You are on page 1of 75

10481-BCL-AKSX-AR-REP-0001-4

NNPC
Nigerian National Petroleum Corporation

Ajaokuta Kaduna Kano


Gas Pipeline Project

ARCHITECTURAL DESIGN BASIS


06-OCT-2020

Project Management Consultant EPC Contractor

BRENTEXCPP Limited
Ajaokuta Kaduna Kano Gas Pipeline Project

10481-BCL- AKSX- AR-REP-0001-4

ARCHI TECTUR AL DESIGN B ASI S

REVISION

4 06-Oct-2020 Issued for Construction Huo Chongyun Arnold Datu Luo Yexin
3 16-Aug-2020 Issued for Approval Huo Chongyun Arnold Datu Luo Yexin
2 18-Jul-2020 Issued for Approval Huo Chongyun Arnold Datu Luo Yexin
1 04-Jun-2020 Issued for Review Huo Chongyun Arnold Datu Luo Yexin
0 22-Mar-2020 Issued for Review Huo Chongyun Arnold Datu Luo Yexin
Rev. Date Status Description Originator Checked Approved

10481-BCL-AKSX-AR-REP-0001_4_IFC_Architectural Design Basis(1) Page 2 of 75


2020
Ajaokuta Kaduna Kano Gas Pipeline Project

10481-BCL- AKSX- AR-REP-0001-4

ARCHI TECTUR AL DESIGN B ASI S

TABLE OF CONTENTS

1 GENERAL 9

2 PURPOSE 9

3 DEFINITIONS AND ABBREVIATIONS 10


3.1 Definitions 10

3.2 Abbreviations 10

4 REFERENCES 12
4.1 Other Reference Documents 14

5 OVERALL DESIGN REQUIREMENTS 15


5.1 Order of Precedence 15
5.2 Codes and Standards 16

5.3 Units of Measurement 19


5.4 Language 20
5.5 Design Life 20

6 BUILDING DESIGN 20
6.1 General Requirements 20
6.2 Scope 21

6.2.1 Building Occupancy Classification 21


6.3 Specific Building Design Requirements 22
6.3.1 General Building Philosophy 22

6.3.2 Control Equipment Shelter 22


6.3.2.1 General Description 22
6.4 Thermal Transmittance (U-Value) 23

6.5 Fire Resistance 23


6.5.1 Passive Fire Protection (PF) Requirements for Buildings 23
6.5.2 Fire Walls 24
6.5.3 Means of Egress 24

10481-BCL-AKSX-AR-REP-0001_4_IFC_Architectural Design Basis(1) Page 3 of 75


2020
Ajaokuta Kaduna Kano Gas Pipeline Project

10481-BCL- AKSX- AR-REP-0001-4

ARCHI TECTUR AL DESIGN B ASI S

6.5.4 Escape Routes 24


6.6 Foundation, Structure and Type of Construction 25
6.6.1 Types and Methods of Construction 25
6.6.2 Blast Resistance Requirements 28
6.7 Submittals to the PMC / Owner 28
6.7.1 PMC / Owner Reviews 28

7 BUILDING OCCUPANCY LEVEL 29


7.1 General Requirements 29
7.2 Entrance Security Check Building 32
7.3 Accommodation Building for Supervisors 32

7.4 Accommodation Building for Personnel 33


7.5 Administration and Security Building 33
7.6 Electrical and Control Building 34
7.7 Prayer House 34
7.8 Guard Post 35
7.9 Workshop and Warehouse 35

8 BUILDING COMPONENTS AND MATERIALS 36


8.1 General requirement 36
8.1.1 Quality 36

8.1.2 Fire Resistance and Combustibility 36


8.1.3 Acoustic Performance 37
8.1.4 Intruder Resistance 37
8.2 Masonry 37
8.2.1 External CMU (Concrete Masonry Unit) Wall 38
8.2.2 Internal CMU (Concrete Masonry Unit) Wall 38
8.3 Steel Structure 38
8.3.1 Sandwich Panels 38
8.3.2 Exterior Single Skin Panels 39

8.3.3 Fabric Sunshades 39

10481-BCL-AKSX-AR-REP-0001_4_IFC_Architectural Design Basis(1) Page 4 of 75


2020
Ajaokuta Kaduna Kano Gas Pipeline Project

10481-BCL- AKSX- AR-REP-0001-4

ARCHI TECTUR AL DESIGN B ASI S

8.4 Roof Covering and Flashings 39


8.4.1 Materials 39
8.5 Insulation Works 41
8.5.1 Materials 41
8.5.1.1 Product for surface waterproofing 41
8.5.1.2 Laminated waterproofing products 41
8.5.1.3 Products for moisture proofing and waterproofing from rolled
materials 41
8.5.1.4 Products for sealing / filling joints, crevices, transitions 41
8.6 Carpentry and Joinery Items 42
8.6.1 General Requirements 42
8.6.2 Quality of Timber 42
8.6.3 Plywood 42
8.6.4 Fabrication 42
8.7 Doors and Windows 42
8.7.1 Materials 42
8.7.2 Steel Doors and Frames 43
8.7.3 Wood Doors and Frames 43
8.7.4 Aluminium Doors and Windows 43

8.7.5 Glass and Glazing 44


8.7.6 Upward Acting Sectional Doors 44
8.7.7 Blast Resistant Doors and Frames 44
8.7.8 Blast Resistant Windows 44
8.8 Building Fabric Sundries 45
8.8.1 Ironmongery 45
8.9 Furniture, Fixtures & Equipment 45
8.9.1 General Requirements 45
8.9.2 Fixtures 45

8.9.3 Fittings 46
8.9.4 General Signage 46

10481-BCL-AKSX-AR-REP-0001_4_IFC_Architectural Design Basis(1) Page 5 of 75


2020
Ajaokuta Kaduna Kano Gas Pipeline Project

10481-BCL- AKSX- AR-REP-0001-4

ARCHI TECTUR AL DESIGN B ASI S

8.10 Sanitary Ware 47


8.10.1 Water Closet / Locker / Shower 47
8.10.2 Janitor Room 47
8.10.3 Safety Showers and Eye Wash 48
8.10.4 Restrooms 48
8.11 Metal Works 48
8.11.1 Steel Ladder 48
8.11.2 Steel Louvers 49
8.12 Hard and Soft Landscaping 49
8.12.1 General Requirements 49

9 SURFACE FINISHES 50
9.1 Suspended Ceilings 50
9.1.1 Materials 50
9.2 Stud Wall with Plasterboard Covering 50
9.2.1 Material 50
9.3 Flooring and Covering Works 51
9.3.1 General Requirements: 51
9.3.2 Raised Access Floor 52
9.3.3 Ceramic Floor Tiles 53

9.3.4 Resilient Flooring 53


9.3.5 Carpet 54
9.3.6 Concrete Floor 54
9.3.7 Sub-floors 55
9.4 Natural and Artificial Stone 55
9.5 Wall Finishes 55
9.5.1 Ceramic Wall Tiles 55
9.5.2 Wall Paint Finish 55
9.6 Plastering Works 56

9.6.1 Materials 56

10481-BCL-AKSX-AR-REP-0001_4_IFC_Architectural Design Basis(1) Page 6 of 75


2020
Ajaokuta Kaduna Kano Gas Pipeline Project

10481-BCL- AKSX- AR-REP-0001-4

ARCHI TECTUR AL DESIGN B ASI S

9.6.1.1 Cement-lime construction mortars 56


9.6.1.2 Gypsum putty 57
9.6.1.3 Water 57
9.6.1.4 Priming agents 57
9.6.1.5 Sand 57
9.7 Painting Works 57
9.7.1 Materials 58
9.7.1.1 Types of materials for indoor painting 58
9.7.1.2 Types of materials for outdoor painting 59
9.7.1.3 Water 60
9.8 FINISHING SCHEDULE 60

10 BUILDING UTILITIES AND SERVICES 62


10.1 General Requirements 62
10.2 Utility Systems 63
10.3 HVAC System 63
10.4 Electrical 63
10.5 Fire Protection and Safety 63
10.5.1 Human Factors 63
10.6 Telecommunication 64

FIGURES

Figure 1 : AKK (Segment 2) Overall Pipeline Route

TABLES

Table 1 Reference Documents

Table 2 Other Reference Documents

Table 3 Code and Standards

Table 4 U-value of Building Envelope

10481-BCL-AKSX-AR-REP-0001_4_IFC_Architectural Design Basis(1) Page 7 of 75


2020
Ajaokuta Kaduna Kano Gas Pipeline Project

10481-BCL- AKSX- AR-REP-0001-4

ARCHI TECTUR AL DESIGN B ASI S

Table 5 Types and Methods of Construction

Table 6 TGS Area Wise Occupancy

Table 7 Building Wise Occupancy

Table 8 Area/Activity Wise Occupancy

Table 9 Area/Activity Wise Occupancy

Table 10 Area/Activity Wise Occupancy

Table 11 Area/Activity Wise Occupancy

Table 12 Area/Activity Wise Occupancy

Table 13 Area/Activity Wise Occupancy

Table 14 Area/Activity Wise Occupancy

Table 15 Area/Activity Wise Occupancy

Table 16 Acceptable Sound Level for Various Types

Table 17 External CMU Wall Layers

Table 18 Internal CMU Wall Layers

Table 19 Indoor and Outdoor Proposed Finishing of Buildings, Shelters/Sheds

Table 20 Unit/Are Code (bbb)

Table 21 Building Code (ccc)

Table 22 Building(s) and Shelter(s) Description and Basic Requirement

APPENDICES

Appendix 1 Building Code

Appendix 2 Building(s) and Shelter(s) Description and Basic Requirement

10481-BCL-AKSX-AR-REP-0001_4_IFC_Architectural Design Basis(1) Page 8 of 75


2020
Ajaokuta Kaduna Kano Gas Pipeline Project

10481-BCL- AKSX- AR-REP-0001-4

ARCHI TECTUR AL DESIGN B ASI S

1 GENERAL

The Nigerian National Petroleum Corporation (NNPC), hereby referred to as the OWNER
has awarded the contract to Brentex CPP Limited for the Engineering, Procurement and
Construction of Ajaokuta Kaduna Kano (AKK) Gas Pipeline and Stations Project
(Segment 2) from Block Valve Station 12 (outer line of the fence) to Kano Terminal Gas
Station with a distance of about 318.66 km of the Trans Nigeria Gas Pipeline and
stations. The pipeline runs from BVS12 roughly northern towards Kano TGS as
illustrated in Figure 1 below:

Figure 1 : AKK (Segment 2) Overall Pipeline Route

This document covers the technical requirements for engineering works and services,
including all items such as pipeline, crossings, stations, BVS, ancillary installations,
temporary installations, etc.
2 PURPOSE
The purpose of this document is to describe the minimum technical and other
requirements for the design and preparation of the architectural documents and drawings
to be used for the complete procurement and construction of the BUILDING(S) and
SHELTER(S) for the PROJECT. In addition to the requirement specified in this
document, the relevant statutory authority requirements and all requirements in FEED
must be observed wherever applicable.

This document provides a tool that can use to clearly present the decision, assumptions,
and specifications that are being used to develop the construction documents in the
project.

10481-BCL-AKSX-AR-REP-0001_4_IFC_Architectural Design Basis(1) Page 9 of 75


2020
Ajaokuta Kaduna Kano Gas Pipeline Project

10481-BCL- AKSX- AR-REP-0001-4

ARCHI TECTUR AL DESIGN B ASI S

This document shall be read and construed in conjunction with other documents
concerning or affecting CONTRACTOR’s execution of the Works.

Nothing contained in the document shall be construed as reducing or diminishing any of


CONTRACTOR’s obligations described else in the Project Documents.
3 DEFINITIONS AND ABBREVIATIONS

3.1 Definitions

PROJECT Ajaokuta Kaduna Kano Gas Pipeline Project

OWNER Nigerian National Petroleum Corporation (NNPC).

PMC NETCO-ILF Consortium.

CONTRACTOR Brentex CPP Limited.

SUBCONTRACTOR The party(s) which carries out all or part of the engineering,
design, survey and geotechnical investigation as specified
by the CONTRACTOR.
SUPPLIER The company or factory that designs and manufactures the
equipment and provides it to the OWNER of this Project.

SUB-SUPPLIER The company or factory that subcontracts the design and


manufacture of the equipment and provides to SUPPLIER
for this Project.

Shall Indicates a mandatory requirement.

Should Indicates a strong recommendation.

3.2 Abbreviations

AG Above Ground

AKK Ajaokuta Kaduna Kano

ANSI American National Standards Institute

API American Petroleum Institute

ASCE American Society of Civil Engineers


American Society of Heating, Refrigerating & Air
ASHRAE
Conditioning Engineers
ASME American Society of Mechanical Engineers

ASTM American Society for Testing and Materials

10481-BCL-AKSX-AR-REP-0001_4_IFC_Architectural Design Basis(1) Page 10 of 75


2020
Ajaokuta Kaduna Kano Gas Pipeline Project

10481-BCL- AKSX- AR-REP-0001-4

ARCHI TECTUR AL DESIGN B ASI S

BS British Standards

BVS Block Valve Station

CCTV Closed Circuit Television

CS Compressor Station

DWV Drain, Waste, and Vent

EMI Electromagnetic Interference

EPC Engineering, Procurement and Construction

ESD Emergency Shutdown

F&G Fire & Gas

FEED Front End Engineering and Design

GA General Arrangement

GE GAP GE Global Asset Protection Services

GP Gas Plant

HDPE High Density Polyethylene pipe

IBC International Building Code

ILF ILF Consulting Engineers

KP Kilometer Point

MS Metering Station

NFPA National Fire Protection Association

NNPC Nigerian National Petroleum Corporation (NNPC)

PAGA Public Address and General Alarm

PFP Passive Fire Protection

PPR Poly Polypropylene random

PS Pigging Station

RTU Remote Terminal Unit

SCADA Supervisory Control and Data Acquisition

SoW Scope of Work

10481-BCL-AKSX-AR-REP-0001_4_IFC_Architectural Design Basis(1) Page 11 of 75


2020
Ajaokuta Kaduna Kano Gas Pipeline Project

10481-BCL- AKSX- AR-REP-0001-4

ARCHI TECTUR AL DESIGN B ASI S

TBC To Be Confirmed

TDR Technical Deviation Request

TGS Terminal Gas Station

TNGP Trans Nigeria Gas Pipeline

TQ Technical Query

UG Underground

4 REFERENCES
In this document references have been made to the following documents.

Table 1 Reference Documents


Document No. Document Title

10481-BCL-AKGE-PM-PLN-0001 Project Execution Plan (PEP)

10481-BCL-AKGE-PM-MDR-0001 Master Document Register (MDR)

