Control Valve Specification Sheet

Customer : Automatizacion Tag nos. : PCV-0623 Prepared by :


Project : T220425-499 Quantity : 1 nos. Page No.:1 Alternate : Michelle Gonzalez
End User : ODL Quote No. : T220425-499 Date/Rev No. : 26/Apr/2022/ Trimteck, LLC
End User Location : P.O No. : Date/Rev No. : Coral Springs, FL
Distributor : Valve Serial Nos. : Accu Valve Ver.: 9.11

1 Pipe Size / Schedule (In/Out) 4.00 / 4.00 inch ; Sch 40 / Sch 40 50 Act. Type/Matl Rack and Pinion / Aluminium
2 Line 51 Actuator Model/Size OpRPA / 125
3 P&ID 52 Rotation 90°
4 Application Valvula de Recirculacion Bomba 53 Spring K8
BOP-071 54 Air to / Fail Position Close / Fail Open
5 Process Fluid Crude Oil 55 Volume Tank
6 Design Press./Temp. 258.00 psi g / 200.00 deg F 56 Tubing & Fittings 1/4" 316 SS Swagelok
7 Allow Noise/Add Attn 85 / 0 dBA 57 Handwheel
8 NACE Compliance Non - NACE 58 Shut off Pres/Act.Fun 258.00 psi g / Throttling
9 Min Nor Max Other 59 Avail. Air Supply 60 psi g
10 Liq Flow Rt U.S.bbl/d 2400.00 6840.00 7680.00 60 Act./Pos. O-Rings Buna-N
11 Inlet Press psi g 63.00 150.00 150.00 61 Make/Model ABB / TZIDC
12 Outlet Press psi g 7.000 15.00 15.00 62 Signal/Options 4 - 20 mA HART / SS Gauges
13 Temperature °F 80.00 130.00 160.00 63 Transducer 4 - 20 mA Feedback
14 Viscosity cSt 113.50 347.00 3971.00 64 Mounting Bracket
15 Vapour Press. psi a 0.80000 0.80000 0.80000 65 Tag #/Cert / Class 1, Div 2, Gr. C,D
16 Critical Press psi a 482.97 482.97 482.97
17 Density lb/ft3 60.30 59.10 58.30 66 Material Aluminium
18 Flow Coeff. (Cv) 10.5 21.3 36.0 67 Model
19 Est Stroke (Degree) 34.8 48.1 59.8 68 Indicate
20 Pressure Drop psi 56.00 135.00 135.00 69 Type
21 Choke Drop psi 46.81 99.74 99.74 70 Voltage/Elec Conduit
22 **Noise (dBA - AV) <70 <70 71.00 71 Tag #
23 Valve Vel ft/s 7.156 20.39 22.90 72 Model
24 Pipe Vel ft/s 1.765 5.031 5.648 73 Position On De-en
25 Valve Model / Body Type OpVEE/V-Notch Ball 74 Electrical
26 Size/Pressure Rating 2.00 inch / CL 150 75 Mounting
27 Trim # / Cv / Characteristic 2.00 / 107 / Modified =% 76 Body Material
28 Ball Pressure Class CL 150-300 77 Haz. Loc.
29 Shaft Orientation Shaft Up 78 Tag #
30 Body Matl ASTM A216 WCB 79 Air Fltr Reg/Set press TT-AFR / 60 psi g
31 Bonnet Matl Carbon Steel 80 Filter / Gauges Yes / Yes
32 End Conn / Face to Face Flanged RF (Integral) / ISA S75.04 81 Flow Booster
33 Flange Finish 125-250 Ra 82 Booster Config
34 Bonnet Type Standard 83 Quick Exhaust
35 Ball Material 316 SS Hard Chrome Plated 84 SupTube/Jctn Box
36 Shaft Material 17-4PH 85 Lockup None
37 Seat Configuration Metal 86 Plate ID
38 Seat Matl Metal / Soft Inconel / 87 Plate Type
39 Retainer Material 316SS+CVD-5B 88 Controller Model
40 Bearings Nitronic 60 89 Pwr. Sup.
41 Packing Matl / Style / Vac / Fire PTFE/Glass Filled (V-Ring) / Standard 90 Wiring Conn. Type
42 Gland Flange Matl / Bolting Stainless Steel / Stainless Steel 91 NDE/Paint Test
43 Bonnet Port Type 92 Paint Test
44 End Plug Stainless Steel 93 Drawings
45 End Seal PTFE 94 Hydrostatic Testing ANSI/ISA 75.19.01
46 Yoke Bolting Stainless Steel 95 Seat Leak/Class ANSI/FCI-70-2 / Class IV
47 96 Documentation Final Inspection
48 97 Cert of Conf. PO or Spec
49 98 Cleaning
50 99 CMTR
51 100 Painting System
101 Body Yoke
102 Actuator Handwheel

