Professional Documents
Culture Documents
Hospital
Planning and
Designing
For Medical Administrators,
Architects and Planners
Ajay Garg
Anil Dewan
123
Manual of Hospital Planning
and Designing
Ajay Garg • Anil Dewan
Manual of Hospital
Planning and Designing
For Medical Administrators,
Architects and Planners
Ajay Garg Anil Dewan
Hospital Administration School of Planning
Teerthanker Mahaveer University and Architecture Delhi
Moradabad, India New Delhi, India
© The Editor(s) (if applicable) and The Author(s), under exclusive license to Springer Nature
Singapore Pte Ltd. 2022
This work is subject to copyright. All rights are solely and exclusively licensed by the Publisher,
whether the whole or part of the material is concerned, specifically the rights of translation,
reprinting, reuse of illustrations, recitation, broadcasting, reproduction on microfilms or in any
other physical way, and transmission or information storage and retrieval, electronic adaptation,
computer software, or by similar or dissimilar methodology now known or hereafter developed.
The use of general descriptive names, registered names, trademarks, service marks, etc. in this
publication does not imply, even in the absence of a specific statement, that such names are
exempt from the relevant protective laws and regulations and therefore free for general use.
The publisher, the authors and the editors are safe to assume that the advice and information in
this book are believed to be true and accurate at the date of publication. Neither the publisher nor
the authors or the editors give a warranty, expressed or implied, with respect to the material
contained herein or for any errors or omissions that may have been made. The publisher remains
neutral with regard to jurisdictional claims in published maps and institutional affiliations.
This Springer imprint is published by the registered company Springer Nature Singapore Pte Ltd.
The registered company address is: 152 Beach Road, #21-01/04 Gateway East, Singapore
189721, Singapore
First and foremost, we would like to thank God. We could never
have done this without the faith we have in God, the Almighty.
My late father Dr. R.N. Gupta for his blessings and my mother
Mrs. Santosh Gupta for inspiring me to write this book.
My wife, Mohini Garg
who was the main person by my corner, pushing me to share
my experience by writing this book. You are my love and
inspiration! Thanks for not just believing but knowing that I
could do this! I Love You Always and Forever!
To my children, Dr. Megha Garg and Parth Garg
The hard work that you put into this book and all the
suggestions and improvements that you made to it have not just
made this book better but have also strengthened our bond. I
wish you both all the happiness and success in this world.
—Ajay Garg
My late father Dewan Hargopal for nurturing me, My Mother
Shanta Rani for having faith in me, My wife, Poonam
for being my steady anchor and moral support.
My son, Gandharv
for constant encouragement and belief in me.
My students—past, present, and future—and teachers who
always inspired me for academic excellence.
—Prof. Dr. Anil Dewan
Preface
vii
viii Preface
zones required in the hospital. After that we have elaborated the important
department of the hospital along with the MEP services in detail.
We have tried to share our experiences in depth such as the location and
number of electrical and communication points, the environmental details of
the rooms, and the size and location of different rooms and areas.
Please note the details given in this book are based purely on the practical-
ity of the working conditions as per our personal experience. Though we have
tried to highlight the norms of various accreditation agencies like JCI and
NABH, but still the promoters are advised to go through the norms of the
agencies/government, applicable in their respective countries. If you feel that
any of the details given in this book are not correct, it may be true for you or
your country and may not be true for other countries. The requirement of the
spaces and facilities varies from user to user or from country to country.
Hence you may consider those issues which you may feel to be beneficial to
you, and rest of the issues may be ignored.
We have tried to write this book in very easily understandable English.
This book may be of great help to the students and small and large hospital
promoters, planners, and designers.
We are thankful to Mr. Suresh Jain the Chancellor and Mr. Manish Jain the
Group Vice-Chairman of Teerthanker Mahaveer University, Moradabad, and
Director Prof. Dr. PSN Rao, Dean Academics, Prof. Dr. Ashok Kumar and
Dean Research Prof. Dr. Sanjay Gupta of the School of Planning and
Architecture, New Delhi, for providing us the platform for learning and gain-
ing experiences in the field of health care. Without your support and inputs, it
would have been difficult to write this book and share our experiences. Here,
we would also like to thank Mr. Abhisekh Kapoor for providing us all his help
in writing this book.
Extending our gratitude toward Dr. Rohit Varshney, we would like to thank
him for his constant support toward our vision, regular discussions, and
brainstorming sessions during the compilation of this book and his guidance
on many small questions and tasks. We would also like to thank him for help-
ing us in compiling and sharing his experiences in a few chapters of this
book.
We would also like to extend thanks to Ar. Sandal Kapoor and his office
Sandal Kapoor Associates for sharing project details which are adapted for
this book and Ar. Arif Ali for helping us with the illustrations.
Lastly, we would like to thank each one who believed in our vision and
supported us throughout this amazing journey. We hope this book helps
everyone in some way and collectively we can make the medical society
achieve great heights.
Thank You!
Ajay Garg
Prof. Dr. Anil Dewan
ix
Introduction
Ajay Garg
Prof. Dr. Anil Dewan
xi
Contents
xiii
xiv Contents
Ajay Garg, FCA, DHA, SAP(FI) has been in the field of healthcare plan-
ning, designing, and administration for the last three decades. He has worked
for about 28 years with various hospitals like Narinder Mohan Hospital &
Heart Centre, Ghaziabad; Jeevan Rekha Hospital, Kashipur; and Teerthanker
Mahaveer Medical College, Moradabad.
He has also completed various hospital projects like Krishna Hospital
(Kashipur), Narayan Hospital (Rudrapur), Le Crest Hospital (Vasundhara,
Ghaziabad), and TSM Medical College & Hospital (Lucknow) as a hospital
consultant.
xlix
Part I
Hospital Planning
Phases of Planning and Designing
1
© The Author(s), under exclusive license to Springer Nature Singapore Pte Ltd. 2022 3
A. Garg, A. Dewan, Manual of Hospital Planning and Designing,
https://doi.org/10.1007/978-981-16-8456-2_1
4 1 Phases of Planning and Designing
This phase includes drawing of various units of This phase is for testing the services, ensuring
the hospital and adding details of infrastructure, specifications, operationalizing the equipment,
designing, including electrical fixtures, furniture training the staff and disinfecting the hospital
location and decor. before kick-starting the hospital.
Therefore, planning, designing and building
hospitals without thorough planning, thinking
1.5 MEP Planning can ultimately lead to troubles and the purpose of
the hospital services may be lost. As hospitals
This phase includes the planning of the MEP ser- provide a wide range of services that are made up
vices of the hospital like electricity, plumbing, or supported by many other functional units of
MGPS, CCD Cameras, Audio-visual networking the hospital, they are one of the most complex
and IT networking. types of building as compared to any other com-
mercial building.
Hospitals generally render the diagnostic and
1.6 Construction therapeutic functions and each of the functional-
ity has different requirements of infrastructure so
This is the phase in which the hospital building is that the concerned functionality can provide
actually being built up step by step. excellent results and quality.
Indeed, hospital design may also be influenced
by many restraints and opportunities like the cli-
1.7 Equipment Planning mate of the area, surrounding facilities, budget
allocation and presently available technology.
In this phase, the requirement of equipment is But the best design will be the one where the
worked out, the configuration and the technical designer can overcome these hurdles to the extent
specifications are finalized, quotations are possible or adopt alternate measures to tackle
invited, the order of the equipment is placed, these hurdles.
installation is completed and the commissioning Can anyone predict what will be the require-
of equipment is done. ment of the hospital after 10, 20, 30, or say
40 years from now? The answer is “No, not at
all.” As the world has undergone the experience
1.8 Man Power Planning of changing health care technology so fast in a
few years, the same is going to change further,
This phase includes assessing the requirement maybe faster than in the past. Under those cir-
of man power, finalizing the Standard Operating cumstances, the hospital has to accept the chang-
Procedures (SOPs), inviting resumes, inter- ing technology and adopt it at the earliest. This
views, appointments and joining of the will only be possible if the infrastructure of the
employees. hospital allows for such adoption. If not, the hos-
pital will lag behind in the race. Therefore, hospi-
tal designs shall be planned to look years ahead
1.9 Finalizing the Standard and should have the flexibility to adopt changes.
Operating Procedures Further, due to the inevitable demographic
of Hospital changes, technology development, changing
norms and codes of various agencies, changing
In this phase, the SOP’s Rules and Regulations, political policy etc., there can be a lot of pressure
Rate List etc. are finalized based on which the on the hospitals to adopt these changes as time
operations of the hospital shall be carried out. progresses.
Further Reading 5
It has been experienced that mostly there is a The future vision of the hospital project starts
tendency to design hospital facilities thinking the day when the idea of building a hospital is
that the problem can be solved as and when the conceived by the owners. The detailed feasibility
problem is faced. It means the immediate need is report has to be worked out, the selection of land
identified and within the existing resources, a is then another crucial factor. The most important
design response is provided as a solution. Like an factor is designing the individual units of the hos-
extension of ICUs, more Operating rooms, more pital like Emergency, Intensive care units and
private beds etc. This methodology can be true Operating complex and Indoor patient wards.
and feasible to a certain extent, but how many Similarly, there are other few things that the
such solutions can be provided and adopted. Over designers or promoters need to carefully consider
a period of time, one or the other day, the designer as they plan the hospital.
has to say NO to these changes.
Since the last few years and till today, the
planning and designing of the hospital building Further Reading
have undergone significant developments and
changes. Therefore, it is emphasized that the ini- Hospital | WBDG - Whole Building Design Guide
[Internet]. [cited 2021 Jun 7]. Available from: https://
tial planning and designing has to be strategic www.wbdg.org/building-types/health-care-facilities/
and integrating with a long-term vision consider- hospital
ing a few factors such as the adoption of the Joint Commission Resources, Inc, editor. Planning,
would-be technology in future, thinking beyond design, and construction of health care facilities.
2nd ed. Oakbrook Terrace, Ill: Joint Commission
the problem-based solutions, thinking the design Resources; 2009. 156 p.
solutions that will fit into the future changes, pro- Political, Economic, Technological and Cultural
viding the spaces for future expansions, adopting Influences that Will Shape Service Delivery in the
modular technology and easing out the move- Next Decade [Internet]. World Meteorological
Organization. 2015 [cited 2021 Jun 7]. Available from:
ment of the men and material. https://public.wmo.int/en/bulletin/political-economic-
It is true that to treat the patients, hospitals technological-a nd-c ultural-i nfluences-w ill-s hape-
need to have a team of experienced and profes- service-delivery-next
sional doctors and other paramedical staff, still Project Management for Construction: The Design and
Construction Process [Internet]. [cited 2021 Jun
the infrastructure of the hospital plays an impor- 7]. Available from: https://www.cmu.edu/cee/proj-
tant role in achieving the objective of the hospi- ects/PMbook/03_The_Design_And_Construction_
tals. As a huge amount of funds are being invested Process.html
in infrastructure, it is not feasible to renovate the Walrath BJ. A Project Planning Guide for Healthcare
Facility Owners [Internet] [Thesis]. Georgia Institute
hospital frequently. Therefore, infrastructure of Technology; 2007 [cited 2021 Jun 7]. Available
must be designed in such a way that it looks from: https://smartech.gatech.edu/handle/1853/14557
attractive, is functional and is safe for the patients
and the health workers.
Inception of the Idea
2
The Planning of the hospital starts as soon as the • If Yes, what type of charity do I want to do?
idea of setting up the hospital is conceived by the Do I want to treat free of cost or at conces-
promoter. What comes to mind as the first thought sional cost?
is ‘Where to set up a hospital?’ The answer to this • If I want to do charity, up to what extent am I
depends on personal factors and understandings planning to do so?
of the promoter. He/she may opt for a particular
place because that can be the place where he/she Once these questions are answered and the
resides, where he/she works, the environment, promoter is sure and affirmative for setting up the
the assumptions that a particular place has more hospital, he/she shall proceed further. The next
patients, assumption that the number of hospitals issue which he/she should answer is ‘What will
are fewer in that particular area etc. But should be the Status of the Hospital?’ Will it be a trust-
we depend on such factors which are not sup- owned charitable hospital, community hospital,
ported by any evidence or documents of assess- or a corporate hospital?
ment? The promoter shall ask himself one The next step after answering these questions
question ‘what is the purpose of building up a and finalizing the place/city is the preparation of
hospital, why at this place and not at other the Feasibility Report. This report indicates the
places’. The promoter shall answer these ques- feasibility of the success of the hospital at that
tions him/herself. The questions to which the place based on the surveys conducted in the
promoter shall put answers to are: nearby area of the proposed hospital location.
There are different agencies that can do this job
• Why did I think of making the hospital? for the promoter. Some of the factors that are
• What is the purpose of this hospital? included and surveyed by the agency are:
• What is the philosophy of the hospital? Is it to
serve the community or to make it a business • What shall be the coverage area, the residents
venture? of which shall avail the services of the
• What is my profession? Am I a medico or non- hospital?
medico? If non-medico, what are my plans to • To how many cities or villages can the hospi-
manage the hospital? tal provide services?
• What about hospital after my death? Are my • What is the approximate population that is
children interested to continue the hospital expected to avail the services of the hospital?
project? • Details of the other hospitals in the vicinity
• Do I want to do charity in the hospital? and the bed strength of these hospitals along
© The Author(s), under exclusive license to Springer Nature Singapore Pte Ltd. 2022 7
A. Garg, A. Dewan, Manual of Hospital Planning and Designing,
https://doi.org/10.1007/978-981-16-8456-2_2
8 2 Inception of the Idea
with the details of services being provided by • The distance of the hospital from the airport.
them. • What is the local mode of transport to the
• Details of nursing homes and individual prac- hospital?
titioners’ clinics in the vicinity. • Police station jurisdiction.
• The distance of the hospital from the nearest
Answers to these questions based on the actual police station.
survey, supported by documentary evidence, can • The distance of the hospital from the nearest
make it easy for the promoters to understand the fire Station.
expected business from that particular location • The main occupation of the public.
and which in turn can help to make decisions • Per capita income of the public.
about the location. • The living standard of the people.
Once the promoters make up their mind about • Paying capacity of the individuals.
the location, the Geographical details are col- • Main industries in the area.
lected by the agency. Some of the factors can be • How many Central Govt. /State Govt. Offices/
like: Employees reside in that area?
• What is the awareness of Health Insurance to
• The exact location of the hospital with address. the population residing in that area?
• On which road the hospital shall be located.
• The distance of the hospital from the railway Once these answers are received and the pro-
Station. moters are satisfied, the final decision can be
• The distance of the hospital from the bus taken about the location of the hospital.
station.
Factors Assessing Feasibility
of the Hospital 3
Consideration of the actual facts is an essential Malaria and/or other chronic diseases like
requirement for developing appropriate hospital Tuberculosis and COPD. Each and every cause
facilities. There must be deep efforts of pre- of disease or illness and death requires a well-
programming, research surveys, and discussion defined approach for prevention and treatment of
to work out the most appropriate programming, such illness, disease and death. For appropriate
planning, and designing of the hospital setup. planning of the proposed hospital, this analysis
Hospitals and facilities in the hospital shall be shall help a lot while planning the services to be
designed to prevent illness, detect diseases as provided, spaces and equipment required and of
early as possible, treat disease and then rehabili- course, the manpower needed. Also, the Non-
tate the patient. communicable ailments such as Cardiac disease,
Paraplegic Stroke, Renal Failure, Diabetes and
Hypertension that are becoming more prevalent
3.1 Demographics these days have to be determined. More impor-
tantly, a careful assessment is required for the
The Population trends in the area along with the infectious diseases, which in turn shall help in
life expectancy of population to be served have to designing the isolation areas of the hospital.
be determined. The total population shall be
determined according to age and gender. Also,
the growth of the population in that particular 3.3 Community
area has to be determined. In some regions, there
can be an accelerating growth rate of population, While designing a hospital, the assessment shall
while others may have a significant aged popula- be done for the people in the community relating
tion or there can be areas with fewer births etc. to the knowledge, awareness, and initiatives to
keep their family and other individuals healthy.
Also, there is a need to assess and consider the
3.2 Understanding the Type climate, culture, religion, traditions, financial
of Diseases wellness, education level of the population par-
ticularly the health education, and the difference
In different regions, there can be different types between needs and wants of the population. It is
of diseases causing illness and death. These could very important to assess the main occupation of
range from waterborne diseases like Typhoid, the population, per capita income of the popula-
© The Author(s), under exclusive license to Springer Nature Singapore Pte Ltd. 2022 9
A. Garg, A. Dewan, Manual of Hospital Planning and Designing,
https://doi.org/10.1007/978-981-16-8456-2_3
10 3 Factors Assessing Feasibility of the Hospital
tion, living standard of the population, and of the Intensive Care Units shall be planned and on
course the paying capacity of the population of the expected attendance in Emergency—Size of
that particular area where the hospital is being the Emergency shall be planned.
planned.
Detailed Project Reports (DPRs) are bankable ments etc. This actual vs. projections are mea-
sets of documents that show the results and out- sured based on:
puts of working and projections while planning
and designing a project. DPR is detailed and 1. Whether the project was completed on time as
elaborated projections and plans for the project compared to the estimated period?
indicating overall calculations, programme, 2. Whether the actual cost of the project was
financials, roles and responsibilities, time plan- within reasonable limits of cost escalation?
ning for project, details of required activities and 3. Whether after completion of the project, was
resources required for completion of the project. it able to deliver the desired results relating to
During the planning stage, a blueprint is pre- the quality and quantity and whether the
pared on paper which gives a detailed study and patient’s satisfaction is achieved at a profit-
analysis of what has to be done to convert the able cost?
investment into a feasible and profitable venture. 4. Whether the project gestation period was
In this set of document, top management’s poli- within the planned duration as estimated?
cies and guidelines, its impact on the project
span, appraisal of financial viability is estimated
and dealt with in-depth. The DPR mainly covers 4.1 Information to Be Generally
the issues like contract drawings, detailed techni- Provided in DPR
cal feasibility studies, financial feasibility calcu-
lations, execution of the project from the practical To start preparing the DPR, some of the following
point of view, the time period for completion of information shall be generally provided in the DPR:
the project and staff planning. DPR also high-
lights the type and nature of inherited risks in the 1. General Information about the hospital
project and other foreseeable external risks that project.
can influence the outcome of the hospital project. 2. Background and the experience of the proj-
The DPR should address and provide measures ect promoters in the hospital industry.
for risk management and risk mitigation. 3. Details of the Bed in hospital; ward wise
The DPR is a document that guides the man- (Table 4.1).
agement about the progress of the project on real- 4. Details of the departments and services to be
time basis. It also provides the tools for given.
comparison of actual vs. projected figures in 5. Details of the proposed project like:
terms of costs, time period, milestone achieve- (a) Number of OPDs.
