You are on page 1of 33

INDUSTRIAL

CURRENT
MONITORING
HANDBOOK
Specialist in Electrical
Current Monitoring
Selection Guide
Transducers and Relays - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2
Current Transformers - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 3
Current Indicators and Voltage Transformers - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 4
Current Transformer Ratios & Window Openings - - - - - - - - - - - - - - - - - - - - - - - - - - 5
Transducers
AC Current to 0-5 Vdc - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 6
AC Current to 4-20 mA, 2-wire - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 8
AC Current to 4-20 mA, 4-wire - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -10
AC Voltage to 4-20 mA, 3-phase - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -12
Relays
AC Current Sensing Relay - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -14
Transformers
High Ratio Current Transformers - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -16
Vertical Mounting, PCB Current Transformers - - - - - - - - - - - - - - - - - - - - - - - - - - - -18
Wire Lead Current Transformers - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -20
Commercial and Metering Class Current Transformers - - - - - - - - - - - - - - - - - - - - - -22
Horizontal Mounting, PCB Current Transformers - - - - - - - - - - - - - - - - - - - - - - - - - -27
Indicators
Wire-Mounted Current Indicator - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -28
Remote Current Indicators - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -30
AC Motor Loads & US Standard Voltages - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -32

Custom Toroid and Bobbin Wound Transformers


Commercial Grade - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -Contact Factory
Military and Aerospace Grade - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - ”
Application Sheets
Excitation Curves - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -Contact Factory
Current Transformer Ratio Error - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - ”
Application Guide - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - ”
Glossary of Terms - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - ”
3-Phase Balanced & Open Leg Networks - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - ”
Other CR Magnetics Catalogs
Rectangular Current Transformers - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -CR30
Wound Primary Current Transformers - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -CR40
Bar Type Current Transformers - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -CR50
Ground Fault and Open Phase Detection - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -CR70
Split-Core Current Transformers - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -CR80
Low Voltage Voltage Transformers - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -CR90
Multi-Ratio Current Transformers - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -CR100
Laboratory Grade Current Transformers - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -CR110
3-Phase Current Transformers - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -CR120
Medium Voltage Current Transformers - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -CR130
Medium Voltage Voltage Transformers - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -CR140
Instrumentation Switches - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -CR160

© 1998 CR Magnetics, Inc. — All rights reserved.

1 © 1998 CR MAGNETICS, INC.


Selection Guide

TRANSDUCERS and RELAYS


Transducers Relays

Part Number CR4310 CR4320 CR4340 CR473 CR4395

AC Current 2-Wire AC 4-Wire AC Voltage to Current


Description to Voltage Current Transmitter Current Transmitter 4-20 mA Sensing
Transducer to 4-20 mA to 4-20 mA Transmitter Relay

Frequency 50/60 Hz 50/60 Hz 50/60 Hz 50/60 Hz 60/400 Hz

.01-0.1 ACA

5 thru 200 5 thru 400 5 thru 600 90-150 Vac 1-10 ACA
Input 3-30 ACA
180-300Vac
Range Amps AC Amps AC Amps AC 6-60 ACA
360-600 Vac
10-100 ACA

Output 5.0 Volts DC 4-20 mA Current 4-20 mA Current 4-20 mA Current Dry Contacts
Loop Loop Loop

Accuracy 0.5 thru 1.0% F.S. 0.5% F.S. 0.5% F.S. 0.5% F.S. —

Dimensions
2.75 x 2.69 x 2.36 4.50 x 2.68 x 2.37
(5 thru 200 ACA) (5 thru 75 ACA)
(H)x(W)x(D) 2.75 x 2.69 x 2.36 4.88 x 4.50 x 4.68 4.88 x 4.50 x 4.68 3.63 x 4.19 x 4.38 2.13 x 3.50 x 2.5
(300 thru 400 ACA) (100 thru 600 ACA)

Power
Source Self-Powered Loop-Powered 120 Vac Loop-Powered 120 Vac

Agency
Approval UL UL UL UL

Located on
Page #...
6 8 10 12 14
in Main
Catalog

CR Magnetics, Inc. 544 Axminister Dr. Fenton MO 63026 (314) 343-8518 FAX (314) 343-5119
2
© 1998 CR MAGNETICS, INC.
Selection Guide

CURRENT TRANSFORMERS
Current Transformers

17,18, 19 CR8750 CR8300 CR8400


High Horizontal Vertical Wire Commercial & Split Medium
Ratio Mount Mount Lead ANSI Class Core Voltage
C/T C/T C/T C/T C/T C/T C/T

60-400 Hz 50-400 Hz 50-400 Hz 50-400 Hz 50-400 Hz 50-400 Hz 50-400 Hz

Up to Up to Up to — Up to Up to Up to
60 ACA 60 ACA 100 ACA 4,000 ACA 10,000 ACA 3,000 ACA

— — — — 5.0, 1.0 5.0 ACA &


5.0 ACA
0.2, 0.1 ACA High Ratios

— — — — Up to 0.3% Up to 0.3% Up to 0.3%

.29 & .55 .272 to .504 .232 to .610


.250 Window Window Window See Catalog See Catalog See Catalog
Window

— — — — — — —

UL UL
— — — — CSA CSA UL

Request Request
16 27 18 20 22 Catalog Catalog
# CR80 # CR130
E-MAIL: sales@crmagnetics.com WEB SITE: crmagnetics.com
3
© 1998 CR MAGNETICS, INC.
Selection Guide

CURRENT INDICATORS
AND VOLTAGE TRANSFORMERS
Indicators Voltage Transformers

Part Number CR45 Model 18 & 19

Low Medium
Wire Mounted Remote Voltage Voltage
Description Current Indicator Current Indicator V/T V/T

Frequency 50/60 Hz 50/60 Hz 60 Hz 60 Hz

Input 2 thru 100 2 thru 100 Up to Up to


Range ACA ACA 600 Vac 34.5 kV

Output Visual Visual 120 Vac 120 Vac

Accuracy Up to 0.3% Up to 0.3%

Dimensions 1.29 x .95 x .46


(H)x(W)x(D)
See Page 30 See Catalog See Catalog

Power Self-Powered — —
Source Self-Powered

Agency UL UL
Approval CSA CSA
Located on Request Request
Page #...
in Main 28 30 Catalog Catalog
Catalog # CR90 # CR140

4 © 1998 CR MAGNETICS, INC.


Current Transformer
Ratios & Window Openings

Changing Current Transformer Ratios

The actual current ratio may be changed from the — for X1 Lead wound from H1 side through window opening
nameplate ratio by wrapping the primary and/or (As shown in illustration below)
secondary leads through the window opening. + for X1 Lead wound from side opposite H1

NUMBER OF SECONDARY TURNS


ACTUAL NAMEPLATE RATIO ± THROUGH WINDOW OPENING
TURNS =
RATIO NUMBER OF PRIMARY TURNS
THROUGH WINDOW OPENING

The illustration shows how a standard


Example:
125:5 nameplate ratio transformer can be
rescaled to provide a non-standard 55:5
current ratio.

125
— 3
5
PRIMARY = 11
(55 ACA) 2

SECONDARY Turns Ratio = 11:1


(5 ACA) Current Ratio = 55:5

Window Openings

The current transformer window opening should be Number of


sized according to the outside diameter of the wire Wires Through K
and the number of wires, with ample clearance added Opening
to facilitate installation. 2 2
Use the following formula for multiple wires of the 3 2.165
same diameters through the current transformer 4 2.414
window opening. 5 2.704
6 3.0
Minimum Outside 7 3.0
Window = K x Wire 8 3.73
Diameter Diameter 9 3.83

5 © 1998 CR MAGNETICS, INC.


Precision, AC Current to
Voltage Transducer

The CR4310 series, Current-to-Voltage Transducer


produces a 0-5 Vdc output signal that is directly
proportional to the input AC current. The output
signal is average-sensing, calibrated for RMS.

