
Y.CurrSum.Ang(Ic)
Y.CurrSum.Flg_OnLoad
Above input and output signals can be used for programmable logic, and following output signals
are only for LCD display and waveform recording function of the device.
1 Y.CurrSum.Ia A
3 Y.CurrSum.Ic A
5 Y.CurrSum.Ang(Ia-Ib) Phase angle between phase A and phase B currents of x side. deg
6 Y.CurrSum.Ang(Ib-Ic) Phase angle between phase B and phase C currents of x side deg
7 Y.CurrSum.Ang(Ic-Ia) Phase angle between phase C and phase A currents of x side deg
Date: 2015-07-29
3 Operation Theory
3.22.6 Settings
NOTICE!
The settings in above table CAN NOT be seen on LCD of equipment. These settings
are usually configured by field commission engineer according to the design drawing
and project requirement.
NOTICE!
In Section 3.23, the prefix “Y” in settings (such as [Y.I1n]) and input/output signals (such
as [Y.Ia]) can be Tr_HVS1, Tr_HVS2, Tr_MVS, Tr_LVS and ST_HVS#. Details of the
prefix are as:
3.23.1 Application
Date: 2015-07-29
3 Operation Theory
Three-phase current element is responsible for pre-processing three phase currents and
calculating sequence components, amplitudes and phases of three phase currents, etc. All
calculated information of three-phase current element is for the protection logic calculation.
3.23.3 Principle
If the calculated residual current is larger than 0.04In plus 25% of the maximum phase current, the
corresponding CT circuit abnormality alarm signal [Y.AlmL_CTS] will be issued with a time delay of
10s, and it will be reset with a time delay of 10s if the CT circuit returns to normal condition.
Current detection
When any phase current is larger than 0.04In, it will be identified that current is detected for the
corresponding CT, CT having current signal can be used for programmable logic application.
3.23.4 Logic
10s 10s
SIG Y.3I0>0.04In+0.25Imax [Y.AlmL_CTS]
SIG Y.Ia>0.04In
≥1
SIG Y.Ib>0.04In [Y.Flg_OnLoad]
SIG Y.Ic>0.04In
Where:
Y.Ia, Y.Ib, and Y.Ic are sampled three phase current values.
Date: 2015-07-29
3 Operation Theory
Curr3P
Y.ia Y.I3P
Y.ib Y.Ia
Y.ic Y.Ib
Y.Ic
Y.I_Avg
Y.AlmL_CTS
Y.Flg_OnLoad
Above input signals and output signals can be used for programmable logic, and following output
signals are only for LCD display of equipment.
Alarm signals
1 Tr_HVS1.Ia
3 Tr_HVS1.Ic
Date: 2015-07-29
3 Operation Theory
7 Tr_HVS2.Ia
9 Tr_HVS2.Ic
13 Tr_MVS.Ia
15 Tr_MVS.Ic
16 Tr_MVS.I1 Positive-sequence current amplitude of CT of main transformer MV side
19 Tr_LVS.Ia
20 Tr_LVS.Ib Phase current amplitude of CT of main transformer LV side
21 Tr_LVS.Ic
26 ST_HVS#.Ib
27 ST_HVS#.Ic
Positive-sequence current amplitude of the big-ratio CT of HV side of
28 ST_HVS#.I1
step-down transformer 1
Access path:
Main menu -> Measurements -> Measurements1-> Tr Values-> Tr Curr Values
Main menu -> Measurements -> Measurements2->Tr Values-> Tr Curr Values
Date: 2015-07-29
3 Operation Theory
Access path:
Main menu -> Measurements -> Measurements2-> Phase Angle-> Tr PhaseAngle Values
3.23.6 Settings
Date: 2015-07-29
3 Operation Theory
NOTICE!
In Section 3.24, the prefix “Y” in settings (such as [Y.U1n]) and input/output signals
(such as [Y.Ua]) can be Tr_HVS, Tr_MVS and Tr_LVS. Details of the prefix are as:
3.24.1 Application
Three-phase voltage element is responsible for pre-processing three phase voltages and
calculating sequence components, amplitudes and phases of three phase voltages, etc. All
calculated information of three-phase voltage element is for the protection logic calculation.
3.24.3 Principle
If one of following two criteria is met and there is no operation of any fault detectors , VT circuit
failure alarm will be issued with a time delay of 10s. The abnormality alarm will be reset with a time
delay of 10s if the VT circuit returns to normal condition.
1) Positive sequence voltage is less than 18V and any phase current is larger than 0.04 In.
2) The three times of negative sequence voltage (3U2) is larger than 8V.
If following two criteria are all met, VT neutral line failure alarm will be issued with a time delay of
20s. The abnormality alarm will be reset with a time delay of 20s if the VT neutral line returns to
normal condition. VT neutral line failure supervision function can be enabled or disabled
independently.
Date: 2015-07-29
3 Operation Theory
2) The third harmonic of calculated residual voltage (3U0_3ω) is larger than K*U1.
K is the VT neutral line failure judge coefficient [Y.K_VTNS], it takes 0.2~0.5 generally.
3.24.4 Logic
SIG 3U2>8V
≥1
10s 10s
SIG U1<18V & [Y.Alm_VTS]
SIG [Y.Flg_OnLoad]
EN Y.En_VTNS
&
20s 20s
SIG U1>48V & [Y.Alm_VTNS]
SIG 3U0_3ω>[Y.K_VTNS]*U1
Where:
U2 and U1 are negative sequence voltage value and positive sequence voltage value respectively.
Volt3P
Y.ua Y.Alm_VTS
Y.ub Y.Alm_VTNS
Y.uc Y.U3P
Y.Flg_OnLoad Y.Ua
Y.Ub
Y.Uc
Y.U_Avg
Date: 2015-07-29
3 Operation Theory
Alarm signals
1 Tr_HVS.Ua
7 Tr_HVS.Uab
Phase-to-phase voltage amplitude of the VT of H V side of main
8 Tr_HVS.Ubc
transformer
9 Tr_HVS.Uca
10 Tr_MVS.Ua
12 Tr_MVS.Uc
Date: 2015-07-29
3 Operation Theory
16 Tr_MVS.Uab
Phase-to-phase voltage amplitude of the VT of MV side of main
17 Tr_MVS.Ubc
transformer
18 Tr_MVS.Uca
19 Tr_LVS.Ua
21 Tr_LVS.Uc
25 Tr_LVS.Uab
Phase-to-phase voltage amplitude of the VT of LV side of main
26 Tr_LVS.Ubc
transformer
27 Tr_LVS.Uca
Access path:
Main menu -> Measurements -> Measurements1-> Tr Values-> Tr Volt Values
Main menu -> Measurements -> Measurements2-> Tr Values-> Tr Volt Values
Access path:
Date: 2015-07-29
3 Operation Theory
Main menu -> Measurements -> Measurements2-> Phase Angle-> Tr PhaseAngle Values
3.24.6 Settings
NOTICE!
In Section 3.25, the prefix “Y” in input/output signals (such as [Y.I1P]) can be Tr_HVS,
and Tr_MVS. Details of the prefix are as:
3.25.1 Application
Residual current element is responsible for pre-processing measured residual current and
calculating the amplitude and the phase angle of residual current, etc. All calculated information of
residual current element is for the protection logic calculation.
Date: 2015-07-29
3 Operation Theory
Curr1P
Y.3i0 Y.I1P
Y.3I0_Ext
Access path:
Main menu -> Measurements -> Measurements1-> Tr Values-> Tr Curr Values
Main menu -> Measurements -> Measurements2->Tr Values-> Tr Curr Values
3.25.4 Settings
NOTICE!
In Section 3.26, the prefix “Y” in input/output signals (such as [Y.U1P]) can be Tr_HVS,
Tr_MVS and Tr_LVS. Details of the prefix are as:
Date: 2015-07-29
3 Operation Theory
3.26.1 Application
Residual voltage element is responsible for pre-processing residual voltage and calculating the
amplitude of residual voltage, etc. All calculated information of residual voltage element is for the
protection logic calculation
Volt1P
Y.3u0 Y.U1P
Y.3U0_Ext
Access path:
Main menu -> Measurements -> Measurements1-> Tr Values-> Tr Volt Values
Main menu -> Measurements -> Measurements2-> Tr Values-> Tr Volt Values
3.26.4 Settings
Date: 2015-07-29
3 Operation Theory
Date: 2015-07-29
3 Operation Theory
Date: 2015-07-29
4 Supervi sion
4 Supervision
Table of Contents
4 Supervision.......................................................................................... 4-a
4.1 Overview........................................................................................................................ 4-1
List of Tables
Table 4.2-1 Alarm description ................................................................................................ 4-1
Date: 2015-07-29
4 Supervi sion
Date: 2015-07-29
4 Supervi sion
4.1 Overview
Protection system is in quiescent state under normal conditions, and it is required to respond
promptly for faults occurred on power system. When the device is in energizing process before the
LED “HEALTHY” is on, the device need to be checked to ensure no abnormality. Therefore, the
automatic supervision function, which checks the health of the protection system when startup and
during normal operation, plays an important role.
The numerical relay based on the microprocessor operations is suitable for implementing this
automatic supervision function of the protection system.
In case a defect is detected during initialization when DC power supply is provided to the device,
the device will be blocked with indication and alarm of relay out of service. It is suggested a trial
recovery of the device by re-energization. Please contact supplier if the device is still failure.
When a failure is detected by the automatic supervision, it is followed by a LCD message, LED
indication and alarm contact outputs. The failure alarm is also recorded in event recording report
and can be printed If required.
If the protective device is blocked or alarm signal is sent during operation, please try to
find out its reason with the help of self-diagnostic record. If the failure reason can not be
found at site, please inform the manufacturer NR or the agent for maintenance. Please
DO NOT simply press button “TARGET RESET” on the protection panel or re-energize
on the device.
Hardware circuit and operation status of the device are self-supervised continuously. If any
abnormal condition is detected, information or report will be displayed and a corresponding alarm
will be issued.
A minor abnormality may block a certain number of protections functions while the other functions
can still work. However, if severe hardware failure or abnormality, such as PWR module failure,
DC converter failure and so on, are detected, all protection functions will be blocked and the LED
“HEALTHY” will be extinguished and blocking output contacts BO_FAIL will be given. The
protective device then can not work normally and maintenance is required to eliminate the failure.
All the alarm signals and the corresponding handling suggestions are listed below.
Blocking
No. Item Description
Device
Fail Signals
The device fails.
1 Fail_Device This signal will be pick up if any fail signal picks up and it will Blocked
drop off when all fail signals drop off.
Date: 2015-07-29
4 Supervi sion
Blocking
No. Item Description
Device
Set value of any setting is out of scope.
2 Fail_Setting_OvRange This signal will pick up instantaneously and will be latched Blocked
unless the recommended handling suggestion is adopted.
Mismatch between the configuration of plug-in modules and
3 Fail_BoardConfig Blocked
the designing drawing of an applied-specific project.
After config file is updated, settings of the file and settings
saved on the device are not matched.
4 Fail_SettingItem_Chgd Blocked
This signal will pick up instantaneously and will be latched
unless the recommended handling suggestion is adopted.
Error is found during checking memory data (fault detector
DSP module).
5 FDBrd.Fail_Memory Blocked
This signal will pick up instantaneously and will be latched
unless the recommended handling suggestion is adopted.
Error is found during checking settings (fault detector DSP
module).
6 FDBrd.Fail_Settings Blocked
This signal will pick up instantaneously and will be latched
unless the recommended handling suggestion is adopted.
DSP chip is damaged (fault detector DSP module).
7 FDBrd.Fail_DSP This signal will pick up instantaneously and will be latched Blocked
unless the recommended handling suggestion is adopted.
AC current and voltage samplings are abnormal (fault detector
DSP module).
8 FDBrd.Fail_Sample This signal will pick up with a time delay of 50ms and will be Blocked
latched unless the recommended handling suggestion is
adopted.
Error is found during checking memory data (protection DSP
module).
9 ProtBrd.Fail_Memory Blocked
This signal will pick up instantaneously and will be latched
unless the recommended handling suggestion is adopted.
Error is found during checking settings (protection DSP
module).
10 ProtBrd.Fail_Settings Blocked
This signal will pick up instantaneously and will be latched
unless the recommended handling suggestion is adopted.
DSP chip is damaged (protection DSP module).
11 ProtBrd.Fail_DSP This signal will pick up instantaneously and will be latched Blocked
unless the recommended handling suggestion is adopted.
AC current and voltage samplings are abnormal (protection
DSP module).
12 ProtBrd.Fail_Sample This signal will pick up with a time delay of 50ms and will be Blocked
latched unless the recommended handling suggestion is
adopted.
13 FDBrd.Fail_HTM The HTM bus for data exchange is abnormal (fault detector Blocked
Date: 2015-07-29
4 Supervi sion
Blocking
No. Item Description
Device
DSP module).
The HTM bus for data exchange is blocked for a long time
14 ProtBrd.Fail_HTM Blocked
(protection DSP module).
The alarm indicating that the tripping output module located in
15 Bx.Fail_Board Blocked
slot No.x (x=12~15) is in abnormal status.
The alarm indicating that the output contactor of the tripping
16 Bx.Fail_Output output module located in slot No.x (x=12~15) is in abnormal Blocked
status.
Alarm Signals
The device is abnormal.
17 Alm_Device This signal will be pick up if any alarm signal picks up and it Unblocked
will drop off when all alarm signals drop off.
18 Alm_Insuf_Memory The memory of MON plug-in module is insufficient. Unblocked
The device is in the communication test mode.
19 Alm_CommTest This signal will pick up instantaneously and will drop off Unblocked
instantaneously.
The error is found during MON module checking settings of
device.
20 Alm_Settings_MON Unblocked
This signal will pick up with a time delay of 10s and will be
latched unless re-powering or rebooting the device.
The error is found during checking the version of software
downloaded to the device.
21 Alm_Version Unblocked
This signal will pick up instantaneously and will drop off
instantaneously.
The active group set by settings in device and that set by
binary input are not matched.
22 Alm_BI_SettingGrp Unblocked
This signal will pick up instantaneously and will drop off
instantaneously.
23 Alm_TimeSyn Time synchronization abnormality alarm. Unblocked
The alarm is to indicate that the IEC103 file in the devi ce is
24 Alm_CfgFile_IEC103 Unblocked
invalid.
The alarm is to indicate that the device is in testing mode for
25 Alm_TestMode Unblocked
signal/trip output.
The alarm is to indicate that the board at slot x (x=10,11) is in
26 Bx.Alm_Board Unblocked
abnormal status.
The power supply of BI plug-in module in slot 04 is abnormal.
27 B10.Alm_OptoDC This signal will pick up with a time delay of 10s and will drop off Unblocked
with a time delay of 10s.
The device is in the GOOSE test mode.
28 Alm_GOOSETest This signal will pick up instantaneously and will drop off Unblocked
instantaneously.
Date: 2015-07-29
4 Supervi sion
Blocking
No. Item Description
Device
The “master” process is alarm.
29 Alm_master This signal will pick up instantaneously and will drop off Unblocked
instantaneously.
Current fault detector element operates for longer than 10s
(fault detector DSP module).
30 FDBrd.Alm_Pkp Unblocked
This signal will pick up with a time delay of 10s and will drop off
with a time delay of 10s.
Current fault detector element operates for longer than 10s
(protection DSP module).
31 ProtBrd.Alm_Pkp Unblocked
This signal will pick up with a time delay of 10s and will drop off
with a time delay of 10s .
Protection Element Alarm Signals
Main transformer HV side 1 CT secondary circuit abnormality
32 Tr_HVS1.AlmL_CTS Unblocked
alarm.
Main transformer HV side 2 CT secondary circuit abnormality
33 Tr_HVS2.AlmL_CTS Unblocked
alarm.
Main transformer MV side CT secondary circuit abnormality
34 Tr_MVS.AlmL_CTS Unblocked
alarm.
Main transformer LV side CT secondary circuit abnormality
35 Tr_LVS.AlmL_CTS Unblocked
alarm.
Step-down transformer HV side big-ratio CT secondary circuit
36 ST_HVS#.AlmL_CTS Unblocked
abnormality alarm.
37 Tr_HVS.Alm_VTS Main transformer HV side VT secondary circuit failure alarm. Unblocked
38 Tr_MVS.Alm_VTS Main transformer MV side VT secondary circuit failure alarm. Unblocked
39 Tr_LVS.Alm_VTS Main transformer LV side VT secondary circuit failure alarm. Unblocked
40 Tr_HVS.Alm_VTNS Main transformer HV side VT neutral line failure alarm. Unblocked
41 Tr_MVS.Alm_VTNS Main transformer MV side VT neutral line failure alarm. Unblocked
42 Tr_LVS.Alm_VTNS Main transformer LV side VT neutral line failure alarm. Unblocked
43 Alm_52_CB1 Circuit breaker 1 auxiliary contact abnormality alarm. Unblocked
44 Alm_52_CB2 Circuit breaker 2 auxiliary contact abnormality alarm. Unblocked
45 Alm_52_CB3 Circuit breaker 3 auxiliary contact abnormality alarm. Unblocked
46 Alm_52_CB4 Circuit breaker 4 auxiliary contact abnormality alarm. Unblocked
Alarm message indicating CT secondary circuit of main
47 Tr.87T.Alm_Diff Unblocked
transformer differential protection is abnormal.
Alarm message indicating that CT secondary circuit of main
48 Tr.87T.Alm_CTS Unblocked
transformer differential protection fails.
Alarm message indicating residual differential current of HV
49 Tr_HVS.64REF.Alm_Diff Unblocked
side of main transformer is abnormal.
Alarm message indicating residual differential current of MV
50 Tr_MVS.64REF.Alm_Diff Unblocked
side of main transformer is abnormal.
51 24.Alm The alarm stage of overe xcitation protection operates to issue Unblocked
Date: 2015-07-29
4 Supervi sion
Blocking
No. Item Description
Device
alarm signal
Stage 1 of underfrequency protection operates to issue alarm
52 81U.UF1.Alm Unblocked
signal.
Stage 2 of underfrequency protection operates to issue alarm
53 81U.UF2.Alm Unblocked
signal.
Stage 3 of underfrequency protection operates to issue alarm
54 81U.UF3.Alm Unblocked
signal.
Stage 4 of underfrequency protection operates to issue alarm
55 81U.UF4.Alm Unblocked
signal.
Stage 1 of underfrequency band accumulate protection
56 81U.UF1.Alm_Accu Unblocked
operates to issue alarm signal.
Stage 2 of underfrequency band accumulate protection
57 81U.UF2.Alm_Accu Unblocked
operates to issue alarm signal.
Stage 3 of underfrequency band accumulate protection
58 81U.UF3.Alm_Accu Unblocked
operates to issue alarm signal.
Stage 4 of underfrequency band accumulate protection
59 81U.UF4.Alm_Accu Unblocked
operates to issue alarm signal.
Stage 1 of overfrequency protection operates to issue alarm
60 81O.OF1.Alm Unblocked
signal.
Stage 2 of overfrequency protection operates to issue alarm
61 81O.OF2.Alm Unblocked
signal.
Stage 3 of overfrequency protection operates to issue alarm
62 81O.OF3.Alm Unblocked
signal.