© The Author(s), under exclusive license to Springer Nature Singapore Pte Ltd. 2022 13
A. Garg, A. Dewan, Manual of Hospital Planning and Designing,
https://doi.org/10.1007/978-981-16-8456-2_4
14 4 Preparation of Detailed Project Report (DPR) and Techno-Commercial Feasibility Report (TCFR)
(b) The number of Private Rooms, Semi- (d) Number of Operating Rooms.
private Room, General Wards etc. (e) Support services to be provided.
(c) Number of critical Units (ICU) and the (f) Equipment to be installed.
number of beds in each ICU. (g) Management teams for the project.
(h) Details of land, buildings and
Table 4.1 Break up of type and number of beds equipment.
General Beds
(i) Details of infrastructural facilities
Semi-private Beds (power, water supply, transport facilities
Private Beds etc.).
Deluxe Room (j) Effluents produced by the project and
Suites treatment procedures adopted.
ICCU (k) Manpower requirement and availability.
CTVS ICU 6. Schedule of implementation period of the
HDU project.
MICU
7. Detailed Project cost (Table 4.2).
Day Care
8. Details of Department Wise Breakup of
SICU
NICU
Required Items (Table 4.3).
PICU 9. Depreciation Statement (Table 4.4).
Pre and post-op. Gynae 10.
Details of Salary and Allowances
Endo. Recovery (Table 4.5).
Emergency 11. Staff requirement Planning (Table 4.6).
Others 12. Resources and Means of finances for the
Total Number of Beds project.
13. Working capital requirements and arrange- 22. Cash Flow statement for the next 10 years
ments thereof (Table 4.7). (Table 4.16).
14. The assumed rate of hospital services
23. The financial ratio for the bank loans.
(Table 4.8). 24. Projected Balance Sheets for the next 10
15. Assumed Operational Expenses (Table 4.9). years.
16. Interest calculation on the loans (Table 4.10). 25. Marketing and selling arrangements made.
17. Assumed number of patients and procedures 26. Mode and means of repayment of term loans
that can be performed (Table 4.11). and cash credit loans.
18. Statement of Bed days occupancy per year 27. Government approvals required for the proj-
(Table 4.12). ect. Local authority’s consents and statutory
19. Revenue earning projections (Table 4.13). permissions required for the project.
20. Revenue expenses projections (Table 4.14). 28. Details of collateral security that can be
21. Profit and loss statement for the next 10 years offered to the financial institutions.
(Table 4.15).
4.1 Information to Be Generally Provided in DPR 17
Table 4.9 (continued)
Rate/
Head of expense Unit percentage Remarks
Variable Expenses
Consultation Fees
Doctors Share Visits Percentage of Fixed Percentage of the Receipt of Income Statement
General Ward Receipts
Doctors Share Visits Percentage of Fixed Percentage of the Receipt of Income Statement
Deluxe Room Receipts
Doctors Share Visits Percentage of Fixed Percentage of the Receipt of Income Statement
Suites Receipts
Consumables
O.T Drugs Percentage of Fixed Percentage of the Receipt of Income Statement
Receipts
Cost of Medicines Percentage of Fixed Percentage of the Receipt of Income Statement
Receipts
Other Variable Expenses
Concession and Percentage of Fixed Percentage of the Total Receipt of Income
Discount Receipts Statement
Other Non-Planned Fixed Assumed
Expenses
This statement of Projected Expenses shall be prepared for all the expenditure in the Hospital
Table 4.13 (continued)
(In million)
Rate (in 10th
Head of income Unit Rs.) Basis of calculation 1st year – year Total
Doctors visit charges
General Wards 2 Visits per Bed occupancy per
day year * Rate of doctors
visit
Private Ward 2 Visits Per Bed Occupancy Per
Day Year * Rate of Doctors
Visit
Income from OPD Per Card Number of OPD
Patients Per Day * 300
Days * Rate of OPD
Card
Echocardiography Per Test Number of Echo Per
Day * 365
Days * Average Rate of
Echo
ECG’s Per ECG Number of ECG’s Per
Day * 365
Days * Average Rate of
ECG
Total
This table shall be filled for each and every service head from where the income of the hospital is expected, and at the
end, the total projected income is worked out
Table 4.14 (continued)
Expenses (in million)
1st
Head of expense Unit Rate (in Rs.) Basis of calculation year – 10th year Total
Total semi-Variable Expenses (B)
Variable expenses
Doctors share
Private ward Percentage Fixed percentage of
of receipts the receipt of
income statement
Income from OPD Percentage Fixed percentage of
of receipts the receipt of
income statement
Echocardiography Percentage Fixed percentage of
of receipts The receipt of
income statement
Angiography Percentage Fixed percentage of
of receipts the receipt of
income statement
Surgeries Percentage Fixed Percentage
of receipts of The Receipt of
Income Statement
Anaesthesia Percentage Fixed Percentage
Charges of Receipts of The Receipt of
Income Statement
Total other variable expenses 2501.77 34621.48
(C 1)
Consumables
O.T Drugs Percentage 50% Fixed Percentage
of Receipts of The Receipt of
Income Statement
Cost of Medicines Percentage 75% Fixed Percentage
of Receipts of The Receipt of
Income Statement
Linen Consumables Lumpsum 25,000 Assumed to be
Fixed Amount
Other Ward Approx. Per 50,000 Assumed to be
Consumables Month Fixed Amount
Total Consumables (C 2)
Other variable expenses
Concession and Percentage Fixed Percentage
Discount of Receipts of The Total
Receipt of Income
Statement
Other Non-Planned Fixed Assumed
Expenses
Total other variable expenses (C 3)
Total variable expenses (D = C1 + C2 + C3)
Total expenses (fixed, semi-Variable, Variable) (E = A + B + D)
(continued)
22 4 Preparation of Detailed Project Report (DPR) and Techno-Commercial Feasibility Report (TCFR)
Table 4.14 (continued)
Expenses (in million)
1st
Head of expense Unit Rate (in Rs.) Basis of calculation year – 10th year Total
Interest on bank On loan Separate working
loan amount @ of the interest
12.5% P.A calculation attached
At reducing with this report
rate
Interest on working On working Amount of CC *
capital capital rate of interest
amount @
13.5% PA
Total interest on term loans (F)
Depreciation (G) As per schedule of
calculation attached
Total expenses (including depreciation and interest) (H = E + F + G)
All the projected expenditures shall be filled up in this table to calculate the total expenditure of the hospital
(i) Present Market Size of the health- (vii) Awareness of the public for
care facilities Medical Insurance
(ii) Public Healthcare Expenditure by 6. Hospital Management Issues
the Governments (a) Management and Commercial Plans
(iii) Healthcare Infrastructure in the (i) Brief Introduction of the Hospital
country Management
(d) Growth (ii) Outpatient Services
(i) Growth drivers (iii) Inpatient Services
(ii) Medical Tourism and improving (iv) Diagnostic Services
health insurance penetration (v) Interventional Services
(iii) Medical Information and (vi) Material Management
Telemedicine (b) Steps that shall be involved in Setting up
(iv) Trend of Outsourcing Diagnostic a Hospital project
Services in the area 7. Planning the Hospital
(v) Govt. Plans to enhance in (a) Brief Description of Major Disorders
Expenditure in public health (b) Permissions and Clearances Required
(vi) Increment in the Health Awareness from the Govt. Local bodies
amongst population
24 4 Preparation of Detailed Project Report (DPR) and Techno-Commercial Feasibility Report (TCFR)
4.3 General Contents in DPR (e) Responsibility for goods damaged while
in transit or during erection and/or
Apart from the contents given above in Sect. 4.2, commissioning.
the DPR shall also contain information about the (f) Condition of admissibility of any increase
Guidelines, Information, Procedures and Policies in the price/rates of the contract.
that will form part of the planning and designing, (g) Contract variations and the manner of
based on which the work will be executed. handling them.
Usually, the following are provided: (h) Mobilization advance to be paid initially
along with the terms and conditions so
1. General guidelines and conditions that shall that the advance is fully secured.
govern all types of contractual agreements (i) Responsibility to supply the equipment
that are likely to be entered with various agen- and necessary accessories and spare parts.
cies during the project implementation period. 6. DPR shall provide an estimate of the phase-
2. General guidelines for resolution of any dis- wise requirement of capital funds. This plan
pute that may arise in future and arbitration shall be the basis of a strategic planning for
procedures to be indicated, specifying the raising the funds from external sources like
nature of the issue that may be referred for banks and financial institutions, and/or
arbitration or for solving the dispute, powers through public issues.
for solving the disputes, choice of the arbitra- 7. Include a schedule for ensuring adequate flow
tor by both the parties and the place where of funds for the timely completion of the proj-
such proceedings should be held. ect with adequate provision for normal
3. Guidelines related to supply, erection, instal- contingencies.
lation, commissioning and guarantee/war- 8. Include the project phase: A recommended
ranty issues of the various equipment required system of monitoring and control of the finan-
for the project. cial expenses on the project, as compared to
4. Guidelines for choosing the vendors. Will it the physical progress of the project.
be a tendering process or direct quotation 9. The PERT chart clearly depicting the time
method? If tendering, whether to follow a period required for completion of a particular
single- or two-stage tendering. It may also activity or the project as a whole. Also, the
contain model documents and formats related plan of starting and ending dates of the depen-
to an invitation to tenders, specifications etc. dent work (where one work is only possible to
5. Guidelines for vendor short-listing and terms start after completion of some earlier ones).
for contracting. Some points related to vendor What shall be the remedy to cope up with the
detailing that are highlighted in the DPR are time lost due to delay in any particular
as cited below: activity?
(a) Commitment concerning delivery period
of the activity and penalty conditions, in
case of failure to fulfil such commitment. 4.4 Evaluation of DPR
(b) General terms of payment including run-
ning/progress payment. As the final onus of the project vests with the
(c) Inspection and testing procedure and owners, the owner must have an appropriate
points where the customer can hold mechanism and methods to evaluate DPR. The
payments. owners must pose the following questions:
(d) Guarantee test, schedule of testing, proce- 1. What are the sources of critical data and infor-
dure of testing, criteria for success and mation that have been taken in the DPR like
failure and accompanying bank guarantee. demand, capital cost and input cost?
Further Reading 27
Selection of a site for construction of the hospital If the future expansion plans are not considered
is an important issue. Lots of factors have to be today it cannot be done in future.
kept in mind while selecting the site. If a wrong
site is selected, it can be very harmful to the over-
all project. While selecting the site, the below 5.2 Assessment of the Covered
thoughts shall be kept in mind. Area Required for Hospital
© The Author(s), under exclusive license to Springer Nature Singapore Pte Ltd. 2022 29
A. Garg, A. Dewan, Manual of Hospital Planning and Designing,
https://doi.org/10.1007/978-981-16-8456-2_5
30 5 Site Selection
5.6 Maximum Permissible The area around the hospital shall have sufficient
Height of the Building security measures to safeguard patients, families,
personnel and the public.
Authorities also lay down the norms of allowed
building height. There can be various factors
affecting the maximum height like distance from 5.11 Availability of Utilities
the airport, the zone of the earthquake and aver-
age wind pressure. Facilities shall be available nearby to provide
Considering all these norms of the authorities adequate and reliable utilities like water, gas,
along with the required calculated area, the sewer and electricity. The water supply shall be
required land space is calculated. sufficient to cater to the normal usage plus fire-
fighting requirements. The electricity supply line
Other Factors shall be near to the hospital and shall have a sta-
Some of the other factors to be considered while ble voltage and frequency. The sewerage line
finalizing the land are: shall be very near to the hospital building.
Further Reading 31
There shall be proper and adequate roads for an easy 8 Important Things to Consider when Choosing a Location
for the Hospital – Hospital Planning [Internet]. World’s
approach to the hospital. The roads shall be wide Largest Collection of Essays! Published by Experts.
enough for quick and easy traffic movement. 2013 [cited 2021 Jun 8]. Available from: https://
www.shareyouressays.com/knowledge/8-important-
things-to-consider-when-choosing-a-location-for-the-
hospital-hospital-planning/115957
5.13 Environmental Pollution Four criteria for selecting health care sites [Internet].
[cited 2021 Jun 8]. Available from: https://www.
One must try to choose the site having the least hfmmagazine.com/articles/3116-f our-c riteria-f or-
environmental pollution. selecting-health-care-sites
Gul M, Guneri AF. Hospital Location Selection: A
Systematic Literature Review on Methodologies
and Applications. Math Probl Eng. 2021 Feb
5.14 Wind and Earthquake 13;2021:e6682958.
Jamali F, Sadrmousavi MS, Eshlaghi M. An introduction
to hospital sites selection and design. J Hosp. 2012
Before finalizing the land, the care shall be given Aug 10;11(2):87–98.
to the history of the wind pressure and the earth- Moradian MJ, Ardalan A, Nejati A, Boloorani AD,
quake in the area. Akbarisari A, Rastegarfar B. Risk Criteria in Hospital
Site Selection: A Systematic Review. PLoS Curr
[Internet]. 2017 May 1 [cited 2021 Jun 8];9. Available
from: https://www.ncbi.nlm.nih.gov/pmc/articles/
5.15 Flood Protection PMC5419719/
Varnakovida P, Messina JP. Hospital Site Selection
If the planned area is prone to the occasional Analysis. :16.
flood, care has to be taken to choose the area
where the flood situation can be handled easily.
General Issues to Be Considered
While Designing Hospital Building 6
© The Author(s), under exclusive license to Springer Nature Singapore Pte Ltd. 2022 33
A. Garg, A. Dewan, Manual of Hospital Planning and Designing,
https://doi.org/10.1007/978-981-16-8456-2_6
34 6 General Issues to Be Considered While Designing Hospital Building
Before starting the designing of the hospital be such which could easily accommodate all such
that designer shall always be clear on some of the advancement, without involving much alterations
issues like: or modifications. The designer shall always think
of at least 20 years ahead and shall provide suffi-
1. Assess the site location with the direction of cient extra spaces for future expansion. A success-
sun/daylight positioning, air pathways etc. ful hospital design and building project require
2. Size, shape and dimensions of the land. careful designing and planning. It is also recom-
3. Regulations of Setback areas, Land Coverage mended that hospitals should follow more of the
and FSI/FAR and thus total buildable area modular concepts of space planning and layout,
allowed. wherever possible though considering the cost
4. Height restrictions in the area, if any. factors also. Similarly, it is also recommended to
5. Efficient master planning. use generic room sizes, use modular, easily
6. Proper working on the rooms and area accessed and easily modifiable mechanical and
requirement. electrical systems.
7. Services to be offered in the hospital/depart-
ments to be operational in the hospital.
8. Future plans of the hospital related to the 6.3 Design for the Patient
expansion of the services/departments. Experience
9. Medical equipment/devices and their spe-
cific requirements in terms of area, utilities, What is the ultimate object of the hospital? It is
weight, heat load and power load. basically the diagnosis and treatment of the
10. Which diagnostic facilities are to be
patients. Additionally, the other goals of the hos-
provided? pital can be health education or prevention of the
11. Staffing numbers in each department and
diseases, but the main objective is diagnosis and
their specific needs. treatment. A designer must create an environ-
12. Waiting area requirements (number of peo- ment that promotes the well-being of patients
ple expected in the waiting area). because the design of a space is a part of the ther-
13. Workflows of men and material. apeutic process. The design shall be more of a
14. Patient footfalls. Patient-focused design such as providing spaces
15. Patient needs. to store patient’s belongings, working places to
16. Bed types and numbers in each category. have proper mobile charging stations, comfort-
17. Operating room numbers, types based on
able and pleasant waiting areas and designated
surgery types. spaces for private discussions with the
18. Horizontal and vertical movements and
physicians.
flows.
ones who have to provide a quality service. It is While designing a hospital, security and safety
these people who have to actually work and features must be built into the design keeping
deliver the result. Then why should not the these issues in mind.
designer consider taking the views of these One of the greatest issues in healthcare design
employees and physicians who have to actually and operation is the safety of the patient.
work? Physicians and employees shall give their Therefore, a great concern is required for the
design and space requirements under which they safety of patients and attendants while designing
can work efficiently and allow them to do their a hospital. Some concerned events can be fall,
jobs flawlessly to best serve patients and their jump, suicide or theft etc. To reduce such events,
families. the designer shall include non-slippery surfaces
including a ramp, double colour staircase of easy
identification of steps, providing proper wall
6.5 Accessibility to the Patient guards and handrails, unobstructed pathways,
handicapped toilets, sealed windows or windows
What is accessibility in terms of the hospital? As with grills etc.
a hospital provides varied services in a large and Another important concern of patient safety is
different area of the hospital building, it is impor- inpatient suicides. The two most common meth-
tant how soon and by which means the patient ods of suicide in hospitals are jumping and hang-
and attendant can reach that area. This is acces- ing. In a room there can be many things that the
sibility. As everyone cannot walk in right away in patients can use to hang themselves, such as bath-
the hospital and the special facilities may have to room curtain rods, showerheads, fans, hook if
be provided to make it accessible for them to any etc. Thus, alternate methods shall be used
enter hospital like an ambulance or a helicopter and such fittings and fixtures should be avoided.
may need access to your facility, therefore the To minimize jumping, provide windows that can-
Helipad and the Ambulance docking may have to not be opened and are doubled-paned, making
be provided. Likewise, patients may need to be them much harder to breakthrough. Still, if open
transferred to hospital who is already on a bed, or windows are to be provided, proper provision for
on a wheelchair or on crutches. So, the design the windows grills shall be present.
must ensure fast and easy access to the facility.
Therefore, the means like hospital corridors,
staircases, and ramps shall be quite wide and suf- 6.7 Sustainability of Resources
ficient. Similarly, there shall be elevators wide
enough (like Bed Elevators) and fast. Likewise, A hospital building is one of the highest consum-
sufficient spaces shall be provided for ambulance ers of resources like energy and water. Hospitals
bays and a proper helipad should be built (if being a large public building, usually have a sig-
planned and needed). nificant impact on the environment and economy
of the surrounding community. Therefore, a sus-
tainable design has to be worked out for reducing
6.6 ecurity and Safety of Men
S the consumption of these natural resources and
and Material reducing a hospital’s costs on these resources.
There are two issues, one is to minimize the wast-
As the Hospitals are public places, a lot of people age and the other is the alternate sources of these
of different class and status visit the regularly. resources. Let us take the example of energy like
Therefore, there are several security concerns Electricity. To minimize wastage, sensor technol-
such as protection of hospital property, assets, ogy can be used, which turns on and off depend-
public, patients and staff, consumables and drugs ing on the entry or exit from the room, through
etc. Also, vulnerability to terrorism or mob attack sensors. Similarly, at places, one can use time-
because of high visibility cannot be ruled out. based switching on/off the lights. For alternate
36 6 General Issues to Be Considered While Designing Hospital Building
energy sources, one can plan for solar energy etc. ities. The cloud and web technologies have
Similarly, for water, we can consider mist show- changed the world and so have medical services
ers instead of running water etc. Rainwater har- in terms of data storage, research, and clinical tri-
vesting can be a good source of water. For als. Also with the changing technology and infec-
petroleum conservation, design can be planned tious diseases like COVID-19 have pushed the
for battery vehicles etc. The Concepts of smart world towards the adaptation of more and more
cities can be applied to the extent possible. Telemedicine.
Considering this fact of continuous advance-
ment in the technologies, the designer while
6.8 Efficiency designing the hospital has to keep in mind that in
and Cost-Effectiveness the coming future, these advancements have to be
adopted by the hospital. Therefore, the designer
While designing any project, particularly a shall plan and provide spaces for easy adaptation
hospital, the first thing to be kept in mind is of these advancements. Also, keep in mind the
efficiency and for that efficiency how much required modifications that need to be done in
extra cost is needed. One shall not compro- future to adapt to the changing technology.
mise with the efficiency in the hospital design In order to provide timely, accurate diagno-
whatsoever. Even though some extra cost has sis, treatment and interventions, physicians need
to shed out towards efficiency, it should be to have complete and real-time information
considered. What is efficiency in the hospital about the patient, symptoms, investigations,
layout? It is like minimizing the distance of care required and different treatment options.
necessary travel between frequently used Technologies such as the Internet, electronic
spaces; rushing to the patient in case of emer- medical records and clinical decision-support
gency; allow supervision of patients visually; systems can help a lot in achieving the
efficient logistics system for supplies of con- assignment.
sumable, medicines and food and of course
removal of waste; keep spaces out of infection
and cross infection; make efficient use of 6.10 S
tress and Fear of Patients
multi-purpose spaces and consolidate spaces and Visitors
to a smaller space where ever possible.
Stress and Fear of the patients and attendants is
one of the major concerns during the course of a
6.9 Adaptation of Technological patient’s treatment and care. People usually feel
Advancements stressed and fear for their relative or friend who is
suffering from the disease. Therefore, while
In the twenty-first century, everybody has seen designing the hospital, the designer shall create a
the advancement in technology, particularly the design that can reduce the stress and fear of the
advancement in electronics. Another major revo- patient. The environment of the hospital shall
lution has been noticed in Web Technology and give a positive feeling to the people present in the
the usage of Smartphones. Today most of the hospital. While designing, the designer shall plan
equipment in the hospitals is electronic-based to give spaces for some worship area in the prem-
and as there is continuous advancement in the ises. Also, the designer can keep the provision of
electronic, the designs of the medical equipment wall hangings having positive quotes and reli-
are changing. Apart from this a lot of new medi- gious photographs. Apart from this, a provision
cal equipment is being invented, resulting in for continuous counselling of the people in the
more advanced medical care and diagnostic facil- hospital can be provided.
6.14 Noise Reduction 37
6.11 Quality Care of Patients Therefore, the design shall be such that it pro-
vides quick and efficient cleaning, sanitizing and
In a hospital, the quality and quick care of the disinfecting. People come to the hospital with
patients matters a lot. The designer has to ensure germs and bacteria, so the need is to ensure that
that in his/her design quality care is provided the materials you select do not hold these items
without wastage of time, e.g. the provision for a in. Very careful selection of the material is the
separate ambulance bay has to be provided for crux to this. While choosing the material the
emergency and the provision of stretcher trolley designer has to keep in mind how easy they are to
and the wheelchair is provided at the entrance of care for, how much footfall they can sustain,
the door for quick movement of the patient. which methods can be used to clean them, and if
Similarly, immediately on arrival of the patient, they can be cleaned and/or sterilized. In addition
high level of quality and competent care, to the other requirements, floors in hospitals must
availability of qualified physicians and allied
be puncture and impact-, abrasion- and
health professionals leave a positive impact on stain-resistant.
the quality of service. To achieve this, the
designer can plan a Medical Officer room just at
the entrance of the emergency department. 6.14 Noise Reduction
Likewise, so many other factors can be consid-
ered while designing the building. In a hospital setup, noise interferes with comforts
of the patients, affects communication, decreases
concentration, distracts, affects cognitive perfor-
6.12 Therapeutic Environment mance and also increases stress and fatigue.
Noise can also adversely impact healing, disturb
Patients and visitors should perceive a hospital as sleep and reduce overall patient satisfaction lev-
an advanced, equipped, comfortable, safe, els. The causes of noise can be due to movement
unthreatening, and stress-free area capable of of a lot of men and materials at a particular point
maintaining privacy. While designing, apart from of time, screaming due to pain and fear, back-to-
the designer, an interior designer also plays an back patient beds on the same wall, vibration
important role in designing to create an excellent noise on the floor, noise of the mechanical/elec-
healthcare environment. For example, this can be trical/plumbing systems, improper flooring, out-
achieved by considering ample natural lights, side traffic horn and unwanted announcements
fresh air, using cheerful and varied colours and and music at high volume. Also, the unwanted
textures, providing outside views from the patient mobile rings and loud talking create nuisance and
bed, and by providing effective signage systems. disturbance to others.
Designers should provide an environment in Therefore, while designing the hospital the
which the overall design of the building contrib- designer has to keep in mind all these issues and
utes to the process of healing and reduces the provide measures to curb the noise in the hospital
fear, noise, infection rate and that are safe and building. Some of the measures can be like beds
private. shall be placed on the opposite walls instead of
common walls, flooring can be noiseless like rub-
ber or PVC, triple glazed windows can be
6.13 Cleanliness and Sanitation planned, usage of nurse call systems with a mini-
mal tone having vibration features, proper vibra-
As hospitals are dealing with sick and infectious tion pads for electrical/mechanical machines,
patients, an important factor to consider when proper insulation of walls can be an option, spe-
building a hospital is cleanliness and sanitation. cial ceiling tiles that can absorb noise shall be
Hospitals need to be kept extremely clean to pre- opted and mobile phones shall be kept on vibrat-
vent the spread of diseases and infections. ing mode.
38 6 General Issues to Be Considered While Designing Hospital Building
6.20 Wind, Earthquake-Resistant allow easy identification of the spaces. Using dif-
and Flood Protection ferent colour choices for patient private rooms,
corridors, waiting areas, examination rooms, pro-
Hospital buildings shall be designed in such a cedure rooms etc. can have a definite effect on
fashion that can address the issues relating to patient motivation, stress levels and satisfaction.
earthquakes, tornadoes, flooding, hurricanes and
other regional disasters. Planning and design
shall consider the need to protect the life and 6.23 Choice of Building Materials
ensure the safety of all hospital workers, occu-
pants and visitors to the hospital. Also, the design For a hospital building, the choice of materials is
shall have the means and way-outs which shall a skill that the designer puts in. Right from the
permit for continuity of services following such a start of construction, the factor of choice of mate-
disaster. rial comes in. Like for RCC work the choice can
be pre-mix concrete, Hollow block instead of
bricks can be used and flooring can have tiles
6.21 Nature Plus Artwork instead of marble stone. It is also true that materi-
als play an important role in the overall look and
The patients and/or attendants coming to the hos- feel. When designing a hospital specifically,
pital are normally in pain and are mentally dis- materials must be considered for both safety and
turbed. Further, if the hospital’s look and aesthetic looks and must stand up to the steady
ambience are not good, or the colours are not movement of men and material. Flooring, furni-
soothing (like Red is not preferred in hospitals, ture, wall coverings, lighting and even handrails
being the colour of blood), or there is a lot of and other fixtures should be conducive to infec-
noise and disturbance, the patients and attendants tion control measures and should be glare and
do not feel comfortable. Therefore, the hospitals slip-resistant were necessary to maximize safety.
shall try to include nature and artwork to the Moreover, after the COVID-19 period, prefer-
extent possible while designing the building and ence is given to a material that can be easily dis-
the colours shall be attractive etc. The windows infected and sanitized.
shall be provided for better natural views.
Providing all these facilities while designing, will
give more positive feelings to the patient and 6.24 Flooring
attendants. Both nature and artwork shall contrib-
ute to patients having a greater sense of For a hospital, the appropriate flooring choice
well-being. must live up to rigorous standards. The Flooring
must meet strict health codes as provided by vari-
ous standards. When choosing flooring systems
6.22 Colours to Be Used for hospitals, there are several considerations to
take into account and many different require-
Colours give a different sense of place in hospi- ments must be met. In hospitals, different spaces
tals. Also, colour has been known to be associ- may require different floorings. Like the flooring
ated with mood. Colour can even help patients to of the ramps has to be slip-resistant, similarly, the
have a sense of orientation. Therefore, while flooring of reception may differ from the flooring
designing the designer must stress the choice of of patient rooms and corridors etc. Flooring shall
colours. As the choice of colour varies from per- promote safety, maintain hygiene and infection
son to person and the promoter may insist on the control protocols, should be easily cleanable and
colour of his/her choice, but the designer shall disinfectable, contribute to a positive patient
insist on the colours that will fit in the use and experience and with proven durability with mini-
give a soothing effect. Also, the colour shall mal maintenance costs. Flooring shall also look
40 6 General Issues to Be Considered While Designing Hospital Building
aesthetic, give a clean appearance and shall pro- Indmedica - Journal of the Academy of Hospital
vide a positive and welcoming atmosphere for Administration [Internet]. [cited 2021 Jun 10].
Available from: https://www.indmedica.com/journals.
patients, attendants and healthcare workers. php?journalid=6&issueid=25&articleid=238&action
=article
Lateef F. Hospital design for better infection control. J
Further Reading Emerg Trauma Shock. 2009;2(3):175–9.
Major Issues and Trends Impacting Health and
Hospital Planning, Design, Construction,
10 Elements of the Perfect Hospital Design - Architizer Operation and Maintenance [Internet].
Journal [Internet]. Journal. 2019 [cited 2021 Jun 1]. [cited 2021 Jun 10]. Available from: https://
Available from: https://architizer.com/blog/practice/ w w w. a s i a n h h m . c o m / f a c i l i t i e s -o p e r a t i o n s /
details/perfect-hospital-design/ issues-trends-hospital-planning-design
Groeneveld B, Dekkers T, Boon B, D’Olivo P. Challenges Nusem E. Design in Healthcare: Challenges and
for design researchers in healthcare. Des Health. 2018 Opportunities. In 2018.
Jul 3;2(2):305–26. Reiling J, Hughes RG, Murphy MR. The Impact of
Hospital design challenges: now and into the future Facility Design on Patient Safety. In: Hughes RG,
[Internet]. [cited 2021 Jun 10]. Available from: , editor. Patient Safety and Quality: An Evidence-
http://hospitalhealth.com.au/content/design-in-health/ Based Handbook for Nurses [Internet]. Rockville
article/hospital-design-challenges-now-and-into-the- (MD): Agency for Healthcare Research and Quality
future-1050121645 (US); 2008 [cited 2021 Jun 10]. (Advances in Patient
How to Ensure Patient Safety in a Healthcare Setting Safety). Available from: http://www.ncbi.nlm.nih.gov/
[Internet]. Regis College Online. 2018 [cited 2021 books/NBK2633/
Jun 10]. Available from: https://online.regiscollege. Theodore D. Better design, better hospitals. CMAJ Can
edu/blog/7-tips-ensuring-patient-safety-healthcare- Med Assoc J. 2016 Sep 6;188(12):902–3.
settings/
Area Requirement and Planning
7
Now that after the preparation of the DPR and tionality or department and is termed as the car-
acceptance of the feasibility studies is done and pet area. The difference between the carpet area
final approval of the promoter is received, the and the total area is that the carpet area is the
designer has to proceed with the further planning actual functional area and if the wall spaces and
part of the building. The next step is working and the movement spaces like corridors, ramps, stair-
calculating the area requirement. cases and lifts are added to it, it is called the total
Hospitals are one of the most complexes of area.
building types. Hospitals provide a wide range of
services and functional units through its various
departments and support services. These include, 7.1 Functional Areas
but are not limited to, diagnostic and therapeutic
functions, such as operating rooms; emergency; Calculation of the area or space requirement is
imaging; clinical laboratories; support functions, the foremost task the designer has to undertake,
such as housekeeping; food services and funda- and based on these requirements only the designer
mental inpatient care or bed-related activities. can begin the work of architectural drawings.
Each of these functionalities of a hospital includ- Basically, if we see the functionality of the hospi-
ing complicated electrical, mechanical, informa- tal, the following are the functional areas:
tion technology and telecommunications systems,
needs specialized knowledge and expertise. 1. Emergency Services: Is for providing the
Furthermore, due to various regulations, norms service to the patient after the OPD timing or
and code of various agencies which govern the the patient who are critically sick or injured
hospital design, planning and designing of hospi- accidentally and trauma cases.
tal becomes much more complicated. 2. Entrance Area: The area in which the
The design process incorporates the sugges- patients or visitors land into before going to
tions and input from the owner and from key hos- any other department or before availing any
pital staff who has to actually work and deliver other services of the hospital.
results. The designer also has to understand the 3. OPD Services: The area where the outdoor
requirements of the patients, visitors, support consultation is provided to patients who are
staff, volunteers and suppliers who do not gener- not critical or follow-up patients.
ally have direct input towards the design. 4. Diagnostic Services: The area where differ-
What does the area mean? The area is the ent types of diagnostic investigation are per-
space required for the particular service, func- formed to support the physicians for the
© The Author(s), under exclusive license to Springer Nature Singapore Pte Ltd. 2022 41
A. Garg, A. Dewan, Manual of Hospital Planning and Designing,
https://doi.org/10.1007/978-981-16-8456-2_7
42 7 Area Requirement and Planning
actual diagnosis of the disease and further a lot of factors and issues based on which the
management and treatment of the patient. It number of rooms required shall be worked out.
can be Imaging, Clinical Laboratories, Cath Below are some of them, but are not limited to:
Lab etc.
5. Other Treatments: These are the areas 1. Do the promoters desire to follow the norms
where support para-medical treatment like of agencies like NABH or JCI which provide
dialysis or physiotherapy are provided. the minimum standards for hospitals?
6. Intensive Care Services: The area where the 2. What are the projections on the numbers of
critical patients are kept under strict supervi- patients expected to utilize the services of the
sion and monitoring and the treatment is hospital?
provided. 3. How much footfall is expected in the entrance
7. Therapeutic Services: This is the area lobby?
where the interventions and surgeries are 4. How many service counters and how many
performed like Operating Room and Labour shops are planned in the entrance hall?
Room. 5. How big the pharmacy shall be? How many
8. Intermediate Care Area: This is the area patients are expected to take medicine from
where the patients are actually admitted in the pharmacy? What will be the quantum of
the indoor for further management and treat- stock in the pharmacy?
ment. It can be General Wards, Semi-private 6. How many specialities and super speciality
Rooms, Private Rooms, Deluxe Room, VIP departments are to be made operational ini-
Suites, Isolation rooms etc. tially and in future?
9. Administrative/Ancillary Services: The 7. What will be the system of conducting OPD?
area from where the administration of the Will a single OPD chamber be allotted to one
hospital is taken care of. This includes areas speciality or otherwise there will be a cham-
like Directors’ office, MS office, NS office, ber sharing system based on time slot?
IT Department and Personnel/Purchase/ 8. For which departments do the OPD’s have to
Marketing/Accounts office. be designed specifically?
10. Hospital Services: The services which indi- 9. What all procedures and diagnostic services
rectly help in the management and treatment will be provided in the OPD? For example, in
of the patients. This can be like CSSD, Ophthalmology will the service be given for
Kitchen, Laundry, Stores and Mortuary. laser, A-Scan, B-Scan etc. and for Cardiology
11. Engineering Services: The support depart- which investigations will be carried out like
ment keeps the systems of the hospital alive ECG, Echocardiography, Holter, Tilt Test,
so that all other services and departments TMT, ABP, Thallium Test, Nuclear Heart
work smoothly. These are like Electrical, Scan, ElectroPhysiology studies and
Mechanical, Public Health, Fire Protection, Dobutamine Stress Echocardiography?
Communication, Medical Gases, HVAC and 10. What services will be provided in Radiology
various Workshops. initially and in future like X-Rays,
12. Other Services: All other services like Ultrasound, Mammography, CT Scan, MRI,
Security, Transport, Housekeeping, PET CT, PET MRI and Gamma Scan?
Conference and Medical Record. 11. Which investigations will be carried out in
clinical laboratories in-house, and which will
be sent to outside labs?
7.2 Room/Space Requirement 12. Which investigations are planned to be pro-
vided in future?
Once the functional areas are finalized, the next 13. Will the blood bank deal only with whole
step is to prepare the list and details of the rooms blood or the components as well and whether
that will be required for each function. There are the apheresis is planned today or in future?
7.2 Room/Space Requirement 43
14. Will the high-end procedures be done in the future, the answers to these types of questions
hospital like Cath Lab? have to be provided. To answer such questions, it
15. Will the department of Oncology be pro-
is felt that a team of experts be formed, including
vided? If yes will Radiotherapy be the physicians and statisticians, to collect details
provided? either from the other such hospitals or by their
16. How many and what type of patients are own experience. The feasibility studies already
expected to land in emergency and triage? done in this regard earlier shall be of great help to
17. Is a major operating room required in an answer most of such questions.
emergency or is a minor OT enough? Once the answers to such questions are pro-
18. What all paramedical treatment facilities to vided, the actual work of room requirements is
be provided like Physiotherapy, Orthotics, started. For preparing the list of rooms, it has to
Speech Therapy and Occupational Therapy? be assessed how many rooms shall be required
19. Will the facility of Dialysis be provided? If for every functionality and each service of that
yes, how many patients are expected per functionality.
day? Another important issue comes out regard-
20. How many ICUs are to be planned along ing the ancillary rooms required attached to or
with the future expansion plans, e.g. MICU, along with the main service room. For exam-
SICU, RICU, NICU, Neuro ICU, ICCU, ple, the Surgery OPD may require the dressing
Gynae ICU, Paedia ICU, Ortho ICU and room, Eye OPD may require a refraction room,
Pulmonary ICU? laser room, dark room, procedure room etc.
21. How many beds are to be provided in each Hence, the detailed work about the ancillary
ICU? rooms has to be done for each and every ser-
22. Is the HDU/Step Down ICU required? vice room.
23. How many Operating Rooms are to be
Based on the experience and practical uses,
planned? Will there be any dedicated operat- we have worked out a list of such ancillary rooms
ing rooms for specialized surgeries like required along with the main service room, which
Organ Transplants? has been given in Table 7.1.
24. How many delivery rooms are to be planned? Based on the above example, the final list of
Out of which, how many are expected to be rooms required has to be finalized.
infectious?