This transducer is used with process control and


industrial instrumentation equipment. The DC output
signal can be connected directly to a high impedance
analog input of a computer or PLC without additional
signal conditioning.

The CR4310 series will measure up to 200% of full


scale on a short time basis (1 minute or less) and
150% on a continuous basis at its rated accuracy.

To protect external circuits from damage caused by


short circuits or motor inrush currents, the output is
limited to 12 Vdc.

Features

• Permanently calibrated Part Numbers


• Output overload protected
• Fully isolated ® CR4310- ❑ ❑ ❑ CURRENT TO VOLTAGE TRANSDUCER
• 10 different ranges E154235
• Self-powered, requires no external Load
Range in AC Accuracy Resistance in
power source Amps % FS OHMS *
5 0-5 1.0 1 MEG
Specifications 10 0-10 0.75 800K
15 0-15 0.75 800K
Accuracy: 20 0-20 0.5 400K
Depends on the range and load resistance, see 30 0-30 0.5 400K
Part Numbers table 50 0-50 0.5 160K
Ripple: 75 0-75 0.5 160K
1% Max. peak ripple on output 100 0-100 0.5 80K
Calibrated Signal Out: 150 0-150 0.5 80K
0-5 Vdc 200 0-200 0.5 80K
Response Time:
250 ms max., 10-90% FS
Max. Signal Out:
12 Vdc
Frequency: * Load Resistance that will provide the rated accuracy.
50/60 Hz Higher resistance will improve accuracy.
Insulation Class:
600 V, BIL 10 kV Full Wave
Operating Temperature Range:
-30°C to +60°C

6 © 1998 CR MAGNETICS, INC.


Precision, AC Current to
Voltage Transducer
Application Notes

2.69

1.69 .50 10

OUTPUT VOLTS, DC
8

6
2.36 5
4
2.00
2

0
.25 0 25 50 75 100 150 200 250 300
#10-32
SCREWS PERCENTAGE FULL SCALE (FS)
.93 DIA.

CONTROL VOLTAGE OUT


VS
FULL-SCALE INPUT CURRENT
2.75

TOTAL LOAD RESISTANCE


0-5 VDC
.15 - +
OUTLINE DRAWING
INTERCONNECT
INSTRUMENTATION
RESISTANCE
RESISTANCE
I PRIMARY

TYPICAL CONNECTIONS

Typical Applications

EXTERNAL CURRENT TRANSFORMER 3-PHASE SYSTEMS


An external current transformer may be used with the transducer by Three-phase systems may be monitored by attaching three transducers
routing the secondary leads through the window opening. Use the in series. The total output voltage will be the sum of each individual
CR4310-5 current transducer with a 5 Amp secondary instrument grade transducer. If each transducer is sized for the full-scale current, the
current transformer. For additional details on current transformers, see output voltage will be 0-15 Vdc for 0 to 100% full-scale. As an alternate,
page 22. each transducer may be sized for 3 times the full-scale current, then the
output voltage will be 0-5 Vdc for 0 to 100% full-scale.

CR Magnetics, Inc. 544 Axminister Dr. Fenton, MO 63026 (314) 343-8518 FAX (314) 343-5119
7 © 1998 CR MAGNETICS, INC.
2-Wire Current Transmitter,
4-20 mA Output

The CR4320 series, loop-powered, 2-Wire Current


Transmitter produces a calibrated 4-20 mA. DC
output current directly proportional to the average
RMS value of the input alternating current. The
controlled current output is unaffected by variations
in supply voltage, interconnect and load impedance
(within specification limits) to provide a highly accu-
rate means for monitoring alternating current over
long distances.

Features

• Permanently calibrated
• Loop-powered ®
• Fully isolated E154235
• 12 different ranges Case Style 2
• 2 case styles, .93” and 1.25” window opening
• Output overload protected Case Style 1

Specifications Part Numbers


Accuracy:
CR4320 - ❑ ❑ ❑ 4-20 MA CURRENT TRANSMITTER
±0.5% Full-Scale (FS)
Repeatability:
Less than 0.1% Full-Scale (FS) Case
Range in AC Amps Style
Ripple & Noise:
1% Max., peak to peak 5 0-5 1
Calibrated Signal Out: 10 0-10 1
4-20 mA DC 15 0-15 1
Response Time:
20 0-20 1
200 ms max., 10-90% FS
30 0-30 1
Max. Signal Out:
30 mA DC 50 0-50 1
Temperature Coefficient: 75 0-75 1
± 0.04%/°C 100 0-100 1
Supply Voltage: 150 0-150 1
24 Vdc ±10% 200 0-200 1
Frequency: 300 0-300 2
50/60 Hz 400 0-400 2
Output Load:
0 to 600 ohms
Insulation Class:
600 V, BIL 10 kV Full Wave
Reverse Polarity Protection:
Yes
Operating Temperature Range:
-30°C to +60°C
Storage Temperature Range:
-55°C to +85°C
8 © 1998 CR MAGNETICS, INC.
2-Wire Current Transmitter
4-20 mA Output
Application Notes

4.50 2.69 28
3.50 .50
1.69 .50 24

OU T P U T C U R R E N T
20

D C MA .
16

4.68 2.36
12
4.12
2.00
8

4
.44 TYP. .25
#8-32 1.25 # 10-32
TERMINALS DIA. 25 50 75 100
SCREWS
.93 DIA.
P E RCE NT A GE F UL L - S CA L E ( F S )

CONTROL CURRENT OUT


4.88
2.75 VS
FULL-SCALE INPUT CURRENT
.06

.15
Case Style 2 Case Style 1
0 to 600 ohms
+ —
INTERCONNECT INSTRUMENTATION
RESISTANCE RESISTANCE
I PRIMARY
I CONTROL

I PRIMARY 24 Vdc
I CONTROL X 16 + 4
FS
FS = FULL-SCALE CURRENT IN AMPS RMS
I PRIMARY = MONITORED CURRENT IN AMPS RMS
I CONTROL = LOOP CURRENT IN mA dc

Typical Applications

An external current transformer may be used with the transmitter by The scaling factor may be changed by threading the primary current-
routing the secondary leads through the window opening. Use the carrying wire several times through the window opening. The "actual"
CR4320-5 current transmitter when using a 5 Amp secondary instrument measurement range will be the name plate range divided by the number
grade current transformer. For additional details on current transformers, of wire passes. For example, the CR4320-30 has the name plate range
see page 22. of 0-30 ACA. Two passes of the wire through the window opening will
then provide an effective range of 0-15 ACA (30÷2).

CR Magnetics, Inc. 544 Axminister Dr. Fenton, MO 63026 (314) 343-8518 FAX (314) 343-5119
9 © 1998 CR MAGNETICS, INC.
4-Wire Current Transmitter
4-20 mA Output

The CR4340 series, 4-Wire Current Transmitter pro-


duces a calibrated 4-20 mA DC signal proportional to
the average RMS value of the input alternating cur-
rent. The output signal is produced by an internal
current generator powered by an external 120 Vac
supply. The output signal is unaffected by variations
in interconnect and load impedance (within specifica-
tion
limits) thus providing a highly accurate means for
monitoring alternating current over long distances.

The 4-wire transmitter allows for direct attachment to


instrumentation. There is no need for external DC
power as required with 2-wire transmitters.

