You are on page 1of 2

HISAC Ultima - Timing Report

HEADER : Test Date Time: 03-09-2019 03:51:42


Substation GMR POWER Breaker ID BAY 407 Gas Pressure 7.0
PLANT
Bay BAY 407 Breaker Type GL 316 Air Pressure PD
Operator VOLTECH Serial Number 166989 Oil Pressure Nil
Manufacturer ALSTOM Voltage (kV) 420

SETTINGS :
Trigger Option Open Sampling Speed (kC) 1 Plot Length(ms) 2500
PIR Disabled Delay tco (ms) 0 Delay toc (ms) 0
Auxiliary Enabled

CLOSE TIMING(ms) :
Main 1 PIR 1 Main 2 PIR 2 Main 3 PIR 3 Main 4 PIR 4
R

OPEN TIMING(ms) :
Main 1 PIR 1 Main 2 PIR 2 Main 3 PIR 3 Main 4 PIR 4
R 1465 1465

Y 22 22

B 1465 1465

This report is generated by HISAC Ultima Software from SCOPE T&M Pvt. Ltd. Pune, India. 07/09/2019 Page 1 of 2
HISAC Ultima - Timing Report
RESULTS :
Main 1 PIR 1 Main 2 PIR 2 Main 3 PIR 3 Main 4 PIR 4
Close
Time (ms) R
Y
B
Max Bounce (ms) R
Y
B
Total Bounce (ms) R
Y
B
No.Of Bounces R
Y
B
Open
Time (ms) R 1465 1465

Y 22 22

B 1465 1465

Max Bounce (ms) R


Y
B
Total Bounce (ms) R
Y
B
No.Of Bounces R
Y
B

AUXILIARY TIMING(MS) :
A1 A2 A3 A4 A5 A6 A7 A8 A9 A10 A11 A12
C 1469
L
O
S
E
O 1460 15 1459
P 1470
E
N

This report is generated by HISAC Ultima Software from SCOPE T&M Pvt. Ltd. Pune, India. 07/09/2019 Page 2 of 2