Professional Documents
Culture Documents
5, OCTOBER 2021
Abstract—Line impedances estimation is of great importance in to calculate the transmission line impedances. Such theoretical
power system studies. Different software are used in utilities to methods for parameter estimation are erroneous as they do not
calculate line impedances using the line conductor and structure consider change in weather condition, ambient temperature, skin
data. The calculated values cannot be reliable due to inaccurate
information or change in atmospheric condition. Also, since there effect, etc. Therefore, industries have paid a growing attention
is a lack of communication between different departments such as in measuring the line parameters to verify the accuracy of
system protection, line construction, etc., a line conductor/structure calculated line parameters. Zero-sequence estimation is more
may be changed while the affected departments are not notified. inaccurate using traditional methods, as it highly depends on
Most of the impedance estimation methods use phasor measure- ground path and mutual effects in double-circuit lines [2].
ment units (PMUs) in the protection relays which are connected
to protection class current transformers (CTs) that do not pro- Parallel transmission lines have extensively been used in
vide accurate currents compared to metering class CTs. These power systems due to their increased power transfer capabilities
methods not only require PMUs in the substations, but also fail and less requirement for new right of way and transmission tow-
to measure zero-sequence voltages and currents due to inadequate ers. Mutual impedances between the transmission lines affect the
zero-sequence components under normal operation. In parallel current and voltage signals measured by the digital protective
transmission lines, zero-sequence impedance estimation is even
more challenging. This paper introduces a method for estimating relays. The impedance matrix of a six-conductor double-circuit
the self and mutual zero-sequence impedances for mutually coupled transmission line is a 6 × 6 matrix including self and mutual
transmission lines using recorded fault data. Extensive simulation impedances. The lines are appropriately arranged or transposed
and protective relay test results in RSCAD/RTDS indicate that the in order to remove the mutual arrays from the impedance matrix.
proposed approach has high accuracy in estimating the self and Although transposition leads to smaller unbalance in the lines,
mutual zero-sequence impedances as well as the fault location in
parallel transmission lines. it cannot remove the mutual zero-sequence impedance. Unlike
positive- and negative- sequence currents, the mutual impedance
Index Terms—Line parameter estimtion, mutually coupled between parallel lines which are due to zero-sequence currents
lines, decaying dc offset, zero-sequence impedance, mutual zero-
sequence.
can be comparable to the self-impedance [3], [4]. Therefore, the
effects of mutual zero-sequence for estimation of zero-sequence
I. INTRODUCTION impedances of the transmission lines cannot be neglected.
Off/on-line methods can be used for measuring the line pa-
OWER system engineers require transmission line
P impedance parameters for various applications. In power
system analysis such as protective relays setting, short-circuit,
rameters. On-line methods are preferred because line outages are
avoided. Several line parameter estimation methods using PMUs
have been introduced in the literature [5]–[14]. In [5], a total least
power flow, state estimation analysis, etc., the series impedance square based algorithm and PMU data of parallel transmission
and shunt admittance of transmission lines are critical infor- lines are used for the line impedance estimation. A method based
mation. Line parameters estimation with high accuracy plays a on synchrophasor measurement for impedance estimation of
significant role in predicting power system response character- short single-circuit transmission lines is presented in [6]. In [7], a
istics and maintaining its stability, security, and resiliency [1]. method using linear estimation theory and PMU data is proposed
Traditionally, the conductor and structure type of a line are used for the impedance estimation in transmission lines. Non-linear
estimation theory and synchrophasor measurements are used
Manuscript received March 2, 2020; revised July 28, 2020; accepted Septem- in [8]–[10] to calculate transmission line impedances. In [11], a
ber 20, 2020. Date of publication September 24, 2020; date of current version method using PMU and SCADA data is proposed for estimating
September 23, 2021. Paper no. TPWRD-00327-2020. (Corresponding author:
Mehdi Etezadi-Amoli.)
the impedances in two and three terminal transmission lines.
