Professional Documents
Culture Documents
www.elsevierhealth.com/journals/jhin
Division of Building Science and Technology, City University of Hong Kong, Tat Chee Avenue, Kowloon,
Hong Kong SAR, China
Introduction
periodically by specialist teams. In Hong Kong, the and any microbes within them.4 Woods et al.
design of operating theatres is based on the UK described the boundary layer that carries skin
Health Technical Memorandum (HTM).1 According flakes from a standing person to the surrounding
to HTM 2025, the downflow of supply air from a air.5 From these data, a typical generation rate of
laminar flow ventilation system should cover a 6 g/min of 7.5 mm (mean diameter) skin flakes for a
minimum projected area of 2.8 m by 2.8 m, which clothed staff member standing in front of an
accommodates the surgical site and instruments. operating table was estimated. Obviously, the
The zone boundary enclosing the supply air diffuser tightness and coverage of the clothing, masks and
should be provided with either a full wall or a caps have a significant effect on the amount of skin
partial wall; the latter should terminate at a flakes transferred to the air. Zamuner referred to
maximum of 2 m from floor level. Pressure stabil- the findings of Kethley that a surgeon bending over
izers on partition walls have the dual purpose of the wound site in a laminar airflow (LAF) system
directing excess air to neighbouring spaces and could be a source of as many as 1000 airborne
maintaining the room pressure differentials. particles/min.6 When the surgical team is working
In many operating theatres around the world, air near the operating table, everyone is subject to an
conditioning and ventilation performance do not airborne infection risk, particularly the patient
comply with up-to-date engineering standards. because of his/her weakness and open wound.
Problems include different forms of terminal The possible number of infectious particles that can
devices, different air velocities at the supply be released during the use of power tools at the
diffuser, different levels of room pressurization, wound site has not been quantified to date.
and omission of the partial wall. An important There are two routes of infection from infectious
reason for this is periodic renovation work at older particles: (i) inhalation, and (ii) by settling directly
hospitals where the site and financial constraints on a susceptible area, such as a wound, or on
lead to deviations. Another reason lies in the instruments or dressings that subsequently come
differences in user behaviour. It is noted that flow into contact with the wound. Small particles
obstructions and heat dissipation from people, emitted from sterilized items do not carry bacteria
lamps and equipment can easily disturb air and therefore will not cause a problem. This
movement. renders meaningless any tests using a particle
In our study, computational fluid dynamics (CFD) counter to indicate the presence of airborne
simulation was used to examine the dispersion of contaminants during surgery.7 Consequently, test-
colony forming units (cfu) in a standard operating ing for the absence of bacteria must be carried out
theatre in Hong Kong. The investigation examined by a culture method.
the effectiveness of the laminar flow system in: (i) Whyte et al. suggested the following standards at
preventing infectious particles on staff from reach- three locations in the ultra-clean operating theatre
ing the patient’s wound; and (ii) protecting the for joint replacement surgery:8
surgical staff from bacteria released from the
wound site. The effects of the following design † 0.5 cfu/m3 for the filtered air supply;
aspects on cfu dispersion were also investigated: † 10 cfu/m3 within 0.03 m of the wound during the
operation; and
† reduced flow velocity at the supply diffuser; † 20 cfu/m3 in the rest of the working area of the
† no partial walls around the supply diffuser; clean air system.
† change of medical lamp position; and
† reduced medical lamp heat flux. Lidwell stated that a fully effective system,
including special clothing, should aim for air
contamination levels below 1 cfu/m3.9 In general
Airborne infection risk consensus with this target, Whyte further suggested
a count of 10 cfu/m3 as the acceptable maximum
The major source of airborne contaminants in the value.10 These recommendations formed the basis
operating theatre is from the surgical team.2 A of the HTM 2025 specification.
