You are on page 1of 9

2768 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 36, NO.

5, OCTOBER 2021

A Fault Data Based Method for Zero-Sequence


Impedance Estimation of Mutually Coupled
Transmission Lines
Oveis Asgari Gashteroodkhani , Student Member, IEEE, Mehrdad Majidi , Member, IEEE,
and Mehdi Etezadi-Amoli , Life Senior Member, IEEE

Abstract—Line impedances estimation is of great importance in to calculate the transmission line impedances. Such theoretical
power system studies. Different software are used in utilities to methods for parameter estimation are erroneous as they do not
calculate line impedances using the line conductor and structure consider change in weather condition, ambient temperature, skin
data. The calculated values cannot be reliable due to inaccurate
information or change in atmospheric condition. Also, since there effect, etc. Therefore, industries have paid a growing attention
is a lack of communication between different departments such as in measuring the line parameters to verify the accuracy of
system protection, line construction, etc., a line conductor/structure calculated line parameters. Zero-sequence estimation is more
may be changed while the affected departments are not notified. inaccurate using traditional methods, as it highly depends on
Most of the impedance estimation methods use phasor measure- ground path and mutual effects in double-circuit lines [2].
ment units (PMUs) in the protection relays which are connected
to protection class current transformers (CTs) that do not pro- Parallel transmission lines have extensively been used in
vide accurate currents compared to metering class CTs. These power systems due to their increased power transfer capabilities
methods not only require PMUs in the substations, but also fail and less requirement for new right of way and transmission tow-
to measure zero-sequence voltages and currents due to inadequate ers. Mutual impedances between the transmission lines affect the
zero-sequence components under normal operation. In parallel current and voltage signals measured by the digital protective
transmission lines, zero-sequence impedance estimation is even
more challenging. This paper introduces a method for estimating relays. The impedance matrix of a six-conductor double-circuit
the self and mutual zero-sequence impedances for mutually coupled transmission line is a 6 × 6 matrix including self and mutual
transmission lines using recorded fault data. Extensive simulation impedances. The lines are appropriately arranged or transposed
and protective relay test results in RSCAD/RTDS indicate that the in order to remove the mutual arrays from the impedance matrix.
proposed approach has high accuracy in estimating the self and Although transposition leads to smaller unbalance in the lines,
mutual zero-sequence impedances as well as the fault location in
parallel transmission lines. it cannot remove the mutual zero-sequence impedance. Unlike
positive- and negative- sequence currents, the mutual impedance
Index Terms—Line parameter estimtion, mutually coupled between parallel lines which are due to zero-sequence currents
lines, decaying dc offset, zero-sequence impedance, mutual zero-
sequence.
can be comparable to the self-impedance [3], [4]. Therefore, the
effects of mutual zero-sequence for estimation of zero-sequence
I. INTRODUCTION impedances of the transmission lines cannot be neglected.
Off/on-line methods can be used for measuring the line pa-
OWER system engineers require transmission line
P impedance parameters for various applications. In power
system analysis such as protective relays setting, short-circuit,
rameters. On-line methods are preferred because line outages are
avoided. Several line parameter estimation methods using PMUs
have been introduced in the literature [5]–[14]. In [5], a total least
power flow, state estimation analysis, etc., the series impedance square based algorithm and PMU data of parallel transmission
and shunt admittance of transmission lines are critical infor- lines are used for the line impedance estimation. A method based
mation. Line parameters estimation with high accuracy plays a on synchrophasor measurement for impedance estimation of
significant role in predicting power system response character- short single-circuit transmission lines is presented in [6]. In [7], a
istics and maintaining its stability, security, and resiliency [1]. method using linear estimation theory and PMU data is proposed
Traditionally, the conductor and structure type of a line are used for the impedance estimation in transmission lines. Non-linear
estimation theory and synchrophasor measurements are used
Manuscript received March 2, 2020; revised July 28, 2020; accepted Septem- in [8]–[10] to calculate transmission line impedances. In [11], a
ber 20, 2020. Date of publication September 24, 2020; date of current version method using PMU and SCADA data is proposed for estimating
September 23, 2021. Paper no. TPWRD-00327-2020. (Corresponding author:
Mehdi Etezadi-Amoli.)
the impedances in two and three terminal transmission lines.
The authors are with the Electrical and Biomedical Engineering De- In [12]–[14], synchronized measurement and Kalman filter are
partment, University of Nevada, Reno, NV 89557-0260 USA (e-mail: used for state and line parameter estimation. The PMU-based
oveisa@nevada.unr.edu; mmajidi@unr.edu; etezadi@unr.edu).
Color versions of one or more figures in this article are available at https:
methods in [5]–[14] may not be accurate as the PMU is a part of
//doi.org/10.1109/TPWRD.2020.3026672. microprocessor relays which are connected to protection class
Digital Object Identifier 10.1109/TPWRD.2020.3026672 current transformers (CTs) which are less accurate than metering
0885-8977 © 2020 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission.
See https://www.ieee.org/publications/rights/index.html for more information.

