You are on page 1of 33

Item code: 14110090

i:::1.:i�lt..J.ii.i 10-TMSS-05, Rev.02


TRANSMISSION MATERIALS STANDARD SPECIFICATION \ '�"')
tY National Grid SA

6.0 DATA SCHEDULE


BARE, COPPER CLAD STEEL GROUNDING CONDUCTOR,
GROUND ROD AND GROUNDING CLAMPS/CONNECTORS

Enquiry No. Date:

Purchase Order No. Date:


or Contract No.

PTS No./Project Title with J.O. No. 20CN1041

REFERENCE
SECTION NO. DESCRIPTION 'A' 'B' 'C'

3.0 APPLICABLE CODES AND STANDARDS


IEC 60228
ASTM B910/B910M *

4.0 DESIGN AND CONSTRUCTION REQUIREMENTS

4.2.2 Copper Clad Steel Grounding Soft drawn annealed bare copper
Conductor conductor, round, non-compacted

AWG Size N/A

Nominal Cross-Section (mm2) 50

Overall Diameter (mm) 8.76

Minimum Tensile Strength (kN) * N/A

D.C. Resistance at 20 ° C (Q/km) * 0.387

'A'- NATIONAL GRID SAUDI ARABIA SPECIFIED DATA/PARAMETERS


'B'- BIDDER/SUPPLIER/VENDOR/CONTRACTOR PROPOSED DATA/PARAMETERS
'C'- REMARKS SUPPORTING THE PROPOSED DEVIATION IN COLUMN 'B'
(*)- DATA/PARAMETERS TO BE PROVIDED/PROPOSED BY THE BIDDER/SUPPLIER/
VENDOR/CONTRACTOR IN COLUMN 'B'

10TMSS05R02/SSA Date of Approval: October 30, 2017 PAGE 9 OF 11


BCC Product ID: 14110090 50 mm2 , Soft Annealed Copper Conductor, Round Non-Compacted
i:::1.:i�lt..J.ii.i 10-TMSS-05, Rev.02
TRANSMISSION MATERIALS STANDARD SPECIFICATION \ '�"')
tY National Grid SA

6.0 DATA SCHEDULE


BARE, COPPER-CLAD STEEL GROUNDING CONDUCTOR,
GROUND ROD AND GROUNDING CLAMPS/CONNECTORS

REFERENCE
SECTION NO. DESCRIPTION 'A' 'B' 'C'

4.2.3 Copper-Clad Steel Ground Rod

Nominal Diameter (mm) 16 N/A

Actual Diameter (mm) 14.3 N/A

Minimum Length (mm) 3,000 N/A

4.3 Conductivity of Annealed Copper­


40 99.9
Clad Steel Wire (% IACS)

4.4 Direction of Lay left hand Right Hand "Outer layer"

4.5 Minimum Copper Thickness for:

Copper-Clad Steel Wire (mm) N/A

Ground Rod (mm) 0.25 N/A

4.6 Length of Grounding Conductor

Total Required Length (m) * As per B.O.Q

1000
Maximum Length per Reel (m) 2,000

Tolerance in Length per Reel ±5% ±5%

Type of Reel wooden Wooden

10TMSS05R02/SSA Date of Approval: October 30, 2017 PAGE 10 OF 11


BCC Product ID: 14110090 50 mm2 , Soft Annealed Copper Conductor, Round Non-Compacted
i:::1.:i�lt..J.ii.i 10-TMSS-05, Rev.02
TRANSMISSION MATERIALS STANDARD SPECIFICATION \ '�"')
tY National Grid SA

6.0 DATA SCHEDULE


BARE, COPPER-CLAD STEEL GROUNDING CONDUCTOR,
GROUND ROD AND GROUNDING CLAMPS/CONNECTORS

A. ADDITIONAL TECHNICAL INFORMATION OR FEATURES TO BE FURNISHED BY


NATIONAL GRID SAUDI ARABIA: NIL

B. ADDITIONAL SUPPLEMENTARY DATA OR FEATURES PROPOSED BY


BIDDER/VENDOR/SUPPLIER/CONTRACTOR: NIL

C. OTHER PARTICULARS TO BE FILLED UP BY BIDDER/VENDOR/SUPPLIER/


CONTRACTOR: NIL

Actual Manufacturer Vendor/Supplier/


of Equipment/Material Contractor

Name of the Company Bahra Cables Co.


Location and address 5989 Jeddah 21432 Saudi Arabia

Name and Signature of Aya Mahmoud Mohamed


Authorized representative Cables Design engineer
and date

Official Seal/Stamp
of the Company & Date

10TMSS05R02/SSA Date of Approval: October 30, 2017 PAGE 11 OF 11


BCC Product ID: 14110090 50 mm 2
, Soft Annealed Copper Conductor, Round Non-Compacted
Item code: 14110120

i:::1.:i�lt..J.ii.i 10-TMSS-05, Rev.02


TRANSMISSION MATERIALS STANDARD SPECIFICATION \ '�"')
tY National Grid SA

6.0 DATA SCHEDULE


BARE, COPPER CLAD STEEL GROUNDING CONDUCTOR,
GROUND ROD AND GROUNDING CLAMPS/CONNECTORS

Enquiry No. Date:

Purchase Order No. Date:


or Contract No.

PTS No./Project Title with J.O. No.