Features
• Permanently calibrated
Case Style 2
• Supply, signal and input fully isolated Case Style 1
• Output overload protected
• 13 different ranges - 6 field selectable
• Internal current generator Part Numbers
• 2 case styles, .94” and 2.13”
window opening
® CR4340 - ❑ ❑ ❑ 4-WIRE CURRENT TRANSMITTER
• Monitors over long distances E154235

Full-Scale (FS) Case


Specifications Range in AC Amps Style

Accuracy: 5 0-5 1
±0.5% Full-Scale (FS) 0-10*
Ripple & Noise: 20 0-15* 1
1% Max., peak to peak 0-20*
Calibrated Signal Out: 0-25*
4-20 mA DC
75 0-50* 1
Response Time:
150 ms max., 10-90% FS
0-75*
Max. Signal Out:
30 mA DC 100 0-100 2
Temperature Coefficient: 150 0-150 2
± 0.02%/°C 200 0-200 2
Supply Voltage: 300 0-300 2
120 ±10% Vac 400 0-400 2
Frequency: 600 0-600 2
50/60 Hz
Output Load:
0-1000 ohms
* RANGE SET WITH FIELD SELECTABLE SWITCH
Insulation Class:
600 V, BIL 10 kV Full Wave
Operating Temperature Range:
-30°C to +60°C
Storage Temperature Range:
-55°C to +85°C 10 © 1998 CR MAGNETICS, INC.
4-Wire Current Transmitter
4-20 mA Output
Application Notes

4.50 28
2.68
3.50 .50
1.70
24

OUTPUT CURRENT DC MA.


20
2.37
4.68 1.97
16
4.12

.23 12
#6-32 TERMINALS RANGE SWITCH
.44 TYP. 4 PLACES 8
#8-32 TERMINALS
4 PLACES 2.13
DIA.
AC AC + - 4
AC AC

25 50 75 100
4.88 4.50 PERCENTAGE FULL-SCALE (FS)

CONTROL CURRENT OUT


.06
.94 DIA. VS
FULL-SCALE INPUT CURRENT
Case Style 2 Case Style 1
0 to 1,000 ohms

120 ± 10% + —
Vac
INTERCONNECT
INSTRUMENTATION
RESISTANCE
RESISTANCE
I PRIMARY - I CONTROL

FS = FULL-SCALE CURRENT IN AMPS RMS


I PRIMARY
I CONTROL X 16 + 4 I PRIMARY = MONITORED CURRENT IN AMPS RMS
FS I CONTROL = LOOP CURRENT IN mA dc

Typical Applications

An external current transformer may be used with the transmitter by The scaling factor may be changed by threading the primary current-
routing the secondary leads through the window opening. Use the carrying wire several times through the window opening. The "actual"
CR4340-5 current transmitter when using 5-Amp secondary instrument measurement range will be the name plate range divided by the number
grade current transformer. For additional details on current transformers, of wire passes. For example, the CR4340-30 has the name plate range
see page 22. of 0-30 ACA. Two passes of the wire through the window opening will
then provide an effective range of 0-15 ACA (30÷2).

CR Magnetics, Inc. 544 Axminister Dr. Fenton, MO 63026 (314) 343-8518 FAX (314) 343-5119
11 © 1998 CR MAGNETICS, INC.
3-Phase Voltage Transmitter
4-20 mA Output

The CR473 series, Voltage Transmitters are expand-


ed scale instruments designed to accurately measure
three-phase voltages. Each model produces three
discrete 4-20 mA signals which are proportional
(across the selected input voltage range) to the
three-phase input voltage. The output is a true con-
stant current driver which is unaffected by resistance
variations in the output loop of 0-600 ohms. The
CR4730 is designed to measure line-to-line voltages
and the CR4731 to measure line-to-neutral. Both are
average-reading, calibrated to read RMS.

Features
• Permanently calibrated
• Fully isolated
• ANSI/ISO 50.1 Class L3
®
E154235

Specifications

Nominal Input Voltages: Load Resistance:


120, 240, 277 & 480 Vac 0-600 OHMS
Accuracy: Frequency:
±0.5% Full-Scale (FS) 50/60 Hz
Ripple On Output: Max. Continuous Input Voltage:
Less than 1% 600 V
Calibrated Signal Out: Operating Temperature Range:
4-20 mA DC -30°C to +60°C
Response Time: Storage Temperature Range:
1.50 sec. max., 10-90% FS -50°C to +85°C
Temperature Coefficient: Shipping Weight:
± 0.03%/°C Approx. 1.3 Pounds
Supply Voltage: Reverse Polarity Protection:
24 Vdc ± 10% Yes

PART NOMINAL INPUT BURDEN TRANSFER


NUMBERS APPLICATION VOLTAGE VOLTAGE (MAX) FUNCTION
RANGE RANGE ILOOP
EIN - 75
CR4730-120 Line-to-line 120 V 90 V to 150 V 0.1 VA @ 240 V 3.75
EIN - 150
CR4730-480 240 V 180 V to 300 V 0.1 VA @ 265 V 7.5
Line-to-line
(Dual Range) EIN - 300
480 V 360 V to 600 V 0.1 VA @ 530 V 1.5
EIN - 75
CR4731-120 Phase-to-neutral 120 V 90 V to 150 V 0.1 VA @ 150 V 3.75
EIN - 150
CR4731-277 Phase-to-neutral 277 V 180 V to 300 V 0.1 VA @ 300 V 7.5
12 © 1998 CR MAGNETICS, INC.
3-Phase Voltage Transmitter
4-20 mA Output
Outline Drawings

4.19 3.63
2.13 3.19

3.44

10
11
12
7
8
9
3.94

1
2
3
4
5
6
4.38

Typical Connection Diagrams

TOTAL LOAD RESISTANCE


RANGE IN CONNECTIONS 0-600 OHMS, EACH PHASE
MODEL 1 7
VOLTS L1 - L2 - L3
L1 - L2 OUTPUT I LOOP
360 TO 600 1-3-5 2 8
CR4730-480 L2 - L3 OUTPUT I LOOP
180 TO 300 2-4-6 3 9
L3 - L1 OUTPUT I LOOP
CR4730-120 90 TO 150 2-4-6 4 10
5 11
+ -
6 12 24 VOLT

CR4730-120 AND CR4730-480


LINE-TO-LINE

NEUTRAL
TOTAL LOAD RESISTANCE
0-600 OHMS, EACH PHASE
1 7
L1 L1 - N OUTPUT I LOOP
2 8
L2 - N OUTPUT I LOOP
3 9
L2 L3 - N OUTPUT I LOOP
4 10
5 11
L3 + -
6 12 24 VOLT

CR4731-120 AND CR4731-277


PHASE-TO-NEUTRAL

CR Magnetics, Inc. 544 Axminister Dr. Fenton, MO 63026 (314) 343-8518 FAX (314) 343-5119
13 © 1998 CR MAGNETICS, INC.
Current Sensing Relay

The CR4395 series, Current Sensing Relay provides


an effective and highly stable method for monitoring
electrical current. The current-carrying wire is routed
through the opening extending from the top of the
case. When current reaches the level set by the trip
point adjustment, the relay trips and starts the
adjustable timer. After the timer cycles the electro-
mechanical relay is energized. A precision voltage
reference circuit ensures a highly repeatable trip
point. Design of the power-on delay circuitry allows
the supply power to be repeatedly cycled on and off,
without affecting the stability of the current sensing
operation. Calibrated Dial
Option Shown
Applications
• Monitor electrical heater elements Features
• Sense motor over/under loads Variable trip point and time delay

