3406C Generator Set 9ES00001-UP(SEBP2752 - 15) - Document Structure Página 2 de 5
Illustration 1 g00874825
(CR1-C6) Diodes
(CR7) Varistor
https://sis.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/s... 16/02/2009
PDF created with pdfFactory trial version www.pdffactory.com
3406C Generator Set 9ES00001-UP(SEBP2752 - 15) - Document Structure Página 3 de 5
Self-excited generators may lose the residual magnetism that normally exists in the exciter field (L1)
and the main field (L3). Residual magnetism is necessary to start the generation process. The
magnetism can be restored by flashing exciter field (L1) with direct current. A 6 VDC battery can be
used to supply the direct current.
NOTICE
Do not flash permanent magnet excited (PME) generators. Damage to
the generator set can occur.
TOOLS NEEDED
Tool Quantity
6 VDC Battery 1
2. At the voltage regulator, disconnect wire F1 GEN from terminal F1 and disconnect wire F2
GEN from terminal F2.
4. Momentarily put the negative cable of the 6 volt source on wire F2 GEN (two or three times).
Note: Do not hold the negative cable to wire F2 GEN for more than one or two seconds.
https://sis.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/s... 16/02/2009
PDF created with pdfFactory trial version www.pdffactory.com
3406C Generator Set 9ES00001-UP(SEBP2752 - 15) - Document Structure Página 4 de 5
Illustration 2 g00614470
Dynamic Flashing Circuit
(2) Diode
Table 2
TOOLS NEEDED
Part Number Tool Quantity
237-5130 Digital Multimeter 1
9P-5153 Diode 1
(MR-504)
Dynamic Flashing Circuit 1
https://sis.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/s... 16/02/2009
PDF created with pdfFactory trial version www.pdffactory.com
3406C Generator Set 9ES00001-UP(SEBP2752 - 15) - Document Structure Página 5 de 5
NOTICE
Do not hold the flashing circuit's test leads on the terminals longer
than necessary. This can cause the voltage to become too high.
Excessive voltage can cause damage to the generator and can cause
damage to the flashing circuit.
5. Hold the red lead of the dynamic flashing circuit to terminal F1.
6. Monitor the voltmeter. Touch the black lead to terminal F2 of the dynamic flashing circuit.
7. When the voltmeter shows an increase in voltage, remove the test leads from terminal F1 and
terminal F2. If the generator voltage does not increase within 5 to 10 seconds, remove the test
leads from terminals F1 and F2.
Copyright 1993 - 2009 Caterpillar Inc. Mon Feb 16 15:36:24 EST 2009