TABLE 205H
SHEARWALL SEGMENT LENGTHS - ENDWALLS
BUILDINGS WITH 8-FT CEILING HEIGHTS
8-INCH CONCRETE OR MASONRY
Building Width
24' 36' 44' 52' 60' 24' 36' 44' 52' 60' 24' 36' 44' 52' 60'
Single-story 0.5 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7
and 1.0 0.7 0.7 0.7 0.7 1.0 0.7 0.7 0.7 0.7 1.6 0.7 0.7 0.7 1.8 2.3
Top 1.5 0.7 0.7 1.1 1.6 2.2 0.7 1.1 1.7 2.4 3.1 0.7 1.7 2.5 3.3 4.1
Story 2.0 0.7 1.2 1.9 2.6 3.3 0.7 1.9 2.8 3.6 4.5 1.3 2.7 3.7 4.8 5.8
of 2.5 0.7 1.9 2.8 3.6 4.5 1.3 2.8 3.8 4.9 5.9 1.9 3.7 5.0 6.2 7.5
Multi- 3.0 1.2 2.6 3.6 4.6 5.6 1.9 3.6 4.9 6.1 7.4 2.6 4.7 6.2 7.7 9.3
story 4.0 2.1 4.0 5.3 6.6 7.9 3.0 5.3 6.9 8.6 10 4.0 6.8 7.6 11 13
Bottom Story 0.5 0.7 0.9 1.5 2.1 2.7 0.7 1.5 2.3 3.0 3.8 1.0 2.2 3.1 4.0 5.0
of Two-story 1.0 1.5 3.0 4.1 5.0 6.9 2.2 4.1 5.4 6.8 8.2 3.1 5.3 6.9 8.6 10
1.5 2.8 5.0 6.6 8.1 9.7 3.9 6.6 8.5 10 12 5.1 8.4 11 13 15
2.0 4.2 7.0 9.1 11 13 5.6 9.1 12 14 17 7.1 11 14 17 20
2.5 5.5 9.1 11 14 17 7.2 12 15 18 21 9.1 14 18 22 26
3.0 0.8 11 14 17 20 8.8 14 18 21 25 11 17 22 26 31
4.0 9.5 15 19 23 27 12 19 24 29 34 15 23 26 35 41
NOTES:
1. Shearwall segments shall be integral with the concrete or masonry over the opening on at least one side. Maximum pier height (height or
that opening) shall be as follows:
a. 4 ft 8 in for a 2 ft segment with 1 #5 each end.
b. 8 ft for a 2 ft segment with 2 #5 or 1 #7 each end.
c. 8 ft for a 4 ft segment or larger with 1 #5 each end.
d. The pier height may be increased by the factor: SLP/SLR
where:
SLP = Shearwall segment length provided
SLR = Shearwall length required
2. For ceiling heights other than 8 ft, the following multipliers shall be applied:
Top & Single Story Bottom Story
Ceiling Height, ft Multiplier Multiplier
10 1.4 1.3
12 1.9 1.5
16 2.7 2.0
20 3.5 2.5
3. Ratio of building length to width. If interior shearwalls are used, use shearwall spacing for L in determining length/width.
4. The minimum length of any shearwall segment shall be 2 ft after adjustments. Values less than 2 ft are shown only for
summation of shearwall segments for nonrectangular buildings and for interpolation purposes.
5. Shearwall segment lengths specified are good for roof angles up to and including 30° (7:12 roof slope). For roof slopes over 30° up
to 45° (12:12 roof slope) the following multipliers shall be applied:
Top & Single Story Bottom Story
Roof Slope Multiplier Multiplier
8:12 1.20 1.0
10:12 1.25 1.1
12:12 1.30 1.1
6. For 6-inch concrete or masonry units, table values shall be multiplied by the following before applying other multipliers:
Table Value Multiplier
0-2 ft 1.50
> 2-4 ft 1.35
> 4 ft 1.30
7. For concrete or solid grouted masonry, shearwall segment lengths may be adjusted as follows:
Length Required Multiplier
0-2 ft 1.0
> 2-4 ft 0.7
> 4-8 ft 0.5
> 8 ft 0.4
8. For three-story buildings, the second-story shearwall segment requirements shall be as determined for the bottom story of a two-story build-
ing. The shear segment length of the bottom story of a three-story building shall be that for the bottom story of a two-story building multiplied
by 1.8.
Building Width
24' 36' 44' 52' 60' 24' 36' 44' 52' 60' 24' 36' 44' 52' 60'
NOTES:
1. Shearwall segments shall be integral with the concrete or masonry over the opening on at least one side. Maximum pier height (height or
that opening) shall be as follows:
a. 4 ft 8 in for a 2 ft segment with 1 #5 each end.
b. 8 ft for a 2 ft segment with 2 #5 or 1 #7 each end.
c. 8 ft for a 4 ft segment or larger with 1 #5 each end.
d. The pier height may be increased by the factor: SLP/SLR
where:
SLP = Shearwall segment length provided
SLR = Shearwall segment length required
2. For ceiling heights other than 8 ft, the following multipliers shall be applied:
Ceiling Height, ft Top & Single Story Multiplier Bottom Story Multiplier
10 1.4 1.3
12 1.9 1.5
16 2.7 2.0
20 3.5 2.5
3. The minimum length of any shearwall segment shall be 2 ft after adjustments. Values less than 2 ft are shown only for summation of shear
wall segments for nonrectangular buildings and for interpolation purposes.