REFERENCE
SECTION NO. DESCRIPTION 'A' 'B' 'C'

3.0 APPLICABLE CODES AND STANDARDS


IEC 60228
ASTM B910/B910M *

4.0 DESIGN AND CONSTRUCTION REQUIREMENTS

4.2.2 Copper Clad Steel Grounding Soft drawn annealed bare copper
Conductor conductor, round, non-compacted

AWG Size N/A

Nominal Cross-Section (mm2) 120

Overall Diameter (mm) 13.87

Minimum Tensile Strength (kN) * N/A

D.C. Resistance at 20 ° C (Q/km) * 0.153

'A'- NATIONAL GRID SAUDI ARABIA SPECIFIED DATA/PARAMETERS


'B'- BIDDER/SUPPLIER/VENDOR/CONTRACTOR PROPOSED DATA/PARAMETERS
'C'- REMARKS SUPPORTING THE PROPOSED DEVIATION IN COLUMN 'B'
(*)- DATA/PARAMETERS TO BE PROVIDED/PROPOSED BY THE BIDDER/SUPPLIER/
VENDOR/CONTRACTOR IN COLUMN 'B'

10TMSS05R02/SSA Date of Approval: October 30, 2017 PAGE 9 OF 11


BCC Product ID: 14110120 120 mm2 , Soft Annealed Copper Conductor, Round Non-Compacted
i:::1.:i�lt..J.ii.i 10-TMSS-05, Rev.02
TRANSMISSION MATERIALS STANDARD SPECIFICATION \ '�"')
tY National Grid SA

6.0 DATA SCHEDULE


BARE, COPPER-CLAD STEEL GROUNDING CONDUCTOR,
GROUND ROD AND GROUNDING CLAMPS/CONNECTORS

REFERENCE
SECTION NO. DESCRIPTION 'A' 'B' 'C'

4.2.3 Copper-Clad Steel Ground Rod

Nominal Diameter (mm) 16 N/A

Actual Diameter (mm) 14.3 N/A

Minimum Length (mm) 3,000 N/A

4.3 Conductivity of Annealed Copper­


40 99.9
Clad Steel Wire (% IACS)

4.4 Direction of Lay left hand Right Hand "Outer layer"

4.5 Minimum Copper Thickness for:

Copper-Clad Steel Wire (mm) N/A

Ground Rod (mm) 0.25 N/A

4.6 Length of Grounding Conductor

Total Required Length (m) * As per B.O.Q

1000
Maximum Length per Reel (m) 2,000

Tolerance in Length per Reel ±5% ±5%

Type of Reel wooden Wooden

10TMSS05R02/SSA Date of Approval: October 30, 2017 PAGE 10 OF 11


BCC Product ID: 14110120 120 mm2 , Soft Annealed Copper Conductor, Round Non-Compacted
i:::1.:i�lt..J.ii.i 10-TMSS-05, Rev.02
TRANSMISSION MATERIALS STANDARD SPECIFICATION \ '�"')
tY National Grid SA

6.0 DATA SCHEDULE


BARE, COPPER-CLAD STEEL GROUNDING CONDUCTOR,
GROUND ROD AND GROUNDING CLAMPS/CONNECTORS

A. ADDITIONAL TECHNICAL INFORMATION OR FEATURES TO BE FURNISHED BY


NATIONAL GRID SAUDI ARABIA: NIL

B. ADDITIONAL SUPPLEMENTARY DATA OR FEATURES PROPOSED BY


BIDDER/VENDOR/SUPPLIER/CONTRACTOR: NIL

C. OTHER PARTICULARS TO BE FILLED UP BY BIDDER/VENDOR/SUPPLIER/


CONTRACTOR: NIL

Actual Manufacturer Vendor/Supplier/


of Equipment/Material Contractor

Name of the Company Bahra Cables Co.


Location and address 5989 Jeddah 21432 Saudi Arabia

Name and Signature of Aya Mahmoud Mohamed


Authorized representative Cables Design engineer
and date

Official Seal/Stamp
of the Company & Date

10TMSS05R02/SSA Date of Approval: October 30, 2017 PAGE 11 OF 11


BCC Product ID: 14110120 120 mm 2
, Soft Annealed Copper Conductor, Round Non-Compacted
Item Code: 14110130
TRANSMISSION MATERIALS STANDARD SPECIFICATION 10-TMSS-05, Rev.02

6.0 DATA SCHEDULE


BARE, COPPER-CLAD STEEL GROUNDING CONDUCTOR,
GROUND ROD AND GROUNDING CLAMPS/CONNECTORS

Enquiry No. Date:

Purchase Order No. Date:


or Contract No.

PTS No./Project Title with J.O. No.

REFERENCE
SECTION NO. DESCRIPTION 'A' 'B' 'C'

3.0 APPLICABLE CODES AND STANDARDS


IEC 60228
ASTM B910/B910M *

4.0 DESIGN AND CONSTRUCTION REQUIREMENTS

4.2.2 Copper-Clad Steel Grounding Soft drawn annealed bare copper


Conductor conductor, round, non-compacted

AWG Size N/A

Nominal Cross-Section (mm²) 150

Overall Diameter (mm) 15.22 "Approx."

Minimum Tensile Strength (kN) * N/A

D.C. Resistance at 20°C (Ω/km) * 0.124

'A'- NATIONAL GRID SAUDI ARABIA SPECIFIED DATA/PARAMETERS


'B'- BIDDER/SUPPLIER/VENDOR/CONTRACTOR PROPOSED DATA/PARAMETERS
'C'- REMARKS SUPPORTING THE PROPOSED DEVIATION IN COLUMN 'B'
(*)- DATA/PARAMETERS TO BE PROVIDED/PROPOSED BY THE BIDDER/SUPPLIER/
VENDOR/CONTRACTOR IN COLUMN 'B'

10TMSS05R02/SSA Date of Approval: October 30, 2017 PAGE 9 OF 11


TRANSMISSION MATERIALS STANDARD SPECIFICATION 10-TMSS-05, Rev.02

6.0 DATA SCHEDULE


BARE, COPPER-CLAD STEEL GROUNDING CONDUCTOR,
GROUND ROD AND GROUNDING CLAMPS/CONNECTORS

REFERENCE
SECTION NO. DESCRIPTION 'A' 'B' 'C'

4.2.3 Copper-Clad Steel Ground Rod

Nominal Diameter (mm) 16 N/A

Actual Diameter (mm) 14.3 N/A

Minimum Length (mm) 3,000 N/A

4.3 Conductivity of Annealed Copper-


40 99.99
Clad Steel Wire (% IACS)