10481-BCL-AKGE-GE-PLN-0001 Engineering Execution Plan

10481-BCL-AKGE-GE-PLN-0002 Engineering Quality Plan

10481-BCL-AKGE-GE-REP-0002 FEED Verification Reports

10481-BCL-AKGE-GE-REP-0003 Basis of Design

10481-BCL-AKGE-GE-PHL-0001 Manning Philosophy

10481-BCL-AKSX-AR-SPC-0001 Architectural Specifications

10481-BCL-AKSX-PR-REP-0001 Process Design Basis

10481-BCL-AKSX-ST-REP-0001 Civil & Structural Design Basis

10481-BCL-AKSX-ME-REP-0001 Mechanical Design Basis

10481-BCL-AKSX-HV-REP-0001 HVAC Design Basis

10481-BCL-AKSX-PB-REP-0001 Plumbing Design Basis

10481-BCL-AKSX-EL-PHL-0001 Electrical Power Supply Philosophy

10481-BCL-AKSX-EL-PHL-0002 Electrical Design Philosophy

10481-BCL-AKSX-TE-REP-0001 Telecom Design Basis

10481-BCL-AKSX-AR-REP-0001_4_IFC_Architectural Design Basis(1) Page 12 of 75


2020
Ajaokuta Kaduna Kano Gas Pipeline Project

10481-BCL- AKSX- AR-REP-0001-4

ARCHI TECTUR AL DESIGN B ASI S

10481-BCL-AKSX-IN-REP-0001 Instrument and Control Design Basis

10481-BCL-AKSX-HS-PHL-0001 HSE Philosophy

10481-BCL-AKSX-HS-PHL-0002 Fire Fighting Philosophy

10481-BCL-AKSX-HS-PHL-0003 Fire Protection Philosophy

10481-BCL-AKSX-HS-PHL-0004 Fire & Gas Detection Philosophy

10481-BCL-AKSX-ST-SPC-0001 Specifications for Concrete Work

10481-BCL-AKSX-ST-SPC-0002 Specifications for Structural Steel Work

10481-BCL-AKSX-ST-SPC-0004 Specifications for Masonry Works

10481-BCL-AKSX-HV-SPC-0001 HVAC Equipment Specification

10481-BCL-AKSX-AR-SPC-0002 Control Equipment Shelter Specification

KADUNA TGS Entrance Security Check


10481-BCL-AKS2-AR-DWG-0001
Building Plans, Elevations, Sections

KANO TGS Entrance Security Check


10481-BCL-AKS4-AR-DWG-0001
Building Plans, Elevations, Sections

KADUNA TGS Accommodation for


10481-BCL-AKS2-AR-DWG-0008
Supervisor Furniture Layout

KANO TGS Accommodation for Supervisor


10481-BCL-AKS4-AR-DWG-0008
Furniture Layout

KADUNA TGS Accommodation for


10481-BCL-AKS2-AR-DWG-0016
Personnel Furniture Layout

KANO TGS Accommodation for Personnel


10481-BCL-AKS4-AR-DWG-0016
Furniture Layout

KADUNA TGS Administration & Security


10481-BCL-AKS2-AR-DWG-0025
Building Furniture Layout

KANO TGS Administration & Security


10481-BCL-AKS4-AR-DWG-0025
Building Furniture Layout

KADUNA TGS Electrical & Control Building


10481-BCL-AKS2-AR-DWG-0034
Furniture Layout

KANO TGS Electrical & Control Building


10481-BCL-AKS4-AR-DWG-0034
Furniture Layout

10481-BCL-AKS2-AR-DWG-0043 KADUNA TGS Prayer House Furniture

10481-BCL-AKSX-AR-REP-0001_4_IFC_Architectural Design Basis(1) Page 13 of 75


2020
Ajaokuta Kaduna Kano Gas Pipeline Project

10481-BCL- AKSX- AR-REP-0001-4

ARCHI TECTUR AL DESIGN B ASI S

Layout

10481-BCL-AKS4-AR-DWG-0043 KANO TGS Prayer House Furniture Layout

KADUNA TGS Workshop & Warehouse


10481-BCL-AKS2-AR-DWG-0051
Furniture Layout

KANO TGS Workshop & Warehouse


10481-BCL-AKS4-AR-DWG-0051
Furniture Layout

KADUNA TGS Guard Post Plans,


10481-BCL-AKS2-AR-DWG-0053
Elevations & Sections

KANO TGS Guard Post Plans, Elevations


10481-BCL-AKS4-AR-DWG-0053
& Sections

4.1 Other Reference Documents

Table 2 Other Reference Documents

Document No. Document Title

G791-ILF-AKPL-GE-SOW-0001_1 Scope of Work

G791-ILF-XXGE-GE-REP-0005_1 Project Description - General

G791-ILF-XXGE-GE-REP-0002_5 Basis of Design

G791-ILF-XXGE-CI-PHL-0001_2 Civil Design Philosophy

G791-ILF-XXGE-CI-SPC-0004_2 Architectural Works Specification

G791-ILF-XXGE-CI-SPC-0005_2 Masonry Works Specification

G791-ILF-XXGE-CI-SPC-0001_1 Concrete Works Specification

G791-ILF-XXGE-CI-SPC-0002_1 Steel Works Specification

G791-ILF-XXGE-SF-PHL-0001_1 Fire Fighting Philosophy

G791-ILF-XXGE-CI-SPC-0006_1 (Passive) Fire Fighting System Specification

G791-ILF-XXGE-ME-SPC-0014_1 (Active) Fire Fighting System Specification

G791-ILF-XXGE-HV-SPC-0001_2 HVAC Specifications

G791-ILF-XXSX-CI-SPC-0001_1 Control Equipment Shelter Specification

10481-BCL-AKSX-AR-REP-0001_4_IFC_Architectural Design Basis(1) Page 14 of 75


2020
Ajaokuta Kaduna Kano Gas Pipeline Project

10481-BCL- AKSX- AR-REP-0001-4

ARCHI TECTUR AL DESIGN B ASI S

Document No. Document Title

Electrical and Control Building Guide Dwg


G791-ILF-AKSX-CI-DWG-0001_1
TGS

G791-ILF-AKSX-CI-DWG-0004_0 Administration and Security Bldg. TGS

G791-ILF-AKSX-CI-DWG-0006_1 Accommodation Buildings TGS

G791-ILF-AKSX-CI-DWG-0007_1 Workshop Warehouse TGS

G791-ILF-AKSX-CI-DWG-0008_0 Entrance Security Check Bldg. TGS

G791-ILF-AKSX-CI-DWG-0009_1 Prayer House TGS

5 OVERALL DESIGN REQUIREMENTS

5.1 Order of Precedence

In the event of conflict between project documents and references made in the project
documents, the order of precedence shall be as follows:

1. National and/or local legislation (laws, regulations, etc.)


2. Project specifications
3. Owner specifications
4. National and International Codes and Standards (whichever is more
stringent)
The information given in each of the above shall be used, in conjunction with all other
above listed documents.

In the event of an inconsistency, conflict or discrepancy between any of the standards,


specifications and regulation requirements, the most stringent and safest requirement
applicable to the project will prevail to the extent of the inconsistency, conflict or
discrepancy.

In such cases, CONTRACTOR shall provide its interpretation in writing of the most
stringent requirement for Owner approval. In all such cases of conflict, Owner’s decision
will be final.

10481-BCL-AKSX-AR-REP-0001_4_IFC_Architectural Design Basis(1) Page 15 of 75


2020
Ajaokuta Kaduna Kano Gas Pipeline Project

10481-BCL- AKSX- AR-REP-0001-4

ARCHI TECTUR AL DESIGN B ASI S

5.2 Codes and Standards

The industry codes and standards referenced in and/or applicable to this document are
listed below in Table 3. A reference, in this specification, to these documents, invokes
the latest edition of the code, specification or amendment, unless otherwise specifically
stated.

SUBCONTRACTOR, CONTRACTOR and VENDOR shall comply with all applicable


codes, specifications and standards in accordance with the present document.
SUBCONTRACTOR, CONTRACTOR and VENDOR shall strictly comply with all Owner
instructions and guidelines.

Vendor shall comply with Owner standards, specifications and shall notify Owner of any
conflicts or discrepancies between standards and shall provide its interpretation in writing
of the most stringent requirement for Owner approval.
Table 3 Code and Standards

Code Document Title

ACI 360 Specification for Structural Steel Buildings

ACI 301:2005 Standard Specification for Structural Concrete

Building Code Requirements for Structural Concrete (ACI 318)


ACI 318/318R:2008
and Commentary (ACI 318R)
Building Code Requirements for Concrete Masonry Structures
ACI 530
and Commentary (ASCE 5) (TN4S 402)

ACI 35OR Environmental Engineering Concrete Structures

ACI 530.1 Specifications for Masonry Structures

ANSI A108.1 Installation of Ceramic Tile

ANSI A108.4 Ceramic Tile Installed with Organic Adhesives

ANSI A108.5 Ceramic Tile Installed with Dry-Set Portland Cement Mortar

Ceramic Tile Installed with Chemical Resistant, Water-


ANSI A108.6
Cleanable Tile-Setting and Grouting Epoxy
Providing Accessibility and Usability for Physically
ANSI A117.1
Handicapped People

ANSI A118.1 Standard Specification for Dry-Set Portland Cement Mortar

ANSI A135.4 Standards for Basic Hardboard

Standard Specification for Organic Adhesives for Installation of


ANSI A136.1
Ceramic Tile

10481-BCL-AKSX-AR-REP-0001_4_IFC_Architectural Design Basis(1) Page 16 of 75


2020
Ajaokuta Kaduna Kano Gas Pipeline Project

10481-BCL- AKSX- AR-REP-0001-4

ARCHI TECTUR AL DESIGN B ASI S

Code Document Title

ANSI A137.1 American National Standard Specification for Ceramic Tile

ANSI A250.2 Nomenclature for Insulated Steel Door Systems

Glazing Materials Used in Buildings, Safety Performance


ANSI Z97.1
Specifications and Methods of Test.
American National Standard Criteria for Evaluating Room
ANSI S12.2
Noise

ASCE 41088 Design of blast resistant buildings in petroleum facilities

ASHRAE Standard 90.1- Energy Standard for Buildings Except Low-Rise Residential
2010 Buildings (I-P Edition)

ASTM A48 Specification for Gray Iron Castings

Specification for Steel Bars, Carbon, Cold-Finished, Standard


ASTM A108
Quality
Specification for Steel, Sheet, Carbon, Cold-Rolled,
ASTM A366
Commercial Quality
Specification for General Requirements for Steel Sheet, Zinc-
ASTM A525
Coated (Galvanized) by the Hot-Dip Process
Specification for Steel Sheet, Zinc-Coated (Galvanized) by the
ASTM A526
Hot-Dip Process.
Specification for Steel, Carbon (0.15 Maximum Percent) Hot-
ASTM A569
Rolled Sheet and Strip Commercial Quality
Specification Steel, Sheet and Strip, High-Strength, Low-Alloy,
ASTM A607
Columbium or Vanadium, or both, Hot-Rolled and Cold-Rolled
Specification for Steel, Sheet and Strip, High-Strength, Low-
ASTM A715 Alloy, Hot-Rolled and Steel Sheet, Cold-Rolled, High Strength,
Low-Alloy, with Improved Formability
Specification for Aluminum and Aluminum-Alloy Sheet and
ASTM B209
Plate
Specification for Aluminum-Alloy Extruded Bars, Rods, Wire,
ASTM B221
Shapes and Tubes
Specification for Aluminum and Aluminum-Alloy Seamless
ASTM B241 Pipe
and Seamless Extruded Tube

ASTM C5 Specification for Quicklime for Structural Purposes

Specification for Inorganic Aggregates for Use in Gypsum


ASTM C35
Plaster

ASTM C36 Standard Specification for Gypsum Wallboard

Specification for ceramic glazed structural clay facing tile,


ASTM C126
facing brick, and solid masonry units

10481-BCL-AKSX-AR-REP-0001_4_IFC_Architectural Design Basis(1) Page 17 of 75


2020
Ajaokuta Kaduna Kano Gas Pipeline Project

10481-BCL- AKSX- AR-REP-0001-4

ARCHI TECTUR AL DESIGN B ASI S

Code Document Title

ASTM C144 Standard Specification for Aggregate for Masonry Mortar

ASTM C206 Standard Specification for Special Finishing Hydrated Lime

Standard Specification for Hydrated Lime for Masonry


ASTM C207
Purposes

ASTM C270 Standard Specification for Mortar for Unit Masonry

Standard Practice for Sampling and Acceptance of thermal


ASTM C390
Insulation Lots

ASTM C475 Joint Compound and Joint Tape for Finishing Gypsum Boar

ASTM C542 Specification for Lock-Strip Gaskets

Standard Specification for Rigid, Cellular Polystyrene Thermal


ASTM C578
Insulation
Standard Specification for Water-Resistant Gypsum Backing
ASTM C630
Board
Standard Specification for the Manufacture, Performance, and
ASTM C635 Testing of Metal Suspension Systems for Acoustical Tile and
Lay-in Panel Ceilings
Standard Practice for Installation of Metal Ceiling Suspension
ASTM C636
Systems for Acoustical Tile and Lay-in Panels
Specification for hollow brick (hollow masonry units
ASTM C652 made from clay or shale)

Standard Specification for Mineral - Fiber Blanket Thermal


ASTM C665 Insulation for Light Frame Construction and Manufactured
Housing
Installation of Steel Framing Members to Receive Screw-
ASTM C754
Attached Gypsum Board
Standard Practice for Selection of Water Vapor Retarders for
ASTM C755
Thermal Insulation

ASTM C840 Application and Finishing of Gypsum Board

ASTM C920 Specification for Elastomeric Joint Sealants

Standard Guide for Design of Built-Up Bituminous Membrane


ASTM C981
Waterproofing Systems for Building Decks
Specification for Steel Drill Screws for the Application of
ASTM C1002 Gypsum Board
or Metal Plaster Bases
Standard Test Method for Measuring the Steady- State
Thermal
ASTM C1199
Transmittance of Fenestration Systems Using Hot Box
Methods

10481-BCL-AKSX-AR-REP-0001_4_IFC_Architectural Design Basis(1) Page 18 of 75


2020
Ajaokuta Kaduna Kano Gas Pipeline Project

10481-BCL- AKSX- AR-REP-0001-4

ARCHI TECTUR AL DESIGN B ASI S

Code Document Title

ASTM D4259 Practice for Abrading Concrete

ASTM D4260 Practice for Acid Etching Concrete

ASTM D4586 Specification for Asphalt Roof Cement, Asbestos Free

Standard Test Method for Surface Burning Characteristics of


ASTM E84
Building Materials
Standard Test Methods for Water Vapor Transmission of
ASTM E96
Materials
Standard Practice for Determining the Acoustical Performance
ASTM E1425
of Exterior Windows and Doors
Standard Practice for Installation of Exterior Windows, Doors
ASTM E2112
and Skylights
Ceiling and Interior Systems Construction Association
CISCA
Handbook

CIBSE Guide A Environmental Design

EIA Environmental Impact Assessment

Environmental Guidelines and Standards for the Petroleum


EGASPIN 2002
Industry in Nigeria

NFPA 5000 Building Construction and Safety Code

NFPA 101-18 Life Safety Code

IBC: 2009 International Building Code

IECC International Energy Conservation Code

IFC International Fire Code

IMC International Mechanical Code

IPC International Plumbing Code

NBC, 2006 National Building Code of Federal Republic of Nigeria

5.3 Units of Measurement

All documents, calculations and drawings shall be carried out using International System
of Units (SI).

10481-BCL-AKSX-AR-REP-0001_4_IFC_Architectural Design Basis(1) Page 19 of 75


2020
Ajaokuta Kaduna Kano Gas Pipeline Project

10481-BCL- AKSX- AR-REP-0001-4

ARCHI TECTUR AL DESIGN B ASI S

5.4 Language

All documentation shall be in English (United States). Where documents (test


certificates, Vendor data etc.) are originally produced in a non-English language, an
English translation must be provided, and the English language version shall take
precedence.

5.5 Design Life

Facilities like Building(s) and Shelter(s) in Project shall have a design life of minimum 25
years.

6 BUILDING DESIGN

6.1 General Requirements

All buildings shall meet the requirements of National Building Code Federal Republic of
Nigeria and IBC. The detailed design of each building shall consider its location relative
to other buildings as well as the surrounding site environment and shall be designed to
maintain a consistent site aesthetic where practical.

The building shall be design and constructed to accommodate the staff and equipment
safely, economically and functionally.

Buildings shall be designed as one storey buildings. The building’s interior shall be
designed to meet the requirements defined by its function. The building shall be
designed as concrete foundation, concrete block walls, plastered, roof as concrete slab
with parapet, floor as concrete slab on the ground. Workshop & Warehouse Building
shall be designed as Steel structure.

Buildings shall be ventilated and air conditioned.

Electrical installations for the buildings shall consist of cabling, socket outlets, indoor
lighting, foundation earthing.