Stage 4 of overfrequency protection operates to issue alarm
63 81O.OF4.Alm Unblocked
signal.
Stage 1 of overfrequency band accumulate protection
64 81O.OF1.Alm_Accu Unblocked
operates to issue alarm signal.
Stage 2 of overfrequency band accumulate protection
65 81O.OF2.Alm_Accu Unblocked
operates to issue alarm signal.
Stage 3 of overfrequency band accumulate protection
66 81O.OF3.Alm_Accu Unblocked
operates to issue alarm signal.
Stage 4 of overfrequency band accumulate protection
67 81O.OF4.Alm_Accu Unblocked
operates to issue alarm signal.
Stage 1 of rate-of-frequency-change protection operates to
68 81R.RF1.Alm Unblocked
alarm.
Stage 2 of rate-of-frequency-change protection operates to
69 81R.RF2.Alm Unblocked
alarm.
Stage 3 of rate-of-frequency-change protection operates to
70 81R.RF3.Alm Unblocked
alarm.
Stage 4 of rate-of-frequency-change protection operates to
71 81R.RF4.Alm Unblocked
alarm.
Date: 2015-07-29
4 Supervi sion
Blocking
No. Item Description
Device
Main transformer HV side pole disagreement position contact
72 Tr_HVS.62PD.Alm Unblocked
abnormality alarm
Main transformer HV side breaker flashover protection circuit
73 Tr_HVS.50F.Alm Unblocked
breaker contact abnormality alarm.
Stage 1 of phase overcurrent element of main transformer HV
74 Tr_HVS.51PAlm1.Alm Unblocked
side operates to issue alarm signal.
Stage 2 of phase overcurrent element of main transformer HV
75 Tr_HVS.51PAlm2.Alm Unblocked
side operates to issue alarm signal.
Stage 3 of phase overcurrent element of main transformer HV
76 Tr_HVS.51PAlm3.Alm Unblocked
side operates to issue alarm signal.
Thermal overload protection of main transformer HV side
77 Tr_HVS.49.Alm Unblocked
operates to alarm.
Phase overvoltage protection alarm stage of main transformer
78 Tr_HVS.59PAlm.Alm Unblocked
HV side operates to issue alarm signal.
Residual overvoltage protection alarm stage of main
79 Tr_HVS.59GAlm.Alm Unblocked
transformer HV side operates to issue alarm signal.
Phase undervoltage protection alarm stage of main
80 Tr_HVS.27PAlm.Alm Unblocked
transformer HV side operates to issue alarm signal.
Main transformer MV side pole disagreement position contact
81 Tr_MVS.62PD.Alm Unblocked
abnormality alarm
Main transformer MV side breaker flashover protection circuit
82 Tr_MVS.50F.Alm Unblocked
breaker contact abnormality alarm.
Stage 1 of phase overcurrent element of main transformer MV
83 Tr_MVS.51PAlm1.Alm Unblocked
side operates to issue alarm signal.
Stage 2 of phase overcurrent element of main transformer MV
84 Tr_MVS.51PAlm2.Alm Unblocked
side operates to issue alarm signal.
Stage 3 of phase overcurrent element of main transformer MV
85 Tr_MVS.51PAlm3.Alm Unblocked
side operates to issue alarm signal.
Thermal overload protection of main transformer MV side
86 Tr_MVS.49.Alm Unblocked
operates to alarm.
Phase overvoltage protection alarm stage of main transformer
87 Tr_MVS.59PAlm.Alm Unblocked
MV side operates to issue alarm signal.
Residual overvoltage protection alarm stage of main
88 Tr_MVS.59GAlm.Alm Unblocked
transformer MV side operates to issue alarm signal.
Phase undervoltage protection alarm stage of main
89 Tr_MVS.27PAlm.Alm Unblocked
transformer MV side operates to issue alarm signal.
Residual overvoltage protection alarm stage of main
90 Tr_LVS.59GAlm.Alm Unblocked
transformer LV side operates to issue alarm signal.
91 MR1.Sig1 Output alarm signal of channel 1 of mechanical protection 1. Unblocked
92 MR1.Sig2 Output alarm signal of channel 2 of mechanical protection 1. Unblocked
93 MR1.Sig3 Output alarm signal of channel 3 of mechanical protection 1. Unblocked
Date: 2015-07-29
4 Supervi sion
Blocking
No. Item Description
Device
94 MR1.Sig4 Output alarm signal of channel 4 of mechanical protection 1. Unblocked
95 MR1.Alm_PwrLoss Power supervision alarm signal of mechanical protection 1. Unblocked
Date: 2015-07-29
4 Supervi sion
2. check whether the wiring connection between the device and the clock
synchronization source is correct
23 Alm_TimeSyn 3. check whether the setting for selecting clock synchronization (i.e.
[Opt_TimeSyn]) is set correctly. If there is no clock synchronization, please
set the setting [Opt_TimeSyn] as ”No TimeSync”.
Date: 2015-07-29
4 Supervi sion
Date: 2015-07-29
4 Supervi sion
If any fault detector picks up to trigger oscillography function, the corresponding binary input
changing report will be recorded in “IO_Events” menu with tripping report [TrigDFR] being issued.
If a fault detector on protection or fault detector DSP module keeps picking up for 10s, the
corresponding alarm signal [ProtBrd.Alm_Pkp] or [FDBrd.Alm_Pkp] will be issued without the
device being blocked.
Date: 2015-07-29
4 Supervi sion
This relay has 10 setting groups, only one setting group could be activiated (is active) at a time.
The settings of active setting group are checked to ensure they are reasonable. If settings are
checked to be unreasonable or out of setting scopes, a corresponding alarm signal will be issued,
and the device is also blocked.
Data in non-volatile memory, which are not changed after device energized, are always checked
during device normal operation, such as settings, pointers, etc. If these data changed abnormally,
the corresponding alarm [ProtBrd.Fail_Memory] or [FDBrd.Fail_Memory] will be issued.
Positive power supply of opto-coupler on each BI module that located in slot No.x (No.x is the slot
number) is continuously monitored, and if a failure or damage on the module is detected, then the
alarm signal [Bx.Alm_OptoDC] will be issued.
State of binary outputs on each BO module that located in slot No.x (No.x is the slot number) is
continuously monitored. If any abnormality is detected on the module, the corresponding alarm
signal [Bx.Alm_Output] will be issued with equipment being blocked.
When protection equipment is in communication test mode the alarm signal [Alm_CommTest] is
issued without blocking equipment.
Date: 2015-07-29
4 Supervi sion
Date: 2015-07-29
5 Management
5 Management
Table of Contents
Date: 2015-07-29
5 Management
Date: 2015-07-29
5 Management
5.1 Overview
The relay also provides some auxiliary functions, such as on-line data metering, binary input
status, event and disturbance recording. All these functions make the relay meet the demands of
the modern power grid requirements.
5.2 Measurement
The device can continuously display the measured analogue input quantities, some internal flags
and calculated value based on the analogue input quantities can also be displayed. The
measurement data are displayed on the LCD of the relay front panel or by the software interface
on the local or remote PC. The analog quantities will be displayed as RMS values of the
secondary side of CT and VT.
The device samples 24 points per cycle. The RMS value is calculated in each interval and the LCD
display will be updated in every 0.5 second.
Users can view the measured data on LCD by navigating the menu “Measurements”, or by
PCS-Explorer software or substation automatic system (SAS) software.
The device has two DSP modules that are protection DSP module and fault detector DSP module,
the displayed values of the menu “Measurements->Measurement1” corresponds to the
measurement data of protection DSP module, and the displayed values of the menu
“Measurements->Measurement2” corresponds to the measurement data of fault detector DSP
module.
Please refer to the output signal list (for measurements) of Section “Inputs and Outputs” of each
protection element in Chapter 3 for detailed description and the concrete access path of each
measurement data. For a certain application, some measurement data listed in Chapter 3 may be
eliminated due to the scheme user required, so please look up the device on site for actual
displayed measurement data.
5.3.1 Introduction
Event recording
Present recording
All the recorded information except for waveform can be viewed on local LCD or by printing.
Waveform must be printed or be extracted using PCS-Explorer software and a waveform software.
Date: 2015-07-29
5 Management
The device can store up to 1024 abnormality alarm reports and 1024 binary input status changing
reports respectively. All the records are stored in non-volatile memory, and when the available
space is fully occupied, the oldest report is automatically overwritten by the latest one.
When binary input status changes, the changed information will be displayed on LCD and logged
as binary input change report at the same time.
5.3.3.1 Application
Users can use the disturbance recorder to achieve a better understanding of the behavior of the
power network and related primary and secondary device during and after a disturbance.
Analyzing on the recorded data can help to resolve practical problem.
5.3.3.2 Design
Disturbance recorder is consisted of tripping report and fault waveform and it is triggered by fault
detector. The device can store 64 pieces of trip reports and waveforms in non-volatile memory.
When protection operates, the operating information will be displayed on LCD and logged as trip
record at same time, which can be viewed in trip report. Here fault recording includes two kinds of
cases:
2) The fault detector element operates along with the operation of protective elements.
The device can store 64 pieces of trip reports in non-volatile memory. If a new fault occurs when
the spaces are fully occupied, the oldest will be overwritten by the latest one.
1) Sequence number
Each operation will be recorded with a sequence number in the report and displayed on LCD
screen.
The time resolution is 1 ms using the relay internal clock. Initiating date and time is when a fault
detector picks up. The relative time is the time when protection element operates to send tripping
signal after fault detector picks up.
Date: 2015-07-29
5 Management
3) Operating time
It is the relative time when protection element operates to send tripping signal relative to fault
detector element operating, the operating time of output relay is not included.
4) Protection element
The protection element that issues the tripping command will be shown. If no protection element
operates to trip but only fault detector element operates, the fault report will record the title of fault
detector element.
MON module of the relay can store 64 pieces of fault waveform in non-volatile memory. If a new
fault occurs when 64 fault waveform recorders have been stored, the oldest will be overwritten by
the latest one.
Each fault record consists of all analog and digital quantities related to protection, such as original
current and voltage, differential current, alarm elements, and binary inputs and etc.
Each time recording includes several-cycle pre-disturbance waveform (the waveform cycle
number before triggering is configured via the communication setting
[Num_Cyc_PreTrigDFR], the default value is 3-cycle) and 8-cycle after-disturbance
waveform.
2) The fault detector element operates along with the operation of protective element.
Each time recording includes several-cycle pre-fault waveform (the waveform cycle number
is configured via the communication setting [Num_Cyc_PreTrigDFR], the default value is
3-cycle), 8-cycle after-fault waveform, several-cycle pre-tripping waveform (the waveform
cycle number is configured via the communication setting [Num_Cyc_PreTrigDFR], the
default value is 3-cycle), 8-cycle after-tripping waveform and all the current and voltage
waveform with disturbance between the fault detector element and the protective element.
Present recording is used to record the waveform of present operating device which can be
triggered manually on LCD of device or remotely through PCS-Explorer software. Recording
content of present recording is same to that of disturbance recording. Each time recording
includes several-cycle pre-disturbance waveform (the waveform cycle number is configured via
the communication setting [Num_Cyc_PreTrigDFR], the default value is 3-cycle) and 8-cycle
after-disturbance waveform.
Date: 2015-07-29
5 Management
Date: 2015-07-29
6 Hardware Description
6 Hardware Description
Table of Contents
6.4.8 Mechanical Signal Input and Output Module (MR module) ............................................. 6-21
List of Figures
Figure 6.1-3 Typical rear view of the device (typical) ........................................................... 6-3
Figure 6.4-1 The module arrangement of PCS-985TE from rear view (typical) ................... 6-6
Date: 2015-07-29
6 Hardware Description
Figure 6.4-11 Pin definition of signal output module NR1523A ......................................... 6-18
Figure 6.4-12 Pin definition of signal output module NR1523B ......................................... 6-19
Figure 6.4-13 Pin definition of signal output module NR1523C ......................................... 6-20
Figure 6.4-14 Pin definition of signal output module NR1523D ......................................... 6-21
Figure 6.4-15 Pin definition of mechanical relay IO module (x=1, 2) ................................. 6-22
List of Tables
Table 6.4-1 Terminal definition and description of PWR plug-in module ............................ 6-7
Date: 2015-07-29
6 Hardware Description
6.1 Overview
Output Relay
Binary Input
External
Protection
CT/VT A/D Calculation
DSP
Fault
A/D Detector Pickup
DSP Relay
ETHERNET
LCD +E
Clock SYN
Power
Uaux LED CPU
Supply
RJ45
Keypad
PRINT
The device adopts 32-bit microchip processor CPU as control core for management and
monitoring function, meanwhile, adopts high-speed digital signal processor DSP to be in charge of
all the protection calculation. 24 points are sampled in every cycle and parallel processing of
sampled data can be realized in each sampling interval to ensure ultra-high reliability and safety of
protection equipment.
The working process of the device is as follows: firstly, the current and voltage is converted into
small voltage signal and sent to DSP module after being filtered and converted by AD for
protection calculation and fault detector respectively. When DSP module completes all the
protection calculation, the result will be sent to 32-bit CPU on MON module to be recorded.
Protection DSP module carries out protection logic calculation, tripping output, and MON module
completes SOE (sequence of event) record, waveform recording, printing, communication
between protection and SAS and communication between HMI and CPU. The work process of
fault detector DSP module is similar to that of protection DSP module, and the only difference is,
when fault detector DSP module decides a fault detector picks up, only positive power supply of
output relay will be switched on.
The device is comprised of intelligent modules, except that few particular modules’ position cannot
be changed in the whole device (please refer to Figure 6.4-1 for details), the others like AI (analog
input) module such as AC current, AC voltage, DC current, and etc., and IO (input and output)
module such as binary input, tripping output, signal output, and etc can be flexibly configured
according to the remained slot positions.
Date: 2015-07-29
6 Hardware Description
MON module provides functions like management function, completed event record, setting
management, and etc.
DSP modules can carry out filtering, sampling, protection calculation and fault detector
calculation.
AI module converts AC current and voltage to low voltage signals with current transfo rmers
and voltage transformers respectively.
BI module provides binary inputs via opto-couplers with rating voltage among
110V/125V/220V/250V (configurable)
MR module provides signal inputs and outputs for the mechanical protection.
BO module provides all kinds of binary output contacts, including signal output contacts and
tripping output contacts.
PWR module converts DC 250/220/125/110V into different DC voltage levels for various
modules of the device.
HMI module is comprised of LCD, keypad, LED indicator and multiplex RJ45 ports for user as
human-machine interface.
Following figures show front and rear views of the device respectively. Programmable LED
indicators (No.4-No.20) can be defined by user through PCS-Explore software.
Date: 2015-07-29
6 Hardware Description
1 11
HEALTHY
2 12 PCS-985
ALARM
3
TRIP
13
TRANSFORMER RELAY
4 14
5 15
C GRP
6 16
7 17 ENT
ES
8 18
9 19
10 20
Slot No. 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 P1
NR1101D NR1156D NR1156D NR1401 NR1401 NR1401 NR1504A NR1536A NR1521A NR1523A NR1523A NR1523C NR1301A
5V BJ
1 2 3 1 2 3
4 5 6 4 5 6 BJJ BSJ
ON
OFF
2 BO_FAIL
3 BO_ALM
4 BO_COM2
5 BO_FAIL
6 BO_ALM
7 OPTO+
8 OPTO-
10 PWR+
11 PWR-
12 GND
Date: 2015-07-29
6 Hardware Description
Channel 7
Ia
Three-phase current
Voltage
BI_TimeSyn 0801
1002 + U
input channel 5
0602 Ian 0802
0603 Un
1003 + BI_Print Ib
0604 Ibn
Channel 8
BI_Maintenance
Voltage
1004 + 0605 0803
Ic U
AI module 1 (NR1401) 0804
BI_RstTarg 0606 Icn Un
1005 +
0401 Ia
Three-phase current
BI_05 0607
input channel 1
Channel 9
1006 + 0402
Three-phase current
Ian Ia
Voltage
0805
input channel 6
0403 0608 U
BI_06 Ib Ian 0806
1007 + Un
0404 0609 Ib
Ibn
1008 0405 0610 Ibn
Not used Ic
Channel
Voltage
0611 0807
0406 Icn Ic U
10
1009 + BI_07 0808
0612 Icn Un
BI module (NR1504)
0407
Three-phase current
1010 + BI_08 Ia
Channel 1
input channel 2
Voltage
0408 0613
Channel
Voltage
Ian U 0809
BI_09 U
11
1011 + 0409 0614
Ib Un 0810 Un
0410
1012 + BI_10 Ibn
Channel 2
0411
Voltage
Ic 0615
Channel
Voltage
BI_11 U 0811
1013 + 0412 U
12
Icn 0616
Un 0812 Un
1014 + BI_12
0413 Ia
Channel 3
Three-phase current
Voltage
0617
input channel 3
Channel
Voltage
1015 + Not used 0414 Ian U 0813
U
13
0618 Un
1016 + BI_13 0415 Ib 0814
Un
0416 Ibn
Channel 4
BI_14
Voltage
1017 + 0417 0619
Channel
Ic
Voltage
U 0815
U
14
0418 Icn 0620
1018 + BI_15 Un 0816
Un
BI_16
Channel 5
1019 +
Voltage
0419 0621
Three-phase current
Channel
Ia U
Voltage
0817
U
input channel 4
15
BI_17 0420 Ian 0622 Un
1020 + 0818 Un
0421 Ib
1021 + BI_18
Channel 6
0422
Voltage
Ibn 0623
Channel
Voltage
U 0819
0423 U
16
1022 - COM- Ic 0624 Un 0820
0424 Un
Icn
Channel
Voltage
0821 U
17
MR IO Module (NR1536A) 0822 Un
Channel
Voltage
0823
1201 1102 MR1.Input1 U
18
BO_Trip_1-1 0824
High Voltage
1202 Un
1103 MR1.Input2
Binary Input Signals of
1203 Mechanical protection
1104 MR1.Input3
1204 BO_Trip_1-2
1105 MR1.Input4
1205
1206 BO_Trip_1-3 1106 BO_MR1.Sig1_1
P110 PWR+
1207 1107 BO_MR1.Sig2_1
Power External DC power
1208 BO_Trip_1-4 1108 BO_MR1.Sig3_1
Supply P111 supply
PWR-
BO module 2 for tripping (NR1521A)
1111 BO_MR1.Sig1_2
1212 BO_Trip_2-2 P102
BO_FAIL
1112 BO_MR1.Sig2_2
1213 BO_ALM P103
1121 Pwr+
Module Power Input
1122 Pwr - Multiplex
RJ45 (Front)
Ethernet C
BO_Signal_2-2 BO_Signal_10-2 BO_Signal_18-2 Ethernet to
1308 1408 1508
MON module (NR1101)
SCADA
Ethernet D
1309 1409 1509
BO_Signal_3-1 BO_Signal_11-1 BO_Signal_19-1
COM(optional)
1515
BO_Signal_5 BO_Signal_13 BO_Signal_21 0102 SYN-
1316 1416 1516
0103 SGND
1317 1417 1517
BO_Signal_6 BO_Signal_14 BO_Signal_22 0104
1318 1418 1518
1319 1419 1519 0105 RTS
PRINT
Date: 2015-07-29
6 Hardware Description
6.3 CT Requirement
-Rated short-time thermal current Ith and rated dynamic current Idyn:
Performance verification
Date: 2015-07-29
6 Hardware Description
For example:
= 30×5×(1+60/25)=510V
Esl′ = 2×Ipcf×Isn×(Rct+Rb)/Ipn
= 2×Ipcf ×Isn×(Rct+(Rr+2×RL+Rc))/Ipn
= 2×40000×5×(1+(0.1+2×0.5+0.1))/2000=440V
The device consists of PWR plug-in module, MON plug-in module, DSP plug-in module, AI plug-in
module, BI plug-in module, BO plug-in module etc. Terminal definitions and application of each
plug-in module are introduced as follows.
