Fire Pump Controllers: Models AF, AFP, AFR, AFY, ATF, ATR, ATP or ATY followed by C or N, followed by additional suffixes. All of the above
controllers are suitable for use on circuits capable of delivering high fault currents. The withstand ratings are as follows:
Max Short Circuit
Current RMS
Circuit Breaker Max V AC Symmetrical Amps
MZMH6-160, MZMH6-250
MZMH6-160, MZMH6-250
The controllers provided with Automatic Transfer Switches are suitable for use on circuits capable of delivering high fault currents. The withstand
rating of the normal power source side is determined by the transfer switch as indicated below:
Max Controller Short Circuit
The withstand ratings for the alternate power source side will be dependent upon the ratings of the external circuit breaker provided. But in no
case will they exceed those of the normal power source side.
All of the above controllers are suitable for use on circuits capable of delivering high fault currents. The withstand ratings are as follows:
Current RMS
Circuit Breaker Max V AC Symmetrical Amps
NZM6B-100, NZM6B-160
The controllers provided with automatic Transfer Switches are suitable for use on circuits capable of delivering high fault currents. The withstand
rating of the entire controller is determined by the transfer switch as indicated below:
The withstand ratings for the alternate power source side will be dependent upon the ratings of the external circuit breaker provided. But in no
case will they exceed those of the normal power source side.
Models FPA, FPP, FPR, FPS, FPV, FPW, FPY, VPA, VPR, and VPS may be followed by additional suffixes. The withstand ratings are as follows:
(Ampere Symmetrical)
OPTIONAL
Model ATG, ATU, VPG or VPU. The controllers provided with Automatic Transfer Switches are suitable for use on circuits capable of delivering high
fault currents. The withstand rating of the normal power side is the same as the withstand ratings of controllers without transfer switches. The
withstand rating of the alternate power side is determined by the transfer switch as indicated by the following tables:
50/60 Hz
50/60 Hz
50/60 Hz
50/60 Hz
60Hz
Withstand
Rating (A)
40 40 — — — 65,000
— — 60 75 — 25,000
— — — — 100 18,000
Specific**
Rating
Transfer
200-208V
230-240V
Withstand
Switch
50/60 Hz
50/60 Hz
Time
Rating
Switch
60 Hz
Time
Rating
Model ATU or VPU: Normal Power Side: Same as withstand rating of controller without transfer switch.
Alternate Power Side: Same as withstand rating of controller without transfer switch.
Short Circuit Withstand Ratings of Limited Service Controllers Without Transfer Switches
OPTIONAL
Model LTG, GLG: Automatic transfer switch for connection to a generator set.
Model LTG: Normal Power Side: Same as withstand rating of controller without transfer switch.
Alternate Power Side: Withstand rating only applies when the generator
TRANSFER SWITCH
200-480 V
WITHSTAND RATING
120 30 25,000
TRANSFER SWITCH
600 V
WITHSTAND RATING
120 30 18,000
Model LTU: Normal Power Side: Same as withstand rating of controller without transfer switch.
Alternate Power Side: Same as withstand rating of controller without transfer switch.
Model LTG: Normal Power Side: Same as withstand rating of controller without transfer switch.
Alternate Power Side: Withstand rating only applies when the generator set is protected
Withstand Rating
Transfer
200-480 V
Specific Withstand
Withstand Rating
Transfer
600 V Specific Withstand
Model LTU: Normal Power Side: Same as withstand rating of controller without transfer switch.
Alternate Power Side: Same as withstand rating of controller without transfer switch.
Models CPA, CPP, CPR, CPS, CPV, CPW, CPY, may be followed by additional suffixes. The withstand ratings are as follows:
Model CPU - The controllers provided with automatic transfer switches are suitable for use on circuits capable of delivering high fault currents. The
withstand rating of the normal power side and the alternate power side is the same as the withstand ratings of controllers without transfer
switches.
Model CPU.
