July 19, 2022 DISSOLVE GAS ANALYTIS REPORT

Client's Name: JX NIPPON MININGS & METALS PHILIPPINES INC.


Address: 117 EAST SCIENCE AVENUE LAGUNA TECHNOPARK INC.
Project / Location: ANNUAL PREVENTIVE MAINTENANCE
Area: POWERPLANT SUBSTATION PHASE 2 Designation: 32-TR-12
Feed From: Feed To:

Capacity: 2500 KVA Make: SQUARE-D Type: OIL TYPE


Pri. volts: 6600 Volts Serial No: 000770-D1 % Imp.:
Sec. volts: 480 Volts Mfg Date: 2001 Ins. Class:
Cycles/Sec.: 60 Hz. Oil Temperature: 50°C Connection:
Total Weight: 5352 kg. Age (years): 21 Weather Condition:

TEST RESULTS
GAS (ppm) ASTM D3612
Sample Date Present
*HYDROGEN H2 = 7.90 (ppm)
*METHANE CH4 = 60.10 (ppm)
*ETHANE C2H6 = 48.20 (ppm)
*ETHYLENE C2H4 = 6.20 (ppm)
*ACETYLENE C2H2 = 0.00 (ppm)
*CARBON MONOXIDE CO = 254.80 (ppm)
CARBON DIOXIDE CO2 = 4,835.00 (ppm)
NITROGEN N2 = 56,610.80 (ppm)
OXYGEN O2 = 4,188.80 (ppm)
TOTAL COMBUSTIBLE GAS = 377.20 (ppm)
TOTAL DISSOLVED GAS CONTENT = 66,011.80 (ppm)

KEY GAS LIMITS ( ASTM D 3612 ) Roger's Ratio Method ( Present Sample )

HYDROGEN ( <75 ppm )


METHANE ( <90 ppm ) C2H2/C2H4 0.00 code = -
ETHANE ( <90 ppm ) CH4/H2 7.65 code = 3
ETHYLENE ( <50 ppm ) C2H4/C2H6 0.13 code = 0
ACETYLENE ( <1 ppm )
CARBON MONOXIDE ( <900 ppm ) ► Data is not definable by Roger's Ratio.
CARBON DIOXIDE ( <10000 ppm )

OIL QUALITY TEST RESULTS ( IEEE C57.106-2015, 69kV Voltage Class )


Sample Date Present
WATER CONTENT (D1533B) = 5 WATER CONTENT (D1533B) = <35 ppm
DBV (D877) 2.5mm = 37.38 DBV (D877) 2.5mm = >30kV
NEUTRALIZATION NO. (D974) = 0.0146 NEUTRALIZATION NO. (D974) = <0.2 mgKOH/g
INTERFACIAL TENSION (D971) = 26.7 INTERFACIAL TENSION (D971) = >25 dynes/cm
COLOR (D1500) = L2.0/CLEAR COLOR (D1500) = <3.5 / Clear
OIL POWER FACTOR @60HZ, 25°C ( D924) = 0.669 OIL POWER FACTOR @60HZ, 25°C ( D924) = <0.5%

IEC 60599 Ratio Method ( Present Sample ) Duval's Triangle Method

C2H2/C2H4 0.00 code = - Triangle 1 Not Applicable


CH4/H2 7.65 code = 2
C2H4/C2H6 0.13 code = 0 Triangle 4 or 5
► Data is not definable using IEC 60599 Ratio.

RECOMMENDATIONS:
Based on Dissolved Gas Analysis Results
CO2/CO -----------
DGA Status * DGA Status 1
Resampling
Faults
Addtnl Remarks: * Recommended Sampling Date July 15,2023
Based on Oil Analysis Results
* Insulating oil fails the Oil Power Factor standard of less than 0.5%. Recommend for Transformer Oil Replacement.
PREPARED BY: SUPERVISED BY: CHECKED BY :

ENGR. JOHN AARON M. COMIA, REE ENGR. RICKY B. VALENCIA, REE ENGR. RICKY M. PAIRAT, PEE
Project Engineer Project Manager President