Terminal definitions are represents with its slot position and pin number. For example, contact
1301-1302 means terminal 01-02 of the module located in slot 13, i.e. 13 represents the slot
position, 01 (02) represents the pin number on the module.
The module arrangement of the device from rear view is shown in the following figure.
NR1101D NR1156D NR1156D NR1401 NR1401 NR1401 NR1504A NR1536A NR1521A NR1523A NR1523A NR1523C NR1301A
BO module 1 for tripping
AC AI module 2
AC AI module 3
DSP module 1
DSP module 2
MON module
PWR module
MR module
BI module
Slot No.
01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 P1
Figure 6.4-1 The module arrangement of PCS-985TE from rear view (typical)
Date: 2015-07-29
6 Hardware Description
PWR module is a DC/DC converter with electrical insulation between input and output. It has an
input voltage range as described in Chapter 2. The standardized output voltages are +5V and
+24V DC. The tolerances of the output voltages are continuously mo nitored.
The +5V DC output provides power supply for all the electrical elements that need +5V DC power
supply in this device. The +24V DC output provides power supply for the static relays of this
device.
The use of an external miniature circuit breaker is recommended. The miniature circuit breaker
must be in the on position when the device is in operation and in the off position when the device is
in cold reserve.
A 12-pin connector is fixed on PWR module. The terminal definition of the connector is described
as below.
NR1301
5V OK ALM
BO_ALM BO_FAIL
1 BO_COM1 P101
BO_FAIL
2 BO_FAIL P102
BO_ALM
3 BO_ALM P103
4 BO_COM2 P104
BO_FAIL
5 BO_FAIL P105
BO_ALM
6 BO_ALM P106
7 OPTO+
8 OPTO-
9
10 PWR+
11 PWR-
12 GND
Date: 2015-07-29
6 Hardware Description
The standard rated voltage of PWR module is self-adaptive to 88~300Vdc. If the input voltage is
out of the range, an alarm signal (Fail_Device) will be issued. For non-standard rated voltage
power supply module please specify when place order, and check whether the rated voltage of
power supply module is the same as the voltage of power source before the device being put into
service.
PWR module provides terminal 12 and grounding screw for device grounding. Terminal 12 shall be
connected to grounding screw and then connected to the earth copper bar of panel via dedicated
grounding wire.
Effective grounding is the most important measure for a device to prevent EMI, so effective
grounding must be ensured before the device is put into service.
Like almost all electronic relays, the device contains electrolytic capacitors. These capacitors are
well known to be subject to deterioration over time if voltage is not applied periodically.
Deterioration can be avoided by powering the relays up once a year.
CAUTION!
Do NOT look into the end of an optical fiber connected to an optical port.
MON module consists of high-performance built-in processor, FLASH, SRAM, SDRAM, Ethernet
controller and other peripherals. Its functions include management of the complete device, human
machine interface, communication and waveform recording etc.
MON module uses the internal bus to receive the data from other modules of the device. It
communicates with the LCD module by RS-485 bus. This module comprises 100BaseT Ethernet
interfaces, RS-485 communication interfaces, PPS/IRIG-B differential time synchronization
interface and RS-232 printing interface.
Date: 2015-07-29
6 Hardware Description
Modules with various combinations of memory and interface are available as shown in the table
below.
TX TX
ETHERNET ETHERNET
RX RX
TX TX
RX RX
ETHERNET
TX
RX
Date: 2015-07-29
6 Hardware Description
02 SYN- synchronization
03 SGND
04
05 RTS
RS-232 06 TXD To printer Cable
07 SGND
2 RJ45 Ethernet To SCADA
01 A
02 B
RS-485 To SCADA
03 SGND
04
05 A
06 B Twisted pair wire
RS-485 To SCADA
07 SGND
NR1101D 256M DDR 08
09 SYN+
10 SYN- To clock
RS-485
11 SGND synchronization
12
13 RTS
RS-232 14 TXD To printer Cable
15 SGND
16
The correct method of connection is shown in Figure 6.4-4. Generally, the shielded cables with two
pairs of twisted pairs inside shall be applied. One pair of the twisted pairs is used to connect the “+”
and “–” terminals of difference signal; the other is used to connect the signal ground of the
interface, i.e. connect the signal groundings of all the devices to a bus through the twisted pair.
The module reserves a free terminal for all the communication ports; the free terminal does not
need to be connected.
Date: 2015-07-29
6 Hardware Description
B 02
COM
cable with single point earthing
To the screen of other coaxial
SGND 03
04
CLOCK SYN
SYN- 02
SGND 03
04
PRINT
TXD 06
SGND 07
The DSP Module 2 consists of high-performance digital signal processor and other peripherals.
The functions of this module include analog data acquisition, calculation of fault detector elements
and providing positive power supply to output relay.
DSP module 1 and DSP module 2 have the same hardware configuration and are located in slot
02 and slot 03 respectively. The following figure shows rear view and terminal definition for the
DSP module.
Date: 2015-07-29
6 Hardware Description
NR1156D
1 2 3
4 5 6
There are two kinds of BI modules available, NR1503 and NR1504. Up to 2 BI modules can be
equipped with one device. The rated voltage can be selected to be 110V, 125V, 220V and 250V.
The well-designed debouncing technique is adopted in this device, and the state change of binary
input within “Debouncing time” will be ignored. As shown in Figure 6.4-6.
Each BI module is with a 22-pin connector for 11 binary inputs (NR1503) or 18 binary inputs
(NR1504).
Date: 2015-07-29
6 Hardware Description
For NR1503, each binary input has independent negative power input of opto-coupler, and can be
configurable. The terminal definition of the connector of BI plug -in module is described as below.
[BI_n] (n=01, 02,…,11 can be configured as a specified binary input by PCS-Explorer software.)
BI_01 01
NR1503 Opto01- 02
BI_02 03
Opto02- 04
BI_03 05
Opto03- 06
BI_04 07
Opto04- 08
BI_05 09
Opto05- 10
BI_06 11
Opto06- 12
BI_07 13
Opto07- 14
BI_08 15
Opto08- 16
BI_09 17
Opto09- 18
BI_10 19
Opto10- 20
BI_11 21
Opto11- 22
Date: 2015-07-29
6 Hardware Description
For NR1504, all binary inputs share one common negative power input, and is configurable. The
terminal definition of the connector of BI plug-in module is described as below. [BI_n] (n=01,
02,…,18 can be configured as a specified binary input by PCS-Explorer software.)
BI_01 01
NR1504 BI_02 02
BI_03 03
BI_04 04
BI_05 05
BI_06 06
BI_07 07
08
BI_08 09
BI_09 10
BI_10 11
BI_11 12
BI_12 13
BI_13 14
15
BI_14 16
BI_15 17
BI_16 18
BI_17 19
BI_18 20
BI_19 21
COM- 22
Date: 2015-07-29
6 Hardware Description
A default configuration is given for first four binary signals (BI_ 02, BI_03, BI_04, BI_05) of the first
BI plug-in module (located in slot No.10), and they are, [BI_TimeSyn], [BI_Print], [BI_Maintenance]
and [BI_RstTarg] respectively. They can also be configured as other signals. Because the first
binary signal [BI_02] is set as [BI_TimeSyn] by default (the state change information of binary
signal [BI_TimeSyn] does not need be displayed), new binary signal should be added to state
change message if it is set as other signal.
It is used to receive clock synchronization signal from clock synchronization device , the binary
input [BI_TimeSyn] will change from “0” to “1” once pulse signal is received. When the device
adopts “Conventional” mode as clock synchronization mode (refer to section “Communication
Settings”), the device can receives PPM (pulse per minute) and PPS (pulse per second). If the
setting [Opt_TimeSyn] is set as other values, this binary input is invalid.
It is used to manually trigger printing latest report when the equipment is configured as manual
printing mode by logic setting [En_AutoPrint]=0. The printer button is located on the panel usually.
If the equipment is configured as automatic printing mode ([En_AutoPrint ] =1), report will be
printed automatically as soon as it is formed.
It is used to block communication export when this binary input is energized. During device
maintenance or testing, this binary input is then energized not to send reports via communication
port, local display and printing still work as usual. This binary input should be de-energized when
the device is restored back to normal.
It is used to reset latching signal relay and LCD displaying. The reset is done by pressing a button
on the panel.
Date: 2015-07-29
6 Hardware Description
NOTICE!
The rated voltage of binary input is optional: 110V, 125V, 220V or 250V, which MUST be
specified when placing an order. It is necessary to CHECK whether the rated voltage of
BI module complies with site DC supply rating before put the relay in service.
Two standard binary output modules, NR1521A, and NR1521H, can be selected. Output contact
can be configured as a specified tripping output contact by PCS-Explorer software according to
user requirement.
Up to four tripping output modules (located in slot 12) can be equipped with one device.
NR1521A
01
BO_Trip_01
NR1521A 02
03
BO_Trip_02
04
05
BO_Trip_03
06
07
BO_Trip_04
08
09
BO_Trip_05
10
11
BO_Trip_06
12
13
BO_Trip_07
14
15
BO_Trip_08
16
17
BO_Trip_09
18
19
BO_Trip_10
20
21
BO_Trip_11
22
NR1521H
NR1521H can provide 11 output contacts controlled by fault detector. The first four output contacts
are in parallel with instantaneous operating contacts which are recommend ed to be configured as
Date: 2015-07-29
6 Hardware Description
01
BO_Trip_01
NR1521H 02
03
BO_Trip_02
04
05
BO_Trip_03
06
07
BO_Trip_04
08
09
BO_Trip_05
10
11
BO_Trip_06
12
13
BO_Trip_07
14
15
BO_Trip_08
16
17
BO_Trip_09
18
19
BO_Trip_10
20
21
BO_Trip_11
22
Four standard binary output modules, NR1523A, NR1523B, NR1523C, and NR1523D, can be
selected to provide protection operation signal and abnormality alarm signal.
Up to four signal output modules (located in slot 08, 09, 10 and 15 respectively) can be equipped
with one device.
NR1523A
The NR1523A module is a standard binary output module for signal, which can provide 8 signal
relays (11 signal output contacts, for the first three signal output relays, each relay includes two
contacts) without controlled by fault detector. All the contacts are normally open (NO) contacts,
and among which, [BO_Signal_6], [BO_Signal_7] and [BO_Siganl_8] are magnetic latched NO
contacts.
All contacts of the module can be configured as specified signal output conta cts of certain
protections by PCS-Explorer software according to users’ requirement. [BO_Signal_ 4] and
[BO_Siganl_5] are recommended to be configured as alarm signal output contacts, other contacts
are recommended to be configured as tripping signal output contacts.
A 22-pin connector is fixed on the front of this module. The pin definition of the connector is
Date: 2015-07-29
6 Hardware Description
described as below.
NR1523A
NR1523A
01 01
BO_Signal_1-1 BO_Signal_1-1
02 02
03 03
BO_Signal_1-2 BO_Signal_1-2
04 04
05 05
BO_Signal_2-1 BO_Signal_2-1
06 06
07 07
BO_Signal_2-2 BO_Signal_2-2
08 08
09 09
BO_Signal_3-1 BO_Signal_3-1
10 10
11 11
BO_Signal_3-2 BO_Signal_3-2
12 12
13 13
BO_Signal_4 BO_Signal_4
14 14
15 15
BO_Signal_5 BO_Signal_5
16
16
17 17
BO_Signal_6 BO_Signal_6
18
18
19 19
BO_Signal_7 BO_Signal_7
20 20
21 21
BO_Signal_8 BO_Signal_8
22 22
NR1523B
The NR1523B module is a standard binary output module for signal, which can provide 11 signal
output contacts without controlled by fault detector. Among those contacts, [BO_Signal_5] and
[BO_Siganl_6] are normally closed (NC) contacts, others are normally open (NO) contacts. All
contacts of the module can be configured as specified signal output contacts of some protection s
by PCS-Explorer software according to user requirement. Besides, only the contact [BO_Siganl_8]
is a magnetic latched NO contact.
A 22-pin connector is fixed on the front of this module. The pin definition of the connector is
described as below.
Date: 2015-07-29
6 Hardware Description
NR1523B
NR1523B
01 01
BO_Signal_1-1 BO_Signal_1-1
02 02
03 03
BO_Signal_1-2 BO_Signal_1-2
04 04
05 05
BO_Signal_2-1 BO_Signal_2-1
06 06
07 07
BO_Signal_2-2 BO_Signal_2-2
08 08
09 09
BO_Signal_3-1 BO_Signal_3-1
10 10
11 11
BO_Signal_3-2 BO_Signal_3-2
12 12
13 13
BO_Signal_4 BO_Signal_4
14 14
15 15
BO_Signal_5 BO_Signal_5
16 16
17 17
BO_Signal_6 BO_Signal_6
18 18
19 19
BO_Signal_7 BO_Signal_7
20 20
21 21
BO_Signal_8 BO_Signal_8
22 22
NR1523C
The NR1523C module is a standard binary output module for signal, which can provide 11 signal
output contacts without controlled by fault detector. Among those contacts, [BO_Signal_3-2],
[BO_Signal_5] and [BO_Siganl_7] are normally closed (NC) contacts, others are normally open
(NO) contacts. All contacts of the module can be configured as specified signal output contacts of
some protections by PCS-Explorer software according to user requirement.
A 22-pin connector is fixed on the front of this module. The pin definition of the connector is
described as below.
Date: 2015-07-29
6 Hardware Description
NR1523C
NR1523C
01 01
BO_Signal_1-1 BO_Signal_1-1
02 02
03 03
BO_Signal_1-2 BO_Signal_1-2
04 04
05 05
BO_Signal_2-1 BO_Signal_2-1
06 06
07 07
BO_Signal_2-2 BO_Signal_2-2
08 08
09 09
BO_Signal_3-1 BO_Signal_3-1
10 10
11 11
BO_Signal_3-2 BO_Signal_3-2
12 12
13 13
BO_Signal_4 BO_Signal_4
14 14
15 15
BO_Signal_5 BO_Signal_5
16 16
17 17
BO_Signal_6 BO_Signal_6
18 18
19 19
BO_Signal_7 BO_Signal_7
20 20
21 21
BO_Signal_8 BO_Signal_8
22 22
NR1523D
The NR1523D module is a standard binary output module for signal, which can provide 11 signal
output contacts without controlled by fault detector. All the contacts are normally open (NO), and
among which, only [BO_Siganl_8] is magnetic latched NO contact. All contacts of the module can
be configured as specified signal output contacts of certain protections by PCS-Explorer software
according to users’ requirement.
A 22-pin connector is fixed on the front of this module. The pin definition of the connector is
described as below.
Date: 2015-07-29
6 Hardware Description
NR1523D
NR1523D
01 01
BO_Signal_1-1 BO_Signal_1-1
02 02
03 03
BO_Signal_1-2 BO_Signal_1-2
04 04
05 05
BO_Signal_2-1 BO_Signal_2-1
06 06
07 07
BO_Signal_2-2 BO_Signal_2-2
08 08
09 09
BO_Signal_3-1 BO_Signal_3-1
10 10
11 11
BO_Signal_3-2 BO_Signal_3-2
12 12
13 13
BO_Signal_4 BO_Signal_4
14 14
15 15
BO_Signal_5 BO_Signal_5
16
16
17 17
BO_Signal_6 BO_Signal_6
18
18
19 19
BO_Signal_7 BO_Signal_7
20 20
21 21
BO_Signal_8 BO_Signal_8
22 22
NR1536A (220Vdc) and NR1536B (110Vdc/125V) are input and output modules (IO module) for
mechanical protection.
A 22-pin connector is fixed on the front of this module. The pin definition of the connector is
described as below.
Date: 2015-07-29
6 Hardware Description
NR1536A NR1536B
MR IO Module x (NR1536A/B)
02 MRx.Input1
High Voltage
Binary Input
03 Signals of MRx.Input2
Mechanical MRx.Input3
04
protection
05 MRx.Input4
06 BO_MRx.Sig1_1
07 BO_MRx.Sig2_1
08 BO_MRx.Sig3_1
09 BO_MRx.Sig4_1
10 Common1
11 BO_MRx.Sig1_2
12 BO_MRx.Sig2_2
13 BO_MRx.Sig3_2
14 BO_MRx.Sig4_2
15 Common2
16 BO_MRx.Sig1_3
17 BO_MRx.Sig2_3
18 BO_MRx.Sig3_3
19 BO_MRx.Sig4_3
20 Common3
21 Pwr+
Module Power Input
22 Pwr -
Date: 2015-07-29
6 Hardware Description
17-20 BO_MR x.Sig2_3 Output alarm signal contact 3 of channel 2 of mechanical protection x (NO contact).
18-20 BO_MR x.Sig3_3 Output alarm signal contact 3 of channel 3 of mechanical protection x (NO contact).
19-20 BO_MR x.Sig4_3 Output alarm signal contact 3 of channel 4 of mechanical protection x (NO contact).
The analog input module is applicable for power plant with conventional VT and CT, the module is
not required if the device is used with ECT/EVT. The analog input module can transform these
high AC input values to relevant low AC output value for the DSP module. The transformers are
used both to step-down the currents and voltages to levels appropriate to the electronic circuitry of
this device and to provide effective isolation between this device and the power system. A low
pass filter circuit is connected to each transformer (CT or VT) secondary circuit for reducing the
noise of each analog AC input signal.
NOTICE!
The rated value of the input current transformer is optional: 1A or 5A. The rated value of
the CT MUST be definitely declared in the technical scheme and the contract.
Maximum linear range of the current converter is 40In.
Because the rated value of the input current transformer is optional, it is nece ssary to
CHECK whether the rated values of the current transformer inputs are accordant to the
demand of the engineering before putting the device into operation.
For AI module, if the plug is not put in the socket, external CT circuit is closed itself. It is shown as
below.
Plug
Socket
In
Out
Date: 2015-07-29
6 Hardware Description
In
Out
The analog input module NR1401 can provide 12-channel analog signal inputs and each channel
can be configured as a specified current or voltage channel by PCS-Explorer software according
to user requirements. Up to four NR1401 modules can be configured for the device. Three kinds of
AI modules can be used for the device:
A 24-pin connector is fixed on the front of this module. The pin definition of the connector is
described as below.
Date: 2015-07-29
6 Hardware Description
NR1401
Current input
I3 05 I3n 06 U3 05 U3n 06 I3 05 I3n 06 I3 05 I3n 06
Current input
I5 09 I5n 10 U5 09 U5n 10 I5 09 I5n 10 I5 09 I5n 10
Voltage input
Current input
Voltage input
I9 17 I9n 18 U9 17 U9n 18 U3 17 U3n 18 I9 17 I9n 18
Voltage
I11 21 I11n 22 U11 21 U11n 22 U5 21 U5n 22 U1 21 U1n 22
input
I12 23 I12n 24 U12 23 U12n 24 U6 23 U6n 24 U2 23 U2n 24
In above figure, I1~I12 and U1~U12 are polarity terminals of corresponding relevant voltage and
current inputs respectively.
