CALCULATION SUMMARY

Project Name : AutoPLAZA-Puruchuco Project Location:

Drawing No. : City:

Design Areas
Design Area Calc. Mode Occupancy Area of Total Water Pressure @ Min. Min. Min. Flow Calculated Hose Margin To
Name (Model) Application Source Density Pressure Heads Streams Source

(sq.ft) (gpm) (psi) (gpm/sq.ft) (psi) (gpm) # (gpm) (psi)

Required
DesignArea_1 Demand(HW) 0 599.097 0 15.68 63.796 10 100 0
68.85

Required
DesignArea_2 Demand(HW) 0 640.857 0 15.68 44.929 12 100 0
34.68

Required
DesignArea_3 Demand(HW) 0 660.766 0 15.68 47.863 12 100 0
33.18

File: C:
Date 14/09/2022 \Users\Lizandro\Desktop\Proyectos2\53.GyG.MOTORPlaza\deLizandro.11082022\calculo4.7_diametros.original
Page 1
es.tycx
Copyright © 2002-2016 Tyco Fire Protection Products
Job : Node Labels: Node Reference
Pipe Labels: Pipe Reference

Diagram for Initial System

File: C:\Users\Lizandro\Desktop\Proyectos2\53.GyG.MOTORPlaza\deLizandro.11082022\calculo4.7_diametros.originales.tycx
Date 14/09/2022 Copyright © 2002-2016 Tyco Fire Protection Products Page 2
Job : Hydraulic Calculations / Fluid Delivery Time Analysis

Node Data : Initial System

Node # Hgroup K-Factor Elevation X


Type Fitting Stat. Pres. Coverage Y
gpm/psi½ m m
psi sq.ft m
src1 SUPPLY 0
-0.75
SUPPLY 0 0
n2 NODE 0
-0.75
NODE us.90 0 -0.737
n22 NODE 3.845
-0.75
NODE us.90 0 -0.737
n23 NODE 3.845
-0.75
NODE us.Tee 0 -1.231
n24 NODE -8.233
-0.75
NODE us.90 0 -1.231
n6 NODE -6.802
-0.75
NODE us.Tee 0 -1.231
n112 NODE -3.22
-0.75
NODE us.Tee 0 -1.231
n8 NODE -1.339
-0.75
NODE 0 -1.231
n9 NODE -0.57
-0.75
NODE 0 -1.231
n12 NODE 7.408
-0.75
NODE 0 -1.231
n14 NODE 12.716
-0.75
NODE us.90 0 -1.231
n15 NODE 12.716
-0.75
NODE us.90 0 1.06
n16 NODE 13.704
-0.75
NODE us.Tee 0 1.06
n17 NODE 18.205
-0.75
NODE us.Tee 0 1.06
n18 NODE 22.004
-0.75
NODE us.Tee 0 1.06
n19 NODE 26.505
-0.75
NODE us.Tee 0 1.06
n20 NODE 30.304
-0.75
NODE us.Tee 0 1.06
n40 NODE 31.901
-0.75
NODE us.90 0 1.06
n5 NODE -8.233
-0.75
NODE us.Tee 0 -28.261
n25 NODE -6.802
-0.75
NODE us.Tee 0 -28.261
n123 NODE -3.22
-0.75
NODE us.Tee 0 -28.261
n27 NODE -1.339
-0.75
NODE 0 -28.261
n28 NODE -0.57
-0.75
NODE 0 -28.261
n35 NODE 13.704
-0.75
NODE us.Tee 0 -28.261
n36 NODE 18.205
-0.75
NODE us.Tee 0 -28.261
n37 NODE 22.004
-0.75
NODE us.Tee 0 -28.261

File: C:
\Users\Lizandro\Desktop\Proyectos2\53.GyG.MOTORPlaza\deLizandro.11082022\calculo4.7_diametros.original
es.tycx
Date 14/09/2022 Copyright © 2002-2016 Tyco Fire Protection Products Page 3
Job : Hydraulic Calculations / Fluid Delivery Time Analysis

Node Data : Initial System

Node # Hgroup K-Factor Elevation X


Type Fitting Stat. Pres. Coverage Y
gpm/psi½ m m
psi sq.ft m
n38 NODE 26.505
-0.75
NODE us.Tee 0 -28.261
n39 NODE 30.304
-0.75
NODE us.Tee 0 -28.261
n21 NODE 31.901
-0.75
NODE us.90 0 -28.261
n55 NODE -14.995
-0.75
NODE us.90 0 -1.965
n56 NODE -13.096
-0.75
NODE us.Tee 0 -1.965
n57 NODE -11.196
-0.75
NODE us.90 0 -1.965
n58 NODE -14.995
-0.75
NODE us.90 0 -4.499
n45 NODE -13.096
-0.75
NODE us.Tee 0 -4.499
n60 NODE -11.196
-0.75
NODE us.90 0 -4.499
n61 NODE -14.995
-0.75
NODE us.90 0 -7.731
n48 NODE -13.096
-0.75
NODE us.Tee 0 -7.731
n63 NODE -11.196
-0.75
NODE us.90 0 -7.731
n64 NODE -14.995
-0.75
NODE us.90 0 -10.265
n65 NODE -13.096
-0.75
NODE us.Tee 0 -10.265
n66 NODE -11.196
-0.75
NODE us.90 0 -10.265
n68 -8.233
NODE -0.75
NODE 0 -8.998
n69 NODE -14.995
-0.75
NODE us.90 0 -12.799
n70 NODE -13.096
-0.75
NODE us.Tee 0 -12.799
n71 NODE -11.196
-0.75
NODE us.90 0 -12.799
n73 NODE -14.995
-0.75
NODE us.90 0 -16.031
n59 NODE -13.096
-0.75
NODE us.Tee 0 -16.031
n74 NODE -11.196
-0.75
NODE us.90 0 -16.031
n76 NODE -14.995
-0.75
NODE us.90 0 -18.565
n62 NODE -13.096
-0.75
NODE us.Tee 0 -18.565
n78 NODE -11.196
-0.75
NODE us.90 0 -18.565
n80 NODE -14.995
-0.75
NODE us.90 0 -21.099

File: C:
\Users\Lizandro\Desktop\Proyectos2\53.GyG.MOTORPlaza\deLizandro.11082022\calculo4.7_diametros.original
es.tycx
Date 14/09/2022 Copyright © 2002-2016 Tyco Fire Protection Products Page 4
Job : Hydraulic Calculations / Fluid Delivery Time Analysis

Node Data : Initial System

Node # Hgroup K-Factor Elevation X


Type Fitting Stat. Pres. Coverage Y
gpm/psi½ m m
psi sq.ft m
n79 NODE -13.096
-0.75
NODE us.Tee 0 -21.099
n81 NODE -11.196
-0.75
NODE us.90 0 -21.099
n82 NODE -8.233
-0.75
NODE us.Tee 0 -17.816
n44 NODE -14.995
-0.75
NODE us.90 0 -24.465
n42 NODE -13.096
-0.75
NODE us.Tee 0 -24.465
n46 NODE -11.196
-0.75
NODE us.90 0 -24.465
n72 NODE -13.096
-0.75
NODE us.Tee 0 -27.265
n47 NODE -14.995
-0.75
NODE us.90 0 -27.265
n49 NODE -11.196
-0.75
NODE us.90 0 -27.265
n50 NODE -14.995
-0.75
NODE us.90 0 -30.965
n77 NODE -13.096
-0.75
NODE us.Tee 0 -30.965
n52 NODE -11.196
-0.75
NODE us.90 0 -30.965
n51 NODE -13.096
-0.75
NODE us.Tee 0 -34.897
n41 NODE -14.995
-0.75
NODE us.90 0 -34.897
n43 NODE -11.196
-0.75
NODE us.90 0 -34.897
n83 NODE -5.008
-0.75
NODE us.Tee 0 -28.262
n87 NODE -6.801
-0.75
NODE us.90 0 -31.32
n85 NODE -5.008
-0.75
NODE us.Tee 0 -31.32
n89 NODE -3.214
-0.75
NODE us.90 0 -31.32
n84 NODE -6.801
-0.75
NODE us.90 0 -35.23
n88 NODE -5.008
-0.75
NODE us.Tee 0 -35.23
n86 NODE -3.214
-0.75
NODE us.90 0 -35.23
n90 NODE -5.008
-0.75
NODE us.90 0 -35.825
n91 NODE 1.924
-0.75
NODE us.90 0 -35.825
n92 NODE -6.802
-0.75
NODE us.Tee 0 -1.965
n93 NODE -3.22
-0.75
NODE us.Tee 0 -1.965

File: C:
\Users\Lizandro\Desktop\Proyectos2\53.GyG.MOTORPlaza\deLizandro.11082022\calculo4.7_diametros.original
es.tycx
Date 14/09/2022 Copyright © 2002-2016 Tyco Fire Protection Products Page 5
Job : Hydraulic Calculations / Fluid Delivery Time Analysis

Node Data : Initial System

Node # Hgroup K-Factor Elevation X


Type Fitting Stat. Pres. Coverage Y
gpm/psi½ m m
psi sq.ft m
n94 NODE -6.802
-0.75
NODE us.Tee 0 -4.499
n95 NODE -6.802
-0.75
NODE us.Tee 0 -7.731
n96 NODE -6.802
-0.75
NODE us.Tee 0 -10.265
n97 NODE -6.802
-0.75
NODE us.Tee 0 -12.799
n98 NODE -6.802
-0.75
NODE us.Tee 0 -16.031
n99 NODE -6.802
-0.75
NODE us.Tee 0 -18.565
n100 NODE -6.802
-0.75
NODE us.Tee 0 -21.099
n101 NODE -6.802
-0.75
NODE us.Tee 0 -24.465
n102 NODE -6.802
-0.75
NODE us.Tee 0 -27.265
n103 NODE -3.22
-0.75
NODE us.Tee 0 -4.499
n104 NODE -3.22
-0.75
NODE us.Tee 0 -7.731
n105 NODE -3.22
-0.75
NODE us.Tee 0 -10.265
n106 NODE -3.22
-0.75
NODE us.Tee 0 -12.799
n107 NODE -3.22
-0.75
NODE us.Tee 0 -16.031
n108 NODE -3.22
-0.75
NODE us.Tee 0 -18.565
n109 NODE -3.22
-0.75
NODE us.Tee 0 -21.099
n110 NODE -3.22
-0.75
NODE us.Tee 0 -24.465
n111 NODE -3.22
-0.75
NODE us.Tee 0 -27.265
n124 NODE 1.924
-0.75
NODE us.Tee 0 -1.231
n113 NODE 1.924
-0.75
NODE us.Tee 0 -1.965
n114 NODE 1.924
-0.75
NODE us.Tee 0 -4.499
n115 NODE 1.924
-0.75
NODE us.Tee 0 -7.731
n116 NODE 1.924
-0.75
NODE us.Tee 0 -10.265
n117 NODE 1.924
-0.75
NODE us.Tee 0 -12.799
n118 NODE 1.924
-0.75
NODE us.Tee 0 -16.031
n119 NODE 1.924
-0.75
NODE us.Tee 0 -18.565

File: C:
\Users\Lizandro\Desktop\Proyectos2\53.GyG.MOTORPlaza\deLizandro.11082022\calculo4.7_diametros.original
es.tycx
Date 14/09/2022 Copyright © 2002-2016 Tyco Fire Protection Products Page 6
Job : Hydraulic Calculations / Fluid Delivery Time Analysis

