Professional Documents
Culture Documents
Authorized licensed use limited to: Kyungsung University. Downloaded on March 13,2010 at 06:04:21 EST from IEEE Xplore. Restrictions apply.
efficiency operation depends upon parameters of the induction
motor equivalent circuit which can vary with temperature or satura-
tion. Further, the value of rotor frequency that yields maximum
efficiency performance is a function of motor speed. Thus, with no
provision to adjust rotor frequency as either motor parameters or
speed change, operation usually occurs at less than maximum
efficiency.
During the past few years, several papers have appeared in the
literature offering control regimes attempting to maintain operation
of adjustable speed drives at the maximum efficiency [l-51. The
potential for energy savings is significant as documented by Refer-
ences 4 and 5. However, all of these proposed control schemes Fig. 2 Per phase equivalent circuit
require an accurate knowledge of the motor parameters for imple-
mentation. Maximum efficiency slip is more sensitive to the value
of rotor resistance .than any other motor parameter, yet rotor resis- The input impedance of the equivalent circuit of Fig. 2 can be
tance changes with load profile, and dynamic measurement of its written as
value is quite difficult, if possible.
Kusko and Galler [2] have offered mention of a testing con- Z,=[ R ~ + R ~ , ( f . s ) l + j [ x ~ + x , ( f . s ) l (7)
troller concept that can be utilized to vary rotor slip frequency in a where
manner to minimize input power while maintaining a particular
torque-speed load point. Kirschen, Novotny, and Lip0 [6] describe
R, (f, s) + s) = (Rms+ j
implementation of a testing or perturbing controller for minimum
loss operation of a field-oriented controlled induction motor. Using (8), the primary copper losses (PI) are given by
Significant energy savings are found for operation at light torque
loads for all speeds. For torque loads near nameplate rated value,
(9)
energy savings at low speed operation are reported.
In a recent thesis, Mehanna [7] presents an adaptive controller
Through use of current division to determine I,, the total average
modification of a constant rotor frequency inverter to operate at
optimal efficiency. The concept is similar to that used by Kirschen value of power crossing the induction motpr airgap (P,) is
et a1 [6] except that the extra complexity of the field-oriented con- expressed as follows:
trol is not required. Further, since the adaptive controller can be R, 3e+X:)I:R,/s
p =31~-=
realized by modification of a constant voltshertz inverter, it offers , s A
the potential of retrofit to inverters already in field service. The
initial results of a computer simulation of this model are promising -
3R
,(: + X2', ) V: R2/ s (10)
in that the controller has been demonstrated capable of seeking out A [(RI +R2, 1' + (XI + X, ),I
the maximum efficiency slip point. Obviously, the advantage of
where
this (perturbing rotor frequency or P E ) scheme is that no
knowledge of motor parameters is necessary; thus, parameter varia-
tions with temperature and saturation are of no consequence.
Implementation and test of this concept are the subject of this
A=
I :I2
R,,+L +(X,,,s+X2)2
A. Efficiency Determination
Authorized licensed use limited to: Kyungsung University. Downloaded on March 13,2010 at 06:04:21 EST from IEEE Xplore. Restrictions apply.
where PI, P,, P,, and PR are given by (9), (IO), (12) and (13), frequency to restore maximum efficiency operation. Thus,
respectively. However, VI depends upon the load torque T,. efficiency improvement is expected when using PRF control for the
Specifically, the developed electromechanical torque (T,) must case of reduced value constant load torque.
equal the load torque, or In order to substantiate the above predictions, two computer
programs were built up to model the motor performance for both
PRF and constant VMz operation. For both programs, the motor
was modelled by the approximate frequency-dependent parameters
Substitution of (lo), (13) and (14) into (17) and rearrangement documented in the Appendix and selected by guidance from Refer-
ence 8. The motor load toque was characterized as dependent on
[
leads to
speed squared with value equal to the rated value at 100% motor
I = s x f A [(RI+ Rz,,,1' + (XI + XZ,,,)'I[TL+k, (1 - s) x f I
3' Rz eS+
x&)
,]"20 8)
speed. The first program predicted PRF performance using the
limited range search approach described in the previous section.