** Insulation Type : 'None' Thickness : 0.0

Line#: Remarks :
1
2
3
4
5
Quantity: 1 Sheet 1 of 3
Flow Chart
Customer : Automatizacion Tag nos. : PCV-0623 Prepared by :
Project : T220425-499 Quantity : 1 nos. Page No.:1 Alternate : Michelle Gonzalez
End User : ODL Quote No. : T220425-499 Date/Rev No. : 26/Apr/2022/ Trimteck, LLC
End User Location : P.O No. : Date/Rev No. : Coral Springs, FL
Distributor : Serial No. : Accu Valve Ver.: 9.11

Fluid Name/State : Crude Oil/Liquid


Min Nor Max Other
Temp deg F 80.000 130.000 160.000 ----
P1 psi g 63.000 150.000 150.000 ----
P2 psi g 7.000 15.000 15.000 ----
Liq Flow U.S.bbl/d 2,400.000 6,840.000 7,680.000 ----
Gas Flow ---- ---- ---- ---- ----
Visc cSt 113.500 347.000 3,971.000 ----
VP psi a 0.800 0.800 0.800 ----
Critical Press psi a 482.970 482.970 482.970 ----
Density lb/ft3 60.300 59.100 58.300 ----
MW ---- ---- ---- ---- ----
Comp. Factor ---- ---- ---- ---- ----
Cp/Cv ---- ---- ---- ---- ----
DP psi g 56.000 135.000 135.000 ----
DpC psi 46.810 99.740 99.740 ----
Vel ft/s 7.156 20.390 22.900 ----
Noise (dBA - AV) <70 <70 71.00 ----
Flow Cap (Cv) 10.500 21.300 36.000 ----
Stroke (Degree) 34.800 48.100 59.800 ----
Info ---- ---- Cav. Cav. ----

** Insulation Type : 'None' Thickness : 0.0

Flow Direction: Shaft Up


Trim Characteristic : Modified =%
* - DISASSEMBLY / MAINTENANCE CLEARANCE
A B C D E WT
INCH 4.9 8.58 6.1 11.73 5.51
mm 124 218 155 298 140

Note: Dimensions are certified correct as per associated specification sheet. End connections
and scaling may not be actual. For accessory information, see associated specification sheet.

MODEL ACTUATOR

OpVEE 125 SQ IN CERTIFIED DIMENSIONAL DRAWING


SIZE AIR TO BY CUSTOMER ITEM

2.00 CLOSE MICHELLE GONZALEZ Automatizacion


RATING / F/F STD FAIL DATE VALVE TAG SHEET

CL 150/ISA S75.04 OPEN 10-June-2020 PCV-0623


END CONNECTION SPRING THIRD ANGLE PROJECTION P.O. NUMBER REVISION

FLANGED RF (INTEGRAL) K8 0
SHAFT TRIM / CV PROJECT SERIAL NUMBER

SHAFT UP 2/107 T220425-499


Control Valve Specification Sheet
Customer : Automatizacion Tag nos. : PCV-0625 Prepared by :
Project : T220425-499 Quantity : 1 nos. Page No.:2 Alternate : Michelle Gonzalez
End User : ODL Quote No. : T220425-499 Date/Rev No. : 26/Apr/2022/ Trimteck, LLC
End User Location : P.O No. : Date/Rev No. : Coral Springs, FL
Distributor : Valve Serial Nos. : Accu Valve Ver.: 9.11