Potable water system shall be as per document no. G791-ILF-XXGE-GE-REP-0002


Rev.5 Basis of Design, section 17.5.4. and Plumbing Design Basis document no. 10481-
BCL-AKSX-PB-REP-0001.

Sewerage system shall be as per document no. G791-ILF-XXGE-GE-REP-0002 Rev.5


Basis of Design section 17.5.1 and Plumbing Design Basis document no. 10481-BCL-
AKSX-PB-REP-0001.

Buildings and facilities related to the security and safety of the Terminal Gas Station,
such as Entrance Security Check Building and the like, the final design shall be agreed
with Owner and relevant local authorities for final approval.

10481-BCL-AKSX-AR-REP-0001_4_IFC_Architectural Design Basis(1) Page 20 of 75


2020
Ajaokuta Kaduna Kano Gas Pipeline Project

10481-BCL- AKSX- AR-REP-0001-4

ARCHI TECTUR AL DESIGN B ASI S

Final setting out for each building shall be engineered and Locations of Mecca shown on
the north arrow of architectural drawings shall be confirmed for exact location from
Ministry of Endowments & Religious Affairs.

Plant buildings shall be located on the periphery of process facilities at a predominantly


upwind or crosswind location. Prevailing wind direction shall be based on the relevant
wind diagram for that location. Buildings shall not be located in electrically classified or
fire hazardous areas. Where this is unavoidable, appropriate safety measures including
fire resistance, building pressurization, gas detection, door controls and adjustment of
floor levels shall be considered and all measures / proposals in this respect agreed with
Owner.

As a minimum requirement, all buildings shall be provided with the following systems
where applicable: Electrical System, Interior & exterior lighting, Earthing and Lightning
protection, emergency and exit lighting, Heating Ventilation & Air-Conditioning, Electric
water heater for Kitchen, Prayer Room and Ablution, Plumbing, Drainage, Fire protection
& Detection Systems, Gas & Smoke Detection Systems, PAGA Systems, Emergency
Communication Systems, Communication Systems and Control Access Systems.

Building design shall address the safety of the occupants, possible hazards and provide
an evacuation plan to applicable codes and standards.

In addition to local jurisdiction and government requirements, occupied buildings shall be


designed in accordance with the International Building Code 2009.

Unoccupied buildings and occupied buildings with primarily industrial occupancies shall
be designed in accordance with NFPA 101 Life Safety Code 2006.

Refer to Appendix ‘2’ – “Building(s) and Shelter(S) Description and Basic Requirement”
and of this document contained herein for the basic requirements of each building.

Where required, all buildings and major equipment areas shall be accessible to allow
installation of large vessels or oversized heavy equipment or crane.

Owner shall be entitled to review all building designs for compliance with their
requirements and building designs shall be modified to comply with Owner requirements
accordingly.

The final design and engineering of each building shall be approved by Owner prior to
the start of building construction.

6.2 Scope

The Architectural scope of work considered in the project, includes as per Appendix 2:
“Building(s) and Shelter(s) Description and Basic requirement”.

6.2.1 Building Occupancy Classification

The building occupancy classification of a building or portion thereof shall be determined


by its intended use based on National Building Code of Federal Republic of Nigeria,
International Building Code and NFPA.

10481-BCL-AKSX-AR-REP-0001_4_IFC_Architectural Design Basis(1) Page 21 of 75


2020
Ajaokuta Kaduna Kano Gas Pipeline Project

10481-BCL- AKSX- AR-REP-0001-4

ARCHI TECTUR AL DESIGN B ASI S

Industrial occupancies shall be classified in accordance with NFPA 101 Life Safety Code
2006, Chapter 40 ‘Industrial Occupancies’.

Building occupancy classification shall be reviewed with Owner to confirm the building
design, building service loads and operation requirements of the buildings. Buildings
shall be designed in accordance to local accessibility standards where applicable, based
on each building’s use and occupancy.

6.3 Specific Building Design Requirements

6.3.1 General Building Philosophy

The general philosophy for the Building(s) and Shelter(s) in the Project shall consider the
purpose of each building, functionality and the location. Building(s) and Shelter(s) must
have road access, simplified design, regular structural modules, safe and away from
hazardous area.

6.3.2 Control Equipment Shelter

6.3.2.1 General Description

Control Equipment Shelter (Passive Cooling) shall suitably house telecommunications


equipment, RTU’s, marshalling equipment, power supply equipment and batteries.

The shelter shall be a welded steel or aluminium structure constructed to ensure water
and dust proofing of the casing. It shall include foundation fixing to withstand the
environmental conditions.

Foundations and construction of the shelter shall withstand wind forces up to 144 km/h
(40 m/s) as described in Basis of Design.

As the shelter shall be mounted at about 0.5 m above ground level an access stair made
of hot dip galvanized steel structure and steel grating shall be provided.

External vertical ladder (hot dip galvanised structure) shall be provided for access to
shelter roof.

Additional substructure for mounting of solar panels shall be provided on the roof. Solar
panels shall be additionally protected against vandalism.

Cooling for the Shelter shall be via Passive cooling. Passive cooling relies on simply the
swing between day and night ambient temperatures and by simply storing night free cold
energy for use during daytime to keep the shelter inside temperature.

For specific requirements refer to Document No. 10481-BCL-AKSX-AR-SPC-0002


“Control Equipment Shelter Specification”.

10481-BCL-AKSX-AR-REP-0001_4_IFC_Architectural Design Basis(1) Page 22 of 75


2020
Ajaokuta Kaduna Kano Gas Pipeline Project

10481-BCL- AKSX- AR-REP-0001-4

ARCHI TECTUR AL DESIGN B ASI S

6.4 Thermal Transmittance (U-Value)

Unless otherwise specified, the thermal transmittance, also known as U-value, to be


considered in this project is shown in below table.

For the detail u-value calculations refer to Document No. 10481-BCL-AKSX-HV-REP-


0001 “HVAC Design Basis and building specific HVAC Calculations Report.

Table 4 U-value of Building Envelope

U-Value
Item Description
to be Considered

1 Roof 1.725

2 Above-Grade Wall Construction 1.914

3 Slab-on-Grade 2.002

4 Insulated Steel Panel 0.495

5 Windows/Glass Curtain Wall


2.0
(Including frame) Ug-Value

6 Door 1.8

 Shading Coefficient (SC) 0.25

6.5 Fire Resistance

The fire resistance, including fire ratings for building components shall be reviewed and
specified in accordance with the National Building Code of Federal Republic of Nigeria,
International Building Code 2009, NFPA 101 Life Safety Code 2006, NFPA 5000 Building
Construction and Safety Code and IFC if applicable.

For specific requirements refer to Document No. 10481-BCL-AKSX-HS-PHL-0001 “ HSE


Philosophy”; 10481-BCL-AKSX-HS-PHL-0002 “Firefighting Philosophy”; 10481-BCL-
AKSX-HS-PHL-0003 “Fire Protection Philosophy”; 10481-BCL-AKSX-HS-PHL-0004 “Fire
& Gas Detection Philosophy”.

6.5.1 Passive Fire Protection (PF) Requirements for Buildings

For specific requirements refer to Document No. 10481-BCL-AKSX-ST-SPC-0005


“Specification for Passive Fire Fighting”.

10481-BCL-AKSX-AR-REP-0001_4_IFC_Architectural Design Basis(1) Page 23 of 75


2020
Ajaokuta Kaduna Kano Gas Pipeline Project

10481-BCL- AKSX- AR-REP-0001-4

ARCHI TECTUR AL DESIGN B ASI S

6.5.2 Fire Walls

Fire walls located within the fire zones designed to protect object or building shall have
minimum fire resistance of 1 hour.

Height and dimensions of the wall shall be defined individually with respect of the height
of the surroundings objects or equipment and due to fire & safety requirements.

Fire Walls shall be made of concrete.

6.5.3 Means of Egress

Buildings shall be provided with means of egress in accordance with the National
Building Code of Federal Republic of Nigeria, International Building Code 2009, based
on use and occupancy and in accordance with the egress requirements of NFPA 101
Life Safety Code 2006.

Plant facilities shall be provided with acceptable access and egress for personnel,
materials, and equipment by using access ways, ladders, roads, stairways, stiles, and
walking / working surfaces (decks, floors, grade, platforms, ramps, runways, and
walkways).
6.5.4 Escape Routes

All areas of the facilities shall be provided with two separate and diverse escape routes,
which shall be readily accessible and unobstructed. Escape routes shall be arranged
such that from each unit, escape is possible in two diverse directions. Escape routes
shall be as direct as possible and shall not be obstructed.

At least one main escape route shall remain passable for long enough to allow personnel
to reach a safe area without incurring injury.

Doors that open on to the route shall not reduce the width of the escape route. Doors
from enclosed areas shall open outwards, in the direction of escape. Emergency doors
from buildings shall be equipped with anti-panic bars. Minimum door dimensions shall be
2m height and 0.8m width. No exit locking facilities shall be provided for doors along
escape routes.

Sizing of escape routes, especially stairways and staircase shall take into consideration
transit of stretchers and persons wearing breathing apparatus.

Escape routes shall be clear of any vents from hazardous areas.

All escape routes shall be of non-slip finish and marked with arrows directing personnel
to a safe area. They shall be adequately illuminated. Direction signs shall be strategically
positioned along escape routes and shall lead personnel to the muster area or
emergency exits.

Windsocks shall be provided at suitable locations in the plant to assist safe escape of
personnel in case of a flammable gas release.

10481-BCL-AKSX-AR-REP-0001_4_IFC_Architectural Design Basis(1) Page 24 of 75


2020
Ajaokuta Kaduna Kano Gas Pipeline Project

10481-BCL- AKSX- AR-REP-0001-4

ARCHI TECTUR AL DESIGN B ASI S

6.6 Foundation, Structure and Type of Construction

The foundation and structure of a building shall be designed in accordance with


document no. 10481-BCL-AKSX-ST-REP-0001 Civil & Structural Design Basis.
6.6.1 Types and Methods of Construction

The buildings shall be designed with the materials and methods of construction
appropriate for its occupancy and shall be built in accordance with the requirements of
the governing building codes.

Unless noted otherwise, type of constructions applicable to Buildings shall be designed


as follows:
Table 5 Types and Methods of Construction

Building Building Structural


Type of Construction
Name Type System

Masonry structure, the external load-bearing


walls shall consist of external render, concrete
block 240mm, internal plaster. The internal
walls shall consist of Internal plaster, concrete
block 120mm or 240mm, internal plaster. The
internal walls made of concrete block shall be
Entrance
designed to ensure adequate load – carrying
Security Masonry
A capacity of the structure, acoustic insulation
Check Structure
and required fire resistance when they perform
Building
the role of fire division. Roof shall be covered
by Foil/Geotextile Layer + Gravel & Roofing
Felt (3 layers) on cast-in-situ flat reinforced
concrete slab. Flooring shall be in reinforced
slab on the ground covered with ceramic tiles &
PVC lining.
Masonry structure, the external load-bearing
walls shall consist of external render, concrete
block 240mm, internal plaster. The internal
walls shall consist of Internal plaster, concrete
block 120mm or 240mm, internal plaster. The
internal walls made of concrete block shall be
Accommod
designed to ensure adequate load – carrying
ation Masonry
A capacity of the structure, acoustic insulation
Building for Structure
and required fire resistance when they perform
Supervisors
the role of fire division. Roof shall be covered
by Foil/Geotextile Layer + Gravel & Roofing
Felt (3 layers) on cast-in-situ flat reinforced
concrete slab. Flooring shall be in reinforced
slab on the ground covered with ceramic tiles &
PVC lining.
Masonry structure, the external load-bearing
Accommod A Masonry walls shall consist of external render, concrete

10481-BCL-AKSX-AR-REP-0001_4_IFC_Architectural Design Basis(1) Page 25 of 75


2020
Ajaokuta Kaduna Kano Gas Pipeline Project

10481-BCL- AKSX- AR-REP-0001-4

ARCHI TECTUR AL DESIGN B ASI S

Building Building Structural


Type of Construction
Name Type System

ation Structure block 240mm, internal plaster. The internal


Building for walls shall consist of Internal plaster, concrete
Personnel block 120mm or 240mm, internal plaster. The
internal walls made of concrete block shall be
designed to ensure adequate load – carrying
capacity of the structure, acoustic insulation
and required fire resistance when they perform
the role of fire division. Roof shall be covered
by Foil/Geotextile Layer + Gravel & Roofing
Felt (3 layers) on cast-in-situ flat reinforced
concrete slab. Flooring shall be in reinforced
slab on the ground covered with ceramic tiles &
PVC lining.
Masonry structure, the external load-bearing
walls shall consist of external render, concrete
block 240mm, internal plaster. The internal
walls shall consist of Internal plaster, concrete
block 120mm or 240mm, internal plaster. The
internal walls made of concrete block shall be
Administrati
designed to ensure adequate load – carrying
on and Masonry
A capacity of the structure, acoustic insulation
Security Structure
and required fire resistance when they perform
Building
the role of fire division. Roof shall be covered
by Foil/Geotextile Layer + Gravel & Roofing
Felt (3 layers) on cast-in-situ flat reinforced
concrete slab. Flooring shall be in reinforced
slab on the ground covered with ceramic tiles,
raised floor & PVC lining.
Masonry structure, the external load-bearing
walls shall consist of external render, concrete
block 240mm, internal plaster. The internal
walls shall consist of Internal plaster, concrete
block 120mm or 240mm, internal plaster. The
internal walls made of concrete block shall be
Electrical designed to ensure adequate load – carrying
Masonry
and Control A capacity of the structure, acoustic insulation
Structure
Building and required fire resistance when they perform
the role of fire division. Roof shall be covered
by Foil/Geotextile Layer + Gravel & Roofing
Felt (3 layers) on cast-in-situ flat reinforced
concrete slab. Flooring shall be in reinforced
slab on the ground covered with ceramic tiles,
raised floor & PVC lining.
Masonry structure, the external load-bearing
Prayer Masonry walls shall consist of external render, concrete
A
House Structure block 240mm, internal plaster. The internal
walls shall consist of Internal plaster, concrete

10481-BCL-AKSX-AR-REP-0001_4_IFC_Architectural Design Basis(1) Page 26 of 75


2020
Ajaokuta Kaduna Kano Gas Pipeline Project

10481-BCL- AKSX- AR-REP-0001-4

ARCHI TECTUR AL DESIGN B ASI S

Building Building Structural


Type of Construction
Name Type System

block 120mm or 240mm, internal plaster. The


internal walls made of concrete block shall be
designed to ensure adequate load – carrying
capacity of the structure, acoustic insulation
and required fire resistance when they perform
the role of fire division. Roof shall be covered
by Foil/Geotextile Layer + Gravel & Roofing
Felt (3 layers) on cast-in-situ flat reinforced
concrete slab. Flooring shall be in reinforced
slab on the ground covered with ceramic tiles
and carpet.
Prefabricated Steel Cabin pre-painted &
insulated by Vendor. The cabin should include
Prefabrica
building components & services such as doors
Guard Post E ted Steel
& windows, lighting fixtures & fittings, plumbing
Cabin
fixtures & fittings, roof rain water arrangement,
F&G system, decoration material.
Steel Framed Structure with Sandwich panels.
Other part such as office, toilet, etc. shall be in
masonry structure similar to other buildings.
Workshop Roofing shall be Sandwich Panels on slope
Steel
and B roof; Foil/Geotextile Layer + Gravel & Roofing
Structure
Warehouse felt (3 layers) on cast-in-situ flat reinforced
concrete slab. Flooring shall be in reinforced
slab on the ground covered with concrete &
ceramic tiles
Fire
Light Steel framed structure with pre-painted profiled
Fighting
C Steel metal composite or single metal cladding panel
Pumping
Structure walls and roof.
Shelter

Diesel and
2 Gas
Genset & Light Steel framed structure with pre-painted profiled
Compresse C Steel metal composite or single metal cladding panel
d Air Structure walls and roof.
System
Shelter

Closed
Light Steel framed structure with pre-painted profiled
Drain
C Steel metal composite or single metal cladding panel
Vessel
Structure walls and roof.
Shed

Light Steel framed structure with pre-painted profiled


Fuel Gas C
Steel metal composite or single metal cladding panel

10481-BCL-AKSX-AR-REP-0001_4_IFC_Architectural Design Basis(1) Page 27 of 75


2020
Ajaokuta Kaduna Kano Gas Pipeline Project

10481-BCL- AKSX- AR-REP-0001-4

ARCHI TECTUR AL DESIGN B ASI S

Building Building Structural


Type of Construction
Name Type System

Shed Structure walls and roof.