Short circuit withstand rating for alternate power circuit with transfer switch (RMS Symmetrical)
V Standard High (optional)
Fire Pump Controller, for engine-driven centrifugal fire pumps Model GPD - followed by a number 12 or 24 - followed by a number 120 or 220 -
may be followed by a letter and number.
Overcurrent Protection Panels, Model OPD; may be followed by a number 200 through 575 with - or /; followed by a number 200 through 600
with /; followed by a number 10 through 500 with /; followed by 1 or 3 with /; followed by 50 or 60 or 50/60. - These panels provide separate
overcurrent protection and disconnect to comply with CSA C22.1 Rule 32-204 and 32-206 and NFPA 20 Article 9.2.3.1, 9.2.3.4, and 9.2.3.4.1.
Fire pump controllers, horsepower rated, Models GPA, GPAe, GPP, GPR, GPS, GPV, GPY, GPYe or GPW; may be followed by a number 110 through
575 with - or /; followed by a number 200 through 600 with /; followed by a number 1 through 500 with /; followed by 1 or 3 with /; followed by
50 or 60 or 50/60.
Fire pump controllers, kilowatt rated, Models GPA, GPP, GPAe, GPR, GPS, GPV, GPY, GPYe or GPW; followed by -400/; followed by a number 0.75
through 315 with kW/; followed by 3 with /; followed by 50 or 60 or 50/60.
Transfer switch, horsepower rated, Model GPU; may be followed by a number 110 through 575 with - or /; followed by a number 200 through
600 with /; followed by a number 1 through 500 with /; followed by 1 or 3 with /; followed by 50 or 60 or 50/60.
Transfer switch, kilowatt rated, Model GPU; followed by -400/; followed by a number 0.75 through 315 with kW/; followed by 3 with /; followed
by 50 or 60 or 50/60.
Withstand ratings of normal power circuit for GPA, GPAe, GPP, GPR, GPS, GPV, GPY, GPYe and GPW controllers with or
without gpu transfer switch.
Short Circuit Withstand Ratings for normal power circuit with or without transfer switch, A Symmetrical
+ - Not applicable to controllers that use components under files DIVQ.E483182, WJAZ.E483183 and NLDX.E483184.
Limited service fire pump controllers, horsepower rated, Models GPL; may be followed by a number 110 through 575 with - or /; followed by a
number 200 through 600 with /; followed by a number 1 through 30 with /; followed by 1 or 3 with /; followed by 50 or 60 or 50/60.
Limited service fire pump controllers, , kilowatt rated, Models GPL; followed by -400/; followed by a number 0.75 through 22 with kW/; followed
by 1 or 3 with /; followed by 50 or 60 or 50/60.
Limited service transfer switch, for connection to a second utility, horsepower rated, Model GLU; may be followed by a number 110 through 575
with - or /; followed by a number 200 through 600 with /; followed by a number 1 through 30 with /; followed by 1 or 3 with /; followed by 50 or
60 or 50/60.
Limited service transfer switch, for connection to a second utility, kilowatt rated, Model GLU; followed by -400/; followed by a number 0.75
through 22 with kW/; followed by 1 or 3 with /; followed by 50 or 60 or 50/60.
Withstand ratings of normal power circuit for GPL controller with or without GLU transfer switch.
Short Circuit Withstand Ratings for normal power circuit with or without transfer switch, A Symmetrical
200-240 65,000 -
Automatic Type: Models FSA and FPA, across-the-line starter type, Models FSR and FPR, reduced voltage auto-transformer starter type, Models
FSP and FPP, reduced voltage partial winding start type, Model FSS and FPS, reduced voltage soft starter type, Model FSV and FPV, reduced
voltage primary resistor starter type, Models FSW and FPW, reduced voltage star-delta closed transition type, Model FSY and FPY, reduced voltage
star-delta open transition type, Input: 200-600 V, 50/60 Hz, 5-400 hp.