The authors are with the Electrical and Biomedical Engineering De- In [12]–[14], synchronized measurement and Kalman filter are
partment, University of Nevada, Reno, NV 89557-0260 USA (e-mail: used for state and line parameter estimation. The PMU-based
oveisa@nevada.unr.edu; mmajidi@unr.edu; etezadi@unr.edu).
Color versions of one or more figures in this article are available at https:
methods in [5]–[14] may not be accurate as the PMU is a part of
//doi.org/10.1109/TPWRD.2020.3026672. microprocessor relays which are connected to protection class
Digital Object Identifier 10.1109/TPWRD.2020.3026672 current transformers (CTs) which are less accurate than metering
0885-8977 © 2020 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission.
See https://www.ieee.org/publications/rights/index.html for more information.
Authorized licensed use limited to: College of Engineering - THIRUVANANTHAPURAM. Downloaded on September 21,2022 at 09:22:32 UTC from IEEE Xplore. Restrictions apply.
GASHTEROODKHANI et al.: FAULT DATA BASED METHOD FOR ZERO-SEQUENCE IMPEDANCE ESTIMATION 2769
Authorized licensed use limited to: College of Engineering - THIRUVANANTHAPURAM. Downloaded on September 21,2022 at 09:22:32 UTC from IEEE Xplore. Restrictions apply.
2770 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 36, NO. 5, OCTOBER 2021
Fig. 2. Typical phase currents and voltages at one terminal of the parallel line.
A. TT-Transform
B. Abrupt Change Detection
Short-Time Fourier Transform (STFT) is written as (1)
∞ TT-matrix is obtained by applying TT-transform to the aerial
ST F T (τ, f ) = h (t)w (τ − t) e−2πif t dt (1) mode of the current signals at both line terminals. Diagonal
−∞ elements of TT-matrix consist of high-frequency components of
the signals which provide valuable information to determine the
In (1), h(t) and w(t) represent the signal and the window
fault inception instant which is used to distinguish the pre-fault
function, respectively. Frequency and time are the parameters
from during-fault intervals [22], [25]. The waveforms at two line
that determine the position of the window function, w(t). If w(t)
ends are aligned with respect to the identified fault inception
is obtained from (2), S-transform will be derived from (1), and
instant to complete the synchronization. Figure 3 shows an
is expressed as (3). In STFT, the height and the width of the
example of abrupt change detection using TT-transform for a
window function are constant values. However, in S-transform,
fault at sample 347.
these parameters depend on the frequency [25].
2 2
|f | −f t III. ESTIMATION OF ZERO-SEQUENCE IMPEDANCES
w(t) = √ exp (2)
2π 2
∞ 2
Figure 4 shows a flowchart of the proposed zero-sequence
|f | −f (τ −t)2
impedance estimation in parallel transmission lines. First, fault
S (τ, f ) = h (t) √ e 2
e−2πif t dt (3)
−∞ 2π data synchronization is executed using TT-transform based
abrupt change detection. Then, DC offset of the fault data is
If we take the inverse Fourier transform of (3), the TT- removed to minimize the negative impact of the during-fault
transform is obtained as (4). transients. Discrete Fourier transform (DFT) is then used to
∞ extract the fundamental phasors. Finally, the fault location, self
T T (τ, t) = S(τ, f )e+2πif t df (4) and mutual zero-sequence impedances of the lines are estimated.
−∞
A simple algorithm for implementation is proposed based on
In (4), τ denote the position of the window function of the symmetrical component networks of single and double line-to-
S-transform and t represents the time [26]. ground faults on the mutually coupled lines.
Authorized licensed use limited to: College of Engineering - THIRUVANANTHAPURAM. Downloaded on September 21,2022 at 09:22:32 UTC from IEEE Xplore. Restrictions apply.
GASHTEROODKHANI et al.: FAULT DATA BASED METHOD FOR ZERO-SEQUENCE IMPEDANCE ESTIMATION 2771
A. DC Offset Removal
Fault currents comprise fundamental, harmonic and decaying
DC components. To extract the fundamental components, DFT
can be used. However, DFT cannot remove the DC offset. If the
fault currents include unfavorable transients, large errors will
be available in the line impedance estimation [27]. Thus, before
applying DFT, the DC offset should be eliminated from the fault
current waveforms. Several methods have been suggested in the Fig. 5. Zero-sequence mutual coupling visualization in parallel lines.
literature for the DC removal. The effective method that uses
one cycle of the fault to calculate and eliminate the DC offset
from fault data is used in this paper [28]. This method is briefly
described here.