• Detect lamp burn-out Monitors currents from 10 mA to 60 AC Amps

• Indicate phase loss Electrical isolation between circuits

• Output relay rated up to 20 Amps
Specifications
• LED trip status indicator
Mounting: • Dead band prevents relay chatter
2 - 3/16” dia. clearance holes on 1 15/16” by • Calibrated dial option available
2 15/16” centers • External current transformers available
Environmental:
Operating Temperature: -30°C to +60°C
Storage Temperature: -55°C to +85°C Part Numbers
Power-On Delay: 100 ms max
Hysteresis: 5% Max. CR4395 - ❑❑ - ❑❑❑ - ❑❑❑ - ❑ - ❑❑ - ❑
Input Supply Power:
Terminals: 2 - 1/4” Male Q C
Operating Class: 600 V
Sensed Current: RELAY TRIP
Max. Continuous: 200% Full Scale STATUS
Frequency: 60-400 Hz EH-Relay Energized on TIME ON DELAY**
high current (above A - .5 to 6 Sec.
Output Relay: trip point) B - 2 to 25 Sec.
Arrangement: 1 Form C (SPDT) EL-Relay Energized on X - none
Contact Material: Silver-cadmium oxide low current (below
Terminals: 3 - 1/4” Male Q C trip point) TRIP RANGES*
Mechanical Life: 10 million operations, typ.@ rated load *The trip ranges shown 110 - 1.0 to 10 ACA
Electrical Life: 100,000 operations, typ. @ rated load are for one wire pass 330 - 3.0 to 30 ACA
through the window open-
Initial Contact resistance: ing. The trip range may be 660 - 6.0 to 60 ACA
proportionally lowered with 101 - 10 to 100 ACA
50 milliohms max. @ 500 mA, 12 Vdc additional wire passes .01.1 -.01 to 0.1 ACA
Contact Rating: UL508/873 & CSA through the window. See
illustration on page 15. .11 - 0.1 to 1.0 ACA
**Minimum Range.
LOAD N.C. N.O. SUPPLY VOLTAGE
VOLTAGE
TYPE CONTACT CONTACT 120-120 Vac ± 10%
240 Vac Resistive 20A 10A
240 Vac Motor 2HP 1/2HP TRIP POINT DIAL
OPTIONS
125 Vac Motor 1HP 1/4HP - Non-calibrated Dial
- none
28 Vdc Resistive 20A 10A CD - Calibrated Dial
L - Latching
FP - Fixed Set Point
EF - Extended Frequency Range
© 1998 CR MAGNETICS, INC. 14 T - Transistor Output
Current Sensing Relay
Outline Drawings Timing Diagram

SUPPLY POWER TERMINALS OUTPUT RELAY TERMINALS POWER-ON DELAY


1/4" MALE QUICK CONNECT 1/4" MALE QUICK CONNECT
TYPICAL 3 PLACES LED ON
TYPICAL 2 PLACES
TIME ON DELAY

3/16 DIA. MOUNTING HOLE RELAY ENERGIZED


NC NO COM TYPICAL 2 PLACES
RELAY DE-ENERGIZED
INDICATING LED
"ON" WHEN RELAY IS TRIPPED
3 1/2
TIME-ON DELAY ADJUSTMENT

MAX
TURN CLOCKWISE TO INCREASE

TRIPPED CURRENT TRIP


25
2 15/16

30
MIN
20
TRIP POINT

15
EH - version

3
10

CURRENT TRIP
5
SENSED CURRENT

MAX
MIN
9/32 1 15/16 9/32
7/8 SENSED CURRENT
2 1/8 .50 DIA.
2 1/2 EL - version
MAX. Non-Calibrated Dial TRIP POINT
X-Option

CALIBRATED DIAL OPTION (CD) SHOWN


Typical Applications

CR

CR
30
25
20

30
25
20
15

15
3
10

3
10

5
M

EXTERNAL CURRENT TRANSFORMERS MOTOR OVER / UNDER MONITOR


The relay may be used with an external split or solid-core current The relay may be used to monitor the operational load of a motor. One
transformer. The external transformer can be used to access remote leg of the motor wiring is routed through the window opening. With the
loads or where the current-carrying wire is too large to fit through the "EH" (Energized on High) option, when the motor current draw exceeds
window opening in the relay. A standard, 5 Amp secondary, commercial the trip point, the relay will energize and open the motor starter. The time
grade current transformer (see page 22) would be attached with the delay would be set long enough to inhibit tripping during high inrush
secondary leads threaded twice through the window opening, as starting current. Note that an electrical fuse and other overload devices
illustrated. The trip range option "110" (1.0 to 10 ACA) would then may still be required for complete circuit protection.
provide full-scale adjustment for the transformer.

"A"
30
25
20

"B"
15

3
10

ONE-WIRE PASS THREE-WIRE PASS OPEN HEATER / LAMP DETECTOR


The relay may be used to provide an alarm signal to indicate an open
The trip ranges shown on page 14 represent one wire pass through the heater element. The current-carrying wire is routed through the window
window opening. The trip range may be changed by threading the opening. With the"EL" (Energized on Low current) option, when the
current-carrying wire through the window opening several times, as heater element draws current above the trip point, the relay remains de-
shown above. The "actual" trip range would be the relay name plate energized. If the element becomes open, the current level will be
range divided by the number of wire passes through the opening. For reduced, causing the relay to become energized. Supply power is
example, a name plate range of 6.0 to 60 ACA with three passes would constantly supplied to the relay with the "A" connection and the relay will
provide an actual range of 2.0 to 20 ACA (6÷3=2.0 & 60÷3=20). cycle every time the temperature controller cycles. Using the alternate
connection with line "B", power is provided to the relay only when the
temperature controller is cycled on. With this connection, the relay will
energize only when the element is open.

CR Magnetics, Inc. 544 Axminister Dr. Fenton, MO 63026 (314) 343-8518 FAX (314) 343-5119

15 © 1998 CR MAGNETICS, INC.


High Ratio
Current Transformers

CR Magnetics offers a versatile line of High-Ratio


Current Sensors. Installed around a current-carrying
wire, the sensor provides a current output relative to
the AC input current (within specification limits). With
the output connected across a resistive load (burden),
the voltage developed is proportional to the input
current.

Applications

• Remote monitoring of electrical loads


• Input to electrical control system
• Detect open heater elements
• Indicate phase loss
• Monitor motor operation

Model 19
Features
• Low cost
• Non-contact, isolated current measurement
• Surface mounting bracket available for Model 17
and Model 18
• 2 case sizes, 3 different standard ratios

Specifications

Frequency: 50-60 Hz
Working Class: 600 Vac
Case Material: Black thermoplastic

Part Numbers
Model 17 Current sensor with wire leads, .55
dia. opening, 2000 turns
Model 17-PCB Current Sensor with Printed Circuit
Board pins, .55 dia. opening, 2000
turns (see NOTE 1)
Model 17 & 18
Model 18 Current Sensor with wire leads, Shown with optional mounting bracket MB-18
.55 dia. opening, 600 turns
Model 18-PCB Current Sensor with Printed Circuit
Board pins, .55 dia. opening, 600
turns (see NOTE 1)
MB-18 Surface Mounting Bracket for
Model 17 or Model 18
Model 19 Current Sensor with .29 dia. open-
ing, 230 turns
NOTE 1: Model 17 & 18 are standard with wire leads (no
PCB pins), add -PCB after the part number for Printed
Circuit Board pins (no wire leads) 16 © 1998 CR MAGNETICS, INC.
High Ratio Current Transformers
Outline Drawings

#22 AWG UL
UL STYLE 1213
51 10
Ohm Ohm . .95
1.0

.29 DIA.
OUTPUT IN VOLTS (v)

12
1.04
0.5 NTS

1.0 Ohm .46

0.0
0 10 20 30
Model 19: 230INTurns
INPUT CURRENT AMPERES (I) Model 19: Current Sensing Transformer
Model 19 - 230 Turns

.55 DIA.
PCB pins

51 to 430 Ohm 430 200 1.48 #20 AWG UL STYLE 1015


Ohm Ohm wire leads
5.0
1.0 & 10 Ohm
10 Ohm .79
0.4 4.0
100 Ohm
OUTPUT IN VOLTS ( V )

0.3 3.0
.20
51 Ohm
0.2 2.0
.375 .48 .25
0.1 1.0 .95 .19 24
.50
1.0 Ohm 1.33 NTS
0 0
0 10 20 30 40
#4-40 INSERT-.17 DEEP .050 dia. +- .003
INPUT CURRENT IN AMPERES (I) PCB pins
Model 18
Model 18:-600
600Turns
Turns TWO PLACES
Model 17 & 18: Current Sensing Transformers
Available with wire leads or PCB pins, both shown only for illustration

430 Ohm
10.0

8.0
OUTPUT IN VOLTS ( V )

6.0 200 Ohm

.875 .25 .25 .750


4.0
1.37 1.25
100 Ohm
2.0 #6 SCREW #4-40 FLAT HEAD
51 Ohm NOT FURNISHED SCREW FURNISHED
10 Ohm
0
0 Model
20 17: 2,000
40 Turns
60
MB-18: Surface Mounting Bracket
INPUT CURRENT IN AMPERES ( I ) for Model 17 & Model 18
Model 17 - 2,000 Turns

CR Magnetics, Inc. 544 Axminister Dr. Fenton, MO 63026 (314) 343-8518 FAX (314) 343-5119

17 © 1998 CR MAGNETICS, INC.


