Professional Documents
Culture Documents
2007
xxxxxx xxxxxx xxxxxx
R/21-20 (Env. Thermal Power Plant (TPP)
IDENTIFICATION OF ENVIRONMENTAL ASPECT IMPACTS
IMPACT ASSESSMENT & MANAGEMENT MEASURES
All contracted activities are goverened by 'General EHS Conditions of Contract' (WI/6-2)
DEPARTMENT / AREA: THERMAL POWER PLANT
Operating Aspect Severity
Adequacy of Measures
Condition Category S2 = EfxC
1 Boiler Light-up and turbine A/E Fire in oil storage area due D Air pollution 1. Diesel tank located at safer location . - HEF 3 1 6 2
rolling and stoppage to back-fire in burners and 2. Fire proof drive and high pressure hoses
diesel pipes are used to avoid hose failure.
3. The quantity of diesel stored is <1000
liters
4. Emergency Preparedness procedure in
place (P-22 & Emergency Plan 2010)
2 A Noise generation due to D Noise pollution Silencers (2 nos.) are provided to minimise - HEF 3 1 6 1
steam venting. the noise level during start up.
3 A Stack dust emission prior to D Air pollution ESP put in service when flue gas ESP is not put in service EF 4 2 6 2
putting ESP in service and temperature reaches above acid dew point. until flue gas
during boiler cooling without temperatures reaches
ESP in service. above acid dew point to
prevent corrosion and
damage to ESP internals.
4 Boiler operation N Generation of CO2 (above D Global warming, 1. CO2 is partly compensated by tree Supply of desired quality EF 4 2 8 3
prescribed/ budgeted norms plantation of coal is subject to
or benchmark) 2. Daily monitoring of Boiler Heat Efficiency economy
& Internal Power Consumption
3. Annual budget & benchmarking for the
above parameters
5 N Generation of Sox, Nox & D air pollution 1. Limestone is used as a sorbent to absorb Presently online LEF 4 3 8 4
CO (above prescribed/ (increase in Sox, SO2 measurement of Sox, Nox
budgeted norms or Nox and CO level in 2. Furnace temperature maintained below & CO is not availabe
benchmark) Ambient Air) 950 deg.C to reduce NOx emission.
3. Excess air level maintained to eliminate
CO emission.
6 N Dust generation D Air pollution 1. ESP installed, interlocked with boiler - HEF 4 1 8 1
2. Documented PM plan/ schedule
followed.
2. Online measurement/ monitoring of
Stack dust emissions
3. Isokinetic measurement of stack dust
emission by Env. Cell fortnightly.
HOD MR / MA (IMS) 1 of 25
Doc.No. DS/21-6, Version, 4.0, Dated 01.12.2007
7 Fly Ash filling in tanker at N Dust generation D Air pollution Fly ash is filled in closed bulkers through 1. Spillage due to EF 3 2 4 1
Fly Ash Silo (Increase in PM-10 telescopic chute equipped with bag filter overfilling,
& PM 2.5 in 2. Occcasional
ambient air) malfunctioning of bag
filters
HOD MR / MA (IMS) 2 of 25
Doc.No. DS/21-6, Version, 4.0, Dated 01.12.2007
8 Dust emission while ash N Dust generation D Air pollution 1. Bag filter installed at silo top & also Dust 1. Spillage due to EF 2 2 4 1
conveying/disposal and conditioner installed for unit 1 for loading in overfilling,
filling conditioned ash in dumpers. 2. Occcasional
dumpers in fly ash disposal 2. For unit 2 & 3 Bulk loading system is malfunctioning of bag
area. installed for filling ash in to bulkers. filters
3. Fly ash silo covered.
9 Oil circulation in pipings & N Fire D Air pollution 2. All the steam lines in the vicinity of oil - HEF 4 1 8 2
bearings and oil storage in line insulated.
Oil tank in Turbine area. 2. Oil with flash point > 250 deg.C used.
10 A Oil leakage D Land 1. Waste Oil is collected in trays and - HEF 3 1 4 2
contamination disposed off at marked area.
2. Bottom floor is made of RCC.
3. Oil leakages are spotted and addressed
on priority.