If user needs other analog input configuration, please declare in the technical scheme and the
contract.
The display panel consists of liquid crystal display module, keyboard, LED and ARM processor.
The functions of ARM processor include display control of the liquid crystal display module,
keyboard processing, and exchanging data with the CPU through serial port etc. The liquid crystal
display module is a high-performance grand liquid crystal panel with soft back lighting, which has a
user-friendly interface and an extensive display range.
Date: 2015-07-29
6 Hardware Description
Date: 2015-07-29
7 Settings
7 Settings
Table of Contents
7 Settings ................................................................................................ 7-a
7.1 Overview........................................................................................................................ 7-1
List of Tables
Table 7.2-1 List of system settings ........................................................................................ 7-1
Date: 2015-07-29
7 Settings
Date: 2015-07-29
7 Settings
7.1 Overview
Settings are classified into two kinds, protection settings and common settings. Each protection
element has its independent setting menu which are given detailed description in Chapter 3. In this
chapter only common settings are introduced. Common settings consist of device settings,
communication settings, label settings, system settings and configuration settings.
The device has ten protection setting groups to coordinate with the different modes of power
system operation. One of these setting groups is assigned to be active. However, common
settings are shared by all protection setting groups, and settings of protection element are set
according to secondary values.
MainMenuSettingsSystem Settings
Date: 2015-07-29
7 Settings
Date: 2015-07-29
7 Settings
Date: 2015-07-29
7 Settings
transformer HV side 2.
Reverse the polarity direction of CT of main
5 Tr_MVS.En_RevCT 0/1
transformer MV side.
Reverse the polarity direction of CT of main
6 Tr_LVS.En_RevCT 0/1
transformer LV side.
Reverse the polarity direction of the big-ratio CT
7 ST_HVS#.En_RevCT 0/1
of HV side of step-down transformer 1.
The neutral line failure judge coefficient for VT of
8 Tr_HVS.K_VTNS 0.10~1.00 HV side of main transformer. The default value
is 0.2.
Logic setting of enabling/disabling VT neutral
0: disable
9 Tr_HVS.En_VTNS line failure supervision function for VT of HV side
1: enable
of main transformer.
The neutral line failure judge coefficient for VT of
10 Tr_MVS.K_ VTNS 0.10~1.00 MV side of main transformer. The default value
is 0.2.
Logic setting of enabling/disabling VT neutral
0: disable
11 Tr_MVS.En_VTNS line failure supervision function for VT of MV
1: enable
side of main transformer.
The neutral line failure judge coefficient for VT of
12 Tr_LVS.K_VTNS 0.10~1.00 LV side of main transformer. The default value is
0.2.
Logic setting of enabling/disabling VT neutral
0: disable
13 Tr_LVS.En_VTNS line failure supervision function for VT o f LV side
1: enable
of main transformer.
Logic setting of enabling non-volatile memory
for accumulate duration of underfrequency
14 81U.En_NVM_ Accu 0/1 protection. When it is set as “1”, the accumulate
duration of underfrequency protection will not be
cleared even when the device is not powered.
Logic setting of enabling non-volatile memory
for accumulate duration of o verfrequency
15 81O.En_NVM_ Accu 0/1 protection. When it is set as “1”, the accumulate
duration of overfrequency protection will not be
cleared even when the device is not powered.
The length of measuring window of
16 81R.MeasWindow 3~25
rate-of-frequency-change.
MainMenuSettingsConfig Settings
Date: 2015-07-29
7 Settings
1. [HDR_EncodedMode]
Default value of [HDR_EncodedMode] is 1 (i.e. UTF-8 code) and please set it to 0 (i.e. GB18030)
according to the special requirement.
2. [Opt_Caption_103]
3. [En_MDisk]
A moveable mdisk is implemented on the MON plug-in module to backup and restore programs,
settings and configurations.
Date: 2015-07-29
7 Settings
If MON plug-in module is broken, remove the mdisk and put it into a new MON plug -in module, use
the menu on HMI to restore the backup programs and configurations. If DSP plug-in module is
broken, after a new DSP plug-in module is installed, use the menu on HMI to restore the backup
programs and configurations. If the moveable mdisk is broken, after a new mdisk is installed on
the MON plug-in module, use the menu on HMI to back up the current programs and
configurations into the new mdisk.
000.000.000.000~
1 IP_LAN1 IP address of Ethernet port 1.
255.255.255.255
000.000.000.000~
2 Mask_LAN1 Subnet mask of Ethernet port 1.
255.255.255.255
000.000.000.000~
3 IP_LAN2 IP address of Ethernet port 2.
255.255.255.255
000.000.000.000~
4 Mask_LAN2 Subnet mask of Ethernet port 2.
255.255.255.255
000.000.000.000~
6 IP_LAN3 IP address of Ethernet port 3.
255.255.255.255
000.000.000.000~
7 Mask_LAN3 Subnet mask of Ethernet port 3.
255.255.255.255
000.000.000.000~
9 IP_LAN4 IP address of Ethernet port 4.
255.255.255.255
000.000.000.000~
10 Mask_LAN4 Subnet mask of Ethernet port 4.
255.255.255.255
000.000.000.000~
12 Gateway Gateway of router.
255.255.255.255
Date: 2015-07-29
7 Settings
4800,9600,19200,
18 Baud_RS485A 38400,57600,115200 Baud rate of rear RS-485 serial port 1.
(bps)
0: IEC103;
1: MODBUS;
19 Protocol_RS485A Communication protocol of rear RS-485 serial port 1.
2: DNP;
3: DLT645.
4800,9600,19200,
21 Baud_RS485B 38400,57600,115200 Baud rate of rear RS-485 serial port 2.
(bps)
0: IEC103;
1: MODBUS;
22 Protocol_RS485B Communication protocol of rear RS-485 serial port 2.
2: DNP;
3: DLT645.
4800,9600,19200,
26 Baud_Printer 38400,57600,115200 Baud rate of printer port.
(bps)
0: disable
27 En_AutoPrint Enable/disable automatic printing function.
1: enable
Date: 2015-07-29
7 Settings
Conventional
SAS
28 Opt_TimeSyn Select the mode of time synchronization of equipment.
Ad vanced
NoTimeSyn
1. [En_LANx] (x= 2, 3, 4)
“1”: enable the IP address of Ethernet port and the corresponding IP address setting is need to be
set.
“0”: disable the IP address of Ethernet port and the corresponding IP address setting is not need to
be set.
2. [En_Broadcast]
This setting is only used for IEC 103 protocol. If NR network IEC103 protocol is used, the setting
must be set as “1”.
3. [Protocol_RS485x] (x=A, B)
The setting is used to select the communication protocol of rear RS-485 serial port x.
1: Modbus protocol
2: DNP protocol
3: DLT645
4. [Format_Measmt]
The setting is used to select the format of measurement data sent to SCADA through IEC103
Date: 2015-07-29
7 Settings
protocol.
1: GDD data type through IEC103 protocol is 7, i.e. 754 short real number of IEEE standard.
5. [En_AutoPrint]
If automatic print is required for disturbance report after protection operating, the setting should be
set as “1”.
6. [Opt_TimeSyn]
There are four selections for clock synchronization of device, each selection includes different time
clock synchronization signals shown in following table.
Item Description
PPS(RS-485): Pulse per second (PPS) via RS-485 differential level.
IRIG-B(RS-485): IRIG-B via RS-485 differential level.
Conventional
PPM(DIN): Pulse per minute (PPM) via the binary input [BI_TimeSyn].
PPS(DIN): Pulse per second (PPS) via the binary input [BI_TimeSyn].
SNTP(PTP): Unicast (point to point) SNTP mode via Ethernet network.
SAS SNTP(BC): Broadcast SNTP mode via Ethernet network.
Message (IEC103): Clock messages through IEC103 protocol.
IEEE1588: Clock message via IEEE1588.
Ad vanced IRIG-B(Fiber): IRIG-B via optical-fibre interface.
PPS(Fiber) PPS: Pulse per second (PPS) via optical-fibre interface.
When no time synchronization signal is connected to the equipment, please select
NoTimeSyn
this option and the alarm message [Alm_TimeSyn] will not be issued anymore.
“Conventional” mode and “SAS” mode are always be supported by device, but “Advanced” mode
is only supported when NET-DSP module is equipped. The alarm signal [Alm_TimeSyn] may be
issued to remind user loss of time synchronization signals.
1) When “SAS” is selected, if there is no conventional clock synchronization signal, the device
will not send the alarm signal [Alm_TimeSyn]. When “Conventional” mode is selected, if there
is no conventional clock synchronization signal, “SAS” mode will be enabled automatically
with the alarm signal [Alm_TimeSyn] being issued simultaneously.
3) When “NoTimeSyn” mode is selected, the device will not send alarm signals without time
synchronization signal. But the device can be still synchronized if receiving time
synchronization signal.
The clock message via IEC103 protocol is invalid when the device receives the IRIG-B signal
through RS-485 port.
7. [IP_Server_SNTP]
Date: 2015-07-29
7 Settings
It is the address of the SNTP time synchronization server which send s SNTP timing messages to
the relay or BCU.
8. OffsetHour_UTC, OffsetMinute_UTC
If the IEC61850 protocol is adopted in substations, the time tags of communication messages are
required according to UTC (Universal Time Coordinated) time.
The setting [OffsetHour_UTC] is used to set the hour offset of the current time zone to the GMT
(Greenwich Mean Time) zone; for example, if a relay is applied in China, the time zone of China is
east 8th time zone, so this setting is set as “8”. The setting [OffsetMinute_UTC] is used to set the
minute offset of the current time zone to the GMT zone.
Date: 2015-07-29
8 Human Machine Interface
Table of Contents
Date: 2015-07-29
8 Human Machine Interface
List of Figures
Figure 8.1-4 Corresponding cable of the RJ45 port in the front panel ................................ 8-4
Figure 8.1-5 Rear view and terminal definition of NR1102M ................................................ 8-5
Figure 8.3-3 LCD display 2 of trip report and alarm report................................................. 8-19
Date: 2015-07-29
8 Human Machine Interface
List of Tables
Date: 2015-07-29
8 Human Machine Interface
Date: 2015-07-29
8 Human Machine Interface
The operator can access the protective device from the front panel. Local communication with the
protective device is possible using a computer via a multiplex RJ45 port on the front panel.
Furthermore, remote communication is also possible using a PC with the substation automation
system via rear RS485 port or rear Ethernet port. The operator is able to check the protective
device status at any time.
This chapter describes human machine interface (HMI), and give operator an instruction about
how to display or print event report, setting and so on through HMI menu tree and display metering
value, including RMS current, voltage and frequency etc. through LCD. Procedures to change
active setting group or a settable parameter value through keypad are also described in details.
8.1 Overview
NOTICE!
The LCD interface in this chapter is ONLY a reference and available for explaining
specific definition of LCD. The displayed interface of the actual protection device may
be some DIFFERENT from it.
The human-machine interface consists of a human-machine interface (HMI) module which allows
a communication to be as simple as possible for the user. The HMI module helps to draw your
attention to something that has occurred which may activate a LED or a report displayed on the
LCD. Operator can locate the data of interest by navigating the keypad.
1 11
5
HEALTHY
2 12 PCS-985
ALARM
3
TRIP
13
TRANSFORMER RELAY
4 14
5 15
C GRP
6 16
7 17 ENT
ES
8 18
9 19 1
4
10 20
3
2
Date: 2015-07-29
8 Human Machine Interface
NOTICE!
Press “+”, “”, “”, “-“, “ENT” IN SEQUENCE to confirm the setting change and press
“+”, “-“, “+”, “-“, “ENT” IN SEQUENCE to execute the report deletion.
+
GR
ENT
ESC
1. “ESC”:
2. “ENT”:
3. “GRP”
Date: 2015-07-29
8 Human Machine Interface
Page up/down
01 HEALTHY 11
01 HEALTHY
02 ALARM 12
03 13 02 ALARM
Recommended
04 14
05 15 03 TRIP
06 16
LED_03 is configured as shown in the right
07 17
side, and other LEDs (LED_04~LED_20)
08 18 are configured according to the practical
09 19 requirement through the PCS-Explorer
10 20 software.
When the device is out of service or any hardware error is defected during
Off
HEALTHY self-check.
Steady Green Lit when the device is in service and ready for operation.
“HEALTHY” LED can only be turned on by energizing the device and no abnormality detected.
“ALARM ” LED is turned on when abnormalities of device occurs like above mentioned and can be
turned off after abnormalities are removed except CT circuit failure alarm signal which can only be
reset when the failure is removed and the device is rebooted or re-energized.
“TRIP” LED is turned on and latched once any protection element operates and can be turned off
by pressing the signal RESET button on the front panel.
Other LED indicators with no labels are configurable and user can configure them to be lit by
signals of operation element, alarm element and binary output contact according to requirement
through PCS-Explorer software, and there are three colors (green, yellow and red) for user
selection.
There is a multiplex RJ45 port on the front panel. This port can be used as an RS-232 serial port
as well as a twisted-pair Ethernet port. As shown in the following figure, a customized cable is
applied for debugging via this multiplex RJ45 port.
Date: 2015-07-29
8 Human Machine Interface
P2
P1
P3
Figure 8.1-4 Corresponding cable of the RJ45 port in the front panel
P1: To connect the multiplex RJ45 port. An 8-core cable is applied here.
The definition of the 8-core cable in the above figure is introduced in the following table.
The Ethernet port can be used to communication with PC via auxiliary software (PCS-Explorer)
after connecting the protection device with PC, so as to fulfill on-line function (please refer to the
instruction manual of PCS-Explorer). At first, the connection between the protection device and PC
must be established. Through setting the IP address and subnet mask of corresponding Ethernet
interface in the menu “Settings→Device Setup→Comm Settings”, it should be ensured that the
protection device and PC are in the same network segment. For example, setting the IP address
and subnet mask of network A. (using network A to connect with PC)
Date: 2015-07-29
8 Human Machine Interface
The IP address and subnet mask of protection device should be [IP_LAN1]= 198.87.96.XXX,
[Mask_LAN1]=255.255.255.0, [En_LAN1]=1. (XXX can be any value from 0 to 255 except 102)
If the logic setting [En_LAN1] is non-available, it means that network A is always enabled. If using
other Ethernet port, for example, Ethernet port B, the logic setting [En_LAN2] must be set as “1”.
NR1102M
ETHERNET
Network A
Network B
ETHERNET
Network C
Network D
SYN+
SYN-
SGND
RTS
TXD
SGND
8.2.1 Overview
Pressing “▲” at any running interface can return to the main menu. Select different submenu by
“▲” and “▼”. Enter the selected submenu by pressing “ENT” or “►”. Press “◄” and return to the
previous menu. Press “ESC” and exit the main menu directly. For fast return to the command
menu, one command menu will be recorded in the quick menu after its first execution. Up to five
latest menu commands can be recorded in the quick menu by “first in first out” principle. It is
arranged from top to bottom and in accordance with the execution order of command menus.
Press “▲” to enter the main menu, the interface is shown in the following diagram:
Date: 2015-07-29
8 Human Machine Interface
Quick Menu
Language
Clock
Device Settings
Mainmenu
If the protective device is powered for the first time, there is no recorded shortcut menu. Press “▲”
to enter the main menu with the interface as shown in the following diagram:
Measurements
Status
Records
Settings
Print
Local Cmd
Information
Test
Clock
Language
NOTICE!
The menu shown in following figure is NOT the specific-application menu. For each
project, the menu VARIES with the protection configuration.
Date: 2015-07-29
8 Human Machine Interface
MAIN MENU
Superv Events
All Test
Select Test
IO Events
All Test
Select Test
Contact Outputs
Internal Signal
Disturb Item
HMI Setup
Clock
BackLitDur
Contrast
Language SupervLCD
SupervLED
Under the main interface, press “▲” to enter the main menu, and select submenu by pressing “▲”,
“▼” and “ENT”. The command menu adopts a tree shaped content structure. The above diagram
provides the integral structure and all the submenus under menu tree o f the protection device.
Date: 2015-07-29
8 Human Machine Interface
8.2.2 Measurements
This menu is mainly used to display the real time sampling value of current, voltage and phase
angle. This menu and “Status” menu can fully reflects of the running environment of the protection
device. As long as the displayed values consist with the actual running situation, basically, the
protection device can work normally. This menu is set to greatly facilitate the debugging and
maintenance of people on site. Please refer to Section “Inputs and Outputs” of each protection
element about the detailed description of each sampled values.
8.2.2.1 Measurements1
(1) The submenu “Tr Values” includes the following command menus.
8.2.2.2 Measurements2
(1) The submenu “Tr Values” includes the following command menus.
Date: 2015-07-29
8 Human Machine Interface
(2) The submenu “Phase Angle” includes the following command menus.
(3) The submenu “Cal Param Display” includes the following command menus.
(4) The submenu “Prot Values” includes the following command menus.
Tr HVS Impedance Prot Display status values related to impedance protection of main transformer
7
Values HV side on fault detector DSP module.
Date: 2015-07-29
8 Human Machine Interface
Tr MVS Impedance Prot Display status values related to impedance protection of main transformer
10
Values MV side on fault detector DSP module.
8.2.3 Status
This menu is mainly used to display the real time input signals and output signals of the device.
This menu and “Measurements” menu fully reflects the running environment of the protection
device. As long as the displayed signals are in accordance with the actual running situation,
basically, the protection device can work normally. This menu is set to greatly facilitate the
debugging and maintenance of people on site.
8.2.3.1 Inputs
8.2.3.2 Outputs
8.2.4 Records
This menu is used to display all kinds of records, including the disturbance records, supervision
events, binary events and device logs, so that the operator can load to view and use as the
reference of analyzing accidents and repairing the device. All records are stored in non-volatile
memory, it can still record them even if it loses its power.
Date: 2015-07-29
8 Human Machine Interface
8.2.5 Settings
This menu is used to browse, modify and set all settings including device setup parameters,
protection settings and system parameters etc. Moreover, it can also execute the setting copy
between different setting groups.
2 Tr Sys Settings To display and modify the system settings of main transformer protection.
4 Prot Settings To display and modify the settings of each protection elements.
5 Device Setup To display and modify the settings related to device setup
To display and modify the settings of restricted earth fault protection of main
2 TrHVS REF Settings
transformer HV side.
To display and modify the settings of restricted earth fault protection of main
3 TrMVS REF Settings
transformer MV side.
12 TrHVS VoltProt Settings To display and modify the settings of phase overvoltage and undervoltage
Date: 2015-07-29
8 Human Machine Interface
To display and modify the settings of earth fault prote ction of main
24 TrLVS EF Settings
transformer LV side.
3 Label Settings To display and modify the label settings of the output signals.
8.2.6 Print
This menu is used for printing device description, setting, all kinds of records, waveform and
information related with 103 Protocol.