Node Data : Initial System

Node # Hgroup K-Factor Elevation X


Type Fitting Stat. Pres. Coverage Y
gpm/psi½ m m
psi sq.ft m
n120 NODE 1.924
-0.75
NODE us.Tee 0 -21.099
n121 NODE 1.924
-0.75
NODE us.Tee 0 -24.465
n122 NODE 1.924
-0.75
NODE us.Tee 0 -27.265
n135 NODE 1.924
-0.75
NODE us.Tee 0 -28.261
n7 NODE 5.511
-0.75
NODE us.Tee 0 -1.231
n125 NODE 5.511
-0.75
NODE us.Tee 0 -1.965
n126 NODE 5.511
-0.75
NODE us.Tee 0 -4.499
n127 NODE 5.511
-0.75
NODE us.Tee 0 -7.731
n128 NODE 5.511
-0.75
NODE us.Tee 0 -10.265
n129 NODE 5.511
-0.75
NODE us.Tee 0 -12.799
n130 NODE 5.511
-0.75
NODE us.Tee 0 -16.031
n131 NODE 5.511
-0.75
NODE us.Tee 0 -18.565
n132 NODE 5.511
-0.75
NODE us.Tee 0 -21.099
n133 NODE 5.511
-0.75
NODE us.Tee 0 -24.465
n134 NODE 5.511
-0.75
NODE us.Tee 0 -27.265
n26 NODE 5.511
-0.75
NODE us.Tee 0 -28.261
h137 HEAD 11.2 -0.35 -14.995
OVERHEAD 0 0 -1.965
h138 HEAD 11.2 -0.35 -11.196
OVERHEAD 0 0 -1.965
h139 HEAD 11.2 -0.35 -14.995
OVERHEAD 0 0 -4.499
h140 HEAD 11.2 -0.35 -11.196
OVERHEAD 0 0 -4.499
h141 HEAD 11.2 -0.35 -14.995
OVERHEAD 0 0 -7.731
h142 HEAD 11.2 -0.35 -11.196
OVERHEAD 0 0 -7.731
h143 HEAD 11.2 -0.35 -14.995
OVERHEAD 0 0 -10.265
h144 HEAD 11.2 -0.35 -11.196
OVERHEAD 0 0 -10.265
h145 HEAD 11.2 -0.35 -14.995
OVERHEAD 0 0 -12.799
h146 HEAD 11.2 -0.35 -11.196
OVERHEAD 0 0 -12.799

File: C:
\Users\Lizandro\Desktop\Proyectos2\53.GyG.MOTORPlaza\deLizandro.11082022\calculo4.7_diametros.original
es.tycx
Date 14/09/2022 Copyright © 2002-2016 Tyco Fire Protection Products Page 7
Job : Hydraulic Calculations / Fluid Delivery Time Analysis

Node Data : Initial System

Node # Hgroup K-Factor Elevation X


Type Fitting Stat. Pres. Coverage Y
gpm/psi½ m m
psi sq.ft m
h147 HEAD 11.2 -0.35 -14.995
OVERHEAD 0 0 -16.031
h148 HEAD 11.2 -0.35 -11.196
OVERHEAD 0 0 -16.031
h149 HEAD 11.2 -0.35 -14.995
OVERHEAD 0 0 -18.565
h150 HEAD 11.2 -0.35 -11.196
OVERHEAD 0 0 -18.565
h151 HEAD 11.2 -0.35 -14.995
OVERHEAD 0 0 -21.099
h152 HEAD 11.2 -0.35 -11.196
OVERHEAD 0 0 -21.099
h153 HEAD 11.2 -0.35 -14.995
OVERHEAD 0 0 -24.465
h154 HEAD 11.2 -0.35 -11.196
OVERHEAD 0 0 -24.465
h155 HEAD 11.2 -0.35 -14.995
OVERHEAD 0 0 -27.265
h156 HEAD 11.2 -0.35 -11.196
OVERHEAD 0 0 -27.265
h157 HEAD 11.2 -0.35 -14.995
OVERHEAD 0 0 -30.965
h158 HEAD 11.2 -0.35 -11.196
OVERHEAD 0 0 -30.965
h159 HEAD 11.2 -0.35 -14.995
OVERHEAD 0 0 -34.897
h160 HEAD 11.2 -0.35 -11.196
OVERHEAD 0 0 -34.897
h161 HEAD 11.2 -0.35 -6.801
OVERHEAD 0 0 -31.32
h162 HEAD 11.2 -0.35 -3.214
OVERHEAD 0 0 -31.32
h163 HEAD 11.2 -0.35 -6.801
OVERHEAD 0 0 -35.23
h164 HEAD 11.2 -0.35 -3.214
OVERHEAD 0 0 -35.23
h165 HEAD 11.2 -0.35 1.924
OVERHEAD 0 0 -35.825
h166 HEAD 11.2 -0.35 -6.802
OVERHEAD 0 0 -1.965
h167 HEAD 11.2 -0.35 -3.22
OVERHEAD 0 0 -1.965
h168 HEAD 11.2 -0.35 -6.802
OVERHEAD 0 0 -4.499
h169 HEAD 11.2 -0.35 -6.802
OVERHEAD 0 0 -7.731
h170 HEAD 11.2 -0.35 -6.802
OVERHEAD 0 0 -10.265
h171 HEAD 11.2 -0.35 -6.802
OVERHEAD 0 0 -12.799
h172 HEAD 11.2 -0.35 -6.802
OVERHEAD 0 0 -16.031

File: C:
\Users\Lizandro\Desktop\Proyectos2\53.GyG.MOTORPlaza\deLizandro.11082022\calculo4.7_diametros.original
es.tycx
Date 14/09/2022 Copyright © 2002-2016 Tyco Fire Protection Products Page 8
Job : Hydraulic Calculations / Fluid Delivery Time Analysis

Node Data : Initial System

Node # Hgroup K-Factor Elevation X


Type Fitting Stat. Pres. Coverage Y
gpm/psi½ m m
psi sq.ft m
h173 HEAD 11.2 -0.35 -6.802
OVERHEAD 0 0 -18.565
h174 HEAD 11.2 -0.35 -6.802
OVERHEAD 0 0 -21.099
h175 HEAD 11.2 -0.35 -6.802
OVERHEAD 0 0 -24.465
h176 HEAD 11.2 -0.35 -6.802
OVERHEAD 0 0 -27.265
h177 HEAD 11.2 -0.35 -3.22
OVERHEAD 0 0 -4.499
h178 HEAD 11.2 -0.35 -3.22
OVERHEAD 0 0 -7.731
h179 HEAD 11.2 -0.35 -3.22
OVERHEAD 0 0 -10.265
h180 HEAD 11.2 -0.35 -3.22
OVERHEAD 0 0 -12.799
h181 HEAD 11.2 -0.35 -3.22
OVERHEAD 0 0 -16.031
h182 HEAD 11.2 -0.35 -3.22
OVERHEAD 0 0 -18.565
h183 HEAD 11.2 -0.35 -3.22
OVERHEAD 0 0 -21.099
h184 HEAD 11.2 -0.35 -3.22
OVERHEAD 0 0 -24.465
h185 HEAD 11.2 -0.35 -3.22
OVERHEAD 0 0 -27.265
h186 HEAD 11.2 -0.35 1.924
OVERHEAD 0 0 -1.965
h187 HEAD 11.2 -0.35 1.924
OVERHEAD 0 0 -4.499
h188 HEAD 11.2 -0.35 1.924
OVERHEAD 0 0 -7.731
h189 HEAD 11.2 -0.35 1.924
OVERHEAD 0 0 -10.265
h190 HEAD 11.2 -0.35 1.924
OVERHEAD 0 0 -12.799
h191 HEAD 11.2 -0.35 1.924
OVERHEAD 0 0 -16.031
h192 HEAD 11.2 -0.35 1.924
OVERHEAD 0 0 -18.565
h193 HEAD 11.2 -0.35 1.924
OVERHEAD 0 0 -21.099
h194 HEAD 11.2 -0.35 1.924
OVERHEAD 0 0 -24.465
h195 HEAD 11.2 -0.35 1.924
OVERHEAD 0 0 -27.265
h196 HEAD 11.2 -0.35 5.511
OVERHEAD 0 0 -1.965
h197 HEAD 11.2 -0.35 5.511
OVERHEAD 0 0 -4.499
h198 HEAD 11.2 -0.35 5.511
OVERHEAD 0 0 -7.731

File: C:
\Users\Lizandro\Desktop\Proyectos2\53.GyG.MOTORPlaza\deLizandro.11082022\calculo4.7_diametros.original
es.tycx
Date 14/09/2022 Copyright © 2002-2016 Tyco Fire Protection Products Page 9
Job : Hydraulic Calculations / Fluid Delivery Time Analysis

Node Data : Initial System

Node # Hgroup K-Factor Elevation X


Type Fitting Stat. Pres. Coverage Y
gpm/psi½ m m
psi sq.ft m
h199 HEAD 11.2 -0.35 5.511
OVERHEAD 0 0 -10.265
h200 HEAD 11.2 -0.35 5.511
OVERHEAD 0 0 -12.799
h201 HEAD 11.2 -0.35 5.511
OVERHEAD 0 0 -16.031
h202 HEAD 11.2 -0.35 5.511
OVERHEAD 0 0 -18.565
h203 HEAD 11.2 -0.35 5.511
OVERHEAD 0 0 -21.099
h204 HEAD 11.2 -0.35 5.511
OVERHEAD 0 0 -24.465
h205 HEAD 11.2 -0.35 5.511
OVERHEAD 0 0 -27.265
n136 -13.096
NODE -0.75
NODE 0 -14.415
n137 -13.096
NODE -0.75
NODE 0 -19.832
n138 -13.096
NODE -0.75
NODE 0 -25.865
n139 -13.096
NODE -0.75
NODE 0 -32.931
n140 -9.42
NODE -0.75
NODE 0 -28.261
n141 -13.096
NODE -0.75
NODE 0 -3.232
n142 -13.096
NODE -0.75
NODE 0 -8.998
n144 -8.233
NODE -0.75
NODE 0 -19.832
n145 -8.233
NODE -0.75
NODE 0 -25.865
n146 -8.233
NODE -0.75
NODE 0 -14.415
n147 -8.233
NODE -0.75
NODE 0 -3.232
n148 NODE -8.233
-0.75
NODE us.Tee 0 -23.037
n149 NODE -1.585
-0.75
NODE us.90 0 -23.037
n150 NODE -1.585
-5.2
NODE us.90 0 -23.037
his2 HOSE -1.585
-5.2
INHOSE 0 -23.238
n151 NODE 10.062
-0.75
NODE us.Tee 0 -1.231
n153 NODE 10.062
-0.75
NODE us.Tee 0 -1.965
n154 NODE 10.062
-0.75
NODE us.Tee 0 -4.499
n155 NODE 10.062
-0.75
NODE us.Tee 0 -7.731

File: C:
\Users\Lizandro\Desktop\Proyectos2\53.GyG.MOTORPlaza\deLizandro.11082022\calculo4.7_diametros.original
es.tycx
Date 14/09/2022 Copyright © 2002-2016 Tyco Fire Protection Products Page 10
Job : Hydraulic Calculations / Fluid Delivery Time Analysis

Node Data : Initial System

Node # Hgroup K-Factor Elevation X


Type Fitting Stat. Pres. Coverage Y
gpm/psi½ m m
psi sq.ft m
n156 NODE 10.062
-0.75
NODE us.Tee 0 -10.265
n157 NODE 10.062
-0.75
NODE us.Tee 0 -12.799
n158 NODE 10.062
-0.75
NODE us.Tee 0 -16.031
n159 NODE 10.062
-0.75
NODE us.Tee 0 -18.565
n160 NODE 10.062
-0.75
NODE us.Tee 0 -21.099
n161 NODE 10.062
-0.75
NODE us.Tee 0 -24.465
n162 NODE 10.062
-0.75
NODE us.Tee 0 -27.265
n163 NODE 10.062
-0.75
NODE us.Tee 0 -28.261
h206 HEAD 11.2 -0.35 10.062
OVERHEAD 0 0 -1.965
h207 HEAD 11.2 -0.35 10.062
OVERHEAD 0 0 -4.499
h208 HEAD 11.2 -0.35 10.062
OVERHEAD 0 0 -7.731
h209 HEAD 11.2 -0.35 10.062
OVERHEAD 0 0 -10.265
h210 HEAD 11.2 -0.35 10.062
OVERHEAD 0 0 -12.799
h211 HEAD 11.2 -0.35 10.062
OVERHEAD 0 0 -16.031
h212 HEAD 11.2 -0.35 10.062
OVERHEAD 0 0 -18.565
h213 HEAD 11.2 -0.35 10.062
OVERHEAD 0 0 -21.099
h214 HEAD 11.2 -0.35 10.062
OVERHEAD 0 0 -24.465
h215 HEAD 11.2 -0.35 10.062
OVERHEAD 0 0 -27.265
n164 NODE -13.096
-0.75
NODE us.Tee 0 -6.982
n165 NODE -13.096
-0.75
NODE us.Tee 0 -17.816
n166 NODE -13.096
-0.75
NODE us.Tee 0 -28.261
n167 NODE -8.233
-0.75
NODE us.Tee 0 -6.982

File: C:
\Users\Lizandro\Desktop\Proyectos2\53.GyG.MOTORPlaza\deLizandro.11082022\calculo4.7_diametros.original
es.tycx
Date 14/09/2022 Copyright © 2002-2016 Tyco Fire Protection Products Page 11
Job : Hydraulic Calculations / Fluid Delivery Time Analysis

Pipe Data : Initial System

Pipe # Type Start End Size HWC Length Fittings Eq.Len. Total Len. Pipe Code
m ft m
fd1 FeedMain src1 n2 4 120 0.737 Steel 40 Blk
fd2 FeedMain n2 n22 4 120 3.845 1(us.Bfly);1(us.Swing); 26 11.77 Steel 40 Blk
fd4 FeedMain n22 n23 4 120 0.494 Steel 40 Blk
m20 Cmain n24 n6 4 120 1.431 Steel 40 Blk
m21 Cmain n6 n112 4 120 3.581 Steel 40 Blk
m22 Cmain n112 n8 4 120 1.881 Steel 40 Blk
m23 Cmain n8 n9 4 120 0.769 6(us.90); 36 11.742 Steel 40 Blk
m28 Cmain n14 n15 4 120 2.291 Steel 40 Blk
m29 Cmain n15 n16 4 120 0.988 Steel 40 Blk
m30 Cmain n16 n17 4 120 4.501 Steel 40 Blk
m31 Cmain n17 n18 4 120 3.799 Steel 40 Blk
m32 Cmain n18 n19 4 120 4.501 Steel 40 Blk
m33 Cmain n19 n20 4 120 3.799 Steel 40 Blk
m34 Cmain n20 n40 4 120 1.597 Steel 40 Blk
m1 Cmain n5 n25 4 120 1.431 Steel 40 Blk
m3 Cmain n123 n27 4 120 1.881 Steel 40 Blk
m4 Cmain n27 n28 4 120 0.769 6(us.90); 36 11.742 Steel 40 Blk
m13 Cmain n35 n36 4 120 4.501 Steel 40 Blk
m14 Cmain n36 n37 4 120 3.799 Steel 40 Blk
m15 Cmain n37 n38 4 120 4.501 Steel 40 Blk
m16 Cmain n38 n39 4 120 3.799 Steel 40 Blk
m17 Cmain n39 n21 4 120 1.597 Steel 40 Blk
m37 Cmain n40 n21 4 120 29.32 Steel 40 Blk
b6 Brline n35 n16 2 120 29.32 Steel 40 Blk
b7 Brline n17 n36 2 120 29.32 Steel 40 Blk
b8 Brline n37 n18 2 120 29.32 Steel 40 Blk
b9 Brline n19 n38 2 120 29.32 Steel 40 Blk
b10 Brline n39 n20 2 120 29.32 Steel 40 Blk
p14 Pipe n55 n56 1 120 1.899 Steel 40 Blk
p15 Pipe n56 n57 1 120 1.9 Steel 40 Blk
p17 Pipe n58 n45 1 120 1.899 Steel 40 Blk
p18 Pipe n45 n60 1 120 1.9 Steel 40 Blk
p20 Pipe n61 n48 1 120 1.899 Steel 40 Blk
p21 Pipe n48 n63 1 120 1.9 Steel 40 Blk
p24 Pipe n64 n65 1 120 1.899 Steel 40 Blk
p25 Pipe n65 n66 1 120 1.9 Steel 40 Blk
p27 Pipe n69 n70 1 120 1.899 Steel 40 Blk
p28 Pipe n70 n71 1 120 1.9 Steel 40 Blk
p30 Pipe n73 n59 1 120 1.899 Steel 40 Blk
p31 Pipe n59 n74 1 120 1.9 Steel 40 Blk
p35 Pipe n76 n62 1 120 1.899 Steel 40 Blk
p36 Pipe n62 n78 1 120 1.9 Steel 40 Blk
p38 Pipe n80 n79 1 120 1.899 Steel 40 Blk
p39 Pipe n79 n81 1 120 1.9 Steel 40 Blk
p3 Pipe n44 n42 1 120 1.899 Steel 40 Blk
p4 Pipe n42 n46 1 120 1.9 Steel 40 Blk

File: C:
\Users\Lizandro\Desktop\Proyectos2\53.GyG.MOTORPlaza\deLizandro.11082022\calculo4.7_diametros.original
es.tycx
Date 14/09/2022 Copyright © 2002-2016 Tyco Fire Protection Products Page 12
Job : Hydraulic Calculations / Fluid Delivery Time Analysis

Pipe Data : Initial System

Pipe # Type Start End Size HWC Length Fittings Eq.Len. Total Len. Pipe Code
m ft m
p5 Pipe n47 n72 1 120 1.899 Steel 40 Blk
p6 Pipe n72 n49 1 120 1.9 Steel 40 Blk
p7 Pipe n50 n77 1 120 1.899 Steel 40 Blk
p8 Pipe n77 n52 1 120 1.9 Steel 40 Blk
p1 Pipe n41 n51 1 120 1.899 Steel 40 Blk
p2 Pipe n51 n43 1 120 1.9 Steel 40 Blk
p43 Pipe n87 n85 1 120 1.794 Steel 40 Blk
p44 Pipe n85 n89 1 120 1.794 Steel 40 Blk
p41 Pipe n84 n88 1 120 1.794 Steel 40 Blk
p42 Pipe n88 n86 1 120 1.794 Steel 40 Blk
p45 Pipe n91 n90 1 120 6.932 Steel 40 Blk
p46 Pipe n90 n88 1 120 0.595 Steel 40 Blk
p47 Pipe n88 n85 1-1/4 120 3.91 Steel 40 Blk
p48 Pipe n85 n83 2 120 3.058 Steel 40 Blk
b11 Brline n6 n92 2 120 0.735 Steel 40 Blk
b12 Brline n92 n94 2 120 2.533 Steel 40 Blk
b13 Brline n94 n95 2 120 3.232 Steel 40 Blk
b14 Brline n95 n96 2 120 2.534 Steel 40 Blk
b15 Brline n96 n97 2 120 2.534 Steel 40 Blk
b16 Brline n97 n98 2 120 3.232 Steel 40 Blk
b17 Brline n98 n99 2 120 2.534 Steel 40 Blk
b18 Brline n99 n100 2 120 2.534 Steel 40 Blk
b19 Brline n100 n101 2 120 3.366 Steel 40 Blk
b20 Brline n101 n102 2 120 2.8 Steel 40 Blk
b21 Brline n102 n25 2 120 0.997 Steel 40 Blk
b33 Brline n112 n93 2 120 0.734 Steel 40 Blk
b34 Brline n93 n103 2 120 2.533 Steel 40 Blk
b35 Brline n103 n104 2 120 3.232 Steel 40 Blk
b36 Brline n104 n105 2 120 2.534 Steel 40 Blk
b37 Brline n105 n106 2 120 2.534 Steel 40 Blk
b38 Brline n106 n107 2 120 3.232 Steel 40 Blk
b39 Brline n107 n108 2 120 2.534 Steel 40 Blk
b40 Brline n108 n109 2 120 2.534 Steel 40 Blk
b41 Brline n109 n110 2 120 3.366 Steel 40 Blk
b42 Brline n110 n111 2 120 2.8 Steel 40 Blk
b43 Brline n111 n123 2 120 0.997 Steel 40 Blk
m41 Cmain n25 n83 4 120 1.794 Steel 40 Blk
m42 Cmain n83 n123 4 120 1.788 Steel 40 Blk
b44 Brline n124 n113 2 120 0.734 Steel 40 Blk
b45 Brline n113 n114 2 120 2.533 Steel 40 Blk
b46 Brline n114 n115 2 120 3.232 Steel 40 Blk
b47 Brline n115 n116 2 120 2.534 Steel 40 Blk
b48 Brline n116 n117 2 120 2.534 Steel 40 Blk
b49 Brline n117 n118 2 120 3.232 Steel 40 Blk
b50 Brline n118 n119 2 120 2.534 Steel 40 Blk
b51 Brline n119 n120 2 120 2.534 Steel 40 Blk

File: C:
\Users\Lizandro\Desktop\Proyectos2\53.GyG.MOTORPlaza\deLizandro.11082022\calculo4.7_diametros.original
es.tycx
Date 14/09/2022 Copyright © 2002-2016 Tyco Fire Protection Products Page 13
Job : Hydraulic Calculations / Fluid Delivery Time Analysis

Pipe Data : Initial System

Pipe # Type Start End Size HWC Length Fittings Eq.Len. Total Len. Pipe Code
m ft m
b52 Brline n120 n121 2 120 3.366 Steel 40 Blk
b53 Brline n121 n122 2 120 2.8 Steel 40 Blk
b54 Brline n122 n135 2 120 0.997 Steel 40 Blk
b22 Brline n7 n125 2 120 0.734 Steel 40 Blk
b23 Brline n125 n126 2 120 2.533 Steel 40 Blk
b24 Brline n126 n127 2 120 3.232 Steel 40 Blk
b25 Brline n127 n128 2 120 2.534 Steel 40 Blk
b26 Brline n128 n129 2 120 2.534 Steel 40 Blk
b27 Brline n129 n130 2 120 3.232 Steel 40 Blk
b28 Brline n130 n131 2 120 2.534 Steel 40 Blk
b29 Brline n131 n132 2 120 2.534 Steel 40 Blk
b30 Brline n132 n133 2 120 3.366 Steel 40 Blk
b31 Brline n133 n134 2 120 2.8 Steel 40 Blk
b32 Brline n134 n26 2 120 0.997 Steel 40 Blk
m43 Cmain n9 n124 4 120 2.494 Steel 40 Blk
m44 Cmain n124 n23 4 120 1.922 Steel 40 Blk
m45 Cmain n23 n7 4 120 1.665 Steel 40 Blk
m46 Cmain n7 n12 4 120 1.897 Steel 40 Blk
m47 Cmain n28 n135 4 120 2.494 Steel 40 Blk
m48 Cmain n135 n26 4 120 3.587 Steel 40 Blk
1 #-1|Sprig|Sprig|21 n55 h137 1 120 0.4 Steel 40 Blk
2 #-1|Sprig|Sprig|21 n57 h138 1 120 0.4 Steel 40 Blk
3 #-1|Sprig|Sprig|21 n58 h139 1 120 0.4 Steel 40 Blk
4 #-1|Sprig|Sprig|21 n60 h140 1 120 0.4 Steel 40 Blk
5 #-1|Sprig|Sprig|21 n61 h141 1 120 0.4 Steel 40 Blk
6 #-1|Sprig|Sprig|21 n63 h142 1 120 0.4 Steel 40 Blk
7 #-1|Sprig|Sprig|21 n64 h143 1 120 0.4 Steel 40 Blk
8 #-1|Sprig|Sprig|21 n66 h144 1 120 0.4 Steel 40 Blk
9 #-1|Sprig|Sprig|21 n69 h145 1 120 0.4 Steel 40 Blk
10 #-1|Sprig|Sprig|21 n71 h146 1 120 0.4 Steel 40 Blk
11 #-1|Sprig|Sprig|21 n73 h147 1 120 0.4 Steel 40 Blk
12 #-1|Sprig|Sprig|21 n74 h148 1 120 0.4 Steel 40 Blk
13 #-1|Sprig|Sprig|21 n76 h149 1 120 0.4 Steel 40 Blk
14 #-1|Sprig|Sprig|21 n78 h150 1 120 0.4 Steel 40 Blk
15 #-1|Sprig|Sprig|21 n80 h151 1 120 0.4 Steel 40 Blk
16 #-1|Sprig|Sprig|21 n81 h152 1 120 0.4 Steel 40 Blk
17 #-1|Sprig|Sprig|21 n44 h153 1 120 0.4 Steel 40 Blk
18 #-1|Sprig|Sprig|21 n46 h154 1 120 0.4 Steel 40 Blk
19 #-1|Sprig|Sprig|21 n47 h155 1 120 0.4 Steel 40 Blk
20 #-1|Sprig|Sprig|21 n49 h156 1 120 0.4 Steel 40 Blk
21 #-1|Sprig|Sprig|21 n50 h157 1 120 0.4 Steel 40 Blk
22 #-1|Sprig|Sprig|21 n52 h158 1 120 0.4 Steel 40 Blk
23 #-1|Sprig|Sprig|21 n41 h159 1 120 0.4 Steel 40 Blk
24 #-1|Sprig|Sprig|21 n43 h160 1 120 0.4 Steel 40 Blk
25 #-1|Sprig|Sprig|21 n87 h161 1 120 0.4 Steel 40 Blk
26 #-1|Sprig|Sprig|21 n89 h162 1 120 0.4 Steel 40 Blk

File: C:
\Users\Lizandro\Desktop\Proyectos2\53.GyG.MOTORPlaza\deLizandro.11082022\calculo4.7_diametros.original
es.tycx
Date 14/09/2022 Copyright © 2002-2016 Tyco Fire Protection Products Page 14
Job : Hydraulic Calculations / Fluid Delivery Time Analysis