4.4 Direction of Lay left hand Outer Layer - Right Hand

4.5 Minimum Copper Thickness for:

Copper-Clad Steel Wire (mm) * N/A

Ground Rod (mm) 0.25 N/A

4.6 Length of Grounding Conductor

Total Required Length (m) * As per B.O.Q

Maximum Length per Reel (m) 2,000 1000

Tolerance in Length per Reel ±5% ±5%

Type of Reel wooden Wooden

10TMSS05R02/SSA Date of Approval: October 30, 2017 PAGE 10 OF 11


TRANSMISSION MATERIALS STANDARD SPECIFICATION 10-TMSS-05, Rev.02

6.0 DATA SCHEDULE


BARE, COPPER-CLAD STEEL GROUNDING CONDUCTOR,
GROUND ROD AND GROUNDING CLAMPS/CONNECTORS

A. ADDITIONAL TECHNICAL INFORMATION OR FEATURES TO BE FURNISHED BY


NATIONAL GRID SAUDI ARABIA: NIL

B. ADDITIONAL SUPPLEMENTARY DATA OR FEATURES PROPOSED BY


BIDDER/VENDOR/SUPPLIER/CONTRACTOR: NIL

C. OTHER PARTICULARS TO BE FILLED UP BY BIDDER/VENDOR/SUPPLIER/


CONTRACTOR: NIL

Actual Manufacturer Vendor/Supplier/


of Equipment/Material Contractor

Name of the Company Bahra Advanced Cable


Location and address Manufacture Co.
Jeddah 21432, Saudi Arabia

Name and Signature of Aya Mahmoud Mohamed


Authorized representative Cables Design Engineer
and date

Official Seal/Stamp
of the Company & Date

10TMSS05R02/SSA Date of Approval: October 30, 2017 PAGE 11 OF 11


TRANSMISSION MATERIALS STANDARD SPECIFICATION 11-TMSS-10, Rev. 02

BCC Ref: TIR No.:


7.0 DATA SCHEDULE

POWER AND/OR CONTROL CABLE, COPPER OR ALUMINUM CONDUCTOR,


600/1000V RATING
450/750V RATING - FOR BUILDING WIRES
SEC Enquiry No. Date:

SEC Purchase Order Date:


No.
or Contract No.

SEC PTS No./Project Title with J.O. No.

REFERENCE
SECTION NO. DESCRIPTION 'A' 'B' 'C'

3.0 APPLICABLE CODES AND STANDARDS

Standards to which material shall conform * IEC 60228,IEC 60227-3

4.0 DESIGN AND CONSTRUCTION REQUIREMENTS

Cu / PVC 450 / 750 V H07V2-R 90 °C 120 mm2 RM G /


4.1 General Y

Cable application (Power or Control) BUILDING WIRE

Cable installation conduit, duct, trays


(conduit, duct, trays, direct burial, GIS etc.)

Voltage rating (kV) * 0.45/0.75

Available ground fault current (kA) N/A


(when shielded cable is required)

Fault current duration (sec.) * Maximum 5 sec.

Conductor DC resistance per km at 20°C


*
(Ω) 0.1530

'A'- SEC SPECIFIED DATA/PARAMETER.


'B'- BIDDER/SUPPLIER/VENDOR/CONTRACTOR PROPOSED DATA/PARAMETERS. 'C'-
REMARKS SUPPORTING THE PROPOSED DEVIATION IN COLUMN 'B'.
(*)- DATA/PARAMETER TO BE PROVIDED/PROPOSED BY THE BIDDER/SUPPLIER/
VENDOR/CONTRACTOR IN COLUMN 'B'.

11TMSS10R02/DBA Date of Approval: May 22, 2017 PAGE NO.10 OF 14


Product ID: 12164240 Cu / PVC 450 / 750 V H07V2-R 90 °C 120 mm2 RM G / Y Date: 11/09/2022
TRANSMISSION MATERIALS STANDARD SPECIFICATION 11-TMSS-10, Rev. 02

7.0 DATA SCHEDULE

POWER AND/OR CONTROL CABLE, COPPER OR ALUMINUM CONDUCTOR,


600/1000V RATING

REFERENCE
SECTION NO. DESCRIPTION 'A' 'B' 'C'

DESIGN AND CONSTRUCTION REQUIREMENTS (Continued)


4.0

Conductor AC resistance per km at 20°C


*
(Ω) 0.1561

Minimum Insulation resistance per km at 20°C


*
(MΩ) As per IEC 60227-3

Maximum permissible continuous


*
conductor temperature (°C) 90° C

Maximum rated temperature of


*
insulation material (°C) 90° C

Maximum permissible continuous


*
jacket temperature (°C) N/A

4.3.1 Conductor Material Cu / Al Cu

Conductor cross sectional area (mm²) * 120

For conductors 4mm² and larger:


Number of strands per conductor * 37

Diameter of compacted strand (mm) * 1.99 "Approx.-Before Stranding"

Number of conductors * 1

For conductors below 4mm²:


Stranding required ? Yes / No No

Number of strands per conductor * N/A

Diameter of compacted strand (mm) * N/A

Number of conductors * N/A

11TMSS10R02/DBA Date of Approval: May 22, 2017 PAGE NO.1 OF 14


Product ID: 12164240 Cu / PVC 450 / 750 V H07V2-R 90 °C 120 mm2 RM G / Y Date: 11/09/2022
TRANSMISSION MATERIALS STANDARD SPECIFICATION 11-TMSS-10, Rev. 02

7.0 DATA SCHEDULE

POWER AND/OR CONTROL CABLE, COPPER OR ALUMINUM CONDUCTOR,


600/1000V RATING
REFERENCE
SECTION NO. DESCRIPTION 'A' 'B' 'C'