Fault current which includes fundamental, harmonic and de-
caying dc components can be expressed as:
p
−t
i(t) = I0 e τ + Im sin(kω1 t + θm ) (5)
m=1
Authorized licensed use limited to: College of Engineering - THIRUVANANTHAPURAM. Downloaded on September 21,2022 at 09:22:32 UTC from IEEE Xplore. Restrictions apply.
2772 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 36, NO. 5, OCTOBER 2021
TABLE II
FAULT LOCATION ESTIMATION
TABLE III
SELF ZERO-SEQUENCE IMPEDANCE ESTIMATION
Fig. 7. Symetrical components network for a double line-to-ground fault in Note: Based on Table I, the reference values are R0 l = 0.3618 and X0 l = 1.2278.
double circuit lines.
where
In our method, the average of m obtained from (11) and (12) + + − −
If = Ilr1 + Irl1 + Ilr1 + Irl1
is used to identify the fault location. Using KVL in Fig. 6, we
have Note that in (16), Z0 l and Rf are unknown. From zero-sequence
loop similar to (17), we have
(1 − m)Zl+ Irl1
+
+ 3Rf If − Vr0 + (1 − m)Zl0 Irl1
0
where Z0 l , Z0 m and Rf are unknown. By solving equations (13), A large number of ground faults are simulated with different
(14) and (15) for Z0 l , Z0 m and Rf , line zero-sequence, mutual fault conditions to evaluate the performance of the proposed
zero-sequence and fault resistance are obtained. method. Table II shows the fault location estimation accuracy
Fault location, self and mutual zero-sequence impedances of for single and double line-to-ground faults in one of the two
the lines can also be calculated using the symmetrical component parallel lines. The results indicate that the method has very good
network shown in Fig. 7 for a double phase-to-ground fault. accuracy in fault location which is obtained first in the proposed
Using negative- and positive-sequence loops in Fig. 7, similar zero-sequence impedances estimation.
results to (11) and (12) are obtained for locating the fault. Using Tables III and IV show the estimation accuracy of the method
KVL in Fig. 7, we have for self and mutual zero-sequence impedances of the lines,
respectively. Several types of faults with different fault location
(1 − m)Zl− Irl1
−
+ Rf If − (1 − m)Zl0 Irl1
0 and with fault resistance of Rf = 0.01 Ω are simulated. The
results confirm that the estimation method is not influenced by
+ Vr0 − Vr− = 0 (16) system conditions.
Authorized licensed use limited to: College of Engineering - THIRUVANANTHAPURAM. Downloaded on September 21,2022 at 09:22:32 UTC from IEEE Xplore. Restrictions apply.
GASHTEROODKHANI et al.: FAULT DATA BASED METHOD FOR ZERO-SEQUENCE IMPEDANCE ESTIMATION 2773
Note: Based on Table I, the reference values are R0 m = 0.1206 and X0 m = 0.4092.
TABLE V
COMPARISON OF DIFFERENT METHODS
TABLE IX
EFFECTS OF MEASUREMENT ERRORS ON FAULT LOCATION AND SELF
ZERO-SEQUENCE ESTIMATION
Note: References [15] and [17] do not consider mutually coupled lines.
TABLE VI
EFFECTS OF FAULT RESISTANCE ON FAULT LOCATION AND SELF
ZERO-SEQUENCE ESTIMATION
Authorized licensed use limited to: College of Engineering - THIRUVANANTHAPURAM. Downloaded on September 21,2022 at 09:22:32 UTC from IEEE Xplore. Restrictions apply.