Authorized licensed use limited to: College of Engineering - THIRUVANANTHAPURAM. Downloaded on September 21,2022 at 09:22:32 UTC from IEEE Xplore. Restrictions apply.
GASHTEROODKHANI et al.: FAULT DATA BASED METHOD FOR ZERO-SEQUENCE IMPEDANCE ESTIMATION 2769

class CTs. Also, these methods fail to estimate the zero-sequence


parameters due to inadequate zero-sequence components under
the steady state operation. In [15]–[17], unsynchronized fault
currents and voltages are used for transmission line impedances
estimation. Reference [15] presents two methods, one using fault
data and the other using fault and pre-fault information for the
impedance estimation based on the distributed parameter line
model. In [16], a method based on unsynchronized pre-fault and Fig. 1. System under study.
fault measurements is introduced for the impedances estimation
in both transposed and untransposed single circuit transmission TABLE I
TRANSMISSION LINE DATA
lines. Another line impedance estimation method using un-
synchronized fault data and electromagnetic wave propagation
speed is proposed in [17] with more transient tolerance and
higher estimation accuracy compared with [15]. However, the
methods in [15]–[17] have been proposed for single transmission
lines. To the best of our knowledge, line impedance estimation
of mutually coupled transmission lines using fault data have
not been studied in the literature. Since many methods in the
literature estimate the positive-sequence impedances in single
lines with good accuracy, and the positive-sequence impedance
estimation in parallel lines is similar to that of single lines, this
presented algorithm to estimate zero-sequence impedances is
paper focusses on estimation of self and mutual zero-sequence
explained in Sections III. Simulation and test results are de-
impedances using fault record data in mutually coupled lines.
scribed in Section IV. Discussion and conclusions are provided
For this purpose, new algorithms are proposed using line-to-
in Sections V and VI, respectively.
ground and line-to-line-to-ground faults data of several sim-
ulated faults in double-circuit lines. Note that there are fault
location methods using line parameters in mutually coupled II. SYSTEM UNDER STUDY AND FAULT DATA
transmission lines in the literature [18], [19]. However, fault SYNCHRONIZATION
location is a by-product and not the main purpose of the proposed A transmission system shown in Fig. 1 is simulated in
method. Our main contributions are as follows: RSCAD/RTDS.
r To the best of our knowledge, this paper is the first study This system includes 6 conductor parallel transmission lines,
which proposes a novel method for estimation of self and lines 1 and 2, with mutual coupling between them. Lines 1, and
mutual zero-sequence impedances of double-circuit lines 2 have a length of 100 km. These lines are connected to 230 kV
using fault data. The majority of the existing line parameter voltage sources, Vsr and Vsl , through two single lines 3 and 4.
estimation methods is based on the PMU measurement The parallel transmission lines data is listed in Table I.
which are not able to correctly estimate the zero-sequence In this paper, single line-to-ground and double line-to-ground
parameters because of inadequate zero-sequence compo- faults are analyzed as they contain rich zero-sequence compo-
nents under the steady state operation. Note that the few nents. The proposed method uses the unsynchronized three-
existing fault-data based methods for zero-sequence esti- phase current and voltage signals measured during the fault
mation [15], [17], only consider single transmission lines. period at both L and R terminals. Figure 2 shows the fault
r The method uses unsynchronized fault currents and volt- data including pre-, during- and post-fault periods for a single
ages data which eliminates the need for PMU installa- line-to-ground fault. The pre- and post-fault waveforms recorded
tion. Abrupt change detection using TT-transform is used by digital relays normally include 3 to 5 cycles. The fault
for synchronization. TT-transform is more sensitive than duration can be a few cycles longer. The fault current and
Wavelet transform (WT) [20] for detecting the abrupt voltage waveforms from all four terminals of the parallel lines
change in the fault waveforms [21]. Also, TT-transform are measured. These waveforms are unsynchronized as they are
performs better than WT for measurement errors [22]–[24]. independently recorded. Fault data is used for estimating the
r The proposed method is able to estimate the self and zero-sequence impedances of the lines since it entails significant
mutual zero-sequence impedances, and fault location with zero-sequence components. To obtain good accuracy, decaying
high accuracy for mutually coupled transmission lines with DC offset needs to be removed from fault data. Also, the effects
different configurations. Both single phase-to-ground and of mutual zero-sequence impedance between the parallel lines
double phase-to-ground event reports in the protective must be considered.
relay’s history can be used by the protection engineers As the measured voltages and currents by digital relays are
to estimate zero-sequence impedances. This enhances the unsynchronized, a synchronization method is needed before
value and practical usefulness of the proposed method since estimating the line impedances. Abrupt change detection can be
a transmission line may have only one type of ground faults. used for waveform synchronization by segmenting the pre- and
The paper is organized as follows: The system under study during-fault intervals. In [20], Wavelet transform (WT) is used
and fault data synchronization are explained in Section II. The for the abrupt change detection. Our previous work [21] shows