Vertical Mounting, PCB Current
Transformers - Series 8300

Features

• Low cost
• 3 standard sizes
• Non-symmetrical mounting pattern

Applications
• Over/under current sensing
• Power monitoring
• Current measurements
CR8350

Specifications CR8349

Frequency:
50 to 400 Hz
Insulation Resistance: CR8348

100 M ohm @ 500 Vdc


SHOWN APPROXIMATELY FULL SIZE
Case Material:
Polypropylene Resin

Part Numbers And Outline Dimensions

inches
All dimensions:
(mm)

MAXIMUM
PART NUMBER OF PRIMARY
A B C D E F G H I J SECONDARY CURRENT
NUMBERS min. max. max.
± .04
max. TURNS AMPS (RMS)
(±1.0)

.272 .925 .433 .118 .984 .040 .075 .60 .75 .374
CR8348-2000 2000 30
(6.9) (23.5) (11) (3) (25) (1.0) (1.905) (15.24) (19.05) (9.5)

CR8349-1500 .354 1.024 .669 .118 1.102 .040 .075 .60 .75 .60
1500 50
(9) (26) (17) (3) (28) (1.0) (1.905) (15.24) (19.05) (15.24)

.504 1.476 .551 .118 1.535 .040 .15 1.00 1.30 .50
CR8350-2000 2000 100
(12.8) (37.5) (14) (3) (39) (1.0) (3.81) (25.4) (33.02) (12.7)

MOUNTING HOLE PATTERN


AND INTERNAL CONNECTION
TOP VIEW

18 © 1998 CR MAGNETICS, INC.


Vertical Mounting, PCB Current
Transformers - Series 8300

Output Voltage vs Sensed Current for Different Values Of Burden Resistance (R)

CR8348-2000 (.272 WINDOW) CR8349-1500 (.354 WINDOW)

1000
1000WW 1000
1000W
W 510510
WW
8 10
510 W
OUTPUT IN VOLTS RMS (V)

8
6

200 W
20
6

4
200 W
100 W
10
2
100 W 2
51
5 W
51 W
10 W 10 W
10
0 0

0 5 10 15 20 25 30 0 10 20 30 40 50
SENSED CURRENT IN AMPS
SENSED CURRENT IN AMPS RMS
RMS ( I () I ) SENSED CURRENT
SENSED CURRENT ININAMPS
AMPSRMS RMS
(I) ( I )

CR8350-20000 (.504 WINDOW)

1000 W
1000 W 510
510 W
W
15
I
OUTPUT IN VOLTS RMS (V)

20200 W
10

5 10
100 W V

51 W
5

10 W
10
0

0 20 40 60 80 100
SENSEDSENSED
CURRENT ININAMPS
CURRENT RMS
AMPS RMS ( I )( I )

CR Magnetics, Inc. 544 Axminister Dr. Fenton, MO 63026 (314) 343-8518 FAX (314) 343-5119

19 © 1998 CR MAGNETICS, INC.


Wire Lead Current Transformers
Series 8400

Features

• Low cost
• 3 standard sizes
• Non-contact, isolated measurement

Applications
• Over/under current sensing
• Ground Faults
• Current measurements
• Power monitoring

Specifications
CR8420
CR8410
Frequency:
50 to 400 Hz
SHOWN APPROXIMATELY FULL SIZE
Insulation Resistance:
100 M ohm @ 500 Vdc
Case Material:
Polypropylene Resin

Part Numbers And Outline Dimensions


inches
All dimensions:
(mm)

MAXIMUM
PART NUMBER OF PRIMARY
A B C D E SECONDARY CURRENT NOTES
NUMBERS min. max. max.
±.12
max. TURNS AMPS (RMS)
(±3.0)

.232 .827 .315 2.75 .709 NICKEL ALLOY CORE WITH


CR8401-1000 1000 30 MAGNETIC SHIELDS FOR
* (5.9) (21.0) (8.0) (70.0) (18.0)
GROUND FAULT APPLICATIONS

.350 .984 .355 2.87 .866 SILICON STEEL CORE FOR


CR8410-1000 1000 10 GENERAL PURPOSE
(8.9) (25.0) (9.0) (73.0) (22.0)
CURRENT MONITORING

NICKEL ALLOY CORE WITH


CR8420-1000 .610 1.299 .355 2.75 1.181
1000 100 MAGNETIC SHIELDS FOR
* (15.5) (33.0) (9.0) (70.0) (30.0) GROUND FAULT APPLICATIONS

* Also available with PCB pins, consult factory

20 © 1998 CR MAGNETICS, INC.


Wire Lead Current Transformers
Series 8400

Output Voltage vs Sensed Current for Different Values Of Burden Resistance (R)

CR8401-1000 (.232 WINDOW) CR8410-1000 (.350 WINDOW)


R=1,000 ohms
1000 W
1 5
510 W

4
OUTPUT IN VOLTS RMS (V)

0.1
3

2 200 W
0.01

1 100 W

51 W

0.001 0 10 W
0.001 0.01 0.1 1 10 0 2 4 6 8 10
SENSED CURRENT IN AMPS RMS ( I ) SENSED CURRENT IN AMPS RMS ( I )

CR8420-1000 (.610 WINDOW)


R=1,000 ohms
10

1
OUTPUT IN VOLTS RMS (V)

R V
0.1

0.01

0.001
0.001 0.01 0.1 1 10
SENSED CURRENT IN AMPS RMS ( I )

21 © 1998 CR MAGNETICS, INC.


Commercial & Metering
Class Current Transformers

The CR Magnetics line of Instrumentation Grade


Electrical Current Transformers are available in either
Commercial or ANSI Metering Class. The commercial
class transformers are lower cost and well-suited for
current monitoring applications. The ANSI metering
class transformers are higher-cost units intended for
power monitoring applications where high accuracy
and minimum phase angle error are required. Nine
different window openings and eight different mount-
ing styles along with numerous secondary ratios are RL SFT
available to meet most applications. This short form
catalog shows an overview of our most popular 5
amp secondary transformers. Contact factory for dif-
ferent sizes or unique electrical requirements.