Pipe Data : Initial System

Pipe # Type Start End Size HWC Length Fittings Eq.Len. Total Len. Pipe Code
m ft m
27 #-1|Sprig|Sprig|21 n84 h163 1 120 0.4 Steel 40 Blk
28 #-1|Sprig|Sprig|21 n86 h164 1 120 0.4 Steel 40 Blk
29 #-1|Sprig|Sprig|21 n91 h165 1 120 0.4 Steel 40 Blk
30 #-1|Sprig|Sprig|21 n92 h166 1 120 0.4 Steel 40 Blk
31 #-1|Sprig|Sprig|21 n93 h167 1 120 0.4 Steel 40 Blk
32 #-1|Sprig|Sprig|21 n94 h168 1 120 0.4 Steel 40 Blk
33 #-1|Sprig|Sprig|21 n95 h169 1 120 0.4 Steel 40 Blk
34 #-1|Sprig|Sprig|21 n96 h170 1 120 0.4 Steel 40 Blk
35 #-1|Sprig|Sprig|21 n97 h171 1 120 0.4 Steel 40 Blk
36 #-1|Sprig|Sprig|21 n98 h172 1 120 0.4 Steel 40 Blk
37 #-1|Sprig|Sprig|21 n99 h173 1 120 0.4 Steel 40 Blk
38 #-1|Sprig|Sprig|21 n100 h174 1 120 0.4 Steel 40 Blk
39 #-1|Sprig|Sprig|21 n101 h175 1 120 0.4 Steel 40 Blk
40 #-1|Sprig|Sprig|21 n102 h176 1 120 0.4 Steel 40 Blk
41 #-1|Sprig|Sprig|21 n103 h177 1 120 0.4 Steel 40 Blk
42 #-1|Sprig|Sprig|21 n104 h178 1 120 0.4 Steel 40 Blk
43 #-1|Sprig|Sprig|21 n105 h179 1 120 0.4 Steel 40 Blk
44 #-1|Sprig|Sprig|21 n106 h180 1 120 0.4 Steel 40 Blk
45 #-1|Sprig|Sprig|21 n107 h181 1 120 0.4 Steel 40 Blk
46 #-1|Sprig|Sprig|21 n108 h182 1 120 0.4 Steel 40 Blk
47 #-1|Sprig|Sprig|21 n109 h183 1 120 0.4 Steel 40 Blk
48 #-1|Sprig|Sprig|21 n110 h184 1 120 0.4 Steel 40 Blk
49 #-1|Sprig|Sprig|21 n111 h185 1 120 0.4 Steel 40 Blk
50 #-1|Sprig|Sprig|21 n113 h186 1 120 0.4 Steel 40 Blk
51 #-1|Sprig|Sprig|21 n114 h187 1 120 0.4 Steel 40 Blk
52 #-1|Sprig|Sprig|21 n115 h188 1 120 0.4 Steel 40 Blk
53 #-1|Sprig|Sprig|21 n116 h189 1 120 0.4 Steel 40 Blk
54 #-1|Sprig|Sprig|21 n117 h190 1 120 0.4 Steel 40 Blk
55 #-1|Sprig|Sprig|21 n118 h191 1 120 0.4 Steel 40 Blk
56 #-1|Sprig|Sprig|21 n119 h192 1 120 0.4 Steel 40 Blk
57 #-1|Sprig|Sprig|21 n120 h193 1 120 0.4 Steel 40 Blk
58 #-1|Sprig|Sprig|21 n121 h194 1 120 0.4 Steel 40 Blk
59 #-1|Sprig|Sprig|21 n122 h195 1 120 0.4 Steel 40 Blk
60 #-1|Sprig|Sprig|21 n125 h196 1 120 0.4 Steel 40 Blk
61 #-1|Sprig|Sprig|21 n126 h197 1 120 0.4 Steel 40 Blk
62 #-1|Sprig|Sprig|21 n127 h198 1 120 0.4 Steel 40 Blk
63 #-1|Sprig|Sprig|21 n128 h199 1 120 0.4 Steel 40 Blk
64 #-1|Sprig|Sprig|21 n129 h200 1 120 0.4 Steel 40 Blk
65 #-1|Sprig|Sprig|21 n130 h201 1 120 0.4 Steel 40 Blk
66 #-1|Sprig|Sprig|21 n131 h202 1 120 0.4 Steel 40 Blk
67 #-1|Sprig|Sprig|21 n132 h203 1 120 0.4 Steel 40 Blk
68 #-1|Sprig|Sprig|21 n133 h204 1 120 0.4 Steel 40 Blk
69 #-1|Sprig|Sprig|21 n134 h205 1 120 0.4 Steel 40 Blk
p49 Pipe n70 n136 1 120 0.041 Steel 40 Blk
p50 Pipe n136 n59 1 120 0.041 Steel 40 Blk
p51 Pipe n79 n137 1 120 0.032 Steel 40 Blk

File: C:
\Users\Lizandro\Desktop\Proyectos2\53.GyG.MOTORPlaza\deLizandro.11082022\calculo4.7_diametros.original
es.tycx
Date 14/09/2022 Copyright © 2002-2016 Tyco Fire Protection Products Page 15
Job : Hydraulic Calculations / Fluid Delivery Time Analysis

Pipe Data : Initial System

Pipe # Type Start End Size HWC Length Fittings Eq.Len. Total Len. Pipe Code
m ft m
p52 Pipe n137 n62 1 120 0.032 Steel 40 Blk
p53 Pipe n42 n138 1 120 0.036 Steel 40 Blk
p54 Pipe n138 n72 1 120 0.036 Steel 40 Blk
p55 Pipe n51 n139 1 120 0.05 Steel 40 Blk
p56 Pipe n139 n77 1 120 0.05 Steel 40 Blk
p57 Pipe n5 n140 2 120 1.187 Steel 40 Blk
p58 Pipe n56 n141 1 120 0.032 Steel 40 Blk
p59 Pipe n141 n45 1 120 0.032 Steel 40 Blk
p60 Pipe n65 n142 1 120 0.032 Steel 40 Blk
p61 Pipe n142 n48 1 120 0.032 Steel 40 Blk
m51 Cmain n82 n144 4 120 2.016 Steel 40 Blk
m54 Cmain n145 n5 4 120 2.397 Steel 40 Blk
m55 Cmain n68 n146 4 120 5.417 Steel 40 Blk
m56 Cmain n146 n82 4 120 3.401 Steel 40 Blk
m57 Cmain n24 n147 4 120 2.001 Steel 40 Blk
m59 Cmain n148 n144 4 120 3.205 Steel 40 Blk
m60 Cmain n145 n148 4 120 2.828 Steel 40 Blk
p69 Pipe n148 n149 2 120 6.648 Steel 40 Blk
p70 Pipe n149 n150 2 120 4.45 Steel 40 Blk
p71 Pipe n150 his2 2 120 0.201 Steel 40 Blk
m62 Cmain n12 n151 4 120 0.067 Steel 40 Blk
m63 Cmain n151 n14 4 120 0.067 Steel 40 Blk
m64 Cmain n26 n163 4 120 4.551 Steel 40 Blk
m65 Cmain n163 n35 4 120 3.642 Steel 40 Blk
b55 Brline n151 n153 2 120 0.734 Steel 40 Blk
b56 Brline n153 n154 2 120 2.533 Steel 40 Blk
b57 Brline n154 n155 2 120 3.232 Steel 40 Blk
b58 Brline n155 n156 2 120 2.534 Steel 40 Blk
b59 Brline n156 n157 2 120 2.534 Steel 40 Blk
b60 Brline n157 n158 2 120 3.232 Steel 40 Blk
b61 Brline n158 n159 2 120 2.534 Steel 40 Blk
b62 Brline n159 n160 2 120 2.534 Steel 40 Blk
b63 Brline n160 n161 2 120 3.366 Steel 40 Blk
b64 Brline n161 n162 2 120 2.8 Steel 40 Blk
b65 Brline n162 n163 2 120 0.997 Steel 40 Blk
s1 Sprig n153 h206 1 120 0.4 Steel 40 Blk
s2 Sprig n154 h207 1 120 0.4 Steel 40 Blk
s3 Sprig n155 h208 1 120 0.4 Steel 40 Blk
s4 Sprig n156 h209 1 120 0.4 Steel 40 Blk
s5 Sprig n157 h210 1 120 0.4 Steel 40 Blk
s6 Sprig n158 h211 1 120 0.4 Steel 40 Blk
s7 Sprig n159 h212 1 120 0.4 Steel 40 Blk
s8 Sprig n160 h213 1 120 0.4 Steel 40 Blk
s9 Sprig n161 h214 1 120 0.4 Steel 40 Blk
s10 Sprig n162 h215 1 120 0.4 Steel 40 Blk
p75 Pipe n45 n164 1-1/2 120 2.484 Steel 40 Blk

File: C:
\Users\Lizandro\Desktop\Proyectos2\53.GyG.MOTORPlaza\deLizandro.11082022\calculo4.7_diametros.original
es.tycx
Date 14/09/2022 Copyright © 2002-2016 Tyco Fire Protection Products Page 16
Job : Hydraulic Calculations / Fluid Delivery Time Analysis

Pipe Data : Initial System

Pipe # Type Start End Size HWC Length Fittings Eq.Len. Total Len. Pipe Code
m ft m
p76 Pipe n164 n48 1-1/2 120 0.749 Steel 40 Blk
p77 Pipe n59 n165 1-1/2 120 1.785 Steel 40 Blk
p78 Pipe n165 n62 1-1/2 120 0.749 Steel 40 Blk
p79 Pipe n72 n166 1-1/2 120 0.997 Steel 40 Blk
p80 Pipe n166 n77 1-1/2 120 2.703 Steel 40 Blk
m66 Cmain n147 n167 4 120 3.75 Steel 40 Blk
m67 Cmain n167 n68 4 120 2.016 Steel 40 Blk
p81 Pipe n164 n167 2 120 4.863 Steel 40 Blk
p82 Pipe n165 n82 2 120 4.863 Steel 40 Blk
p83 Pipe n140 n166 2 120 3.676 Steel 40 Blk

File: C:
\Users\Lizandro\Desktop\Proyectos2\53.GyG.MOTORPlaza\deLizandro.11082022\calculo4.7_diametros.original
es.tycx
Date 14/09/2022 Copyright © 2002-2016 Tyco Fire Protection Products Page 17
HYDRAULIC CALCULATIONS
for
Job Information
Project Name :

Contract No. : City:

Project Location: Date: 12/09/2022

Contractor Information
Name of Contractor:

Address: City:

Phone Number: E-mail:

Name of Designer:

Authority Having Jurisdiction:

Design
Remote Area Name DesignArea_1

Remote Area Location

Occupancy Classification

Density (gpm/sq.ft) N/A (In-Rack)

Area of Application (sq.ft) 0

Coverage per Sprinkler (sq.ft) N/A (In-Rack)

Number of Calculated Sprinklers 10

In-Rack Demand (gpm) 0

Special Heads

Hose Streams (gpm) 100

Total Water Required (incl. Hose Streams) (gpm) 599.097

Pressure at Source (psi) 68.85

Type of System Wet

Volume - Entire System Volume (gal) 479.3 gal

Water Supply Information


Date

Location

Source

Notes

File: C:
\Users\Lizandro\Desktop\Proyectos2\53.GyG.MOTORPlaza\deLizandro.11082022\calculo4.7_diametros.original
es.tycx
Date 14/09/2022 Copyright © 2002-2016 Tyco Fire Protection Products Page 18
Job : Node Labels: Pressure (Total) [psi]
Pipe Labels: Flow [gpm]

Diagram For Design Area : DesignArea_1

File: C:\Users\Lizandro\Desktop\Proyectos2\53.GyG.MOTORPlaza\deLizandro.11082022\calculo4.7_diametros.originales.tycx
Date 14/09/2022 Copyright © 2002-2016 Tyco Fire Protection Products Page 19
Job :

Hydraulic Analysis for : DesignArea_1


Calculation Info
Calculation Mode Demand
Hydraulic Model Hazen-Williams
Fluid Name Water @ 60F (15.6C)
Fluid Weight, (lb/ft³) N/A for Hazen-Williams calculation.
Fluid Dynamic Viscosity, (centipoise) N/A for Hazen-Williams calculation.

Water Supply Parameters

Hoses
Inside Hose Flow / Standpipe Demand (gpm) 100

Outside Hose Flow (gpm) 0

Additional Outside Hose Flow (gpm)

Other (custom defined) Hose Flow (gpm) 0

Total Hose Flow (gpm) 100

Sprinklers
Ovehead Sprinkler Flow (gpm) 499.097

InRack Sprinkler Flow (gpm) 0

Other (custom defined) Sprinkler Flow (gpm) 0

Total Sprinkler Flow (gpm) 499.097

Other
Required Margin of Safety (psi) 0

Base of Riser - Required Pressure (psi) 68.85

Base of Riser - Flow (gpm) 599.097

Demand w/o System Pump(s) N/A

File: C:
\Users\Lizandro\Desktop\Proyectos2\53.GyG.MOTORPlaza\deLizandro.11082022\calculo4.7_diametros.original
es.tycx
Date 14/09/2022 Copyright © 2002-2016 Tyco Fire Protection Products Page 20
Job :

Hydraulic Analysis for : DesignArea_1

System Demand

80

D2
70

60

50
Pressure, psi

40

30

20

10
D1

0
0 200 300 400 500 600 700
Flow, gpm

Graph Labels
Values
Label Description
Flow (gpm) Pressure (psi)
D1 Elevation Pressure 0 0.57
D2 System Demand 599.097 68.85

File: C:
\Users\Lizandro\Desktop\Proyectos2\53.GyG.MOTORPlaza\deLizandro.11082022\calculo4.7_diametros.original Page 21
es.tycx
Date 14/09/2022 Copyright © 2002-2016 Tyco Fire Protection Products
Job :

Hydraulic Analysis for : DesignArea_1

Open Heads
Required Calculated
Head Ref. Head Type Coverage K-Factor
Density Flow Pressure Density Flow Pressure

(sq.ft) (gpm/psi½) (gpm/sq.ft) (gpm) (psi) (gpm/sq.ft) (gpm) (psi)

h151 OVERHEAD 0 11.2 0 15.68 0 63.796 32.45

h152 OVERHEAD 0 11.2 0 15.68 0 63.795 32.44

h153 OVERHEAD 0 11.2 0 15.68 0 47.943 18.32

h154 OVERHEAD 0 11.2 0 15.68 0 47.942 18.32

h155 OVERHEAD 0 11.2 0 15.68 0 48.45 18.71

h156 OVERHEAD 0 11.2 0 15.68 0 48.449 18.71

h157 OVERHEAD 0 11.2 0 15.68 0 45.013 16.15

h158 OVERHEAD 0 11.2 0 15.68 0 45.012 16.15

h159 OVERHEAD 0 11.2 0 15.68 0 44.35 15.68

h160 OVERHEAD 0 11.2 0 15.68 0 44.349 15.68

File: C:
\Users\Lizandro\Desktop\Proyectos2\53.GyG.MOTORPlaza\deLizandro.11082022\calculo4.7_diametros.original
es.tycx
Date 14/09/2022 Copyright © 2002-2016 Tyco Fire Protection Products Page 22
Job name : Sheet number:___________________

PIPE INFORMATION

Node 1 Elev 1 K-Factor 1 Flow added(q)* Nominal ID Fittings L C Factor total (Pt)
Node 2 Elev 2 K-Factor 2 Total flow (Q) Actual ID quantity x (name) = length F Pf per m elev (Pe) NOTES
T frict (Pf)

(m) (gpm/psi½) (gpm) (in) (m) (m) (psi) (psi)

h160 -0.35 11.2 44.349 1 1.312 120 15.68


n43 -0.75 44.349 1.049 0 0.5667 0.57
1.312 0.74
n43 -0.75 0 1 1x(us.Tee-Br) = 5 6.233 120 16.99
n51 -0.75 44.349 1.049 5 0.5667 0
11.233 6.37
n51 -0.75 44.35 1 0.328 120 23.36
n77 -0.75 88.698 1.049 0 2.0458 0
0.328 0.67
n77 -0.75 90.024 1-1/2 1x(us.Tee-Br) = 8 8.869 120 24.03
n166 -0.75 178.723 1.61 8 0.9296 0
16.869 15.68
n166 -0.75 192.784 2 15.954 120 39.71
n5 -0.75 371.506 2.067 0 1.0675 0
15.954 17.03
n5 -0.75 -19.857 4 4.695 120 56.74
n25 -0.75 351.65 4.026 0 0.0375 0
4.695 0.18
n25 -0.75 -32.458 4 11.75 120 56.92
n123 -0.75 319.191 4.026 0 0.0314 0
11.75 0.37
n123 -0.75 -31.345 4 6x(us.90) = 60 16.877 120 57.28
n135 -0.75 287.847 4.026 60 0.0259 0
76.876 1.99
n135 -0.75 -35.516 4 11.769 120 59.27
n26 -0.75 252.33 4.026 0 0.0203 0
11.769 0.24
n26 -0.75 -38.073 4 14.931 120 59.51
n163 -0.75 214.258 4.026 0 0.015 0
14.931 0.22
n163 -0.75 -34.031 4 11.948 120 59.74
n35 -0.75 180.226 4.026 0 0.0109 0
11.948 0.13
n35 -0.75 -26.298 4 14.767 120 59.87
n36 -0.75 153.928 4.026 0 0.0081 0
14.767 0.12
n36 -0.75 -22.339 4 12.464 120 59.99
n37 -0.75 131.589 4.026 0 0.0061 0
12.464 0.08
n37 -0.75 -19.498 4 14.767 120 60.06
n38 -0.75 112.091 4.026 0 0.0045 0
14.767 0.07
n38 -0.75 -16.665 4 12.464 120 60.13
n39 -0.75 95.426 4.026 0 0.0034 0
12.464 0.04
n39 -0.75 -14.66 4 1x(us.90) = 10 5.24 120 60.17
n21 -0.75 80.766 4.026 10 0.0025 0
15.24 0.04
n21 -0.75 0 4 1x(us.90) = 10 96.195 120 60.21
n40 -0.75 80.766 4.026 10 0.0025 0
106.19 0.26
5
n40 -0.75 0 4 5.24 120 60.47
n20 -0.75 80.766 4.026 0 0.0025 0
5.24 0.01

© 2006 National Fire Protection Association Page 23


Job name : Sheet number:___________________

PIPE INFORMATION

Node 1 Elev 1 K-Factor 1 Flow added(q)* Nominal ID Fittings L C Factor total (Pt)
Node 2 Elev 2 K-Factor 2 Total flow (Q) Actual ID quantity x (name) = length F Pf per m elev (Pe) NOTES
T frict (Pf)

(m) (gpm/psi½) (gpm) (in) (m) (m) (psi) (psi)

n20 -0.75 14.66 4 12.464 120 60.48


n19 -0.75 95.426 4.026 0 0.0034 0
12.464 0.04
n19 -0.75 16.665 4 14.767 120 60.52
n18 -0.75 112.091 4.026 0 0.0045 0
14.767 0.07
n18 -0.75 19.498 4 12.464 120 60.59
n17 -0.75 131.589 4.026 0 0.0061 0
12.464 0.08
n17 -0.75 22.339 4 14.767 120 60.67
n16 -0.75 153.928 4.026 0 0.0081 0
14.767 0.12
n16 -0.75 26.298 4 1x(us.90) = 10 3.241 120 60.79
n15 -0.75 180.226 4.026 10 0.0109 0
13.241 0.14
n15 -0.75 0 4 1x(us.90) = 10 7.515 120 60.93
n14 -0.75 180.226 4.026 10 0.0109 0
17.515 0.19
n14 -0.75 0 4 0.221 120 61.12
n151 -0.75 180.226 4.026 0 0.0109 0
0.221 0
n151 -0.75 34.031 4 6.446 120 61.12
n7 -0.75 214.258 4.026 0 0.015 0
6.446 0.1
n7 -0.75 38.073 4 1x(us.Tee-Br) = 20 5.463 120 61.22
n23 -0.75 252.33 4.026 20 0.0203 0
25.463 0.52
n23 -0.75 346.767 4 1x(us.90) = 10 1.62 120 61.74
n22 -0.75 599.097 4.026 10 0.1006 0
11.62 1.17
n22 -0.75 0 4 1x(us.Bfly) = 12 12.616 120 62.91
n2 -0.75 599.097 4.026 1x(us.Swing) = 22 44 0.1006 0
1x(us.90) = 10 56.616 5.7
n2 -0.75 0 4 2.418 120 68.6
src1 -0.75 599.097 4.026 0 0.1006 0
2.418 0.24
h159 -0.35 11.2 44.35 1 1.312 120 15.68
n41 -0.75 44.35 1.049 0 0.5667 0.57
1.312 0.74
n41 -0.75 0 1 1x(us.Tee-Br) = 5 6.231 120 16.99
n51 -0.75 44.35 1.049 5 0.5667 0
11.231 6.36
h158 -0.35 11.2 45.012 1 1.312 120 16.15
n52 -0.75 45.012 1.049 0 0.5825 0.57
1.312 0.76
n52 -0.75 0 1 1x(us.Tee-Br) = 5 6.233 120 17.48
n77 -0.75 45.012 1.049 5 0.5825 0
11.233 6.54
h157 -0.35 11.2 45.013 1 1.312 120 16.15
n50 -0.75 45.013 1.049 0 0.5825 0.57
1.312 0.76
n50 -0.75 0 1 1x(us.Tee-Br) = 5 6.231 120 17.49
n77 -0.75 45.013 1.049 5 0.5825 0
11.231 6.54

© 2006 National Fire Protection Association Page 24


Job name : Sheet number:___________________

PIPE INFORMATION

Node 1 Elev 1 K-Factor 1 Flow added(q)* Nominal ID Fittings L C Factor total (Pt)
Node 2 Elev 2 K-Factor 2 Total flow (Q) Actual ID quantity x (name) = length F Pf per m elev (Pe) NOTES
T frict (Pf)

(m) (gpm/psi½) (gpm) (in) (m) (m) (psi) (psi)

h154 -0.35 11.2 47.942 1 1.312 120 18.32


n46 -0.75 47.942 1.049 0 0.6546 0.57
1.312 0.86
n46 -0.75 0 1 1x(us.Tee-Br) = 5 6.233 120 19.75
n42 -0.75 47.942 1.049 5 0.6546 0
11.233 7.35
n42 -0.75 47.943 1 0.233 120 27.1
n72 -0.75 95.885 1.049 0 2.3633 0
0.233 0.55
n72 -0.75 96.899 1-1/2 1x(us.Tee-Br) = 8 3.27 120 27.66
n166 -0.75 192.784 1.61 8 1.0696 0
11.27 12.05
h153 -0.35 11.2 47.943 1 1.312 120 18.32
n44 -0.75 47.943 1.049 0 0.6547 0.57
1.312 0.86
n44 -0.75 0 1 1x(us.Tee-Br) = 5 6.231 120 19.75
n42 -0.75 47.943 1.049 5 0.6547 0
11.231 7.35
h156 -0.35 11.2 48.449 1 1.312 120 18.71
n49 -0.75 48.449 1.049 0 0.6675 0.57
1.312 0.88
n49 -0.75 0 1 1x(us.Tee-Br) = 5 6.233 120 20.16
n72 -0.75 48.449 1.049 5 0.6675 0
11.233 7.5
h155 -0.35 11.2 48.45 1 1.312 120 18.71
n47 -0.75 48.45 1.049 0 0.6676 0.57
1.312 0.88
n47 -0.75 0 1 1x(us.Tee-Br) = 5 6.231 120 20.16
n72 -0.75 48.45 1.049 5 0.6676 0
11.231 7.5
h152 -0.35 11.2 63.795 1 1.312 120 32.44
n81 -0.75 63.795 1.049 0 1.1112 0.57
1.312 1.46
n81 -0.75 0 1 1x(us.Tee-Br) = 5 6.233 120 34.47
n79 -0.75 63.795 1.049 5 1.1112 0
11.233 12.48
n79 -0.75 63.796 1 0.211 120 46.95
n62 -0.75 127.591 1.049 0 4.0114 0
0.211 0.85
n62 -0.75 0 1-1/2 1x(us.Tee-Br) = 8 2.456 120 47.8
n165 -0.75 127.591 1.61 8 0.498 0
10.456 5.21
n165 -0.75 0 2 1x(us.Tee-Br) = 10 15.954 120 53.01
n82 -0.75 127.591 2.067 10 0.1475 0
25.954 3.83
n82 -0.75 119.857 4 1x(us.90) = 10 54.413 120 56.83
n24 -0.75 247.447 4.026 10 0.0196 0
64.413 1.26
n24 -0.75 0 4 4.695 120 58.09
n6 -0.75 247.447 4.026 0 0.0196 0
4.695 0.09
n6 -0.75 32.458 4 11.75 120 58.19
n112 -0.75 279.906 4.026 0 0.0246 0
11.75 0.29