Authorized licensed use limited to: College of Engineering - THIRUVANANTHAPURAM. Downloaded on September 21,2022 at 09:22:32 UTC from IEEE Xplore. Restrictions apply.
2770 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 36, NO. 5, OCTOBER 2021

Fig. 3. Abrupt change detection using TT-transform.

Fig. 2. Typical phase currents and voltages at one terminal of the parallel line.

that Time Time-transform (TT-transform) is more sensitive than


WT to detect the abrupt change in the fault waveforms. Also,
TT-transform outperforms WT under noisy condition [22]–[24].
Therefore, TT-transform is used for abrupt change detection in
this paper. A brief description of TT-transform and the way it is
used for abrupt change detection are provided here. Fig. 4. Flowchart of the proposed method.

A. TT-Transform
B. Abrupt Change Detection
Short-Time Fourier Transform (STFT) is written as (1)
 ∞ TT-matrix is obtained by applying TT-transform to the aerial
ST F T (τ, f ) = h (t)w (τ − t) e−2πif t dt (1) mode of the current signals at both line terminals. Diagonal
−∞ elements of TT-matrix consist of high-frequency components of
the signals which provide valuable information to determine the
In (1), h(t) and w(t) represent the signal and the window
fault inception instant which is used to distinguish the pre-fault
function, respectively. Frequency and time are the parameters
from during-fault intervals [22], [25]. The waveforms at two line
that determine the position of the window function, w(t). If w(t)
ends are aligned with respect to the identified fault inception
is obtained from (2), S-transform will be derived from (1), and
instant to complete the synchronization. Figure 3 shows an
is expressed as (3). In STFT, the height and the width of the
example of abrupt change detection using TT-transform for a
window function are constant values. However, in S-transform,
fault at sample 347.
these parameters depend on the frequency [25].
 2 2
|f | −f t III. ESTIMATION OF ZERO-SEQUENCE IMPEDANCES
w(t) = √ exp (2)
2π 2
 ∞  2 
Figure 4 shows a flowchart of the proposed zero-sequence
|f | −f (τ −t)2
impedance estimation in parallel transmission lines. First, fault
S (τ, f ) = h (t) √ e 2
e−2πif t dt (3)
−∞ 2π data synchronization is executed using TT-transform based
abrupt change detection. Then, DC offset of the fault data is
If we take the inverse Fourier transform of (3), the TT- removed to minimize the negative impact of the during-fault
transform is obtained as (4). transients. Discrete Fourier transform (DFT) is then used to
 ∞ extract the fundamental phasors. Finally, the fault location, self
T T (τ, t) = S(τ, f )e+2πif t df (4) and mutual zero-sequence impedances of the lines are estimated.
−∞
A simple algorithm for implementation is proposed based on
In (4), τ denote the position of the window function of the symmetrical component networks of single and double line-to-
S-transform and t represents the time [26]. ground faults on the mutually coupled lines.

Authorized licensed use limited to: College of Engineering - THIRUVANANTHAPURAM. Downloaded on September 21,2022 at 09:22:32 UTC from IEEE Xplore. Restrictions apply.
GASHTEROODKHANI et al.: FAULT DATA BASED METHOD FOR ZERO-SEQUENCE IMPEDANCE ESTIMATION 2771

A. DC Offset Removal
Fault currents comprise fundamental, harmonic and decaying
DC components. To extract the fundamental components, DFT
can be used. However, DFT cannot remove the DC offset. If the
fault currents include unfavorable transients, large errors will
be available in the line impedance estimation [27]. Thus, before
applying DFT, the DC offset should be eliminated from the fault
current waveforms. Several methods have been suggested in the Fig. 5. Zero-sequence mutual coupling visualization in parallel lines.
literature for the DC removal. The effective method that uses
one cycle of the fault to calculate and eliminate the DC offset
from fault data is used in this paper [28]. This method is briefly
described here.
Fault current which includes fundamental, harmonic and de-
caying dc components can be expressed as:
p