4. For 6-inch concrete or masonry, table values shall be multiplied by the following before applying other multipliers:
Table Value Multiplier
0-2 ft 1.50
> 2-4 ft 1.35
> 4 ft 1.30
5. For concrete or solid grouted masonry, shearwall segment lengths may be adjusted as follows:
Length Required Multiplier
0-2 ft 1.0
> 2-4 ft 0.7
> 4-8 ft 0.5
> 8 ft 0.4
6. For three-story buildings, the second-story shearwall segment requirements shall be as determined for the bottom story of a two-story build-
ing. The shear segment length of the bottom story of a three-story building shall be that for the bottom story of a two-story building multiplied
by the following factor:
Building Width, ft Multiplier
24 1.8
36 1.7
44 1.6
52 1.6
60 1.5
FIGURE 205K
SHEARWALL SEGMENTS
205.6 INTERIOR SHEARWALLS
205.6.1 Interior shearwalls may be used to decrease the length-to-width ratio of buildings provided:
1. Bond beams in interior walls containing shearwalls shall extend the full width of the building and shall be subject
to the same restrictions as shearwalls in exterior walls;
2. The length of an interior shearwall shall be sized in accordance with 205.5. For interior shearwalls, the total
shearwall length shall be the sum of the shearwall lengths required for each building length on each side of the
interior shearwall;
3. Bond beam reinforcement of interior walls containing shearwalls shall be continuous with bond beam reinforce-
ment of exterior walls;
4. Where concrete or masonry shearwalls or shearwall segments terminate below the roof diaphragm, the
diaphragm shall be connected to the shearwall or shearwall segments by the roof trusses or framing. Such con-
crete or masonry walls shall be laterally supported by a ceiling diaphragm in accordance with 207 (See Figure
208H).
205.6.2 When an interior shearwall is used in the bottom story of a two-story building without an interior shearwall
above it (i.e. wider shearwall spacing in top story than bottom story), the following procedure shall be used:
1. L/W for both stories shall be based on top story;
2. Top-story shearwall segment lengths shall be as shown in Table 205H;
3. For bottom-story shearwall segment lengths, one must use upper-story spacing and reduce table values as fol-
lows:
a. Shearwall having a shearwall above it, multiply by 0.82.
b. Shearwall without shearwall above it, multiply by 0.35.
FIGURE 205L
ONE-STORY CONCRETE OR MASONRY WALL
FIGURE 205M
CONTINUITY OF FIRST- AND SECOND-FLOOR
VERTICAL WALL REINFORCEMENT
FIGURE 205N
EXTERIOR WALL REINFORCEMENT SUMMARY
ONE STORY (TWO STORY SIMILAR)
NOTES:
1. All loads are superimposed at the top of the wall and do not include dead loads of the bond beam or masonry above the assembly. Add
100% of additional dead loads to the gravity loads and subtract 85% of these loads from the uplift loads.
2. Use 4-foot roof span for assemblies in endwalls.
3. For total roof dead loads over 10 psf, increase gravity loads by the following amount:
(Roof Dead Load - 10 psf) x (Roof Span + 2 ft)
2
4. Uplift rating is required only if a pre-engineered assembly is used to directly support a roof. (See Section 205.8.1.3(2) for cases where uplift
need not be considered.)
Floor1
Span Minimum Rated Gravity Load Assembly (plf)
(ft) Assembly Clear Span (ft)
4 6 8 12 16 20
NOTES:
1. For a wall supporting floors on both sides, enter Table with the sum of the 2 full spans.
NOTE: Tabular values are for 1/2 the load of the full span shown.
2. Use 4 ft building width for assemblies in nonfloorbearing walls (normally endwalls and interior masonry walls and shearwalls).
3. The values in this table may be interpolated.
4. These loads take into account the dead load of any masonry in the wall above the assembly and live and dead loads of the roof and floor
supported. Dead load of the assembly is not included in the table and if not included in the pre-engineered concrete design must be added
to the loads in the table.
5. This table is applicable for all roof dead loads.
TABLE 205P3
SUPERIMPOSED LOADS
MINIMUM RATED LOAD CAPACITY OF NOMINAL 8 INCH THICK
PRE-ENGINEERED ASSEMBLIES SPANNING OPENINGS OF
BOTTOM STORY OF TWO-STORY BUILDINGS, SECOND AND BOTTOM STORIES OF
THREE-STORY BUILDINGS—HOLLOWCORE FLOOR SYSTEM
Floor1
Span Minimum Rated Gravity Load of Assembly (plf)
(ft) Assembly Clear Span (ft)
4 6 8 12 16 20
NOTES:
1. For a wall supporting floors on both sides, enter Table with the sum of the 2 full spans.
NOTE: Tabular values are for 1/2 the load of the full span shown.
2. Use 4 ft building width for assemblies in nonfloorbearing walls (normally endwalls and interior masonry walls and shearwalls).
3. The values in this table may be interpolated.
4. These loads take into account the dead load of any masonry in the wall above the assembly and live and dead loads of the roof and floor
supported. Dead load of the assembly is not included in the table and if not included in the pre-engineered concrete assembly design must
be added to the loads in the table.
5. This table is applicable for all roof dead loads.
Roof Bond Beam 6" Thick Wall1,2,4 Bond Beam 8" Thick Wall1,2,4
Span
(ft) 16-1 16-2 C12-1 C12-2 C16-1 C16-2 16-1 16-2 C12-1 C12-2 C16-1 C16-2
43 16-0 17-4 16-0 20-8 18-0 24-8 16-0 18-8 15-4 20-8 17-4 23-4
12 12-0 13-4 12-0 15-4 14-0 18-8 12-8 14-0 11-4 16-0 13-4 18-0
24 8-8 8-8 9-4 10-8 10-8 14-8 10-0 11-4 8-8 12-8 10-8 14-8
36 6-8 6-8 8-0 8-0 9-4 11-4 8-8 8-8 7-4 10-0 8-8 12-0
44 6-0 6-0 7-4 7-4 8-0 10-0 7-4 7-4 6-8 8-8 8-0 11-4
52 5-4 5-4 6-0 6-0 8-0 8-8 6-8 6-8 6-8 8-0 7-4 10-8
60 4-8 4-8 6-0 6-0 7-4 8-0 6-0 6-0 6-0 7-4 7-4 10-0
NOTES:
1. Designation of bond beam types over openings:
a. Letter C designates a concrete bond beam. All other bond beams are masonry.
b. The first number denotes the nominal height of the bond beam in inches.
c. The second number denotes the number of #5 reinforcing bars in the top and the bottom of the beam. 1-#7 may be used in lieu of 2-#5.