© 2006 National Fire Protection Association Page 25


Job name : Sheet number:___________________

PIPE INFORMATION

Node 1 Elev 1 K-Factor 1 Flow added(q)* Nominal ID Fittings L C Factor total (Pt)
Node 2 Elev 2 K-Factor 2 Total flow (Q) Actual ID quantity x (name) = length F Pf per m elev (Pe) NOTES
T frict (Pf)

(m) (gpm/psi½) (gpm) (in) (m) (m) (psi) (psi)

n112 -0.75 31.345 4 6x(us.90) = 60 16.877 120 58.48


n124 -0.75 311.25 4.026 60 0.0299 0
76.876 2.3
n124 -0.75 35.516 4 1x(us.Tee-Br) = 20 6.305 120 60.78
n23 -0.75 346.767 4.026 20 0.0366 0
26.305 0.96
h151 -0.35 11.2 63.796 1 1.312 120 32.45
n80 -0.75 63.796 1.049 0 1.1112 0.57
1.312 1.46
n80 -0.75 0 1 1x(us.Tee-Br) = 5 6.231 120 34.47
n79 -0.75 63.796 1.049 5 1.1112 0
11.231 12.48
his2 -5.2 100 2 1x(us.90) = 5 0.659 120 57.71
n150 -5.2 100 2.067 5 0.0939 0
5.659 0.53
n150 -5.2 0 2 1x(us.90) = 5 14.6 120 58.24
n149 -0.75 100 2.067 5 0.0939 -6.33
19.6 1.84
n149 -0.75 0 2 1x(us.Tee-Br) = 10 21.812 120 53.76
n148 -0.75 100 2.067 10 0.0939 0
31.812 2.99
n148 -0.75 19.857 4 17.129 120 56.75
n82 -0.75 119.857 4.026 0 0.0051 0
17.129 0.09
n5 -0.75 0 4 1x(us.Tee-Br) = 20 17.14 120 56.74
n148 -0.75 19.857 4.026 20 0.0002 0
37.14 0.01
n25 -0.75 0 2 2x(us.Tee-Br) = 20 88.682 120 56.92
n6 -0.75 32.458 2.067 20 0.0117 0
108.68 1.27
2
n123 -0.75 0 2 2x(us.Tee-Br) = 20 88.682 120 57.28
n112 -0.75 31.345 2.067 20 0.011 0
108.68 1.19
2
n135 -0.75 0 2 2x(us.Tee-Br) = 20 88.682 120 59.27
n124 -0.75 35.516 2.067 20 0.0138 0
108.68 1.5
2
n26 -0.75 0 2 2x(us.Tee-Br) = 20 88.682 120 59.51
n7 -0.75 38.073 2.067 20 0.0157 0
108.68 1.71
2
n163 -0.75 0 2 2x(us.Tee-Br) = 20 88.682 120 59.74
n151 -0.75 34.031 2.067 20 0.0128 0
108.68 1.39
2
n35 -0.75 0 2 2x(us.Tee-Br) = 20 96.195 120 59.87
n16 -0.75 26.298 2.067 20 0.0079 0
116.19 0.92
5
n36 -0.75 0 2 2x(us.Tee-Br) = 20 96.195 120 59.99
n17 -0.75 22.339 2.067 20 0.0059 0
116.19 0.68
5

© 2006 National Fire Protection Association Page 26


Job name : Sheet number:___________________

PIPE INFORMATION

Node 1 Elev 1 K-Factor 1 Flow added(q)* Nominal ID Fittings L C Factor total (Pt)
Node 2 Elev 2 K-Factor 2 Total flow (Q) Actual ID quantity x (name) = length F Pf per m elev (Pe) NOTES
T frict (Pf)

(m) (gpm/psi½) (gpm) (in) (m) (m) (psi) (psi)

n37 -0.75 0 2 2x(us.Tee-Br) = 20 96.195 120 60.06


n18 -0.75 19.498 2.067 20 0.0045 0
116.19 0.53
5
n38 -0.75 0 2 2x(us.Tee-Br) = 20 96.195 120 60.13
n19 -0.75 16.665 2.067 20 0.0034 0
116.19 0.4
5
n39 -0.75 0 2 2x(us.Tee-Br) = 20 96.195 120 60.17
n20 -0.75 14.66 2.067 20 0.0027 0
116.19 0.31
5

* Discharge shown for flowing nodes only

© 2006 National Fire Protection Association Page 27


HYDRAULIC CALCULATIONS
for
Job Information
Project Name :

Contract No. : City:

Project Location: Date: 12/09/2022

Contractor Information
Name of Contractor:

Address: City:

Phone Number: E-mail:

Name of Designer:

Authority Having Jurisdiction:

Design
Remote Area Name DesignArea_2

Remote Area Location

Occupancy Classification

Density (gpm/sq.ft) N/A (In-Rack)

Area of Application (sq.ft) 0

Coverage per Sprinkler (sq.ft) N/A (In-Rack)

Number of Calculated Sprinklers 12

In-Rack Demand (gpm) 0

Special Heads

Hose Streams (gpm) 100

Total Water Required (incl. Hose Streams) (gpm) 640.857

Pressure at Source (psi) 34.68

Type of System Wet

Volume - Entire System Volume (gal) 469.5 gal

Water Supply Information


Date

Location

Source

Notes

File: C:
\Users\Lizandro\Desktop\Proyectos2\53.GyG.MOTORPlaza\deLizandro.11082022\calculo4.7_diametros.original
es.tycx
Date 14/09/2022 Copyright © 2002-2016 Tyco Fire Protection Products Page 28
Job : Node Labels: Pressure (Total) [psi]
Pipe Labels: Flow [gpm]

Diagram For Design Area : DesignArea_2

File: C:\Users\Lizandro\Desktop\Proyectos2\53.GyG.MOTORPlaza\deLizandro.11082022\calculo4.7_diametros.originales.tycx
Date 14/09/2022 Copyright © 2002-2016 Tyco Fire Protection Products Page 29
Job :

Hydraulic Analysis for : DesignArea_2


Calculation Info
Calculation Mode Demand
Hydraulic Model Hazen-Williams
Fluid Name Water @ 60F (15.6C)
Fluid Weight, (lb/ft³) N/A for Hazen-Williams calculation.
Fluid Dynamic Viscosity, (centipoise) N/A for Hazen-Williams calculation.

Water Supply Parameters

Hoses
Inside Hose Flow / Standpipe Demand (gpm) 100

Outside Hose Flow (gpm) 0

Additional Outside Hose Flow (gpm)

Other (custom defined) Hose Flow (gpm) 0

Total Hose Flow (gpm) 100

Sprinklers
Ovehead Sprinkler Flow (gpm) 540.857

InRack Sprinkler Flow (gpm) 0

Other (custom defined) Sprinkler Flow (gpm) 0

Total Sprinkler Flow (gpm) 540.857

Other
Required Margin of Safety (psi) 0

Base of Riser - Required Pressure (psi) 34.68

Base of Riser - Flow (gpm) 640.857

Demand w/o System Pump(s) N/A

File: C:
\Users\Lizandro\Desktop\Proyectos2\53.GyG.MOTORPlaza\deLizandro.11082022\calculo4.7_diametros.original
es.tycx
Date 14/09/2022 Copyright © 2002-2016 Tyco Fire Protection Products Page 30
Job name : Sheet number:___________________

PIPE INFORMATION

Node 1 Elev 1 K-Factor 1 Flow added(q)* Nominal ID Fittings L C Factor total (Pt)
Node 2 Elev 2 K-Factor 2 Total flow (Q) Actual ID quantity x (name) = length F Pf per m elev (Pe) NOTES
T frict (Pf)

(m) (gpm/psi½) (gpm) (in) (m) (m) (psi) (psi)

h173 -0.35 11.2 44.35 1 1.312 120 15.68


n99 -0.75 44.35 1.049 0 0.5667 0.57
1.312 0.74
n99 -0.75 -16.834 2 8.314 120 16.99
n100 -0.75 27.515 2.067 0 0.0086 0
8.314 0.07
n100 -0.75 44.447 2 11.043 120 17.06
n101 -0.75 71.962 2.067 0 0.0511 0
11.043 0.56
n101 -0.75 45.203 2 9.186 120 17.63
n102 -0.75 117.164 2.067 0 0.1259 0
9.186 1.16
n102 -0.75 46.715 2 1x(us.Tee-Br) = 10 3.27 120 18.78
n25 -0.75 163.88 2.067 10 0.2345 0
13.27 3.11
n25 -0.75 -33.344 4 11.75 120 21.9
n123 -0.75 130.536 4.026 0 0.006 0
11.75 0.07
n123 -0.75 163.541 4 6x(us.90) = 60 16.877 120 21.97
n135 -0.75 294.076 4.026 60 0.0269 0
76.876 2.07
n135 -0.75 -34.762 4 11.769 120 24.04
n26 -0.75 259.314 4.026 0 0.0213 0
11.769 0.25
n26 -0.75 -39.127 4 14.931 120 24.29
n163 -0.75 220.187 4.026 0 0.0158 0
14.931 0.24
n163 -0.75 -34.973 4 11.948 120 24.52
n35 -0.75 185.214 4.026 0 0.0114 0
11.948 0.14
n35 -0.75 -27.026 4 14.767 120 24.66
n36 -0.75 158.188 4.026 0 0.0085 0
14.767 0.13
n36 -0.75 -22.957 4 12.464 120 24.79
n37 -0.75 135.23 4.026 0 0.0064 0
12.464 0.08
n37 -0.75 -20.037 4 14.767 120 24.87
n38 -0.75 115.193 4.026 0 0.0047 0
14.767 0.07
n38 -0.75 -17.126 4 12.464 120 24.94
n39 -0.75 98.067 4.026 0 0.0035 0
12.464 0.04
n39 -0.75 -15.065 4 1x(us.90) = 10 5.24 120 24.98
n21 -0.75 83.001 4.026 10 0.0026 0
15.24 0.04
n21 -0.75 0 4 1x(us.90) = 10 96.195 120 25.02
n40 -0.75 83.001 4.026 10 0.0026 0
106.19 0.27
5
n40 -0.75 0 4 5.24 120 25.29
n20 -0.75 83.001 4.026 0 0.0026 0
5.24 0.01
n20 -0.75 15.065 4 12.464 120 25.31
n19 -0.75 98.067 4.026 0 0.0035 0
12.464 0.04

© 2006 National Fire Protection Association Page 31


Job name : Sheet number:___________________

PIPE INFORMATION

Node 1 Elev 1 K-Factor 1 Flow added(q)* Nominal ID Fittings L C Factor total (Pt)
Node 2 Elev 2 K-Factor 2 Total flow (Q) Actual ID quantity x (name) = length F Pf per m elev (Pe) NOTES
T frict (Pf)

(m) (gpm/psi½) (gpm) (in) (m) (m) (psi) (psi)

n19 -0.75 17.126 4 14.767 120 25.35


n18 -0.75 115.193 4.026 0 0.0047 0
14.767 0.07
n18 -0.75 20.037 4 12.464 120 25.42
n17 -0.75 135.23 4.026 0 0.0064 0
12.464 0.08
n17 -0.75 22.957 4 14.767 120 25.5
n16 -0.75 158.188 4.026 0 0.0085 0
14.767 0.13
n16 -0.75 27.026 4 1x(us.90) = 10 3.241 120 25.63
n15 -0.75 185.214 4.026 10 0.0114 0
13.241 0.15
n15 -0.75 0 4 1x(us.90) = 10 7.515 120 25.78
n14 -0.75 185.214 4.026 10 0.0114 0
17.515 0.2
n14 -0.75 0 4 0.221 120 25.98
n151 -0.75 185.214 4.026 0 0.0114 0
0.221 0
n151 -0.75 34.973 4 6.446 120 25.98
n7 -0.75 220.187 4.026 0 0.0158 0
6.446 0.1
n7 -0.75 39.127 4 1x(us.Tee-Br) = 20 5.463 120 26.08
n23 -0.75 259.314 4.026 20 0.0213 0
25.463 0.54
n23 -0.75 381.543 4 1x(us.90) = 10 1.62 120 26.63
n22 -0.75 640.857 4.026 10 0.114 0
11.62 1.32
n22 -0.75 0 4 1x(us.Bfly) = 12 12.616 120 27.95
n2 -0.75 640.857 4.026 1x(us.Swing) = 22 44 0.114 0
1x(us.90) = 10 56.616 6.45
n2 -0.75 0 4 2.418 120 34.41
src1 -0.75 640.857 4.026 0 0.114 0
2.418 0.28
h172 -0.35 11.2 44.389 1 1.312 120 15.71
n98 -0.75 44.389 1.049 0 0.5676 0.57
1.312 0.74
n98 -0.75 16.834 2 10.604 120 17.02
n97 -0.75 61.223 2.067 0 0.0379 0
10.604 0.4
n97 -0.75 44.929 2 1x(us.Tee-Br) = 10 37.952 120 17.42
n6 -0.75 106.152 2.067 10 0.1049 0
47.952 5.03
n6 -0.75 133.344 4 11.75 120 22.45
n112 -0.75 239.496 4.026 0 0.0184 0
11.75 0.22
n112 -0.75 107.285 4 6x(us.90) = 60 16.877 120 22.67
n124 -0.75 346.781 4.026 60 0.0366 0
76.876 2.81
n124 -0.75 34.762 4 1x(us.Tee-Br) = 20 6.305 120 25.48
n23 -0.75 381.543 4.026 20 0.0436 0
26.305 1.15
h174 -0.35 11.2 44.447 1 1.312 120 15.75
n100 -0.75 44.447 1.049 0 0.569 0.57
1.312 0.75

