Star/wye connection and delta connection are the two different methods which are
used for connecting 3 phase system.
STAR CONNECTION
if you observe the diagram carefully, you’ll find that the sum of return currents is
zero at every instance. For example, at instant shown above, corresponding to
240 deg, Ic = Imax and Ib = Ia = -0.5 Imax.
So, if we add these return currents, we’ll get the sum =0, and this is true for every
instance.
Ia + Ib + Ic = (-0.5Imax – 0.5Imax) + Imax
Ia + Ib + Ic = – Imax + Imax = 0
We can therefore, remove the neutral conductor without affecting the voltage or
current in the circuit.
So, we have reduced the number of conductors 6 which was the initial stage to 3.
50% saving in conductor cost!
However, to achieve this, the load shown in the circuit must be identical. If the
load is not identical, then removing neutral conductor can cause unequal voltages
across the loads.
So, in an ideal situation or in the situation where load is equal, current flowing
through neutral conductor is Zero.
The conditions where load is not equal, a neutral must be provided.
3.5 core cable, that 0.5 core is your neutral conductor.
The figure shown above is called as 3 phase 4 wire system. The neutral conductor can
be of similar size or may be slightly smaller than the other conductors. 3 phase 4 wire
system is widely used to supply power to commercial and industrial customers.
VOLTAGE & CURRENT IN START CONNECTION
Now, when we talk about star connected three phase system, we must know about
these two concepts.
1. Line to line voltage
2. Line to neutral voltage.
Voltage which we receive in our home is the Line to neutral voltage I.e. 230 volts
(in India) .
DELTA CONNECTION
One of the other way to connect three phase system is called as delta connection. The
connection is so named because it resembles the greek letter delta .
Voltage & current in Delta connection
Let have a look at the voltage and currents relationship in delta connection.
Voltage in Delta connection
Now in case of delta connection, voltage across each connection is same as line voltage.
This is the power transferred by a single phase. To calculate the power transferred by 3
phase we can multiply this equation by 3.
Similarly, Apparent power transferred by a single phase of delta connection is given by.
Multiply above equation by 3 to calculate power transferred by 3 phase. And you’ll get
the same result as star connection.
SUMAMRY
3 phase system can be connected in two different styles I.e. star or delta.
In star connection, line to line current is equal to line to neutral current. But, line
to line voltage is root 3 times the line to neutral voltage.
In delta connection, voltage across each element is equal to line voltage. But, line
current is root 3 times the current flowing through each element.
Power transmitted by both the connection is same.