The generator output voltage level can be controlled from a remote location. The generator output
voltage can be controlled with the use of a remotely mounted voltage adjust potentiometer. In order
to control the voltage from a remote location, perform the following steps:
Illustration 1 g01021519
https://sis.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/s... 16/02/2009
PDF created with pdfFactory trial version www.pdffactory.com
3406C Generator Set 9ES00001-UP(SEBP2752 - 15) - Document Structure Página 2 de 2
The terminals and heat sinks are live at hazardous voltages when power
is applied and for up to 8 minutes after power is removed.
For an acceptable voltage control, the remote mounted potentiometer must be 10 K Ohm +5% with
three turns or more and a dielectric strength of 1000 VAC minimum. The terminals of the remote
mounted potentiometer are fragile.
The wiring that is connected to a remote mounted potentiometer, should not have a diameter larger
than 18 gauge. A wire with a larger diameter is not recommended. The wire should be 600 Volt class
with 90 °C (194.0 °F) insulation.
When the remote potentiometer is mounted a long distance (up to 15.24 m (50 ft)) from the generator
set, a shielded cable may be necessary in order to isolate the signal from noise.