Professional Documents
Culture Documents
I. INTRODUCTION
In the conventional PID control system; set-point kick
phenomenon is there because of derivative term. By using
PI-D or I-PD control schemes we can avoid this set-point
kick phenomenon. In the literature, PI-PD control and PID-
PD control has been used. Such control schemes are two
degree of freedom (2DOF) control schemes [1].
Control system’s degree of freedom is nothing but Fig. 1 1DOF PID control system
quantity of closed-loop transfer functions that are
This type of control system causes the difficulty that if we
autonomous. In [2-4] various 2DOF PID controllers, there
are trying to obtain the disturbance response then the set-
analyses, equivalent transformations and effects of the
point response will be oscillatory and if we are trying to
2DOF structure are shown. The paper is organized as
obtain set-point response then the disturbance response
follows: In section 2 two degree of freedom PID controller
deviates [5] as these two necessities clash with each other
is described; section 3 explains the system description of
and cannot fulfilled by using the 1DOF control so that here
temperature control setup with its model, in section 4 two
we have used 2DOF PID controller to satisfy these two
simulation examples are taken, section 5 describe
necessities. The 2DOF PID Controller has set point
experimentation and results, section 6 has some conclusion
weighting on the proportional and derivative action to
remarks.
achieve both smooth set point tracking and good disturbance
II. 2DOF PID CONTROLLER rejection. It has two inputs, one is reference signal and
another is from feedback and output is the difference
Fig. 1 shows the one degree of freedom control system
between these two signals. 2DOF PID controller has two
[1], where d is the load disturbance, r is the set-point, Gሺsሻ
controllers, one is in feed-forward path for set-point tracking
is the controller and Pሺsሻ is the process transfer function. purpose and another is in feedback path for disturbance
Assume that Pሺsሻis unchangeable. rejection. Fig. 2 shows the structure of 2DOF PID
For this system, two closed loop transfer functions Gyr controller. There are different equivalents forms of 2DOF
and Gyd are as- PID controller explained in [3].
Y(s) P(s)
Gyd = = (4)
D(s) 1+C(s)P(s)
Fig. 3 Experimental setup of temperature control system
Here are two tunable elements i.e. C(s) and X(s) because
X(s) is independent of Gyd . We assumed that C(s) and G(s) IV. SIMULATION EXAMPLES
are the same controllers in both 1DOF and 2DOF control Here we have taken FOPDT and higher order system with
system so that the disturbance responses of these systems time delay for simulation study.
are similar and the set-point responses are different from
A. Example 1
each other because of the second term of the 2DOF PID
controller. 2DOF PID controller has the additional Consider first-order plus time delay system
parameter called set-point weighting factors. 1
Where the controllers transfer functions are- Pሺsሻ= e-0.2s (8)
s+1
1
C(s)=Kc ቄ1+ +Td sቅ (5) For this FOPDT system we have designed 2DOF PID
Ti s
controller by using chien-hrones-reswich (CHR) for
disturbance optimal parameters, Integral time absolute error
X(s)=Kc ሼb+cTd sሽ (6)
(ITAE), Ziegler-Nichols (ZN) open loop method and
Analytical robust tuning (ART) with maximum sensitivity
Where, Kc , Ti , Td are the PID parameters i.e. controller
Ms = 1.4 [6]. Table I shows the PID tuning parameters for
gain, integral time constant and derivative time constant
these methods. Fig. 4 shows the set-point tracking response
respectively, b is set point weight on proportional term and c is
and fig. 5 shows set-point tracking response with load
set point weight on derivative term [7]. There is no effect of b
disturbance. Table II shows time domain specifications for
and c on the closed loop stability because the closed loop
these methods.
poles location depends only on the C(s) parameters.
TABLE I. PID TUNING PARAMETERS
III. SYSTEM DESCRIPTION
Tuning method Kc Ti Td b c
The temperature control process setup consist of heating
CHR
tank of 0.5 liter fitted with solid state relay (SSR) controlled (20% overshoot)
6 0.4 0.084 0.6 0.63
heater for heating of water. Here RTD PT100 type ITAE 6.2302 0.3621 0.0768 0.6 0.63
temperature sensor is used for sensing temperature of water.
The water flow can be measured and adjusted by Rota meter ZN 6 0.4 0.1 0.6 0.63
which is fitted on process setup. One heater with two coils ART (Ms =1.4) 1.65 0.8633 - 0.6 -
587
Fig. 4 Unit step response for set-point tracking Fig. 6 Unit step response for set-point tracking for plant uncertainty
C. Example 2
Consider the following 5th order system with time delay-
1
Pሺsሻ= e-2s (10)
s5 +5s4 +10s3 +10s2 +5s+1
ZN 1.58 5.35
ART (Ms =1.4) 2.37 2.58
B. Robustness analysis
For robustness analysis of controller we have increased IJ
by 20% and ș has been decreased by 20%. Then obtained
model is-
1
Pሺsሻ= e-0.16s (9)
1.2s+1
588
TABLE III. PID TUNING PARAMETERS TABLE V. EXPERIMENTATION RESULTS
589