Applications
SFL SHT
• Ammeters
• Energy Management ®
• Watt/VAR/Watthour Transducers,
• Current Sensing Relays, see pages 14 & 15

Part Numbers
❑❑❑❑-❑❑❑-❑❑❑
SHL RT
MOUNTING STYLES
RL Round with leads
SFT Square with feet & terminals
SFL Square with feet & leads
SHT Square without feet & with terminals
SHL Square without feet & with leads
RT Round with terminals
RBT Round with bracket & terminals
RBL Round with bracket & leads

SERIES WINDOW RBT RBL


DIAMETER
CR1A 0.64
CR2 1.13
CR2DA 1.00
XXX Specifications
CR5 1.56
CR5A 1.56
Frequency: 50-400 Hz
CR6A 2.06
x10 Insulation: .6 kV, BIL 10 kV Full Wave
CR7 2.50
CR7A 2.50 MULTIPLIER *
CR8 3.25 FIRST TWO
NUMBERS OF
CR56 2.06
PRIMARY CURRENT
Specials
CR76 3.00
CR170 4.25 RATING *
• Ultra low frequency to 20 Hz
*Example: 50 AMP primary current
rating would read 500, 300 AMP would • Water Proof
read 301 and 4000 AMP would read • High volume, low cost styles
402.
• 1.0, 0.2 & 0.1 ACA secondary ratios available

All current transformers are standard with sec-


ondary of 5.0 Ampere. Secondary of 1.0, 0.2 and 22 © 1998 CR MAGNETICS, INC.
0.1 Ampere may be ordered as specials.
Commercial Class Current Transformers
WINDOW BURDEN
DIMENSIONS ACCURACY
OPENING SERIES MOUNTING CURRENT VA
DIMENSION STYLE RATIO AT 60 Hz
AT 60 Hz
A B C D E F G
50:5 ±3% 2.0
RL 2.46 1.05 - - - - 60:5 ±2% 2.0
75:5 ±2% 2.0
SFT 2.68 2.00 1.75 1.60 .27 .31 80:5 ±2% 2.0
100:5 ±1% 2.0
1.13 CR2 SFL 2.68 2.00 1.75 1.60 .27 .31 120:5 ±1% 2.5
125:5 ±1% 2.5

SHT 2.71 0.95 - - - - 150:5 ±1% 4.0


200:5 ±1% 4.0
250:5 ±1% 6.0
SHL 2.71 0.95 - - - -
300:5 ±1% 8.0

RL 3.56 1.10 - - - - 50:5 ±2% 1.0


75:5 ±2% 1.5
SFT 3.78 2.15 2.75 1.77 .21 .31 100:5 ±2% 2.0
150:5 ±1% 5.0
SFL 3.78 2.15 2.75 1.77 .21 .31 200:5 ±1% 5.0
250:5 ±1% 10.0
SHT 3.83 1.09 - - - -
1.56 CR5 300:5 ±1% 12.5
SHL 3.83 1.09 - - - - 400:5 ±1% 12.5
500:5 ±1% 20.0
RT 3.62 1.13 - - - - 600:5 ±1% 25.0
750:5 ±1% 25.0
RBT * 3.90 1.25 3.88 - .44 .27 800:5 ±1% 25.0
1000:5 ±1% 25.0
RBL * 3.70 1.25 3.88 - .44 .27 1200:5 ±1% 30.0
100:5 ±2% 2.5
RL 4.70 1.10 - - - - 150:5 ±1% 5.0
SFT 4.85 2.13 3.78 1.75 .25 .31 200:5 ±1% 5.0
250:5 ±1% 5.0
SFL 4.85 2.13 3.78 1.75 .25 .31 300:5 ±1% 12.0
400:5 ±1% 15.0
2.50 CR7 SHT 4.70 1.10 - - - - 500:5 ±1% 25.0
600:5 ±1% 30.0
SHL 4.70 1.10 - - - - 750:5 ±1% 30.0
RT 4.61 1.10 - - - - 800:5 ±1% 35.0
1000:5 ±1% 30.0
RBT 4.94 1.25 5.75 6.5 .28 .28 1200:5 ±1% 35.0
1500:5 ±1% 40.0
RBL 4.70 1.25 5.75 6.5 .28 .28 1600:5 ±1% 45.0
50:5 ±3% 0.5
RL 3.50 1.09 - - - - 75:5 ±1% 0.5
100:5 ±1% 1.0
SFT 3.63 2.15 2.70 1.70 .21 .31 150:5 ±1% 2.5
200:5 ±1% 4.0
250:5 ±1% 6.0
SFL 3.63 2.15 2.70 1.70 .21 .31
2.06 CR56 300:5 ±1% 7.5
400:5 ±1% 10.0
RT 3.62 1.10 - - - - 500:5 ±1% 12.5
600:5 ±1% 15.0
RBT 3.90 1.25 3.88 4.50 .27 .44 750:5 ±1% 7.0
800:5 ±1% 8.0
1000:5 ±1% 10.0
RBL 3.70 1.25 3.88 4.50 .27 .44 1200:5 ±1% 12.5
200:5 ±1% 5.0
RL 4.50 1.09 - - - - 250:5 ±1% 5.0
300:5 ±1% 6.0
SFT 4.68 2.08 3.70 1.75 .25 .31 400:5 ±1% 10.0
500:5 ±1% 10.0
SFL 4.68 2.08 3.70 1.75 .25 .31 600:5 ±1% 10.0
3.00 CR76 750:5 ±1% 10.0
RT 4.62 1.10 - - - - 800:5 ±1% 12.5
1000:5 ±1% 10.0
RBT 4.94 1.25 5.75 6.50 .28 .28 1200:5 ±1% 10.0
1500:5 ±1% 12.5
1600:5 ±1% 12.5
RBL 4.70 1.25 5.75 6.50 .28 .28 2000:5 ±1% 15.0

1.99 50:5 ±2% 1.0


60:5 ±1% 2.0
75:5 ±1% 2.0
RL
80:5 ±1% 2.0
.64 CR1A 1.25 - - - - 100:5 ±1% 2.5
120:5 ±1% 3.0
125:5 ±1% 3.0
150:5 ±1% 4.0

* RBT and RBL mounting styles in the CR5 series are


not available in current ratios of 750:5 thru 1200:5
200:5
250:5
±1%
±1%
5.0
7.5

23 © 1998 CR MAGNETICS, INC.


ANSI Metering Class Current Transformers

CURRENT
WINDOW
DIMENSIONS ANSI METERING CLASS @ 60 Hz

RATIO
OPENING SERIES MOUNTING
DIMENSION STYLE
A B C D E F G B0.1 B0.2 B0.5 B0.9 B1.8
50:5 2.4 - - - -
60:5 2.4 - - - -
75:5 2.4 2.4 - - -
80:5 1.2 2.4 - - -
100:5 1.2 1.2 - - -
1.0 CR2DA RL 2.47 1.75
120:5 1.2 1.2 - - -
125:5 0.6 1.2 - - -
150:5 0.6 1.2 2.4 - -
200:5 0.3 0.6 1.2 - -
250:5 0.3 0.6 1.2 - -
300:5 0.3 0.3 0.6 1.2 -
100:5 1.2 - - - -
150:5 1.2 1.2 - - -
200:5 0.6 0.6 - - -
RL 3.56 1.10 250:5 0.6 0.6 1.2 - -
SFT 3.77 2.15 300:5 0.3 0.3 1.2 - -
2.75 1.77 .21 .31
1.56 CR5A SFL 3.77 2.15 400:5 0.3 0.3 0.6 1.2 -
2.75 1.77 .21 .31
SHT 3.70 1.10 500:5 0.3 0.3 0.6 1.2 -
SHL 3.70 1.10
600:5 0.3 0.3 0.6 0.6 1.2
750:5 0.3 0.3 0.6 0.6 -
800:5 0.3 0.3 0.6 0.6 -
1000:5 0.3 0.3 0.3 0.6 -
1200:5 0.3 0.3 0.3 0.3 0.6
100:5 2.4 - - - -
150:5 1.2 1.2 - - -
200:5 0.6 1.2 - - -
250:5 0.3 0.6 2.4 - -
RL 4.08 1.10 300:5 0.3 0.6 1.2 2.4 -
SFT 4.21 2.12 3.34 1.75 .25 .31
2.06 CR6A 400:5 0.3 0.3 0.6 1.2 -
SFL 4.21 2.12 3.34 1.75 .25 .31
500:5 0.3 0.3 0.6 1.2 -
SHT 4.22 1.10
600:5 0.3 0.3 0.6 0.6 1.2
SHL 4.22 1.10
750:5 0.3 0.3 0.6 0.6 -
800:5 0.3 0.3 0.6 0.6 -
1000:5 0.3 0.3 0.3 0.6 -
1200:5 0.3 0.3 0.3 0.3 0.6
1500:5 0.3 0.3 0.3 0.3 0.6
100:5 2.4 - - - -
150:5 1.2 2.4 - - -
200:5 0.6 1.2 - - -
250:5 0.6 1.2 1.2 - -
RL 4.70 1.10 300:5 0.6 0.6 1.2 2.4 -
SFT 4.85 2.13 3.78 1.75 .25 .31 400:5 0.3 0.3 0.6 1.2 -
2.50 CR7A SFL 4.85 2.13 3.78 1.75 .25 .31 500:5 0.3 0.3 0.6 1.2 -
SHT 4.70 1.10 600:5 0.3 0.3 0.6 0.6 1.2
SHL 4.70 1.10 750:5 0.3 0.3 0.6 0.6 1.2
800:5 0.3 0.3 0.6 0.6 1.2
1000:5 0.3 0.3 0.3 0.6 1.2
1200:5 0.3 0.3 0.3 0.3 0.6
1500:5 0.3 0.3 0.3 0.3 0.6
1600:5 0.3 0.3 0.3 0.3 0.6
24 © 1998 CR MAGNETICS, INC.
ANSI Metering Class Current Transformers
WINDOW