The second program calculated constant V/Hz performance
In general, TL= TL(q,,) is speed dependent; thus, substitution of with V , / f maintained at the value determined by ratio of nameplate
(18) into (16) yields efficiency as a function of s, f, and N,: rated values. Implementation was carried out by substituting
VI = f ( V l / f ) m d and f = o , / ( l - s ) x into (17) and incrementing s
(19) from a small value until the equality of (17) was established.
Results of the theoretical study are. presented by Figs. 3-5.
where Fig. 3 shows that for speed less than approximately 65% with the
squared-law torque load, significant efficiency improvement is
f3 = X S (1 -S> f R, (&,+x~,)[TL(O,)+kNK(l -s) fl (20)
shown by PRF control over constant V/Hz control. Figs. 4 and 5
€4 = kN S R, [(I -S)f12 + es
(Cs ) (21) illustrate that for the lower speed operation the PRF control acts to
i
f, = [ T ~ ( O , ) + k ~ x ( 1 - - S ) f ] sR,&,+X&) +
lower voltage and increase frequency over constant VMz control at
each operating point to result in a reduction in core losses and,
subsequently, to reduce the total losses.
R,[(S~,+R~)~+S~(X~+X,)~I
+R,,,,,[R;+s2X;1
B. Theoretical Predictions
reduced in magnitude, points A and C would move to the right Percentage Speed
228
Authorized licensed use limited to: Kyungsung University. Downloaded on March 13,2010 at 06:04:21 EST from IEEE Xplore. Restrictions apply.
(a,) are compared by the speed summer to yield the speed error
loo 1 / ” signal (vE). vE is processed by the PI controller to give the error
- PRF Control
signal vk used to set the value of bias signal Avds that adjusts the
V/Hz Control
volts/hertz ratio, thus changing the dc link voltage. If a, is greater
~
Percentage Speed
The perturbing subcontroller senses the inverter input power
(P) and then either increases or decreases signal So,. If a change in
Fig. 5 Voltage-speed characteristics 60, reduces the value of P, the perturbing subcontroller then
changes 60, another increment in the previous direction. If inverter
card offered by the inverter manufacturer is installed in the power P increases due to a change in &or, then the subcontroller
inverter. The card provides the normal inverter adjustments for begins to alter 60,in the opposite direction. Hence, the inverter
setting acceleration, deceleration, and volts/hertz ratio. However, output frequency is adjusted until a point at which minimum input
two features of the card are of particular interest in the design of power to maintain the mechanical load point is reached.
the controller that is the focus of the described research. First, the Although the controller concept has been presented by analog
slip signal input can be bidirectional signal to dynamically alter the block diagram, the actual realization is better suited to a digital
volts/hertz control ratio, allowing control of the dc link voltage of implementation. An 8-bit microprocessor-based implementation of
the inverter independent of inverter output frequency. Second, the the controller is used. Introduction of 12-bit A/D and D/A convert-
card accepts a square-wave input reference signal to directly ers are necessary to obtain the performance accuracy required by
control the inverter output frequency. In-house circuit designs are the problem. An abbreviated flow chart of the adaptive controller
implemented to allow operation in either of two modes: (1) con- program is displayed by Fig. 7 to give an understanding of the con-
stant rotor frequency control, in which external command of rotor troller logic.
frequency is set and the controller acts to adjust dc link voltage
magnitude to maintain the set speed; (2) perturbing control, in B. Test Descriptions
which rotor frequency command is perturbed in a manner to search
for minimum input power while dc link voltage is adjusted to Losses of components under test are measured by the princi-
maintain the set speed. ple of air calorimetry [9] to circumvent the error that can be intro-
A block diagram of the adaptive perturbing controller is duced by electrical instrument with inadequate frequency response.
presented by Fig. 6. Speed command (a,) and actual motor speed
3 - PHASE
I N PUT
I
TRANS-
DUCER
1
PERTURBING
SUB-
CONTROLLER
I
a,
ROTOR FREP.