25. What shall be the bed capacity in each ward/ Table 7.1 Rooms required for various zones/units/
function? For example, the number of beds departments
planned for Triage, Emergency ward, Zone Function/room
General Wards etc.? Entrance area
26. How many Private, Semi-Private, Deluxe
Entrance lobby Trolley park
and VIP Suits are planned? General waiting
Public utilities
27. How many administrative staff are planned
Reception Enquiry counter
to be seated at a time?
Registration counter
28. Will the services of Laundry and Kitchen be Queuing tracks
in-house or outsourced? Records
29. Whether the Oxygen supply is made through Admission counter
a cylinder manifold or liquid oxygen plant Discharge counter
has to be installed? Cash counter
Health insurance counter
Before working out the actual room require- Empanelled patients counter
ment initially and keeping provision for the (continued)
44 7 Area Requirement and Planning
It is recommended that while deciding the After adding the movement area to the func-
room sizes, it shall be borne in mind that the tional area, the total area required for the building
rooms shall be of reasonable size and not to be shall be finalized. It is this sheet on which the
too big resulting in the wastage of space, neither designer will start the work of placing the depart-
too small which may hamper working in that ments, functionalities and services in the archi-
room. tectural drawings.
For deciding the final size of the room, one
has to plan the internal layout of the room, i.e.
how the equipment/machinery shall be placed in 7.4 Zoning
the room, how the bed/couch shall be placed,
what all furniture shall be required in the room, The next step after the calculation of the area
how many people shall be present at a particular requirement is to divide the entire building into
point of time and how much working and move- different zones. What is Zoning? It is grouping
ment space is required in the room. different areas of a hospital according to func-
Based on this layout, the length and breadth of tionality and accessibility to the patient. Normally
the room are decided. Based on these dimen- the hospitals have the following zones:
sions, the area of the room shall be worked out. It
is better if such a list is prepared in a spreadsheet. 1. Outer Zone—Fast movement Zone: These
In the first column, the room name is mentioned, are the areas that are mostly visited by the
the second column is for the number of such patients/attendants. This zone shall be open
rooms required, third is for length, fourth is for for all and immediately accessible to the pub-
breadth, the fifth is for area per room and sixth is lic. These areas are like emergency service,
for the total area of all such rooms. After this outpatient service, cafeteria, entrance hall and
exercise, the total area required for services and administrative service.
functionalities has been finalized. Let us call it a 2. Second Zone—Semi-movement zone: These
Functional Area. are the areas that receive and serve the patients
The format of such a spreadsheet can be as but patients are generally not in direct contact
shown in Table 7.2. with the workers of this zone neither the
Once the functional area of the rooms has patients nor the attendants are required to visit
been worked out, then comes the addition of this zone. But truly speaking some of the ser-
movement spaces like corridors, staircases, stair- vices of this zone requires the physical atten-
case lobbies, lift wells, lift lobbies and ramps to dance of the patients like radiology. The
the functional area. These areas are not directly department like laboratory, pharmacy and
related to any service or functionality but are radiology fall in this zone.
common to all. 3. Inner Zone—Limited movement zone: In
The best way to provide provision for these this zone mostly the indoor wards are cov-
movement spaces is to add a percentage area to ered. Here the services of nursing care and
the functional area actually worked out for each management of patients are provided. This
service and functionalities. Again a question that zone includes Intermediate Care Areas like
arises is: What Percentage to add for Movement General Wards, Semi-Private Rooms, Private
Areas. The percentage shall again depend on the Rooms, Deluxe Rooms and VIP suites.
norms and codes of regulating agencies or other- Generally, the patients/attendants and guests
wise be based on the practical experience of of the patients are allowed in this zone.
users. 4. Deep Zone—Banned Zone: This zone
Normally, it is believed that somewhere includes the critical units and the operating
between 35 and 40% of the total functional area theatre complex. As this needs to be highly
should be added towards the movement areas. sterilized and free from any types of infection,
56
Table 7.2 Sample of working out the room requirement and area calculation for hospital building
Function/room No. of rooms Size Covered area per Total covered area in Total covered area in
Zone Length Breadth unit sq. ft. sq. mt.
OPD services
Specialities Medicine block
Examination room with exam. 4 12 15 180.00 720.00 66.89
cubicles
Rooms for special clinics 4 12 15 180.00 720.00 66.89
Clinical demonstration room 1 25 15 375.00 375.00 34.84
Extra rooms for future 2 12 15 180.00 360.00 33.45
expansion
Reception and enquiry 1 8 8 64.00 64.00 5.95
Registration 1 8 8 64.00 64.00 5.95
Record room 1 12 12 144.00 144.00 13.38
Store 1 8 8 64.00 64.00 5.95
Public utility for faculty 1 8 8 64.00 64.00 5.95
Public utility for patients and 1 12 15 180.00 180.00 16.72
attendants
Sub waiting 1 30 30 900.00 900.00 83.61
Total 3655.00 339.58
Add movement area 35% 1279.25 118.85
Total required area 4934.25 458.43
7 Area Requirement and Planning
7.5 Placement of Zones in the Building 57
the movement in this zone is banned. This Let us take an example of a building having 12
zone is totally segregated from the other pub- stories with a breakup of:
lic zones like outer, second and inner zones.
This zone includes functionalities like all 1. Second basement
ICUs, operation theatres, surgical service, 2. First basement
delivery service and NICU. 3. Ground floor
5. Isolation Zone—Restricted Zone: This zone 4. First floor
is reserved for the infected patient, who can 5. Second floor
easily transmit the disease to other patients or 6. Service floor
healthy people. The patients suffering from 7. Third floor
infections like COVID-19 are kept in this 8. Fourth floor
zone. All the services required for such 9. Fifth floor
patients like isolation ICU, wards and rooms 10. Sixth floor
are located in this zone. The movement to this 11. Seventh floor
zone shall be careful and with all the neces- 12. Eighth floor
sary precautions.
6. Service Zone—This zone is for all other ser- If we want to allot spaces to different zones in
vices department that provides support ser- this building, it can be done as follows:
vices to the functionality of the hospital. This
zone includes areas like dietary service, 1. Second basement: The Services Zone can be
housekeeping service, laundry, MGPS, placed in this basement. Some of the services
Workshops and Medical Records. that can be placed are like Medical Records,
Hospital and Staff Committee (Conference)
Room, Housekeeping, Mobile Transport,
7.5 Placement of Zones Security Control, Workshops, MGPS,
in the Building Communication, Fire Protection Control,
Mechanicals like AC plant, Electrical Panel
Now the time has come to allot the floors and and UPS room, Medical and General Stores,
spaces to different zones in the hospital building. Hospital Information Control including Server
The designer shall keep in mind the distances to be room, Purchase Officer, Marketing Officer,
travelled and the movement of men and material Account Office and Personnel Office. Please
from one zone to another. Moreover, two different avoid the services requiring heavy water con-
zones providing support to each other shall not be sumption or the services which drain heavy
far off but in the vicinity to each other (Fig. 7.1). amounts of water, because it is a very cumber-
some job to drain water from the basements.
Placement of Bunkers for Radiotherapy is a
good option to be done in this basement.
2. First Basement: We can place the administra-
tive department and diagnostic department
along with some of the OPD’s in this base-
ment. The departments and services are like
Radiology, Clinical Laboratories, Blood
Bank, Physiotherapy, Directors Office, Medi-
cal Superintendent Office, Dy. Medical
Superintendent Office, Nursing Superinten-
dent Office, Dy. Nursing Superintendent
Office, Central Sterile Supply, Hospital
Fig. 7.1 Sample drawing of zoning of the hospital
buildings Kitchen and Mortuary.
58 7 Area Requirement and Planning
3. Ground Floor: As the approach to this floor is admitted here. The set up shall include all
accessible easily, so the departments and ser- types of wards, ICU’s and diagnostic facilities
vices most often used by the public are placed like mobile radiology.
on this floor. The departments and services
that can be placed at this floor can be like
Emergency Department along with Further Reading
Emergency Operation theatre complex,
Entrance Lobby, Reception, Billing and A new method for calculating health care spaces
[Internet]. [cited 2021 Jun 10]. Available from:
Registration, Help Desk, Pharmacy, Waiting https://www.hfmmagazine.com/articles/3244-
areas, Cardiac Investigations, Pulmonology calculating-health-care-spaces
Investigations, Neurology Investigations, Academy of architecture for health. Guidelines for design
Other Investigations and Sample Collection and construction of hospital and health care facilities:
2001 edition. Washington, D.C.: AIA; 2002.
room. Almansi K. DEVELOPING A TECHNIQUE TO
4. First Floor: The leftover OPD’s and investiga- CALCULATE THE HOSPITAL SERVICE AREA
tions can be taken on this floor along with the AND MEASURE THE ACCESSIBILITY LEVELS
waiting areas. TO TERTIARY HOSPITALS USING GIS. Int J Sci
Knowl. 2015 Aug 31;6:9.
5. Second Floor: This floor can be used for the Benitez GB, Da Silveira GJC, Fogliatto FS. Layout
Intensive Care Unit and the Operation Theatre Planning in Healthcare Facilities: A Systematic
complex. The departments and the functional- Review. HERD Health Environ Res Des J. 2019 Jul
ity that can be placed here are Operation 1;12(3):31–44.
Gibson I. An approach to hospital planning and design
Theatre Suite, Cath Lab, CCU, SICU and using discrete event simulation. In 2007. p. 1501–9.
CTVS ICU, MICU, RICU, PICU, Burn ICU Griffin CH, Joint Commission, Joint Commission
etc. Also, the Delivery Suite along with OBS Resources, Inc, Joint Commission International, AIA
OT can be placed here. If the Delivery suite is Academy of Architecture for Health, editors. Planning,
design, and construction of health care facilities:
placed here then Neonatal ICU also has to be addressing Joint Commission and JCI standards and
placed near to that only. other considerations--from planning to commission-
6. Service Floor: This floor is mainly used for ing. Third edition. Oak Brook, IL: Joint Commission
the services like BioMedical Workshops, Resources; 2015. 138 p.
Jiang S, Verderber S. On the Planning and Design
other workshops and the placing of the AHU’s of Hospital Circulation Zones: A Review of the
of HVAC. Evidence-Based Literature. HERD Health Environ
7. Third Floor: This floor can be used for Semi- Res Des J. 2016 Oct 14;10.
intensive Care Floor and the functionalities Lavy S, Hamilton DK, Jiang Y, Kircher A, Dixit MK,
Lee J-T. Hospital Building and Departmental
like Step Down ICU/HDU and Dialysis can Area Calculation: Comparison of 36 Recent North
be placed here. American Projects. HERD Health Environ Res Des J.
8. Fourth Floor to Seventh Floor: These floors 2019 Oct 1;12(4):174–85.
can be used for placement of all the General Staff CC. Hospital Space Planners: Planning Hospitals of
the Future [Internet]. [cited 2021 Jun 10]. Available
Wards, Semi-private Ward, Private Ward, from: https://blog.cmecorp.com/hospital-space-
Deluxe Ward and Family Suites. planners-planning-hospitals-of-the-future
9. Eighth Floor: This Floor can be dedicated to
Isolation and only infected patients shall be
Part II
Schematic Design of Hospital
Schematic Design
8
Once the designer is out of the planning phase, the location of rooms, placement of doors and
he/she starts working on the Second Phase, i.e. windows and the overall structure of the building.
Schematic Design. The outlines of spaces for different functional-
ities planned during phase 1 are produced as a
design. Once these are defined, the designer shall
8.1 hat Is the Schematic
W produce several different hospital designs utiliz-
Design? ing these spaces in several unique ways.
The hospital promoters thereafter review and
It is an exercise to produce the complete design refine the designs, keeping in mind the issues
of a project on papers, in the shape of drawings, related to the functionality and usability of the
as planned in phase 1. The schematic design spaces. Also to see that the issues like required
phase aims to develop a plan of action relating to adjacencies, safety, security, code compliance
the building that how the building will look based and aesthetics have been taken care of. The pro-
on the planning and designing and also based on moter and other planning team members then
the client’s budget. carefully scrutinize these schematic drawings for
While preparing the designs, the designer any errors or omissions. The owners choose one
needs to consider the relationship between differ- design that best aligns with their vision for the
ent functionalities of the hospital. It includes the finished hospital project. Once a schematic
complete description of building systems such as design is settled on, the scale at which the project
structural design, mechanical works, HVAC sys- will move forward is defined.
tem, firefighting system, CCTV, plumbing and
electrical systems. The designer also designs the
rough interior and exterior finishes. Schematic Further Reading
Design also includes descriptions of all engineer-
ing considerations that are to be used during the Code C and. Understanding the Architects Design
Phases: Schematic Design; Design Development;
construction and operation of the hospital, mate- Construction Documents [Internet]. [cited 2021 Jun
rials, equipment, systems and spaces to be 10]. Available from: http://canadiantimberframes.
included in the project. These designs also com/understanding-t he-a rchitects-d esign-p hases-
include the floor plans, site plans and building schematic-design-design-development-construction-
documents
elevations produced. Fig. 1.Design schematic from a hospital construction
The designer starts with preparing rough project [Internet]. ResearchGate. [cited 2021 Jun 10].
plans, or schematics, showing a general model of Available from: https://www.researchgate.net/figure/
© The Author(s), under exclusive license to Springer Nature Singapore Pte Ltd. 2022 61
A. Garg, A. Dewan, Manual of Hospital Planning and Designing,
https://doi.org/10.1007/978-981-16-8456-2_8
62 8 Schematic Design
After a schematic design is finalized, the next ance and prevention of the disease among the
step is to prepare the final working drawings. general public.
However, the recent COVID-19 pandemic has In almost all countries, the experience of
defined that the world will have to live with such COVID-19 has demonstrated the potential for
viruses indefinitely. Hospitals being healthcare fundamental shifts, changes or alterations in the
providers, are affected by such pandemics due to hospitals. This includes the design and construc-
a variety of reasons. This chapter will highlight tion of hospitals, training of healthcare workers,
some potential issues that arise in a hospital dur- maintenance of hygiene in the healthcare facility,
ing a pandemic and provide possible solutions to curbing the rate of cross-infection and nosoco-
them which can be practised during the designing mial infection, procurement and management of
phase. critical care equipment along with the personal
Nobody can deny that pandemics are not new, protective equipment (PPE) etc.
but it is this time that the world has known about
the major threat that such pandemics can deliver
if not handled properly, efficiently and in time. 9.1 What Will Be the Design
Globally, the leaders of hospitals are dealing with of Future Hospitals
unprecedented levels of demand for healthcare in
their hospitals and struggling about the solution What will be the design of future healthcare insti-
tutions capable enough to handle pandemics?
to provide optimal medical care to all the needed
patients and the public as a whole. If living with In the past, designers have always concen-
diseases is what we eventually will end up with, trated on the patient and healthcare workers’
there should be certain long-term measures that safety while designing hospitals. However,
shall become a part of our lives. Out of all these, experts predict that post-COVID-19, there are
Hospital Architecture, Design and Planning are more areas to focus on leading to the changes to
the most important. be incorporated in a healthcare facility. Strategies
During the recent COVID-19 pandemic, hos- need to be developed for handling such diseases
pitals faced a large number of problems such as beyond the current scope and capacities. At the
shortage of space to handle the patient surge, same time, a careful balance needs to be main-
infection spread, scarcity of hospital beds, tained to ensure that we do not build such facili-
advanced equipment, doctors and paramedical ties that lay under or unutilized, leading to
staff, and poor awareness of health care, insur- wastage of critical resources like trained staff,
medical equipment and money. To do this, we
© The Author(s), under exclusive license to Springer Nature Singapore Pte Ltd. 2022 63
A. Garg, A. Dewan, Manual of Hospital Planning and Designing,
https://doi.org/10.1007/978-981-16-8456-2_9
64 9 Effects of COVID-19 on the Design of the Hospital
need an advanced and extensive network of sensus with the new or modified design of
accessible, available and affordable hospital-like the healthcare facility.
facilities.
For example, locally available healthcare Let us discuss the above issues in a few more
facility centres can be redeveloped to serve as details:
healthcare provider centres that can address the
rising needs of beds in hospitals and act as an
extension of larger hospitals or neighbourhood 9.3 Changes in the Design
clinics. Coupled with similar screening and treat- of Building, Location, Spaces
ment infrastructure protocols, these facilities can and Sizes of the Rooms
prove to be an asset to the communities. Also, as in the Healthcare Facility
the virus spread rapidly, a new approach is known
as ‘isolation and containment zones’ is essential One has to consider that COVID-19 will force
in the hospital building, design and architecture. experts to think about the transformation of both
If existing healthcare institutions cannot redesign design and material to be used in all spaces of the
their facilities, they shall modify them to a pos- hospital. It has made the world aware of the threat
sible extent. from large-scale infectious diseases, the crip-
pling effect they can have on human lives and this
should lead to a better design in places we live,
9.2 Issues to Be Addressed While work and entertain. Thus, we suggest the follow-
Planning and Designing ing architectural changes that can be imple-
a Hospital mented while designing a new hospital facility or
in Post-COVID-19 Era redesigning an existing one.
zone. Segregation of patients can easily be For an existing hospital, the following altera-
achieved in such a design and the entry of outsid- tions must be performed to a possible extent:
ers can also be restricted to avoid the spread of
infection.
9.4.1 Entrance Lobbies
9.3.2.11 H VAC and Air Handling
System The entrance lobbies are the first place where the
HVAC systems play a very important role in hos- patients, workers and visitors land into. This is
pitals, not only by maintaining comfortable cli- the place from where onwards the segregation,
matic conditions for patients and employees but distancing, and infection control begins.
also by maintaining a clean and germ-free envi- Normally, services like Reception, Inquiry desk,
ronment to contribute to the wellness of the Help desk, Registration, Admission and
patients and to prevent further spread of disease. Discharge desk and Cash Counter are provided in
Also, medical equipment in hospitals is very sen- the entrance lobby. Following are some of the
sitive to temperature and humidity levels and technological advancements that help reduce the
requires perfect air control for them to function spread of infection in the entrance lobbies:
accurately and uninterrupted. These important
factors for air control means the design of air 9.4.1.1 Reduction of People Landing
conditioning systems for the hospitals must con- in the Entrance Lobby
sider the characteristics that need special atten- It is recommended that the entrance, waiting,
tion in this sector. Details of the HVAC system gathering and sitting areas in the entrance lobby
have been provided in another chapter of this should be reduced to a possible extent. The
book under the section ‘Air-Conditioning’. arrangement should be made to provide such ser-
vices through using online registrations, admis-
sions and discharges over the phone etc. There
9.4 Changes in the Layout, shall be no sitting provision in the lobby (if
Facilities of Various essential very few can be allowed with proper
Departments, Emergency social distancing, used majorly for disabled peo-
Rooms, Operating Rooms, ple, pregnant ladies or sick patients).