Light Steel framed structure with pre-painted profiled


Block Valve
C Steel metal composite or single metal cladding panel
Pit Shed
Structure walls and roof.

Light
Car Parking
D Steel Steel framed structure with fabric roof.
Shed
Structure

Control Passive
Passive Cooling shelter (by vendor) with Solar
Equipment F Cooling
Panels
Shelter Shelter

6.6.2 Blast Resistance Requirements

Required mitigation measure shall be depended on FERA report. Refer to Fire Protection
Philosophy 10481-BCL-AKSX-HS-PHL-0003.

6.7 Submittals to the PMC / Owner

6.7.1 PMC / Owner Reviews

Unless otherwise specified, the following documents shall be provided to PMC / Owner
for review during detailed design activities:

 Architectural Building Layout / General Arrangement Plans showing space


utilization
 Architectural Building Plans, Elevations & Sections, Enlarged Plans
 Architectural Details (including wall, connections, flashings, insulation, etc.)

 Building Specifications
 All Building Schedules, including but not limited to:
o Door & window schedules

o Finishes schedules
 Product data sheets (if applicable)
 Material Details
 Furniture, fixture & equipment layout
 Architectural detailed plans, detailed elevations, and detailed wall sections

10481-BCL-AKSX-AR-REP-0001_4_IFC_Architectural Design Basis(1) Page 28 of 75


2020
Ajaokuta Kaduna Kano Gas Pipeline Project

10481-BCL- AKSX- AR-REP-0001-4

ARCHI TECTUR AL DESIGN B ASI S

 Architectural life safety drawings (if applicable)


 Reflected ceiling plans and details
 Tiling plans and details
 Ironmongery schedules
 Carpentry and Joinery drawings and schedules

7 BUILDING OCCUPANCY LEVEL


The design Occupancy level in manned buildings shall be in accordance to IBC-2009
Table 1004.1.1 and to the building listed in the drawings below:
 KADUNA TGS Entrance Security Check Building;
 KANO TGS Entrance Security Check Building;
 KADUNA TGS Accommodation for Supervisor;
 KANO TGS Accommodation for Supervisor;
 KADUNA TGS Accommodation for Personnel;
 KANO TGS Accommodation for Personnel;

 KADUNA TGS Administration & Security Building;


 KANO TGS Administration & Security Building;
 KADUNA TGS Electrical & Control Building;

 KANO TGS Electrical & Control Building;


 KADUNA TGS Prayer House;
 KANO TGS Prayer House;

 KADUNA TGS Workshop & Warehouse;


 KANO TGS Workshop & Warehouse;
 KADUNA TGS Guard Post;

 KANO TGS Guard Post.

7.1 General Requirements

The Project Manned Building designs are based on the Building Occupancy level
established in FEED and will be developed during detailed engineering.

10481-BCL-AKSX-AR-REP-0001_4_IFC_Architectural Design Basis(1) Page 29 of 75


2020
Ajaokuta Kaduna Kano Gas Pipeline Project

10481-BCL- AKSX- AR-REP-0001-4

ARCHI TECTUR AL DESIGN B ASI S

Expected maximum personnel on both Terminal Gas Stations at any one point of time
(All Phases): 100 people of which (consider for 20% female staff on site, peak 60% of
total visitors).

Below Table 6 is based on the following category:


 Minimum Personnel in Buildings at Any One Point of Time: based on
drawings layout and 10481-Manning Concept_Rev4.

 Expected Maximum Number of Personnel & Visitors of Buildings: based on


drawings layout and 10481-Manning Concept_Rev4 + peak 60% visitors.
 Maximum Number of Occupants Allowed: based on IBC & NFPA occupant
calculation per Gross Floor Area.
Table 6 TGS Area Wise Occupancy

Minimum Expected Maximum Maximum


Station Name

Personnel in Number of Number of


Description Buildings at Any Personnel & Visitors Occupants
One Point of of Buildings Allowed
Time

3 people
Guards at ESB 2 3
(3 male, 0 female)
1 people
Guard at GP 1 1
(1 male, 0 female)
Administration,
Engineers, 45 people
28 107
KANO TGS

Technical & Staffs (36 male, 9 female)


at ASB, ECB & WW
50 people
TOTAL 31 111
(40 male, 10 female)
3 people
Guards at ESB 2 3
(3 male, 0 female)
1 people
Guard at GP 1 1
(1 male, 0 female)

Administration,
KADUNA TGS

Engineers, 45 people
28 107
Technical & Staffs (36 male, 9 female)
at ASB, ECB & WW

50 people
TOTAL 31 111
(40 male, 10 female)

10481-BCL-AKSX-AR-REP-0001_4_IFC_Architectural Design Basis(1) Page 30 of 75


2020
Ajaokuta Kaduna Kano Gas Pipeline Project

10481-BCL- AKSX- AR-REP-0001-4

ARCHI TECTUR AL DESIGN B AS I S

Table 7 Building Wise Occupancy

Maximum Minimum
Station

Number of People in Building


Name

Building Name Remarks


Occupants at Any One Point
Allowed of Time

At the entrance
Entrance Security
3 2 of Terminal Gas
Check Building
Station.

Accommodation At the
Building for 3 1 accommodation
Supervisor area.

Accommodation At the
Building for 3 2 accommodation
Personnel area.

Administration At the
and Security 30 8 Administration
Building area.

Electrical and
47 4 At the plant area.
Control Building
At the
Prayer House 112 38* accommodation
area.
At the plant area
KANO TGS

Guard Post 1 1
entrance.
Workshop and
30 16 At the plant area.
Warehouse
At the entrance
Entrance Security
3 2 of Terminal Gas
Check Building
Station.
Accommodation At the
Building for 3 1 accommodation
KADUNA TGS

Supervisor area.

Accommodation At the
Building for 3 2 accommodation
Personnel area.

10481-BCL-AKSX-AR-REP-0001_4_IFC_Architectural Design Basis(1) Page 31 of 75


2020
Ajaokuta Kaduna Kano Gas Pipeline Project

10481-BCL- AKSX- AR-REP-0001-4

ARCHI TECTUR AL DESIGN B ASI S

Maximum Minimum
Station

Number of People in Building


Name

Building Name Remarks


Occupants at Any One Point
Allowed of Time

Administration At the
and Security 30 8 Administration
Building area.

Electrical and
47 4 At the plant area.
Control Building

At the
Prayer House 112 38* accommodation
area.
At the plant area
Guard Post 1 1
entrance.

Workshop and
30 16 At the plant area.
Warehouse

*Transient

7.2 Entrance Security Check Building

As this is a security related building and it shall always be manned. It is not expected to
have any female staff in this building. This facility is to provide permit in the Station. The
Occupancy breakdown is as follows:
Table 8 Area/Activity Wise Occupancy

Area/ Activity Staff Position Occupancy

Entrance Security Check Building Security Officer 2

7.3 Accommodation Building for Supervisors

The Accommodation Building for Supervisors have a total of 4 typical buildings (including
3 spares for future accommodation) in each Terminal Gas Station. The Occupancy
breakdown is shown below:
Table 9 Area/Activity Wise Occupancy

Area/ Activity Staff Position Occupancy

Accommodation Building for Supervisor Supervisor 1

10481-BCL-AKSX-AR-REP-0001_4_IFC_Architectural Design Basis(1) Page 32 of 75


2020
Ajaokuta Kaduna Kano Gas Pipeline Project

10481-BCL- AKSX- AR-REP-0001-4

ARCHI TECTUR AL DESIGN B ASI S

Area/ Activity Staff Position Occupancy

TOTAL (incl. future accommodation) 4

7.4 Accommodation Building for Personnel

The Accommodation Building for Personnel have a total of 13 typical buildings (including
11 spares for future accommodation) in each Terminal Gas Station. The Occupancy
breakdown is shown below:
Table 10 Area/Activity Wise Occupancy

Area/ Activity Staff Position Occupancy

Accommodation Building for Personnel Support Staff 2

TOTAL (incl. future accommodation) 26

Note: There will be two Accommodation Buildings for Personnel which housing 2 people
each.

7.5 Administration and Security Building

The Occupancy breakdown is shown below:


Table 11 Area/Activity Wise Occupancy

Area/ Activity Staff Position Occupancy

Office Area Site Supervisor 1

Deputy Site Supervisor 1

Assistant/Secretary 1

HSE Officer 1

Security Officer 2

Cleaning Staff 1

Guest 2*

Kitchen Dining table 4*

First Aid Room Nurse 1

10481-BCL-AKSX-AR-REP-0001_4_IFC_Architectural Design Basis(1) Page 33 of 75


2020
Ajaokuta Kaduna Kano Gas Pipeline Project

10481-BCL- AKSX- AR-REP-0001-4

ARCHI TECTUR AL DESIGN B ASI S

Area/ Activity Staff Position Occupancy

Patient 1*

Minimum people in the building


Minimum Expected Occupancy 8 Min.
at any one point

Maximum Building Occupancy


Maximum Building Occupancy Level 30 Max.
(to allow visitors)

*Transient

7.6 Electrical and Control Building

The Occupancy breakdown is shown below:


Table 12 Area/Activity Wise Occupancy

Area/ Activity Staff Position Occupancy

Control Room Operators 2

Operator-Security System
1
Workstations

Engineering Room Maintenance Engineer 1

Kitchen Dining Table 4*

Minimum people in the building


Minimum Expected Occupancy 4 Min.
at any one point

Maximum Building Occupancy


Maximum Building Occupancy Level 47 Max.
(to allow visitors and operators)

*Transient

7.7 Prayer House

The Occupancy breakdown is shown below (considered 30% for female):


Table 13 Area/Activity Wise Occupancy

Area/ Activity Staff Position Occupancy

Prayer Hall Male 27*

10481-BCL-AKSX-AR-REP-0001_4_IFC_Architectural Design Basis(1) Page 34 of 75


2020
Ajaokuta Kaduna Kano Gas Pipeline Project

10481-BCL- AKSX- AR-REP-0001-4

ARCHI TECTUR AL DESIGN B ASI S

Area/ Activity Staff Position Occupancy

Female 11*

TOTAL 38*

*Transient

7.8 Guard Post

Guard Post is to monitor vehicles and pedestrian access in and out of the Terminal Gas
Station. It is not expected to have any female staff in this building. The Occupancy
breakdown is as follows:
Table 14 Area/Activity Wise Occupancy

Area/ Activity Staff Position Occupancy

Guard Post Guard 1

7.9 Workshop and Warehouse

The Occupancy breakdown is shown below:


Table 15 Area/Activity Wise Occupancy

Area/ Activity Staff Position Occupancy

Office Facility Manager 1

Instrumentation Engineer/
Warehouse & Workshop 1
Technician

Mechanical Engineer/
1
Technician

Electrical Engineer/ Technician 1

Pipeline Maintenance Staff 12

Minimum people in the building


Minimum Expected Occupancy 16 Min.
at any one point

Maximum Building Occupancy


Maximum Building Occupancy Level 30 Max.
(to allow visitors and operators)

10481-BCL-AKSX-AR-REP-0001_4_IFC_Architectural Design Basis(1) Page 35 of 75


2020
Ajaokuta Kaduna Kano Gas Pipeline Project

10481-BCL- AKSX- AR-REP-0001-4

ARCHI TECTUR AL DESIGN B ASI S

8 BUILDING COMPONENTS AND MATERIALS

8.1 General requirement

Unless stated otherwise or applicable, governing jurisdictions specify more stringent


requirements, products for buildings shall be designed and specified in accordance with
this Basis of Design.

Competent architectural design resource shall be employed for the Project to prepare
and agree external and internal materials, fixtures, fittings, finishes samples and color
schemes with Owner.

All finishes specified in this document do not include colors or identified finishes
manufacturers. Final selection of colors and finishes shall be submitted by
CONTRACTOR for Owner’s approval.
8.1.1 Quality

Notwithstanding the requirements relating to Owner approved vendor lists, materials for
buildings generally shall be obtained from Owner’s’ approved manufacturers and
suppliers. All materials shall be new, free of defects and shall conform to the
requirements of applicable codes and standards.

Consideration shall be applied to the uniformity and commonality of specification for all
finishes, textures, colors, components, features, and materials and for the high quality of
design, construction and workmanship required.

All building materials and components specified shall be resistant to potential local pest
infestation.
8.1.2 Fire Resistance and Combustibility

Fire resistance of building material / separating walls and associated structure shall be
maintained to the required Project standards, including the National Building Code of
Federal Republic of Nigeria, International Building Code 2009 and NFPA.

Any necessary approvals shall be obtained from applicable fire authorities. The use of
readily combustible materials within buildings and structures is not acceptable. All
internal lining and structural surfaces shall be material of limited combustibility such that
they adequately resist the spread of flame over their surfaces. Buildings and structures
shall be constructed in accordance with NFPA 5000 code.

For specific requirements refer to Document No. 10481-BCL-AKSX-HS-PHL-0001 “ HSE


Philosophy”; 10481-BCL-AKSX-HS-PHL-0002 “Firefighting Philosophy”; 10481-BCL-
AKSX-HS-PHL-0003 “Fire Protection Philosophy”; 10481-BCL-AKSX-HS-PHL-0004 “Fire
& Gas Detection Philosophy”; 10481-BCL-AKSX-ST-SPC-0005 “Specification for
Passive Fire Fighting”.

10481-BCL-AKSX-AR-REP-0001_4_IFC_Architectural Design Basis(1) Page 36 of 75


2020
Ajaokuta Kaduna Kano Gas Pipeline Project

10481-BCL- AKSX- AR-REP-0001-4

ARCHI TECTUR AL DESIGN B ASI S

8.1.3 Acoustic Performance

If sound sources are located indoors or outdoors adjacent to buildings, soundproofing


shall be considered when selecting materials for the wall, roof, ceiling, internal partitions
or other parts and if necessary, specialist acoustic materials shall be adopted. The
building design shall give due consideration to the avoidance of prolonged exposure to
high and / or low frequency noise.

Below are acceptable sound levels for various room types:


Table 16 Acceptable Sound Level for Various Types

Item Room Noise Criteria (dBA*)

1 Bedrooms, Religious Prayer Rooms 25-35

2 Living Rooms, Conference Rooms 25-35

3 Offices, Private Works Rooms 35-40

4 Corridor, Open Offices, Bathrooms, Toilets,


45-50
Lobbies

5 Kitchen, Common Spaces, Dining Halls,


45-55
Workshops

6 Equipment Room, Battery Room, HVAC Room 55-70

*dBA means Decibel A.

ANSI S12.2: American National Standard Criteria for Evaluating Room Noise serves as
the basis on the values above.
8.1.4 Intruder Resistance

Requirements for intruder resistant construction to building types as shown in Appendix 2


‘Building(s) and Shelter(s) Description and Basic Requirement’ of this document shall be
agreed with Owner. ‘Intruder resistant’ is a higher-level construction where the complete
material and components of the building are designed to withstand a determined attempt
to force entry into the building (this is in addition to door and window locks).

8.2 Masonry

For specific requirements refer to Document No. 10481-BCL-AKSX-ST-SPC-0004


“Specification for Masonry Works”.