© 2006 National Fire Protection Association Page 32


Job name : Sheet number:___________________

PIPE INFORMATION

Node 1 Elev 1 K-Factor 1 Flow added(q)* Nominal ID Fittings L C Factor total (Pt)
Node 2 Elev 2 K-Factor 2 Total flow (Q) Actual ID quantity x (name) = length F Pf per m elev (Pe) NOTES
T frict (Pf)

(m) (gpm/psi½) (gpm) (in) (m) (m) (psi) (psi)

h182 -0.35 11.2 44.488 1 1.312 120 15.78


n108 -0.75 44.488 1.049 0 0.57 0.57
1.312 0.75
n108 -0.75 -17.67 2 8.314 120 17.09
n109 -0.75 26.817 2.067 0 0.0082 0
8.314 0.07
n109 -0.75 44.58 2 11.043 120 17.16
n110 -0.75 71.397 2.067 0 0.0503 0
11.043 0.56
n110 -0.75 45.323 2 9.186 120 17.72
n111 -0.75 116.719 2.067 0 0.1251 0
9.186 1.15
n111 -0.75 46.821 2 1x(us.Tee-Br) = 10 3.27 120 18.87
n123 -0.75 163.541 2.067 10 0.2336 0
13.27 3.1
h181 -0.35 11.2 44.53 1 1.312 120 15.81
n107 -0.75 44.53 1.049 0 0.571 0.57
1.312 0.75
n107 -0.75 17.67 2 10.604 120 17.13
n106 -0.75 62.2 2.067 0 0.039 0
10.604 0.41
n106 -0.75 45.084 2 1x(us.Tee-Br) = 10 37.952 120 17.54
n112 -0.75 107.285 2.067 10 0.107 0
47.952 5.13
h183 -0.35 11.2 44.58 1 1.312 120 15.84
n109 -0.75 44.58 1.049 0 0.5722 0.57
1.312 0.75
h171 -0.35 11.2 44.929 1 1.312 120 16.09
n97 -0.75 44.929 1.049 0 0.5805 0.57
1.312 0.76
h180 -0.35 11.2 45.084 1 1.312 120 16.2
n106 -0.75 45.084 1.049 0 0.5842 0.57
1.312 0.77
h175 -0.35 11.2 45.203 1 1.312 120 16.29
n101 -0.75 45.203 1.049 0 0.5871 0.57
1.312 0.77
h184 -0.35 11.2 45.323 1 1.312 120 16.38
n110 -0.75 45.323 1.049 0 0.5899 0.57
1.312 0.77
h176 -0.35 11.2 46.715 1 1.312 120 17.4
n102 -0.75 46.715 1.049 0 0.624 0.57
1.312 0.82
h185 -0.35 11.2 46.821 1 1.312 120 17.48
n111 -0.75 46.821 1.049 0 0.6266 0.57
1.312 0.82
his2 -5.2 100 2 1x(us.90) = 5 0.659 120 22.88
n150 -5.2 100 2.067 5 0.0939 0
5.659 0.53
n150 -5.2 0 2 1x(us.90) = 5 14.6 120 23.41
n149 -0.75 100 2.067 5 0.0939 -6.33
19.6 1.84
n149 -0.75 0 2 1x(us.Tee-Br) = 10 21.812 120 18.93
n148 -0.75 100 2.067 10 0.0939 0
31.812 2.99

© 2006 National Fire Protection Association Page 33


Job name : Sheet number:___________________

PIPE INFORMATION

Node 1 Elev 1 K-Factor 1 Flow added(q)* Nominal ID Fittings L C Factor total (Pt)
Node 2 Elev 2 K-Factor 2 Total flow (Q) Actual ID quantity x (name) = length F Pf per m elev (Pe) NOTES
T frict (Pf)

(m) (gpm/psi½) (gpm) (in) (m) (m) (psi) (psi)

n148 -0.75 33.344 4 1x(us.90) = 10 71.542 120 21.92


n24 -0.75 133.344 4.026 10 0.0062 0
81.542 0.51
n24 -0.75 0 4 4.695 120 22.42
n6 -0.75 133.344 4.026 0 0.0062 0
4.695 0.03
n99 -0.75 0 2 8.314 120 16.99
n98 -0.75 16.834 2.067 0 0.0035 0
8.314 0.03
n25 -0.75 0 4 1x(us.Tee-Br) = 20 4.695 120 21.9
n5 -0.75 33.344 4.026 20 0.0005 0
24.695 0.01
n5 -0.75 0 4 17.14 120 21.91
n148 -0.75 33.344 4.026 0 0.0005 0
17.14 0.01
n135 -0.75 0 2 2x(us.Tee-Br) = 20 88.682 120 24.04
n124 -0.75 34.762 2.067 20 0.0133 0
108.68 1.44
2
n26 -0.75 0 2 2x(us.Tee-Br) = 20 88.682 120 24.29
n7 -0.75 39.127 2.067 20 0.0165 0
108.68 1.8
2
n163 -0.75 0 2 2x(us.Tee-Br) = 20 88.682 120 24.52
n151 -0.75 34.973 2.067 20 0.0134 0
108.68 1.46
2
n35 -0.75 0 2 2x(us.Tee-Br) = 20 96.195 120 24.66
n16 -0.75 27.026 2.067 20 0.0083 0
116.19 0.97
5
n36 -0.75 0 2 2x(us.Tee-Br) = 20 96.195 120 24.79
n17 -0.75 22.957 2.067 20 0.0062 0
116.19 0.72
5
n37 -0.75 0 2 2x(us.Tee-Br) = 20 96.195 120 24.87
n18 -0.75 20.037 2.067 20 0.0048 0
116.19 0.56
5
n38 -0.75 0 2 2x(us.Tee-Br) = 20 96.195 120 24.94
n19 -0.75 17.126 2.067 20 0.0036 0
116.19 0.42
5
n39 -0.75 0 2 2x(us.Tee-Br) = 20 96.195 120 24.98
n20 -0.75 15.065 2.067 20 0.0028 0
116.19 0.33
5
n108 -0.75 0 2 8.314 120 17.09
n107 -0.75 17.67 2.067 0 0.0038 0
8.314 0.03

* Discharge shown for flowing nodes only

© 2006 National Fire Protection Association Page 34


HYDRAULIC CALCULATIONS
for
Job Information
Project Name :

Contract No. : City:

Project Location: Date: 12/09/2022

Contractor Information
Name of Contractor:

Address: City:

Phone Number: E-mail:

Name of Designer:

Authority Having Jurisdiction:

Design
Remote Area Name DesignArea_3

Remote Area Location

Occupancy Classification

Density (gpm/sq.ft) N/A (In-Rack)

Area of Application (sq.ft) 0

Coverage per Sprinkler (sq.ft) N/A (In-Rack)

Number of Calculated Sprinklers 12

In-Rack Demand (gpm) 0

Special Heads

Hose Streams (gpm) 100

Total Water Required (incl. Hose Streams) (gpm) 660.766

Pressure at Source (psi) 33.18

Type of System Wet

Volume - Entire System Volume (gal) 469.5 gal

Water Supply Information


Date

Location

Source

Notes

File: C:
\Users\Lizandro\Desktop\Proyectos2\53.GyG.MOTORPlaza\deLizandro.11082022\calculo4.7_diametros.original
es.tycx
Date 14/09/2022 Copyright © 2002-2016 Tyco Fire Protection Products Page 35
Job : Node Labels: Pressure (Total) [psi]
Pipe Labels: Flow [gpm]

Diagram For Design Area : DesignArea_3

File: C:\Users\Lizandro\Desktop\Proyectos2\53.GyG.MOTORPlaza\deLizandro.11082022\calculo4.7_diametros.originales.tycx
Date 14/09/2022 Copyright © 2002-2016 Tyco Fire Protection Products Page 36
Job :

Hydraulic Analysis for : DesignArea_3


Calculation Info
Calculation Mode Demand
Hydraulic Model Hazen-Williams
Fluid Name Water @ 60F (15.6C)
Fluid Weight, (lb/ft³) N/A for Hazen-Williams calculation.
Fluid Dynamic Viscosity, (centipoise) N/A for Hazen-Williams calculation.

Water Supply Parameters

Hoses
Inside Hose Flow / Standpipe Demand (gpm) 100

Outside Hose Flow (gpm) 0

Additional Outside Hose Flow (gpm)

Other (custom defined) Hose Flow (gpm) 0

Total Hose Flow (gpm) 100

Sprinklers
Ovehead Sprinkler Flow (gpm) 560.766

InRack Sprinkler Flow (gpm) 0

Other (custom defined) Sprinkler Flow (gpm) 0

Total Sprinkler Flow (gpm) 560.766

Other
Required Margin of Safety (psi) 0

Base of Riser - Required Pressure (psi) 33.18

Base of Riser - Flow (gpm) 660.766

Demand w/o System Pump(s) N/A

File: C:
\Users\Lizandro\Desktop\Proyectos2\53.GyG.MOTORPlaza\deLizandro.11082022\calculo4.7_diametros.original
es.tycx
Date 14/09/2022 Copyright © 2002-2016 Tyco Fire Protection Products Page 37
Job :

Hydraulic Analysis for : DesignArea_3

System Demand

35 D2

30

25
Pressure, psi

20

15

10

D1

0
0 200 300 400 500 600 700
Flow, gpm

Graph Labels
Values
Label Description
Flow (gpm) Pressure (psi)
D1 Elevation Pressure 0 0.57
D2 System Demand 660.766 33.18

File: C:
\Users\Lizandro\Desktop\Proyectos2\53.GyG.MOTORPlaza\deLizandro.11082022\calculo4.7_diametros.original Page 38
es.tycx
Date 14/09/2022 Copyright © 2002-2016 Tyco Fire Protection Products
Job :

Hydraulic Analysis for : DesignArea_3

Open Heads
Required Calculated
Head Ref. Head Type Coverage K-Factor
Density Flow Pressure Density Flow Pressure

(sq.ft) (gpm/psi½) (gpm/sq.ft) (gpm) (psi) (gpm/sq.ft) (gpm) (psi)

h192 OVERHEAD 0 11.2 0 15.68 0 47.863 18.26

h193 OVERHEAD 0 11.2 0 15.68 0 47.736 18.17

h194 OVERHEAD 0 11.2 0 15.68 0 47.773 18.19

h195 OVERHEAD 0 11.2 0 15.68 0 48.223 18.54

h202 OVERHEAD 0 11.2 0 15.68 0 47.745 18.17

h203 OVERHEAD 0 11.2 0 15.68 0 47.633 18.09

h204 OVERHEAD 0 11.2 0 15.68 0 47.681 18.12

h205 OVERHEAD 0 11.2 0 15.68 0 48.16 18.49

h212 OVERHEAD 0 11.2 0 15.68 0 44.442 15.75

h213 OVERHEAD 0 11.2 0 15.68 0 44.35 15.68

h214 OVERHEAD 0 11.2 0 15.68 0 44.387 15.71

h215 OVERHEAD 0 11.2 0 15.68 0 44.773 15.98

File: C:
\Users\Lizandro\Desktop\Proyectos2\53.GyG.MOTORPlaza\deLizandro.11082022\calculo4.7_diametros.original
es.tycx
Date 14/09/2022 Copyright © 2002-2016 Tyco Fire Protection Products Page 39
Job name : Sheet number:___________________

PIPE INFORMATION

Node 1 Elev 1 K-Factor 1 Flow added(q)* Nominal ID Fittings L C Factor total (Pt)
Node 2 Elev 2 K-Factor 2 Total flow (Q) Actual ID quantity x (name) = length F Pf per m elev (Pe) NOTES
T frict (Pf)

(m) (gpm/psi½) (gpm) (in) (m) (m) (psi) (psi)

h213 -0.35 11.2 44.35 1 1x(us.Tee-Br) = 5 1.312 120 15.68


n160 -0.75 44.35 1.049 5 0.5667 0.57
6.312 3.58
n160 -0.75 -15.31 2 8.314 120 19.83
n159 -0.75 29.04 2.067 0 0.0095 0
8.314 0.08
n159 -0.75 44.442 2 1x(us.Tee-Br) = 10 56.87 120 19.91
n151 -0.75 73.482 2.067 10 0.0531 0
66.869 3.55
n151 -0.75 214.43 4 6.446 120 23.45
n7 -0.75 287.912 4.026 0 0.0259 0
6.446 0.17
n7 -0.75 78.667 4 1x(us.Tee-Br) = 20 5.463 120 23.62
n23 -0.75 366.579 4.026 20 0.0405 0
25.463 1.03
n23 -0.75 294.187 4 1x(us.90) = 10 1.62 120 24.65
n22 -0.75 660.766 4.026 10 0.1206 0
11.62 1.4
n22 -0.75 0 4 1x(us.Bfly) = 12 12.616 120 26.06
n2 -0.75 660.766 4.026 1x(us.Swing) = 22 44 0.1206 0
1x(us.90) = 10 56.616 6.83
n2 -0.75 0 4 2.418 120 32.89
src1 -0.75 660.766 4.026 0 0.1206 0
2.418 0.29
h214 -0.35 11.2 44.387 1 1x(us.Tee-Br) = 5 1.312 120 15.71
n161 -0.75 44.387 1.049 5 0.5676 0.57
6.312 3.58
n161 -0.75 15.31 2 9.186 120 19.86
n162 -0.75 59.697 2.067 0 0.0361 0
9.186 0.33
n162 -0.75 44.773 2 1x(us.Tee-Br) = 10 3.27 120 20.19
n163 -0.75 104.47 2.067 10 0.1018 0
13.27 1.35
n163 -0.75 109.96 4 11.948 120 21.54
n35 -0.75 214.43 4.026 0 0.015 0
11.948 0.18
n35 -0.75 -31.289 4 14.767 120 21.72
n36 -0.75 183.141 4.026 0 0.0112 0
14.767 0.17
n36 -0.75 -26.579 4 12.464 120 21.89
n37 -0.75 156.562 4.026 0 0.0084 0
12.464 0.1
n37 -0.75 -23.198 4 14.767 120 21.99
n38 -0.75 133.364 4.026 0 0.0062 0
14.767 0.09
n38 -0.75 -19.828 4 12.464 120 22.08
n39 -0.75 113.536 4.026 0 0.0046 0
12.464 0.06
n39 -0.75 -17.442 4 1x(us.90) = 10 5.24 120 22.14
n21 -0.75 96.094 4.026 10 0.0034 0
15.24 0.05
n21 -0.75 0 4 1x(us.90) = 10 96.195 120 22.19
n40 -0.75 96.094 4.026 10 0.0034 0
106.19 0.36
5

© 2006 National Fire Protection Association Page 40


Job name : Sheet number:___________________

PIPE INFORMATION

Node 1 Elev 1 K-Factor 1 Flow added(q)* Nominal ID Fittings L C Factor total (Pt)
Node 2 Elev 2 K-Factor 2 Total flow (Q) Actual ID quantity x (name) = length F Pf per m elev (Pe) NOTES
T frict (Pf)

(m) (gpm/psi½) (gpm) (in) (m) (m) (psi) (psi)

n40 -0.75 0 4 5.24 120 22.55


n20 -0.75 96.094 4.026 0 0.0034 0
5.24 0.02
n20 -0.75 17.442 4 12.464 120 22.57
n19 -0.75 113.536 4.026 0 0.0046 0
12.464 0.06
n19 -0.75 19.828 4 14.767 120 22.63
n18 -0.75 133.364 4.026 0 0.0062 0
14.767 0.09
n18 -0.75 23.198 4 12.464 120 22.72
n17 -0.75 156.562 4.026 0 0.0084 0
12.464 0.1
n17 -0.75 26.579 4 14.767 120 22.82
n16 -0.75 183.141 4.026 0 0.0112 0
14.767 0.17
n16 -0.75 31.289 4 1x(us.90) = 10 3.241 120 22.99
n15 -0.75 214.43 4.026 10 0.015 0
13.241 0.2
n15 -0.75 0 4 1x(us.90) = 10 7.515 120 23.19
n14 -0.75 214.43 4.026 10 0.015 0
17.515 0.26
n14 -0.75 0 4 0.221 120 23.45
n151 -0.75 214.43 4.026 0 0.015 0
0.221 0
h212 -0.35 11.2 44.442 1 1x(us.Tee-Br) = 5 1.312 120 15.75
n159 -0.75 44.442 1.049 5 0.5689 0.57
6.312 3.59
h215 -0.35 11.2 44.773 1 1x(us.Tee-Br) = 5 1.312 120 15.98
n162 -0.75 44.773 1.049 5 0.5768 0.57
6.312 3.64
h203 -0.35 11.2 47.633 1 1.312 120 18.09
n132 -0.75 47.633 1.049 0 0.6469 0.57
1.312 0.85
n132 -0.75 -16.711 2 8.314 120 19.51
n131 -0.75 30.922 2.067 0 0.0107 0
8.314 0.09
n131 -0.75 47.745 2 1x(us.Tee-Br) = 10 56.87 120 19.59
n7 -0.75 78.667 2.067 10 0.0602 0
66.869 4.03
h204 -0.35 11.2 47.681 1 1.312 120 18.12
n133 -0.75 47.681 1.049 0 0.6481 0.57
1.312 0.85
n133 -0.75 16.711 2 9.186 120 19.54
n134 -0.75 64.392 2.067 0 0.0416 0
9.186 0.38
n134 -0.75 48.16 2 1x(us.Tee-Br) = 10 3.27 120 19.92
n26 -0.75 112.552 2.067 10 0.1169 0
13.27 1.55
n26 -0.75 -2.592 4 14.931 120 21.48
n163 -0.75 109.96 4.026 0 0.0044 0
14.931 0.07
h193 -0.35 11.2 47.736 1 1.312 120 18.17
n120 -0.75 47.736 1.049 0 0.6494 0.57
1.312 0.85

© 2006 National Fire Protection Association Page 41


Job name : Sheet number:___________________

PIPE INFORMATION

Node 1 Elev 1 K-Factor 1 Flow added(q)* Nominal ID Fittings L C Factor total (Pt)
Node 2 Elev 2 K-Factor 2 Total flow (Q) Actual ID quantity x (name) = length F Pf per m elev (Pe) NOTES
T frict (Pf)

(m) (gpm/psi½) (gpm) (in) (m) (m) (psi) (psi)

n120 -0.75 -14.554 2 8.314 120 19.59


n119 -0.75 33.183 2.067 0 0.0122 0
8.314 0.1
n119 -0.75 47.863 2 1x(us.Tee-Br) = 10 56.87 120 19.69
n124 -0.75 81.046 2.067 10 0.0636 0
66.869 4.26
n124 -0.75 213.141 4 1x(us.Tee-Br) = 20 6.305 120 23.94
n23 -0.75 294.187 4.026 20 0.027 0
26.305 0.71
h202 -0.35 11.2 47.745 1 1.312 120 18.17
n131 -0.75 47.745 1.049 0 0.6497 0.57
1.312 0.85
h194 -0.35 11.2 47.773 1 1.312 120 18.19
n121 -0.75 47.773 1.049 0 0.6504 0.57
1.312 0.85
n121 -0.75 14.554 2 9.186 120 19.62
n122 -0.75 62.326 2.067 0 0.0391 0
9.186 0.36
n122 -0.75 48.223 2 1x(us.Tee-Br) = 10 3.27 120 19.98
n135 -0.75 110.55 2.067 10 0.1131 0
13.27 1.5
n135 -0.75 2.592 4 6x(us.90) = 60 16.877 120 21.48
n123 -0.75 113.141 4.026 60 0.0046 0
76.876 0.35
n123 -0.75 -28.116 4 11.75 120 21.83
n25 -0.75 85.025 4.026 0 0.0027 0
11.75 0.03
n25 -0.75 -25.417 4 1x(us.Tee-Br) = 20 4.695 120 21.86
n5 -0.75 59.608 4.026 20 0.0014 0
24.695 0.03
n5 -0.75 0 4 17.14 120 21.9
n148 -0.75 59.608 4.026 0 0.0014 0
17.14 0.02
n148 -0.75 100 4 1x(us.90) = 10 71.542 120 21.92
n24 -0.75 159.608 4.026 10 0.0087 0
81.542 0.71
n24 -0.75 0 4 4.695 120 22.63
n6 -0.75 159.608 4.026 0 0.0087 0
4.695 0.04
n6 -0.75 25.417 4 11.75 120 22.67
n112 -0.75 185.025 4.026 0 0.0114 0
11.75 0.13
n112 -0.75 28.116 4 6x(us.90) = 60 16.877 120 22.8
n124 -0.75 213.141 4.026 60 0.0148 0
76.876 1.14
h192 -0.35 11.2 47.863 1 1.312 120 18.26
n119 -0.75 47.863 1.049 0 0.6527 0.57
1.312 0.86
h205 -0.35 11.2 48.16 1 1.312 120 18.49
n134 -0.75 48.16 1.049 0 0.6602 0.57
1.312 0.87
h195 -0.35 11.2 48.223 1 1.312 120 18.54
n122 -0.75 48.223 1.049 0 0.6618 0.57
1.312 0.87

© 2006 National Fire Protection Association Page 42


Job name : Sheet number:___________________

PIPE INFORMATION

Node 1 Elev 1 K-Factor 1 Flow added(q)* Nominal ID Fittings L C Factor total (Pt)
Node 2 Elev 2 K-Factor 2 Total flow (Q) Actual ID quantity x (name) = length F Pf per m elev (Pe) NOTES
T frict (Pf)

(m) (gpm/psi½) (gpm) (in) (m) (m) (psi) (psi)

his2 -5.2 100 2 1x(us.90) = 5 0.659 120 22.89


n150 -5.2 100 2.067 5 0.0939 0
5.659 0.53
n150 -5.2 0 2 1x(us.90) = 5 14.6 120 23.42
n149 -0.75 100 2.067 5 0.0939 -6.33
19.6 1.84
n149 -0.75 0 2 1x(us.Tee-Br) = 10 21.812 120 18.93
n148 -0.75 100 2.067 10 0.0939 0
31.812 2.99
n160 -0.75 0 2 11.043 120 19.83
n161 -0.75 15.31 2.067 0 0.0029 0
11.043 0.03
n35 -0.75 0 2 2x(us.Tee-Br) = 20 96.195 120 21.72
n16 -0.75 31.289 2.067 20 0.0109 0
116.19 1.27
5
n36 -0.75 0 2 2x(us.Tee-Br) = 20 96.195 120 21.89
n17 -0.75 26.579 2.067 20 0.0081 0
116.19 0.94
5
n37 -0.75 0 2 2x(us.Tee-Br) = 20 96.195 120 21.99
n18 -0.75 23.198 2.067 20 0.0063 0
116.19 0.73
5
n38 -0.75 0 2 2x(us.Tee-Br) = 20 96.195 120 22.08
n19 -0.75 19.828 2.067 20 0.0047 0
116.19 0.55
5
n39 -0.75 0 2 2x(us.Tee-Br) = 20 96.195 120 22.14
n20 -0.75 17.442 2.067 20 0.0037 0
116.19 0.43
5
n132 -0.75 0 2 11.043 120 19.51
n133 -0.75 16.711 2.067 0 0.0034 0
11.043 0.04
n26 -0.75 0 4 11.769 120 21.48
n135 -0.75 2.592 4.026 0 0 0
11.769 0
n120 -0.75 0 2 11.043 120 19.59
n121 -0.75 14.554 2.067 0 0.0026 0
11.043 0.03
n123 -0.75 0 2 2x(us.Tee-Br) = 20 88.682 120 21.83
n112 -0.75 28.116 2.067 20 0.009 0
108.68 0.97
2
n25 -0.75 0 2 2x(us.Tee-Br) = 20 88.682 120 21.86
n6 -0.75 25.417 2.067 20 0.0074 0
108.68 0.81
2

* Discharge shown for flowing nodes only