11 Coal plant operations e.g. N Dust generation D Air pollution 1. Water sprinklers provided on belt 1. Sometimes sprinklers EF 4 2 8 2
coal unloading, (Increase in PM-10 conveyors. may not work properly
transportation, storage, & PM 2.5 level in 2. Jet pulse filter provided at all transfer due to nozzle choking.
sampling, stacking, dozing ambient air) points. 2. Col area close to plant
in feed hopper, crushing 3. All the belts covered with hood. boundary
and filling of screened coal 4. Regular insprection by shift supervisor/ 3. Dust emission during
in Bunker, involving Engineer shifting of coal from Rly.
operation of conveyor Siding to plant
belts, Vibrating Screen,
Crusher, JCB, Loader, etc.
13 N Spontaneous fire in coal D Deplition of natural 1. Regular water spray on feed belts During summers, fire is EF 4 2 4 2
piles resources 2. Fire affected coal is shifted to another possible at the prevailing
location & extinguished through water ambinet temp.
spray .
HOD MR / MA (IMS) 3 of 25
Doc.No. DS/21-6, Version, 4.0, Dated 01.12.2007
14 Plant operation, routine N High intensity noise D Noise pollution 1. Daily inspection of machines - HEF 4 1 4 2
inspection and 2. Scheduled PM plan followed.
Maintenance of auxiliary 2. Work place noise level is monitored and
equipments. (Turbine- controlled so as to maintain the Ambient
Generator, Boiler, Feed Noise below 70 dB.
Pump, etc.),
15 N Spillage of oil (Haz. Waste) D Land 1. Area is concrete paved to prevent ingress - HEF 1 1 6 2
contamination of oil into land
2. Regular inspect to identify & rectify such
leakages through check list .
3. In special case ,trays are kept below the
leaking equipment for collection of oil and
collected as spent oil and handed over to
Stores for further disposal.
16 Compressor operation and N Noise generation D Noise pollution Comprssors are installed in a separate - HEF 2 1 2 1
use of Compressed Air (Increase in enclosed building & with noise hood.
ambient noise)
17 N Spillage of oil (Haz. Waste) D Land 1. Area is paved to prevent ingress of oil - HEF 4 1 6 4
contamination. into land
2. Regular inspect to identify & rectify such
leakages through check list .
3. In special case ,trays are kept below the
leaking equipment for collection of oil and
collected as spent oil and handed over to
Stores for further disposal.
18 Operation of water N Damage to environment D Land 1. HDPE tank is used for storage and PVC - HEF 3 1 6 1
treatment plant Handling, due to spillage of acid/alkali contamination. fittings provided.
storage and use of and chemicals 2. Tanks base upon concrete flooring,
acid/alkali and chemicals 3. Use of caustic Flakes in place of liquid
in WT plant. caustic.
4. Acid usage minimzed by replacing WCC
with ACC
5. Regular inspection and monitoring by
WTP staff
HOD MR / MA (IMS) 4 of 25
Doc.No. DS/21-6, Version, 4.0, Dated 01.12.2007
19 N Waste water generation D Water pollution, 1. ACC installed in all the units - HEF 4 1 8 3
during regeneration of PSF, Max. limit of 2. High TDS blowdown water and waste
Softener, MB unit and DMF. discharge qty. water is tested & neutralized in
prescribed neutralization pit and then used for dust
suppression.
3. Water meters installed at inlet & outlet to
monitor waste water generation and
discharge
4. Daily monitoring of discharge quantities
by WTP staff
20 N Gas/ fumes generation D Air pollution Acid tank located outside of building. Leakage in tank EF 1 2 2 1
Proper ventilation is provided so that
suffocation, inhaling of acid fumes can be
avoided.
22 Movement of Trailers, N Dust, Sox, Nox generation D Air pollution Concrete road in fly ash area & coal plant Spillage of powedery EF 3 2 2 2
trucks, JCB/Loader and (Increase in Sox, Roads are periodically cleaned to minimise material from moving
other vehicles for various NOX, PM-10 & PM the impact. vehicles
plant activities. 2.5 level in ambient
air)
23 Generation of electricity N Consumption of water D Depletion of 1. WCC replaced with Air cooled condenser. - HEF 4 1 8 3
(beyond budgeted norms/ natural resources. 2. Chemical treatment of Auxiliary cooling
benchmark) water is being done to reduce blowdown
loss.