,a,T,-r
COMM.
.--
FW-1
FREO
SUMMER
P I CONTROLLER
1“avdc
’ v;
,
FREP C O M M .
NONLINEAR
FEED B A C K
8
SPEED S U M M E R I
Fig. 6 Block diagram of adaptive controller
229
Authorized licensed use limited to: Kyungsung University. Downloaded on March 13,2010 at 06:04:21 EST from IEEE Xplore. Restrictions apply.
Fig. 9 Rotor frequency (upper trace) and
input power (lower trace)
traces of input power and rotor frequency command for the case of
50% speed- 114 torque, illustrating the dynamic nature of the PRF
control. The rotor frequency has decreased by 23 steps for .05
Hdstep from 1.33 Hz to .19 Hz; meanwhile input power has
decreased by 27.5% for standard-efficiency induction motor.
The PRF control is successful in finding an operating point to
improve motor efficiency and, consequently, the overall system
efficiency over the V/Hz control. Figs. 10 and 11 show percentage
efficiency vs. speed for 114 and 414 torque, respectively, comparing
overall system efficiency for V/Hz control and PRF control. As
torque increases, the efficiency improvement of PRF over V/Hz
decreases to an insignificant value, thus substantiating the earlier
prediction that significant efficiency improvement only for reduced
torque loads is to be expected.
The specific impact of the previous conclusion that the non-
linear torque load type is best suited for PRF control can be seen
quantitatively from the plot of the square-law torque load data in
Fig. 12. Then the torque demand at 75% and 50% speed would be
56.25% (9/16) and 25% (114) of rated torque, respectively. The
Fig. 7 Flow chart of controller program
RESULTS OF TESTS
I -!
Ib 20 io 40 510 $0 A Bo 90 ,bo
Percentage Speed
Fig. 8 Block diagram of test arrangement Fig. 11 Efficiency-speeddata for 414 torque
230
Authorized licensed use limited to: Kyungsung University. Downloaded on March 13,2010 at 06:04:21 EST from IEEE Xplore. Restrictions apply.
loo 1 Frequency Dependent Model:
I t perturbing c o n t r o i
Rio = 0.2151 R cI = 0.8868 x lo4
R20 = 0.1231 R c2 = 1.236x
C, = 2.2133~10-~ CL = 1.75
p = 1.45
ACKNOWLEDGEMENT
-
APPENDIX MACHINE PARAMETERS [7] C. Y. Mehanna, "Perturbing Controller for Minimum Loss
Operation of Induction Machines", M.S. Thesis, University of
Nameplate Data: Kentucky, August 1985.
10 hp, 2301460 V, 27113.5 A [8] A. Bellini, R. Miglio, U. Reggiani, and C. Tassoni, "Voltage-
1755 rpm, 60 Hz, Design B Frequency Law in Frequency-Controlled Induction Motor
1.15 SF Drives", Proceedings of I978 IEEE-IAS Annuat Meeting, pp.
690-693.
Equivalent Circuit Parameters (60 Hz):
RI = 0.2264 R R2 = 0.1256R [9] J. J. Cathey, M. Rabiee, and S. H. Jan, "Application of
XI = 0.5842 R X, = 0.7292 R Calorimetry in Efficiency Determination of Power Condi-
R,,,%= 0.8382 R X,, = 10.367 R tioned Drives", Electric Machines and Power Systems, vol.
14, no. 1, 1988, pp. 33-44.
230 V connection
23 1
Authorized licensed use limited to: Kyungsung University. Downloaded on March 13,2010 at 06:04:21 EST from IEEE Xplore. Restrictions apply.