Woodward MFR 3
Woodward MFR 3
37166F
MFR 3
Multi Function Relay
Mains & Generator
Protection & Control
· Complete controller
with generator and
APPLICATIONS DESCRIPTION (continued) mains protection,
synchronizer, and
Woodward's MFR 3 Multi function Relay incorporates Protection ANSI # load/var control in one
functions and features for multiple application with up to Mains single digital relay
14 generators, each with a maximum individual rating of · Over-/undervoltage (59/27)
16MW. Whether isolated or in parallel with the utility this · Over-/underfrequency (81O/U) · True RMS sensing
device was designed for generators and switchgear · Phase/vector shift (78)
· Synchronization for
equipment that require independent protection. · df/dt (ROCOF) (81RL)
The MFR 3 digitally measures true RMS values ensuring Generator one/two circuit breakers
measurement accuracy - maintaining integrity against · Over-/undervoltage (2 steps) (59/27) · Load/var sharing for
harmonics, transients or power surges. Mains voltage · Over-/underfrequency (2 steps) (81O/U)
monitoring may be configured as phase-phase or phase- up to 14 participants
· Overload (32)
neutral. Front panel push-buttons allow direct control of · Reverse/reduced power (32R/F) · Counters for kWh,
power circuit breakers, setpoint values, and configuration · Unbalanced load (46)
of the unit. A phase sequence detection prevents a
kvarh, engine starts,
· Loss of excitation (40Q)
breaker closure in case of mismatching phases. operating hours,
· Definite time-overcurrent (TOC) (50)
The MFR 3 is available for one (MFR 31) or two (MFR 32) · Inverse time-overc. (incl. volt. restr.) (51V) maintenance call
circuit breakers. Even if the MFR 31 front panel reflects · Calculated earth fault (64)
only one circuit breaker, it may operate two. · Freely configurable
For utility parallel applications the combined mains and Controller discrete and analog
generator breaker protection offer a very compact · Synchronizer for 1 or 2 breaker/s (gen/mains) alarm inputs
solution. In addition to protection the MFR 3 offers · Isolated operation
frequency, voltage, real power and re-active power · Mains parallel operation
· Freely configurable
control allowing load/var sharing · Softloading relay and analog
· Speed/frequency/real power outputs
DESCRIPTION · Voltage/power factor cosphi
· PC and front panel
· Mains import/export power
Features · Load/var sharing (up to 14 generators) configurable
· True RMS 8× voltage (gen/bus/mains) · Remote real power setpoint (0/4 to 20 mA)
· True RMS 4× current (gen/mains) · CAN bus based
· Battery voltage monitoring Package PSVX communication
· Phase sequence detection · Remote power factor setpoint (0/4 to 20 mA)
· kWh/kvarh/oper.hours/start/maintenance counter
· Microprocessor
· 5 analog measuring inputs
· Configurable trip/control set points (1 x 0/4 to 20 mA, 4 x Pt100) technology for accurate,
· Configurable delays for each alarm · Event recorder with real time clock repeatable and reliable
· 12 configurable discrete alarm inputs operation
· 7 configurable/programmable relays Option Q
· 2 conf. analog outputs (20 mA) · Discrete raise/lower for n/f/V/P/Q * · Programmable two step
· 2 conf. pulse outputs for kWh/kvarh · Analog raise/lower for n/f/V/P/Q * threshold set points
