DATA SHEET FOR MOTOR OPERATED VALVE

Unit Price- Rs. 1,38,000/-


DOC NO.:0822-40-96-03-31REV.: 0 Dt: 29.01.2009 SHEET NO.: 15 of 16
GENERAL

1 Tag Nos. HV-1212


2 Service FEED WATER ISOLATION VALVE (IBR)
3 Ambient Temperat 50oC
4 Qty 1 No
5 Fluid / State STEAM
6 DP Shut-off 75.00
SERVICE CONDITIONS

25% 50% 75% 100%


7 Operating Process Design Unit
MCR MCR MCR MCR
8 Temperature 105 105 105 105 200 ºC
9 Flow rate 5.4 10.8 16.1 21.5 21.5 T/hr
Kg/cm²
10 Inlet Pressure 41.3 42.89 45.52 52.89 75
(g)
Kg/cm²
11 Outlet Pressure 41.3 42.89 45.52 49.19 75
(g)
12 DENSITY 954.7
13 Valve Duty ON / OFF Type
14 Valve type GATE
15 ValveSizePort Size NB 80
16 Valve thrust CORRESPONDING TO DP SHUTOFF
17 Body Rating 600
18 Body Material and CS
19 Body Seat Type Integeral
20 Type of Bonnet Material
STD/Integral Same as body material
21 Bonnet Gasket Graphoil
VALVE

22 Disc material same as body material.


Leakage class at
23 Class IV
full closure
24 Valve Stroking TimLess than 25 Sec.
25 Valve travel range 100%
26 Pipe mateOD/Thick SA 106 Gr B 88.9 / 5.49
27 End Connection ( BW ASME B 16.25
28 End
Facetype
to Face BW to ASME B16.25
29 Dimension As per ISA Standard
30 mm
Direction of flow LATER
31 Gland Packing Mate GRAFOIL
32 Type Rising stem outside screw and yoke
TRIM

33 Disc seat material STELLITED


34 Body seat ring STELLITED
35 Seat Material STELLITED
36 Valve design ASME B16.34/API 600
CODES
CODES 37 Face to face dimenASME B16.10, ASME B16.25 & ISA Standard
38 Testing standards API 600 / API 598
39 Pressure / temperaASME B16.34