−t
i(t) = I0 e τ + Im sin(kω1 t + θm ) (5)
m=1

where I0 and τ denote the magnitude and time constant of dc


component. Also,θm and Im denote the phase angle and magni-
tude of the mth harmonic component of the fault current. If Z(t)
is the integral of (5) for one period, T, we will have
 t
t T
Z(t) = i(t)dt = − I0 τ.e− τ (1 − e τ ) (6)
t−T

Therefore, the integral of (5) after a small time step, Δt is


(t+Δt) T Δt
Z(t + Δt) = −I0 τ.e− τ (1 − e τ ) = Z(t).e− τ (7)
Using the first two terms of Taylor series expansion and (7),
Fig. 6. Symetrical components network for a single line-to-ground fault in
we have double circuit lines.
Δt 1 Z(t + Δt)
e− τ = 1 + (−Δt) = (8)
τ Z(t) C. Algorithms for Zero-Sequence Impedance Estimation
Therefore, τ can be computed as As mentioned earlier, mutual zero-sequence is present in
Δt the mutually coupled lines even if they are fully transposed.
τ=  (9) In addition, mutual positive- and negative-sequence values can
Z(t+Δt)
1− Z(t) be neglected as they are very small compared to the mutual
From (6), the DC component at time t can be obtained as zero-sequence components. Figure 6 illustrates the symmetrical
component network with zero-sequence mutual coupling for
t Z(t) a single line-to-ground fault. Note that in this figure, all the
I 0 e− τ = T (10)
−τ.(1 − e τ ) sequence currents and voltages at the ends of the lines are
obtained through the three-phase measurements. Also, the lines
Using this dc removal technique, the dc component is esti-
positive- and negative-sequence impedances are assumed to be
mated after one cycle and can be removed from the fault current
known.
in each sample.
Using the negative-sequence loop, fault location (m) can be
obtained as follows:
B. Mutual Zero-Sequence Impedance
In the double-circuit lines, the mutual zero-sequence Vr− − Vl− + mZl− (Ilr1

) − (1 − m)Zl− (Irl1

)=0
impedance, Z0 m is considerable regardless of the conductors’ −Vr− + Vl− + Zl− Irl1

arrangement. In some cases, zero-sequence mutual impedance m= − − − (11)
Zl (Ilr1 + Irl1 )
is comparable to the positive-sequence impedance. The zero-
sequence mutual impedance which depends on the structure and Similarly, m can be obtained using the positive-sequence loop
geometry of the lines can always be measured. Figure 5 shows as follows:
the zero-sequence mutual coupling visualization. As shown, if I0 Vr+ − Vl+ + mZl+ Ilr1
+
− (1 − m)Zl+ Irl1
+
=0
is the zero-sequence current flowing in one line of a parallel line,
an induced voltage which equals to Z0 m × I° can be considered −Vr+ + Vl+ + Zl+ Irl1
+
m= + + + (12)
in the other line for visualizing the zero-sequence mutual effect. Zl (Ilr1 + Irl1 )

Authorized licensed use limited to: College of Engineering - THIRUVANANTHAPURAM. Downloaded on September 21,2022 at 09:22:32 UTC from IEEE Xplore. Restrictions apply.
2772 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 36, NO. 5, OCTOBER 2021

TABLE II
FAULT LOCATION ESTIMATION

TABLE III
SELF ZERO-SEQUENCE IMPEDANCE ESTIMATION

Fig. 7. Symetrical components network for a double line-to-ground fault in Note: Based on Table I, the reference values are R0 l = 0.3618 and X0 l = 1.2278.
double circuit lines.

where
In our method, the average of m obtained from (11) and (12) + + − −
If = Ilr1 + Irl1 + Ilr1 + Irl1
is used to identify the fault location. Using KVL in Fig. 6, we
have Note that in (16), Z0 l and Rf are unknown. From zero-sequence
loop similar to (17), we have
(1 − m)Zl+ Irl1
+
+ 3Rf If − Vr0 + (1 − m)Zl0 Irl1
0

− Vr− + (1 − m)Zl− Irl1



− Vr+ = 0 (13) Vr0 − Vl0 + mZl0 Ilr1
0
+ mZm 0 0
Ilr2 − (1 − m)Zl0 Irl1
0
=0
(17)
+
where If = Ilr1 +
+ Irl1 In (17), Z0 l and Z0 m are unknown. Using another KVL in
0
Note that in (13), Z l and Rf are unknown. From zero-sequence Fig. 7, we have
loop, we have + 0 0
mZl + Ilr1 + Rf If − mZm Ilr2 − mZl0 Ilr1
0
+ Vl0
Vr0 − Vl0 + mZl0 Ilr1
0 0 0
+ mZm Ilr2 − (1 − m)Zl0 Irl1
0
=0 − Vl+ = 0 (18)
(14)
where Z0 l and Z0 m are unknown. Using another KVL in Fig. 6, In (18), Z0 l , Z0 m and Rf are unknown. By solving equations
we have (16), (17) and (18) for Z0 l , Z0 m and Rf , line zero-sequence,
+
mutual zero-sequence and fault resistance are obtained.
mZl + Ilr1 + 3Rf If − Vl0 + mZl0 Ilr1
0 0 0
+ mZm Ilr2
− Vl− + mZl− Ilr1