10481-BCL-AKSX-AR-REP-0001_4_IFC_Architectural Design Basis(1) Page 37 of 75


2020
Ajaokuta Kaduna Kano Gas Pipeline Project

10481-BCL- AKSX- AR-REP-0001-4

ARCHI TECTUR AL DESIGN B ASI S

8.2.1 External CMU (Concrete Masonry Unit) Wall

Table 17 External CMU Wall Layers

Description Dimension Unit

a External Render 25 mm

b Concrete Block 240 mm

c Internal Plaster 15 mm

8.2.2 Internal CMU (Concrete Masonry Unit) Wall

Table 18 Internal CMU Wall Layers

Description Dimension Unit

a Internal Plaster 15 mm

b Concrete Block 120, 240 mm

c Internal Plaster 15 mm

8.3 Steel Structure

8.3.1 Sandwich Panels

A sandwich structure is a fabricated material that consist of two relatively thin, stiff
facings sheets separated by a thicker, lower density core material or structure.
One or both metal faces may be flat, lightly profiled or fully profiled to Owner’s approval.
The formulae and the design rules are applicable for the range of face thickness of 0.5 to
2.0 mm and for panel depths of 50 to 300 mm. Outside these ranges, additional
precautions are required.

The core material may be a chemically formulated foam (e.g polyurethane,


polyisocyanurate, polystyrene, phenolic resin), mineral wool or other material having
similar mechanical and insulating characteristics. It must have sufficient strength and
stiffness to contribute to the composite action and to enable the panel to adequately
carry the design loads. The core itself and its bond with the face material must have
adequate durability with regard to both short- and long-term effects including creep and
ageing.

10481-BCL-AKSX-AR-REP-0001_4_IFC_Architectural Design Basis(1) Page 38 of 75


2020
Ajaokuta Kaduna Kano Gas Pipeline Project

10481-BCL- AKSX- AR-REP-0001-4

ARCHI TECTUR AL DESIGN B ASI S

The sandwich panel system must include suitable fastening to secure the composite
cladding units to the supporting framework in a sound and weathertight manner without
crushing the core material.

Sandwich Panel shall be used for the Workshop and Warehouse building and as
indicated in the Architectural drawings and specifications.

8.3.2 Exterior Single Skin Panels

Exterior single skin pre-painted profiled steel panels shall be used on the roofs of
shelters / sheds to provide a protective outer shell on the following. Steel sheeting shall
be hot-dip galvanized.

 Fire Fighting Pumping Shelter

 Diesel and 2 Gas Genset & Compressed Air System Shelter

 Closed Drain Vessel Shed

 Fuel Gas Shed

8.3.3 Fabric Sunshades

Parking and Walkway sunshades shall be provided to car parking areas as shown in
architectural drawings to Owner’s approval. They shall be of lightweight PVC coated
Poly-tetrafluoroethylene (PTFE) fabric top supported on a lightweight painted steel
structure offering over 90% UVA/B protection and 75% shade to people and vehicles.
The sunshade design and selected fabric shall be insured & adequate to withstand the
design wind velocities, including cyclones, as defined in the local meteorological and
seismic design data. The sunshade structure shall be robust to withstand the harsh local
weather conditions. In addition, sunshades shall be protected against impact from tall
vehicles.

8.4 Roof Covering and Flashings

8.4.1 Materials

The materials used for roof coverings and flashings shall be manufactured in accordance
with current standards and they use-by date should be affixed to packaging / container.
Steel sheeting shall be hot-dip galvanized.

 Asphalt-saturated felt on building board consists of asphalt coated board and


mineral finish. It shall comply with:
o it shall have even edges and be free from any damage and creases,

o felt surface shall be free from any visible asphalt stains,

10481-BCL-AKSX-AR-REP-0001_4_IFC_Architectural Design Basis(1) Page 39 of 75


2020
Ajaokuta Kaduna Kano Gas Pipeline Project

10481-BCL- AKSX- AR-REP-0001-4

ARCHI TECTUR AL DESIGN B ASI S

o when unrolling the roll, any damage resulting from felt sticking together
shall be unacceptable,
o 3 instances of slight perpendicular tearing of the felt edge up to 30 mm
long per each 10 m of felt length are acceptable,
o after tearing off and delamination, felt colour shall be uniform dark -
brown;
 Underlayment thermoweldable membrane - Asphalt-saturated felt based on
polyester nonwoven fabric;
 Top thermoweldable membrane - asphalt-saturated felt for the top coat
based on polyester nonwoven fabric. The top surface with coarse-grained
finish, the bottom surface protected with plastic film;
 Bitumen and polymer bitumen adhesive - Hot-applied adhesive with fillers:
o softening point: 60-80°C,

o ignition point: 200°C,


o water content ≤ 0,5%,
o runoff – shall not flow off the layer binding two membrane layers
inclined at 45° in the temperature of 50°C for 5 hours,
o bonding capacity – shall not separate when tearing off membrane strips
glued together and to concrete in the temperature of 18°C;
 Bitumen primer;
 Refined asphalt putty;
 Solvent-free epoxy putty;
 Flat galvanized steel sheet – two-side hot-dip galvanized steel sheets;
 Coated steel sheet;
 Titanium zinc sheet;
 Prefabricated rain gutters and downpipes made of galvanized/coated/titanium
zinc sheet;
 Gutter and downpipe clips.
Insulation layers shall be made in accordance with following standards: ASTM E96,
ASTM C390, ASTM C578, ASTM C665, ASTM C755, ASTM C981.

The roof will be built with attics, water drainage by means of outdoor gutters and PVC
downpipes.

10481-BCL-AKSX-AR-REP-0001_4_IFC_Architectural Design Basis(1) Page 40 of 75


2020
Ajaokuta Kaduna Kano Gas Pipeline Project

10481-BCL- AKSX- AR-REP-0001-4

ARCHI TECTUR AL DESIGN B ASI S

The flat roof for buildings will be accessible via outdoor ladder permanently fastened on
the object structure in accordance of relevant regulations in the scope of occupational
health and safety.

8.5 Insulation Works

8.5.1 Materials

8.5.1.1 Product for surface waterproofing

For surface waterproofing the following putties are used:

 of asphalt and asphalt-polymer,


 polymer,
 cement,
 cement-polymer,

 bituminous-mineral.

8.5.1.2 Laminated waterproofing products

Waterproofing laminates used at the site include:

 asphalt, asphalt-polymer and polymer putties reinforced with fabric or fibre


not subject to biological corrosion,
 cement and cement-polymer putties reinforced with fabric or fiber,
 bituminous-mineral putties reinforced with fabric or fibre.

8.5.1.3 Products for moisture proofing and waterproofing from rolled materials

For insulation of underground parts and building footings, the following rolled materials

are used:

 asphalt felts on cardboard and glass fiber tissue, and thermally welded or
adhesive felts.

8.5.1.4 Products for sealing / filling joints, crevices, transitions

 Sealing asphalt putty,


 Solvent-free epoxy putty,

 Joint-tapes for water stops.

10481-BCL-AKSX-AR-REP-0001_4_IFC_Architectural Design Basis(1) Page 41 of 75


2020
Ajaokuta Kaduna Kano Gas Pipeline Project

10481-BCL- AKSX- AR-REP-0001-4

ARCHI TECTUR AL DESIGN B ASI S

8.6 Carpentry and Joinery Items

8.6.1 General Requirements

Timber / wood shall not generally be used for construction work, unless noted or
specified otherwise. If timber is used, it shall be pre-treated to protect against termite
attack.

8.6.2 Quality of Timber

All timber to be used shall be highly quality, locally sourced hardwood, free from all sap,
shakes, large, lose or dead knots, waney edge, borers and other serious defects. All
timbers shall be properly seasoned.

8.6.3 Plywood

Plywood shall be of highest quality available. Thickness of the plywood shall be


according to standard dimensions, as shown on the drawings. All plywood shall be
exterior grade, water resistant bonded type WBP (Weather and Boil Proof).

8.6.4 Fabrication

All works necessary for correct jointing of carpentry and joinery works, such as mortising,
miters, tenoning, grooving, matching, tonguing, housing, rebating, etc. shall be carried
out by the CONTRACTOR in a proper, workmanlike manner and to the best standards of
local workmanship.

8.7 Doors and Windows

8.7.1 Materials

All materials for the installation of the doors and windows should conform to the
requirements included in the appropriate Local and International Standards, and be
obtained from a manufacturer of repute.

Continuity shall be maintained between elements in the doors and the weather resistant
barrier that provides weather protection, air leakage control and resistance to heat flow
and vapour diffusion (acc. to ASTM E2112).

Doors to technological and security areas shall be included in the access control system.

Doors dimension:

 door dimensions result from the need to meet fire safety and technological
requirements,
 door types according to operation, acoustic or fire safety requirements,

10481-BCL-AKSX-AR-REP-0001_4_IFC_Architectural Design Basis(1) Page 42 of 75


2020
Ajaokuta Kaduna Kano Gas Pipeline Project

10481-BCL- AKSX- AR-REP-0001-4

ARCHI TECTUR AL DESIGN B ASI S

 door height – 2100 mm, for people access.


 door height – 2300 mm, for equipment access.
 the width of the doors on the escape routes leading from the stair wells to the
outside or to another zone, shall be not less than the width of the stair well
flight,
 for double leaf doors – at least one leaf width shall be 900 mm,
 door opening direction – inwards (except the rooms subject to different
requirements).
8.7.2 Steel Doors and Frames

Doors shall be seamless-composite construction, except as otherwise specified, and


shall be installed complete with frames, hardware and other accessories.

Doors and frames shall be cold rolled steel with a stretcher level degree of flatness,
smooth, clean surface, hot-dip galvanized. Steel sheet metal shall conform to ASTM
A366 for cold rolled steel and ASTM A525 for hot-dip galvanized.

Fire rated doors shall have a mineral wool fibreboard core.

Minimum thickness of external steel sheet doors shall be 2 mm.

Doors and frames shall be powder-coated.

8.7.3 Wood Doors and Frames

Face panels – two or more wood veneer plies. Side edge veneer bands to match face
veneers species. Hardwood core construction.

For fire rated door use only pressed welded steel frames.

8.7.4 Aluminium Doors and Windows

Selected system of windows hardware shall be based upon aluminium systems proved in
climatic conditions in Nigeria or on other systems meeting similar technical requirements
in the scope of the resistance to wind pressure, impermeability to rain water, air
infiltration, sound attenuation and heat transfer coefficient.

Minimum aluminium doors and windows thickness – 3 mm.

Hardware shall be furnished and installed by the door manufacturer. Hardware finish
shall match finish of doors and frames.

Doors shall be design for glazing with clear laminated safety glass.

Doors and frames shall be powder-coated.

10481-BCL-AKSX-AR-REP-0001_4_IFC_Architectural Design Basis(1) Page 43 of 75


2020
Ajaokuta Kaduna Kano Gas Pipeline Project

10481-BCL- AKSX- AR-REP-0001-4

ARCHI TECTUR AL DESIGN B ASI S

8.7.5 Glass and Glazing

Doors and windows glazing shall be installed by the manufacturer.

All other glass shall be set as required by the glazing facilities provided and location
requirements relative to glass embedment.

All glass shall be protected against breakage during the construction period and all
broken or cracked glass shall be replaced at the time of completion of the work, at no
cost to the Owner.

All glass shall be cleaned just before final inspection. The cleaning of reflective glass
shall conform to the manufacturer’s instructions.

8.7.6 Upward Acting Sectional Doors

Doors shall have steel flush panel type with foamed in place insulation cores. Doors shall
have steel front and back panels.

Doors shall be installed complete with overhead tracks, springs and hardware.

Operation shall by electric motor operator.

Steel sheet shall by roll formed commercial quality sheets, hot-dip galvanized in
accordance with ASTM A525, ASTM A526 phosphate coated, pre-painted with primer
and baked-on polyester topcoat.

Insulation core shall by polyurethane, foamed in place.

Hinges shall by manufactured of hot dipped galvanized steel.

Rollers shall be full floating ball bearing in case hardened steel races, mounted to fit the
slope of track.

8.7.7 Blast Resistant Doors and Frames

The doors, frames and fixtures for all external door openings and the internal door
openings of air locks in external blast-resistant walls shall be designed to be able to
resist an external explosion pressure acting inward and outward. Latch and hinge
mechanisms shall be capable of withstanding the door rebound loading.

Doors shall have panic bar, automatic door closers, non-sparking latch bolts, threshold,
stainless steel lever and pull handles.

8.7.8 Blast Resistant Windows

Windows shall be sealed with extruded vinyl weather – stripping with consideration for
blowing sand.

10481-BCL-AKSX-AR-REP-0001_4_IFC_Architectural Design Basis(1) Page 44 of 75


2020
Ajaokuta Kaduna Kano Gas Pipeline Project

10481-BCL- AKSX- AR-REP-0001-4

ARCHI TECTUR AL DESIGN B ASI S

Safety glass for exterior windows and exterior door lights shall by laminated, tinted and
coordinated with HVAC design for proper shading coefficient. For interior windows and
interior door lights glass shall by laminated plate safety glass, clear.

8.8 Building Fabric Sundries

8.8.1 Ironmongery

The ironmongery shall be of a heavy-duty type, functional, attractive, and durable.

All hinged doors shall have profiled cylinder mortise lockset with SCP lever handles
(except those marked "Emergency", which shall be provided with a suitable panic latch,
key operated from the outside).

All external & fire-escape doors shall be provided with automatic door closers.

All external doors shall be provided with locks. Where keys are used a key cabinet shall
be provided in an appropriate location in each respective building containing a key for
each lock in that building. A key cabinet for each building shall also be provided in the
control building each containing a set of keys for each building.

Emergency access doors shall be provided with panic bars & bolts and a pad external
LOCKING attachment. The panic bolts shall provide 2-point locking.

External doors to the technical and store rooms shall be provided with a sand trap
ventilation grill.

All ironmongery shall be obtained from well-known and approved manufacturers.


Samples shall be submitted for Owner’s approval.

8.9 Furniture, Fixtures & Equipment

8.9.1 General Requirements

Loose furniture, all built-in fixtures, equipment and fittings for buildings shall be supplied
within Project scope of work. Owner shall be consulted for any operation and user
requirements where necessary and agree with Owner the final specifications and product
selections before placing the purchase order.

8.9.2 Fixtures

All built-in fixtures and furnishings including worktops and cabinets, vanity counters to
WC’s and counter tops shall be fabricated from approved materials to designs to Owner

10481-BCL-AKSX-AR-REP-0001_4_IFC_Architectural Design Basis(1) Page 45 of 75


2020
Ajaokuta Kaduna Kano Gas Pipeline Project

10481-BCL- AKSX- AR-REP-0001-4

ARCHI TECTUR AL DESIGN B ASI S

requirements. The selected materials shall be classified as suitable for the purpose and
shall be finished in accordance with good trade practice and methods.

All surface finishes shall be smooth and free from protrusions, crevices and corners in
order to avoid personal injury and damage to clothing. Minimize number of joints and
allow for continuous trim(s) between angles or ends of runs wherever possible.

Timber used in the fabrication of other furnishings shall be properly seasoned and
conditioned by the manufacturer so that moisture content is between the limits required
for local climatic conditions. All metal parts shall be corrosion resistant or shall have a
corrosion resistant finish.

Metal lockers and associated benching shall be provided to locker rooms, type subject to
Owner’s approval.

8.9.3 Fittings

Handrails and guardrails in ramps and steps (if applicable) shall be designed such that
open guardrails shall have intermediate rails or an ornamental pattern of guardrails so
that a sphere 300mm in diameter cannot pass through, as per IBC requirements.

