You are on page 1of 2

TYPE TEST REPORT

Customer : SUN INTERNATIONAL CORP Date : 09/09/2022


Sales Order : FPO 2216

SUMMERY OF TEST RESULTS


To whom it may concern.

We hereby certify that the products supplied on this order comply with the requirements of the
designated norms and that they have been manufactured and tested in compliance with the
following international standards:-

IEC / EN 61439-1 2009

BUS BAR INSULATOR

SAMPLE DESCRIPTION
Low Tension Insulator Made of Polyester Resins With Brass Inserts
Operating Rated voltage 600 V – 3000 V
Glaze Brick Red
Type Conical Type Bus Bar Insulator

TEST DETAILS
1 Dry Power Frequency Voltage Withstand Test
2 Wet Power Frequency Voltage Withstand Test
3 Cantilever Load Withstand Test

Unless otherwise specified above, we certify that the supplies and services detailed above
have been inspected and tested in accordance with the conditions and requirements of the
contract of the purchase order and unless otherwise noted below, conform in all respects to the
specification(s) and drawing(s) relevant thereto.

For AFTEC INTERNATIONAL

AFTEC INTERNATIONAL, P.O.Box : 146, Road Town, Tortola, British Virgin Islands
Tel : 1-284-4942434, Fax : 1-284-4943754, Email : Info@aftec.org.uk
TYPE TEST REPORT
Customer : SUN INTERNATIONAL CORP Date : 09/09/2022
Sales Order : FPO 2216

SUMMERY OF TEST RESULTS

ATMOSPHERIC CONDITION
Dry bulb temperature 31°C
Wet bulb temperature 29°C
Atmospheric Pressure 754 mm of Hg

Sr.
Test Conducted Test Requirement Obtained Results Remarks
No
1 Dry Power The test voltage of 3 Kv The sample The sample
Frequency rms corrected to WITHSTOOD the test CONFORMS to the
Voltage reference atmospheric voltage satisfactorily. test requirement
Withstand Test condition shall be applied
between the H.V.
Terminal & earth for 1
minute duration.
2 Wet Power The test voltage of 3 Kv The sample The sample
Frequency rms corrected to WITHSTOOD the test CONFORMS to the
Voltage reference atmospheric voltage satisfactorily. test requirement
Withstand Test condition shall be applied
between the H.V.
Terminal & earth for 1
minute duration under
artificial rain fall
condition.
3 Cantilever Load The insulator broke at
Withstand Test -------------------- the load of 3.28 Kn. --------------------

For AFTEC INTERNATIONAL

AFTEC INTERNATIONAL, P.O.Box : 146, Road Town, Tortola, British Virgin Islands
Tel : 1-284-4942434, Fax : 1-284-4943754, Email : Info@aftec.org.uk