2774 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 36, NO. 5, OCTOBER 2021
TABLE X
FAULT LOCATION, SELF AND MUTUAL IMPEDANCE ESTIMATION USING THE
ACTUAL RELAY OUTPUT
Note: The reference values are m = 0.8, R0 l = 0.3618 and X0 l = 1.2278, R0 m = 0.1206,
X0 m = 0.4092, and Rf = 0.01.
V. DISCUSION
In this paper, the effects of shunt capacitance on the equations Fig. 9. Event report from the relay at bus L (a) unfiltered, (b) filtered.
derived from the symmetrical components network have not
been considered. To evaluate these effects on the zero-sequence TABLE XI
SELF AND MUTUAL IMPEDANCE ESTIMATION FOR AG FAULT AT A 120 KV
impedance estimation, a test system with lower voltage level of SYSTEM WITH 15 KM LINE LENGTH
120 kV and shorter line length, 15 km is considered here. Ta-
ble XI shows the results of self and mutual impedance estimation
for AG fault at different fault location in the test system with
lower shunt capacitance. As shown, the estimation error will
decrease when the shunt capacitance is lower. Similar results
are achieved using an actual relay as shown in Table XII.
Authorized licensed use limited to: College of Engineering - THIRUVANANTHAPURAM. Downloaded on September 21,2022 at 09:22:32 UTC from IEEE Xplore. Restrictions apply.
GASHTEROODKHANI et al.: FAULT DATA BASED METHOD FOR ZERO-SEQUENCE IMPEDANCE ESTIMATION 2775
REFERENCES
[1] N. Bhusal, M. Abdelmalak, M. Kamruzzaman, and M. Benidris, “Power
system resilience: Current practices, challenges, and future directions,” in
IEEE Access, vol. 8, pp. 18064–18086, 2020.
[2] F. Kiessling, P. Nefzger, J. F. Nolasco, and U. Kaintzyk. Overhead Power
Lines: Planning, Design, Construction. Berlin, Germany: Springer, 2014.
[3] F. Calero, “Mutual impedance in parallel lines–protective relaying and
fault location considerations,” in Proc. 34th Annu. Western Protective
Relay Conf., 2007, pp. 1–15.
[4] J. L. Blackburn, Symmetrical Components for Power Systems Engineering.
New York, NY, USA: Marcel Dekker, pp. 295–321, 1976.
[5] L. Ding, B. Tianshu, and D. N. Zhang, “Transmission line parameters
identification based on moving-window TLS and PMU data,” Int. Conf.
Adv. Power Syst. Automat. Protection, vol. 3, 2011.
[6] D. Shi et al., “Identification of short transmission-line parameters from
synchrophasor measurements,” in Proc. 40th North Amer. Power Symp.,
Calgary, Canada, pp. 1–8, Sep. 2008.
[7] D. Shi et al., “Transmission line parameter identification using PMU
measurements,” Eur. Trans. Elect. Power, vol. 21, no. 4, pp. 1574–1588,
2011.
[8] Y. Du and Y. Liao, “On-line estimation of transmission line parameters,
temperature and sag using PMU measurements,” Elect. Power Syst. Res.,
vol. 93, pp. 39–45, 2012.
[9] Y. Liao and M. Kezunovic, “Optimal estimate of transmission line fault lo-
cation considering measurement errors,” IEEE Trans. Power Del., vol. 22,
no. 3, pp. 1335–1441, Jul. 2007.
[10] Y. Liao and M. Kezunovic, “Online optimal transmission line parameter
estimation for relay applications,” IEEE Trans. Power Del., vol. 24, no. 1,
pp. 486–493, Jan. 2009.
Fig. 10. Symmetrical components of the filtered voltage and currents of the [11] S. S. Mousavi-Seyedi, F. Aminifar, and S. Afsharnia, “Parameter es-
relay at bus L. timation of multi-terminal transmission line using joint PMU and
SCADA data,” IEEE Trans. Power Del., vol. 30, no. 3, pp. 1077–1085,
TABLE XII Jun. 2015.