− Vl+ = 0 (15) IV. SIMULATION AND TEST RESULTS

where Z0 l , Z0 m and Rf are unknown. By solving equations (13), A large number of ground faults are simulated with different
(14) and (15) for Z0 l , Z0 m and Rf , line zero-sequence, mutual fault conditions to evaluate the performance of the proposed
zero-sequence and fault resistance are obtained. method. Table II shows the fault location estimation accuracy
Fault location, self and mutual zero-sequence impedances of for single and double line-to-ground faults in one of the two
the lines can also be calculated using the symmetrical component parallel lines. The results indicate that the method has very good
network shown in Fig. 7 for a double phase-to-ground fault. accuracy in fault location which is obtained first in the proposed
Using negative- and positive-sequence loops in Fig. 7, similar zero-sequence impedances estimation.
results to (11) and (12) are obtained for locating the fault. Using Tables III and IV show the estimation accuracy of the method
KVL in Fig. 7, we have for self and mutual zero-sequence impedances of the lines,
respectively. Several types of faults with different fault location
(1 − m)Zl− Irl1

+ Rf If − (1 − m)Zl0 Irl1
0 and with fault resistance of Rf = 0.01 Ω are simulated. The
results confirm that the estimation method is not influenced by
+ Vr0 − Vr− = 0 (16) system conditions.

Authorized licensed use limited to: College of Engineering - THIRUVANANTHAPURAM. Downloaded on September 21,2022 at 09:22:32 UTC from IEEE Xplore. Restrictions apply.
GASHTEROODKHANI et al.: FAULT DATA BASED METHOD FOR ZERO-SEQUENCE IMPEDANCE ESTIMATION 2773

TABLE IV TABLE VIII


MUTUAL ZERO-SEQUENCE IMPEDANCE ESTIMATION EFFECTS OF SYSTEM CONFIGURATION ON FAULT LOCATION AND SELF
ZERO-SEQUENCE ESTIMATION

Note: Based on Table I, the reference values are R0 m = 0.1206 and X0 m = 0.4092.

TABLE V
COMPARISON OF DIFFERENT METHODS

TABLE IX
EFFECTS OF MEASUREMENT ERRORS ON FAULT LOCATION AND SELF
ZERO-SEQUENCE ESTIMATION

Note: References [15] and [17] do not consider mutually coupled lines.

TABLE VI
EFFECTS OF FAULT RESISTANCE ON FAULT LOCATION AND SELF
ZERO-SEQUENCE ESTIMATION

= 0.01 Ω to 75 Ω. As shown, the method provides promising


results for all the cases.
Table VIII shows the performance of the proposed method for
AG fault with m = 0.2 and Rf = 0.01 Ω in systems with different
voltage levels, line lengths, and conductor arrangements. The
Note: Based on Table I, the reference values are R0 l = 0.3618 and X0 l = 1.2278.
results confirm that the method is immune to change in system
TABLE VII structures.
EFFECTS OF FAULT RESISTANCE ON MUTUAL ZERO-SEQUENCE ESTIMATION The effects of random and biased measurement errors on the
immunity of the proposed method for a 120kV transmission
system are given in Table IX. For considering random measure-
ment errors, the voltage and current signals at all four terminals
of the parallel lines have been contaminated with Gaussian noise
with signal to noise ratio, SNR = 30dB. For considering biased
measurement error, the voltage and current signals at only one
terminal is increased by 10%. As shown in Table IX, the method
is secure against measurement uncertainty. This can be due to
Note: Based on Table I, the reference values are R0 m = 0.1206 and X0 m
the fact that for synchronizing the signals, the proposed method
= 0.4092.
uses TT-transform which is robust against noisy measurements
[22]–[24].
Table V shows the maximum and average errors in zero- We also test the proposed method on an actual commercial
sequence parameters estimation for the proposed method in grade relay [29]. The relay is tested using real-time digital
parallel lines compared to results from [15], [17] which do not simulator (RTDS) facilities at our university laboratory. Figure 8
handle mutually coupled lines and only consider single lines. As shows the RTDS and the relay used in this study.
shown, the proposed method produces accurate results despite Several fault scenarios are simulated in the mutually coupled
the fact that parameter estimation in parallel lines is a chal- lines in RSCAD software and the current and voltage signals
lenging problem due to the effects of the mutual zero-sequence of each terminals of the parallel lines are sent to the relay. The
impedance. relay uses analog low-pass and one-cycle cosine filter to remove
The effects of fault resistance are also evaluated on the perfor- dc component and the harmonics greater than the fundamental.
mance of the line impedance estimation method. Tables VI and The relay’s filtered event report includes voltage and current
VII depict the fault location and self and mutual zero-sequence and symmetrical components with 32 samples per cycle. Fig-
estimation for several fault scenarios with fault resistances of Rf ure 9 shows unfiltered and filtered current and voltage signals