3. Treated B/D water is used for dust
suppression to conserve fresh water
4. Daily monitoring of water consumption
through water meters
24 N Consumption of coal/ fuel D Deplition of natural 1. Annual budget for Boiler Heat Rate & Supply of desired quality EF 4 2 4 4
(beyond budgeted norms/ resources. internal power consumption of coal is subject to
benchmark) 2. Daily energy monitoring economy
3. Energry efficient CFBC Boilers in CPP-2 &
3.
HOD MR / MA (IMS) 5 of 25
Doc.No. DS/21-6, Version, 4.0, Dated 01.12.2007
25 Unloading of acid in N Damage to environment D Land degradation 1. Acid and leak proof hose pipes used for - HEF 2 1 4 1
storage tank due to spillage of acid unloading.
2. Work instruction are strictly followed.
3. Use of sulphuric acid eliminated.
4. HCl storage tank is housed in RCC
enclosure.
5. Unloading is done under expert
supervision
HOD MR / MA (IMS) 6 of 25
Doc.No. DS/21-6, Version, 4.0, Dated 01.12.2007
xxxxxx xxxxxx xxxxxx
Regulatory or
'Other'
requirement Total = Impact Regulatory or 'Other' Additional control
apply? S1+S2+D1 Classifica Ref. Doc.
Yes = 5 +E1 tion requirements' explanation required Y/N
No = Zero
(E1)
5 37 I Air, Water Consent, EC, IBR & Yes, Online Sox, Nox and Capex
Factories Act, National Ambient CO analyser to be installed proposal/
Air Quality Standards, 2009 before Dec'11 ISMP for
online
stack gas
analyser
HOD MR / MA (IMS) 7 of 25
Doc.No. DS/21-6, Version, 4.0, Dated 01.12.2007
Regulatory or
'Other'
requirement Total = Impact
Regulatory or 'Other' Additional control
apply? S1+S2+D1 Classifica Ref. Doc.
Yes = 5 +E1 tion requirements' explanation required Y/N
No = Zero
(E1)
HOD MR / MA (IMS) 8 of 25
Doc.No. DS/21-6, Version, 4.0, Dated 01.12.2007
Regulatory or
'Other'
requirement Total = Impact
apply? S1+S2+D1 Classifica Regulatory or 'Other' Additional control Ref. Doc.
requirements' explanation required Y/N
Yes = 5 +E1 tion
No = Zero
(E1)
0 14 M - No ?
0 14 M -
HOD MR / MA (IMS) 9 of 25
Doc.No. DS/21-6, Version, 4.0, Dated 01.12.2007
Regulatory or
'Other'
requirement Total = Impact
apply? S1+S2+D1 Classifica Regulatory or 'Other' Additional control Ref. Doc.
requirements' explanation required Y/N
Yes = 5 +E1 tion
No = Zero
(E1)
5 15 M No
HOD MR / MA (IMS) 10 of 25
Doc.No. DS/21-6, Version, 4.0, Dated 01.12.2007
Regulatory or
'Other'
requirement Total = Impact Regulatory or 'Other' Additional control
apply? S1+S2+D1 Classifica requirements' explanation required Y/N Ref. Doc.
Yes = 5 +E1 tion
No = Zero
(E1)
0 6 T - No
0 6 T - No
HOD MR / MA (IMS) 11 of 25
Doc.No. DS/21-6, Version, 4.0, Dated 01.12.2007
Regulatory or
'Other'
requirement Total = Impact Regulatory or 'Other' Additional control
apply? S1+S2+D1 Classifica Ref. Doc.
requirements' explanation required Y/N
Yes = 5 +E1 tion
No = Zero
(E1)
HOD MR / MA (IMS) 12 of 25
IMPACT CLASSIFICATION & ACTIONS TO BE TAKEN
Risk Score Category Status
Trivial
0 - 11
12-20 Moderate
Non-significant
21-32 Substantial
Effective EF 2
Less Effective LEF 3
Ineffective IEF 4
DETERMINING EFFECTIVENESS OF CONTROLS
Criteria