Date: 2015-07-29
8 Human Machine Interface
4 Superv Events To print self-check alarm and device operation abnormal alarm reports.
8.2.6.1 Settings
(1) The submenu “Prot Settings” includes the following command menus.
Date: 2015-07-29
8 Human Machine Interface
11 TrHVS EF Settings To print the settings of earth fault protection of main transformer HV side.
13 TrHVS Impedance Settings To print the settings of impedance protection of main transformer HV side.
18 TrMVS EF Settings To print the settings of earth fault protection of main transformer MV side.
20 TrMVS Impedance Settings To print the settings of impedance protection of main transformer MV side.
24 TrLVS EF Settings To print the settings of earth fault protection of main transformer LV side.
(2) The submenu “Device Setup” includes the following command menus.
Date: 2015-07-29
8 Human Machine Interface
2 Tr Curr Wave To print the recorded current waveforms of main transformer protection.
3 Tr Volt Wave To print the recorded voltage waveforms of main transformer protection.
1 Reset Target Reset the local signal, the signal indicator lamp and the LCD display
8.2.8 Information
In this menu the LCD displays software information of DSP module, MON module and HMI module,
which consists of version, creating time of software, CRC codes and management sequence
number. Besides, hardware board information can also be viewed.
8.2.9 Test
This menu is used for developers to debug the program and for engineers to maintain the device.
It can be used to check item fault message, and fulfill the communication test function. It is also
used to generate all kinds of report or event to transmit to the SAS without any external input, so
as to debug the communication on site.
Date: 2015-07-29
8 Human Machine Interface
8.2.10 Clock
The current time of internal clock can be viewed here. The time is displayed in the form
YY-MM-DD and hh:mm:ss. All values are presented with digits and can be modified.
8.2.11 Language
Date: 2015-07-29
8 Human Machine Interface
8.3.1 Overview
There are five kinds of LCD display: SLD (single line diagram) display, tripping reports, alarm
reports, binary input changing reports and device logs. Tripping reports and alarm reports will not
disappear until these reports are acknowledged by pressing the “RESET” button in the protection
panel (i.e. energizing the binary input [BI_RstTarg]). User can press “ESC” first then “ENT”
simultaneously to switch the display among trip reports, alarm reports and the SLD display. Binary
change reports will be displayed for 5s and then it’ll return to the previous d isplay interface
automatically. Device logs will not pop up and can only be viewed by navigating the corresponding
menu.
After the protection device is powered and turns into the initiating interface, it takes 45 seconds to
complete the initialization of protection device. During the initialization, the “ HEALTHY” indicator of
the protection device goes out.
Under normal condition, the LCD will display the interface similar as Figure 8.3-1. The LCD adopts
white color as its backlight that is activated if once there is any keyboard operation, and is
extinguished automatically after 60 seconds of no operation.
When the device is powered on, the LCD will display single line diagram as following:
Date and time
Communication address Addr:102 2014-10-28 10:10:00 Group 01 Active setting group number
The displayed content of the interface contains: the current date and time of the protection device
(with a format of yy-mm-dd hh:mm:ss:), the currently valid setting group number, the three -phase
current sampled values, differential current etc.
Date: 2015-07-29
8 Human Machine Interface
element operating, the LCD will automatically display the latest fault report, and two kinds of LCD
display will be available depending on whether there is self-check report at present.
If the device has no self-check report, the display interface will only show the fault report.
Disturb Records NO.2 shows the title and SOE number of the report.
2014-11-28 07:10:00:200 shows the time when fault detector picks up, the format is
year–month-date and hour: minute:second:millisecond.
0000ms TrigDFR shows fault detector of protection element and operation time of fault detector is
fixed as 0ms.
0024ms Tr.87T.Op_Biased shows the relative operation time and operation element of protection
element
All the protection elements have been listed in Chapter 3 “Operation Theory”, and please refer to
Section “Inputs and Outputs” of each protection element for details. Operation reports of fault
detector and the reports related to oscillography function are shown in the following table.
For the situation that the fault report and the self-check alarm report occur simultaneously in the
following figure, the upper half part is fault report, and the lower half part is self-check report. As to
Date: 2015-07-29
8 Human Machine Interface
the upper half part, it displays separately the record number of fault report, fault name, generating
time of fault report (with a format of yy-mm-dd hh:mm:ss:), protection element and tripping element.
If there is protection element, there is relative time on the basis of fault detector element. At the
same time, if the total lines of protection element and tripping element are more than 3, a scroll bar
will appear at the right. The height of the black part of the scroll bar basically indicates the total
lines of protection element and tripping element, and its position suggests the position of the
currently displayed line in the total lines. The scroll bar of protection element and tripping element
will roll up at the speed of one line per time. When it rolls to the last three lines, it’ll roll from the
earliest protection element and tripping element again. The displayed content of the lower half pa rt
is similar to that of the upper half part.
0000ms TrigDFR
0024ms Tr.87T.Op_Biased
Superv Events
24.Alm
Settings_Chgd 0 1
Date: 2015-07-29
8 Human Machine Interface
Superv Events NO.4 shows the SOE number and title of the report
2014-11-29 09:18:47:500 shows the data and time of the report occurred: year–month-date
and hour:minute:second:millisecond
IO Events NO.4
2014-11-29 09:18:47:500ms
BI_Maintenance 0 1
2014-11-29 09:18:47:500 shows the date and time of the report occurred, the format is
year–month-date and hour:minute:second:millisecond
BI_Maintenance 0->1 shows the state change of binary input, including binary input name,
original state and final state
Contact inputs and contact outputs are listed in the following two tables, and user can define
undefined binary inputs as the specific binary inputs via PCS-Explorer software.
NOTICE!
The binary input number of BI intelligent module of different type may be DIFFERENT
and signals list in following table are just for reference, please refer to Chapter
“Hardware” for details.
Date: 2015-07-29
8 Human Machine Interface
3 BI_Maintenance Binary input of indicating the protection device is under maintenance state
4 BI_RstTarg Binary input of resetting signal of protective device
5 Bxx.BI_01 Binary input 01 of the binary input module located in slot No.xx.
6 Bxx.BI_02 Binary input 02 of the binary input module located in slot No.xx.
7 Bxx.BI_03 Binary input 03 of the binary input module located in slot No.xx.
8 Bxx.BI_04 Binary input 04 of the binary input module located in slot No.xx.
9 Bxx.BI_05 Binary input 05 of the binary input module located in slot No.xx.
10 Bxx.BI_06 Binary input 06 of the binary input module located in slot No.xx.
11 Bxx.BI_07 Binary input 07 of the binary input module located in slot No.xx.
12 Bxx.BI_08 Binary input 08 of the binary input module located in slot No.xx.
13 Bxx.BI_09 Binary input 09 of the binary input module located in slot No.xx.
14 Bxx.BI_10 Binary input 10 of the binary input module located in slot No.xx.
15 Bxx.BI_11 Binary input 11 of the binary input module located in slot No.xx.
16 Bxx.BI_12 Binary input 12 of the binary input module located in slot No.xx.
17 Bxx.BI_13 Binary input 13 of the binary input module located in slot No.xx.
18 Bxx.BI_14 Binary input 14 of the binary input module located in slot No.xx.
19 Bxx.BI_15 Binary input 15 of the binary input module located in slot No.xx.
20 Bxx.BI_16 Binary input 16 of the binary input module located in slot No.xx.
21 Bxx.BI_17 Binary input 17 of the binary input module located in slot No.xx.
22 Bxx.BI_18 Binary input 18 of the binary input module located in slot No.xx.
Date: 2015-07-29
8 Human Machine Interface
Device Logs NO. 4 shows the title and the number of the report
2008-11-28 10:18:47:569 shows the date and time when the report occurred, the format is
year–month-date and hour:minute:second:millisecond
Date: 2015-07-29
8 Human Machine Interface
2. Press the key “▲” or “▼” to move the cursor to the “Measurements” menu, and then
press the “ENT” or “►” to enter the menu.
3. Press the key “▲” or “▼” to move the cursor to any command menu item, and then press
the key “ENT” to enter the submenu.
4. Press the “▲” or “▼” to page up/down (if all information cannot be displayed in one
display screen, one screen can display 14 lines of information at most).
5. Press the key “◄” or “►” to select pervious or next command menu.
6. Press the key “ENT” or “ESC” to exit this menu (returning to the “Measurements” menu).
2. Press the key “▲” or “▼” to move the cursor to the “Status” menu, and then press the
“ENT” or “►” to enter the menu.
3. Press the key “▲” or “▼” to move the cursor to any command menu item, and then press
the key “ENT” to enter the submenu.
4. Press the “▲” or “▼” to page up/down (if all information cannot be displayed in one
display screen, one screen can display 14 lines of information at most).
5. Press the key “◄” or “►” to select pervious or next command menu.
6. Press the key “ENT” or “ESC” to exit this menu (returning to the “Status” menu).
Date: 2015-07-29
8 Human Machine Interface
2. Press the key “▲” or “▼” to move the cursor to the “Records” menu, and then press the
key “ENT” or “►” to enter the menu.
3. Press the key “▲” or “▼” to move the cursor to any command menu, and then press the
key “ENT” to enter the submenu.
6. Press the key “◄” or “►” to select pervious or next command menu.
7. Press the key “ENT” or “ESC” to exit this menu (returning to the “Records” menu).
2. Press the key “▲” or “▼” to move the cursor to the “Settings” menu, and then press the
key “ENT” or “►” to enter the menu.
3. Press the key “▲” or “▼” to move the cursor to any command menu, and then press the
key “ENT” to enter the menu.
6. Press the key “◄” or “►” to select pervious or next command menu.
7. Press the key “ESC” to exit this menu (returning to the menu “Settings”).
If the displayed information exceeds 14 lines, the scroll bar will appear on the right side of
the LCD to indicate the quantity of al l displayed information of the command menu and the
relative location of information where the current cursor points at.
2. Press the key “▲” or “▼” to move the cursor to the “Print” menu, and then press the
“ENT” or “►” to enter the menu.
3. Press the key “▲” or “▼” to move the cursor to any command menu, and then press the
“ENT” to enter the menu.
Date: 2015-07-29
8 Human Machine Interface
Press the “+” or “-” to select pervious or next record. After pressing the key “ENT”,
the LCD will display “Start Printing... ”, and then automatically exit this menu
(returning to the menu “Print”). If the printer doesn’t complete its current print task
and re-start it for printing, and the LCD will display “Printer Busy…”. Press the key
“ESC” to exit this menu (returning to the menu “Print”).
Selecting the command menu “Superv Events” or “IO Events”, and then press the
key “▲” or “▼” to move the cursor. Press the “+” or “-” to select the starting and
ending numbers of printing message. After pressing the key “ ENT”, the LCD will
display “Start Printing…”, and then automatically exit this menu (return ing to the
menu “Print”). Press the key “ESC” to exit this menu (returning to the menu “Print”).
4. If selecting the command menu “Device Info”, “Device Status“ or “IEC103 Info”, press
the key “ENT”, the LCD will display “Start printing..”, and then automatically exit this menu
(returning to the menu “Print”).
5. If selecting the “Settings”, press the key “ENT” or “►” to enter the next level of menu.
6. After entering the submenu of “Settings”, press the key “▲” or “▼” to move the cursor,
and then press the key “ENT” to print the corresponding default value. If selecting any
item to printing:
Press the key “+” or “-” to select the setting group to be printed. After pressing the key
“ENT”, the LCD will display “Start Printing…”, and then automatically exit this menu
(returning to the menu “Settings”). Press the key “ESC” to exit this menu (returning to the
menu “Settings”).
7. After entering the submenu “Waveforms”, press the key “ENT” or “►” to enter the next
level of menu. After entering the submenu of “Waveforms”, press the “+” or “-” to
select the waveform item to be printed and press “ENT” to enter. If there is no any
waveform data, the LCD will display “No Waveform Data!” (If there is no any waveform
data, users can execute the command menu “Trig Oscillograph” in the menu “Local
Cmd”, then waveform data can be generated). With waveform data existing:
Press the key “+” or “-” to select pervious or next record. After pressing the key “ENT”,
the LCD will display “Start Printing…”, and then automatically exit this menu (returning to
the menu “Waveforms”). If the printer does not complete its current print task and
re-start it for printing, and the LCD will display “Printer Busy…”. Press the key “ESC” to
exit this menu (returning to the menu “Waveforms”).
2. Press the key “▲” or “▼” to move the cursor to the “Settings” menu, and then press
the key “ENT” or “►” to enter the menu.
3. Press the key “▲” or “▼” to move the cursor to any command menu, and then press
Date: 2015-07-29
8 Human Machine Interface
6. Press the key “◄” or “►” to select pervious or next command menu.
7. Press the key “ESC” to exit this menu (returning to the menu “Settings”).
8. Select the command menu “Device Settings” “Comm Settings” or “Label Settings”,
users need to enter the submenu “Device Setup” firstly.
9. Selecting the command menu “Device Settings”, move the cursor to the setting item
to be modified, and then press the key “ENT”.
Press the key “+” or “-” to modify the value (if the modified value is of multi-bit, press
the key “◄” or “►” to move the cursor to the digit bit, and then press the “ +” or “-” to
modify the value), press the key “ESC” to cancel the modification and return to the
displayed interface of the command menu “Device Settings”. Press the key “ENT” to
automatically exit this menu (returning to the displayed interface of the command menu
“Device Settings”).
Move the cursor to continue modifying other setting items. After all set ting values are
modified, press the key “◄”, “►” or “ESC”, and the LCD will display “Save or Not?”.
Directly press the “ESC” or press the key “◄” or “►” to move the cursor. Select the
“Cancel”, and then press the key “ENT” to automatically exit this menu (returning to the
displayed interface of the command menu “Device Settings”).
Press the key “◄” or “►” to move the cursor. Select “No” and press the key “ENT”, all
modified setting item will restore to its original value, exit this menu (returning to the
menu “Settings”).
Press the key “◄” or “►” to move the cursor to select “Yes”, and then press the key
“ENT”, the LCD will display password input interface.
Date: 2015-07-29
8 Human Machine Interface
Password:
____
Input a 4-bit password (“+”, “◄”, “▲” or “-”). If the password is incorrect, continue
inputting it, and then press the “ESC” to exit the password input interface and return to
the displayed interface of the command menu “Device Settings”. If the password is
correct, LCD will display “Save Settings…”, and then exit this menu (returning to the
displayed interface of the command menu “Device Settings”), with all modified setting
items as modified values.
10. If selecting the command menu of protection element such as “Tr Diff Settings”, the
LCD will display the following interface:
Tr Diff Settings
Active Group: 01
Selected Group: 02
Then move the cursor to the modified value and press “ENT” to enter. If the setting
[Tr.87T.I_Biased] is selected to modify, then press the “ENT” to enter and the LCD will
display the following interface. is shown the “+” or “-” to modify the value and then press
the “ENT” to enter.
Date: 2015-07-29
8 Human Machine Interface
Tr.87T.I_Biased
11. If selecting the other menus, move the cursor to the setting to be modified, and then
press the “ENT”.
For different setting items, their displayed interfaces are different but their modification methods
are the same.
After modifying the settings (except for communication settings), the “HEALTHY” indicator of the
protection device will go out, and the protection device will automatically restart and r e-check the
protection setting. If the check doesn’t pass, the protection device will be blocked.
2. Press the key “▲” or “▼” to move the cursor to the “Settings” menu, and then press the
key “ENT” or “►” to enter the menu;
3. Press the key “▲” or “▼” to move the cursor to the command menu “ Copy Settings”,
and then press the key “ENT” to enter the menu. The following display will be shown on
LCD.
Date: 2015-07-29
8 Human Machine Interface
Copy Settings
Active Group: 01
Copy To Group: 02
Press the key “+” or “-” to modify the value. Press the key “ESC”, and return to the
menu “Settings”. Press the “ENT”, the LCD will display the interface for password input,
if the password is incorrect, continue inputting it, press the key “ESC” to exit the
password input interface and return to the menu “ Settings”. If the password is correct,
the LCD will display “Copy Settings Success!”, and exit this menu (returnin g to the menu
“Settings”).
Active Group: 01
Change To Group: 02
Press the “+” or “-” to modify the value, and then press the key “ESC” to exit this menu
(returning to the main menu). After pressing the key “ENT”, the LCD will display the password
Date: 2015-07-29
8 Human Machine Interface
input interface. If the password is incorrect, continue inputting it, and then press the key “ ESC” to
exit the password input interface and return to its original state. If the password is correct, the
“HEALTHY” indicator of the protection device will go out, and the protection device will re -check
the protection setting. If the check doesn’t pass, the protection device will be blocked. If the check
is successful, the LCD will return to its original state.
The operation of deleting device records will delete ALL messages saved by the
protection device, including disturbance records, supervision events and binary events,
but it will NOT DELETE the user operation reports (i.e. device logs). Furthermore, all
deleted records are IRRECOVERABLE after deletion, please do the operation with
great cautious.
2. Press the “+”, “-”, “+”, “-” and key “ENT”; Press the key “ESC” to exit this menu
(returning to the original state). Press the key “ENT” to carry out the deletion.
2. Press the key “▲” or “▼” to move the cursor to the “Clock” menu, and then press the key
“ENT” to enter clock display.
Date: 2015-07-29
8 Human Machine Interface
Clock
Year 2008
Month 11
Day 28
Hour 20
Minute 59
Second 14
3. Press the key “▲” or “▼” to move the cursor to the date or time to be modified.
4. Press the key “+” or “-”, to modify value, and then press the key “ENT” to save the
modification and return to the main menu.
5. Press the key “ESC” to cancel the modification and return to the main menu.
2. Press the key “▲” or “▼” to move the cursor to the “Information” menu, and then press
the “ENT” to enter the menu.
3. Press the key “▲” or “▼” to move the cursor to the command menu “ Version Info”, and
then press the key “ENT” to display the software version.
2. Press the key “▲” or “▼” to move the cursor to the “Information” menu, and then press
the key “ENT” or “►” to enter the menu.
3. Press the key “▲” or “▼” to move the cursor to the command menu “ Board Info”, and
then press the “ENT” to enter the menu.
5. Press the key “ENT” or “ESC” to exit this menu (returning to the “Information” menu).
Date: 2015-07-29
8 Human Machine Interface
2. Press the key “▲” or “▼” to move the cursor to the command menu “ Language”, and
then press the key “ENT” to enter the menu and the following display will be shown on
LCD.
1 中文
2 English
3. Press the key “▲” or “▼” to move the cursor to the language user preferred and press
the key “ENT” to execute language switching. After language switching is finished, LCD
will return to the menu “Language”, and the display language is changed. Otherwise,
press the key “ESC” to cancel language switching and return to the menu “ Language”.
Date: 2015-07-29
9 Configurabl e Function
9 Configurable Function
Table of Contents
9 Configurable Function ....................................................................... 9-a
9.1 General Description ................................................................................................... 9-1
List of Figures
Figure 9.3-1 Setting device information ................................................................................ 9-2
Date: 2015-07-29
9 Configurable Function
Date: 2015-07-29
9 Configurabl e Function
Overall functions:
Click “Device Config”→“Device Setup” node, and four labels are displayed in the edit window. The
four labels are used to set device information, configure the software and hardware related
function according to the selected series number of MOT, configure protection function and
configure protection function group respectively.