SELF AND MUTUAL IMPEDANCE ESTIMATION USING THE RELAY OUTPUT FOR [12] X. Bian, X. Li, H. Chen, D. Gan, and J. Qiu, “Joint estimation of state and
A 120 KV SYSTEM WITH 15 KM LINE LENGTH parameter with synchrophasors part I: State tracking,” IEEE Trans. Power
Syst., vol. 26, no. 3, pp. 1196–1208, Aug. 2011.
[13] X. Bian, X. Li, H. Chen, D. Gan, and J. Qiu, “Joint estimation of state and
parameter with synchrophasors part II: Parameter tracking,” IEEE Trans.
Power Syst., vol. 26, no. 3, pp. 1209–1220, Aug. 2011.
[14] R. Pengxiang, H. Lev-Ari, and A. Abur, “Tracking three-phase untrans-
posed transmission line parameters using synchronized measurements,”
IEEE Trans. Power Syst., vol. 33, no.4, pp. 4155–4163, Jul. 2018.
[15] Y. Liao and N. Kang, “Fault location algorithms without utilizing line
parameter based on the distributed parameter line model,” IEEE Trans.
Power Del., vol. 24, no. 2, pp. 579–584, Apr. 2009.
For the future work, we aim to incorporate the effects of [16] C. A. Apostolopoulos and G. N. Korres, “A novel method for locating
the shunt capacitance in the estimation equations derived from faults on transposed/untransposed transmission lines without utilizing line
the symmetrical components network to further increase the parameters,” IEEE Trans. Power Del., vol. 25, no. 4, pp. 2328–2338,
Oct. 2010.
accuracy of the zero-sequence impedance estimation for lines [17] W. Yang and W. Xu, “Algorithms and field experiences for estimating
with higher voltage level and longer length. transmission line parameters based on fault record data,” IET Gener. Trans.
Distrib., vol. 9, no. 13, pp. 1773–1781, 2015.
[18] T. Takagi, Y. Yamakoshi, M. Yamaura, R. Kondow, and T. Matsushima,
VI. CONCLUSION “Development of a new type fault locator using the one-terminal volt-
age and current data,” IEEE Trans. Power App. Syst., vol. 101, no. 8,
This paper uses fault record data to estimate zero-sequence pp. 2892–2898, Aug. 1982.
impedances of parallel transmission lines where the mutual [19] S. Jiale and G. Yaozhong, “A new accurate fault locating method of the
zero-sequence impedance is not zero even if the line conductors fault between two lines on the double circuit line on the same tower,” Proc.
CSEE, vol. 12, no. 3, pp. 1–9, 1992 (in Chinese).
are completely transposed. For zero-sequence parameter estima- [20] A. Ukil and R. Zivanovic, “Application of abrupt change detection in
tion, the mutual effect must be considered. Single and double power systems disturbance analysis and relay performance monitoring,”
line-to-ground fault symmetrical component networks are used IEEE Trans. Power Del., vol. 22, no. 1, pp. 59–66, Jan. 2007.
[21] O. A. Gashteroodkhani, M. Majidi, M. Etezadi-Amoli, A. F. Nematallahi,
to provide an effective method for zero-sequence impedance es- and B. Vahidi, “A hybrid SVM-TT transform based method for fault
timation. The method is simple to implement and works well for location in transmission lines combined with underground cable,” Elect.
different fault locations, resistances and tower configurations. Power Syst. Res., vol. 170, pp. 205–214, 2019.
[22] O. A. Gashteroodkhani, M. Majidi, M. S. Fadali, M. Etezadi-Amoli, and
Since to best of our knowledge, there are no line impedance E. M. Amiri, “A protection scheme for microgrids using time-time matrix
estimation methods for mutually coupled lines using fault record Z-score vector,” Int. J. Elect. Power Energy Syst., vol. 110, pp. 400–410,
data in the literature, we compared our method to those that 2019.
[23] O. A. Gashteroodkhani, B. Vahidi, and A. Zaboli, “Time-time matrix
only consider single transmission lines. The simulation and z-score vector based fault analysis method for series compensated trans-
test results confirm the great ability of the proposed method mission lines,” Turkish J. Elect. Eng. Comput. Sci., vol. 25, pp. 2647–2659,
in zero-sequence impedance estimation for parallel lines. 2017.