The bottom reinforcing steel shall be located no more than 2 3/4 inches clear distance from the bottom of masonry bond beams and 1 1/2
inches for concrete bond beams.
2. All bond beams have reinforcement in the top as required by Table 205C or D as appropriate. If 2-#5 are required in this table and only 1-#5
by Table 205D, the additional bar shall be placed in the top of the bond beam over the opening and shall extend past the opening a minimum of
24 inches.
3. Use 4 foot roof span for lintels in endwalls.
4. The bottom reinforcement in precast lintels may be used to satisfy the continuous bond beam bottom reinforcement requirement.
5. For roof dead loads more than 10 psf:
a. For 20 psf roof dead load, multiply allowable clear spans by 0.85.
b. For 30 psf roof dead load, multiply allowable clear spans by 0.75.
c. Values for other roof dead loads may be interpolated.
TABLE 205R3
MAXIMUM CLEAR SPAN CAPACITY OF
CONTINUOUS BOND BEAMS ACTING AS LINTELS
BOTTOM STORY OF TWO-STORY BUILDINGS, SECOND AND BOTTOM STORIES OF
THREE-STORY BUILDINGS—HOLLOWCORE SECOND FLOOR
4 11-4 12-0 14-8 16-0 18-8 22-8 23-4 27-4 29-4 30-0 29-4 34-0 35-4 38-0 39-4 40-8
12 8-0 8-8 11-4 12-0 14-8 17-4 18-8 22-9 23-3 24-8 24-8 28-9 29-4 31-4 33-4 34-0
24 6-0 6-9 8-8 8-8 11-4 14-0 14-0 18-0 18-0 18-0 20-0 22-0 22-0 26-0 26-0 26-0
6" 36 4-8 4-8 6-8 6-8 10-0 10-8 10-8 14-0 14-0 14-0 17-4 17-4 17-4 20-8 20-8 20-8
44 4-0 4-0 6-0 6-0 9-4 9-4 9-4 12-8 12-8 12-8 15-4 15-4 15-4 18-0 18-0 18-0
52 3-4 3-4 5-4 5-4 8-0 8-0 8-0 11-4 11-4 11-4 14-0 14-0 14-0 16-8 16-8 16-8
60 3-4 3-4 4-8 4-8 7-4 7-4 7-4 10-0 10-0 10-0 12-8 12-8 12-8 15-4 15-4 15-4
4 12-0 12-8 14-8 16-8 17-4 23-4 24-8 25-4 30-0 30-8 26-8 32-8 35-4 34-0 39-4 40-8
12 8-8 9-4 11-4 13-4 14-0 18-8 20-0 21-4 24-8 26-0 22-8 28-0 30-0 29-4 34-0 35-4
24 6-8 7-4 9-4 10-0 11-4 15-4 16-0 17-4 20-8 21-4 19-4 23-4 25-4 25-4 28-8 30-0
8" 36 6-0 6-0 8-0 8-8 9-4 13-4 13-4 15-4 17-4 17-4 16-8 20-8 21-4 22-0 24-8 24-8
44 5-4 5-4 7-4 7-4 8-8 11-4 11-4 14-0 15-4 15-4 16-0 18-8 18-8 20-8 22-0 22-0
52 4-8 4-8 6-8 6-8 8-0 10-0 10-0 13-4 14-0 14-0 14-8 17-4 17-4 19-4 20-0 20-0
60 4-0 4-0 6-0 6-0 8-0 9-4 9-4 12-8 12-8 12-8 14-0 15-4 15-4 18-8 18-8 18-8
NOTES:
1. Designation of combined bond beam/lintels:
a. The first number denotes the nominal height of the bond beam/lintel in inches.
b. The second number denotes the number of #5 reinforcing bars in the bottom of the bond beam/lintel. The equivalent or greater area of rein-
forcement may be obtained by using reinforcement other than #5. For example, when 3-#5 are required 1-#9 may be used. Also, 1-#7 may be
used to replace 2-#5 or 2-#7 to replace 4-#5. The bottom reinforcing steel is to be located not more than 2 3/4 inches clear distance from the
bottom of the lintel.
2. All bond beams shall have reinforcement in the top in accordance with Table 205C or D, as appropriate.
43 9-4 12-0 16-0 16-8 18-0 20-0 22-8 24-0 24-0 26-8
12 8-0 10-8 14-0 15-4 16-0 18-8 20-8 22-0 22-0 24-0
24 6-0 8-8 12-0 12-0 14-0 15-4 18-0 18-0 20-0 20-8
36 4-8 6-8 10-0 10-0 12-8 13-4 16-0 16-0 18-0 18-0
44 4-0 6-0 9-4 9-4 12-0 12-0 14-8 14-8 16-8 16-8
52 4-0 5-4 8-8 8-8 10-8 10-8 13-4 13-4 16-0 16-0
60 3-4 4-8 8-0 8-0 10-0 10-0 12-8 12-8 14-8 14-8
TABLE 205S3
COMBINED BOND BEAM/LINTELS
BOTTOM STORY OF TWO-STORY BUILDINGS, SECOND AND BOTTOM STORIES OF
THREE-STORY BUILDINGS — HOLLOWCORE FLOOR SYSTEM
43 8-8 11-4 15-4 16-0 17-4 19-4 22-0 23-4 23-4 25-4
12 6-8 9-4 12-8 12-8 14-8 16-0 18-8 18-8 20-8 21-4
24 4-8 6-0 9-4 9-4 12-0 12-0 14-8 14-8 17-4 17-4
36 3-4 4-8 7-4 7-4 10-0 10-0 12-0 12-0 14-8 14-8
44 2-8 4-0 6-8 6-8 8-8 8-8 11-4 11-4 13-4 13-4
52 2-8 4-0 6-0 6-0 8-0 8-0 10-0 10-0 12-0 12-0
60 2-8 3-4 5-4 5-4 7-4 7-4 9-4 9-4 11-4 11-4
206.4 REINFORCEMENT
206.4.1 Vertical Reinforcement. Above-grade concrete walls shall have vertical reinforcement in accordance with
206.1, 206.2, or 206.3 and 206.6. All vertical reinforcement in the top-most ICF story shall terminate with a bend in
accordance with 202.3.4 or a standard hook and be provided with a minimum lap splice of 24 inches (610 mm) with
the top horizontal reinforcement.
