SLIDING STEM CONTROL VALVE SPECIFICATION

Customer: GIPROMORNEFTEGAZ Emerson Process Management AG


Contact: Contact: Alexander Ushakov
Reference: Quote: 401-042825 Rev: 01 24 FEB 05
Project: Data Sheet:
Item: 001 Rev: Qty: 1

Service: Presure Control Valve Positioner Type: DVC6010F, Std Cntl / Adv Diag
Input Signal: Fieldbus
Tag: PIC Access: Airset
Size and Type: 8 Inch ET Body Gauges: Yes, , Supply, Output
Action: Single/Direct
Body Style: Globe Certification: ATEX/LCIE XP
Design Temp: 100 deg C
Design Press: 100 bar-g Controller Type: None
End Connect: Class 600 Action:
In: RTJ Flanged Measure Element:
Out: RTJ Flanged Range:
Material: WCC HT Output:
Ports: Single Port Mounting:
Flow Directn: Down Airset:
Mounting:
Trim Number: DST 3 stages
Cage Matl: 316/ENC Transducer: None
Retainer Matl: None Input Signal:
Bushing Matl: Output Signal:
Seat Ring Matl: 316/CoCr-A Seat Action:
VALVE PLUG Mounting:
Material: 316/CoCr-A Airset:
Guiding: Certifications:
Balance: Balanced
Shutoff Class: ANSI Class III (0.1%) Line In: 10.000 in, STD
Port Size: 5 3/8 Inch Line Out: 10.000 in, STD
Characteristic: Linear Insulation:
Stem Material: Nitronic 50 Service Cond: Throttling
Stem Size: 3/4 inch Process Fluid: OIL
Minimum Normal 80/4
Bonnet Style: Plain SG 0.851 0.851 0.851
Boss Size: 3 9/16 Inch T deg C 20.000 20.000 20.000
Packing: Dbl PTFE #1 P1 bar(g) 60.000 60.000 80.000
Access: Pv bar(g) 0.095 0.095 0.095
Bolt, Bonnet: B7/2H dP bar 50.000 50.000 76.000
PackFlg/Bltg: Q m3/h 801.000 867.000 850.000
Vlv Lpa dB(A) < 85 < 85 < 85
Actuator: Spg & Diaph Cv 120.811 130.765 104.055
Type/Size: 667/76 Fl 0.975 0.975 0.975
Travel: 2 Inch Notes: CHOKED
Bench Set: 0.98 - 2.50 bar-g
Push Down To: Close
Supply: Instrumentation Air % Open - - -
To Actuator: 2.8 bar-g
Fails Valve: Close Maximum Rated Flow Coefficient: 190 Cv
Handwheel: Side Mtd

1. Counter Flanges ASTM A105,


Studs, Nuts, Seal Rings
2. Limit Switch, Open Position, Exd
3. dPoff = 80 bar

1.2.39-1.2.39-RUMOS_NT1 28 FEB 05 10:07:33 am


SIZING CALCULATION
GIPROMORNEFTEGAZ Emerson Process Management AG

Contact: Contact: Alexander Ushakov


RFQ: Quote: 401-042825 Rev: 01 Date: 24 FEB 05
Project:

Item: 001 - VALVE/REGULATOR SIZING CALCULATION: ISA/EN Liquid


Item Desc: 8 in ET DST 3 Stage Trim
Tags: PIC

SERVICE & SIZING Minimum Normal 80/4 60/4


Liquid Name OIL OIL OIL OIL
Inlet Pressure (bar(g)) 60.000 60.000 80.000 60.000
Pressure Drop (bar) 50.000 50.000 76.000 56.000
Atm. Pressure (kg/cm2a) 1.033 1.033 1.033 1.033

Critical Pressure (bar(g)) 34.999 34.999 34.999 34.999


Vapor Pressure (bar(g)) 0.095 0.095 0.095 0.095
Specific Gravity 0.851 0.851 0.851 0.851
Temperature (deg C) 20.000 20.000 20.000 20.000
Liquid Flow Rate (m3/h) 801.000 867.000 850.000 850.000
Pressure Recovery Factor, Fl 0.975 0.975 0.975 0.975
Combined Recovery Factor, Flp 0.974 0.974 0.974 0.974
Piping Correction Factor, Fp 1.000 1.000 1.000 1.000
Critical Pres Ratio Factor, Ff 0.911 0.911 0.911 0.911
Valve diameter d (in) 8.000 8.000 8.000 8.000
Inlet Pipe Diameter, D1 (in) 10.000 10.000 10.000 10.000
Outlet Pipe Diameter, D2 (in) 10.000 10.000 10.000 10.000
Cavitation Index, Kc 1.000 1.000 1.000 1.000

Sizing Coefficient, Cv 120.811 130.765 104.055 121.139


dP Choked (bar) 56.924 56.924 75.898 56.924
dP Cavitation (bar) 59.905 59.905 79.905 59.905
Cavitrol Trim Application Ratio, Ar 0.835 0.835 0.951 0.935
Notes: CHOKED

NOISE CALCULATION
Fisher Valve/Reg Trim Type CAVIII 2STG CAVIII 2STG CAVIII 2STG CAVIII 2STG
Downstream Pipe Size (in) 10.000 10.000 10.000 10.000
Downstream Pipe Schedule STD STD STD STD
Valve/Reg LpA (SPL) (dB(A)) < 85 < 85 < 85 < 85

1.2.39-1.2.39-RUMOS_NT1 28 FEB 05 10:07:33 am