Authorized licensed use limited to: College of Engineering - THIRUVANANTHAPURAM. Downloaded on September 21,2022 at 09:22:32 UTC from IEEE Xplore. Restrictions apply.
2776 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 36, NO. 5, OCTOBER 2021
[24] O. A. Gashteroodkhani, M. Majidi, and M. Etezadi-Amoli, “A combined Mehrdad Majidi (Member, IEEE) received the B.Sc. and M.Sc. degrees (with
deep belief network and time-time transform based intelligent protection Hons.) in electrical engineering from the Power and Water University of Technol-
Scheme for microgrids,” Elect. Power Syst. Res., vol. 182, 2020, Art. ogy, Tehran, Iran, in 2009 and 2011, respectively, and Ph.D. degree in electrical
no. 106239. engineering from the University of Nevada, Reno (UNR), NV, USA, in 2016.
[25] R. G. Stockwell, L. Mansinha, and R. P. Lowe, “Localization of the Since then, he has been a Part Time Faculty with Electrical & Biomedical
complex spectrum: The S transform,” IEEE Trans. Signal Process., vol. 44, Engineering Department, UNR. From May 2016 to July 2020, he was a Senior
no. 4, pp. 998–1001, Apr. 1996. Protection Engineer with System Protection Department, NV Energy, Reno,
[26] C. R. Pinnegar and L. Mansinha, “A method of time–time analysis: The NV. He is currently working as a Principal Engineer with System Protection,
TT-transform,” Digit. Signal Process., vol. 13, no. 4, pp. 588–603, 2003. Automation, and Control (SPACE) Department at San Diego Gas & Electric,
[27] G. Benmouyal, “Removal of dc-offset in current waveforms using digital San Diego, CA. His research interests include system protection, fault location,
mimic filtering,” IEEE Trans. Power Del., vol. 10, no. 2, pp. 621–630, state estimation, and applications of signal processing in power system. He is a
Apr. 1995. licensed Professional Engineer in states of Nevada and California.
[28] Y. S. Cho, C. K. Lee, G. Jang, and H. J. Lee, “An innovative decaying DC
component estimation algorithm for digital relaying,” IEEE Trans. Power
Del., vol. 24, no. 1, pp. 73–78, Jan. 2009.
Mehdi Etezadi-Amoli (Life Senior Member, IEEE) received the BSEE, MSEE,
[29] Schweitzer Engineering Laboratories (SEL), “Online”. Available: https:
and Ph.D. degrees from New Mexico State University, Las Cruces, NM, in
//selinc.com
1970, 1972, and 1974, respectively. From 1975 to 1979, he was an Assistant
Professor of electrical engineering, New Mexico State and the University of
New Mexico, Alberquerque, NM, USA. From 1979 to 1983, he was a Senior
Protection Engineer with Arizona Public Service Company, Phoenix, AZ, USA.
In 1983, he joined the Faculty of the Electrical Engineering Department,
the University of Nevada, Reno, NV, USA. During summers 1985–1998, He
was with NV Energy (formerly Sierra Pacific Power Company). His current
Oveis Asgari Gashteroodkhani (Student Member, IEEE) received the B.S.
and M.S. degrees in electrical engineering from the University of Guilan and interests include large-scale systems, power system distribution and protection,
distributed generation, and renewable energy. Prof. Etezadi-Amoli is currently
Amirkabir University of Technology (Tehran Polytechnic), in 2012, and 2015,
a Registered Professional Engineer in Nevada.
respectively. Also, he received the Ph.D. degree in electrical engineering from
the University of Nevada, Reno, in 2020. He is currently working as a Senior
Power Engineer with ETAP, Operation Technology, Inc. in California, USA. His
main research interests include power system protection, smart grids, microgrids,
machine learning and signal processing applications in power systems.
Authorized licensed use limited to: College of Engineering - THIRUVANANTHAPURAM. Downloaded on September 21,2022 at 09:22:32 UTC from IEEE Xplore. Restrictions apply.