206.4.2 Horizontal Reinforcement. Concrete walls with minimum thickness of 4 inches (102 mm) shall have a mini-
mum of one continuous #4 horizontal reinforcing bar placed at 32 inches (812 mm) on center with one bar within 12
inches (305 mm) of the top of the wall story. Concrete walls 5.5 inches (140 mm) thick or greater shall have a mini-
mum of one continuous #4 horizontal reinforcing bar placed at 48 inches (1.2 m) on center with one bar located within
12 inches (305 mm) of the top of the wall story.
Horizontal reinforcement shall be continuous around building corners using corner bars or by bending the bar in
accordance with 202.3.4. In either case, the minimum lap splice shall be 24 inches (610 mm).
206.5 WALL OPENING. Wall openings shall have a minimum of 8 inches (203 mm) of depth of concrete over the
length of the opening for flat and waffle-grid ICF walls and 12 inches (305 mm) for screen-grid ICF walls. Wall open-
ings for waffle-grid and screen-grid ICF walls shall have a minimum depth of concrete along the side of the openings,
for the full height, equal to 1/2 of the core width (W). Reinforcement around the openings shall be provided in accor-
dance with Table 206E and Figure 206D. All reinforcement placed horizontally above or below an opening shall
extend a minimum of 24 inches (610 mm) beyond the limits of the opening. Wall opening reinforcement shall be pro-
vided in addition to the reinforcement required by 206.1, 206.2, 206.3 and 206.4. The perimeter of all wall openings
shall be framed with a minimum 2x4, preservative-treated plate, anchored to the wall with 1/2 diameter anchor bolts
spaced a maximum of 24 inches on center. The bolts shall be embedded into the concrete a minimum of 4 inches
and have a minimum of 1 1/2 inches of concrete cover to the face of the wall.
EXCEPTION: The 2x4 plate is not required where the wall is formed to provide solid concrete around the perimeter
of the opening with a minimum depth of 4 inches for the full thickness of the wall.
206.6 LINTELS
206.6.1 General Requirements. Lintels shall be provided over all openings greater than or equal to four feet (1.2 m)
in width. Lintels for flat ICF walls and screen-grid walls shall be constructed in accordance with Figures 206D and
206E. Lintels for waffle-grid ICF walls shall be constructed in accordance with Figures 206D, 206F and 206G. Lintels
depths are permitted to be increased by the height of ICF wall located directly above the lintels, provided that the lin-
tel depth spans the entire length of the opening.
206.6.2 Stirrups. A minimum #3 stirrups shall be installed for all lintels at a maximum spacing of d/2 where d equals
the depth of the lintel D minus the bottom cover of concrete as shown in Figures 206E, 206F and 206G. Where the
spacing of stirrups in waffle-grid walls places the stirrup between vertical cores, the stirrup shall be relocated to the
closest vertical core. In no case shall the total number of stirrups required be reduced.
206.6.3 Horizontal Reinforcement. One #4 horizontal bar shall be provided in the top of the lintel. Horizontal rein-
forcement placed within 12 inches of the top of the wall in accordance with Section 206.4 shall be permitted to serve
as the top or bottom reinforcement in the lintel provided the reinforcement meets the location requirements in Figures
206D, 206E, 206F or 206G, and the size requirements in Tables 206F1, 206F2, 206G1, 206G2, 206H or 206J.
206.6.4 Loadbearing Walls. Lintels for flat and screen-grid ICF walls supporting roof or floor loads shall comply with
Tables 206F1 or 206F2. Lintels for waffle-grid ICF walls supporting roof or floor loads shall comply with Tables 206G1
and 206G2.
EXCEPTION: Where spans larger than those permitted in Tables 206F1, 206F2, 206G1 or 206G2 are required,
the lintels shall comply with Table 206H.
206.7 SHEARWALLS
Exterior ICF walls shall have a minimum of solid wall length to total wall length in accordance with Table 206K, but
not less than 15 percent for ICF walls supporting a light framed roof or 20 percent for ICF walls supporting an ICF or
light framed second story and light framed roof. The minimum percentage of solid wall length shall include only those
solid wall segments which are a minimum of 24 inches (610 mm) in length. The maximum distance between wall seg-
ments included in determining solid wall length shall not exceed 18 feet (5.5 m) on center. A minimum length of 24
inches (610 mm) of solid wall segment, extending the full height of each wall story, shall occur at all corners of exteri-
or walls.
206.10 TERMITES
In areas where hazard of termite damage is very heavy, according to the Standard Building Code, clearance between
earth and insulated concrete forms (ICF) shall be not less than 6 inches (152 mm).
1. Not all vertical reinforcement is required to be tied to the foundation with dowels. Vertical reinforcement not tied to the foundation with dow-
els shall reach within 12 inches of the floor slab below. See 203.3 for dowel requirements.
1. Not all vertical reinforcement is required to be tied to the foundation with dowels. Vertical reinforcement not tied to the foundation with dow-
els shall reach within 12 inches of the floor slab below. See 203.3 for dowel requirements.
1. Not all vertical reinforcement is required to be tied to the foundation with dowels. Vertical reinforcement not tied to the foundation with
dowels shall reach within 12 inches of the floor slab below. See 203.3 for dowel requirements.