1 Pipe Size / Schedule (In/Out) 4.00 / 4.00 inch ; Sch 40 / Sch 40 50 Act. Type/Matl Rack and Pinion / Aluminium
2 Line 51 Actuator Model/Size OpRPA / 125
3 P&ID 52 Rotation 90°
4 Application Valvula de Recirculacion Bomba 53 Spring K8
BOP-072 54 Air to / Fail Position Close / Fail Open
5 Process Fluid Crude Oil 55 Volume Tank
6 Design Press./Temp. 258.00 psi g / 200.00 deg F 56 Tubing & Fittings 1/4" 316 SS Swagelok
7 Allow Noise/Add Attn 85 / 0 dBA 57 Handwheel
8 NACE Compliance Non - NACE 58 Shut off Pres/Act.Fun 258.00 psi g / Throttling
9 Min Nor Max Other 59 Avail. Air Supply 60 psi g
10 Liq Flow Rt U.S.bbl/d 2400.00 6840.00 7680.00 60 Act./Pos. O-Rings Buna-N
11 Inlet Press psi g 63.00 150.00 150.00 61 Make/Model ABB / TZIDC
12 Outlet Press psi g 7.000 15.00 15.00 62 Signal/Options 4 - 20 mA HART / SS Gauges
13 Temperature °F 80.00 130.00 160.00 63 Transducer 4 - 20 mA Feedback
14 Viscosity cSt 113.50 347.00 3971.00 64 Mounting Bracket
15 Vapour Press. psi a 0.80000 0.80000 0.80000 65 Tag #/Cert / Class 1, Div 2, Gr. C,D
16 Critical Press psi a 482.97 482.97 482.97
17 Density lb/ft3 60.30 59.10 58.30 66 Material Aluminium
18 Flow Coeff. (Cv) 10.5 21.3 36.0 67 Model
19 Est Stroke (Degree) 34.8 48.1 59.8 68 Indicate
20 Pressure Drop psi 56.00 135.00 135.00 69 Type
21 Choke Drop psi 46.81 99.74 99.74 70 Voltage/Elec Conduit
22 **Noise (dBA - AV) <70 <70 71.00 71 Tag #
23 Valve Vel ft/s 7.156 20.39 22.90 72 Model
24 Pipe Vel ft/s 1.765 5.031 5.648 73 Position On De-en
25 Valve Model / Body Type OpVEE/V-Notch Ball 74 Electrical
26 Size/Pressure Rating 2.00 inch / CL 150 75 Mounting
27 Trim # / Cv / Characteristic 2.00 / 107 / Modified =% 76 Body Material
28 Ball Pressure Class CL 150-300 77 Haz. Loc.
29 Shaft Orientation Shaft Up 78 Tag #
30 Body Matl ASTM A216 WCB 79 Air Fltr Reg/Set press TT-AFR / 60 psi g
31 Bonnet Matl Carbon Steel 80 Filter / Gauges Yes / Yes
32 End Conn / Face to Face Flanged RF (Integral) / ISA S75.04 81 Flow Booster
33 Flange Finish 125-250 Ra 82 Booster Config
34 Bonnet Type Standard 83 Quick Exhaust
35 Ball Material 316 SS Hard Chrome Plated 84 SupTube/Jctn Box
36 Shaft Material 17-4PH 85 Lockup None
37 Seat Configuration Metal 86 Plate ID
38 Seat Matl Metal / Soft Inconel / 87 Plate Type
39 Retainer Material 316SS+CVD-5B 88 Controller Model
40 Bearings Nitronic 60 89 Pwr. Sup.
41 Packing Matl / Style / Vac / Fire PTFE/Glass Filled (V-Ring) / Standard 90 Wiring Conn. Type
42 Gland Flange Matl / Bolting Stainless Steel / Stainless Steel 91 NDE/Paint Test
43 Bonnet Port Type 92 Paint Test
44 End Plug Stainless Steel 93 Drawings
45 End Seal PTFE 94 Hydrostatic Testing ANSI/ISA 75.19.01
46 Yoke Bolting Stainless Steel 95 Seat Leak/Class ANSI/FCI-70-2 / Class IV
47 96 Documentation Final Inspection
48 97 Cert of Conf. PO or Spec
49 98 Cleaning
50 99 CMTR
51 100 Painting System
101 Body Yoke
102 Actuator Handwheel

