HISAC Swift - CRM Test Report Report

HEADER :
Trigger Option CRM Date 05-08-22
Brk Sr. No. ABB SACE EMAX2 Time 13:13:40
Customer JyW CIA Location JyW CIA
Operator XPRO-E

Results for CRM Operation :

CONTACT RESISTANCE
R (A) 020.8 Micro
Y(B) 018.9 Micro
B (C) 019.4 Micro

08/08/2022
This report is generated by CPLOT Graphical Analysis Software from SCOPE T&M Pvt. Ltd. Pune, India. Page 1 Of 1
HISAC Swift - Timing & Coil Current Test Report
HEADER :
Trigger Option C Date 05-08-22
Sampling Speed (kC) 10 kC Time 13:16:44
Current Range C (A) 10 A Record No. 38
PIR Disable Brk Sr. No. ABB SACE EMAX2
Auxiliary WET Location JyW CIA
Delay Close 0100 mS Operator XPRO-E SAC
Delay Open 0100 mS Customer JyW CIA
Delay Tco (mS) 0300 mS Air PR. 1.01
Delay Toc (mS) 0300 mS Gas PR. 1.10
Plot Length (mS) 0400 mS Oil PR. 15
Voltage 480 V

GRAPH :

08/08/2022
This report is generated by CPLOT Graphical Analysis Software from SCOPE T&M Pvt. Ltd. Pune, India. Page 1 Of 2
HISAC Swift - Timing & Coil Current Test Report
OPEN TIME (mS) CLOSE TIME (mS)
R(A) R(A) Y(B) Y(B) B(C) B(C) R(A) R(A) Y(B) Y(B) B(C) B(C)
Main PIR Main PIR Main PIR Main PIR Main PIR Main PIR
Time 1 48.3 48.4 48.3 48.1 48.2 48.1
Time 2 48.8 48.6 48.8 48.6 48.5 48.4
Time 3 48.9 49.1 48.7 48.9
Time 4 49.1
Time 5
Time 6
Time 7
Time 8
Time 9
AUXILIARY TIME : WET
OPEN TIME (mS) CLOSE TIME (mS)
A1 A2 A1 A2
Time 1
Time 2
Time 3
Time 4
Time 5
Time 6
Time 7
Time 8
Time 9
COIL CURRENT(A)
07.75 A
OPEN CLOSE
Pole Mismatch (mS) 0.1

08/08/2022
This report is generated by CPLOT Graphical Analysis Software from SCOPE T&M Pvt. Ltd. Pune, India. Page 2 Of 2
HISAC Swift - Timing & Coil Current Test Report
HEADER :
Trigger Option O Date 05-08-22
Sampling Speed (kC) 10 kC Time 13:15:06
Current Range C (A) 10 A Record No. 37
PIR Disable Brk Sr. No. ABB SACE EMAX2
Auxiliary WET Location JyW CIA
Delay Close 0100 mS Operator XPRO-E SAC
Delay Open 0100 mS Customer JyW CIA
Delay Tco (mS) 0300 mS Air PR. 1.01
Delay Toc (mS) 0300 mS Gas PR. 1.10
Plot Length (mS) 0400 mS Oil PR. 15
Voltage 480 V

GRAPH :

08/08/2022
This report is generated by CPLOT Graphical Analysis Software from SCOPE T&M Pvt. Ltd. Pune, India. Page 1 Of 2
HISAC Swift - Timing & Coil Current Test Report
OPEN TIME (mS) CLOSE TIME (mS)
R(A) R(A) Y(B) Y(B) B(C) B(C) R(A) R(A) Y(B) Y(B) B(C) B(C)
Main PIR Main PIR Main PIR Main PIR Main PIR Main PIR
Time 1 27.4 28.2 28.5 27.5
Time 2 27.6 27.7
Time 3 28 28.3
Time 4 28.4
Time 5
Time 6
Time 7
Time 8
Time 9
AUXILIARY TIME : WET
OPEN TIME (mS) CLOSE TIME (mS)
A1 A2 A1 A2
Time 1
Time 2
Time 3
Time 4
Time 5
Time 6
Time 7
Time 8
Time 9
COIL CURRENT(A)
07.97 A
OPEN CLOSE
Pole Mismatch (mS) 1.1

08/08/2022
This report is generated by CPLOT Graphical Analysis Software from SCOPE T&M Pvt. Ltd. Pune, India. Page 2 Of 2
PW Series Relay Testing System

REPORTE DE PRUEBAS

INTERRUPTOR ABB E4 Emax2

Test Object-Device Setting

Station/Bay Information:
Station Name: SALA ELECTRICA Bay Address: GLORIA
Station Address: SALA ELECTRICA Tester: XPRO-E S.A.C
Bay Name: GENERADOR CAT.3

Device Information:
Device Name: ABB Serial Number: CB91164368
Device Model: Emax 2 Setting List Number: 1
Device Address: 1 Additional Info: GENERADOR CAT.3
Manufacturer: ABB

Nominal Values:
Vnom: 57.735V Fnom: 60.000Hz
Inom: 5.000A Vdc: 110.000V Debounce Time: 0ms

Test Equipment Information:


Type: T10000 A Imax: 1000.000A
Serial Number: PE154190901 Test Start: 08-05-2022 11:50:38
CommunicationPort: ETHERNET.COM Test End: 08-05-2022 11:51:33
Vmax: 300.000V

Page 1
PW Series Relay Testing System

Test Result

1.df/dt Trip Value


Hold Time: 5.000s In Start: 980.00 A In stop: 1000.00 A
Fre. Stop: 60.000Hz Frequency: 60.000Hz

Current Current Settings Error Assess


980.000A 980.000A 960.000A 0.02 Passed

Test Result Assessing:

The test points are all successful!

Test By: LTQ Approve By: PPR