TABLE 206D
DIMENSIONAL REQUIREMENTS FOR CORES AND WEBS IN
WAFFLE-GRID AND SCREEN-GRID ICF WALLS1,2
Notes:
1. For width (W), thickness (T), spacing, and web thickness, refer to Figures 206B and 206C.
2. N/A indicates not applicable.
TABLE 206E
MINIMUM WALL OPENING REINFORCEMENT
REQUIREMENTS IN ICF WALLS
Provide lintels in accordance with Two No. 4 bar for the full height of
Flat, Waffle-, and Section 206.6. Top and bottom the wall story within 12 inches
Screen-grid lintel reinforcement shall extend a of each side of the opening.
L 4 minimum of 24 inches beyond the
limits of the opening.
Notes:
1. #3 stirrups are required at d/2 spacing.
2. Interpolation is permitted between ground snow loads and between lintel depths.
Notes:
1. #3 stirrups are required at d/2 spacing.
2. Interpolation is permitted between ground snow loads and between lintel depths.
Notes:
1. #3 stirrups are required at d/2 spacing.
2. Interpolation is permitted between ground snow loads and between lintel depths.
3. For actual wall lintel width, refer to Table 206D.
4. Lintel width corresponds to the nominal waffle-grid ICF wall thickness with a minimum web thickness of 2 inches.
TABLE 206G2
MAXIMUM ALLOWABLE CLEAR SPAN FOR
WAFFLE-GRID ICF WALL LINTELS1,2
#5 Bottom Bar Size
Notes:
1. #3 stirrups are required at d/2 spacing.
2. Interpolation is permitted between ground snow loads and between lintel depths.
3. For actual wall lintel width, refer to Table 206D.
4. Lintel width corresponds to the nominal waffle-grid ICF wall thickness with a minimum web thickness of 2 inches.
24 1-#5 1-#7; 2-#5 1-#7; 2-#5 1-#8; 2-#6 1-#8; 2-#6 D/R
7.5 20 1-#6; 2-#4 1-#7; 2-#5 1-#8; 2-#6 D/R D/R D/R
24 1-#6; 2-#4 1-#7; 2-#5 1-#7; 2-#5 1-#8; 2-#6 1-#8; 2-#6 1-#8; 2-#6
9.5 20 1-#6; 2-#4 1-#7; 2-#5 1-#8; 2-#6 1-#8; 2-#6 1-#8; 2-#6 1-#9; 2-#6
24 1-#6; 2-#4 1-#7; 2-#5 1-#7; 2-#5 1-#8; 2-#6 1-#8; 2-#6 1-#9; 2-#6
9.5 24 1-#7; 2-#5 1-#9; 2-#6 1-#9; 2-#6 D/R D/R D/R
24 1-#5 1-#7; 2-#5 1-#7; 2-#5 1-#8; 2-#6 1-#8; 2-#6 D/R
24 1-#5 1-#7; 2-#5 1-#7; 2-#5 1-#8; 2-#6 1-#8; 2-#6 1-#8; 2-#6
8 12 6
12 16 8
16 16 10
20 16 12
24 16 16
90 mph 100 mph 110 mph 90 mph 100 mph 110 mph
3:12 15 15 20 40 50 55
6:12 20 20 25 50 55 60
4" Flat 9:12 30 40 45 70 85 95
12:12 40 50 60 80 95 100
3:12 15 15 15 30 40 40
6:12 15 15 20 35 40 45
5.5" Flat 9:12 20 25 30 50 60 70
12:12 25 35 40 55 70 75
3:12 15 15 15 25 30 30
6:12 15 15 15 25 30 35
7.5" Flat 9:12 15 20 25 40 45 50
12:12 20 25 30 40 50 55
3:12 15 15 20 35 45 50
6:12 20 20 25 45 50 55
6" Waffle-Grid 9:12 25 35 40 60 75 85
12:12 35 45 50 70 85 90
3:12 15 15 15 30 35 35
6:12 15 15 20 30 35 40
8" Waffle-Grid 9:12 20 25 30 45 55 60
12:12 25 30 35 50 60 65
3:12 20 20 25 45 55 60
6:12 25 30 35 50 60 70
6" Screen-Grid 9:12 45 50 65 80 90 100
12:12 55 65 80 85 100 100
Interpolation is permitted:
SIDEWALL ENDWALL
L/W MULTIPLIER MULTIPLIER
FIGURE 206A
FLAT ICF WALLS
FIGURE 206B
WAFFLE-GRID ICF WALLS
FIGURE 206C
SCREEN-GRID WALLS
FIGURE 206D
WALL OPENINGS
FIGURE 206E
FLAT ICF LINTEL
FIGURE 206F
WAFFLE-GRID ICF LINTEL
(SINGLE FORM HEIGHT)
FIGURE 206G
WAFFLE-GRID LINTEL
(DOUBLE FORM HEIGHT)
TABLE 207A
REQUIRED CEILING DIAPHRAGM CAPACITIES
90 mph 100 mph 110 mph
Building Width
24' 36' 44' 52' 60' 24' 36' 44' 52' 60' 24' 36' 44' 52' 60'
W 75 90 97 105 115 95 110 115 130 140 115 130 147 160 170
2W 40 45 48 53 60 50 55 62 67 70 60 65 75 82 85
3W 25 30 33 37 40 30 35 38 42 45 40 45 48 52 55
W = Building Width
TABLE 207B
REQUIRED ENDWALL CONNECTION CAPACITIES
90 mph 100 mph 110 mph
Building Width
24' 36' 44' 52' 60' 24' 36' 44' 52' 60' 24' 36' 44' 52' 60'
Outward Pressure 90 110 120 130 140 115 135 148 162 175 140 165 182 197 210
FIGURE 207C
GYPSUM CEILING DIAPHRAGM TO SIDEWALL CONNECTION
FIGURE 207D
DIRECT TRUSS TO MASONRY CONNECTION, ENDWALL
FOR GYPSUM CEILING DIAPHRAGM
FIGURE 207E
DIRECT TRUSS TO MASONRY ALTERNATE, ENDWALL
FOR GYPSUM CEILING DIAPHRAGM
207.3.2 Wood Structural Panels: Where wood structural panels are used to create the required diaphragm, this
diaphragm is necessary at each endwall, and each diaphragm length shall be as shown in Table 207F for the building
widths and eave heights given. The panels shall be 15/32" thick minimum. Blocking and diaphragm chords shall be
2x4 or larger, Group III species lumber, grade #2, or better. When truss framing is used, bottom chord of truss shall
NOT be used as a diaphragm chord or as blocking (See Figures 207G, H, and I).