Authorized licensed use limited to: College of Engineering - THIRUVANANTHAPURAM. Downloaded on September 21,2022 at 09:22:32 UTC from IEEE Xplore. Restrictions apply.
2774 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 36, NO. 5, OCTOBER 2021

Fig. 8. The actual relay and RTDS facilities.

TABLE X
FAULT LOCATION, SELF AND MUTUAL IMPEDANCE ESTIMATION USING THE
ACTUAL RELAY OUTPUT

Note: The reference values are m = 0.8, R0 l = 0.3618 and X0 l = 1.2278, R0 m = 0.1206,
X0 m = 0.4092, and Rf = 0.01.

obtained from the relay at bus L of Fig. 1 for AG fault at 80% of


the Line 1 with Rf = 0.01 Ω. Note that the relay output currents
and voltages were exported to MATLAB from the available relay
software to enhance the quality of these waveforms.
Figure 10 shows the symmetrical components of the filtered
voltage and currents obtained from the relay at bus L of Fig. 1
for AG fault at 80% of the Line 1 with Rf = 0.01 Ω.
Voltage and current symmetrical components received from
the relay are used in equations (13)–(15) or (16)–(18) for
single phase-to-ground and double phase-to-ground faults, re-
spectively, to calculate fault location error, self and mutual
zero-sequence impedances, and fault resistance for each fault
scenarios as shown in Table X.

V. DISCUSION
In this paper, the effects of shunt capacitance on the equations Fig. 9. Event report from the relay at bus L (a) unfiltered, (b) filtered.
derived from the symmetrical components network have not
been considered. To evaluate these effects on the zero-sequence TABLE XI
SELF AND MUTUAL IMPEDANCE ESTIMATION FOR AG FAULT AT A 120 KV
impedance estimation, a test system with lower voltage level of SYSTEM WITH 15 KM LINE LENGTH
120 kV and shorter line length, 15 km is considered here. Ta-
ble XI shows the results of self and mutual impedance estimation
for AG fault at different fault location in the test system with
lower shunt capacitance. As shown, the estimation error will
decrease when the shunt capacitance is lower. Similar results
are achieved using an actual relay as shown in Table XII.

Authorized licensed use limited to: College of Engineering - THIRUVANANTHAPURAM. Downloaded on September 21,2022 at 09:22:32 UTC from IEEE Xplore. Restrictions apply.
GASHTEROODKHANI et al.: FAULT DATA BASED METHOD FOR ZERO-SEQUENCE IMPEDANCE ESTIMATION 2775