Intensive Care Area,
Diagnostic Facilities, Waiting 9.4.1.2 Portal Technology
Lobbies, Staff Zones, As the patients are increasingly becoming more
the Administrative and more technology savvy, the portal helps them
Zones etc. do most of the hospital-related bits of help and
tasks. Portals can ease the registration, collection
Hospitals have various departments like Out of reports, inquiry and bookings etc. without vis-
Patient Department, Indoor Patient Department, iting a hospital.
Emergency Department, Intensive Care Suits,
Operating Rooms, Waiting lobbies and Diagnostic 9.4.1.3 Self-service Kiosks
departments like Radiology and Laboratory. In Similar to portals, self-service kiosks can help to
the post-COVID era, the design of these depart- expedite processes like registration in hospital,
ments needs to be altered (redesigned) to avoid enquiry and healthcare information. Patients can
the spread of infection. If a new hospital is to be increasingly do the work that could have been
set up, changes must be planned and imple- done at counters without having to come in con-
mented during the designing phase while keeping tact with anyone. This can help with staff savings
in mind the effect of current pandemic and more while increasing patient comfort. Automated
infections to come in the future. kiosks can assist patients with paying charges of
9.4 Changes in the Layout, Facilities of Various Departments, Emergency Rooms, Operating Rooms,… 67
to sit were preferred. But now, post-COVID-19, all visitor is issued a token at the time of registra-
public spaces, like waiting areas, lobbies and din- tion so that they are well aware of their turn.
ing halls, will have to be carefully planned and They need not be in the waiting lobby or near
designed to create a greater physical separation the service room but can wait somewhere else.
between people by introducing an efficient queu- For information about the status of the token,
ing system. Following are the few suggestions to LCDs can be provided at various places in the
redesign waiting rooms and public spaces: hospital. We can even use advanced technology,
where an SMS will be sent to the mobile num-
9.4.2.1 Individual Seats ber of the token holder as and when his/her
The foremost principle to be followed is that indi- turn arrives.
vidual seats shall be provided to aid social
distancing.
9.4.3 Outpatient Department
9.4.2.2 Sub-waiting Lobbies
It is recommended that instead of large waiting 9.4.3.1 Design of OPD to Be Modified
lobbies, hospitals shall design small and sub- In the future, the design of an OPD has to be
waiting lobbies. For example, instead of provid- modified to maintain social distancing and avoid
ing a large lobby with a seating capacity of 200 in direct contact with patients. For this, some type
the OPD block, a separate sub-waiting lobby of of acrylic or glass partitions will have to be used,
around 30 seats serving one or two OPD rooms wherein on one side of the partition is a staff
shall be created. However, such measures may member, and on the other side is the patient. For
not be practical in all situations, especially for communication between the two, a two-way
small hospitals, nursing homes and clinics. The audio system shall be preferred. Also, doctors
number of people who can be allowed to wait in can use the telemedicine approach to see the
hospital lobbies shall be limited to a certain max- patient remotely on video, and conduct examina-
imum number with a specific minimum spacing tions remotely using IoT-enabled devices.
between their seats. So, future waiting lobbies
could be smaller but in scattered clusters. 9.4.3.2 Use of Touch-Free Medical
Devices
9.4.2.3 Minimize Interaction To avoid direct and close contact with the patient,
with Others it is advised to replace current medical devices
The concept of a smaller enclave waiting space such as BP apparatus, Stethoscope, Pulse
that separates the sick from other patients or visi- Oximeter and Thermometer with their wireless
tors will be preferred. The seating has to be in the and touch-free counterparts.
clusters of small numbers of chairs, say 2–3
chairs per cluster. Further, each cluster shall be 9.4.3.3 OPD Consultation Rooms
portioned from the other with at least 5 ft. acrylic with Videoconferencing
or glass partition to reduce exposure with other Solutions
patients/visitors. It is evident that in the near future, patients
would avoid going to hospitals until and unless
9.4.2.4 Outside Waiting it is really necessary. This would result in
Patients and families shall be encouraged and patients adopting more and more video consul-
advised to wait outside or in their car instead of tations rather than OPD visits, thereby allowing
waiting in the lobby. OPDs to be less crowded. This would com-
pletely change the layout and design of the OPD
9.4.2.5 Adopting a Token System consultation rooms, which would now need to
To reduce the crowd in waiting lobbies, a token incorporate more elements for videoconferenc-
system shall be introduced, where the patient or ing solutions.
9.4 Changes in the Layout, Facilities of Various Departments, Emergency Rooms, Operating Rooms,… 69
9.4.3.4 Creating Virtual OPD Health tools for orders, documentation or simply
We recommend to adopt and introduce the concept search for more patient information.
of Virtual OPD, wherein IT infrastructure shall
play a major role in designing. The patient to doc-
tor communication interface and doctor-to- staff 9.4.4 Emergency Department
communication will be carried out through AV
controls. In today’s world, the widely available The emergency care area that was originally
technologies such as video chat and virtual reality designed for patient resuscitation and attendant
headsets will have to be incorporated to help waiting will now need to be redesigned to prevent
patients stay connected to friends and family. the spread of the virus and cross infection.
7. Administrative departments may be moved A few of the issues that the designer can take
away from the infected areas or otherwise care of while designing a hospital are:
work-from-home arrangements may be
devised to reduce the staff in the hospital
premises. 9.5.1 A
ntimicrobial Finishes and
8. The number of students and vendors inside Materials
the hospital premises at a given point of time
may be limited. The adoption of materials and finishes that are
9. More storage spaces and stores shall be easy to sanitize or are naturally germ-resistant,
planned for storing additional required sup- make it easier to maintain a high level of cleanli-
plies due to increased utilization. ness and hygiene necessary in a hospital environ-
10. This pandemic has shown that there is a need ment. Any material or finish used in a hospital
for giving healthcare workers a place to rest shall be nonporous and nonreactive when exposed
in between hectic shifts, especially the staff to common disinfectants such as bleach, alcohol
like nurses and physicians who find it more and ammonium compounds.
tiring.
11. Proper handwashing facilities, sanitizer
dispensers, donning and doffing rooms for 9.5.2 Use of Antibacterial Materials
PPE kits, Masks/gloves and shoe cover dis-
pensers shall be provided at all the required Antibacterial materials like copper-based prod-
stations. ucts need to be considered for elevators, hand-
rails, doorknobs etc. as these would be frequent
touchpoints. Few manufactures have already
9.5 Acceptance of the New invented and introduced antimicrobial coatings
and Improved Building on floorings, facades, paints and furniture.
Materials Which Seems
to Be More Appropriate
as Per the New Building 9.5.3 Use of Non-porous Materials
Designs or Which Can Ease
Out the Concept of the New The products that are non-porous, wipeable and
and Better-Designed cleanable are not affected by regular fumigation
Building and spraying of disinfectants. The products that
can be used are PVC, UPVC, Glass,
Infection control is one of the most important Polycarbonate, high-pressure laminates etc.
considerations for any hospital as patients and
staff both require a clean and safe working envi-
ronment. A hospital space designed to support 9.5.4 For the Furniture
infection control makes healthcare providers’ job
much easier and saves more lives. Therefore, Use of cloth fabric for furniture upholstery and
while taking the design decisions this important curtains shall be avoided rather, easy-to-clean
factor shall be addressed too. For this, the and sanitize, synthetic materials can be used.
designer may have to reshuffle some of the
spaces, upgrading the materials and the addition
of motion sensors to doors and sinks can be 9.5.5 Touch-free Controls
implemented through renovations to existing
facilities. These modifications can also be Focus shall be given more to ensure minimum
adopted in future hospital designs for better hand contact with either the patients, amongst the
infection control. staff and various other touchpoints. Hence sen-
9.6 Temporary Conversion of Space in the Hospital into Treatment Units, Emergency Suits, ICUs… 73
sors and touch-free technology shall be preferred, used, which are easier to clean and sterilize.
like touch-free control of lights operations, ther- Moreover, nowadays certain floor tiles are avail-
mal controlled sensors for air conditioners, able which are acid, chemical and scratch
detecting overcrowding, sensor-based taps in resistant.
washrooms and other handwashing stations.
9.5.12 Dehumidification
9.5.7 Smart Facade Glazing
In some spaces where the humidity is more than
Smart facade glazing that allows occupants to the required levels, portable dehumidifiers can be
electronically control the quantity and quality of used to control the humidity, hence safeguarding
daylight into the rooms can be used. Such glass the medical equipment that works properly at a
technology allows avoiding fabric blinds that har- defined humidity level.
bour germs and are not easy to clean and sanitize.
Instead of normal wall paints, antibacterial wash- Conference rooms could be fitted with voice-
able paints shall be preferred as there are fewer activated technologies to control lighting, audio
chances of bacterial and viral growth and accu- and visual equipment.
mulation on such surfaces. Also, it is easy to
clean these surfaces.
9.5.15 Automation
9.5.16 Automatic Body Thermal are toilets, then bathrooms might not be there.
Scanner Lifts and staircases to these spaces may not have
been designed for the movement of stretchers and
Automatic body thermal scanners shall be hospital equipment. The AC ducts and vents are
installed at the entrance of crowded places, which not built as per hospital protocol. Other services
beeps if anyone has a temperature beyond the like medical gas pipe system, kitchen, laundry,
accepted range while standing in front of it. general and pharmacy stores and toilets had to be
added to these facilities to make them compre-
hensive for accommodating the patients. If some
9.6 Temporary Conversion of these services do exist, they have to be aug-
of Space in the Hospital into mented to meet the demand and make the stay of
Treatment Units, Emergency patients comfortable. It is relatively easy to locate
Suits, ICUs and Isolation physical space, but more difficult to design the
Units to Handle Surges needed privacy and create a clinical environment.
in the Number of Patients Parking areas could be designed in a way that
due to Pandemics they could be easily converted to a containment
zone or holding areas. If there are car parking
Till today, hospitals are often designed without garages, they can be converted into temporary
having any flexibility or arrangements to accom- COVID treatment spaces.
modate a sudden surge of patients. Some hospi- Some hospitals ended up placing extra beds in
tals may have slight flexibility but are still not Private Rooms, which is not recommended
able to fulfil the surging demand. During the because it may pose a problem of cross-infection.
COVID-19 pandemic, it was felt by all the hospi- Some tried to set up beds in the lobbies and con-
tals that they are running out of spaces and ference rooms. These temporary hospital spaces
resources to treat COVID-19 patients with severe are more likely to support isolation and medical
symptoms, while at the same time handling those care for mild COVID-19 patients than to repli-
patients having mild symptoms or are totally cate a permanent ICU fully. There are many ser-
asymptomatic, who may infect healthcare work- vices required for the treatment of patients in
ers and other patients. ICU like monitoring systems, the supply of medi-
As COVID-19 cases filled up the emergency cal gases, proper air conditioning systems and
rooms and intensive care units across the world, availability of emergency medical equipment.
both in Government hospitals and in Private Hence, it is not advisable to convert any general
COVID hospitals, the management and the or vacant space to an ICU.
Government officials have been rushing to con- In converted buildings, you cannot have
vert hotels, convention centres, stadiums and hospital-like compliance, standards and airflows.
parks into new hospital spaces. One limitation is that the air conditioning, heat-
Spaces like conference halls, lecture theatres, ing and ventilation of converted buildings cannot
seminar halls and library are a part of the hospital be provided in such hospital isolation rooms. But
but not meant for patient use. Apart from these converted sports arenas and hotels could function
are spaces like parking lots (basements or multi- as quarantine centres for mild COVID-19 cases
level car parks), cafeterias and administrative so that hospitals can focus more and more on the
rooms. All these spaces can be temporarily con- seriously sick patients, who require critical care
verted to patient spaces in case of emergency. and strict isolation.
However, these spaces are not designed to Therefore, it is insisted that future hospital
become hospitals; hence there is severe pressure designs shall have more flexibility to handle such
on the medical staff to follow stringent protocols pandemics and other such events that create tem-
to avoid infectious spread, especially in tempo- porary surges and demand.
rarily converted places. Many of these structures On the other hand, it is also true that under
may not have adequate washrooms, and if there such circumstances, the management is left with
9.6 Temporary Conversion of Space in the Hospital into Treatment Units, Emergency Suits, ICUs… 75
no other alternative but to compromise on the pressure and accidents in such temporary lines
quality of services required in these spaces. The Area Line Pressure Alarms, Isolation Valves and
following services are generally required and can Regulators shall be provided at the start point of
be quickly redesigned: such an HP Tube network.
Some of the spaces like parking lots may not have Most hospitals are equipped with regularly
the proper wall finishes, resulting in the spread or required hospital furniture. If extra spaces have to
accumulation of infection. For this, we recom- be converted into patient treatment or quarantine
mend affixing wallpapers or panelling of PVC spaces bed and bedside lockers shall be provided.
material, which not only takes less time but is also Firstly, it is difficult to get hospital furniture in
easy to clean and aesthetically looks decent. such a short period and secondly, a huge invest-
ment has to be planned to acquire the furniture.
The remedy to this is Corrugated Cardboard fur-
9.6.2 Flooring niture. It can be made available and assembled
quickly and is cheap compared to steel furniture.
If the flooring of any of these spaces is rough,
Vinyl floorings can be laid down in a very short
time. Such floorings are found to be hygienic and 9.6.6 Partitions
easy to clean.
The partitions between the bed, nursing station
and other services can be temporarily modular
9.6.3 Electrical Points and expandable and can be created with material
like ICRA Panels or by using the frame of light-
Temporary exposed electrical lines can be planned. weight extruded aluminium panels fitted with
For this, PVC conduit can be fixed on the walls (at Vinyl laminated or PVC Panel Sections. The
a height, out of reach by hand) and wires and erection of this type of partition is cheap and
cables shall pass through such conduit. Wherever time-saving (Fig. 9.2).
required a drop can be given and switches/sockets
can be given on the exposed gang boxes. To ensure
safety, proper circuits shall be prepared and safe- 9.6.7 Washrooms
guarded with the MCBs and circuit breakers. If
medical equipment has to be operated with these There are a lot of options for setting up tempo-
temporary electrical lines, a provision for stabiliz- rary washrooms, one of them is Prefabricated toi-
ers and/or UPS shall be provided. let cabins made out of various materials like FRP,
Steel, RCC and Sandwich puff panel. Other
options can be Rented Toilet Trailers or Chemical
9.6.4 Medical Gases Toilets.
thermal losses and humidity in the area. As soon as he/she activates a call, the ID number is
designing and fixing the HVAC system is a costly displayed at the nurse station.
affair and time consuming, we feel that by divert-
ing some air from the pre-existing AHUs (by
splitting the air ducts), the extended space can be 9.7 Modification and Adoption
air conditioned. Though it will not be as comfort- of Improved Working
able as a designed HVAC system but can be Systems and SOPs Which Are
accepted. However, for large spaces, this method in Consensus with the New
shall not work out. For small rooms, one option is or Modified Design
portable air conditioners. of Healthcare Facility
It is a difficult and costly affair to install a proper A healthcare worker is foremost in healthcare.
nurse call system. But wireless, infrared or All other components, equipment, technologies,
Bluetooth-controlled nurse call systems can be tools, workspaces, facilities, environment, remu-
installed. The remote with a pre-designated ID in neration and organizational conditions provided
the system can be given to the patient, and as to the healthcare workers are secondary.
9.7 Modification and Adoption of Improved Working Systems and SOPs Which Are in Consensus… 77
Therefore, any measures to strengthen the safety (h) All hospital staff should undergo the anti-
and support must be worker focused to facilitate body test, and only those with antibodies
acceptance and implementation. Some of the rec- (and hence with some immunity) should
ommended steps that shall be adopted are: serve in ICUs and Coronavirus wards.
(i) Hand hygiene shall be performed regularly
(a) Health workers treating infected and sus- and after using the toilets, blowing nose,
pected patients, and those treating non- coughing, sneezing, before eating, before
infected patients shall be segregated and after changing dressings or bandages
altogether. This shall help in minimizing the and while entering or leaving rooms.
risk of cross-infection of patients and health- (j) You may be asked to wear a surgical mask
care workers. when leaving your room.
(b) The highest risk tasks to which healthcare (k) Turn away from other people in the room.
workers are exposed are aerosol-generating (l) The entire hospital shall be sanitized as per
procedures like intubation, airway suction- time to time guidelines and protocol issued
ing and bronchoscopy. Health workers treat- by the management. If required fumigation
ing infectious and suspected patients shall shall also be done as per protocol.
be provided with personal protective tools (m) There shall be clearly defined protocols,
and gadgets. The main is donning full PPE systems, procedures and policies for entire
kits, including eye protection, disposable hospital cleaning and sterilization/sanita-
gown, gloves and either an N95 mask or tion. All the surfaces such as working and
powered air purifying respirator. reception counters, tables and ledges shall
(c) Daily temperature monitoring of all health- also be cleaned as per the written protocol.
care workers shall be made mandatory to (n) Limit the number of staff who is exposed to
identify those who are unwell and prevent infectious patients by posting dedicated staff
intra-hospital propagation of infection. in dedicated units.
Healthcare workers whose temperature (o) Try to utilize overtime and long duty shifts
readings are found to be higher than 37.5°C for staff in the infectious units to limit the
shall be immediately be referred for further number of staff required.
evaluation. (p) When possible, use staff who are already
(d) All the healthcare workers shall be encour- immune (recovered) from infectious diseases.
aged to work only for one primary institute (q) Vaccinate all staff for infectious diseases to
and shall not be allowed to work in any other reduce the burden of that disease.
hospital. (r) Arrange for in-house childcare centres for
(e) Mealtimes for healthcare workers shall be the wellness of the children of healthcare
staggered. workers if schools are closed. This can be
(f) Training, teaching and departmental meet- done with the help of screened volunteers.
ings shall be conducted using video confer- (s) Provide medical day care for sick family
encing. These measures are necessary as members.
part of risk mitigation and to maintain the
hospital’s working continuity.
(g) Policies and infrastructure shall support clear, 9.7.2 Entrance
proper and timely communications with
healthcare workers. This will facilitate effec- It is important to screen the patient just at the
tive cascading of information to frontline staff entry point of the hospital. The effective methods
members enabling their work and facilitating for doing this are:
their interactions with the patient and public.
Daily routine instructions can be triggered (a) Wheelchairs and stretcher trolleys kept out-
through emails, Facebook, WhatsApp mes- side the entrance hall shall be sanitized and
sages, SMS or other social media. sterilized regularly.
78 9 Effects of COVID-19 on the Design of the Hospital
(b) Face mask and shoe cover dispenser shall be 9.7.3 Waiting Lobbies
made available at the entrance gate, and it shall
be made mandatory for all visitors, patients As recommended to opt for sub-waiting lobbies
and health workers entering the hospital. instead of one large lobby, the waiting lobbies
(c) The amount of clutter that is located at the shall be small with limited seating capacity.
entrance, corridors and in waiting lobbies Some issues which need consideration are:
shall be minimized.