1. Chords are required at both diaphragm edges parallel to the endwall. Chords shall be one piece for the full width
of the building or shall be spliced in accord with Table 207F.
2. Blocking is required at all panel joints and all edges at sidewalls. Blocking may be installed flatwise.
3. Wood structural panels shall be fastened to ceiling framing, chords, and blocking with 8d common or 8d hot-
dipped galvanized box nails. Nail spacing at ceiling framing shall be 12" o.c. max. Nail spacing at chords and
blocking shall be as shown in Table 207F.
4. Nails for chord splicing and for fastening chords and blocking to walls shall be 10d common or 10d hot-dipped
galvanized box nails. The number of nails required for each side of each chord splice shall be as shown in Table
207F. Nails shall be spaced to avoid splitting of wood. Diaphragm chords shall be nailed to plate at walls at 4" o.c.
at side walls and 6" o.c. at end walls.
5. Finish ceiling material may be applied over the wood structural panel diaphragm and over the ceiling framing
throughout the remainder of the building with or without furring. This ceiling material is not a part of the diaphragm
requirement.
TABLE 207F
WOOD STRUCTURAL PANELS CEILING DIAPHRAGM
24 4 4 15 8 6 10 8 6 12
36 8 4 19 8 4 24 12 4 19
44 12 6 21 12 4 25 16 6 23
52 12 4 31 16 4 28 16 4 34
60 16 4 33 16 4 40 20 4 39
24 8 6 9 8 6 11 8 4 13
36 8 4 22 12 6 18 12 4 22
44 12 4 24 12 4 29 16 4 27
52 12 4 35 16 4 33 20 4 32
60 16 4 38 20 4 37 24 4 37
FIGURE 207G
WOOD STRUCTURAL PANELS CEILING DIAPHRAGM
FIGURE 207H
WOOD STRUCTURAL PANEL CEILING DIAPHRAGM
SECTION PARALLEL TO RIDGE-ATTACHMENT TO ENDWALL
FIGURE 207I
WOOD STRUCTURAL PANEL CEILING DIAPHRAGM
SECTION PERPENDICULAR TO RIDGE-ATTACHMENT TO SIDEWALL
208.4 BRACING
208.4.1 When a gable endwall extends from the uppermost floor to the underside of the roof and is not supported by
a ceiling diaphragm, endwall roof bracing shall be provided perpendicular to the rafters or trusses in the first two rafter
or truss spaces at each end and shall be spaced at 4 ft maximum on center, as shown in Figure 208A. Bracing mem-
bers shall be full depth of rafters or truss top chords.
FIGURE 208A
ROOF SHEATHING LAYOUT
AND ENDWALL BRACING
FIGURE 208B
ROOF SHEATHING NAILING ZONES
TABLE 208C
ROOF DIAPHRAGM REQUIREMENTS AT SIDEWALLS
24 75 90 110
36 85 105 130
NOTES:
1. The following adjustments to the table values are required:
a. If the top story ceiling height is more than 8 ft.:
for 10 ft. ceiling height, multiply by 1.10
for 12 ft. ceiling height, multiply by 1.2
for 16 ft. ceiling height, multiply by 1.5
for 20 ft. ceiling height, multiply by 1.7
b. If total building length (L) is less than the building width, multiply by W/L.
c. If roof slope is more than 7:12 (30°):
for 8:12 roof slope (33.7°), multiply by 1.1
for 10:12 roof slope (39.8°), multiply by 1.3
for 12:12 roof slope (45°), multiply by 1.5
2. The following adjustments to the table values shall be permitted:
a. If roof slope is less than 7:12 (30°):
for 6:12 roof slope (26.6°), multiply by 0.90
for 2:12 roof slope (10°), multiply by 0.65
b. If total building length (L) is greater than the building width, multiply by W/L.
c. If a ceiling diaphragm is provided for lateral support of the gable end, multiply by 0.40.
d. For single story, multiply by 0.82 for 8 ft to 10 ft ceiling heights and 0.90 for 12 ft to 20 ft ceiling heights.
Maximum
Distance 90 mph 100 mph 110 mph
Between
Shearwalls
W/2 35 45 50
W 65 80 95
1. Values in the table above are for an 8 ft. top-floor ceiling height. For other ceiling
heights with roof slopes of 30° or less (7:12), values in the table shall be multiplied by:
2. For single-story buildings, values for roofs may be multiplied by 0.82 for 8 ft and 10
ft ceiling heights and 0.90 for all others.
