HISAC Ultima - Timing Report

HEADER : Test Date Time: 15-03-2021 12:22:28


Substation 220 KV GIS S/S Breaker ID BAY 205 Gas Pressure 0.72 MPa
AT 30 MLD
DESALINATION
PLANT
Bay 205 ESB T/F Breaker Type HEMO-305B Air Pressure ESB
Operator N Serial Number 10144073 6 Oil Pressure NIL
GOVINDARAS
U
Manufacturer HYOSUNG Voltage (kV) 220

SETTINGS :
Trigger Option Open Sampling Speed (kC) 10 Plot Length(ms) 3000
PIR Disabled Delay tco (ms) 0 Delay toc (ms) 0
Auxiliary Disabled

CLOSE TIMING(ms) :
Main 1 PIR 1 Main 2 PIR 2 Main 3 PIR 3 Main 4 PIR 4
R 738.8
751.8

OPEN TIMING(ms) :
Main 1 PIR 1 Main 2 PIR 2 Main 3 PIR 3 Main 4 PIR 4
R 736.9
751.0
752.1

Y 740.9

B 724.4

This report is generated by HISAC Ultima Software from SCOPE T&M Pvt. Ltd. Pune, India. 17/03/2021 Page 1 of 2
HISAC Ultima - Timing Report

RESULTS :
Main 1 PIR 1 Main 2 PIR 2 Main 3 PIR 3 Main 4 PIR 4
Close
Time (ms) R
Y
B
Max Bounce (ms) R
Y
B
Total Bounce (ms) R
Y
B
No.Of Bounces R
Y
B
Open
Time (ms) R 752.1

Y 740.9

B 724.4

Max Bounce (ms) R 1.9

Y
B
Total Bounce (ms) R 15.2

Y
B
No.Of Bounces R 2.0

Y
B

AUXILIARY TIMING(MS) :
A1 A2 A3 A4 A5 A6 A7 A8 A9 A10 A11 A12
C
L
O
S
E
O
P
E
N

This report is generated by HISAC Ultima Software from SCOPE T&M Pvt. Ltd. Pune, India. 17/03/2021 Page 2 of 2