(d) Hospitals shall have a mandate to set up a (a) The patients and visitors shall be encouraged
facility to screen all the patients and visitors to just arrive at the time of appointment so
of the hospital via a window-protected inter- that the time of waiting is minimized.
view, before allowing them into the hospital. (b) Proper mask and shoe covers shall be worn
This facility shall be set up outside the hospi- while seated in the waiting lobby.
tal entrance lobby. It is important to segre- (c) Distance is essential and visitors or patients
gate the infectious and non-infectious shall not be allowed to shift or move his/her
patients. Those reporting any suspicious chair close to another chair.
symptoms (even the mildest) should be redi- (d) Use the token system to help the patient or
rected to where they can be tested for any visitors know about their turn easily.
infectious disease like COVID-19. (e) Discourage wandering here and there in the
(e) Open walk-in access to OPDs should be waiting lobby.
banned. (f) Limit the use of lavatory and washrooms.
(f) Visitors and outpatients may be the potential Use only if necessary.
carriers of infectious pathogens in the hospi- (g) Discourage littering waste material and pro-
tal. To minimize this risk, arrangements shall mote the use of provided dustbins. Also,
be made so that all the visitors and outpa- keep the lobby smoke and noise free.
tients shall undergo a questionnaire survey of (h) No outside food shall be allowed in the wait-
travel and contact history. Along with this, ing lobbies.
they shall also undergo thermal scanning for
fever before they are allowed into the hospi-
tal premises. 9.7.4 Out Patient Department
(g) Discourage using the services of the inquiry
counter or help desk. Instead, encourage Out Patient Department (OPD) is a place where
online inquiry and online help. the health workers and the patient come in close
(h) Encourage the use of kiosk kept in the proximity to each other. Further one can never
entrance hall of the hospital. know if anyone out of patients and visitors is
(i) Tools such as crowd detection and thermal infected or not. Therefore, care and distancing
scanning shall be used to identify critical spots are necessary. The following steps are recom-
and segregate potential disease carriers. mended, which may help in controlling the
(j) Waiting in the entrance halls shall be discour- spread of infection:
aged and unnecessary waiting shall be avoided.
The waiting chairs in the entrance hall shall be 1. To avoid the rush and gatherings at reception
very limited and reserved for sick, elderly per- and waiting areas, it is recommended that
sons or pregnant women. Others shall be Registration and Scheduling Appointment for
encouraged either to wait outside or move to Consultation shall be promoted. Hence, the
the concerned sub-waiting lobbies. following shall be followed:
(k) Each outpatient/in-patient shall be allowed (a) Online registration and scheduling an
only ONE accompanying person when appointment shall be introduced. Patients
attending the outpatient clinic or staying are made aware of online registration and
with the patient indoors. appointment scheduling.
9.7 Modification and Adoption of Improved Working Systems and SOPs Which Are in Consensus… 79
(b) The payment of the consultation can also (f) Printed prescriptions and reports shall be
be made online. avoided; rather, they shall be sent to the
(c) If the patient still walks into the hospital patient’s registered mobile or email.
without an appointment, he/she shall be (g) An online request shall be sent to the con-
discouraged from going to the reception cerned department if an investigation is
and shall be encouraged to use the kiosk prescribed, like laboratory or radiology,
placed in the entrance lobby. and the patient should be guided to the
(d) On receiving the patient’s online request concerned department.
for an appointment, the hospital shall give
a particular date and time of appointment,
with a request to the patient to be on time 9.7.5 Indoor and Isolation
for the appointment; otherwise, the
appointment might be cancelled. In-patients who stay for a longer duration in the
2. Visitor or patient shall sanitize hands before hospital are more prone to spread or acquire
entering the doctor’s cabin. infections. Therefore, it is recommended that:
3. OPD consultation rooms shall be sterilized
and disinfected by UV-C light on a regular (a) The zoning concept shall be followed strictly.
basis. Care should be taken that the UV light The patient/visitors of one zone must be
is switched off before anybody enters the restricted to enter another zone unless allowed.
OPD consultation room. (b) Separate staff shall take care of such patients
4. Only one person shall be allowed to enter the in each zone. For this, separate staff will be
doctor’s cabin with the patient. needed for isolation cabins, intensive care
5. Specialists (Doctors) shall use the necessary units, and other indoor units. Further in each
personal protective tools and gadgets like PPE unit, separate staff shall be deputed for infec-
kits, eye protection face shields, disposable tive and non-infective spaces.
gowns, gloves and either an N95 mask or (c) Each in-patient shall be restricted to only
powered air purifying respirator while provid- ONE specified visitor to be allowed during
ing consultation in the OPD. the tenure of the hospitalization of the
6. Audio-Video consultation shall be encour- patient. These measures can contribute to
aged. This can either be done by the patient reducing the likelihood of introducing infec-
right from his/her home. In case a patient tion from the community into the hospital
has to come to the OPD, the doctor shall environment.
avoid being in close proximity to the patient. (d) Equipment that is not being used should be
Few steps that can be taken while consulting placed in storage areas with the utmost care
are: and precautions.
(a) The doctor shall remain seated in the cov- (e) One of the factors for the spread of infection
ered acrylic/glass partition and the patient in the hospital can be the face-to-face patient/
should be seated on the other side of the visitor interaction with the nurse in indoor
partition. units. Hence, this face-to-face interaction
(b) The doctor shall use two-way audio com- shall be restricted and other means of interac-
munication kept in the OPD for convers- tion such as intercom, mobile or audio-visual
ing with the patient. communication must be implemented.
(c) The patient shall not try to enter the doc- (f) There will be an integration of technology
tor’s cabin unless advised. with digital infrastructure. Also, with the use
(d) Promote the use of touch-free and wire- of video calls and a virtual contact can be
less substitutes for gadgets like BP appa- established between patients in quarantine,
ratus, Pulse Oximeter and Stethoscope. isolation or intensive care with nurses, doc-
(e) Physical examination shall be avoided tors and their loved ones to minimize contact
unless necessary. and yet create comfort.
80 9 Effects of COVID-19 on the Design of the Hospital
© The Author(s), under exclusive license to Springer Nature Singapore Pte Ltd. 2022 81
A. Garg, A. Dewan, Manual of Hospital Planning and Designing,
https://doi.org/10.1007/978-981-16-8456-2_10
82 10 Site Plan
8. It must show large trees on the land if any. approval. Once it is approved, it will serve as a lay-
9. It has to show Existing and Proposed out map for further designing of the floor plans.
Conditions. Another factor is soil analysis. As the struc-
10. It has to show construction limits and lay ture of the hospital depends a lot upon the soil
down areas. condition, the soil analysis must be performed by
11. It has to show parking. a reputed agency to check the load-bearing capac-
12. It has to show the surrounding streets and ity, type of soil etc. before designing the structure
ground sign locations. of the building.
13. It has to show fire hydrants.
14. Clearly show the location of the other ser-
vices which are being planned outside the
Further Reading
building like Transformer Room, Generator
space, Bio-Medical Waste storage, STP/ETP Ayeni D, Olalusi C, Tukur R. Sustainable Site Planning
Tanks, Liquid Oxygen Plant, Security huts and the Architects’ Role. Acad J Sci. 2017 Jul
and Lawns with waiting areas. 6;07:47–55.
Johnson BJ. Site Planning for Planners: The View from
the Other Side. J Educ Built Environ. 2009 Jul
This site plan shall then be submitted to the pro- 1;4(1):31–56.
moters for finalization. Once the site plan is final- Lai R. Site Planning Scheme of Hard Landscape.
ized, it is then submitted to the authorities for initial Kai Tak Commer [Internet]. [cited 2021 Jun 14];
Further Reading 83
© The Author(s), under exclusive license to Springer Nature Singapore Pte Ltd. 2022 85
A. Garg, A. Dewan, Manual of Hospital Planning and Designing,
https://doi.org/10.1007/978-981-16-8456-2_11
86 11 Detailed Engineering Drawings
• Are the shafts for services provided of the exterior surfaces using stones, paints, glass,
properly? grills etc. These drawings also provide information
• Are the movement spaces sufficient? about the height of the building and the external and
• Is the fire escape root approachable? internal markings, such as doors and windows along
• Is the provision of natural light and cross air with the sizes that will look from outside. It helps a
ventilation properly taken care of? designer understand which direction the building
• Are the doors and windows properly will be facing, the direction of the sun and wind cor-
placed? responding to the building. Even the promoters pre-
• Is there any possibility to reshuffle the room fer to have a 3D look on the elevation to see how the
layouts for better design? building will look from outside (Figs. 11.4 and 11.5).
• (Fig. 11.2).
They are the drawings of the exterior of the building It contains smaller details for finishing of the
and the exterior surfaces of the building. This shall building spaces. It includes the details of types and
include the location of windows and beautification dimension of the finishing part of the spaces like
11.6 Finishing Drawing 87
ENTRANCE
1
5
4
1.WATER BODY 1
2.CHILDREN PLAY AREA
3.GARDEMS (THEME GARDEN)
3
4.JOGGING OR STROLLING 2
5.PAVILION
6.SEAT
7.PLAY COURTS
8.CHESS GARDEN 8 10
9.SCULPTURE GARDEN
10.HERBAL GARDEN
7 11
flooring, false ceiling, paints, colours, plaster, tex- exact measurement and dimensions of each and
tures, doors, toilet fittings, electrical fixtures and every component. If required, the enlarged draw-
window designs. Depending on the requirements, ings of a particular component shall be depicted in
these drawings can be further divided into differ- the final working plan (Fig. 11.8).
ent drawings pertaining to one or more items. For
example, a separate drawing can be prepared
which will show the type, pattern, design, mate- 11.8 Section Drawings
rial, size etc. of doors and windows. Similarly, for
electrical fittings and fixtures, there can be sepa- They show the structure in a sliced form, mean-
rate drawing to show location, type, design colour ing, a particular component is sliced into layers,
of such fittings and fixtures (Fig. 11.7). which helps to identify the primary structures of
the building. Further, section drawings also pro-
vide information for the types of materials to be
11.7 Working Plan Drawings used during construction and how to erect such
material during construction (Fig. 11.9).
The working plans or also called construction
plans are for the contractors to help them in under-
standing the scope of work of the project. The ben- 11.9 Structural Drawings
efits of such a plan are to facilitate the contractors
to calculate and access the construction material to They are the engineering drawings focused on the
be used according to the overall design. The leg- structural part of the building like columns, beams,
end provided in the working drawings provides foundation and slab casting. The design of the
information about the different components of the structure is a crucial part of the building design as
drawings to the contractors. It shall incorporate the the building’s strength depends on the structure.
11.13 Roof Beam and Shuttering Layout Drawings 89
11.11 P
linth Beam Layout
Drawings
11.12 L
intel Beam Layout
Drawings
These are the details of excavation to be done for The hospital requires a system of power and elec-
starting the construction of the building. In case tricity to run the building. This drawing is gener-
there is a basement, this drawing depicts the ally prepared by the Electrical Engineer. It depicts
details of basements and the excavation to be the electrical planning for the Transformer,
done. Also, this drawing shows the details of Energy metre, Main Panel, Floor Panel Circuit
excavations to be done for the foundations of the Diagrams, Line layout, Distribution Boxes,
Switch Boards, Earthing etc. The drawing also
92 11 Detailed Engineering Drawings
Internal Plaster
switches. Also, the escape route drawings in case
12mm
40 mm Terrazo
of fire have to be drawn showing the routes along
Floor Finish
Sub Floor
with the staircases, ramps, fire doors and the sig-
75 mm Brick Bals
RCC Slab
nage location. The drawings also show the loca-
tion of the pressurizing system for lift wells, lift
RCC Iintel (300 mm) lobbies and staircases (Figs. 11.18 and 11.19).
RCC Chaija
These are the construction designs depicting how
projecting 600 mm
an object has to be installed, fitted or manufac-
PCC Drip
100 x 50 mm woodern
frame with rebates for
tured. These drawings are generally prepared for
shutters
35 mm thk wooden services like Air Conditioning, MGPS, CCTV
shutter
6mm thk glass
Wire mesh
network, EPABX network, IT network, Public
Address System network and PTS (Pneumatic
Tube System). They are detailed line diagrams
35 mm thk wooden
shutter
depicting the location of the machines and the
100 x 50 mm wooden
frame with rebates for line of the system. For example, in the case of
shutters
PCC Drip MGPS, the drawing shall show the routing of the
PCC sill projecting
200 mm
External Plaster
pipelines, location of the gas points, design of the
20 mm
manifold room, the pump room etc. Similarly, for
air conditioning, the layout plan of ducts, chilled
water pipelines, AHUs, Plant room and cooling
towers are set in the drawing. Mostly, the shop
C Window Sill detail
Scale 1:10
drawings are prepared by contractors or subcon-
tractors to whom the work has been or would be
Fig. 11.13 Sample of lintel beam layout drawing
Now, as the set of detailed drawings is ready, struction documents are required for the follow-
we move on to the next phase of construction. ing activities:
This phase is to engage contractors for starting
the construction work; however, some docu- 1. Soil analysis.
ments are required for the contractor to under- 2. Excavation of land.
stand before he/she gives his/her rates and 3. Civil Construction.
quotation. It is this set of construction 4. Reinforcement steel binding.
documents. 5. Electrical and Power.
6. Plumbing and Sanitary.
7. Firefighting.
12.1 Definition of Construction 8. Air Conditioning.
Documents 9. Information Technology (Computerization).
10. CCTV System.
It is a set of documents containing the general 11. Public Announcement System.
and supplementary conditions, owner’s special 12. Door Windows.
requirements, drawings, specifications, details, 13. Painting and Polishing.
change orders and other documents prepared by 14. False Ceiling.
the designer or his/her consultants. Contraxct 15. Flooring.
Documents describes the scope, type, quality of 16. Elevation.
materials, supplies, equipment, systems and other 17. Staircase Railing.
elements required to construct a project and 18. Site Development and Landscaping.
accepted by the promoter. 19. Elevators/Lifts.
In any hospital, there are different contractors 20. MGPS.
for different activities. For each and every activ- 21. Modular OT.
ity, a separate contractor may have to be engaged. 22. Signage.
Therefore, each of these contractors may require 23. Curtain track system.
a separate set of construction documents relating 24. Nurse Call System.
to their activity. Generally, for a hospital, con- 25. General Furniture.
© The Author(s), under exclusive license to Springer Nature Singapore Pte Ltd. 2022 103
A. Garg, A. Dewan, Manual of Hospital Planning and Designing,
https://doi.org/10.1007/978-981-16-8456-2_12
104 12 Preparation of Construction Documents
This document contains general information The General Conditions such as the right, respon-
about the site, size of the land, project size, own- sibilities and relationships between the owner
ers of the project, the mission of the project, ser- and contractors shall be laid down. It shall offer a
vices to be provided by the hospital, total covered legal framework for the overall construction con-
area of the hospital etc. This document helps the tract and includes dispute resolution clauses.
contractor to understand the background of the
project.
12.2.6 Special Conditions
into the construction project. It also includes an to bid on or before the last date. The bid has to be
itemized list on the estimated costs of materials, submitted in a sealed envelope under receiving
parts and labour in the construction project. The from the owner.
total cost estimate can be worked out by multi- On the pre-decided date, the envelopes are
plying the quantity (as stated in the bill of quan- opened in front of the bidders. The comparative
tity (BOQ)) with the estimated costs and then sheet is prepared to work out the lowest bidder,
adding the labour or erection charge. and rounds of discussions are carried out with the
bidders. Owners shall satisfy themselves about
the work experience, the capability of the bidder
12.2.10 Drawings to perform the task, bidder’s earlier experience,
availability of the manpower, tools with the bid-
The Construction documents shall also include a der etc.
set of simple drawings that can provide a graphic Once the management is satisfied with all
representation of the scope, extent and character these issues, the agreement’s final terms and con-
of the work that will have to be performed by the ditions are re-discussed and finalized. Last is the
contractor. This is to make the contractor under- negotiation on the price and costs. The terms of
stand the work in drawings. payment are also agreed upon and documented in
the contract agreement.
Once the terms and conditions and cost are
12.2.11 Other Documents agreed upon, the contract agreement is signed
off by both the parties and the work order is
Depending on the requirements, the construction issued.
documents may or may not include the following
documents:
Further Reading
1. Information about liens.
2. Staff requirements. 10 Documents Must Be Included on Every Construction
Project [Internet]. Construction Tuts. 2016 [cited 2021
3. Supervision requirements.
Jun 14]. Available from: https://www.constructiontuts.
4. Safety instructions. com/documents-for-construction-project/
5. Safe work method statements. 10 Documents to Include in Your Construction Contracts
6. Contractor Pre-qualifications terms. [Internet]. The Balance Small Business. [cited 2021
Jun 14]. Available from: https://www.thebalancesmb.
7. Defect management and liability clauses.
com/contract-d ocuments-f or-every-c onstruction-
8. Test requirement and terms. project-844919
9. Inspection and test plans. Construction Contract Documents | A Guide to Common
10. Environmental monitoring system. Contract Parts [Internet]. Levelset. 2019 [cited 2021
Jun 14]. Available from: https://www.levelset.com/
11. Site meetings.
blog/construction-contract-documents-guide/
12. Quality monitoring terms and conditions. Construction Document Preparation – Architect Helper
13. Terms for Extension of time. [Internet]. [cited 2021 Jun 14]. Available from:
14. Materials ordering and inspections terms. http://www.architecthelper.com/our-s ervices/
construction-document-preparation
15. Daily reporting system.
Construction documents checklist: Ensure you have
16. Disposal of wastage. the docs you need [Internet]. Sitemate. 2019
[cited 2021 Jun 14]. Available from: https://site-
These contract documents are given to the mate.com/uk/resources/articles/construction/
contractors who qualify for the pre-bidding qual- construction-documents-checklist/
Contract documents for construction [Internet]. https://
ifications. The bidder is then allowed to visit the www.designingbuildings.co.uk; [cited 2021 Jun 14].
site and seek clarification. Generally, the last date Available from: https://www.designingbuildings.
for bidding is fixed, and the bidders are advised co.uk/wiki/Contract_documents_for_construction
106 12 Preparation of Construction Documents
As the hospital is an institute providing varied The designer has to develop an understanding
types of services in varied departments through of a department or space key requirements to
various means and equipment, each department’s effectively plan and design an efficient and
requirements or space shall be separate. No two patient-friendly environment of that particular
requirements can be alike. For example, the ICU department or space.
and patient room, both are meant to admit the Also, it is true that if the requirement of a par-
patient in-house and provide treatment, but the ticular department or space is not met or designed
setup requirements are totally different. properly, it may not provide the services effec-
Similarly, the requirement of different OPDs tively, resulting in compromised quality.
may be different from each other. Hence, every In the following few chapters, we will discuss
department or space faces unique challenges, and the layouts, placement of equipment, internal
there is no single design solution for any specific designing, finishing and furniture etc. of some of
department or space. these departments and spaces.