person releases about 10 million particles/day. The Effectiveness of an LAF system is accomplished
release rate is 10 000 particles/min when walking. by the provision of a high-efficiency particulate air
About 5–10% of these particles (2.5–20 mm in size) filter (and pre-filters) upstream from the supply air
carry bacteria.3 The patient is not usually a diffuser. The flow velocity at the supply diffuser is
significant contaminant source because his/her crucial to ensure sufficient air movement at the
movement is minimal. However, power tools have operating plane, i.e. at the level of the patient on
the potential to create an aerosol from the tissues the operating table. HTM quotes the average
140 T.T. Chow, X.Y. Yang
minimum air velocity as 0.38 m/s at 2 m from the (freshness) of air at discrete locations. The bound-
floor when a partial wall is used. The corresponding ary conditions for a UCV system can be the relative
air velocity at the operating plane will then provide pressures of the neighbouring spaces, the flow
a washing effect against settlement of airborne velocity at terminal units (diffusers, stabilizers and
particles. With a minimum velocity of 0.2 m/s, the grilles), temperature and humidity levels of air at
air stream can readily remove contaminants the entry and exit points, and the surface tempera-
released from the human body. The design target, tures and heat fluxes of the enclosing walls, lamps,
therefore, is to achieve a contaminant level of less equipment and human beings. When the flow is
than 10 cfu/m3 in the critical area when the staff steady (i.e. the boundary conditions are fixed),
wear conventional cotton clothing, or less than results such as velocity and temperature represent
1 cfu/m3 when special clothing or a body exhaust the time averages, but when the flow is unsteady
system is in use. (i.e. the boundary conditions change with time),
Direct measurement and numerical computation the results are ensemble averages.
are the two main approaches used in the assess- Using CFD analysis, Chen et al. showed that a
ment of operating theatre airflow pattern and higher air inflow rate and a larger air inlet area are
airborne particle concentrations. The most realistic desirable for contaminant control, but these are
information on airflow can be obtained by direct detrimental to the thermal comfort of the staff.15
measurement. The relevant studies contributing to Particle concentrations in different parts of the
design of ultra-clean ventilation (UCV) systems room were found to be very sensitive to the location
were mainly conducted between the 1960s and of the particle sources. Higher heat sources had
the 1980s.11,12 For examining the airflow perform- little or negligible effect on particle distribution
ance in relation to a given UCV design or renovation and thermal comfort. This finding concurred with
work, CFD is extremely useful. This technique the work of Luscuere et al., which pointed out that
underwent rapid development in the 1990s, and is the physical obstruction of the lamp seemed to be
now well recognized as a powerful and economical far more important than its heat dissipative
tool in parametric studies that involve indoor air disturbance.16 Tinker and Roberts applied the
distribution and contaminant dispersion. Readers standard CFD model in an operating theatre in the
can refer to standard texts such as Awbi, and UK; the convective plume caused by the medical
Etheridge and Sandberg for technical details of the lamp was only noticeable in low-velocity airflows,
applications of CFD in building-related studies.13,14 typically below 0.1 m/s.17 At 0.3 m/s or more, the
The following section serves as a brief introduction plume was found to be non-existent. They also
of the technique. carried out full-scale experimental validation of the
simulation results, and found that the discrepancies
between simulation and measurements in tempera-
ture and air speed were of the order of 2% and 5%,
Numerical analysis by CFD respectively. It was highlighed that the length of
the partial wall would not affect the contamination
CFD is a complex and rapidly evolving field of around the wound site. More reviews of previous
development. It refers to the numerical technique work in this area can be found elsewhere.12
that provides solutions to a set of conservation There are limitations in the application of CFD
equations governing a fluid flow field, such that the such as grid-dependent solutions, slow or uncertain
flow variables (e.g. temperature and velocity) at all convergence, and the need for a skilled operator.
points in the field can be determined. However, with improvements in user-friendliness of
In the prediction of airflow in an operating the software, the difficulties are gradually being
theatre, the flow equations must account for reduced. Other limitations, which are more related
turbulence and buoyancy. The starting point is to to physical science, are the empiricisms employed
subdivide the flow field (room space) into a number for the coefficients in the equations and, particu-
of finite volumes (cells), so that the conservation larly, the empirical wall functions.
equations for mass, momentum, energy and species The majority of CFD applications in ventilation
concentration can be established for each cell. For design are likely to be for steady flow, but there is
some given boundary conditions and assumptions, no fundamental limitation to such flows. In prin-
the set of equations are solved together by iteration ciple, any type of unsteady flow can be treated. A
for the temperature, pressure and velocity vectors. transient flow occurs when an initially steady state
It is also possible to determine the distribution of is disturbed by a change in the boundary conditions.