** Insulation Type : 'None' Thickness : 0.0

Line#: Remarks :
1
2
3
4
5
Quantity: 1 Sheet 2 of 3
Flow Chart
Customer : Automatizacion Tag nos. : PCV-0625 Prepared by :
Project : T220425-499 Quantity : 1 nos. Page No.:2 Alternate : Michelle Gonzalez
End User : ODL Quote No. : T220425-499 Date/Rev No. : 26/Apr/2022/ Trimteck, LLC
End User Location : P.O No. : Date/Rev No. : Coral Springs, FL
Distributor : Serial No. : Accu Valve Ver.: 9.11

Fluid Name/State : Crude Oil/Liquid


Min Nor Max Other
Temp deg F 80.000 130.000 160.000 ----
P1 psi g 63.000 150.000 150.000 ----
P2 psi g 7.000 15.000 15.000 ----
Liq Flow U.S.bbl/d 2,400.000 6,840.000 7,680.000 ----
Gas Flow ---- ---- ---- ---- ----
Visc cSt 113.500 347.000 3,971.000 ----
VP psi a 0.800 0.800 0.800 ----
Critical Press psi a 482.970 482.970 482.970 ----
Density lb/ft3 60.300 59.100 58.300 ----
MW ---- ---- ---- ---- ----
Comp. Factor ---- ---- ---- ---- ----
Cp/Cv ---- ---- ---- ---- ----
DP psi g 56.000 135.000 135.000 ----
DpC psi 46.810 99.740 99.740 ----
Vel ft/s 7.156 20.390 22.900 ----
Noise (dBA - AV) <70 <70 71.00 ----
Flow Cap (Cv) 10.500 21.300 36.000 ----
Stroke (Degree) 34.800 48.100 59.800 ----
Info ---- ---- Cav. Cav. ----

** Insulation Type : 'None' Thickness : 0.0

Flow Direction: Shaft Up


Trim Characteristic : Modified =%
* - DISASSEMBLY / MAINTENANCE CLEARANCE
A B C D E WT
INCH 4.9 8.58 6.1 11.73 5.51
mm 124 218 155 298 140

Note: Dimensions are certified correct as per associated specification sheet. End connections
and scaling may not be actual. For accessory information, see associated specification sheet.

MODEL ACTUATOR

OpVEE 125 SQ IN CERTIFIED DIMENSIONAL DRAWING


SIZE AIR TO BY CUSTOMER ITEM

2.00 CLOSE MICHELLE GONZALEZ Automatizacion


RATING / F/F STD FAIL DATE VALVE TAG SHEET

CL 150/ISA S75.04 OPEN 10-June-2020 PCV-0625


END CONNECTION SPRING THIRD ANGLE PROJECTION P.O. NUMBER REVISION

FLANGED RF (INTEGRAL) K8 0
SHAFT TRIM / CV PROJECT SERIAL NUMBER

SHAFT UP 2/107 T220425-499


Control Valve Specification Sheet
Customer : Automatizacion Tag nos. : PCV-0627 Prepared by :
Project : T220425-499 Quantity : 1 nos. Page No.:3 Alternate : Michelle Gonzalez
End User : ODL Quote No. : T220425-499 Date/Rev No. : 26/Apr/2022/ Trimteck, LLC
End User Location : P.O No. : Date/Rev No. : Coral Springs, FL
Distributor : Valve Serial Nos. : Accu Valve Ver.: 9.11