DESIGN AND CONSTRUCTION REQUIREMENTS (Continued)


4.0

Outer diameter of conductor (mm) * 13.87 "Approximate"

Is conductor tinning required? Yes / No No

Insulation Material PVC /


4.3.2
XLPE PVC

Nominal thickness of insulation *


(mm) 1.60 "Nominal"

Outer diameter over insulation (mm) * 17.07 "Approximate"

Insulation shield material, if any * N/A

Thickness of insulation shield (mm) * N/A

4.3.3 Binder required ? Yes / No N/A

4.3.4 Metallic shield required ? Yes / No N/A

Thickness of metallic shield (mm) * N/A

4.3.5 Armor material, if any * N/A

4.3.6 Jacket Material * N/A

Nominal thickness (mm) * N/A

Overall diameter of cable (mm) * 17.1 "Approximate"

4.4.7 Reference standard for core


*
identification (IEC, ICEA) IEC - N/A

4.4.8 Color of single core cable/wire (if


*
applicable) GREEN YELLOW

11TMSS10R02/DBA Date of Approval: May 22, 2017 PAGE NO.1 OF 14


Product ID: 12164240 Cu / PVC 450 / 750 V H07V2-R 90 °C 120 mm2 RM G / Y Date: 11/09/2022
TRANSMISSION MATERIALS STANDARD SPECIFICATION 11-TMSS-10, Rev. 02

7.0 DATA SCHEDULE

POWER AND/OR CONTROL CABLE, COPPER OR ALUMINUM CONDUCTOR,


600/1000V RATING

REFERENCE
SECTION NO. DESCRIPTION 'A' 'B' 'C'

TESTS
5.0

5.3 List of special tests, if required N/A

6.0 PACKING AND SHIPPING

6.3 Cable weight (kg/km) * 1142 "Approximate"

Reel and cable weight (kg) * 1,192.5 "Approximate"

Cable length per Reel (m) * 1000

Total quantity required (m) * As per B.O.Q

Cable reel diameter (mm) * 1140 "Wooden drum"

Cable reel width (mm) * 810

Maximum pulling tension (kN) *

Minimum bending radius (mm) *

All weights and dimensions may slightly vary according to actual cables length, dimension and weights

11TMSS10R02/DBA Date of Approval: May 22, 2017 PAGE NO.1 OF 14


Product ID: 12164240 Cu / PVC 450 / 750 V H07V2-R 90 °C 120 mm2 RM G / Y Date: 11/09/2022
TRANSMISSION MATERIALS STANDARD SPECIFICATION 11-TMSS-10, Rev. 02

7.0 DATA SCHEDULE

POWER AND/OR CONTROL CABLE, COPPER OR ALUMINUM CONDUCTOR,


600/1000V RATING

A. ADDITIONAL TECHNICAL INFORMATION OR FEATURES TO BE FURNISHED BY


SEC:
Nil

B. ADDITIONAL SUPPLEMENTARY DATA OR FEATURES PROPOSED BY


BIDDER/VENDOR/SUPPLIER/CONTRACTOR:
Nil

C. OTHER PARTICULARS TO BE FILLED UP BY BIDDER/VENDOR/SUPPLIER/


CONTRACTOR:
Nil

Actual Manufacturer Vendor/Supplier/


of Equipment/Material Contractor

Name of the Company Bahra Advanced Cable


Manufacture Co.
Location and address Jeddah 21432, Saudi Arabia

Name and Signature of Eng. Aya Mahmoud El Sharqawy


(Ms)
authorized
representative
and date 11/09/2022

Official Seal/Stamp 11/09/2022


of the Company &
Date

11TMSS10R02/DBA Date of Approval: May 22, 2017 PAGE NO.1 OF 14


Product ID: 12164240 Cu / PVC 450 / 750 V H07V2-R 90 °C 120 mm2 RM G / Y Date: 11/09/2022
TRANSMISSION MATERIALS STANDARD SPECIFICATION 11-TMSS-10, Rev. 02

Drawing:

1 2

Description Cu / PVC 450 / 750 V H07V2-R 90 °C 120 mm2 RM G / Y

1 Copper conductor with round shape


2 PVC TI-3 Insulation

11TMSS10R02/DBA Date of Approval: May 22, 2017 PAGE NO.1 OF 14


Product ID: 12164240 Cu / PVC 450 / 750 V H07V2-R 90 °C 120 mm2 RM G / Y Date: 11/09/2022
TRANSMISSION MATERIALS STANDARD SPECIFICATION 11-TMSS-10, Rev. 02

BCC Ref: TIR No.:


7.0 DATA SCHEDULE

POWER AND/OR CONTROL CABLE, COPPER OR ALUMINUM CONDUCTOR,


600/1000V RATING
450/750V RATING - FOR BUILDING WIRES
SEC Enquiry No. Date:

SEC Purchase Order Date:


No.
or Contract No.

SEC PTS No./Project Title with J.O. No.

REFERENCE
SECTION NO. DESCRIPTION 'A' 'B' 'C'

3.0 APPLICABLE CODES AND STANDARDS

Standards to which material shall conform * IEC 60228,IEC 60227-3

4.0 DESIGN AND CONSTRUCTION REQUIREMENTS

Cu / PVC 450 / 750 V H07V2-R 90 °C 240 mm2 RM G /


4.1 General Y

Cable application (Power or Control) BUILDING WIRE

Cable installation conduit, duct, trays


(conduit, duct, trays, direct burial, GIS etc.)

Voltage rating (kV) * 0.45/0.75

Available ground fault current (kA) N/A


(when shielded cable is required)

Fault current duration (sec.) * Maximum 5 sec.

Conductor DC resistance per km at 20°C


*
(Ω) 0.0754

'A'- SEC SPECIFIED DATA/PARAMETER.