REFERENCES
[1] N. Bhusal, M. Abdelmalak, M. Kamruzzaman, and M. Benidris, “Power
system resilience: Current practices, challenges, and future directions,” in
IEEE Access, vol. 8, pp. 18064–18086, 2020.
[2] F. Kiessling, P. Nefzger, J. F. Nolasco, and U. Kaintzyk. Overhead Power
Lines: Planning, Design, Construction. Berlin, Germany: Springer, 2014.
[3] F. Calero, “Mutual impedance in parallel lines–protective relaying and
fault location considerations,” in Proc. 34th Annu. Western Protective
Relay Conf., 2007, pp. 1–15.
[4] J. L. Blackburn, Symmetrical Components for Power Systems Engineering.
New York, NY, USA: Marcel Dekker, pp. 295–321, 1976.
[5] L. Ding, B. Tianshu, and D. N. Zhang, “Transmission line parameters
identification based on moving-window TLS and PMU data,” Int. Conf.
Adv. Power Syst. Automat. Protection, vol. 3, 2011.
[6] D. Shi et al., “Identification of short transmission-line parameters from
synchrophasor measurements,” in Proc. 40th North Amer. Power Symp.,
Calgary, Canada, pp. 1–8, Sep. 2008.
[7] D. Shi et al., “Transmission line parameter identification using PMU
measurements,” Eur. Trans. Elect. Power, vol. 21, no. 4, pp. 1574–1588,
2011.
[8] Y. Du and Y. Liao, “On-line estimation of transmission line parameters,
temperature and sag using PMU measurements,” Elect. Power Syst. Res.,
vol. 93, pp. 39–45, 2012.
[9] Y. Liao and M. Kezunovic, “Optimal estimate of transmission line fault lo-
cation considering measurement errors,” IEEE Trans. Power Del., vol. 22,
no. 3, pp. 1335–1441, Jul. 2007.
[10] Y. Liao and M. Kezunovic, “Online optimal transmission line parameter
estimation for relay applications,” IEEE Trans. Power Del., vol. 24, no. 1,
pp. 486–493, Jan. 2009.
Fig. 10. Symmetrical components of the filtered voltage and currents of the [11] S. S. Mousavi-Seyedi, F. Aminifar, and S. Afsharnia, “Parameter es-
relay at bus L. timation of multi-terminal transmission line using joint PMU and
SCADA data,” IEEE Trans. Power Del., vol. 30, no. 3, pp. 1077–1085,
TABLE XII Jun. 2015.
SELF AND MUTUAL IMPEDANCE ESTIMATION USING THE RELAY OUTPUT FOR [12] X. Bian, X. Li, H. Chen, D. Gan, and J. Qiu, “Joint estimation of state and
A 120 KV SYSTEM WITH 15 KM LINE LENGTH parameter with synchrophasors part I: State tracking,” IEEE Trans. Power
Syst., vol. 26, no. 3, pp. 1196–1208, Aug. 2011.
[13] X. Bian, X. Li, H. Chen, D. Gan, and J. Qiu, “Joint estimation of state and
parameter with synchrophasors part II: Parameter tracking,” IEEE Trans.
Power Syst., vol. 26, no. 3, pp. 1209–1220, Aug. 2011.
[14] R. Pengxiang, H. Lev-Ari, and A. Abur, “Tracking three-phase untrans-
posed transmission line parameters using synchronized measurements,”
IEEE Trans. Power Syst., vol. 33, no.4, pp. 4155–4163, Jul. 2018.
[15] Y. Liao and N. Kang, “Fault location algorithms without utilizing line
parameter based on the distributed parameter line model,” IEEE Trans.
Power Del., vol. 24, no. 2, pp. 579–584, Apr. 2009.
For the future work, we aim to incorporate the effects of [16] C. A. Apostolopoulos and G. N. Korres, “A novel method for locating
the shunt capacitance in the estimation equations derived from faults on transposed/untransposed transmission lines without utilizing line
the symmetrical components network to further increase the parameters,” IEEE Trans. Power Del., vol. 25, no. 4, pp. 2328–2338,
Oct. 2010.
accuracy of the zero-sequence impedance estimation for lines [17] W. Yang and W. Xu, “Algorithms and field experiences for estimating
with higher voltage level and longer length. transmission line parameters based on fault record data,” IET Gener. Trans.
Distrib., vol. 9, no. 13, pp. 1773–1781, 2015.
[18] T. Takagi, Y. Yamakoshi, M. Yamaura, R. Kondow, and T. Matsushima,
VI. CONCLUSION “Development of a new type fault locator using the one-terminal volt-
age and current data,” IEEE Trans. Power App. Syst., vol. 101, no. 8,
This paper uses fault record data to estimate zero-sequence pp. 2892–2898, Aug. 1982.
impedances of parallel transmission lines where the mutual [19] S. Jiale and G. Yaozhong, “A new accurate fault locating method of the
zero-sequence impedance is not zero even if the line conductors fault between two lines on the double circuit line on the same tower,” Proc.
CSEE, vol. 12, no. 3, pp. 1–9, 1992 (in Chinese).
are completely transposed. For zero-sequence parameter estima- [20] A. Ukil and R. Zivanovic, “Application of abrupt change detection in
tion, the mutual effect must be considered. Single and double power systems disturbance analysis and relay performance monitoring,”
line-to-ground fault symmetrical component networks are used IEEE Trans. Power Del., vol. 22, no. 1, pp. 59–66, Jan. 2007.
[21] O. A. Gashteroodkhani, M. Majidi, M. Etezadi-Amoli, A. F. Nematallahi,
to provide an effective method for zero-sequence impedance es- and B. Vahidi, “A hybrid SVM-TT transform based method for fault
timation. The method is simple to implement and works well for location in transmission lines combined with underground cable,” Elect.
different fault locations, resistances and tower configurations. Power Syst. Res., vol. 170, pp. 205–214, 2019.
[22] O. A. Gashteroodkhani, M. Majidi, M. S. Fadali, M. Etezadi-Amoli, and
Since to best of our knowledge, there are no line impedance E. M. Amiri, “A protection scheme for microgrids using time-time matrix
estimation methods for mutually coupled lines using fault record Z-score vector,” Int. J. Elect. Power Energy Syst., vol. 110, pp. 400–410,
data in the literature, we compared our method to those that 2019.
[23] O. A. Gashteroodkhani, B. Vahidi, and A. Zaboli, “Time-time matrix
only consider single transmission lines. The simulation and z-score vector based fault analysis method for series compensated trans-
test results confirm the great ability of the proposed method mission lines,” Turkish J. Elect. Eng. Comput. Sci., vol. 25, pp. 2647–2659,
in zero-sequence impedance estimation for parallel lines. 2017.