8.9.4 General Signage

The use / purpose of all internal rooms shall be identified on a label / nameplate attached
to all doors accessing each room. All exterior doors are to be marked with the building
number, name of the building, and door number. The lettering shall be white and a
minimum of 50mm high. Access doors into rooms containing hazardous materials shall
be appropriately labelled describing the hazard and / or listing hazardous materials
present and any special protective equipment required before entering.

All exterior and interior signage, including safety and emergency escape signage to
building(s) and shelter(s) shall be submitted to Owner for approval.

Safety signs shall be provided throughout the facilities. Emergency signs shall be
provided to inform personnel of escape routes, emergency exits, fire-fighting and rescue
equipment locations.

Enclosures protected by gaseous agent or water mist shall have at their entrance
warning signs that inform personnel of imminent gaseous agent or water mist discharge
as well as instruction to inhibit the system before entering the area.

Hazard warning notices with reference to the admission of unauthorized persons and
vehicles, naked lights, smoking, traffic hazards, speed limits, vehicular head room, toxic
risk, etc., shall be prominently displayed.

10481-BCL-AKSX-AR-REP-0001_4_IFC_Architectural Design Basis(1) Page 46 of 75


2020
Ajaokuta Kaduna Kano Gas Pipeline Project

10481-BCL- AKSX- AR-REP-0001-4

ARCHI TECTUR AL DESIGN B ASI S

8.10 Sanitary Ware

The sanitary drawing symbols as shown in the architectural drawings shall be used to
quantify the sanitary fixtures requirements and sanitary fixture and fitting schedules,
drawings and specifications shall be produced for Owner’s approval.

All plumbing installation and fittings shall be in accordance with IPC.

All sanitary fitments of the same kind shall be one uniform make and type supplied by the
same approved manufacturer.

8.10.1 Water Closet / Locker / Shower

All WC and locker / showers’ fittings shall be white glazed vitreous ceramic Pedestal-
type. WC’s shall be close-coupled flush tank. All flush boxes shall consume no more than
three litres of water.

All WC, wash areas, kitchens, battery rooms, mechanical plant rooms, janitor’s rooms,
service areas and locker areas shall be provided with chromium plated, stainless steel or
other approved floor drains / gratings.

All units shall be complete with manufacturer’s fittings, accessories and fasteners. All
toilet fittings shall be provided with an adjacent water tap and hose. Wash hand basins
shall be provided with central pillar mixing taps and all necessary accessories. Water
supply control fittings to ablution areas shall be provided with automatic shut-off timer
valves.

 Stainless steel accessories for each WC shall include:

o Paper towel dispensers and receptacles


o Toilet tissue dispensers
o Stainless steel framed mirrors
o Soap dispensers
o Shelves
o Coat hooks
o Hot air hand dryer

8.10.2 Janitor Room

Janitor’s room/area shall be provided with stainless steel sinks and hose connections.

10481-BCL-AKSX-AR-REP-0001_4_IFC_Architectural Design Basis(1) Page 47 of 75


2020
Ajaokuta Kaduna Kano Gas Pipeline Project

10481-BCL- AKSX- AR-REP-0001-4

ARCHI TECTUR AL DESIGN B ASI S

8.10.3 Safety Showers and Eye Wash

Safety showers and eyebaths /bottles shall be located within buildings and other process
areas where there is a hazard of chemical spillage or splashes. They shall be self-
contained and supplied with potable water. The piping shall be protected to prevent
temperature extremes due to solar radiation and routed to prevent stagnation to avoid
bacterial growth.

The maximum travel distance from the hazard to a safety shower or eyewash station
shall be 15m; also, they shall be located as close as practicable to escape routes from
hazards identified.

Safety showers and eyebaths /bottles shall be provided in accordance with ANSI Z358.1.

8.10.4 Restrooms

Restrooms shall be provided with electric hand dryer, soap dispensers, paper towel
dispensers, waste receptacle, mirrors, and a shelf for personal items. Restrooms without
toilet compartments shall be provided with additional accessories as described above for
toilet compartments.

Materials shall be commercial grade, heavy-duty, non-permeable, corrosion and stain


resistant.

Anchors shall be concealed and shall be made of nonferrous metal or stainless steel.

8.11 Metal Works

8.11.1 Steel Ladder

Steel ladder, external access platforms and landings shall be designed as per IBC and
NFPA 101.

Steel ladder shall be constructed of galvanized steel.

Provide a cage, well, or ladder safety system where it is shown on architectural drawings
or where the length of climb is 6m or more above or below ground level, or above or
below a floor or roof with access/egress from ground level, floor, or roof.

Safety guards shall be provided along open-sided walking surfaces, including equipment
platforms, stairs, ramps and landings that are located more than 762mm measured
vertically to the floor or grade below at any point within 914mm horizontally to the edge of
the open side, except vehicle service pits or on the loading side of loading platforms.

10481-BCL-AKSX-AR-REP-0001_4_IFC_Architectural Design Basis(1) Page 48 of 75


2020
Ajaokuta Kaduna Kano Gas Pipeline Project

10481-BCL- AKSX- AR-REP-0001-4

ARCHI TECTUR AL DESIGN B ASI S

Where walking surfaces could be exposed to a slippery fluid, such as water or oil, it shall
have a non-skid surface. Steel plate with diamond or other patterns may be provided for
such walking surfaces but does not over-ride the requirement for anti-skid paint.

8.11.2 Steel Louvers

Steel louvers shall be colour coated with chemical, sand abrasion and pollution resistant
paint, to match cladding with drainable blades to minimize water and sand penetration
while maintaining a high free area.

Louvers shall be designed with a frame that includes a jamb gutter, a recessed drip lip at
the head, and an extended water stop on the back of the sill.

Louvers shall be in accordance with AMCA 511 and shall bear the AMCA-certified rating
seal for both air performance and water penetration.

Wherever applicable, the sunshade provisions shall be provided to all windows of the
building. The sun shades shall be of aluminium horizontal louver frame, placed above the
full length of the windows with a minimum projection of 600 mm.

At the office areas there will be internal vertical blinds with the same length of the window
height, to be used manually.

8.12 Hard and Soft Landscaping

8.12.1 General Requirements

This shall include, but not limited to, all soft landscaping, all paving / footpath
arrangements on building perimeter, plinth protection around buildings, planting,
irrigation, shaded car parking, shaded walkways.

For road paving refer to Document Number 10481-BCL-AKSX-CI-SPC-0002


“Specification for Road and Paving”.

Perimeter paving shall be installed at footpaths and approaches to buildings in materials


to be approved by Owner. Interlocking pavers shall not be used in areas with gypsum or
expansive clay soil, unless noted otherwise.

Local faunas and plants shall be used where possible, with appropriate irrigation and
landscaping strategy to be agreed with Owner. Special care shall be given to
landscaping areas where there is considerable amount of gypsum or expansive clay soil.

10481-BCL-AKSX-AR-REP-0001_4_IFC_Architectural Design Basis(1) Page 49 of 75


2020
Ajaokuta Kaduna Kano Gas Pipeline Project

10481-BCL- AKSX- AR-REP-0001-4

ARCHI TECTUR AL DESIGN B ASI S

The paving system shall utilize locally available products, providing these comply with
the specified requirements and are of a type and size suitable for pedestrian traffic.
Pavers shall be bedded on cement/sand mortar of the type of bond recommended by the
paving manufacturer and to achieve an aesthetically attractive finish. Mix of mortar shall
be suitable for light duty paving generally except to areas where heavy equipment may
need to be moved. Technical requirement of paving shall be in line with project
specifications.

Please note that hard and soft landscaping in this section is for guidelines only, which
shall be as per the Project approved scope of works.

9 SURFACE FINISHES

All finishes requirements shall be based on the room finishes schedule as indicated in
the architectural drawings and as described below.

9.1 Suspended Ceilings

9.1.1 Materials

Acoustical pane ceiling shall be made of mineral fiber, textured and with factory applied
washable vinyl paint. Size of panels: 600mm x 600mm.

Substructure – of bearing galvanized steel profiles, invisible. The suspension system


shall be design to support ceiling, lighting fixtures, grilles, diffusers and other required
items without sagging.

Habitable rooms shall have a ceiling height of not less than 2.4m unless otherwise
specified. Offices shall have a clear height of 3.0 meter as specified in the Architecture
Drawings.

Suspended ceilings shall be humidity, mold, vermin resistant. Suspended ceilings shall
be executed in accordance with ASTM C635 and ASTM C636.

9.2 Stud Wall with Plasterboard Covering

9.2.1 Material

For execution of stud walls with plasterboard covering, the following materials are used:

 circumferential profiles of galvanized cold-bent profiles fixed to walls and


ceilings using connectors appropriate for the subgrade,

10481-BCL-AKSX-AR-REP-0001_4_IFC_Architectural Design Basis(1) Page 50 of 75


2020
Ajaokuta Kaduna Kano Gas Pipeline Project

10481-BCL- AKSX- AR-REP-0001-4

ARCHI TECTUR AL DESIGN B ASI S

 vertical profiles (poles), fixed to circumferential profiles, together forming the


frame of the wall,
 plasterboard, fixed to the frame of the wall in one or two layers. Depending
on design requirements, boards are made in regular, fire-resistant,
impregnated and impregnated fire-resistant version,
 insulation material filling the space inside the wall, serving as acoustic
insulation or for meeting fire-resistance requirements,
 steam insulation (optional), fixed on the frame under the covering,
 screws for metal to connect profiles and fixing boards to the structure,
 self-threading screws for fixing regular profiles and boards to door-frame
profiles,
 protective corner panels of aluminium, perforated to secure wall edges,
 connective tapes (of paper, non-woven interlining, glass fibre), reinforcing
joint filling between covering boards,
 mortars and putties for filling joints between the boards,
 thin-layered putties for smoothing wall surfaces in the case of increased
quality requirements,
 insulation (acoustic) tapes to separate wall structure from neighbouring
building elements (walls, floors, ceilings),
 connectors (dowels, rawlplugs, power-actuated fasteners) for fixing
circumferential profiles to the neighbouring building elements,
 strengthening, traverses, boards, ducts (also for installations), for
strengthening wall structures for fixing (suspension) of heavier elements and
equipment assembly,

9.3 Flooring and Covering Works

9.3.1 General Requirements:

Refer to the Schedule of Finishes for respective building drawings. All specified floor
finishes and colours shall be submitted to Owner for approval.

 Solid vinyl floor tiles shall be in accordance with ASTM F 1700.


 Vinyl composition floor tile shall be in accordance with ASTM F 1066.

 Rubber floor tile shall be in accordance with ASTM F 1344.


 Vinyl sheet floor covering shall be in accordance with ASTM F 1303.

10481-BCL-AKSX-AR-REP-0001_4_IFC_Architectural Design Basis(1) Page 51 of 75


2020
Ajaokuta Kaduna Kano Gas Pipeline Project

10481-BCL- AKSX- AR-REP-0001-4

ARCHI TECTUR AL DESIGN B ASI S

 Rubber sheet floor covering shall be in accordance with ASTM F 1860.


 Marble stone tile shall be in accordance with ASTM C503.
 Linoleum floor tile shall be in accordance with ASTM F 2195.
 Ceramic floor tile shall be in accordance with ANSI A 137.1.
 Resilient wall base shall be rubber or vinyl as indicated and shall be in
accordance with ASTM F 1861.
 Access floor systems shall be in accordance with Section 9.3.2.
The transitions between different types of floor coverings should not result in trip
hazards. Metal threshold plates shall be used appropriately.

Medium-range directional carpet roll (pattern to show Mecca Direction) for Prayer House
shall considered and provided for Owner’s approval.

9.3.2 Raised Access Floor

Raised access floor, flush with surrounding floor levels, shall be provided to control,
instrumentation, telecom, electrical equipment and computer rooms where indicated on
architectural drawings. The flooring systems shall be proprietary, pre-fabricated and
approved and shall comply with all relevant IBC / NFPA requirements for loading,
electrical conductivity / standards and physical performance. The concrete sub-floor shall
be epoxy paint finished to prevent dust formation. Allow for 800mm raised access floor
(Top of base floor to Finished Floor Level) in rooms or as shown in the Architectural
drawings.

The 600 X 600mm square fully removable floor panels shall be formed from heavy duty
composite materials with acoustic properties to prevent impact noise, noise transference
and tile rocking. They shall be finished with a factory applied, hardwearing, anti-static
vinyl surface and with an aluminium base. Perimeter make up panels shall be used
where required by room shape to detailed design requirements and Owner’s approval.

Floor panels shall be supported by removable stringers and braced, adjustable and
lockable steel pedestals, mechanically fixed to the concrete floor base. The pedestal
support and floor tile system shall be separated from supports for the electrical and
instrumentation equipment supports. Where required provide ventilation floor panels to
ventilate heat load.

Panels and support systems shall be in accordance with CISCA-Recommended Test


Procedures for Access Floors.

Floor panels shall have a Class ‘A’ flame-spread rating when tested without floor
covering in accordance with ASTM E 84. Floor panel covering shall be as indicated in
this specification

10481-BCL-AKSX-AR-REP-0001_4_IFC_Architectural Design Basis(1) Page 52 of 75


2020
Ajaokuta Kaduna Kano Gas Pipeline Project

10481-BCL- AKSX- AR-REP-0001-4

ARCHI TECTU R AL DESIGN B ASI S

The supporting system shall be as follows:

 A commercial heavy duty, bolted grid system.


 Free from vibrations squeaks.
 Designed to support the equipment that will be located on the access flooring
system.

 Resistant to seismic loads.


The access floor system shall support the minimum loads as per IBC or local statutory
requirements. The entire flooring system shall be electrically grounded.

9.3.3 Ceramic Floor Tiles

Ceramic, non-slip ceramic, acid-resisting ceramic tiles and matching coved base tiles
shall be plain, square-edged, flat tiles. All floor tiles shall comply with relevant ANSI
Standards. Ceramic tiles’ design, size, and colour shall be submitted to Owner for
approval.

Ceramic floor tile shall have a minimum 10mm thickness. Ceramic tiles size shall be as
per Architectural drawings.

9.3.4 Resilient Flooring

Resilient flooring and accessories shall be obtained from a single approved manufacturer
including all primers, adhesives and sealant. Flooring shall be vinyl sheet and tile with
filled vinyl plastic wear-layer and fibrous backing. The material shall be non-combustible.
Compatible coved wall base units shall be provided with preformed or moulded corner
sections.

All fitting materials shall be approved and recommended proprietary products. Installation
shall comply with the manufacturer’s recommendations. Each product shall be provided
from a single manufacturer as approved by Owner.

PVC tiles:

 Tiles of polyvinyl chloride of min. 2 mm thickness, not easily ignitable,


meeting the requirements of the design documentation, referring to technical-
utility properties (format, dielectric / anti-electrostatic properties, anti-skid
properties, abrasibility, etc.),
 Glue for PVC tiles, meeting the requirement of their manufacturer and design
documentation, also in the aspect of electric conductivity properties.

Reeled PVC floor covering:

10481-BCL-AKSX-AR-REP-0001_4_IFC_Architectural Design Basis(1) Page 53 of 75


2020
Ajaokuta Kaduna Kano Gas Pipeline Project

10481-BCL- AKSX- AR-REP-0001-4

ARCHI TECTUR AL DESIGN B ASI S

 PVC floor covering, not easily ignitable, meeting the requirements of the
design documentation, referring to technical-utility properties (format,
dielectric / anti-electrostatic properties, anti-skid properties, abrasibility, etc.),
 glue for PVC flooring, meeting the requirements of its manufacturer and
design documentation, also in the aspect of electric conductivity properties.
Roughcast, levelling putties, screeds, impregnating agents:

 Materials for preparing the base under the floor covering (depending on its
type and condition, type of glue and floor covering), for levelling,
strengthening, egalisation, priming, increased adhesion.
Ancillary materials, accessories:

 baseboards – systemic, of floor covering material,


 expansion joints, doorstep boards, pass boards, masking boars, etc.,

 copper tapes - in the case of design documentation requirements for anti-


electrostatic (conductive) properties of the floor covering.
9.3.5 Carpet

Where specified, commercial grade carpet shall be installed, type to Owner agreement,
complete with all necessary accessories, underlay, grippers, edgings and trims.
Installation shall be carried out only when the base surface has a relative humidity above
75%, unless otherwise complying with the recommendations of the carpet manufacturer.
Any adhesives used in the installation shall be as specified by the carpet manufacturer.
Colours and textures shall be selected from the manufacturer’s standard range and
subject to Owner approval.