Date: 2015-07-29
9 Configurable Function
Select “Device Information” page to view the basic information of the device. All these information
are default settings in the selected driver package for creatin g the device. Part of the basic
information can be modified including “Project Name”, “User File Version” and “User Modify Time”.
Choose “Function Configuration” page to enter function configuration interface as shown below
(the content may vary subject to created projects). Click the pull-down list in “Code” column to
perform function configuration.
Choose “Function Group Configuration” page to enter function group configuration interface as
shown below (the content may vary subject to created projects). Click the pull-down list in “Code”
Date: 2015-07-29
9 Configurabl e Function
On front panel of the device, two columns of indicators are normally provided. The first two
indicators indicate device running status (Healthy) and alarm status (Alarm). Colors of these
indicators may vary with functions of device.
The third LED (i.e. in3) is configured as the protection tripping LED indicator (TRIP) as default. If
user want to configure the third LED as other functions, please inform manufacturer when placing
an order.
Click “Program”→“B01:MON_Main” node, and select “LED” page to view and configure LED
element.
Date: 2015-07-29
9 Configurable Function
Double click LED element to open its attributes setup window. users can see that it consists of 4
sub-pages. Switch to “Func Block Parameter” sub-page. Here, indicators LED3~20 can be set.
Each indicator has two items to be set: Parameter “ledx_latched” (x=3~20): click corresponding
entry under “Set Value” to select “yes” or “no”. If “yes” is selected, indicator attribute is “latched”,
indicating that after this indicator is lit, it will remain on even the initiation signal disappears until it
is reset. If “no” is selected, indicator attribute is “un-latched”, indicating that the indicator status will
follow the change of its initiation signal.
The other parameter is “ledx_color” (x=3~20): The color of indicator can be selected as required:
green, yellow, and red.
After completion of setup, click “OK” to close attributes setup window. The set parameters will be
displayed on the element, as shown below.
Next, indicators initiation signals should be placed on the page and connect them to corresponding
input interfaces of LED element: select the output signal from the “Source” tab at the right side of
the window to be used as input source. Press and hold left button of mouse, and directly drag it to
the page. When this signal passes input signal connection point, a red dot will appear to prompt
Date: 2015-07-29
9 Configurabl e Function
connection. After placing it at a suitable position, connection line will be automatically generated to
connect this input signal.
The device is normally configured with a number of IO modules. Quantities may vary with different
project.
9.4.2.1 Configuration of BI
Click “Program” node. Unfold module node “B10:BI_NR1504”, one page node: “NR1504” is
shown.
Click the page “NR1504”, the corresponding BI configuration graph is shown in an editing window.
Date: 2015-07-29
9 Configurable Function
In the graph, numbers in the “PIN” column are input terminal numbers of NR150 4 module, and
name or function of each pin is described in the “BI_Name” column.
For the two parameters columns of symbols “ ” and “ ”, the former indicates BI delay
pick up time and the latter indicates BI delay drop off time. If voltage applied between a BI input
and the common terminal exceeds the BI delay pick up time, corresponding output signal will be
energized, and if the applied voltage is disappeared for a period exceeding the BI delay drop off
time, the output signal will be reset.
All configurable binary inputs can be viewed in the “Destination” tab at the right side of the window
(variable library). The input signals of BI modules can be configured or modified according to the
application or drag the required signals from the variable library.
Please refer to the input signals table in Section “Inputs and Outputs” of each protection element in
Chapter 3 for the detailed description of each configurable binary inputs.
9.4.2.2 Configuration of BO
Click “Program” node. Unfold module node “B13:BO1”, one page node: “NR1523A” is shown.
Date: 2015-07-29
9 Configurabl e Function
In the graph, numbers in the “PIN” column are input terminal numbers of NR1523A module, and
name or function of each pin is described in the “BO_Name” column.
Inputs of all configurable binary outputs can be viewed in the “Source” tab at the right side of the
window (variable library). As shown in the figure, each input corresponds to one output contact of
the BO module. The output contact of BO module will operate (output relay pickup or reset) in
response to the status change of corresponding input signal. The output contacts of BO modules
can be configured or modified according to the application or drag the required signals from the
variable library.
Please refer to the output signals table in Section “Inputs and Outputs” of each protection element
in Chapter 3 for the detailed description of each configurable binary outputs.
Click “Settings” node to enter “Settings” interface. In the middle of editing window is the setting
group setup interface, where two parameters can be set: “Active Group” and “Setting Groups:
[1-31]” (shown in Figure 9.5-1), users can change the number in the two text boxes then click the
button “Set” to modify the two parameters. The text box of “Active Group” is used for users to
change the current active setting group. The text box of “Setting Groups: [1-31]” is used for users
to change the number of active setting groups, the number of sub -nodes of “Setting” node will
change with this parameter.
Several sub-nodes: “Global” and “Group x” (x: 1~n, n is the number that inputted in the text box of
“Setting Groups: [1-31]”, n should not be larger than 31). Among them, global settings (the
sub-node “Global”) are common for all setting groups. In setting groups Group 1~Group n, only
one group is the current active setting group used in device operation, and mainly includes
protection settings, the current active setting group can be switched among Group 1~Group n
when required.
Date: 2015-07-29
9 Configurable Function
Click “Settings”→“Global” node, five sub-nodes are unfolded (number of sub-nodes may vary with
different device models) in the edit window. These sub-nodes are used to set system settings,
logic links, device settings, communication settings and label settings.
Click “Settings”→“Group x” node, all the protective settings of corresponding group can be shown
by clicking corresponding setting menu item.
Although there are many setting group nodes, settings under these nodes have the same layout in
editing page. Therefore, steps of modification of settings are basically the same. It is seen from the
graph that when any setting node is clicked and open, the editing page will display name, value,
range, step, and unit of the settings in this sequence. Here, user can modify name and set value of
the settings according to actual application requirements.
The name of a setting is the name user will finally see on the device. Users can suitably modify
this name according to actual project requirements: right click on the name entry to be modified to
pop up a right-key context menu, execute command “Modify Name”; the following window will pop
Date: 2015-07-29
9 Configurabl e Function
up:
In the “Modify Name” dialog box, users will see two entries, “Original Name” is the default name of
this setting in the symbol library, and “Name” is the name currently used, and can be modified.
Modified setting value must not exceed its range (if there has an ordain). There are two types of
set value modification operation: direct input of the value after double clicking corresponding entry
of the setting value, or selection from a pull-down menu.
User can also right click the entry of set value and select “Get Default Value” in the right-key
context menu, so as to obtain default set value of this entry from the symbol library.
During modification and editing operations of settings in the customizing editing window, modified
item will become red, till users perform saving operation.
Date: 2015-07-29
9 Configurable Function
Date: 2015-07-29
10 Communications
10 Communications
Table of Contents
10 Communications............................................................................. 10-a
10.1 General Description ...............................................................................................10-1
Date: 2015-07-29
10 Communications
List of Figures
Figure 10.2-1 EIA RS-485 bus connection arrangements ................................................... 10-2
Figure 10.5-1 Dual-net full duplex mode sharing the RCB block instance........................ 10-9
Figure 10.5-2 Dual-net hot-standby mode sharing the same RCB instance.................... 10-10
Figure 10.5-3 Dual-net full duplex mode with 2 independent RCB instances ..................10-11
Date: 2015-07-29
10 Communications
This section introduces NR’s remote communications interfaces. The protective device is
compatible with three protocols via the rear communication interface ( RS-485 or Ethernet). The
protocol provided by the protective device is indicated in the submenu in the “ Comm Settings”
column. Using the keypad and LCD to set the parameter [Protocol_RS485A] and
[Protocol_RS485B], the corresponding protocol will be selected.
The rear EIA RS-485 interface is isolated and is suitable for permanent connection no matter
whichever protocol is selected. It has advantage that 32 protective devices can be “daisy chained”
together in electrical connection using a twisted pair.
It should be noted that the descriptions in this section do not aim to fully introduce the protocol
itself. The relevant documentation for the protocol should be referred for this information. This
section serves to describe the specific implementation of the protocol in the relay.
This protective device provides two rear RS-485 communication ports, and each port has three
terminals in the 12-terminal screw connector located on the back of the relay. Each port has a
ground terminal for earth shield of communication cable. The rear ports provide RS-485 serial data
communication and are intended for permanently wired connection to a remote control center.
The EIA RS-485 two-wire connection provides a half-duplex fully isolated serial connection to the
product. The connection is polarized and whilst the product’s connection diagrams indicate the
polarization of the connection terminals it should be borne in mind that there is no agreed
definition of which terminal is which. If the master is unable to communicate with the product, but
the communication parameters match, then it is possible that the two -wire connection is reversed.
The EIA RS-485 bus must have 120Ω (Ohm) ½ Watt terminating resistors fitted at either end
across the signal wires (refer to Figure 10.2-1). Some devices may be able to provide the bus
terminating resistors by different connection or configuration arrangements, in which case
separate external components will not be required. However, this product does not provide such a
facility, so an external termination resistor is required when it is located at the bus terminus.
Date: 2015-07-29
10 Communications
EIA RS-485
Master 120 Ohm
120 Ohm
The EIA RS-485 requires that each device is directly connected to the physical cable i.e. the
communications bus. Stubs and tees are strictly forbidden, such as star topologies. Loop bus
topologies are not part of the EIA RS-485 standard and are forbidden also.
Two-core screened cable is recommended. The specification of the cable will be dependent on the
application, although a multi-strand 0.5mm2 per core is normally adequate. Total cable length
must not exceed 500m. The screen must be continuous and connected to ground at one end,
normally at the master connection point; it is important to avoid circulating currents, especia lly
when the cable runs between buildings, for both safety and noise reasons.
This product does not provide a signal ground connection. If a signal ground connection is present
in the bus cable then it must be ignored, although it must have continuity for the benefit of other
devices connected to the bus. The signal ground shall not be connected to the cables screen or to
the product’s chassis at any stage. This is for both safety and noise reasons.
10.2.1.4 Biasing
It may also be necessary to bias the signal wires to prevent jabber. Jabber occurs when the signal
level has an indeterminate state due to inactively driven of tubs. This can occur when all the slaves
are in receive mode and the master unit is slow to turn from receive mode to transmit mode. The
reason is that the master purposefully waits in receive mode, or even in a high impedance state,
until it has something to transmit. Jabber can result in the loss of first bits of the first character in
the packet for receiving device(s), which will lead to the rejection of messages for slave units,
causing non-responding between master unit and slave unit. This could brings poor response
times (due to retries), increase in message error counters, erratic communications, and even a
complete failure to communicate.
Biasing requires that the signal lines shall be weakly pulled to a defined voltage level of about 1V.
There should be only one bias point on the bus, which is best situated at the master connection
point. The DC source used for the bias must be clean; other wise noise will be injected. Please
note that some devices may (optionally) be able to provide the bus bias that the external
components will not be required.
NOTICE!
It is extremely IMPORTANT that the 120Ω termination resistors are fitted. Failure to do
Date: 2015-07-29
10 Communications
will result in an excessive bias voltage that may damage the devices connected to the
bus.
As the field voltage is much higher than that required, NR CANNOT assume
responsibility for any damage that may occur to a device connected to the network as a
result of incorrect application of this voltage.
ENSURE that the field voltage is not being used for other purposes (i.e. powering logic
inputs) as this may cause noise to be passed to the communication network.
This protective device can provide four rear Ethernet interfaces (optional) and they are unattached
to each other. Parameters of each Ethernet port can be configured in the submenu “ Comm
Settings”.
It is recommended to use twisted screened eight-core cable as the communication cable. A picture
is shown bellow.
Each device is connected with an exchanger via communication cable, and thereby it forms a star
structure network. Dual-network is recommended in order to increase reliability. SCADA is also
connected to the exchanger acting as the master station, and every device which has been
connected to the exchanger will act as a slave unit.
Date: 2015-07-29
10 Communications
SCADA
Exchanger A
Exchanger B
The IEC specification IEC60870-5-103: Telecontrol Equipment and Systems, Part 5: Transmission
Protocols Section 103 defines the use of standards IEC60870-5-1 to IEC60870-5-5 to perform
communication with protective device. The standard configuration of IEC60870 -5-103 protocol is
using a twisted pair EIA RS-485 connection over distances up to 500m. It also supports an
Ethernet for communication between devices. The relay operates as a slave unit in the system to
respond commands received from master station.
To use the rear port with IEC60870-5-103 communication, the relevant settings of the protective
device must be configured by using keypad and LCD user interface. In the submenu “ Comm
Settings”, set the parameters [Protocol_RS485A], [Protocol_RS485B] and [Baud_RS485]. To use
the Ethernet port with IEC60870-5-103 communication, the IP address and the submask of each
Ethernet port shall be set in the same submenu. Please refer to the corresponding section in
Chapter “Settings” for further details.
The IEC60870-5-103 interface over serial port (RS-485) is a master/slave interface and the
protective device is the slave device.
Initialization (reset)
Time synchronization
General interrogation
General commands
Date: 2015-07-29
10 Communications
Disturbance records
Two EIA RS-485 standardized ports are available for IEC60870-5-103 in this protective device.
The transmission speed is optional: 4800 bit/s, 9600 bit/s, 19200 bit/s or 38400 bit /s.
The link layer strictly abides by the rules defined in the IEC60870-5-103.
10.3.2 Initialization
When the protective device is powered up, or the communication parameters are changed, a reset
command is required to initialize the communications. The protective device will respond to either
of the two reset commands (Reset CU or Reset FCB), the difference is that the Reset CU will clear
any unsent messages in the transmit buffer.
The protective device will respond to the reset command with an identification mes sage ASDU 5,
the COT (Cause Of Transmission) of this response will be either Reset CU or Reset FCB
depending on the nature of the reset command.
The time and date of protective device can be set by time synchronization feature of the
IEC60870-5-103 protocol. The transmission delay as specified in IEC60870 -5-103 will be
corrected in the protective device. If the time synchronization message is sent as a send/confirm
message, then the protective device will respond with a confirmation. Wh ether the
time-synchronization message is sent as a send confirmation or a broadcast (send/no reply)
message, a time synchronization class 1 event will be generated/produced.
If the protective device clock is synchronized using the IRIG-B input, the protection device will not
be able to set the time using the IEC60870-5-103 interface. For attempt to set the time via the
interface, the protective device will create an event with the date and time taken from the IRIG -B
synchronized internal clock.
Messages sent to substation automation system are grouped according to IEC60870 -5-103
protocol. Operation elements are sent by ASDU2 (time-tagged message with relative time), and
status of binary Input and alarm element are sent by ASDU1 (time-tagged message). The cause of
transmission (COT) of these responses is 1.
The complete list of all events produced by the protective device can be printed by choosing the
submenu “IEC103 Info” in the menu “Print”.
Date: 2015-07-29
10 Communications
The GI can be used to read the status of the relay, the function numbers, and the information
numbers that will be returned during the GI cycle. The GI cycle strictly abides by the rules defined
in the IEC60870-5-103.
Refer the IEC60870-5-103 standard can get the enough details about general interrogation.
The general functions can be used to read the setting and protection measurement of t he relay,
and modify the setting. Two supported type identifications are ASDU 21 and ASDU 10. For more
details about generic functions, please see the IEC60870-5-103 standard.
Generic service group numbers supported by the relay can be printed by the submenu “IEC103
Info” in the menu “Print”.
The disturbance records are stored in uncompressed format and can be extracted using the
standard mechanisms described in IEC60870-5-103.
The IEC60870-5-103 interface over Ethernet is a master/slave interface with the relay as the slave
device. All the functions provided by this relay are based on generic functions of the
IEC60870-5-103. This relay will send all the relevant information on group caption to SAS or RTU
after establishing a successful communication link.
10.5.1 Overview
The IEC 61850 standard is the result of years of work by electric utilities and vendors of electronic
device to produce standardized communications systems. IEC 61850 is a series of standards
describing client/server and peer-to-peer communications, substation design and configuration,
testing, environmental and project standards. The complete set includes:
Date: 2015-07-29
10 Communications
IEC 61850-5: Communications and requirements for functions and device models
IEC 61850-7-1: Basic communication structure for substation and feeder device - Principles
and models
IEC 61850-7-2: Basic communication structure for substation and feeder device - Abstract
communication service interface (ACSI)
IEC 61850-7-3: Basic communication structure for substation and feeder device – Common
data classes
IEC 61850-7-4: Basic communication structure for substation and feeder device – Compatible
logical node classes and data classes
IEC 61850-8-1: Specific Communication Service Mapping (SCSM) – Mappings to MMS (ISO
9506-1 and ISO 9506-2) and to ISO/IEC 8802-3
IEC 61850-9-1: Specific Communication Service Mapping (SCSM) – Sampled values over
serial unidirectional multidrop point to point link
IEC 61850-9-2: Specific Communication Service Mapping (SCSM) – Sampled values over
ISO/IEC 8802-3
These documents can be obtained from the IEC (http://www.iec.ch). It is strongly recommended
that all those involved with any IEC 61850 implementation obtain this document set.
The relay supports IEC 61850 server services over TCP/IP communication protocol stacks. The
TCP/IP profile requires IP address to establish communications. These addresses are located in
the submenu “Settings→Device Setup→Comm Settings”.
1. MMS protocol
IEC 61850 specifies the use of the Manufacturing Message Specification (MMS) at the upper
(application) layer for transfer of real-time data. This protocol has been in existence for a number
of years and provides a set of services suitable for the transfer of data within a substation LAN
environment. IEC 61850-7-2 abstract services and objects are mapped to actual MMS protocol
services in IEC61850-8-1.
2. Client/server
This is a connection-oriented type of communication. The connection is initiated by the client, and
communication activity is controlled by the client. IEC61850 clients are often substation computers
running HMI programs or SOE logging software. Servers are usually substation device such as
protection relays, meters, RTUs, instrument transformers, tap changers, or bay controllers.
Please note that gateways can be considered as clients and servers subject to the communication
Date: 2015-07-29
10 Communications
object. When retrieving data from IEDs within the substation, the gatewa ys are considered as
servers whereas transmitting data to control centers, the gateways are considered as clients.
3. Peer-to-peer
A substation configuration language is a number of files used to describe IED configurations and
communication systems according to IEC 61850-5 and IEC 61850-7. Each configured device has
an IED Capability Description (ICD) file and a Configured IED Description (CID) file. The
substation single line information is stored in a System Specification Description (SSD) file. The
entire substation configuration is stored in a Substation Configuration Description (SCD) file. The
SCD file is the combination of the following items: individual ICD files, SSD file, communication
system parameters (MMS, GOOSE control block, SV control block), as well as GOOSE/SV
connection relationship amongst IEDs.
To enhance the stability and reliability of SAS, dual-MMS Ethernet is widely adopted. This section
is applied to introduce the details of dual-MMS Ethernet technology. Generally, single-MMS
Ethernet is recommended to be adopted in the SAS of 110kV and lower voltage levels, while
dual-MMS Ethernet is recommended to be adopted in the SAS of voltage levels above 110kV.
Client-server mode is adopted: clients (SCADA, control center and etc.) communicate with the
IEDs via MMS communication network, and the IEDs operate as the servers. IEDs are connected
to clients passively, and they can interact with the clients according to the configuration and the
issued command of the clients.
Three modes for dual-MMS Ethernet (abbreviated as dual-net) are provided as below.