1 Pipe Size / Schedule (In/Out) 4.00 / 4.00 inch ; Sch 40 / Sch 40 50 Act. Type/Matl Rack and Pinion / Aluminium
2 Line 51 Actuator Model/Size OpRPA / 125
3 P&ID 52 Rotation 90°
4 Application Valvula de Recirculacion Bomba 53 Spring K8
BOP-073 54 Air to / Fail Position Close / Fail Open
5 Process Fluid Crude Oil 55 Volume Tank
6 Design Press./Temp. 258.00 psi g / 200.00 deg F 56 Tubing & Fittings 1/4" 316 SS Swagelok
7 Allow Noise/Add Attn 85 / 0 dBA 57 Handwheel
8 NACE Compliance Non - NACE 58 Shut off Pres/Act.Fun 258.00 psi g / Throttling
9 Min Nor Max Other 59 Avail. Air Supply 60 psi g
10 Liq Flow Rt U.S.bbl/d 2400.00 6840.00 7680.00 60 Act./Pos. O-Rings Buna-N
11 Inlet Press psi g 63.00 150.00 150.00 61 Make/Model ABB / TZIDC
12 Outlet Press psi g 7.000 15.00 15.00 62 Signal/Options 4 - 20 mA HART / SS Gauges
13 Temperature °F 80.00 130.00 160.00 63 Transducer 4 - 20 mA Feedback
14 Viscosity cSt 113.50 347.00 3971.00 64 Mounting Bracket
15 Vapour Press. psi a 0.80000 0.80000 0.80000 65 Tag #/Cert / Class 1, Div 2, Gr. C,D
16 Critical Press psi a 482.97 482.97 482.97
17 Density lb/ft3 60.30 59.10 58.30 66 Material Aluminium
18 Flow Coeff. (Cv) 10.5 21.3 36.0 67 Model
19 Est Stroke (Degree) 34.8 48.1 59.8 68 Indicate
20 Pressure Drop psi 56.00 135.00 135.00 69 Type
21 Choke Drop psi 46.81 99.74 99.74 70 Voltage/Elec Conduit
22 **Noise (dBA - AV) <70 <70 71.00 71 Tag #
23 Valve Vel ft/s 7.156 20.39 22.90 72 Model
24 Pipe Vel ft/s 1.765 5.031 5.648 73 Position On De-en
25 Valve Model / Body Type OpVEE/V-Notch Ball 74 Electrical
26 Size/Pressure Rating 2.00 inch / CL 150 75 Mounting
27 Trim # / Cv / Characteristic 2.00 / 107 / Modified =% 76 Body Material
28 Ball Pressure Class CL 150-300 77 Haz. Loc.
29 Shaft Orientation Shaft Up 78 Tag #
30 Body Matl ASTM A216 WCB 79 Air Fltr Reg/Set press TT-AFR / 60 psi g
31 Bonnet Matl Carbon Steel 80 Filter / Gauges Yes / Yes
32 End Conn / Face to Face Flanged RF (Integral) / ISA S75.04 81 Flow Booster
33 Flange Finish 125-250 Ra 82 Booster Config
34 Bonnet Type Standard 83 Quick Exhaust
35 Ball Material 316 SS Hard Chrome Plated 84 SupTube/Jctn Box
36 Shaft Material 17-4PH 85 Lockup None
37 Seat Configuration Metal 86 Plate ID
38 Seat Matl Metal / Soft Inconel / 87 Plate Type
39 Retainer Material 316SS+CVD-5B 88 Controller Model
40 Bearings Nitronic 60 89 Pwr. Sup.
41 Packing Matl / Style / Vac / Fire PTFE/Glass Filled (V-Ring) / Standard 90 Wiring Conn. Type
42 Gland Flange Matl / Bolting Stainless Steel / Stainless Steel 91 NDE/Paint Test
43 Bonnet Port Type 92 Paint Test
44 End Plug Stainless Steel 93 Drawings
45 End Seal PTFE 94 Hydrostatic Testing ANSI/ISA 75.19.01
46 Yoke Bolting Stainless Steel 95 Seat Leak/Class ANSI/FCI-70-2 / Class IV
47 96 Documentation Final Inspection
48 97 Cert of Conf. PO or Spec
49 98 Cleaning
50 99 CMTR
51 100 Painting System
101 Body Yoke
102 Actuator Handwheel

