MAINTENANCE (ELECTRICAL) DOC SOP/08/ELE/
SMP/OCPL/ELE/
Standard
SOPMaintenance
of HT Motor &Procedure
Feeder for NO. 002 002
HT MOTOR
7 Check the space heater of motor & of the cable chamber/ panel.
8 Tighten all the control and power connections.
9 Check all the control fuses for proper rating. Check the LED
indication lamps condition. Repair/replace if faulty.
10 Clean accumulated dirt from the motor body. Check the general
structure of the motor for signs of any corrosion or other
damages.
11 Check the cooling tubes condition. The tubes should be clear
from any obstruction. If required do the tube cleaning.
12 Check all earthing connections on the motor for cleanliness and
tightness. Replace the rusted nut bolts if required.
ISSUE / REV. NO DATE REVIEWED & ISSUED BY APPROVED BY
1/00 01/04/2022
01/02/2013
ELECTRICAL ENGINEER
Manager – Electrical DGM
Vice ELECTRICAL
President - Electrical
Page 1 of 2
QEHS DEPARTMENTAL MANUAL BORL, Bina
MCMP, HEMGIRE
14 Open the motor terminal box having star point of the motor. Engg/Supervisor/AM
Check the tightness of connections and any abnormalities. In
case of motor having differential protection, check the
tightness of CT terminals
15 Check and tighten the motor canopy. While boxing up the
terminal boxes apply little grease on the bolts.
16 Check the LCS for any abnormality. Clean the LCS. Tighten the
connections. Do the proper housekeeping of the area.
17 Ensure cable support/gland is firmly secured. Ensure that all cable
glands are tight and there is no visible damage to cabling external
to the motor.
18 Check Insulation Resistance (IR) of HT Motor and Power cable
with HT Meggar after final box-up / completing the job.
6. RECORDS:
1/00 01/04/2022
01/02/2013
ELECTRICAL ENGINEER
Manager – Electrical DGM
Vice ELECTRICAL
President - Electrical