'B'- BIDDER/SUPPLIER/VENDOR/CONTRACTOR PROPOSED DATA/PARAMETERS. 'C'-
REMARKS SUPPORTING THE PROPOSED DEVIATION IN COLUMN 'B'.
(*)- DATA/PARAMETER TO BE PROVIDED/PROPOSED BY THE BIDDER/SUPPLIER/
VENDOR/CONTRACTOR IN COLUMN 'B'.

11TMSS10R02/DBA Date of Approval: May 22, 2017 PAGE NO.10 OF 14


Product ID: 12164270 Cu / PVC 450 / 750 V H07V2-R 90 °C 240 mm2 RM G / Y Date: 11/09/2022
TRANSMISSION MATERIALS STANDARD SPECIFICATION 11-TMSS-10, Rev. 02

7.0 DATA SCHEDULE

POWER AND/OR CONTROL CABLE, COPPER OR ALUMINUM CONDUCTOR,


600/1000V RATING

REFERENCE
SECTION NO. DESCRIPTION 'A' 'B' 'C'

DESIGN AND CONSTRUCTION REQUIREMENTS (Continued)


4.0

Conductor AC resistance per km at 20°C


*
(Ω) 0.0813

Minimum Insulation resistance per km at 20°C


*
(MΩ) As per IEC 60227-3

Maximum permissible continuous


*
conductor temperature (°C) 90° C

Maximum rated temperature of


*
insulation material (°C) 90° C

Maximum permissible continuous


*
jacket temperature (°C) N/A

4.3.1 Conductor Material Cu / Al Cu

Conductor cross sectional area (mm²) * 240

For conductors 4mm² and larger:


Number of strands per conductor * 61

Diameter of compacted strand (mm) * 2.20 "Approx.-Before Stranding"

Number of conductors * 1

For conductors below 4mm²:


Stranding required ? Yes / No No

Number of strands per conductor * N/A

Diameter of compacted strand (mm) * N/A

Number of conductors * N/A

11TMSS10R02/DBA Date of Approval: May 22, 2017 PAGE NO.1 OF 14


Product ID: 12164270 Cu / PVC 450 / 750 V H07V2-R 90 °C 240 mm2 RM G / Y Date: 11/09/2022
TRANSMISSION MATERIALS STANDARD SPECIFICATION 11-TMSS-10, Rev. 02

7.0 DATA SCHEDULE

POWER AND/OR CONTROL CABLE, COPPER OR ALUMINUM CONDUCTOR,


600/1000V RATING
REFERENCE
SECTION NO. DESCRIPTION 'A' 'B' 'C'

DESIGN AND CONSTRUCTION REQUIREMENTS (Continued)


4.0

Outer diameter of conductor (mm) * 19.65 "Approximate"

Is conductor tinning required? Yes / No No

Insulation Material PVC /


4.3.2
XLPE PVC

Nominal thickness of insulation *


(mm) 2.20 "Nominal"

Outer diameter over insulation (mm) * 24.05 "Approximate"

Insulation shield material, if any * N/A

Thickness of insulation shield (mm) * N/A

4.3.3 Binder required ? Yes / No N/A

4.3.4 Metallic shield required ? Yes / No N/A

Thickness of metallic shield (mm) * N/A

4.3.5 Armor material, if any * N/A

4.3.6 Jacket Material * N/A

Nominal thickness (mm) * N/A

Overall diameter of cable (mm) * 24.0 "Approximate"

4.4.7 Reference standard for core


*
identification (IEC, ICEA) IEC - N/A

4.4.8 Color of single core cable/wire (if


*
applicable) GREEN YELLOW

11TMSS10R02/DBA Date of Approval: May 22, 2017 PAGE NO.1 OF 14


Product ID: 12164270 Cu / PVC 450 / 750 V H07V2-R 90 °C 240 mm2 RM G / Y Date: 11/09/2022
TRANSMISSION MATERIALS STANDARD SPECIFICATION 11-TMSS-10, Rev. 02

7.0 DATA SCHEDULE

POWER AND/OR CONTROL CABLE, COPPER OR ALUMINUM CONDUCTOR,


600/1000V RATING

REFERENCE
SECTION NO. DESCRIPTION 'A' 'B' 'C'

TESTS
5.0

5.3 List of special tests, if required N/A

6.0 PACKING AND SHIPPING

6.3 Cable weight (kg/km) * 2319 "Approximate"

Reel and cable weight (kg) * 2,433.6 "Approximate"

Cable length per Reel (m) * 1000

Total quantity required (m) * As per B.O.Q

Cable reel diameter (mm) * 1440 "Wooden drum"

Cable reel width (mm) * 1010

Maximum pulling tension (kN) *

Minimum bending radius (mm) *

All weights and dimensions may slightly vary according to actual cables length, dimension and weights

11TMSS10R02/DBA Date of Approval: May 22, 2017 PAGE NO.1 OF 14


Product ID: 12164270 Cu / PVC 450 / 750 V H07V2-R 90 °C 240 mm2 RM G / Y Date: 11/09/2022
TRANSMISSION MATERIALS STANDARD SPECIFICATION 11-TMSS-10, Rev. 02

7.0 DATA SCHEDULE

POWER AND/OR CONTROL CABLE, COPPER OR ALUMINUM CONDUCTOR,


600/1000V RATING

A. ADDITIONAL TECHNICAL INFORMATION OR FEATURES TO BE FURNISHED BY


SEC:
Nil

B. ADDITIONAL SUPPLEMENTARY DATA OR FEATURES PROPOSED BY


BIDDER/VENDOR/SUPPLIER/CONTRACTOR:
Nil

C. OTHER PARTICULARS TO BE FILLED UP BY BIDDER/VENDOR/SUPPLIER/


CONTRACTOR:
Nil

Actual Manufacturer Vendor/Supplier/


of Equipment/Material Contractor

Name of the Company Bahra Advanced Cable


Manufacture Co.
Location and address Jeddah 21432, Saudi Arabia

Name and Signature of Eng. Aya Mahmoud El Sharqawy


(Ms)
authorized
representative
and date 11/09/2022

Official Seal/Stamp 11/09/2022


of the Company &
Date

11TMSS10R02/DBA Date of Approval: May 22, 2017 PAGE NO.1 OF 14


Product ID: 12164270 Cu / PVC 450 / 750 V H07V2-R 90 °C 240 mm2 RM G / Y Date: 11/09/2022
TRANSMISSION MATERIALS STANDARD SPECIFICATION 11-TMSS-10, Rev. 02

Drawing:

1 2

Description Cu / PVC 450 / 750 V H07V2-R 90 °C 240 mm2 RM G / Y

1 Copper conductor with round shape


2 PVC TI-3 Insulation

11TMSS10R02/DBA Date of Approval: May 22, 2017 PAGE NO.1 OF 14


Product ID: 12164270 Cu / PVC 450 / 750 V H07V2-R 90 °C 240 mm2 RM G / Y Date: 11/09/2022
TRANSMISSION MATERIALS STANDARD SPECIFICATION 11-TMSS-10, Rev. 02

BCC Ref: TIR No.:


7.0 DATA SCHEDULE

POWER AND/OR CONTROL CABLE, COPPER OR ALUMINUM CONDUCTOR,


600/1000V RATING
450/750V RATING - FOR BUILDING WIRES
SEC Enquiry No. Date:

SEC Purchase Order Date:


No.
or Contract No.

SEC PTS No./Project Title with J.O. No.

REFERENCE
SECTION NO. DESCRIPTION 'A' 'B' 'C'

3.0 APPLICABLE CODES AND STANDARDS

Standards to which material shall conform * IEC 60228,IEC 60227-3

4.0 DESIGN AND CONSTRUCTION REQUIREMENTS

Cu / PVC 450 / 750 V H07V2-R 90 °C 95 mm2 RM G /


4.1 General Y

Cable application (Power or Control) BUILDING WIRE

Cable installation conduit, duct, trays


(conduit, duct, trays, direct burial, GIS etc.)

Voltage rating (kV) * 0.45/0.75

Available ground fault current (kA) N/A


(when shielded cable is required)

Fault current duration (sec.) * Maximum 5 sec.

Conductor DC resistance per km at 20°C


*
(Ω) 0.1930

'A'- SEC SPECIFIED DATA/PARAMETER.


'B'- BIDDER/SUPPLIER/VENDOR/CONTRACTOR PROPOSED DATA/PARAMETERS. 'C'-
REMARKS SUPPORTING THE PROPOSED DEVIATION IN COLUMN 'B'.
(*)- DATA/PARAMETER TO BE PROVIDED/PROPOSED BY THE BIDDER/SUPPLIER/
VENDOR/CONTRACTOR IN COLUMN 'B'.

11TMSS10R02/DBA Date of Approval: May 22, 2017 PAGE NO.10 OF 14


Product ID: 12164230 Cu / PVC 450 / 750 V H07V2-R 90 °C 95 mm2 RM G / Y Date: 11/09/2022
TRANSMISSION MATERIALS STANDARD SPECIFICATION 11-TMSS-10, Rev. 02

7.0 DATA SCHEDULE

POWER AND/OR CONTROL CABLE, COPPER OR ALUMINUM CONDUCTOR,


600/1000V RATING

REFERENCE
SECTION NO. DESCRIPTION 'A' 'B' 'C'

DESIGN AND CONSTRUCTION REQUIREMENTS (Continued)


4.0

Conductor AC resistance per km at 20°C


*
(Ω) 0.1954

Minimum Insulation resistance per km at 20°C


*
(MΩ) As per IEC 60227-3

Maximum permissible continuous


*
conductor temperature (°C) 90° C

Maximum rated temperature of


*
insulation material (°C) 90° C

Maximum permissible continuous


*
jacket temperature (°C) N/A

4.3.1 Conductor Material Cu / Al Cu

Conductor cross sectional area (mm²) * 95

For conductors 4mm² and larger:


Number of strands per conductor * 19

Diameter of compacted strand (mm) * 2.47 "Approx.-Before Stranding"

Number of conductors * 1

For conductors below 4mm²:


Stranding required ? Yes / No No

Number of strands per conductor * N/A

Diameter of compacted strand (mm) * N/A

Number of conductors * N/A

11TMSS10R02/DBA Date of Approval: May 22, 2017 PAGE NO.1 OF 14


Product ID: 12164230 Cu / PVC 450 / 750 V H07V2-R 90 °C 95 mm2 RM G / Y Date: 11/09/2022
TRANSMISSION MATERIALS STANDARD SPECIFICATION 11-TMSS-10, Rev. 02

7.0 DATA SCHEDULE

POWER AND/OR CONTROL CABLE, COPPER OR ALUMINUM CONDUCTOR,


600/1000V RATING
REFERENCE
SECTION NO. DESCRIPTION 'A' 'B' 'C'

DESIGN AND CONSTRUCTION REQUIREMENTS (Continued)


4.0

Outer diameter of conductor (mm) * 12.32 "Approximate"

Is conductor tinning required? Yes / No No

Insulation Material PVC /


4.3.2
XLPE PVC

Nominal thickness of insulation *


(mm) 1.60 "Nominal"

Outer diameter over insulation (mm) * 15.52 "Approximate"

Insulation shield material, if any * N/A

Thickness of insulation shield (mm) * N/A

4.3.3 Binder required ? Yes / No N/A

4.3.4 Metallic shield required ? Yes / No N/A

Thickness of metallic shield (mm) * N/A

4.3.5 Armor material, if any * N/A

4.3.6 Jacket Material * N/A

Nominal thickness (mm) * N/A

Overall diameter of cable (mm) * 15.5 "Approximate"

4.4.7 Reference standard for core


*
identification (IEC, ICEA) IEC - N/A

4.4.8 Color of single core cable/wire (if


*
applicable) GREEN YELLOW

11TMSS10R02/DBA Date of Approval: May 22, 2017 PAGE NO.1 OF 14


Product ID: 12164230 Cu / PVC 450 / 750 V H07V2-R 90 °C 95 mm2 RM G / Y Date: 11/09/2022
TRANSMISSION MATERIALS STANDARD SPECIFICATION 11-TMSS-10, Rev. 02

7.0 DATA SCHEDULE

POWER AND/OR CONTROL CABLE, COPPER OR ALUMINUM CONDUCTOR,


600/1000V RATING

REFERENCE
SECTION NO. DESCRIPTION 'A' 'B' 'C'

TESTS
5.0

5.3 List of special tests, if required N/A

6.0 PACKING AND SHIPPING

6.3 Cable weight (kg/km) * 921 "Approximate"

Reel and cable weight (kg) * 965.9 "Approximate"

Cable length per Reel (m) * 1000

Total quantity required (m) * As per B.O.Q

Cable reel diameter (mm) * 1040 "Wooden drum"

Cable reel width (mm) * 760

Maximum pulling tension (kN) *

Minimum bending radius (mm) *

All weights and dimensions may slightly vary according to actual cables length, dimension and weights

11TMSS10R02/DBA Date of Approval: May 22, 2017 PAGE NO.1 OF 14


Product ID: 12164230 Cu / PVC 450 / 750 V H07V2-R 90 °C 95 mm2 RM G / Y Date: 11/09/2022
TRANSMISSION MATERIALS STANDARD SPECIFICATION 11-TMSS-10, Rev. 02

7.0 DATA SCHEDULE

POWER AND/OR CONTROL CABLE, COPPER OR ALUMINUM CONDUCTOR,


600/1000V RATING

A. ADDITIONAL TECHNICAL INFORMATION OR FEATURES TO BE FURNISHED BY


SEC:
Nil

B. ADDITIONAL SUPPLEMENTARY DATA OR FEATURES PROPOSED BY


BIDDER/VENDOR/SUPPLIER/CONTRACTOR:
Nil

C. OTHER PARTICULARS TO BE FILLED UP BY BIDDER/VENDOR/SUPPLIER/


CONTRACTOR:
Nil

Actual Manufacturer Vendor/Supplier/


of Equipment/Material Contractor

Name of the Company Bahra Advanced Cable


Manufacture Co.
Location and address Jeddah 21432, Saudi Arabia

Name and Signature of Eng. Aya Mahmoud El Sharqawy


(Ms)
authorized
representative
and date 11/09/2022

Official Seal/Stamp 11/09/2022


of the Company &
Date

11TMSS10R02/DBA Date of Approval: May 22, 2017 PAGE NO.1 OF 14


Product ID: 12164230 Cu / PVC 450 / 750 V H07V2-R 90 °C 95 mm2 RM G / Y Date: 11/09/2022
TRANSMISSION MATERIALS STANDARD SPECIFICATION 11-TMSS-10, Rev. 02

Drawing:

1 2

Description Cu / PVC 450 / 750 V H07V2-R 90 °C 95 mm2 RM G / Y

1 Copper conductor with round shape


2 PVC TI-3 Insulation

11TMSS10R02/DBA Date of Approval: May 22, 2017 PAGE NO.1 OF 14


Product ID: 12164230 Cu / PVC 450 / 750 V H07V2-R 90 °C 95 mm2 RM G / Y Date: 11/09/2022
TRANSMISSION MATERIALS STANDARD SPECIFICATION 11-TMSS-10, Rev. 02

BCC Ref: TIR No.:


7.0 DATA SCHEDULE

POWER AND/OR CONTROL CABLE, COPPER OR ALUMINUM CONDUCTOR,


600/1000V RATING
450/750V RATING - FOR BUILDING WIRES
SEC Enquiry No. Date:

SEC Purchase Order Date:


No.
or Contract No.

SEC PTS No./Project Title with J.O. No.

REFERENCE
SECTION NO. DESCRIPTION 'A' 'B' 'C'

3.0 APPLICABLE CODES AND STANDARDS

Standards to which material shall conform * IEC 60228,IEC 60227-3

4.0 DESIGN AND CONSTRUCTION REQUIREMENTS

Cu / PVC 450 / 750 V H07V2-R 90 °C 50 mm2 RM G /


4.1 General Y

Cable application (Power or Control) BUILDING WIRE

Cable installation conduit, duct, trays


(conduit, duct, trays, direct burial, GIS etc.)

Voltage rating (kV) * 0.45/0.75

Available ground fault current (kA) N/A


(when shielded cable is required)

Fault current duration (sec.) * Maximum 5 sec.

Conductor DC resistance per km at 20°C


*
(Ω) 0.3870

'A'- SEC SPECIFIED DATA/PARAMETER.


'B'- BIDDER/SUPPLIER/VENDOR/CONTRACTOR PROPOSED DATA/PARAMETERS. 'C'-
REMARKS SUPPORTING THE PROPOSED DEVIATION IN COLUMN 'B'.
(*)- DATA/PARAMETER TO BE PROVIDED/PROPOSED BY THE BIDDER/SUPPLIER/
VENDOR/CONTRACTOR IN COLUMN 'B'.

11TMSS10R02/DBA Date of Approval: May 22, 2017 PAGE NO.10 OF 14


Product ID: 12164210 Cu / PVC 450 / 750 V H07V2-R 90 °C 50 mm2 RM G / Y Date: 11/09/2022
TRANSMISSION MATERIALS STANDARD SPECIFICATION 11-TMSS-10, Rev. 02

7.0 DATA SCHEDULE

POWER AND/OR CONTROL CABLE, COPPER OR ALUMINUM CONDUCTOR,


600/1000V RATING

REFERENCE
SECTION NO. DESCRIPTION 'A' 'B' 'C'

DESIGN AND CONSTRUCTION REQUIREMENTS (Continued)


4.0

Conductor AC resistance per km at 20°C


*
(Ω) 0.3874

Minimum Insulation resistance per km at 20°C


*
(MΩ) As per IEC 60227-3

Maximum permissible continuous


*
conductor temperature (°C) 90° C

Maximum rated temperature of


*
insulation material (°C) 90° C

Maximum permissible continuous


*
jacket temperature (°C) N/A

4.3.1 Conductor Material Cu / Al Cu

Conductor cross sectional area (mm²) * 50

For conductors 4mm² and larger:


Number of strands per conductor * 19

Diameter of compacted strand (mm) * 1.75 "Approx.-Before Stranding"

Number of conductors * 1

For conductors below 4mm²:


Stranding required ? Yes / No No

Number of strands per conductor * N/A

Diameter of compacted strand (mm) * N/A

Number of conductors * N/A

11TMSS10R02/DBA Date of Approval: May 22, 2017 PAGE NO.1 OF 14


Product ID: 12164210 Cu / PVC 450 / 750 V H07V2-R 90 °C 50 mm2 RM G / Y Date: 11/09/2022
TRANSMISSION MATERIALS STANDARD SPECIFICATION 11-TMSS-10, Rev. 02

7.0 DATA SCHEDULE

POWER AND/OR CONTROL CABLE, COPPER OR ALUMINUM CONDUCTOR,


600/1000V RATING
REFERENCE
SECTION NO. DESCRIPTION 'A' 'B' 'C'

DESIGN AND CONSTRUCTION REQUIREMENTS (Continued)


4.0

Outer diameter of conductor (mm) * 8.76 "Approximate"

Is conductor tinning required? Yes / No No

Insulation Material PVC /


4.3.2
XLPE PVC

Nominal thickness of insulation *


(mm) 1.40 "Nominal"

Outer diameter over insulation (mm) * 11.56 "Approximate"

Insulation shield material, if any * N/A

Thickness of insulation shield (mm) * N/A

4.3.3 Binder required ? Yes / No N/A

4.3.4 Metallic shield required ? Yes / No N/A

Thickness of metallic shield (mm) * N/A

4.3.5 Armor material, if any * N/A

4.3.6 Jacket Material * N/A

Nominal thickness (mm) * N/A

Overall diameter of cable (mm) * 11.6 "Approximate"

4.4.7 Reference standard for core


*
identification (IEC, ICEA) IEC - N/A

4.4.8 Color of single core cable/wire (if


*
applicable) GREEN YELLOW

11TMSS10R02/DBA Date of Approval: May 22, 2017 PAGE NO.1 OF 14


Product ID: 12164210 Cu / PVC 450 / 750 V H07V2-R 90 °C 50 mm2 RM G / Y Date: 11/09/2022
TRANSMISSION MATERIALS STANDARD SPECIFICATION 11-TMSS-10, Rev. 02

7.0 DATA SCHEDULE

POWER AND/OR CONTROL CABLE, COPPER OR ALUMINUM CONDUCTOR,


600/1000V RATING

REFERENCE
SECTION NO. DESCRIPTION 'A' 'B' 'C'

TESTS
5.0

5.3 List of special tests, if required N/A

6.0 PACKING AND SHIPPING

6.3 Cable weight (kg/km) * 476 "Approximate"

Reel and cable weight (kg) * 510.9 "Approximate"

Cable length per Reel (m) * 1000

Total quantity required (m) * As per B.O.Q

Cable reel diameter (mm) * 940 "Wooden drum"

Cable reel width (mm) * 710

Maximum pulling tension (kN) *

Minimum bending radius (mm) *

All weights and dimensions may slightly vary according to actual cables length, dimension and weights

11TMSS10R02/DBA Date of Approval: May 22, 2017 PAGE NO.1 OF 14


Product ID: 12164210 Cu / PVC 450 / 750 V H07V2-R 90 °C 50 mm2 RM G / Y Date: 11/09/2022
TRANSMISSION MATERIALS STANDARD SPECIFICATION 11-TMSS-10, Rev. 02

7.0 DATA SCHEDULE

POWER AND/OR CONTROL CABLE, COPPER OR ALUMINUM CONDUCTOR,


600/1000V RATING

A. ADDITIONAL TECHNICAL INFORMATION OR FEATURES TO BE FURNISHED BY


SEC:
Nil

B. ADDITIONAL SUPPLEMENTARY DATA OR FEATURES PROPOSED BY


BIDDER/VENDOR/SUPPLIER/CONTRACTOR:
Nil

C. OTHER PARTICULARS TO BE FILLED UP BY BIDDER/VENDOR/SUPPLIER/


CONTRACTOR:
Nil

Actual Manufacturer Vendor/Supplier/


of Equipment/Material Contractor

Name of the Company Bahra Advanced Cable


Manufacture Co.
Location and address Jeddah 21432, Saudi Arabia

Name and Signature of Eng. Aya Mahmoud El Sharqawy


(Ms)
authorized
representative
and date 11/09/2022

Official Seal/Stamp 11/09/2022


of the Company &
Date

11TMSS10R02/DBA Date of Approval: May 22, 2017 PAGE NO.1 OF 14


Product ID: 12164210 Cu / PVC 450 / 750 V H07V2-R 90 °C 50 mm2 RM G / Y Date: 11/09/2022
TRANSMISSION MATERIALS STANDARD SPECIFICATION 11-TMSS-10, Rev. 02

Drawing:

1 2

Description Cu / PVC 450 / 750 V H07V2-R 90 °C 50 mm2 RM G / Y

1 Copper conductor with round shape


2 PVC TI-3 Insulation

11TMSS10R02/DBA Date of Approval: May 22, 2017 PAGE NO.1 OF 14


Product ID: 12164210 Cu / PVC 450 / 750 V H07V2-R 90 °C 50 mm2 RM G / Y Date: 11/09/2022