CURRENT
DIMENSIONS ANSI METERING CLASS @ 60 Hz

RATIO
OPENING SERIES MOUNTING
DIMENSION STYLE
A B C D E F G B0.1 B0.2 B0.5 B0.9 B1.8
200:5 1.2 1.2 - - -
250:5 0.6 1.2 2.4 - -
300:5 0.6 0.6 1.2 2.4 -
400:5 0.3 0.6 1.2 1.2 -
500:5 0.3 0.3 0.6 1.2 2.4
600:5 0.3 0.3 0.6 1.2 1.2
RL 5.73 1.15 750:5 0.3 0.3 0.3 0.6 1.2
3.25 CR8 SHT 5.73 1.15 800:5 0.3 0.3 0.3 0.6 1.2
SHL 5.73 1.15 1000:5 0.3 0.3 0.3 0.6 0.6
1200:5 0.3 0.3 0.3 0.6 0.6
1500:5 0.3 0.3 0.3 0.6 0.6
1600:5 0.3 0.3 0.3 0.6 0.6
2000:5 0.3 0.3 0.3 0.3 0.3
2500:5 0.3 0.3 0.3 0.3 -
3000:5 0.3 0.3 0.3 0.3 -
3200:5 0.3 0.3 0.3 0.3 -
4000:5 0.3 0.3 0.3 0.3 -
200:5 1.2 1.2 - - -
250:5 1.2 1.2 - - -
300:5 0.6 0.6 1.2 2.4 -
400:5 0.6 0.6 1.2 1.2 2.4
500:5 0.3 0.3 0.6 1.2 2.4
600:5 0.3 0.3 0.6 0.6 1.2
750:5 0.3 0.3 0.3 0.3 0.6
RL 6.73 1.25 800:5 0.3 0.3 0.3 0.3 0.6
4.25 CR170 SHT 6.73 1.28
1000:5 0.3 0.3 0.3 0.3 0.6
SHL 6.73 1.28
1200:5 0.3 0.3 0.3 0.3 0.6
1500:5 0.3 0.3 0.3 0.6 0.6
1600:5 0.3 0.3 0.3 0.6 0.6
2000:5 0.3 0.3 0.3 0.3 0.3
2500:5 0.3 0.3 0.3 0.3 0.3
3000:5 0.3 0.3 0.3 0.3 0.3
3500:5 0.3 0.3 0.3 0.3 0.3
4000:5 0.3 0.3 0.3 0.3 0.3

25 © 1998 CR MAGNETICS, INC.


Commercial & Metering Class
Current Transformers
Outline Drawings

UL 1015 #16 AWG G D MOUNTING


24" LONG (TYPICAL) HOLE PATTERN
F
A

B B

A C C C
RL RBL
D G
F
#8-32 UNC BRASS MOUNTING
TERMINAL (TYPICAL) E HOLE PATTERN

B B

A
C C
RT SFT
D G
F
MOUNTING
G D MOUNTING
E HOLE PATTERN
HOLE PATTERN
F
A
A

B B

E C C
RBT SFL

A A
B B

C C
SHL SHT

CR Magnetics, Inc. 544 Axminister Dr. Fenton, MO 63026 (314) 343-8518 FAX (314) 343-5119
26 © 1998 CR MAGNETICS, INC.
Horizontal Mounting, PCB
Current Transformer

The CR8750 series, PCB Current Transformer pro-


vides a low cost method for monitoring electrical cur-
rent. The transformer is intended to be mounted on a
Printed Circuit Board with the current-carrying wire
routed through the center window opening. A five-pin,
non-symmetrical mounting pattern ensures correct
orientation on the PCB. Two different winding ratios
are available to accommodate various applications.
The graph below illustrates how different values of
burden resistors attached to the output terminal will
provide a number of different output voltage ranges.

Specifications Part Numbers

Frequency: 60-400 Hz CR8750 - ❑ ❑ ❑ ❑ PCB CURRENT TRANSFORMER

Insulation Level: 600 V


230 TURNS
1000 TURNS

Application Notes

1.125
MIN.
.850
0.280" .425
.90 MAX. H1 X1

.250 X2
MIN. .140 .040 DIA.
.47 MAX. TYP.

0.187" Recommended Mounting Hole Window Polarity


Pattern (Top View)
Outline Drawing (Top View)

Typical Response

51 10 51 to 430 Ohm 430 200


Ohm Ohm Ohm Ohm
5.0
1.0 & 10 Ohm
1.0
10 Ohm
OUTPUT IN VOLTS (v)

0.4 4.0
I 100 Ohm
OUTPUT IN VOLTS ( V )

0.3 3.0

R V 0.5
0.2 2.0 51 Ohm

1.0 O 0.1 1.0

1.0 Ohm
0.0 0 0
0 10 20 30 0 10 20 30 40
INPUT CURRENT IN AMPERES (I) INPUT CURRENT IN AMPERES (I)

CR8750-230 CR8750-1000
27 © 1998 CR MAGNETICS, INC.
230 Turns 1000 Turns
Wire-Mounted
Current Indicator

The CR-45 series, Wire-Mounted Electrical Current


Indicators provides an effective method of monitoring
electrical current. The indicator is attached directly to
a current-carrying wire. When the current exceeds
the turn-on point, the LED will illuminate to indicate
the presence of current.

Applications
• Monitor status of heater elements
CR-45 Current Indicators
• Observe remote loads
(Shown Approx. Full Size)
• Indicate phase loss
• Monitor motor operation

Features
• Self powered
• Red or green indicator
• Easy to install
• Supplied with plastic tie
• Bright yellow case for easy identification
• Panel mounting bracket available
MB-45 Panel Mounting Bracket
(Shown Approx. Full Size)

Specifications
Min. Turn-on Point Case Material:
2 Amps for CR-45-R Thermoplastic WIRE TURN-ON MAX. WIRE
PASSES POINT DIAMETER
2.5 Amps for CR-45-G Case Color:
Indicating Range: Bright Safety Yellow RED GREEN
2 to 100 Amps (for CR-45-R) Weight: 1 2 2.5 .29
2.5 to 100 Amps (for CR-45-G) .5 oz. 2 1 1.25 .14
Max. Continuous Current: Frequency: 3 .66 .83 .13
100 Amps 50-60 Hz 4 .5 .62 .12
LED Type: Mounting Bracket Material:
N 2÷N 2.5÷N
T 13/4 Diffused Non-Magnetic Aluminum
LED Color:
Red or Green

Part Numbers

CR45 - ❑ Current Indicator with (Red or Green) LED


R-Red Indicator
G-Green Indicator
MB-45 Panel Mounting Bracket for CR-45

28 © 1998 CR MAGNETICS, INC.