3. For roof slopes over 30° (7:12), the following multiplier shall be applied for roof
slope and/or ceiling height indicated:
5 psf 310 445 535 630 720 400 570 690 810 930 500 715 860 1005 1155
7 psf 285 405 485 570 655 370 530 640 750 865 470 675 810 950 1090
10 psf 240 345 415 490 560 330 470 570 670 770 430 615 740 870 995
15 psf 170 245 295 350 400 260 370 450 530 610 360 515 620 725 835
20 psf 100 145 175 210 240 190 270 330 390 450 290 415 500 585 675
25 psf 30 45 55 70 80 120 170 210 250 290 220 315 380 445 515
5 psf 415 595 715 835 960 535 765 920 1075 1235 665 950 1145 1340 1540
7 psf 375 540 650 760 875 495 710 855 1000 1150 625 900 1080 1265 1455
10 psf 320 460 555 650 750 440 630 760 890 1025 570 820 985 1155 1330
15 psf 230 325 395 465 535 345 495 600 705 810 480 685 825 970 1115
20 psf 135 195 235 275 320 255 365 440 515 595 385 550 665 780 900
25 psf 40 60 75 90 110 160 230 280 330 385 290 420 505 595 690
5 psf 620 890 1070 1255 1440 800 1145 1380 1615 1855 995 1425 1720 2015 2310
7 psf 565 810 975 1145 1315 745 1065 1280 1505 1725 940 1345 1620 1900 2185
10 psf 480 690 830 975 1120 660 945 1140 1335 1535 855 1225 1480 1735 1990
15 psf 340 490 590 695 800 520 745 900 1055 1215 715 1025 1240 1455 1670
20 psf 200 290 350 415 480 380 545 660 775 890 575 895 1000 1175 1350
25 psf 60 90 110 135 160 240 345 420 495 575 435 625 760 895 1030
NOTES:
1. Individual connector ratings shall not be less than 100 lbs for uplift.
2. Roof and ceiling dead loads shall be actual loads provided, not counting the roof covering. In the absence of more accurate data, the follow-
ing roof and ceiling dead loads shall be used: 7 psf for truss assembly (roof sheathing, trusses, gypsum ceiling); 7 psf for rafter assembly
(roof sheathing, rafters, gypsum ceiling); 10 psf for rafter/ceiling assembly (roof sheathing, rafters and ceiling joists connected per Table
2306.1 of the Standard Building Code).
EXCEPTION: Where roof tile is installed in accordance with the SBCCI Standard for Determining the Wind Resistance of Concrete and Clay
Roof Tile, the actual weight of the tile shall be permitted to be included in the total roof and ceiling dead load.
3. The following adjustments shall be permitted (uplift shall not be less than 100 lbs per connector after adjustment):
a. The required uplift capacity shall be permitted to be reduced by 30% (multiply by 0.70) for connections at least w/5 from corners but
not less than 6 feet.
b. The values in the tables assume a maximum eave height of 30 ft. When the eave height is 12 ft or less, the values shall be permitted
to be reduced by 20% (multiply by 0.80).
c. Footnote 3b shall be permitted to be applied simultaneously with footnote 3a.
FIGURE 208F
ROOF TO MASONRY SIDEWALL CONNECTION
DIRECT TO BOND BEAM
FIGURE 208G
ROOF TO MASONRY SIDEWALL CONNECTION
BOLTED TOP PLATE ALTERNATE
208.6.3 Continuous Gable Endwalls: A 2x wood nailer shall be bolted to the rake beam at the top of the endwall
with 1/2" standard anchor bolts spaced per Table 205E (See Figure 205E). Roof sheathing shall be fastened to nailer
in the same manner as to other roof framing.
208.6.4 Gable Truss Endwalls: The roof system shall be fastened to the endwall bond beam to resist shear loads
from the roof diaphragm. Gable truss endwalls are permitted only when a ceiling diaphragm as specified in 206 is
provided to resist lateral wind pressures on the endwall.
1. Direct Truss to Concrete or Masonry Connections: Anchor each gable end truss with rated connectors capa-
ble of resisting shear (in pounds) equal to the required diaphragm capacity at endwalls as determined in
Table 208D times the connector spacing (in feet) (Refer to Figure 207D).
2. Top Plate Alternate: A minimum 2x wood plate shall be bolted to the bond beam, 4 ft on center with 1/2 inch
anchor bolts or equal (Refer to Figure 207E). The plate shall be positioned on the beam so that it bears
against the inside face of the bottom chord of the gable truss. Nail the bottom chord to the plate with 16d
common or hot-dipped galvanized box nails 8 inches on center.
208.6.5 Wood-Framed Gable Endwalls: See Chapter 4, Combined Concrete or Masonry and Wood Exterior Wall
Construction.
208.6.6 Hip Roof Trusses at Endwalls: Connect trusses to endwalls using same methods as for sidewalls (See
208.6.1 and 208.6.2). Connections for hip trusses to wall shall resist the uplift loads shown in Table 208E as modified
by Table 208J. This method is for a step down hip system only (see Figure 208K). Truss-to-truss connections shall be
part of the truss design. Lateral loads parallel to the wall and lateral loads perpendicular to the wall are the same as in
208.6.1(2).
208.6.7 Interior Shearwall to Roof Connection: Connections shall be similar to those for endwalls (Refer to Figure
208H for connection of interior shearwall to roof system).
FIGURE 208H
INTERIOR SHEARWALL TO ROOF CONNECTION
TABLE 208J
WIND UPLIFT LOADS FOR HIP ROOF STEP DOWN SYSTEM
Top plate to truss connection loads (lbs)
Hip Truss Member From Table 208E For 7-ft For 11-ft
Find the Uplift Load Endjack System Endjack System
For Multiply Uplift Load By
FIGURE 208K
HIP ROOF FRAMING USING TRUSSES
209.1 GENERAL
209.1.1 Description: There are three general types of open structures addressed by this standard (See 102.1(6) for
graphic description):
1. Unenclosed attached (3 sides open)
2. Unenclosed portions of the main building (1 or 2 sides open)
3. Open unattached (all sides open).
Examples of open structures are porches, carports, and decks.
209.1.2 Foundations: For unenclosed attached structures, other than that for the common wall with the main build-
ing, foundations shall be in accordance with 203 for a one-story building of the same size as the attached structure.
The foundation for the common wall shall be as required for the main building.
209.1.3 Common Walls: The common wall is the wall between an unenclosed attached structure and the main build-
ing. No increase in shear segment requirements shall be required for the common wall due to the attached structure.
One vertical No. 5 shall be provided at the juncture of the common wall and the ends of the attached structure (See
Figure 209B).
209.1.4 Bond Beam/Lintels: Bond beam/lintels or precast elements shall be rated for the applicable superimposed
uplift and gravity loads of Tables 209A, 209C and 209E or shall be in accordance with 205.8, Beams Spanning
Openings.