9.3.6 Concrete Floor

Chemically resistant floor hardener shall be applied to inhibit dusting and to improve the
hardness and chemical resistance of concrete floors.

For impregnation of floor surface, solutions of acrylic and epoxy resins, silicate and
silane are used.

For filling expansion joints, flexible putties (masses) are used on the basis of
polysulphides (Thiokol sealants), polyurethanes, polyurethane-epoxy mixes or silicon.

Materials for subgrade repair, cleaning agents (solvents appropriate for the impregnate),
etc., have been determined in specifications of MSDS charts.

10481-BCL-AKSX-AR-REP-0001_4_IFC_Architectural Design Basis(1) Page 54 of 75


2020
Ajaokuta Kaduna Kano Gas Pipeline Project

10481-BCL- AKSX- AR-REP-0001-4

ARCHI TECTUR AL DESIGN B ASI S

9.3.7 Sub-floors

Sub-floors shall be sealed with epoxy resin and chemical resistant coating to prevent
dusting. Drains shall be provided in the sub-floor to prevent flooding, unless Owner has
approved the use of dry chemical fire extinguishers with no potential source of moisture
or water ingress.

9.4 Natural and Artificial Stone

Locally sourced natural or artificial stone shall be considered in the following areas for
Owner’s approval.

 Thresholds under doors at the transition of two different floor finishes;


 Thresholds located in main entrance door of wet areas (toilet and showers).

 Thresholds and window sills shall have a minimal thickness of 25 mm.

9.5 Wall Finishes

9.5.1 Ceramic Wall Tiles

Ceramic and chemical resistant ceramic wall tiles and accessories shall comply with
relevant ANSI Standards and requirements and shall be square edged, plain and flat.

Ceramic wall tiles shall have a minimum thickness of 6mm. Sizes shall be as per
Architectural drawings.

All fitting materials shall be approved and recommended proprietary products. Installation
shall comply with the manufacturer’s recommendations. Each product shall be provided
from a single manufacturer as approved by Owner. Colours and textures shall be
selected from the manufacturer’s standard ranges and shall be agreed with Owner.

9.5.2 Wall Paint Finish

Paint finish to external render, steelwork and concrete and to internal plaster, concrete,
steelwork and gypsum boarding shall only be carried out when factory-finishing or
installer-finishing has not been included.

The extent of electrolyte resistant, anti-static and slip-resistant paint coverage shall be
determined in Battery room according to the type of battery and battery bank
arrangement.

10481-BCL-AKSX-AR-REP-0001_4_IFC_Architectural Design Basis(1) Page 55 of 75


2020
Ajaokuta Kaduna Kano Gas Pipeline Project

10481-BCL- AKSX- AR-REP-0001-4

ARCHI TECTUR AL DESIGN B ASI S

9.6 Plastering Works

Concrete Masonry Unit (CMU) walls as specified in the Architectural drawings shall be
finished with a water tight sand/cement render for external and plaster for internal with a
thickness of 25 mm for external walls and 15 mm for internal walls with a minimum of 2
coats. The plastered walls shall be finished with a wall paint as described in the Painting
section of this document. Where indicated, any fair faced walls suitable for direct paint
finish shall comply with BS 6150, laid in gauged mortar and finished with a neat flush
joint.

9.6.1 Materials

All materials and products used for execution of plastering works must correspond to the
requirements contained in reference documents (standards, technical approvals).

Approved waterproofing shall be added to all mortar used for external plastering.

Mortar for plastering shall be mixed per batch in powered mixing drums on site, to control
the mixing proportions as per relevant standards, and handled by buckets.

All external corners of plaster work above finished floor level shall be finished with
heavily galvanized angle beads.

Galvanized steel stop beads shall be used wherever necessary for a proper termination
of the plaster coat.

Plaster coats with a thickness greater than 18 mm shall be provided with a light mesh of
galvanized steel wires 0.8 mm diameter with a 10 mm square grid, or alternatively,
expanded metal lathing.

A 150 mm wide strip of such mesh shall be used in plaster at junctions between block
walls and concrete elements such as beams, columns or walls.

9.6.1.1 Cement-lime construction mortars

 brand and composition of mortar must correspond to the requirements of


ASTM C1328/C1328M-12,
 mortar preparation for plastering work must be executed mechanically,
 mortar must be prepared in such volume to be used possibly quickly, namely
within approx. 3 hours,

 for plastering mortar, use river sand or mined sand,


 for cement-lime mortar, use Portland cement,

10481-BCL-AKSX-AR-REP-0001_4_IFC_Architectural Design Basis(1) Page 56 of 75


2020
Ajaokuta Kaduna Kano Gas Pipeline Project

10481-BCL- AKSX- AR-REP-0001-4

ARCHI TECTUR AL DESIGN B ASI S

 for cement-lime mortars, use hydrated or slaked lime in the form of lime cake
of calcined lime, which should form a uniform and monochromatic mass.
Volumetric composition of mortars must be selected experimentally,
depending on the required mortar brand, as well as types of cement and
lime.

9.6.1.2 Gypsum putty

For performance of gypsum putty on concrete subgrade, cement and cement-lime


plasters, use gypsum putty acc. to requirements of ASTM C28/C28M-00(2010).

9.6.1.3 Water

Without laboratory tests, exclusively drinkable water from the mains can be used.

It is prohibited to use effluent, sewerage, bog waters, or waters containing organic fats,
oils and mud.

9.6.1.4 Priming agents

Use priming agents for priming mineral subgrade, to reduce their absorbability, surface
hardening and increased adhesion.

9.6.1.5 Sand

Sands for construction mortars, in particular:

 it must not contain organic additives,


 It must have fractions of various sizes – fine-grained sand 0.25-0.5 mm,
medium grained sand 0.5-1.0 mm, thick-grained sand – 1.0-2.0 mm.
For bottom plaster layers, use thick-grained sand of variation 1, for top layers – medium
grained sand of variation 2, for finishing – fine-grained, passing through sieve of 0.5 mm.

9.7 Painting Works

All building external painting shall be specified for the following conditions:

 Chemical exposure condition shall be defined as areas where surfaces are


exposed to chemical Vapour or liquid spillage that have detrimental effect on
the surface materials.

10481-BCL-AKSX-AR-REP-0001_4_IFC_Architectural Design Basis(1) Page 57 of 75


2020
Ajaokuta Kaduna Kano Gas Pipeline Project

10481-BCL- AKSX- AR-REP-0001-4

ARCHI TECTUR AL DESIGN B ASI S

 Severe exposure condition shall be defined as areas where surfaces are


usually moist or are exposed to condensation, sporadic water immersion or
relative humidity greater than 85%.
 Paint finishes shall be sand abrasion resistant to local conditions and tested
in accordance with ASTM D968.
All internal painting shall be specified for the following conditions:

 Mild exposure condition, for example in air-conditioned areas.


 Severe exposure, for example in ventilated areas without air conditioning.
 Chemical exposure, for example in laboratory buildings and chemical
storage.
Surface preparation, priming, finish coats, storing, mixing and application shall be in
accordance with manufacturer’s instructions.

All internal and external exposed surfaces shall be painted, except where the schedules
indicate that a surface or material is not to be painted or is to remain natural. If the
schedules do not specifically mention an item or surface, then it shall be painted the
same as similar adjacent materials or surfaces.

All exposed piping shall be painted (moving parts excluded).

The best quality grade of the various types of paint, coating and finish materials shall
provide from approved manufacturers. Materials not exhibiting the manufacturer’s
standard identification as a best-grade product shall not be accepted.

All paint and coating materials shall be applied in strict accordance with the
manufacturer’s instructions.

Safety colours for, for example, piping and equipment, shall be in accordance with OSHA
29 CFR 1910 regulations for marking physical hazards.

9.7.1 Materials

9.7.1.1 Types of materials for indoor painting

For painting surfaces indoors, the following could be used:

 dispersion paints,
 oil paints, phthalic paints, modified phthalic paints and copolymerized styrene
phthalic paints,
 oil-resin, phthalic, modified phthalic and copolymerized phthalic enamels,

10481-BCL-AKSX-AR-REP-0001_4_IFC_Architectural Design Basis(1) Page 58 of 75


2020
Ajaokuta Kaduna Kano Gas Pipeline Project

10481-BCL- AKSX- AR-REP-0001-4

ARCHI TECTUR AL DESIGN B ASI S

 styrene enamels,
 paints on bonds: solvent resin other than oil and phthalic, water-soluble resin,
mineral with or without modifying additives in the form of liquid or dry mixes
for mixing with water, one- or several-component water-soluble mineral-
organic, which must meet the requirements of technical approvals,
 water-soluble varnishes,
 varnishes on solvent resin bonds other than oil and phthalic, which must
meet the requirements of technical approvals,
 primers, which must meet the requirements of technical approvals.

9.7.1.2 Types of materials for outdoor painting

For painting surfaces outdoors, the following can be used:

 dispersion paints,

 on plasters – emulsion paints on bonds of polyvinyl acetate, butadiene-


styrene latex, and other, according to principles specified in standards,
 oil paints, phthalic paints, modified phthalic paints and copolymerized styrene
phthalic paints corresponding to the requirements of standard PN-C-
81901:2002,
 oil-resin, phthalic, modified phthalic and copolymerized styrene phthalic
enamels,
 paints on solvent resin bonds other than oil and phthalic, mineral with
modifying additives in the form of liquid or dry mixes for mixing with water,
one- or several component water-soluble mineral-organic paints,
 water-soluble paints and enamels on resin bond, meeting the requirements of
technical approvals,
 paints on mineral bonds with modifying additives in liquid form, meeting the
requirements of technical approvals,
 primers, which must meet the requirements of technical approvals.
Ancillary materials for performing floors and cladding:

 solvents, including: water, turpentine, spirit for varnishes and enamels,


denatured spirit, other prefabricated solvents,
 agents for degreasing, washing and cleaning subgrade,

 agents for elimination of runs and efflorescence,

10481-BCL-AKSX-AR-REP-0001_4_IFC_Architectural Design Basis(1) Page 59 of 75


2020
Ajaokuta Kaduna Kano Gas Pipeline Project

10481-BCL- AKSX- AR-REP-0001-4

ARCHI TECTUR AL DESIGN B ASI S

 putties for subgrade repair,


 painting tapes and foils for securing neighbouring surfaces / elements /
equipment (cladding, window / door frames, etc.).
All such materials must feature technical properties specified by the manufacturer or
corresponding to the requirements of relevant standards or technical approvals.

9.7.1.3 Water

Without laboratory tests, exclusively drinkable water from the mains can be used. It is
prohibited to use effluent, sewerage, bog waters, or waters containing organic fats, oils
and mud.

9.8 FINISHING SCHEDULE

The finishing schedule for walls, skirting, ceiling & floor and detailed information refer to
project architectural drawings. Below are for guidance and reference only.

Indoor and outdoor proposed finishing of buildings are shown in table 19.
Table 19 Indoor and Outdoor Proposed Finishing of Buildings, Shelters/Sheds
Item Description Finishing Location Remark

Painting Masonry building


External
1
wall surface Color steel
Steel structure building
sandwich panel

Stone/concrete
Entrance of buildings
slab step
2 Steps
Cement mortar Buildings as specified in the
step architectural drawings

Fine concrete Buildings as specified in the


3 Apron
apron architectural drawings

Ceramic floor tile


(Anti-slip and
visually
appealing in the
Office, vestibule, hall, corridor,
Entrance and
4 Flooring communication area, technical
Communication
room, storage, and prayer room
Area of the
Administration &
Security
Building)

10481-BCL-AKSX-AR-REP-0001_4_IFC_Architectural Design Basis(1) Page 60 of 75


2020
Ajaokuta Kaduna Kano Gas Pipeline Project

10481-BCL- AKSX- AR-REP-0001-4

ARCHI TECTUR AL DESIGN B ASI S

Item Description Finishing Location Remark

resting room, guard room,


bedroom, corridor, living room,
PVC lining
office, storage, meeting room,
first aid room, and security room.

Ceramic anti-slip
Toilets, showers, bathrooms,
floor tile (with
ablution, lockers
waterproof layer)

Anti-static raised control rooms, equipment room,


flooring engineering room, telecom room

Epoxy paint with


concrete
trenches covered
with steel
checkered plate
Electrical room
& removable
concrete with
epoxy paint
similar to floor
finish.

Acid resistant,
Anti-slip & oil
proof ceramic
Battery room
floor & wall tile
up to 2 meter
from FFL to wall.

Firefighting pumping shelter,


Trowel-Finished Diesel and 2 gas genset and
Concrete compressed shelter, Fuel gas
shed

Trowel-Finished Car parking shelter, closed drain


Concrete vessel shed

Ceramic tile
Ceramic tile room
skirting

Cement skirting Cement floor room


5 Skirting
PVC skirting PVC lining room

Metal skirting Anti-static raised flooring room

Internal wall Ceramic tile


6 Toilet & wet areas
surface surface

10481-BCL-AKSX-AR-REP-0001_4_IFC_Architectural Design Basis(1) Page 61 of 75


2020
Ajaokuta Kaduna Kano Gas Pipeline Project

10481-BCL- AKSX- AR-REP-0001-4

ARCHI TECTUR AL DESIGN B ASI S

Item Description Finishing Location Remark

Painting surface Masonry building

Suspended Control room, cabinet room


ceiling with
aluminum square
Toilet & wet areas
board

Damp proofing
7 Ceiling
plasterboard with Office room, meeting room, rest
light gauge steel room, corridor, hall
joist

Emulsion
Rooms without false ceiling
painting

Window Stone/concrete Buildings as specified in the


8
board slab architectural drawings

Steel framed
slope roof with Workshop & Warehouse (steel
color steel structure building)
sandwich panel

Flat roof with


9 Roof
water proofing Masonry building
layer

Single layer
Steel structural open shelter,
profiled steel
shed
sheet

10 BUILDING UTILITIES AND SERVICES

10.1 General Requirements

For the Electrical and Control Building, all utilities shall be hidden from view to the
greatest extent possible while still permitting ease of maintenance.

Openings provided in walls, ceilings, roof, floor, foundations for services into or out of the
building shall be sealed after installation of the service to prevent ingress of moisture,
dust, debris and vermin.

10481-BCL-AKSX-AR-REP-0001_4_IFC_Architectural Design Basis(1) Page 62 of 75


2020
Ajaokuta Kaduna Kano Gas Pipeline Project

10481-BCL- AKSX- AR-REP-0001-4

ARCHI TECTUR AL DESIGN B ASI S

10.2 Utility Systems

For building’s plumbing requirements, refer to Plumbing Design Basis document no.
10481-BCL-AKSX-PB-REP-0001.

10.3 HVAC System

For building’s HVAC requirements, refer to HVAC Design Basis document no. 10481-
BCL-AKSX-HV-REP-0001.

The HVAC systems at all Terminal Gas Stations (TGS) shall be designed to maintain
and control the temperature, relative humidity, air filtration and ventilation for normal
operation of the personnel, process instrumentation and equipment in buildings and
containers.

10.4 Electrical

For building’s electrical requirements, refer to Electrical Design Philosophy document no.
10481-BCL-AKSX-EL-PHL-0002.

