You are on page 1of 7

LSA 50.2 M6 AREP 50.

0Hz 400V
D550 serial number:22006A00351

23/12/2021 Configuration Number of pages: 7

1. Machine configuration and wiring:


The machine:
Generator rated voltage = 400 V
Generator rated frequency = 50 Hz
Generator rated power factor = 0.8 PF
Generator rated apparent power = 1250 kVA
Generator rated real power (calculated) = 1000 kW
Generator rated reactive power (calculated) = 750 kVAr
Generator rated current (calculated) = 1804.22 A

The exciter:
Generator rated field inductor resistance = 12.73 Ohms
Iex shutdown = 0.5 A
Generator rated nominal field current = 3.89 A

Wiring:

1
LSA 50.2 M6 AREP 50.0Hz 400V
D550 serial number:22006A00351

23/12/2021 Configuration Number of pages: 7

2. Capability curve limitations:

2
LSA 50.2 M6 AREP 50.0Hz 400V
D550 serial number:22006A00351

23/12/2021 Configuration Number of pages: 7

3. Over excitation limitations:

3
LSA 50.2 M6 AREP 50.0Hz 400V
D550 serial number:22006A00351

23/12/2021 Configuration Number of pages: 7

4. Stator current limitations:

5. Protections:
No protection activated.

6. Start-up:

The start order come from:Always enabled

7. Regulation mode:
7.1 Voltage:
a. Characteristics:
The regulation is activated by: Always enabled
Setpoint source is:Analog input

4
LSA 50.2 M6 AREP 50.0Hz 400V
D550 serial number:22006A00351

23/12/2021 Configuration Number of pages: 7

Min setpoint as % of rated voltage = 90 %


Max setpoint as % of rated voltage = 110 %
The setpoint is driving by the analog input n°1
V/Hz knee frequency = 49 Hz
V/Hz slope = 2

b. PID settings:
Voltage regulation proportional gain = 6000
Voltage regulation integral gain = 30
Voltage regulation derivative gain = 1200
Voltage regulation overall gain = 80

7.2 Field current:


a. Characteristics:
The regulation is activated by: None
Setpoint source is:Fixed setpoint in configuration
Min field current setpoint as % of rated IEX = 0 %
Max field current setpoint as % of rated IEX = 100 %
Field current setpoint = 3.89 A

b. PID settings:
Current regulation proportional gain = 2000
Current regulation integral gain = 50
Current regulation derivative gain = 30
Current regulation overall gain = 100

7.3 Volt matching:


The regulation is activated by: None

7.4 Power factor:


a. Characteristics:
The regulation is activated by: None
Setpoint source is:Fixed setpoint in configuration
Min generator PF setpoint = -0.9 PF
Max generator PF setpoint = 0.6 PF
Generator PF setpoint = 0.8 PF

b. PID settings:
Reactive power/PF regulation proportional gain = 100
Reactive power/PF regulation integral gain = 30
Reactive power/PF regulation derivative gain = 200
Reactive power/PF regulation overall gain = 100

7.5 Grid power factor:


a. Characteristics:
The regulation is activated by: None
Setpoint source is:Fixed setpoint in configuration
Minimum grid PF reference = 1 PF

5
LSA 50.2 M6 AREP 50.0Hz 400V
D550 serial number:22006A00351

23/12/2021 Configuration Number of pages: 7

Maximum grid PF reference = 0.8 PF


Grid power factor regulation reference = 0.8 PF

b. PID settings:
Grid power factor regulation proportional gain = 100
Grid power factor regulation integral gain = 30
Grid power factor regulation derivative gain = 200
Grid power factor regulation overall gain = 100

7.6 KVAr:
a. Characteristics:
The regulation is activated by: None
Setpoint source is:Fixed setpoint in configuration
Min kVAr setpoint as % of nominal kVA = -30 %
Max kVAr setpoint as % of nominal kVA = 70 %
Reactive power setpoint = 0 kVAr

b. PID settings:
Reactive power/PF regulation proportional gain = 100
Reactive power/PF regulation integral gain = 30
Reactive power/PF regulation derivative gain = 200
Reactive power/PF regulation overall gain = 100
DC Bus voltage compensation is activated

8. Digitals inputs:
Digital Input Active Destination

9. Digitals Outputs:
Source Active Digital Output

10. Analogs Inputs:


Configuration
ID Destination 0% value 100% value
AI
AIO1 0-10V Voltage setpoint 360.00 440.00

11. Analogs Outputs:


Wirebreak
   ID
monitoring
   AIO1

   AIO2

   AIO3

   AIO4

12. Curves functions:


No curve function used.

13. Logics gates:

6
LSA 50.2 M6 AREP 50.0Hz 400V
D550 serial number:22006A00351

23/12/2021 Configuration Number of pages: 7

No logical function used.

14. User variable


User variable 1 = 0
User variable 2 = 0
User variable 3 = 0
User variable 4 = 0
User variable 5 = 0
User variable 6 = 0
User variable 7 = 0
User variable 8 = 0
User variable 9 = 0
User variable 10 = 0
User variable 11 = 0
User variable 12 = 0
User variable 13 = 0
User variable 14 = 0
User variable 15 = 0
User variable 16 = 0
User variable 17 = 0
User variable 18 = 0
User variable 19 = 0
User variable 20 = 0

15. Synchronization
Minimum slip frequency = -0.5 Hz
Maximum slip frequency = 0.5 Hz
Minimum delta voltage = -5 %
Maximum delta voltage = 5 %
Minimum angle = -10 °
Maximum angle = 10 °
Total Closing time = 50 ms

16. GRID CODE


No GRID CODE function is activated.

17. Log Event


Enabled / Iexc during last
Event Event counter
Disabled event

18. Second configuration


Analog parameters type
Configuration 1 Configuration 2
Paremter Id Destination
value value
Switch parameters type
Configuration 1 Configuration 2
Parameter Id Destination
value value