Authorized licensed use limited to: College of Engineering - THIRUVANANTHAPURAM. Downloaded on September 21,2022 at 09:22:32 UTC from IEEE Xplore. Restrictions apply.
2776 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 36, NO. 5, OCTOBER 2021

[24] O. A. Gashteroodkhani, M. Majidi, and M. Etezadi-Amoli, “A combined Mehrdad Majidi (Member, IEEE) received the B.Sc. and M.Sc. degrees (with
deep belief network and time-time transform based intelligent protection Hons.) in electrical engineering from the Power and Water University of Technol-
Scheme for microgrids,” Elect. Power Syst. Res., vol. 182, 2020, Art. ogy, Tehran, Iran, in 2009 and 2011, respectively, and Ph.D. degree in electrical
no. 106239. engineering from the University of Nevada, Reno (UNR), NV, USA, in 2016.
[25] R. G. Stockwell, L. Mansinha, and R. P. Lowe, “Localization of the Since then, he has been a Part Time Faculty with Electrical & Biomedical
complex spectrum: The S transform,” IEEE Trans. Signal Process., vol. 44, Engineering Department, UNR. From May 2016 to July 2020, he was a Senior
no. 4, pp. 998–1001, Apr. 1996. Protection Engineer with System Protection Department, NV Energy, Reno,
[26] C. R. Pinnegar and L. Mansinha, “A method of time–time analysis: The NV. He is currently working as a Principal Engineer with System Protection,
TT-transform,” Digit. Signal Process., vol. 13, no. 4, pp. 588–603, 2003. Automation, and Control (SPACE) Department at San Diego Gas & Electric,
[27] G. Benmouyal, “Removal of dc-offset in current waveforms using digital San Diego, CA. His research interests include system protection, fault location,
mimic filtering,” IEEE Trans. Power Del., vol. 10, no. 2, pp. 621–630, state estimation, and applications of signal processing in power system. He is a
Apr. 1995. licensed Professional Engineer in states of Nevada and California.
[28] Y. S. Cho, C. K. Lee, G. Jang, and H. J. Lee, “An innovative decaying DC
component estimation algorithm for digital relaying,” IEEE Trans. Power
Del., vol. 24, no. 1, pp. 73–78, Jan. 2009.
Mehdi Etezadi-Amoli (Life Senior Member, IEEE) received the BSEE, MSEE,
[29] Schweitzer Engineering Laboratories (SEL), “Online”. Available: https:
and Ph.D. degrees from New Mexico State University, Las Cruces, NM, in
//selinc.com
1970, 1972, and 1974, respectively. From 1975 to 1979, he was an Assistant
Professor of electrical engineering, New Mexico State and the University of
New Mexico, Alberquerque, NM, USA. From 1979 to 1983, he was a Senior
Protection Engineer with Arizona Public Service Company, Phoenix, AZ, USA.
In 1983, he joined the Faculty of the Electrical Engineering Department,
the University of Nevada, Reno, NV, USA. During summers 1985–1998, He
was with NV Energy (formerly Sierra Pacific Power Company). His current
Oveis Asgari Gashteroodkhani (Student Member, IEEE) received the B.S.
and M.S. degrees in electrical engineering from the University of Guilan and interests include large-scale systems, power system distribution and protection,
distributed generation, and renewable energy. Prof. Etezadi-Amoli is currently
Amirkabir University of Technology (Tehran Polytechnic), in 2012, and 2015,
a Registered Professional Engineer in Nevada.
respectively. Also, he received the Ph.D. degree in electrical engineering from
the University of Nevada, Reno, in 2020. He is currently working as a Senior
Power Engineer with ETAP, Operation Technology, Inc. in California, USA. His
main research interests include power system protection, smart grids, microgrids,
machine learning and signal processing applications in power systems.

Authorized licensed use limited to: College of Engineering - THIRUVANANTHAPURAM. Downloaded on September 21,2022 at 09:22:32 UTC from IEEE Xplore. Restrictions apply.

You might also like