10.5 Fire Protection and Safety

Fire protection and safety for buildings, including automatic fire sprinkler systems, F&G
detection System, Smoke Detection System, Portable fire extinguishers and clean agent
fire extinguisher systems, Hydrant, Hose Reels, etc., shall be in accordance with the
documents; HSE Philosophy document no. 10481-BCL-AKSX-HS-PHL-0001; Fire
Fighting Philosophy document no. 10481-BCL-AKSX-HS-PHL-0002; Fire protection
Philosophy document no. 10481-BCL-AKSX-HS-PHL-0003; Fire & Gas Detection
Philosophy document no. 10481-BCL-AKSX-HS-PHL-0004.

10.5.1 Human Factors

Human Factors Engineering (HFE) is the process of designing a facility for human use.
The intent is to improve the interface between personnel and the systems they operate
thereby improving operating performance as well as reducing the likelihood of human
error.

Human factors shall be accounted for in the design of facilities and selection of
equipment requiring human interaction or intervention for construction, commissioning,
operation and maintenance activities.

Areas for particular analysis shall be control rooms, control panels, switchgear rooms
and vendor packaged equipment.

10481-BCL-AKSX-AR-REP-0001_4_IFC_Architectural Design Basis(1) Page 63 of 75


2020
Ajaokuta Kaduna Kano Gas Pipeline Project

10481-BCL- AKSX- AR-REP-0001-4

ARCHI TECTUR AL DESIGN B ASI S

The following HFE objectives shall be accounted for in the design of the facilities:
 Operability: To ensure that all operable components, including valves,
instruments, controls and displays, can be viewed, reached, and operated
effectively and safely by the expected working population;
 Maintainability: To ensure that safe and efficient removal of equipment
requiring maintenance;
 Access and Egress: To ensure that all areas of the facilities including
equipment packages can be accessed and evacuated safely and efficiently
under normal and emergency conditions;
 Materials Handling: To ensure that requirements for lifting/lowering, holding
and moving of equipment manually and mechanically have been addressed
with due consideration for safety and the bio-mechanical and physiological
capabilities of the expected working population;
 Environmental Factors: To ensure environmental aspects applicable to
human health, safety and performance including noise, lighting, vibration,
climatic conditions and proximity to hot, cold, hazardous and contaminated
equipment or areas have been addressed;

 Constructability: To ensure the efficiency and safety of construction


operations.

10.6 Telecommunication

For building’s telecommunication requirements, refer to Telecom Design Basis document


no. 10481-BCL-AKSX-TE-REP-0001.

10481-BCL-AKSX-AR-REP-0001_4_IFC_Architectural Design Basis(1) Page 64 of 75


2020
Ajaokuta Kaduna Kano Gas Pipeline Project

10481-BCL- AKSX- AR-REP-0001-4

ARCHI TECTUR AL DESIGN B ASI S

Appendix 1 Building Code

The basic format for building code shall be as follows:

aaa-bbb-cccdd

Where:

aaa = A three-digit numeric group that defines the Facility/Location Code. Refer to Tag
Numbering Philosophy 10481-BCL-AKSX-PR-PHL-0002

bbb = A three-digit numeric group that defines the Unit/Area Code. Refer to Table 21
below.

ccc = A two or three alpha character that defines the Building Code, as defined in Table
2 below.

dd = A two-digit code (commencing 01) indicating the unique identification number for
that type of building in the system.
Table 20 Unit/Are Code (bbb)
Code Description

000 Common

001 Admin Area

002 Plant Area

10481-BCL-AKSX-AR-REP-0001_4_IFC_Architectural Design Basis(1) Page 65 of 75


2020
Ajaokuta Kaduna Kano Gas Pipeline Project

10481-BCL- AKSX- AR-REP-0001-4

ARCHI TECTUR AL DESIGN B ASI S

003 Utilities Area

Table 21 Building Code (ccc)


Code Description

ESB Entrance Security Check Building

ACV Accommodation Building for Supervisors

ACP Accommodation Building for Personnel

ASB Administration and Security Building

ECB Electrical and Control Building

PH Prayer House

GP Guard Post

WW Workshop and Warehouse

FFS Fire Fighting Pumping Shelter

Diesel and 2 Gas Genset & Compressed Air System


GCS
Shelter

CDS Closed Drain Vessel Shed

FGS Fuel Gas Shed

CES Control Equipment Shelter

BVP Block Valve Pit Shed

CPS Car Parking Shed

Example:

300-001-ESB01

Where:

300 = Kaduna PS and TGS

001 = Admin Area

ESB = Entrance Security Check Building

10481-BCL-AKSX-AR-REP-0001_4_IFC_Architectural Design Basis(1) Page 66 of 75


2020
Ajaokuta Kaduna Kano Gas Pipeline Project

10481-BCL- AKSX- AR-REP-0001-4

ARCHI TECTUR AL DESIGN B ASI S

01 = Sequencing number

10481-BCL-AKSX-AR-REP-0001_4_IFC_Architectural Design Basis(1) Page 67 of 75


2020
Ajaokuta Kaduna Kano Gas Pipeline Project

10481-BCL- AKSX- AR-REP-0001-4


ARCHI TECTUR AL DESIGN B ASI S

Appendix 2 Building(s) and Shelter(s) Description and Basic Requirement

List of buildings, shelter, and shed is shown in Table 19 were based on FEED Guide Drawings which still subject to change in the
detailed design stage.
Table 22 Building(s) and Shelter(s) Description and Basic Requirement

Manned
Intruder Air Gross
Station
Name

or Structural Construc
Code Building Name Resista Conditio Floor Area Building Description
Unmanne System tion Type
nt n Type (m²)
d

300-001- Entrance Manned Masonry A* Yes Split 27** o To check and provide permit in
ESB01 Security Check structure Unit the station and other security
Building measures required.

o It has vestibule, guard room,


resting room, and toilet.

o Vertical Tripod Turnstile with


integrated Card Readers shall
be installed near the building.

300-001- Accommodatio Manned Masonry A* No Split 50** o To provide suitable


ACV01 n Building for Structure Unit accommodation for
Supervisors Supervisors.

o It has corridor, bedroom, living


room, and bathroom.
Kaduna TGS

300-001- Accommodatio Manned Masonry A* No Split 50** o To provide suitable


ACP01 n Building for Structure Unit accommodation for Personnel.
Personnel
o It has bedrooms (2x), and

10481-BCL-AKSX-AR-REP-0001_4_IFC_Architectural Design Basis(1) Page 68 of 75


2020
Ajaokuta Kaduna Kano Gas Pipeline Project

10481-BCL- AKSX- AR-REP-0001-4


ARCHI TECTUR AL DESIGN B ASI S

Manned
Intruder Air Gross
Station
Name or Structural Construc
Code Building Name Resista Conditio Floor Area Building Description
Unmanne System tion Type
nt n Type (m²)
d
bathrooms (2x).

300-001- Administration Manned Masonry A* No Split 276** o To provide suitable workspace


ASB01 and Security Structure Unit areas for the Terminal Gas
Building Station administration and
management purposes.

o It has waiting area, offices,


conference/meeting room,
kitchen, communication area,
first aid room, telecom
equipment room, security,
storage, toilets, and showers.

300-002- Electrical and Manned Masonry A* No PAC 439** o To provide control facility for
ECB01 Control Structure the management of station,
Building operation and maintenance.

o It has corridor, storage,


electrical room, battery room,
equipment room, control room,
engineering room, telecom
equipment room, kitchen.
Lockers, toilets, and showers.

300-001- Prayer House Manned Masonry A* No Split 134** o To provide suitable place for
PH01 Structure Unit worship for station personnel.

o It has separate entrance hall

10481-BCL-AKSX-AR-REP-0001_4_IFC_Architectural Design Basis(1) Page 69 of 75


2020
Ajaokuta Kaduna Kano Gas Pipeline Project

10481-BCL- AKSX- AR-REP-0001-4


ARCHI TECTUR AL DESIGN B ASI S

Manned
Intruder Air Gross
Station
Name or Structural Construc
Code Building Name Resista Conditio Floor Area Building Description
Unmanne System tion Type
nt n Type (m²)
d
for male and female, corridor,
separate ablution & toilets for
male and female, separate
prayer hall for male & female.

300-002- Workshop and Manned Steel B* No Split 281** o To provide general


WW01 Warehouse Structure Unit maintenance and workshop
facility, storage for the station.

o It has corridor, electrical


workshop & storage,
workshop, storage, office and
toilet.

300-001- Guard Post Manned Prefabric E* Yes Split 12** o To monitor vehicular and
GP01 ated Unit pedestrian access in and out
Steel of the station.
Cabin
o It has guard post and toilet.

300-002- Fire Fighting Unmann Light C* N/A N/A 45** o To provide shelter for
FFS01 Pumping ed Steel firefighting pump.
Shelter Structure

300-002- Generators Unmann Light C* N/A N/A 306** o To provide shelter for
GS01 Shelter ed Steel generators.
Structure

300-002- Air Unmann Light C* N/A N/A 80** o To provide shelter for

10481-BCL-AKSX-AR-REP-0001_4_IFC_Architectural Design Basis(1) Page 70 of 75


2020
Ajaokuta Kaduna Kano Gas Pipeline Project

10481-BCL- AKSX- AR-REP-0001-4


ARCHI TECTUR AL DESIGN B ASI S

Manned
Intruder Air Gross
Station
Name or Structural Construc
Code Building Name Resista Conditio Floor Area Building Description
Unmanne System tion Type
nt n Type (m²)
d
ACS01 Compressor ed Steel compressed air system.
Shelter Structure

300-002- Closed Drain Unmann Light C* N/A N/A 35** o To provide shed for close drain
CDS01 Vessel Shed ed Steel vessel.
Structure

300-002- Fuel Gas Shed Unmann Light C* N/A N/A 14** o To provide shed for fuel gas.
FGS01 ed Steel
Structure

300-001- Car Parking Unmann Light D* N/A N/A 315** o To provide shed for car
CPS01 Shelter ed Steel parking.
Structure

500-001- Entrance Manned Masonry A* Yes Split 27** o To check and provide permit in
ESB01 Security Check structure Unit the station and other security
Building measures required.

o It has vestibule, guard room,


resting room, and toilet.

o Vertical Tripod Turnstile with


integrated Card Readers shall
be installed near the building.
Kano TGS

500-001- Accommodatio Manned Masonry A* No Split 50** o To provide suitable


ACV01 n Building for Structure Unit accommodation for
Supervisors Supervisors.

10481-BCL-AKSX-AR-REP-0001_4_IFC_Architectural Design Basis(1) Page 71 of 75


2020
Ajaokuta Kaduna Kano Gas Pipeline Project

10481-BCL- AKSX- AR-REP-0001-4


ARCHI TECTUR AL DESIGN B ASI S

Manned
Intruder Air Gross
Station
Name or Structural Construc
Code Building Name Resista Conditio Floor Area Building Description
Unmanne System tion Type
nt n Type (m²)
d

o It has corridor, bedroom, living


room, and bathroom.

500-001- Accommodatio Manned Masonry A* No Split 50** o To provide suitable


ACP01 n Building for Structure Unit accommodation for Personnel.
Personnel
It has bedrooms (2x), and
bathrooms (2x).

500-001- Administration Manned Masonry A* No Split 276** o To provide suitable workspace


ASB01 and Security Structure Unit areas for the Terminal Gas
Building Station administration and
management purposes.

o It has waiting area, offices,


conference/meeting room,
kitchen, communication area,
first aid room, telecom
equipment room security,
storage, toilets, and showers.

500-002- Electrical and Manned Masonry A* No AHU 439** o To provide control facility for
ECB01 Control Structure the management of station,
Building operation and maintenance.

o It has corridor, storage,


electrical room, battery room,
equipment room, control room,
engineering room, telecom
10481-BCL-AKSX-AR-REP-0001_4_IFC_Architectural Design Basis(1) Page 72 of 75
2020
Ajaokuta Kaduna Kano Gas Pipeline Project

10481-BCL- AKSX- AR-REP-0001-4


ARCHI TECTUR AL DESIGN B ASI S

Manned
Intruder Air Gross
Station
Name or Structural Construc
Code Building Name Resista Conditio Floor Area Building Description
Unmanne System tion Type
nt n Type (m²)
d
equipment room, kitchen.
Lockers, toilets, and showers.

500-001- Prayer House Manned Masonry A* No Split 134 ** o To provide suitable place for
PH01 Structure Unit worship for station personnel.

o It has separate entrance hall


for male and female, corridor,
separate ablution & toilets for
male and female, separate
prayer hall for male & female.

500-002- Workshop and Manned Steel B* No Split 281** o To provide general


WW01 Warehouse Structure Unit maintenance and workshop
facility, storage for the station.

o It has corridor, electrical


workshop & storage,
workshop, storage, office and
toilet.

500-001- Guard Post Manned Prefabric E* Yes Split 12** o To monitor vehicular and
GP01 ated Unit pedestrian access in and out
Steel of the station.
Cabin
o It has guard post and toilet.

500-002- Fire Fighting Unmann Light C* N/A N/A 45** o To provide shelter for
FFS01 Pumping ed Steel firefighting pump.

10481-BCL-AKSX-AR-REP-0001_4_IFC_Architectural Design Basis(1) Page 73 of 75


2020
Ajaokuta Kaduna Kano Gas Pipeline Project

10481-BCL- AKSX- AR-REP-0001-4


ARCHI TECTUR AL DESIGN B ASI S

Manned
Intruder Air Gross
Station
Name or Structural Construc
Code Building Name Resista Conditio Floor Area Building Description
Unmanne System tion Type
nt n Type (m²)
d
Shelter Structure

500-002- Generators Unmann Light C* N/A N/A 306** o To provide shelter for
GS01 Shelter ed Steel generators.
Structure

500-002- Air Unmann Light C* N/A N/A 80** o To provide shelter for
ACS01 Compressor ed Steel compressed air system.
Shelter Structure

500-002- Closed Drain Unmann Light C* N/A N/A 35** o To provide shed for close drain
CDS01 Vessel Shed ed Steel vessel.
Structure

500-002- Fuel Gas Shed Unmann Light C* N/A N/A 14** o To provide shed for fuel gas.
FGS01 ed Steel
Structure

500-001- Car Parking Unmann Light D* N/A N/A 315** o To provide shed for car
CPS01 Shelter ed Steel parking.
Structure

913-002- Control Unmann Prefabric F* No Passiv 15** o House telecommunications


CES01 Equipment ed ated e equipment, RTU’s, marshalling
Shelter Steel/Alu Cooling equipment, power supply
BVS 13-22

to minium equipment and batteries.


Cabin
922-002- o It has equipment room and
CES22

10481-BCL-AKSX-AR-REP-0001_4_IFC_Architectural Design Basis(1) Page 74 of 75


2020
Ajaokuta Kaduna Kano Gas Pipeline Project

10481-BCL- AKSX- AR-REP-0001-4


ARCHI TECTUR AL DESIGN B ASI S

Manned
Intruder Air Gross
Station
Name or Structural Construc
Code Building Name Resista Conditio Floor Area Building Description
Unmanne System tion Type
nt n Type (m²)
d
battery room

913-002- Block Valve Pit Unmann Light C* N/A N/A 160** o To provide shed for block
BVP01 Shed ed Steel valve pit.
Structure
to

922-002-
BVP22

400-002- Control Unmann Prefabric F* No Passiv 15** o House telecommunications


CES01 Equipment ed ated e equipment, RTU’s, marshalling
Shelter Steel/Alu Cooling equipment, power supply
minium equipment and batteries.
Cabin
o It has equipment room and
battery room
ZARIA PS

400-002- Closed Drain Unmann Light C* N/A N/A 35** o To provide shed for close drain
CDS01 Vessel Shed ed Steel vessel.
Structure

Note:

(*) – Refer Table 5: Type and Method of Construction.

(**) – Areas shown are tentative, final areas shall be updated during IFC submission stage.

10481-BCL-AKSX-AR-REP-0001_4_IFC_Architectural Design Basis(1) Page 75 of 75


2020

You might also like