© The Author(s), under exclusive license to Springer Nature Singapore Pte Ltd. 2022 109
A. Garg, A. Dewan, Manual of Hospital Planning and Designing,
https://doi.org/10.1007/978-981-16-8456-2_13
Design of the Main Entrance Gate
to the Hospital 14
The hospital’s main entrance is the main gate necting gate between the public road and the hos-
through which the patients or visitors walk into pital road. While designing the main gate, the
the hospital premises. This main gate is a con- following issues shall be considered (Fig. 14.1):
ELEVATION
ENTRANCE
PLAN
© The Author(s), under exclusive license to Springer Nature Singapore Pte Ltd. 2022 111
A. Garg, A. Dewan, Manual of Hospital Planning and Designing,
https://doi.org/10.1007/978-981-16-8456-2_14
112 14 Design of the Main Entrance Gate to the Hospital
1. Usually, the main gate is fixed in the bound- 8. To involve technology, automated gates or
ary wall of the hospital. automated barriers are also used these days.
2. Normally, the hospital shall have at least two 9. The provision for checking the vehicles shall
or more such main gates. One for entrance also be provided at the main gate.
and the other is for exit. 10. The guard shall be trained to guide the driver
3. The width of the gate shall be at least 20 ft. of the vehicle about the landing bay and
connected to the internal road of 20 ft. parking.
4. Be careful that there shall be no hump or 11. The guard at the gate shall also be trained
speed breaker at the main gate. about the Gate Pass system.
5. On one side of the gate, a small additional
gate shall be provided for the pedestrians.
6. Inside the hospital premises, a security post Further Reading
shall be provided to guard the gate for
24 h. Before You Walk through the Door: Site Design for
Healthcare|HDR [Internet]. [cited 2021 Jun 18].
7. Preferably the gate shall be fabricated from Available from: https://www.hdrinc.com/insights/
such material which is rustproof. Use of you-walk-through-door-site-design-healthcare
Stainless Steel is recommended for the fabri- NHS Estates. The design of hospital main entrances.
cation of the gate. London: H.M.S.O.; 1993.
Designing of the Entrance Lobby
of the Hospital 15
The entrance lobbies are the first place where the 15.1.1 The Infrastructure
patients, workers and visitors land into. Entrance of the Entrance Lobby
lobbies in hospitals are more than a transitional (Fig. 15.1)
space between the outside and the inside of the
building. This is the starting point in a hospital to Entrance Lobby Trolley Park
General Waiting
provide quality healthcare services. As it is said,
Public Utilities
‘the first impression is the last impression’, and it
Reception Enquiry Counter
is this lobby that reflects the first impression of Registration Counter
the hospital. Queuing Tracks
This is the place from where onwards the seg- Records
regation, distancing and infection control begin. Admission Counter
Normally, services like Reception, Inquiry desk, Discharge Counter
Help desk, Registration, Admission and Cash Counter
Discharge desk and Cash Counter are provided in Health Insurance Counter
Empanelled Patients
the entrance lobby.
counter
Pharmacy Storage and Disbursing Hall
Bulk Storage
15.1 Location of the Entrance Cold Room
Lobby Expiry Medicine Room
Costly Medicine Room
The Entrance lobby shall be located on the Cut Strip Sorting Room
ground floor of the building and shall be placed Pharmacist Office
just near the main hospital building entrance. It Public Utility for Staff
Arcade Temple
must be placed at a prominently visible location
Snack Counter
from outside as soon as the patient/visitor
Book Shop
approaches the main hospital building. The Gift Shop
approach way to the lobby shall be marked with Other Shop—1
the signage’s so that the visitor/patient can easily Other Shop—2
reach the entrance lobby. ATM
© The Author(s), under exclusive license to Springer Nature Singapore Pte Ltd. 2022 113
A. Garg, A. Dewan, Manual of Hospital Planning and Designing,
https://doi.org/10.1007/978-981-16-8456-2_15
114 15 Designing of the Entrance Lobby of the Hospital
15.4 H
elp Desk, Registration
and Admission
and Discharge Counters
Fig. 15.2 Sample of reception drawing Along with the Reception and enquiry counters,
on either side of the Reception, or other conve-
appealing. Alternatively, a counter made out of nient places in the lobby, the Help Desk, Patient
wood can also be provided. Registration and Admission Discharge counters
A storeroom shall be provided behind the shall be placed. But these counters shall be sepa-
reception, where the receptionist can keep gen- rate and at some distance so that these services’
eral items like stationery, forms, documents and users shall not intermingle with each other. These
discharged files. This room shall have only one counters’ size shall again depend on the expected
door that shall open in the reception. The size of number of patients/visitors likely to use the ser-
this room can be about 3657 mm × 3048 mm. vices. Still, space shall be provided for two staff
The required racks and cupboards shall be pro- members to be seated on each counter. Hence, the
vided in the storeroom (Fig. 15.2). ideal size can be about 2438 mm–3657 mm long.
The counters can either be made out of civil work
with an aesthetic look, and the granite of other
15.3.1 Furniture at the Reception material can be used to make it more appealing.
Alternatively, the counters made out of wood can
1. The counter’s front side shall be about also be provided.
1524 mm in height to let a person stand com-
fortably while talking to the receptionist. On
the other side of the counter, a 610-mm broad 15.4.1 Furniture at Help Desk,
and 762 mm high working top shall be pro- Registration, Admission
vided for the receptionists. and Discharge Counters
2. Two chairs for the receptionists.
1. The counter’s front side shall be about
1524 mm in height to let a person stand com-
15.3.2 Electrical and Other Points at fortably while talking to the staff. On the other
the Reception side of the counter, a 610-mm broad and
762 mm high working top shall be provided
1. At least six 6 Amp Switches/Sockets on the for the staff.
counter wall at the height of about 152 mm 2. Two chairs for the staff on each counter.
from the working top. These points shall be
116 15 Designing of the Entrance Lobby of the Hospital
15.6 Cafeteria
7. Two RJ 11 for Intercom and extension lines. Gift Shop, Book Shop, ATM and Newspaper
8. Sufficient Power/USB points for charging reading deck. The size of these spaces shall be
mobiles in the dining area. decided depending on the requirement and space
availability. As far as the electrical points and
other connectivity points are concerned, it shall
15.7 Pharmacy be as per the concerned shop’s demand.
Self-service kiosks can help expedite processes 1. The lobby shall have two sets of doors, one
like hospital registration, Enquiry and Healthcare for entrance and the other for exit.
Information. Patients can increasingly do the 2. Single door set shall be at least 2438 mm wide
work that could have been done at counters with- with two doors open on both sides.
out having to come in contact with anyone. This 3. For automation, the sensor-operated glass
can help with staff savings while increasing doors can also be opted for.
patient comfort. Automated kiosks can assist 4. An Airlock space connecting the external
patients with paying co-pays, checking identifi- areas with internal areas shall be provided.
cation, signing paperwork and other registration This can be done by providing two doors at a
requirements. distance of say 1829 mm from each other. The
purpose is to decrease the infection rate and to
maintain air conditioning, temperature and air
15.12 Interiors of the Entrance pressurization from internal to external areas.
Lobby 5. Measure shall be provided to prevent outside
air contaminants, such as dust entering the
1. Enlivened by the creation of art galleries or building and therefore the air curtain can be
exhibition spaces. provided.
2. Wide range of materials, colours and textures
shall be used to make it attractive.
3. Adequate windows provision to bring in nat- 15.14 Signage and Wayfinding
ural light and offer views of nature. in the Lobby
4. Spaces for indoor plants.
5. Private space for visitors to discuss their Proper Signage shall be provided, which will
health and payment issues with receptionists allow visitors to understand the layout of the lobby.
and other personnel at the counters. Provide simple and clear wayfinding solu-
6. Play areas for children, if possible. tions. This can be done either with proper signage
120 15 Designing of the Entrance Lobby of the Hospital
or design and material solutions, such as colour- to be provided, the number of visitors
coordinating paths or accent lighting. expected in the lobby etc.
5. Security features like CCTV shall be pro-
vided in this area and shall not be visible and
15.15 Acrylic or Glass Partitions noticeable to the visitors.
6. Security features such as hooters and alarms
It is believed that despite automation, some shall be provided.
patients/visitors will be using the counters and 7. Security to the Reception Desk shall be pro-
service desks. Under such circumstances, there vided to prevent unauthorized access behind
are chances of the staff getting infected. To over- counter areas.
come this issue, it is advised to make a good 8. The cashier shall also be provided with
1219 mm high acrylic or glass partition at the top appropriate barrier for safety.
of the counter or desk so that the staff is always 9. Provision for proper heating and air condi-
on the other side of the partition. tioning shall be provided.
10. A wheelchair-accessible reception booth
should be provided for disabled patients.
15.16 G
eneral Issues Related
to Entrance Lobby
15.17 Outside Entrance Lobby
1. Inside the lobby, the spaces shall be clearly
demarcated into visual zones and visual Outside of the lobby, there shall be a Landing bay
pathways. for dropping and picking up the visitors. This
2. A security checkpoint shall be located in landing bay shall preferably be provided with a
close proximity to the entrance of the lobby. Porch at the entrance gate as a shelter from
3. Security barriers that can be locked in case of inclement weather. The porch shall be wide
emergencies shall be provided. enough to allow two vehicles to pass easily at a
4. Size of the lobby shall be decided based on time. The height of the porch shall be at least
the number of service counters to be pro- 4572 mm from the road level.
vided, the size of the counters, waiting spaces There shall be a clear traffic pattern outside
the lobby.
The emergency department’s entrance lobby the hospital’s doors and entrances. Any staff,
has to be separate and shall not conflict with the patients and visitors entering the Hospital shall
main entrance lobby (Fig. 15.6). be encouraged to use them regularly. As in the
The trolley bay shall be provided outside the case of Hand Wash and Sanitizer stations, before
lobby for parking of wheelchairs and stretcher placing the dispensers, an analysis of the build-
trollies so that the patients dropping in the porch ing’s layout for other accessible locations should
can use them. be done.
The Emergency Department provides urgent The staff in the emergency department should
diagnostic and therapeutic care to patients with: be professionally expert in performing their jobs.
Also, the supporting departments should be ade-
1. Injuries by accidents. quate with good communication facilities. The
2. Sudden attacks of illness or exacerbation of emergency department should have a close rela-
the disease. tionship with all other departments and units of
3. Illness during non-OPD hours or holidays. the hospital.
© The Author(s), under exclusive license to Springer Nature Singapore Pte Ltd. 2022 123
A. Garg, A. Dewan, Manual of Hospital Planning and Designing,
https://doi.org/10.1007/978-981-16-8456-2_16
124 16 Emergency Services
3. Providing first-aid and/or providing the 5. Clear signage for facilities toilets, drinking
required treatment to the patients. water and refreshments areas shall be
4. Screening patients for admission and provid- provided.
ing OPD care during the non-OPD hours or 6. Signage for visually impaired patients and
on the holidays. visitors shall also be planned.
7. All the signage shall be Multilingual, and
one language shall be the local language of
16.2 Location of Emergency the area.
Department 8. Signage of the fire exit shall be prominent at
the places.
The hospital’s emergency department should be 9. Fire escape route maps shall be provided at
located on the ground floor, in front of the hospi- the prominent places.
tal with a separate entry. The emergency shall be 10. Staircases and ramp shall have luminated
easily identifiable using signboards by the signboards.
patients and the vehicles coming into the hospi- 11. Lifts shall have proper signboards.
tal. The department should be near to other inves- 12. Room numbers shall be allotted for each
tigative departments like laboratory and room and also the signage of room number/
radiology. name shall be displayed on the door.
13. Signboard of all the room details with room
numbers shall be displayed at the reception.
16.3 Signage of the Emergency 14. Signboard of precautions to be taken in the
Department department shall be provided.
15. List of do’s and don’ts shall also be provided
An emergency is an important department and in the department.
patients or visitors landing in this department are
usually disturbed and in a hurry. Thus, an effec-
tive signage system allows them to easily identify 16.4 Size of the Emergency
their way for treatment. The following idea must Department
be considered while designing signages for the
emergency department: The overall size of the Emergency depends on the
volume and scope of services provided in the
1. The hospital entrance must be well sign- department. It is not the overall department floor
posted with illuminated signboards. space that is important, but the space critical to
2. Signboards with proper directions should be the services’ efficient functioning. To decide the
displayed at the entrance gate of the hospital size of the emergency department and about ser-
compound and emergency department. vices to be provided in the department, various
3. Signboards with proper direction for all the factors influence the decision, few of them are:
rooms in the Emergency department should
be displayed at the reception and waiting 1. The area in which the hospital is located and
lobby. the type of patients received in the emergency
4. Clear way-finding paths for movement in an department. For example, suppose the hospi-
Emergency Department shall be provided for tal is situated on a roadside or in an industrial
easy movement of the staff, patients and visi- area, accidents cases are always expected to
tors in the department. This can be done with be more, but if the hospital is in a residential
the colour-coded strips on the floor or the area, more patients with cardiac, gastrointes-
walls of the department. tinal or pulmonary diseases will be seen.
16.5 Areas Required for Emergency Department 125
Entrance lobby for the emergency department Outside the Emergency Entrance, space shall be
has to be separate and shall not conflict with the provided for handwash stations or hand sanitizer
main entrance lobby. dispensers.
16.7.2 Furniture
16.8 Triage and Resuscitation
The following furniture shall be placed in the
reception: This is the most important area and the heart of
the emergency department. A triage acts as the
1. Reception Counter. first evaluation area, where a patient’s condition
2. Reception Chairs. and degree of urgency to provide treatment is
assessed. Depending on the patient assessment
outcome, if immediate care is required, the
16.7.3 Tools and Instruments patient will be resuscitated. If required, the
patient will be shifted to the Intensive Care Unit
Reception shall include a provision to place: after resuscitation, or if there is a separate treat-
1. Computer with Printer and UPS. ment cum resuscitation room attached to the
130 16 Emergency Services
emergency, the patient is shifted there. If the con- Apart from this, the triage size also depends
dition of the patient is not critical but requires on the number of beds to be placed in triage and
indoor admission, he/she shall be sent to the the numbers of partitions that have to be done in
ward. Otherwise, the patient shall be given first- the triage to break it into areas like Isolation
aid and discharged. rooms. Once the number of beds to be placed has
been decided, the area required by triage is calcu-
lated considering the standard layout plan of beds
16.8.1 Location of Triage and services. However, per bed area in the triage
shall not be less than 120 sq. feet.
The following shall be considered while deciding However, depending on the load factors of the
the location of a Triage: Emergency department more than one triage area
can be considered. If more than one triage is
1. It shall be immediately near to the entrance planned, each triages can also be designated for
and reception. different departments. Like one for Medicine,
2. It should not be far off from the other support one for Gynae and Obs, one for Orthopaedic, one
services like Radiology. for Surgery etc.
3. It shall have an uninterrupted entry and follow
a single corridor from the entrance to triage.
16.8.3 Issues Related
to Infrastructure of Triage
16.8.2 Size of Triage
The following issues shall be kept in mind while
The size of Triage depends on a lot of factors deciding the infrastructure of Triage:
which are given below:
1. The Triage shall be in a single hall. However,
1. How many patients are expected in Triage separate triage can be planned for infectious
per Day? patients.
2. How many of them may require immediate 2. In a single Triage hall, not more than 10 beds
attention? shall be placed. If more patients are landing
3. Is the hospital located near the main road or or expected, the second hall of triage shall be
industrial area, because if it is so, the number planned.
of accidental cases can be more? 3. The Triage shall have a single entry door.
4. Whether separate resuscitation/treatment 4. The Room of the Emergency Doctor shall be
area has been provided? attached to Triage, and a door connecting
5. What shall be the average length of patient both shall be provided.
stay in triage? 5. The Support Services like X-Ray, Ultrasound,
6. Time taken for investigations. Minor OT shall be attached to Triage as far as
7. The admission rate of the patients. possible.
8. Number of patients of accidents or head injury. 6. Twenty-five percent of the total bed in
9. Number of patients of acute emergency like Triage shall be Isolation beds for infected
cardiac and gastroenterology. patients.
10. Medico-Legal cases attended per day. 7. Toilet shall be attached to Triage.
11. Turnaround time for radiological, pathologi- 8. Plaster Room shall be attached to Triage.
cal and other investigations. 9. Treatment Room shall be attached to Triage.
16.8 Triage and Resuscitation 131
10. Nursing Station of the Triage shall be located few normal beds can be converted to isolation
in the centre of the hall. beds in the triage using collapsible shutters
11. Attached to Triage shall be the Clean Utility, around the bed or fixing temporary acrylic
Dirty Utility, Equipment Store, Medicine partitions.
Store, General Store and Nurse duty room. For Negatively pressurizing the isolation
room/unit/bed please refer to the chapter of
‘HVAC’ (Chap. 38) of this book.
16.8.4 Bed Layout in Triage
The bed in the triage shall be laid out in such a 16.8.6 Resuscitation Rooms
fashion, that it allows easy and smooth working in Triage
all around the bed, also the inter-bed spaces shall
be appropriate for easy working and reduce As mentioned earlier in this chapter, depending
cross-infection rate. The following issues shall be on the patient load and management policies, the
kept in mind while laying down a bed in Triage: Resuscitation Room may or may not be created.
If the Resuscitation area is created, the setup will
1. The head end of the Bed shall be at least be more or less the same except for the following
610 mm away from the wall. differences:
2. The Head support panel of the bed shall be
removable. 1. Normally, the resuscitation room has a single
3. A clear space shall be about 1524 mm on the bed. If it has more than one bed, it will act as
foot end so that the stretcher trolley can be a triage.
easily turned around, and the patient can be 2. The resuscitation room aims to provide exten-
transferred from/to bed. sive care and treatment to the patient at a place
4. Most important, distance from bed to bed away from the other patients.
shall not be less than 1829 mm. 3. The individual room shall be equipped with
gadgets for extensive monitoring like ECG,
NIBP, Oxygen saturation, core temperature,
16.8.5 Isolation Room/Units/Area invasive monitoring, CO2 monitoring and
in Triage defibrillator.
4. Each room shall have a facility for invasive
Triage is the area where all the patients land. and non-invasive ventilation.
Triage shall have the provision for normal beds 5. Each room shall have an emergency crash cart
and a few beds for infected patients called equipped with medicines, material for intuba-
Isolation cabin. Infected patients arriving in the tion, catheters, cannulization and external
Triage shall be placed separately from the non- pacing facilities.
infected patients. 6. Each room shall have a separate washbasin
Therefore, it is recommended that air- for hand wash.
tightened and negative pressure isolation rooms 7. Good quality portable OT light shall also be
shall be created in the Triage. The isolation room/ provided in the room.
units shall have a separate entry than the normal 8. Two portable ventilators shall be provided for
entry of the triage. It is recommended that about all the rooms put together for patient transfer
25% of the triage bed be fixed for isolation bed/ to imaging and other clinical facilities or other
room/unit. Isolation rooms should have attached indoor units like ICU.
toilet. Separate staff shall take care of the patients 9. If needed, the patient warming system shall be
in isolation cabins. In case of shortage of space, a provided.