water vapour (hence relative humidity) or particu- An example of this is when a door between two
lates (e.g. cfus), and to assess the mean age rooms is opened. The changing boundary conditions
Ventilation performance in the operating theatre against airborne infection 141
of the flow field are then at the positions of the door medical equipment at 650 W on all exposed
and the pressure stabilizers. surfaces. Heat flux from each of the two medical
lamps was 250 W, released at the downward sur-
face. All heat and contaminant sources were
assumed to be uniform at the emitting surfaces.
The computer simulation model In this CFD model, a non-uniform rectangular grid
of approximately 140 000 cells was used. Simu-
The physical arrangement of the operating theatre lations were executed using the standard k–3 model
used in this study was based on a typical layout in a of the commercial software CFX4.3.19 A detailed
relatively new hospital in Hong Kong. Figure 1 shows description of this simulation approach including
the isometric view. The overall dimensions were
the validation work can be found in Chow et al.20
7.8 m (L)!6.6 m (W)!2.7 m (H) in the X, Y and Z
Seven simulation cases were performed, as
directions, respectively. All surgical staff members
follows.
(Staff 1–7) were assumed to be in upright stationary
positions surrounding the patient, who lay on the
operating table with the head towards the positive Case 1
Y direction. In this model, the locations of the staff
members, medical lamps and equipment relative to This was the reference condition, as shown in Figure
the operating table were according to the DIN 4799 1. The design complied fully with the HTM require-
specification.18 ments, with the partial wall terminating at 2 m
In the numerical grid, the surgical staff and from floor level, an air velocity of 0.38 m/s at the
patient were treated as rectangular solid boxes, supply diffuser (hence the same flow velocity at the
each of size 0.5 m!0.2 m!1.7 m. Each person partial wall outlet position), the main medical lamp
released a heat flux of 100 W from the exposed at the centre plane of the operating table near to
surfaces. At the same time, each surgical staff the patient’s head, and the satellite lamp at one
member released infectious particles at a rate of side of the operating table.
100 cfu/min from his/her surface facing the
patient. A power tool was assumed to be working
on the wound, with an arbitrary bacterial release Case 2
rate of 400 cfu/min at the patient’s waist position
(on the upper surface). Heat energy was considered Design as in Case 1, but with the flow velocity
to be released from each of the two pieces of reduced by one-third (0.25 m/s).
Figure 2 Airflow patterns at section xZ4.2 m cutting across the midplane of the operating table.
144 T.T. Chow, X.Y. Yang
Figure 3 Accumulated infectious particle concentration contours at zZ1.1 m operating plane for (a) Case 1
(reference condition), (b) Case 2 (supply velocity: 0.25 m/s), (c) Case 3 (supply velocity: 0.19 m/s), (d) Case 4 (supply
velocity: 0.13 m/s), (e) Case 5 (without partial wall), and (f) Case 6 (changed main medical lamp position).
occasion to another. There appears to be no good to 0.25 m/s, the concentration at the position of the
reason to reduce the supply velocity for the sake of wound is around 8 cfu/m3, as in Figure 3(b), and
thermal comfort as the comfort level can be fine- exceeds 10 cfu/m3 at the position of the head. This
tuned by changing the thermostat setting. indicates a failure of the washing effect. At 0.13 m/s,
The particulate concentration in the operating as in Figure 3(d), the concentration is over 10 cfu/m3
theatre (particularly in the ‘clean’ zone) is higher for the entire body of the patient. The concentration
when the room air change rate decreases and the above the equipment table is about 8 cfu/m3. As the
bacterial concentration at the patient’s position supply velocity gradually reduces from 0.38 m/s to
increases. For a reduction of supply velocity by 33% 0.13 m/s, the number of surgical staff experiencing
Ventilation performance in the operating theatre against airborne infection 145
Figure 4 Concentration contours of infectious particle from patient’s waist at zZ1.6 m breathing level for (a) Case 1
(reference condition), (b) Case 2 (supply velocity: 0.25 m/s), (c) Case 3 (supply velocity: 0.19 m/s), (d) Case 4 (supply
velocity: 0.13 m/s), (e) Case 5 (without partial wall), and (f) Case 6 (changed main medical lamp position).