· Two-line LC display · PWM raise/lower for n/f/P * with individual time
· Synchroscope * n = speed; f = frequency; V = voltage; delays
· Push-buttons for direct control P = real power; Q = reactive power
· CAN bus communication · CE marked
· Language manager (English/German preloaded)
· UL/cUL Listed
· Multi level password protection
SPECIFICATIONS (for details refer to manual 37107)
DIMENSIONS APPLICATION
MFR 3
27
59
144,0 mm
32,0 mm 81O
12,0 mm
81U
47
Configuration plug 78
52 79
42,0 mm
81RL
90
8,0 mm 25
48 25
130 138
X1 X5 52 79 25
27
144,0 mm
93 99
59
50 81O
83 60
32 81U
54
32R
50
12 32F
01 24 38 40Q I/O
136,0 mm 111,0 mm
39 46 0/4..20mA
49 55 RS232
2002-11-21 | MFR 3 Dimensions r3ww-4702-ab.skf
G 90 CAN
74
WIRING DIAGRAM (example: MFR 32; for MFR 31 refer to manual 37107)
Q Package
[A1]
IA
SPS
0/4 to 20 mA
- Setpoint: power factor
CAN-H
GND
CAN bus interface
Guidance level
74 75 76 77 78 79 80 81 82 83 37 38 47 48
Termination Relay [R7]
up to 14 additional generators
(each via one MFR 3)
Relay [R5]
Relaismanager
Analog input 5 [T5] Relay [R3]
Pt100
- Alarm input
Relay [R2]
lower SPEED / POWER
Drive
(three-position controller)
raise
or Relay [R1]
Analog controller output
(three-position controller)
raise
or
5 6 7 33 34 35 36 60 61 62 63 64 65 66 67 68 69 70 71 72 73 18 19 43 44
Analog controller output
Centralized alarm
Generator voltage L3
Generator voltage L2
3 Ready for operation
3/(4)
Generator voltage L1
L3
X2/S2 (L) x2/s2 (l) s2 (l) Alarm input [D11] B NO/#1
NC
NC
Command: close GCB
Alarm input [D03] or 3 NO/#1
Switch breaker logic NC
Alarm input [D02] or
GCB
2 NO/#1
Operation mode selector locked NC
Command: open GCB
Alarm input [D01] or 1 NO/#1
Mains decoupling via MCB NC
3
Mains voltage L2 12/24 Vdc
Mains voltage L1 N
Subject to technical mocifications. 2005-10-10 | MFR 3 Packages Wiring Diagram r3ww-4105-ap.skf
FEATURE OVERVIEW
International
Woodward
PO Box 1519 MFR 31 MFR 32
Fort Collins CO, USA
PSVX+Q
PSVX+Q
80522-1519
1000 East Drake Road
Fort Collins CO 80525 ANSI
Ph: +1 (970) 498-3634
Fax: +1 (970) 498-3058 Control
email: Breaker control logic 1 2
SalesPGD_NAandCA@woodward.com Synchronization 25 ü ü
Isolated single-unit operation ü ü
Europe Mains parallel operation ü ü
Woodward GmbH
Handwerkstrasse 29
Softloading ü
70565 Stuttgart, Germany Accessories
Ph: +49 (0) 711 789 54-510 kWh counter ü ü
Fax: +49 (0) 711 789 54-101 kvarh counter ü ü
email:
SalesPGD_EMEA@woodward.com
Operation hrs./start/maintenance counter ü ü
Configuration via PC #1 ü ü
Distributors & Service Event recorder, real time clock 50 50
Woodward has an international Protection
network of distributors and
service facilities. For your Mains: over-/undervoltage 59/27 ü ü
nearest representative, call the Mains: over-/underfrequency 81O/U ü ü
Fort Collins plant or see the Mains: df/dt (ROCOF) 81RL ü ü
Worldwide Directory on our Mains: dj/dt (phase/vector jump) 78 ü ü
website. Gen.: Over-/undervoltage 59/27 ü ü
Gen.: Over-/underfrequency 81O/U ü ü
www.woodward.com Gen.: Overload 32 ü ü
Gen.: Reverse power 32R ü ü
Gen.: Reduced power 32F/37 ü ü
Gen.: Unbalanced load 46 ü ü
Gen.: Loss of excitation 40Q ü ü
Gen.: Definite time-overcurrent (TOC) 50 ü ü
For more information contact: