Franchise Area
The franchise area of the Company covers all cities and municipalities of Metro
Manila, the entire provinces of Bulacan, Rizal and Cavite, parts of the
provinces of Laguna, Quezon and Batangas, and several barangays in
Pampanga. Alternating current at a nominal frequency of sixty hertz (60 Hz)
is distributed throughout the territory served by the Company. Normally, the
electric power supply of an applicant shall be served through an overhead
distribution system. However, if requested, an underground distribution
system may be used, upon compliance with certain Company requirements.
Service Voltages
The following are the service voltages being maintained and offered by the
Company in its franchise area.
1)1000 kva at 230 volts; 2000 kva at 460 volts; 1000 kva at 400Y / 230 volts.
Meralco made available to its customers the 400Y/230-volt, three-phase, four-
wire service voltage starting year-2006.
2) 400Y / 230 volts service may be provided for the following types of loads:
1) Three-phase solely-served industrial establishments,
2) Three-phase solely-served commercial establishments, and
3) Purely residential buildings/condominiums served solely by three-phase
transformer bank/s. However, this service shall be provided only in areas
where the standard primary distribution voltages of 34500Y/19920 volts and
13200Y/7620 volts are available.
2) For service applications in the network area (portions of Binondo, Sta. Cruz
& Quiapo), the applicant shall provide a transformer vault room (for
installation of Meralco’s pad-mounted transformer) within the building
premises under any or both of the following conditions: when the total
connected load of the building is more than 40 kW or when the total building
floor area is more than 280 square meters.
The high voltage service is provided by the Company under any of the
following conditions, 1) The applied load is 10,000 kW and above, 2) The
service shall utilize voltage disturbing loads such as arc furnace, large motor
loads, etc., where the operation of such equipment may cause the flickering
of the distribution voltage, as determined by the Company, 3) Other cases as
established by the Company.
The service shall be metered at the primary voltage side, and the customer
shall provide space, as determined by the Company, for the installation of the
necessary metering facilities. The applicant shall provide, install and maintain
all electrical facilities after the metering point (i.e., transformers, distribution
facilities, main primary service protection). The customer shall provide space,
as determined by the Company, for the installation of the necessary metering
facilities.