high bacterial counts increases, as visualized from prevent the ‘short circuit’ of flow between the supply
the expansion of the unacceptably high concen- diffuser and a high-level outlet. Figure 2(e) shows the
tration region in Figure 4(a–d). extent of disturbance on the ingress of surrounding air
in the absence of a partial wall. Figure 4(e) indicates
that Staff 1 and 2 were exposed to bacterial
Partial wall concentrations above 10 cfu/m3 due to an increased
entrainment (air ingress) effect at the supply diffuser
The purpose of the partial wall is to maintain the boundary. Notwithstanding this, a slightly better
unidirectional downward flow of supply air and to performance at the patient’s position can be
146 T.T. Chow, X.Y. Yang
observed when comparing Figure 3(e) with Figure demonstrated CFD in a standard operating theatre
3(a). The results recorded a concentration reduction environment in Hong Kong, and presented seven
at the patient’s position to below 2 cfu/m3. A short cases of CFD simulation. Flow velocity at the supply
circuit of flow at Stabilizer 2 was found in Case 5 but diffuser was identified as one of the most important
the extent was not detrimental. factors in governing the dispersion of airborne
infectious particles. The position of the medical
lamps was also found to be critical.
Medical lamp The design of an ultra-clean airflow system can
be a complex issue. A successful outcome depends
Moving the main medical lamp from its original not only on overcoming the technical obstacles, but
position at the midplane of the operating table can also on solving human factors such as user habits.
make the flow smoother over the patient in this More work needs to be done in this area, and in
plane, as shown in Figure 2(f). There is no apparent parallel, more investigations should be conducted
evidence of an overall improvement in bacterial on the combined effect of various determining
dispersion, however, when comparing Figure 3(a) factors. The CFD approach, together with continu-
with Figure 3(f) (other than the head position of the ous monitoring and periodic air sampling at the
patient), and Figure 4(a) with Figure 4(f). The surgical site, is expected to offer a new dimension
overall airflow pattern depends on the relative in related studies.
positions of personnel, lamps and equipment,
whereas the contaminant dispersion also depends
on the locations of the contaminant sources.
Obviously the obstruction effect of the medical
Acknowledgements
lamp carries more weight than its heat dissipation
The work described in this paper was supported by a
effect. In principle, Cases 1 and 7 gave almost the
grant from the Research Grants Council of the Hong
same results.
Kong Special Administrative Region, China (project
no. 7001609).
Human activities
10. Whyte W. The role of clothing and drapes in the operation of operating theatres with the help of computer flow
room. J Hosp Infect 1988;11(Suppl C):2—17. modeling. Proceedings of Indoor Air 1993, Helsinki, Finland,
11. Stacey A, Humphreys H. A UK historical perspective on vol. 5, 1993. p. 575—580.
operating theatre ventilation. J Hosp Infect 2002;52:77—80. 17. Tinker JA, Roberts D. Indoor air quality and infection
12. Chow TT, Yang XY. Ventilation performance in operating problems in operating theatres. Proceedings of EPIC 1998,
theatre against airborne infection: review of research Lyon, France, vol. 1, 1998. p. 285—290.
activities and practical guidance. J Hosp Infect 2004;56: 18. DIN 4799. Heating, ventilation and air conditioning. Testing
85—92. of air distribution systems serving operating theatres.
13. Awbi HB. Ventilation of buildings. London: E&FN Spon; 1999. Berlin: Beuth Verlag; 1990.
14. Etheridge D, Sandberg M. Building ventilation: theory and 19. CFX 4.3. Flow solver user guide. UK: Harwell Laboratory;
measurement. Chichester, UK: Wiley; 1996. 1999.
15. Chen Q, Jiang Z, Moser A. Control of airborne particle 20. Chow TT, Yang XY. Performance of ventilation system in a
concentration and draught risk in an operating room. Indoor
non-standard operating room. Build Environ 2003;38:
Air 1992;2:154—167.
1401—1411.
16. Luscuere PG, Lemaire TD, Ham PJ. Improvement capabilities