** Insulation Type : 'None' Thickness : 0.0

Line#: Remarks :
1
2
3
4
5
Quantity: 1 Sheet 3 of 3
Flow Chart
Customer : Automatizacion Tag nos. : PCV-0627 Prepared by :
Project : T220425-499 Quantity : 1 nos. Page No.:3 Alternate : Michelle Gonzalez
End User : ODL Quote No. : T220425-499 Date/Rev No. : 26/Apr/2022/ Trimteck, LLC
End User Location : P.O No. : Date/Rev No. : Coral Springs, FL
Distributor : Serial No. : Accu Valve Ver.: 9.11

Fluid Name/State : Crude Oil/Liquid


Min Nor Max Other
Temp deg F 80.000 130.000 160.000 ----
P1 psi g 63.000 150.000 150.000 ----
P2 psi g 7.000 15.000 15.000 ----
Liq Flow U.S.bbl/d 2,400.000 6,840.000 7,680.000 ----
Gas Flow ---- ---- ---- ---- ----
Visc cSt 113.500 347.000 3,971.000 ----
VP psi a 0.800 0.800 0.800 ----
Critical Press psi a 482.970 482.970 482.970 ----
Density lb/ft3 60.300 59.100 58.300 ----
MW ---- ---- ---- ---- ----
Comp. Factor ---- ---- ---- ---- ----
Cp/Cv ---- ---- ---- ---- ----
DP psi g 56.000 135.000 135.000 ----
DpC psi 46.810 99.740 99.740 ----
Vel ft/s 7.156 20.390 22.900 ----
Noise (dBA - AV) <70 <70 71.00 ----
Flow Cap (Cv) 10.500 21.300 36.000 ----
Stroke (Degree) 34.800 48.100 59.800 ----
Info ---- ---- Cav. Cav. ----

** Insulation Type : 'None' Thickness : 0.0

Flow Direction: Shaft Up


Trim Characteristic : Modified =%
* - DISASSEMBLY / MAINTENANCE CLEARANCE
A B C D E WT
INCH 4.9 8.58 6.1 11.73 5.51
mm 124 218 155 298 140

Note: Dimensions are certified correct as per associated specification sheet. End connections
and scaling may not be actual. For accessory information, see associated specification sheet.

MODEL ACTUATOR

OpVEE 125 SQ IN CERTIFIED DIMENSIONAL DRAWING


SIZE AIR TO BY CUSTOMER ITEM

2.00 CLOSE MICHELLE GONZALEZ Automatizacion


RATING / F/F STD FAIL DATE VALVE TAG SHEET

CL 150/ISA S75.04 OPEN 10-June-2020 PCV-0627


END CONNECTION SPRING THIRD ANGLE PROJECTION P.O. NUMBER REVISION

FLANGED RF (INTEGRAL) K8 0
SHAFT TRIM / CV PROJECT SERIAL NUMBER

SHAFT UP 2/107 T220425-499