Wire-Mounted Current Indicator
Outline Drawings

.31 DIA. 1.16 Max. .175 Max


.144 DIA.
TWO #6 SCREWS ± .005
.20 DIA. NOT FURNISHED 2 PLACES
.25

.781
1.04 ±.005

1.562
±.005
.203 DIA.
.95 .46 ±.005
RUBBER
WASHER
FURNISHED
CR-45
Recommended
MB-45 Mounting Hole Pattern

Typical Installation

One-Wire Pass Two-Wire Passes Three-Wire Passes


MB-45 with CR-45

Typical Application

Load Center Control Panel Process Heating

CR Magnetics, Inc. 544 Axminister Dr. Fenton, MO 63026 (314) 343-8518 FAX (314) 343-5119
29 © 1998 CR MAGNETICS, INC.
Remote Current Indicators

The CR Magnetics line of Remote Electrical Current Applications


Indicators provides an effective method for remote
monitoring of electrical current. The remote current • Indicate open heater elements
sensing transformer is installed around the current-
carrying wire and is connected directly to the LED • Observe remote loads
panel indicator. When the current exceeds the turn- • Indicate phase loss
on point of the sensing transformer, the LED illumi- • Monitor motor operation
nates to indicate the presence of current. Two sizes
of remote current sensing transformers are available
for use with either one of two types of LED indicators.

Model 19 Remote Current Transformer Model 18 Remote Current Transformer


(Connect directly to either PH-25 or PH-31 LED indicator) (Connect directly to either PH-25 or PH-31 LED indicator)
Indicating Range: 2 to 100 Amps (1-Wire Pass) SHOWN WITH MB-18, SURFACE MOUNTING BRACKET
Minimum turn-on point: 2 Amps Indicating Range: 2.5 to 100 Amps (1-Wire Pass)
Max. Cont. Current: 100 Amps Minimum turn-on point: 2.5 Amps
Max.Transient Current: 150 Amps for 5 Sec. Max. Cont. Current: 100 Amps
Working Class: 600 Volts, 50-60 Hz Max.Transient Current: 150 Amps for 5 Sec.
Working Class: 600 Volts, 50-60 Hz
WIRE PASSES TURN-ON POINT MAX. WIRE
DIAMETER MAX. WIRE
WIRE PASSES TURN-ON POINT
1 2 .29 DIAMETER
2 1 .14 1 2.5 .55
3 .66 .13 2 1.25 .27
N 2÷N 3 .83 .25
N 2.5 ÷ N

PH-25 Press-In LED Panel Indicator PH-31 Splash-Proof LED Panel Indicator
(Supplied with two types of mounting hardware) (Supplied with rubber sealing washer)
LED type: T-13/4, Bi-Polar, Red/Red Diffused LED type: T-13/4, Bi-Polar, Red/Red Diffused
Mounting Hole: .250 ± .002” Dia. Housing Material: Chrome Plated Brass
Mounting Hardware: Use either one-piece press-in Mounting Hole: .312 ± .005” Dia.
red lens or two-piece mounting clip
30 © 1998 CR MAGNETICS, INC.
Remote Current Indicators
Outline Drawings

#22 AWG UL .55 DIA.


UL STYLE 1213

. .95 1.48
#20 AWG
.29 DIA. UL STYLE 1015
.79

12
1.04
NTS
.95 .19 .25
1.33 24
.46 .50
NTS
#4-40 INSERT-.17 DEEP

Model 19: Remote Current Transformer Model 18: Remote Current Transformer

12
NTS

.875 .25 .25 .750


1.37 1.25
#6 SCREW #4-40 FLAT HEAD
NOT FURNISHED SCREW FURNISHED
CURRENT LIMITING RESISTOR

MB 18: Surface Mounting Bracket


.062 MIN. .125
.125 MAX. MAX.
12 16 MAX.
NTS PANEL
THICKNESS

.39 DIA

ONE PIECE TWO PIECE


RED LENS MOUNTING CLIP CURRENT LIMITING RESISTOR WASHER

PH-25: Press-In LED Panel Indicator PH-31: Splash-Proof LED Panel Indicator

Typical Applications

Model 19 Model 18 PH-31


PH-25
with MB-18
Part Numbers
Model 19 Current Transformer with .29 dia. opening
Model 18 Current Transformer with .55 dia. opening
MB-18 Surface Mounting Bracket for Model 18
PH-25 Press-In LED Panel Indicator
PH-31 Splash-Proof LED Panel Indicator

CR Magnetics, Inc. 544 Axminister Dr. Fenton, MO 63026 (314) 343-8518 FAX (314) 343-5119
31 © 1998 CR MAGNETICS, INC.
AC Motor Loads & U.S.
Standard Voltages

A.C. Motor Loads *

MOTOR FULL LOAD CURRENTS MAXIMUM LOCKED ROTOR CURRENTS


SINGLE
PHASE 3-PHASE A.C. INDUCTION 3-PHASE A.C. INDUCTION

HP 115 V 230 V 115 V 200 V 230 V 460 V 575 V 2300 V 4160 V 200 V 220/230 V 440/460 V 550/575 V 2300 V 4160 V
1/2 9.8 4.9 4 2.3 2 1 .8 23 20 10 8
3/4 13.8 6.9 5.6 3.2 2.8 1.4 1.1 29 25 12.5 10
1 16 8 7.2 4.15 3.6 1.8 1.4 34.5 30 15 12
11/2 20 10 10.4 6 5.2 2.6 2.1 46 40 20 16
2 24 12 13.6 7.8 6.8 3.4 2.7 57.5 50 25 20
3 34 17 11 9.6 4.8 3.9 73.5 64 32 25
5 56 28 17.5 15.2 7.6 6.1 106 92 46 37
71/2 80 40 25 22 11 9 146 127 63 51
10 100 50 32 28 14 11 186 162 81 65
15 48 42 21 17 267 232 116 93
20 62 54 27 22 334 290 145 116
25 78 68 34 27 420 365 182 146 35 19
30 92 80 40 32 500 435 217 174 41 23
40 120 104 52 41 667 580 290 232 55 30
50 150 130 65 52 834 725 362 290 69 38
60 177 154 77 62 16 8.9 1000 870 435 348 83 46
75 221 192 96 77 20 11 1250 1085 592 435 104 57
100 285 248 124 99 26 14.4 1670 1450 725 580 139 76
125 358 312 156 125 31 17 2085 1815 907 726 173 96
150 415 360 180 144 37 20.5 2500 2170 1085 870 208 115
200 550 480 240 192 49 27 3340 2900 1450 1160 278 153
OVER
200HP
APPROX.
AMPS/HP 2.75 2.40 1.20 .96 .24 .133
*This information provided as reference only. Consult motor manufacturer and related standards for additional information.

U.S. STANDARD VOLTAGES

SINGLE-PHASE POLYPHASE
A
A
LINE
A 240 (480) 208 (416)
120 (240) 120 (240) [480] C N B
N GROUND 240 (480) C B 120 (240) [480] 120 (240)
120 (240) 240 (480)
B LINE
120 (240) [480]
120 (240)
120/240 V, 3 W (240/480 V, 3 W)
THREE-WIRE 120 V, 3 W (240 V, 3 W) [480 V, 3 W] 240/120 V, 4 W (480/240 V, 4 W)
THREE-PHASE, THREE-WIRE THREE-PHASE, FOUR-WIRE DELTA

LINE
A
208 (480)
120 (277)
B
120 (240) [480]
A 120 (277) 208 (480)
GROUND
N
208 (480)
N
120 V, 2 W (240 V, 2 W) [480 V, 2 W] 120 (277)
TWO-WIRE
C
208Y/120 V, 4 W (480Y/277 V, 4 W)
THREE-PHASE, FOUR-WIRE WYE
32
© 1998 CR MAGNETICS, INC.