NOTICE!
Hereinafter, the normal operation status of net means the physical link and TCP link are
both ok. The abnormal operation status of net means physical link or TCP link is
broken.
1) Mode 1: Dual-net full duplex mode sharing the same RCB instance
Date: 2015-07-29
10 Communications
Client Client
TCP Link
MMS Link
Figure 10.5-1 Dual-net full duplex mode sharing the RCB block instance
Net A and Net B share the same report control block (abbreviated as RCB) enabled by the client.
IED sends undifferentiated date through dual-net to the clients. If one net is physically
disconnected, the flag of RCB instance (i.e.: “RptEna” in above figure) is still “true”. Only when
both Net A and Net B are disconnected, the flag of the RCB instance will automatically change to
“false”.
In normal operation status of mode 1, IED provides the same MMS service for Net A and Net B. If
one net is physically disconnected (i.e.: “Abnormal operation status” in above figure), the working
mode will switch to single-net mode seamlessly and immediately. Network communication
supervision is unnecessary here, and Buffered Report Control Block (abbreviated as BRCB) need
not to be used. On the other net, date alternation works normally. Therefore, MMS service can
interact normally without interruption. This mode ensures no data loss during one net is in
abnormal operation status.
In mode 1, one report will be transmitted twice via dual nets for the same report instance, so the
client needs to distinguish whether two reports are same according to corresponding EntryIDs.
Date: 2015-07-29
10 Communications
Client Client
TCP Link
Figure 10.5-2 Dual-net hot-standby mode sharing the same RCB instance
In mode 2, the MMS service is provided on main MMS link, no MMS service interacts on the
standby MMS link. The definitions of two links are as follows:
Main MMS Link: Physically connected, TCP level connected, MMS report service available.
Standby MMS Link: Physically connected, TCP level connected, MMS report service not
available.
If the main net fails to operate (i.e.: “Abnormal operation status” in the above figure), the IED will
set “RptEna” to “false”. Meanwhile the client will detect the failure by heartbeat message or
“keep-alive”, it will automatically enable the RCB instance by setting “RptEna” back to “true”
through standby MMS link. By the buffer function of BRCB, the IED can provide uninterrupted
MMS service on the standby net. However, the differences of BRCB standards among different
manufacturers may cause data loss. Moreover, if duration of net switch is too long, the data loss is
positively as the capacity of BRCB’s buffer function is limited.
NOTICE!
In mode 1 and mode 2, Net A IED host address and Net B IED host address must be
the same. E.g.: if the subnet mask is 255.255.0.0, network prefix of Net A is
198.120.0.0, network prefix of Net B is 198.121.0.0, Net A IP address of the IED is
198.120.1.2, and then Net B IP address of the IED must be configured as 198.121.1.2,
i.e.: Net A IED host address =1x256+2=258, Net B IED host address =1x256+2=258,
Net A IED host address equals to Net B IED host address.
Date: 2015-07-29
10 Communications
Client Client
TCP Link
MMS Link
Figure 10.5-3 Dual-net full duplex mode with 2 independent RCB instances
In mode 3, IED provides 2 report instances for each RCB, Net A and Net B work independently
from each other, failures of one net will not affect the other net at all.
In this mode, 2 report instances are required for each client. Therefore, the IED may be unable to
provide enough report instances if there are too many clients.
Net A and Net B send the same report separately when they operates normally, To ensure no
repeated data is saved into database, massive calculation is required for the client.
Moreover, accurate clock synchronization of the IED is required to distinguish whether 2 reports
are the same report according to the timestamps. Clock synchronization error of the IED may lead
to report loss/redundancy.
As a conclusion:
In mode 3, the IED may be unable to provide enough report instances if too many clients are
applied on site.
For the consideration of client treatment and IED implementation, mode 1 (Dual-net full duplex
mode sharing the same report instance) is recommended for MMS communication network
deployment.
IEC61850 defines an object-oriented approach to data and services. An IEC61850 physical device
can contain one or more logical device(s) (for proxy). Each logical device can contain many logical
Date: 2015-07-29
10 Communication s
nodes. Each logical node can contain many data objects. Each data object is composed of data
attributes and data attribute components. Services are available at each level for performing
various functions, such as reading, writing, control commands, and reporting.
Each IED represents one IEC61850 physical device. The physical device contains one or more
logical device(s), and the logical device contains many logical nodes. The logical node LPHD
contains information about the IED physical device. The logical node LLN0 contains common
information about the IED logical device.
The GGIO logical node is used to provide access to digital status points (including general I/O
inputs and warnings) and associated timestamps and quality flags. The data content must be
configured before using. GGIO provides digital status points for access by clients. It is intended for
the use of GGIO by client to access to digital status values from PCS-985TE relays. Clients can
utilize the IEC61850 buffered report from GGIO to build sequence of events (SOE) logs and HMI
display screens. Buffered reporting should generally be used for SOE logs since the buffering
capability reduces the chances of missing data state changes. All needed status data objects are
transmitted to HMI clients via buffered reporting, and the corresponding buffered reporting control
block (BRCB) is defined in LLN0.
Most of measured analog values are available through the MMXU logical nodes, and metering
values in MMTR, the others in MMXN, MSQI and so on. Data of each MMXU logical node is
provided from a IED current/voltage “source”. There is one MMXU available for each configurable
source. Data of MMXU1 is provided from CT/VT source 1 (usually for protection purpose), and
data of MMXU2 is provided from CT/VT source 2 (usually for monitor and display purpose). All
these analog data objects are transmitted to HMI clients via unbuffered reporting periodically, and
the corresponding unbuffered reporting control block (URCB) is defined in LLN0. MMXUx logical
nodes provide the following data for each source:
MMXU.MX.Hz: frequency
Date: 2015-07-29
10 Communications
The following list describes the protection elements for PCS-985TE relays. The specified relay will
contain a subset of protection elements from this list.
The protection elements listed above contain start (pickup) and operate flags, instead of any
element has its own start (pickup) flag separately, all the elements share a common start (pickup)
flags “PTRC.ST.Str.general”. The operate flag for PDIF1 is “PDIF1.ST.Op.general”. For
PCS-985TErelay protection elements, these flags take their values from related module for the
corresponding element. Similar to digital status values, the protection trip information is reported
via BRCB, and it also locates in LLN0.
Logical node LLN0 is essential for an IEC61850 based IED. This LN shall be used to address
common issues for Logical Devices. Most of the public services, the common settings, control
values and some device oriented data objects are available here. The public services may be
BRCB, URCB and GSE control blocks and similar global defined for the whole device; the
common settings include all the setting items of communication settings, system settings and
some of the protection setting items, which can be configured to two or more protec tion elements
(logical nodes). In LLN0, the item Loc is a device control object, this item indicates the local
operation for complete logical device, when it is true, all the remote control commands to the IED
will be blocked until Loc is changed to false. In PCS-985TE relays, besides the logical nodes
described above, there are some other logical nodes in the IEDs:
LPHD: Physical device information, the logical node to model common issues for physical
device.
PTRC: Protection trip conditioning, it is used to connect the “operate” outputs of one or more
Date: 2015-07-29
10 Communications
RDRE: Disturbance recorder function. It triggers fault wave recorder and its output refers to
the “IEEE Standard Format for Transient Data Exchange (COMTRADE) for Power System” (IEC
60255-24). All enabled channels are included in the recording and is independent of the trigger
mode.
IEC61850 buffered and unbuffered reporting control blocks are located in LLN0, they can be
configured to transmit information of protection trip information (in the Protection logical nodes),
binary status values (in GGIO) and analog measured/calculated values (in MMXU, MMTR and
MSQI). The reporting control blocks can be configured in CID files, an d then be sent to the IED via
an IEC61850 client. The following items can be configured.
- Bit 1: Data-change
- Bit 4: Integrity
- Bit 1: Sequence-number
- Bit 2: Report-time-stamp
- Bit 3: Reason-for-inclusion
- Bit 4: Data-set-name
- Bit 5: Data-reference
- Bit 8: Conf-revision
- Bit 9: Segmentation
Date: 2015-07-29
10 Communications
MMS file services allows transfer of oscillography, event record or other files from a PCS-985TE
relay.
10.5.5.3 Timestamps
The timestamp values associated with all IEC61850 data items represent the time of the last
change of either the value or quality flags of the data item.
IEC61850 specifies that each logical node can have a name with a total length of 11 characters.
The name is composed of:
Complete names are in the form of xxxxxxPTOC1, where the xxxxxx character string is
configurable. Details regarding the logical node naming rules are given in IEC61850 parts 6 and
7-2. It is recommended that a consistent naming convention be used for an entire substation
project.
IEC61850 specifies the type of broadcast data transfer services: Generic Object Oriented
Substation Events (GOOSE). IEC61850 GOOSE services provide virtual LAN (VLAN) support,
Ethernet priority tagging, and Ether-type Application ID configuration. The support for VLANs and
priority tagging allows for the optimization of Ethernet network traffic. GOOSE messages can be
given a higher priority than standard Ethernet traffic, and they can be separated onto specific
VLANs. Devices that transmit GOOSE messages also function as server s. Each GOOSE
publisher contains a “GOOSE control block” to configure and control the transmission.
The GOOSE transmission (including subscribing and publishing) is controlled by GOOSE logic link
settings in device.
The relay supports IEC61850 Generic Object Oriented Substation Event (GOOSE)
communication. All GOOSE messages contain IEC61850 data collected into a dataset. It is this
dataset that is transferred using GOOSE message services. The GOOSE related dataset is
configured in the CID file and it is recommended that the fixed GOOSE be used for
implementations that require GOOSE data transfer between PCS-985TE relays.
IEC61850 GOOSE messaging contains a number of configurable parameters, all of which must be
correct to achieve the successful transfer of data. It is critical that the configured datasets at the
transmission and reception devices are an exact match in terms of data structure, and that the
Date: 2015-07-29
10 Communications
Client-Server Roles
SCSMS Supported
Where:
C1: Shall be "M" if support for LOGICAL-DEVICE model has been declared
O: Optional
M: Mandatory
M1 Logical device C2 C2 Y
M2 Logical node C3 C3 Y
M3 Data C4 C4 Y
M4 Data set C5 C5 Y
M5 Substitution O O Y
Reporting
Date: 2015-07-29
10 Communications
M7-1 sequence-number Y Y Y
M7-2 report-time-stamp Y Y Y
M7-3 reason-for-inclusion Y Y Y
M7-4 data-set-name Y Y Y
M7-5 data-reference Y Y Y
M7-6 buffer-overflow Y Y N
M7-7 entryID Y Y Y
M7-8 BufTm N N N
M7-9 IntgPd Y Y Y
M7-10 GI Y Y Y
M8-1 sequence-number Y Y Y
M8-2 report-time-stamp Y Y Y
M8-3 reason-for-inclusion Y Y Y
M8-4 data-set-name Y Y Y
M8-5 data-reference Y Y Y
M8-6 BufTm N N N
M8-7 IntgPd N Y Y
Logging
M9 Log control O O N
M9-1 IntgPd N N N
M10 Log O O N
GSE
M12 GOOSE O O Y
M13 GSSE O O N
M16 Time M M Y
Where:
C2: Shall be "M" if support for LOGICAL-NODE model has been declared
C3: Shall be "M" if support for DATA model has been declared
C4: Shall be "M" if support for DATA-SET, Substitution, Report, Log Control, or Time models has
Date: 2015-07-29
10 Communications
been declared
C5: Shall be "M" if support for Report, GSE, or SMV models has been declared
M: Mandatory
Server
S1 ServerDirectory M Y
Application association
S2 Associate M Y
S3 Abort M Y
S4 Release M Y
Logical device
S5 LogicalDeviceDirectory M Y
Logical node
S6 LogicalNodeDirectory M Y
S7 GetAllDataValues M Y
Data
S8 GetDataValues M Y
S9 SetDataValues M Y
S10 GetDataDirectory M Y
S11 GetDataDefinition M Y
Data set
S12 GetDataSetValues M Y
S13 SetDataSetValues O Y
S14 CreateDataSet O N
S15 DeleteDataSet O N
S16 GetDataSetDirectory M Y
Substitution
S17 SetDataValues M Y
Date: 2015-07-29
10 Communications
Reporting
S24 Report M Y
S24-1 data-change M Y
S24-2 qchg-change M N
S24-3 data-update M N
S25 GetBRCBValues M Y
S26 SetBRCBValues M Y
S27 Report M Y
S27-1 data-change M Y
S27-2 qchg-change M N
S27-3 data-update M N
S28 GetURCBValues M Y
S29 SetURCBValues M Y
Logging
S30 GetLCBValues O N
S31 SetLCBValues O N
Log
S32 QueryLogByTime O N
S33 QueryLogAfter O N
S34 GetLogStatusValues O N
S35 SendGOOSEMessage M Y
S36 GetGoReference O Y
S37 GetGOOSEElementNumber O N
S38 GetGoCBValues M Y
S39 SetGoCBValuess M N
Control
S51 Select O N
Date: 2015-07-29
10 Communications
S52 SelectWithValue M Y
S53 Cancel M Y
S54 Operate M Y
S55 Command-Termination O Y
S56 TimeActivated-Operate O N
File transfer
S58 SetFile O N
S59 DeleteFile O N
Time
SNTP M Y
The relay support IEC61850 logical nodes as indicated in the following table. Note that the actual
instantiation of each logical node is determined by the product order code.
Nodes PCS-985TE
Date: 2015-07-29
10 Communications
Nodes PCS-985TE
PTOF: Overfrequency -
PTUC: Undercurrent -
PTUV: Undervoltage -
PTUF: Underfrequency -
RREC: Autoreclosing -
CILO: Interlocking -
Date: 2015-07-29
10 Communications
Nodes PCS-985TE
IARC: Archiving -
MMTR: Metering -
Date: 2015-07-29
10 Communications
Nodes PCS-985TE
ZBAT: Battery -
ZBSH: Bushing -
ZCON: Converter -
ZGEN: Generator -
ZMOT: Motor -
ZREA: Reactor -
10.6.1 Overview
The descriptions given here are intended to accompany this relay. The DNP3.0 protocol is not
described here; please refer to the DNP3.0 protocol standard for the details about the DNP3.0
implementation. This manual only specifies which objects, variations and qualifiers are supported
in this relay, and also specifies what data is available from this relay via DNP3.0.
The relay operates as a DNP3.0 slave and supports subset level 3 of the protocol, plus some of
the features from level 4. The DNP3.0 communication uses the Ethernet ports (electrical or optical)
at the rear side of this relay.
Please see the DNP3.0 protocol standard for the details about the linker layer functions.
Please see the DNP3.0 protocol standard for the details about the transport functions.
Date: 2015-07-29
10 Communications
The supported object groups and object variations are show in the following table.
Date: 2015-07-29
10 Communications
Date: 2015-07-29
10 Communications
Date: 2015-07-29
10 Communications
Date: 2015-07-29
10 Communications
This relay now supports 4 Ethernet clients and 2 serial port clients. Each client can be set the DNP
related communication parameters respectively and be selected the user-defined communication
table. This relay supports a default communication table and 4 user -defined communication tables,
and the default communication table is fixed by the manufacturer and not permitted to configure by
the user.
The user can configure the user-defined communication table through the PCS-Explorer
Date: 2015-07-29
10 Communications
configuration tool auxiliary software. The object groups “Binary Input”, “Binary Output”, “Analog
Input” and “Analog Output” can be configured according to the practical engineering demand.
To the analog inputs, the attributes “deadband” and “factor” of each analog input can be configured
independently. To the analog outputs, only the attribute “factor” of each analog output needs to be
configured. If the integer mode is adopted for the data formats of analog values (to “Analog Input”,
“Object Variation” is 1, 2 and 3; to “Analog Output”, “Object Variation” is 1 and 2.), the analog
values will be multiplied by the “factor” respectively to ensure their accuracy. And if the float mode
is adopted for the data formats of analog values, the actual float analog values will be sent directly.
The judgment method of the analog input change is as below: Calculate the difference between
the current new value and the stored history value and make the difference value multiply by the
“factor”, then compare the result with the “deadband” value. If the result is greater than the
“deadband” value, then an event message of corresponding analog input change will be cr eated.
In normal communication process, the master can online read or modify a “deadband” value by
reading or modifying the variation in “Group34”.
The remote control signals, logic links and external extended output commands can be configured
into the “Binary Output” group. The supported control functions are listed as below.
Information Point Pulse On/Null Pulse On/Close Pulse On/Trip Latch On/Null Latch Off/Null
Remote Control Not supported Close Trip Close Trip
Logic Link Not supported Set Clear Set Clear
Extended Output See following description
This relay does not transmit the unsolicited messages if the related logic setting is set as “0”. If the
unsolicited messages want to be transmitted, the related logic setting should be set as “1” or the
DNP3.0 master will transmit “Enable Unsolicited” command to this relay through “Function Code
20” (Enable Unsolicited Messages). If the “Binary Input” state changes or the difference value of
the “Analog Input” is greater than the “deadband” value, this device will transmit unsolicited
messages. If the DNP3.0 master needs not to receive the unsolicited messages, it should forbid
this relay to transmit the unsolicited messages by setting the related logic setting as “0” or through
the “Function Code 21” (Disable Unsolicited Messages).
If the DNP3.0 master calls the Class0 data, this relay will transmit all actual values of the “Analog
Input”, “Binary Input” and “Analog Output”. The classes of the “Analog Input” and “Binary Input”
can be defined by modifying relevant settings. In communication process, the DNP3.0 master can
Date: 2015-07-29
10 Communications
online modify the class of an “Analog Input” or a “Binary Input” through “Function Code 22” (Assign
Class).
Date: 2015-07-29
11 Installation
11 Installation
Table of Contents
11 Installation ....................................................................................... 11-a
11.1 Overview.................................................................................................................... 11-1
List of Figures
Figure 11.6-1 Dimensions and panel cut-out of PCS-985TI .................................................11-3
Figure 11.6-2 Demonstration of plugging a board into its corresponding slot ..................11-3
Figure 11.7-4 Glancing demo about the wiring for electrical cables...................................11-7
Date: 2015-07-29
11 Installation
Date: 2015-07-29
11 Installation
11.1 Overview
The device must be shipped, stored and installed with the greatest care.
Choose the place of installation such that the communication interface and the controls on the
front of the device are easily accessible.
Air must circulate freely around the device. Observe all the requirements regarding place of
installation and ambient conditions given in this instruction manual.
Take care that the external wiring is properly brought into the device and terminated correctly and
pay special attention to grounding. Strictly observe the corresponding guidelines contained i n this
section.
In certain cases, the settings have to be configured according to the demands of the engineering
configuration after replacement. It is therefore assumed that the personnel who replace modules
and units are familiar with the use of the operator program on the service PC.
WARNING!
ONLY insert or withdraw a module while the device power supply is switched off. To this
end, disconnect the power supply cable that connects with the PWR module.
NOTICE!
Industry packs and ribbon cables may ONLY be replaced on a workbench for electronic
equipment. Electronic components are sensitive to electrostatic discharge when not in
the unit's housing.
NOTICE!
NOTICE!
A module can ONLY be inserted in the slot designated in the chapter 6. Components
can be damaged or destroyed by inserting module in a wrong slot.