Full Service Transfer Switches: Models ATG (generation set) and ATU (secondary utility), Input: 200-600 V, 50/60 Hz, 40-400 hp.
Full Service Controllers for Electric Motor-Driven Pumps With Automatic Transfer Switch
Automatic Type: Models TF and TD, across-the-line type; Models TFR and TDR, reduced voltage auto-transformer type; and Model TFS, solid
state soft start, Input: 3.7-75 kW, 208-240 V, 3.7-150 kW, 416 V, 3.7-225 kW, 480-600 V, 60 Hz, 3 phase, 3 wire. Dual Full Service, Model TDF,
across-the-line type; Model TDFR, reduced voltage auto-transformer type; Model TDS, reduced voltage solid state soft start type; and Model ATP
reduced voltage part winding type, Input: 3.7-75 kW, 208-290 V, 3.7-150 kW, 416 V, 3.7-225 kW, 480-600 V, 60 Hz, 3 phase, 3 wire. A prefix "A" in
front of the model designation indicates conformance with specific short circuit requirements of NFPA 20. Model CSx, x: A, P, R, S, Y, G and U.
Input: 5-150 HP, 200-208 V, 5-200 HP, 220-240 V, 5-300 HP, 380-415 V, 5-400 HP, 440-480 V, 5-500 HP, 575-600 V, 60 Hz, 3 phase, 3 Wire.
Non-Automatic Type: Model TF-N (complete with automatic transfer switch), across-the-line type; and Model TFR-N, reduced voltage auto-
transformer type, Input: 3.7-75 kW, 208-240 V, 3.7-150 kW, 416 V, 3.7-225 kW, 480-600 V, 60 Hz, 3 phase, 3 wire. Dual Full Service, Model TDF-N,
across-the-line type; and Model TDFR-N, reduced voltage auto-transformer type, Input: 3.7-75 kw, 208-290 V, 3.7-150 kW, 416 V, 3.7-225 kW,
480-600 V, 60 Hz, 3 phase, 3 wire. A prefix "A" in front of the model designation indicates conformance with specific short circuit requirements of
NFPA 20.
Limited Service Controllers for Electric Motor-Driven Pumps: Model LS Series and Model TL (complete with automatic transfer switch), across-
the-line type, Input: 3.7-22.4 kW, 208-600 V, 60 Hz, 3 phase, 3 wire. Model LS1 Series, across-the-line type, Input: 2.3-11.2 kW, 208-240 V, 60 Hz,
single phase. A prefix "A" in front of the model designation indicates conformance with specific short circuit requirements of NFPA 20. Model FPL,
GPL, limited full service, across-the-line, Input: 200-600 V, 50/60 Hz, 3-30 hp.
Limited Service Transfer Switches: Models LTG (generation set) and LTU, GLG, GLU, (secondary utility), Input: 200-600 V, 50/60 Hz, 3-30 hp.
Controllers for Engine-Driven Pumps - Automatic Type: Model FPD, 12 V or 24 V dc; Input: 120 V, 60 Hz, 1 phase, 6 A.
Fire pump controllers , Models GPA, GPP, GPR, GPS, GPV, GPY and GPW.
Trademark and/or Tradename:
The appearance of a company's name or product in this database does not in itself assure that products so identified have been manufactured
under UL Solutions' Follow - Up Service. Only those products bearing the UL Mark should be considered to be Certified and covered under UL
Solutions' Follow - Up Service. Always look for the Mark on the product.
UL Solutions permits the reproduction of the material contained in Product iQ subject to the following conditions: 1. The Guide Information,
Assemblies, Constructions, Designs, Systems, and/or Certifications (files) must be presented in their entirety and in a non-misleading manner,
without any manipulation of the data (or drawings). 2. The statement "Reprinted from Product iQ with permission from UL Solutions" must appear
adjacent to the extracted material. In addition, the reprinted material must include a copyright notice in the following format:
"©2022 UL LLC."