209.1.5 Posts: Posts shall be constructed of standard masonry units or pilaster block or may be cast-in-place con-
crete. Maximum post height (to the top of the bond beam) shall be 10 feet. Posts shall contain the following minimum
reinforcement without column ties:
1. 8" x 8": 1 #5 in the center.
2. 8" x 16": 1 #5 in each cell.
3. 16" x16" L-shaped (3-cell): 1 #5 in each cell.
4. 12" x12" & 16"x16": 4 #5 one in each corner.
209.1.6 Columns: Columns shall be constructed of masonry units or pilaster block or may be cast-in-place concrete.
Maximum column height (to the top of the bond beam) shall be 10 ft. Columns shall contain a minimum of four verti-
cal bars, one in each corner.
1. Vertical column reinforcement shall be four No. 3 bars for 8x8 inch columns and four No. 5 bars for all other
column sizes.
2. Clearance from the vertical bar to the masonry unit shall be 1/2 inch. Minimum cover for cast-in-place
columns shall be 1 1/2 inches over the column ties.
3. Lateral ties of a minimum 1/4 inch diameter shall be used to enclose vertical column reinforcement as follows:
1. Maximum vertical spacing of lateral ties shall not exceed the least nominal cross sectional dimension of
the column.
2. Lateral ties may be placed in the mortar joint (provided they are no larger than 1/4 inch diameter) or
they may be placed in the grout.
3. The bottom lateral ties shall be located vertically not more than one-half the lateral tie spacing above
the top of the footing, slab, or beam in any story. The top lateral tie shall not be more than one-half a lat-
eral tie spacing below the lowest horizontal reinforcement in the beam above.
209.1.7 Connection: The connection of columns and posts to the foundation below and to the bond beam at the top
shall be as follows:
1. 8x8 inch: one No. 5 standard 90° hook into the support at the bottom and into the bond beam at the top.
2. 8x16 inch: two No. 5 standard 90° hooks (one in each cell) both at the bottom and at the top.
3. 12x12 inch and 16x16 inch:
Bottom: Four No. 5 standard 90° hooks (one at each vertical bar) extending from the foundation and spliced
with the vertical reinforcement;
Top: For corner columns or posts, three No. 5 standard 90° hooks into the bond beam, minimum, each
spliced to a vertical bar. For columns located other than at a corner, two No. 5 standard 90° hooks into the
bond beam shall be spliced to separate vertical bars.
4 13 21 30 31 43 56 60 90 100
1. Unenclosed attached structures include but are not limited to carports, porches, and decks.
2. Uplift loads:
a. Y L/2 : Length of attachment (Y) is less than or equal to 1/2 of building dimension to which attached (L/2) (See Figure 209B).
b. Y > L/2 : Length of attachment (Y) is greater than 1/2 of building dimension to which attached (L/2) (See Figure 209B).
c. Total uplift at the top of the common wall for sizing connectors (if a single connector is used for both roofs) shall be determined by adding
the appropriate uplift of this table to that of Table 208E. Also, if the roofs coincide, an uplift value assigned to the overhang of the main
structure may be deducted as follows:
31 plf for 90 mph zone.
43 plf for 100 mph zone.
56 plf for 110 mph zone.
EXAMPLE 1: 110 mph: For a one-story structure with a 20 ft wide attachment adjoining the 32 ft endwall of a 48 ft long building; roofs do
not coincide; Y > L/2.
Required uplift rating for attached structure connector = 281 plf
EXAMPLE 2: 110 mph: For a one-story structure with a 20 ft wide attachment adjoining the 48 ft sidewall of a 32 ft wide building; roofs
coincide and a single connector is used for roofs on both sides; Y L/2:
Uplift from main building including overhang = 617 plf (Table 208E, by interpolation)
3. Total gravity loads for sizing beams and lintels in the common wall are determined in the same manner as for uplift above. Add the appropriate
gravity load for the attached structure from this table to that of appropriate Table 205P1 to 205P3. An overhang value of 60 plf attributed to the
main building overhang may be deducted if the roofs coincide.
4. Values in this table may be interpolated.
FIGURE 209B
UNENCLOSED ATTACHED STRUCTURES
TABLE 209C
ADDITIONAL UPLIFT REQUIREMENTS
FOR UNENCLOSED PORTIONS OF BUILDINGS
4' 27
8' 53
12' 80
16' 106
20' 133
NOTES:
1. Welded wire fabric is required for the slab of the unenclosed area. Slab shall be keyed or interlocked with wall and foundation (i.e.
stemwall header block foundation or monolithic foundation).
2. Posts may be used instead of columns when supporting a roof and/or deck only and Wall A is loadbearing.
3. Wood beams/drag struts shall be allowed if connections meeting the requirements of Table 305L1 or Table 305L2 are met.
FIGURE 209D
REQUIREMENTS FOR UNENCLOSED PORTIONS OF MAIN BUILDING
NOTES:
1. Beams shall be precast units rated for the appropriate above superimposed uplift and gravity loads or shall be in accordance with 205.2.
2. Uplift and gravity loads are superimposed (at top of beam). Values include up to a 2 ft overhang and shall be used for sizing beams and
truss anchors.
3. Corner post shall be 16 inches by 16 inches.
FIGURE 209F
OPEN UNATTACHED STRUCTURES
209.4.2 Post spacing in open unattached structures shall be in accordance with Table 209G.
TABLE 209G
MAXIMUM SPACINGS OF POSTS
0-200 24 24 24
300 22 24 24
400 18 24 24
500 15 24 24
600 13 24 24
700 11 23 24
800 10 20 24
210.1 STUCCO
Application of stucco (portland cement plaster) shall be in accordance with ASTM C 926, Application of Portland
Cement Based Plaster.
TABLE 210A
METAL TIES FOR BRICK VENEER
FIGURE 210B
TYPICAL WALL SECTIONS – BRICK VENEER ON CONCRETE MASONRY WALLS