Should boards have to be removed from this device installed in a grounded cubicle in an HV
switchgear installation, please discharge yourself by touching station ground (the cubicle)
beforehand.
Date: 2015-07-29
11 Installation
Only hold electronic boards at the edges, taking care not to touch the components.
Only works on the board which has been removed from the cubicle on a workbench designed
for electronic equipment and wear a grounded wristband. Do not wear a grounded wristband,
however, while inserting or withdrawing units.
Always store and ship the electronic boards in their original packing. Place electronic parts in
electrostatic screened packing materials.
Visually inspect all the material when unpacking it. When there is evidence of transport damage,
lodge a claim immediately in writing with the last carrier and notify the neares t NR Company or
agent.
If the equipment is not going to be installed immediately, store all the parts in their original packing
in a clean dry place at a moderate temperature. The humidity at a maximum temperature and the
permissible storage temperature range in dry air are listed in Chapter “Technical Data”.
A suitable drill and spanners are required to secure the cubicles to the f loor using the plugs
provided (if this device is mounted in cubicles).
Excessively high temperature can appreciably reduce the operating life of this device.
The place of installation should permit easy access especially to front of the device, i.e. to the
human machine interface of the equipment.
There should also be free access at the rear of the equipment for additions and replacement of
electronic boards.
Since every piece of technical equipment can be damaged or destroyed by inadmissible ambient
conditions, such as:
1. The location should not be exposed to excessive air pollution (dust, aggressive substances).
2. Surge voltages of high amplitude and short rise time, extreme changes of temperature, high
levels of humidity, severe vibration and strong induced magnetic fields should be avoided as
far as possible.
Date: 2015-07-29
11 Installation
The equipment can in principle be mounted in any attitude, but it is normally mounted vert ically
(visibility of markings).
It is necessary to leave enough space top and bottom of the cut-out in the cubicle for
heat emission of this device.
The device is made of one 4U height 19" chassis with 8 connectors on its rear panel. Following
figure shows the dimensions and cut-out size in the cubicle of this device for reference in
mounting.
482.6 (290.0)
465.0
101.6
177.0
465.0±0.2
+0.4
451.0 -0.0
4-Φ6.8
+0.4
179.0 -0.0
101.6±0.1
Following figure shows the installation way of a module being plugged into a corresponding slot.
Date: 2015-07-29
11 Installation
In the case of equipment supplied in cubicles, place the cubicles on the foundations that have
been prepared. Take care while doing so not to jam or otherwise damage any of the cables that
have already been installed. Secure the cubicles to the foundations.
NOTICE!
All these precautions can only be effective if the station ground is of good quality.
Switching operations in HV installations generate transient over voltages on control signal cables.
There is also a background of electromagnetic RF fields in electrical installations that can induce
spurious currents in the devices themselves or the leads connected to them.
On the other hand, electronic apparatus can transmit interference tha t can disrupt the operation of
other apparatus.
In order to minimize these influences as far as possible, certain standards have to be observed
with respect to grounding, wiring and screening.
The cubicle must be designed and fitted out such that the impedance for RF interference of the
ground path from the electronic device to the cubicle ground terminal is as low as possible.
Metal accessories such as side plates, blanking plates etc., must be effectively connected
surface-to-surface to the grounded frame to ensure a low-impedance path to ground for RF
interference. The contact surfaces must not only conduct well, they must also be non -corroding.
NOTICE!
If the above conditions are not fulfilled, there is a possibility of the cubicle or p arts of it
forming a resonant circuit at certain frequencies that would amplify the transmission of
interference by the devices installed and also reduce their immunity to induced
interference.
Movable parts of the cubicle such as doors (front and back) or hinged equipment frames must be
effectively grounded to the frame by three braided copper strips (see Figure 11.7-1).
The metal parts of the cubicle housing and the ground rail are interconnected electrically
conducting and corrosion proof. The contact surfaces shall be as large as possible.
NOTICE!
For metallic connections please observe the voltage difference of both materials
according to the electrochemical code.
The cubicle ground rail must be effectively connected to the station ground rail by a
grounding strip (braided copper).
Date: 2015-07-29
11 Installation
Door or hinged
equipment frame
Cubicle ground
rail close to floor
Braided
copper strip
Station
ground
Conducting
connection
There is a ground terminal on the rear panel, and the ground br aided copper strip can be
connected with it. Take care that the grounding strip is always as short as possible. The main thing
is that the device is only grounded at one point. Grounding loops from unit to unit are not allowed.
There are some ground terminals on some connectors of this device, and the sign is “GND”. All the
ground terminals are connected in the cabinet of this device. Therefore, the ground terminal on the
rear panel (see Figure 11.7-2) is the only ground terminal of this device.
High frequency currents are produced by interference in the ground connections and because of
skin effect at these frequencies, only the surface region of the grounding strips is of consequence.
The grounding strips must therefore be of (preferably tinned) braided copper and not round copper
conductors, as the cross-section of round copper would have to be too large.
Proper terminations must be fitted to both ends (press/pinch fit and tinned) with a hole for bolting
them firmly to the items to be connected.
Date: 2015-07-29
11 Installation
The surfaces to which the grounding strips are bolted must be electrically conducting and
non-corroding.
Press/pinch fit
cable terminal
Braided
copper strip Terminal bolt
Contact surface
There are several types of cables that are used in the connectio n of this device: braided copper
cable, serial communication cable etc. Recommendation of each cable:
2 2
Grounding: braided copper cable, 2.5mm ~ 6.0mm
Power supply, binary inputs & outputs: brained copper cable, 1.0mm 2 ~ 2.5mm2
DANGER!
NEVER allow a open current transformer (CT) secondary circuit connected to this
device while the primary system is live. Open CT circuit will produce a dangerously high
voltage that cause death.
A female connector is used for connecting the wires with it, and then a fe male connector plugs into
a corresponding male connector that is in the front of one board. See Chapter “Hardware” for
further details about the pin defines of these connectors.
The following figure shows the glancing demo about the wiring for the electric al cables.
Date: 2015-07-29
11 Installation
01 02
03 04
Tighten 05 06
07 08
09 10
11 12
01
13 14
15 16
17 18
19 20
21 22
23 24
Figure 11.7-4 Glancing demo about the wiring for electrical cables
Date: 2015-07-29
11 Installation
Date: 2015-07-29
12 Commissioning
12 Commissioning
Table of Contents
12 Commissioning ............................................................................... 12-a
12.1 Overview ................................................................................................................... 12-1
12.2 Safety Instructions................................................................................................. 12-1
12.3 Commission Tools ................................................................................................. 12-1
Date: 2015-07-29
12 Commissioning
Date: 2015-07-29
12 Commissioning
12.1 Overview
This device is numerical in their design, implementing all functions in software. The device
employs a high degree self-checking, so in the unlikely event of a failure, it will give an alarm.
Blank commissioning test and setting records are provided at the end of this manual for
completion as required.
Before carrying out any work on the device, the user should be familiar with the contents of the
safety and technical data sections and the ratings on the device’s rating label.
DANGER!
WARNING!
ONLY qualified personnel should work on or in the vicinity of this device. This
personnel MUST be familiar with all safety regulations and service procedures
described in this manual. During operating of electrical device, certain part of the
device is under high voltage. Severe personal injury and significant device damage
could result from improper behavior.
The earthing screw of the device must be connected solidly to the protective earth conductor
before any other electrical connection is made.
Hazardous voltages can be present on all circuits and components connected to the supply
voltage or to the measuring and test quantities.
Hazardous voltages can be present in the device even after disconnection of the supply
voltage (storage capacitors!)
The limit values stated in the Chapter “Technical Data” must not be exceeded at all, not even
during testing and commissioning.
When testing the device with secondary test equipment, make sure that no other
measurement quantities are connected. Take also into consideration that the trip circuits and
may be close commands to the circuit breakers and other primary switches are disconnected
from the device unless expressly stated.
Date: 2015-07-29
12 Commissioning
NOTICE!
Modern test set may contain many of the above features in one unit.
Multifunctional dynamic current and voltage injection test set with interval timer.
Multimeter with suitable AC current range and AC/DC voltage ranges of 0~440V and 0~250V
respectively.
Optional equipment:
An electronic or brushless insulation tester with a DC output not exceeding 500V (for
insulation resistance test when required).
A portable PC, with appropriate software (this enables the rear communications port to be
tested, if this is to be used, and will also save considerable time during commissioning).
EIA RS-485 to EIA RS-232 converter (if EIA RS-485 IEC60870-5-103 port is being tested).
Tester: HELP-9000.
With the front cover in place all keys are accessible. All menu cells can be read. The LED
indicators and alarms can be reset. Protection or configuration settings can be changed, or fault
and event records cleared. However, menu cells will require the appropriate password to be
entered before changes can be made.
If the application-specific settings have been applied to the device prior to commissioning, it is
Date: 2015-07-29
12 Commissioning
advisable to make a copy of the settings so as to allow them restoration later. This could be done
by extracting the settings from the device itself via printer or manually creating a setting record.
This device is fully numerical and the hardware is continuously monitored. Commissioning tests
can be kept to a minimum and need only include hardware tests and conjunctive tests. The
function tests are carried out according to user’s correlative regulations.
The following tests are necessary to ensure the normal operation of the equipment before it is first
put into service.
Hardware tests
These tests are performed for the following hardware to ensure that there is no hardware
defect. Defects of hardware circuits other than the following can be detected by
self-monitoring when the DC power is supplied.
Function tests
These tests are performed for the following functions that are fully software -based.
Timers test
Conjunctive tests
The tests are performed after the device is connected with the primary equipment and other
external equipment.
On load test.
After unpacking the product, check for any damage to the device case. If there is any damage, the
internal module might also have been affected, contact the vendor. The following items listed are
necessary.
Device panel
Carefully examine the device panel, device inside and other parts inside to see that no
physical damage has occurred since installation.
Panel wiring
Check the conducting wire which is used in the panel to assure that their cross section
Date: 2015-07-29
12 Commissioning
Carefully examine the wiring to see that they are no connection failure exists.
Check each plug-in module of the equipment on the panel to make sure that they are well
installed into the equipment without any screw loosened.
Earthing cable
Check whether the earthing cable from the panel terminal block is safely screwed to the panel
steel sheet.
Check whether all the switches, equipment keypad, isolator binary inputs and push buttons
work normally and smoothly.
Insulation resistance tests are only necessary during commissioning if it is required for them to be
done and they have not been performed during installation.
Isolate all wiring from the earth and test the isolation with an electronic or brushless insulation
tester at a DC voltage not exceeding 500V, The circuits need to be tested should include:
DC power supply
Output contacts
Communication ports
Test method:
To unplug all the terminals sockets of this device, and do the Insulation resistance test for each
circuit above with an electronic or brushless insulation tester.
On completion of the insulation resistance tests, ensure all external wiring is correctly
reconnected to the device.
Check that the external wiring is correct to the relevant device diagram and scheme diagram.
Ensure as far as practical that phasing/phase rotation appears to be as expected.
Check the wiring against the schematic diagram for the installation to ensure compliance with the
customer’s normal practice.
Date: 2015-07-29
12 Commissioning
WARNING!
Energize this device ONLY if the power supply is within the specified operating range in
the Chapter “Technical Data”.
The device only can be operated under the auxiliary power supply depending on the device’s
nominal power supply rating.
The incoming voltage must be within the operating range specified in Chapter “Technical Data”,
before energizing the device, measure the auxiliary supply to ensure it within the operating range.
Other requirements to the auxiliary power supply are specified in Chapter “Technical Data”. See
this section for further details about the parameters of the power supply.
The current and voltage transformer connections must remain isolated from the device for these
checks. The trip circuit should also remain isolated to prevent accidental operation of the
associated circuit breaker.
Connect the device to DC power supply correctly and turn the device on. Check program version
and forming time displayed in command menu to ensure that are corresponding to what ordered.
If the time and date is not being maintained by substation automation system, the date and t ime
should be set manually.
Set the date and time to the correct local time and date using menu item “ Clock”.
In the event of the auxiliary supply failing, with a battery fitted on CPU board, the time and date
will be maintained. Therefore when the auxiliary supply is restored the time and date will be
correct and not need to set again.
To test this, remove the auxiliary supply from the device for approximately 30s. After being
re-energized, the time and date should be correct.
On power up, the green LED “HEALTHY” should have illuminated and stayed on indicating that
the device is healthy.
The device has latched signal devices which remember the state of the trip, auto-reclose when
the device was last energized from an auxiliary supply. Therefore these indicators may also
illuminate when the auxiliary supply is applied. If any of these LEDs are on then they should be
Date: 2015-07-29
12 Commissioning
reset before proceeding with further testing. If the LED successfully reset, the LED goes out.
There is no testing required for that that LED because it is known to be operational.
It is likely that alarms related to voltage transformer supervision will not reset at this stage.
Apply the rated DC power supply and check that the “HEALTHY” LED is lighting in green. We
need to emphasize that the “HEALTHY” LED is always lighting in operation course except that the
equipment find serious errors in it.
Produce one of the abnormal conditions listed in Chapter “Supervision”, the “ALARM ” LED will
light in yellow. When abnormal condition reset, the “ALARM ” LED extinguishes.
NOTICE!
The closing circuit should remain isolated during these checks to prevent accidental
operation of the associated circuit breaker.
This test verified that the accuracy of current measurement is within the acceptable tolerances.
Apply rated current to each current transformer input in turn; checking its magnitude using a
multimeter/test set readout. The corresponding reading can then be checked in th e devices menu.
NOTICE!
The closing circuit should remain isolated during these checks to prevent accidental
operation of the associated circuit breaker.
This test verified that the accuracy of voltage measurement is within the acceptable tolerances.
Apply rated voltage to each voltage transformer input in turn; checking its magnitude using a
multimeter/test set readout. The corresponding reading can then be checked in the devices menu.
This test checks that all the binary inputs on the equipment are functioning correctly.
The binary inputs should be energized one at a time, see external connection diagrams for
terminal numbers.
Ensure that the voltage applied on the binary input must be within the operating range.
The status of each binary input can be viewed using device menu. Sign “1” denotes an energized
input and sign “0” denotes a de-energized input.
1. Confirm the external wiring to the current and voltage inputs is correct.
Date: 2015-07-29
12 Commissioning
However, these checks can only be carried out if there are no restrictions preventing the
tenderization of the plant being protected.
Remove all test leads, temporary shorting leads, etc. and replace any external wiring that has
been removed to allow testing.
If it has been necessary to disconnect any of the external wiring from the device in order to
perform any of the foregoing tests, it should be ensured that all connections are replaced in
accordance with the relevant external connection or scheme diagram. Confirm current and
voltage transformer wiring.
If the device is in a new installation or the circuit breaker has just been maintained, the circuit
breaker maintenance and current counters should be zero. If a test block is installed, remove the
test plug and replace the cover so that the device is put into service.
Ensure that all event records, fault records and alarms have been cleared and LED’s has been
reset before leaving the device.
Date: 2015-07-29
12 Commissioning
Date: 2015-07-29
13 Maintenance
13 Maintenance
Table of Contents
13 Maintenance .................................................................................... 13-a
13.1 Appearance Check .................................................................................................13-3
Date: 2015-07-29
13 Maintenance
This device is designed to require no special maintenance. All measurement and signal
processing circuit are fully solid state. All input modules are also fully solid state. The output relays
are hermetically sealed.
Since the device is almost completely self-monitored, from the measuring inputs to the output
relays, hardware and software defects are automatically detected and reported. The
self-monitoring ensures the high availability of the device and generally allows for a corrective
rather than preventive maintenance strategy. Therefore, maintenance checks in short intervals are
not required.
Operation of the device is automatically blocked when a hardware failure is detected. If a problem
is detected in the external measuring circuits, the device normally only provides alarm messages.
2. It is only allowed to plug or withdraw device board when the supply is reliably switched off.
Never allow the CT secondary circuit connected to this equipment to be opened while the
primary system is live when withdrawing an AC module. Never try to insert or withdraw the
device board when it is unnecessary.
3. Check weld spots on PCB whether they are well soldered without any rosin joint. All dual
inline components must be well plugged.
When a failure is detected by supervision, a remote alarm is issued and the failure is indicated on
the front panel with LED indicators and LCD display. It is also recorded in the event record.
Failures detected by supervision are traced by checking the “ Superv State” screen on the LCD.
Date: 2015-07-29
13 Maintenance
WARNING!
Module can ONLY be replaced while the device power supply is switched off.
ONLY appropriately trained and qualified personnel can perform the replacement by
strictly observing the precautions against electrostatic discharge.
WARNING!
Five seconds is NECESSARY for discharging the voltage. Hazardous voltage can be
present in the DC circuit just after switching off the DC power supply.
CAUTION!
Take anti-static measures such as wearing an earthed wristband and placing modules
on an earthed conductive mat when handling a module. Otherwise, electronic
components could be damaged.
CAUTION!
If the failure is identified to be in the device module and the user has spare modules, the user can
recover the device by replacing the failed modules.
Repair at the site should be limited to module replacement. Maintenance at the component level is
not recommended.
Check that the replacement module has an identical module name (AI, PWR, MON, BI, BO, etc.)
and hardware type-form as the removed module. Furthermore, the MON module replaced should
have the same software version. In addition, the AI and PWR module replaced should have the
same ratings.
The module name is indicated on the top front of the module. The software version is indicated in
LCD menu “Information”->“Version Info”.
1) Replacing a module
Short circuit all AC current inputs and disconnect all AC voltage inputs
After replacing the MON module, input the application-specific setting values again.
Unplug the ribbon cable on the front panel by pushing the catch outside.
13.4 Cleaning
Before cleaning the device, ensure that all AC/DC supplies, current transformer connections are
isolated to prevent any chance of an electric shock whilst cleaning. Use a smooth cloth to clean
the front panel. Do not use abrasive material or detergent chemicals.
13.5 Storage
The spare device or module should be stored in a dry and clean room. Based on IEC standard
60255-1 the storage temperature should be from -40°C to +70°C, but the temperature of from 0°C
to +40°C is recommended for long-term storage.
Date: 2015-07-29
13 Maintenance
Table of Contents
14 Decommissioning and Disposal .................................................. 14-a
14.1 Decommissioning ...................................................................................................14-3
14.2 Disposal.....................................................................................................................14-3
Date: 2015-07-29
14 Decommi ssioning and Di sposal
Date: 2015-07-29
14 Decommi ssi oning and Di sposal
14.1 Decommissioning
DANGER!
Switch OFF the circuit breaker for primary CTs and VTs BEFORE disconnecting the
cables of AI module.
WARNING!
Switch OFF the external miniature circuit breaker of device power supply BEFORE
disconnecting the power supply cable connected to the PWR module.
WARNING!
1. Switching off
To switch off this device, switch off the external miniature circuit breaker of the power supply.
2. Disconnecting cables
Disconnect the cables in accordance with the rules and recommendations made by relational
department.
3. Dismantling
The device rack may now be removed from the system cubicle, after which the cubicles may
also be removed.
14.2 Disposal
NOTICE!
Strictly observe all local and national laws and regulations when disposing the device.
Date: 2015-07-29
14 Decommi ssioning and Di sposal
Date: 2015-07-29
15 Manual Version Hi story
Date: 2015-07-29
15 Manual Version Hi story
Date: 2015-07-29