132 16 Emergency Services
non-invasive ventilation may be required. Hence, 2. Air conditioning control button with tempera-
the supply of Piped Centralized Medical Supply ture adjustment.
is a must. The gases supplied shall be: 3. At least 3 pairs of 6/16 Amp switches/sockets
on each bed and these shall be on UPS
• Oxygen. supply.
• Compressed Air. 4. In the centre of two beds, a pair of two
• Wall-mounted Suction. 6/16 Amp switches/sockets shall be provided
• Nitrous Oxide. at the height of 457 mm from the floor level.
Out of these two, one pair shall be on UPS.
In Triage, the supply (except Nitrous Oxide, 5. Two 6/16 Amp switches/sockets at the height
which is used in OTs) lines shall be provided on of 1219 mm shall be provided on the wall near
each bed. In some hospitals, the outlets of these or behind the nursing counter for View Box or
gases are fixed on the wall itself. charging the medical equipment.
Nowadays, the bed head panel is used for this. 6. Two 6 Amp Switches/Sockets shall be given
Bed Head panel is a 1524-mm panel made of on the Nursing Counter.
extruded sections of aluminium. This panel has a
provision of fixing the gas outlets and electrical
points. This panel also has a service railing on 16.8.15 Other Communication
which the IV rod, tray, and utility basket can be Points in Triage
fixed. This panel is fixed at a height of 1524 mm
above the floor level and goes up to 1829 mm. The following communication points shall be
Other options can be the ceiling suspended provided at each Bed of Triage:
pendant. This has the same facilities as a Bed
Head Panel but is fixed on the ceiling and is sus- 1. Point for Nurse Call device.
pended below so that the bottom of the pendant 2. RJ 45 point for Computer networking.
shall be 1524 mm above the floor level. 3. RJ 11 for Intercom and extension line.
In Triage each bed shall have the following 4. HDMI point for monitor display at other
outlets: locations.
ing issues relating to curtain partitions must be 5. Rooms shall have a provision of an attached
taken care of: toilet.
6. Furniture wise, the room shall have one office
1. The Bed shall be placed in front of one wall of table, chair, bed and cupboard.
the Triage. 7. The room shall have points for a computer
2. The Bed shall have a curtain on all other three with an Internet connection and intercom
sides of the patient bed. point apart from the light and fan.
3. The ceiling suspended curtain track is fixed at 8. The room shall be air-conditioned and the
2134 mm above the floor level. control button with temperature adjustment
4. Curtains shall be hanged on these tracks and shall be provided in the room.
shall be moveable and collapsible.
5. The bottom of the curtain shall be about
457 mm above the floor to allow easy 16.9 Treatment/Procedure Room/
cleaning. Minor Operation Theatre
16.9.3 T
he Infrastructure of Minor 16.9.7 Tools and Instruments
OT
Sterilizing Drums Torches
Extension Cord and Examination Light
Attached to Minor OT shall be: Boxes
Instrument Boxes Chetal Forceps
1. Separate changing room for males and Forceps of all styles and Scissors of all styles and
females. sizes sizes
2. Scrub Room. Needle Holders Suture Sets
3. Store Room. Tray of all styles and All other required
sizes instruments
4. Clean Supply Room.
5. Dirty Utility.
6. Equipment Store.
16.9.8 Doors
16.9.4 Issues Related The Door of the Minor OT shall not be less than
to Infrastructure of Minor OT 1829 mm wide, unobstructed. The door shall be
openable on both the sides in and out.
1. It shall be in a single complex and shall be a
sterilized area.
2. It shall have a single OT table. 16.9.9 Windows
3. It shall have a single entry door.
A window need not be provided in the Minor OT.
2. These can be located in the backside of the Equipment, Instruments and Tools, Doors,
department but connected through a proper Windows, Central Medical Gas Supply,
corridor. Electrical Points and Other Communication
3. Corridor shall be wide enough to easily move Points, please refer to the chapter of ‘Operation
the stretcher or the patient bed without any Theatre Suite’ (Chap. 19) of this book.
interruption.
16.12.3 The Infrastructure 1. The head end of the bed shall be at least
of Observation Ward 305 mm away from the wall.
2. The head support panel of the bed shall be
Observation Ward removable.
Ward Store
3. A clear space of about 1524 mm shall be kept
Examination and Treatment room
near the foot end to allow easy stretcher trol-
Nurses Duty Room
Ward Pantry ley movement for patient transfer.
Resident Doctors and Student 4. Inter-bed space shall not be less than 914 mm.
Duty Room
Night Duty Room for Junior
Residents 16.12.6 Isolation Room
Public Utility for Faculty
in the Observation Ward
Public Utility for Patients and
Attendants
Out of all normal beds, the ward shall have about
25% beds for infected patients called Isolation
cabin. For this, negatively pressurized and air-
16.12.4 Issues Related tightened isolation rooms shall be created with an
to Infrastructure attached toilet in the Observation Ward. These
of Observation Ward isolation rooms shall not be mixed with other
beds in the same hall, but shall be a separate zone
1. It shall preferably be in a single hall. with a barrier in between. Separate staff shall
2. It shall have a single entry door. take care of the patients in isolation cabins.
3. Support services like X-Ray, Ultrasound and In case of a shortage of space for separate
Minor OT shall not be far from the Observation rooms, few beds in the observational ward can be
Ward. converted to isolation cabins. This can be done
4. Twenty-five percent of the total beds in the using collapsible shutters around the bed or by
Observation Ward shall be treated as Isolation fixing temporary acrylic partitions.
beds for the infected patients. For negatively pressurizing the isolation
5. Separate male and female toilets shall be room/bed, please refer to the chapter ‘HVAC’
attached to Observation Ward. (Chap. 38) of this book.
6. Nursing Station of the Observation Ward shall
preferably be located in the centre of the hall.
7. Attached to Observation Ward shall be the 16.12.7 Furniture in Observation
Clean Utility, Dirty Utility, Equipment Store, Ward
Medicine Store, General Store and Nurse duty
room. 16.12.7.1 Patient Furniture
8. Resident doctors’ duty room shall also be pro-
Patient Bed (Multi-positional ICU
vided near the Observation Ward.
Bed on lockable wheels and bedside
safety rails) Step Stool
Bed Side Locker Oxygen
16.12.5 B
ed Layout in Observation Cylinder
Ward Trolley
Over Bed Table IV Stand
Wheel Chair IV Rod
The bed layout should allow easy and smooth
Instrument Trollies Crash Cart
working, along with enough inter-bed space to Stretcher Trolley Back Rest
reduce cross-infection rate. Some of the follow- Dressing Trollies Patient
ing issues shall be considered while laying down Transfer
beds in an Observation Ward: System
16.12 Day-Care Observation Ward 139
6. Two 6 Amp switches/sockets shall be given Use of natural light is recommended as much
on the nursing counter. as possible. All the rooms and the corridors
shall be well lit with proper overlapping of the
lights. No fancy lights are recommended.
16.12.15 Other Communication 4. Temperature
Points in Observation Emergency Department shall preferably be
Ward centrally air-conditioned and maintained at a
comfortable temperature. Particular attention
1. Point for nurse call device. shall be paid towards the proper return of the
2. RJ 45 point for computer networking. air, with no mixing allowed. Air-conditioning
Also, the following points shall be provided at temperature control shall be provided in all
the nursing station: rooms.
1. Point for Nurse Call Control Console. 5. Cross Ventilation
2. RJ 45 point for Computer networking. Cross ventilation must be encouraged without
3. RJ 11 for Intercom and extension line. mixing return air.
4. HDMI point for computer display at other 6. Space for a patient brought dead
locations. When a patient is declared dead on arrival, no
treatment is carried out and the body needs to
be handed over either to the police or to the
16.12.16 Curtain Partitions relatives for further disposal. The procedural
formalities involved in such cases are likely to
All beds in the Observation Ward shall be pro- take some time till the body is disposed of.
vided with hanging curtain partitions. Some However, in the meantime, it is unreasonable
issues related to curtain partitions are as follows: to send the body to the mortuary and it is kept
at a place that is not otherwise visible to other
1. The bed shall be placed in front of one wall of incoming patients/visitors.
the observation ward. 7. Calming colours
2. The bed shall have a curtain on all other three Bright colours shall be avoided in the emer-
sides. gency department. It is advisable to use pastel
3. The ceiling suspended curtain track is fixed at or other soothing colours.
2134 mm above the floor level. 8. Artwork, pictures, posters murals and images
4. Curtains shall be hung on these tracks and shall be provided wherever possible in the
shall be moveable and collapsible. department, as it can help to reduce stress and
5. The bottom of the curtain shall be about anxiety in patients.
457 mm above the floor to allow easy 9. The flooring of the department shall be non-
cleaning. slippery. The level of the floors shall be at
Zero for all the rooms and corridors. If tiles
are fixed on the floor, they should be jointless
16.13 O
ther Issues Relating and no spacers shall be used for fixing the
to Emergency Department tiles.
the same time, it is not practically possible for a phine, pethidine, anti-tetanus serum, anti-gas
hospital to keep a huge amount of equipment, gangrene serum and antibiotics, or fresh blood
staff and supplies at all times to deal with such and plasma expanders. General supplies like
mass casualties as such incidents may occur beds, mattresses, blankets, linen, stretchers
rarely. However, with a prepared plan to deal and refreshments may fall short. Inter-
with such a situation, it should be possible for the department communication may become dif-
existing staff to accept the challenge and provide ficult due to overload on available telephones.
quality patient care effectively, without Available transport may not be enough for
confusion. speedy evacuation. Hence, while designing an
This plan aims to enable the hospital to arrange emergency department all these issues shall
for collection and treatment of casualties arising be addressed, and facilities provided
from major accidents and disasters like air/train beforehand.
crash, major industrial or traffic accidents, fire, 7. Besides the above problems, the arrival of
hurricane, earthquake and flood. mass casualties along with anxious relatives
and curious spectators may create security
issues related to cash and valuables belonging
16.14.1 Factors for Disaster Plan to disabled patients.
Hospital swinging-door requirements [Internet]. [cited New strategies in ED design [Internet]. [cited 2021 Jun
2021 Jun 18]. Available from: https://www.hfmmaga- 18]. Available from: https://www.hfmmagazine.com/
zine.com/articles/3401-hospital-swinging-door-policy articles/1451-new-strategies-in-ed-design
In and Out of the Emergency Room | Streamlined design of Wang T, Zhang S, Bai X. Study on the Design of
patient flow [Internet]. [cited 2021 Jun 18]. Available Emergency Entrances for Hospitals Evidence from
from: https://www.asianhhm.com/facilities-operations/ extremely cold regions -- Urban healing transition
emergency-department-streamlining space. 2017;6.
Marsh RH, Chalmers KD, Checkett KA, Ansara J, Rimpel What’s The Future Of Emergency Department Design?
L, Edmond MC, et al. Emergency Department Design [Internet]. DuvaSawko. 2018 [cited 2021 Jun 18].
in Low- and Middle-Income Settings: Lessons from a Available from: https://www.duvasawko.com/
University Hospital in Haiti. Ann Glob Health. 2020 emergency-department-design/
Jan 20;86(1):6.
Outpatient Department
17
The Outpatient Department (OPD) Unit, also 11. A connecting chain between the community
known as Ambulatory Care Unit, is the depart- and the hospital and helps in providing the
ment in a hospital where consultation is given knowledge and education to the community at
to the ambulatory patients by specialists or large regarding health awareness and prevention
super-specialists. Patients who do not have to of the diseases and promotion of public health.
remain in the hospital overnight are attended to
in OPD.
The main purpose of OPD is to avoid the rush 17.1 Location of the OPD
in the indoor department and to provide follow up
management of the indoor patient after discharge. Location wise, the OPD should be located on the
This is an arrangement of mutual advantage to all ground floor, easily approachable and preferably
concerned, i.e. the doctor, the patient, the society should have a separate entry. In some cases,
and the hospital. because of the shortage of space, it becomes evi-
The OPD provides the following functions: dent that the upper floors are also used for
OPD. In such cases the upper floors should be
1. Consultation with medical specialists and reserved for the examination rooms and the
super specialists. ground floor should be preferred for the
2. Physical examination and investigations. Reception, Registration and Waiting etc.
3. Providing treatment on a day-care basis. Further, all the OPDs should be located near
4. Performing Minor procedures. to each other, so that the patients can easily be
5. Follow up consultation and ongoing case referred to other doctors for cross-reference.
management. Ideally, if possible a separate OPD block should
6. Pre-operative screening of the patient. be provided.
7. Providing health education and counselling A good arrangement of the OPD is that a main
of the patients and families. waiting hall should be made in the centre and the
8. Referring the patients to other specialities or OPDs should be made around that hall, other-
super-specialities for second opinion or wise, there should be the main corridor running
ongoing care and treatment. through the centre of the clinical section, side
9. Refer the patient for admission to a hospital corridors giving access to and separating the dif-
for inpatient services. ferent units. Wherever required the OPD rooms
10. Good centre for providing the training and should be provided with an examination room,
education to the students. and if the space permits, a dressing room.
© The Author(s), under exclusive license to Springer Nature Singapore Pte Ltd. 2022 143
A. Garg, A. Dewan, Manual of Hospital Planning and Designing,
https://doi.org/10.1007/978-981-16-8456-2_17
144 17 Outpatient Department
the height of about 1219 mm from the top of It is recommended that instead of large
the counter with a cut window on the lower waiting lobbies, hospitals shall be designed
side of the glass. for small and sub-waiting lobbies, e.g. instead
2. Two chairs for the staff on each counter. of providing a large lobby with a seating
capacity of 200 in the OPD block, a separate
sub-waiting lobby of around 30 seats serving
17.5.2 Electrical and Other Points at one or two OPD rooms shall be created.
Registration Counters However, such measures may not be practical
in all situations, especially for small hospi-
Each of these counters shall have: tals, nursing homes, clinics etc. The number
of people who shall be allowed to wait in hos-
1. At least six 6 Amp Switches/Sockets on the pital lobbies shall be limited to a defined
wall of the counter at a height of about number of persons that shall be maximum
152 mm from the working top. These points allowed with a specified minimum spacing
shall be used for connecting computers, print- between their seats. So, future waiting lob-
ers and other similar devices. bies could be smaller and in scattered clusters
2. Also, two 15 Amp Switches/Sockets shall be (Fig. 17.2).
provided on the wall behind each counter for 3. Minimize Interaction with others
other appliances. The concept of a smaller enclave waiting
3. Two RJ 45 point for Computer networking. space that separates the sick from other
4. Two RJ 11 for Intercom and extension line. patients or the visitors shall be preferred. The
5. Two USB points for charging mobiles or for seating also has to be in the clusters of small
other use. numbers of chairs, say 2–3 chairs per cluster.
Further, each cluster shall be portioned from
the other with at least 1524 mm acrylic or
17.6 Waiting Lobby/Hall glass partition to reduce exposure with other
patients/visitors.
After getting registered for OPD consultation, 4. Outside waiting
patients need to wait for their turn for consulta- Patients and families shall be advised to
tion. Waiting area shall have drinking water and wait outside or in their car instead of waiting
toilet facilities. Hospitals may have a temple or in the lobby.
meditation room in the waiting hall. Pre-COVID 5. Adopting a Token system
era, there was a concept to create more and more To reduce the crowd in waiting lobbies, a
spaces for waiting lobbies to make it comfortable token system shall be introduced. With this
for patients and attendants to wait. The design system, the patient or visitor is issued a token
was such to accommodate more and more chairs at the time of registration so that he/she is
for seating. Now post COVID-19, all public well aware of his/her turn. He/she need not
spaces including waiting areas, lobbies and dining be in the waiting lobby near the service room
hall shall be carefully planned and designed to but can be waiting somewhere else. For
create a better physical separation between people information about the status of the token,
and the system of appropriate queuing shall be LCDs can be provided at various places of
introduced. Few of the concerned issues are: the hospital wherein a token holder can see
the status of his/her token number. We can
1. The foremost principle to be followed is that further use SMS services where a notifica-
individual seats shall be provided in a fashion tion will be sent to the registered mobile
to maintain appropriate social distancing. number of the token holder as and when his/
2. Sub-waiting lobbies her turn arrives.
148 17 Outpatient Department
Fig. 17.2 Sample
layout of waiting areas
17.7 Examination Rooms ciality can use this room. The benefit of this type
of arrangement is that every time the equipment
The examination/consultation rooms can be of need not be removed from the room, resulting in
two types. First is the Combined Multi- low wear and tear.
Disciplinary Consultation room and the second is
the Separate Consultation Room.
17.8 Procedure/Treatment Rooms
17.7.1 Combined Multi-Disciplinary There are some OPDs that require procedure/
Consultation Room treatment rooms, e.g. Surgery OPD requires
Dressing Room, Minor OT; Ophthalmology
Under this design, several physicians of different requires, Refraction, Orthopty, Dark Room,
disciplines share the same room at different Dressing Room rooms; ENT requires Audiometry,
points of days or time. In this type of scheme, the ENG Lab Speech Therapy Rooms; Gynae Obs.
equipment required for that particular speciality require D&C Room, Antenatal Clinic, Family
is brought into the room when needed and stored Welfare Clinic, Cancer Detection Clinic and
again when not in use. The benefits of this type of Colposcopy Room etc.
scheme are that it can be used for consultation of Preferably, this procedures/treatment shall be
different specialities and saves floor spaces. placed near their respective OPD. Locating them
in a cluster at a particular location is not recom-
mended, as it results in the wastage of physicians’
17.7.2 Separate Consultation Room time and unnecessary movement of the patients.
The total list of such rooms is provided in
Under this type of design, an individual room is this book in the chapter of ‘Area Requirement
allotted to a single speciality and no other spe- and Planning’ (Chap. 7).
17.11 Number of OPDs Required 149
17.10 General Issue While The number of OPDs required depends on many
Designing the OPD factors such as:
1. Transfer of noise and sound between the 1. Number of physicians who will be conducting
consultation rooms should be minimised to OPD at a particular moment of time.
improve the concentration of the physician 2. Type of OPD-like system of whether
and to reduce miscommunication, disrup- Combined Consultation room or Separate
tions and staff errors. Consultation Room. Naturally, if the manage-
2. Waiting rooms and play areas should be ment opts for Single Consultation room con-
located away from consultation and treat- cept, the requirement of OPD consultation
ment rooms as these areas are generally more rooms will be more.
noisy. 3. The size of the population served by the unit
3. Natural Light/Lighting shall be maximized. and demographic trends.
150 17 Outpatient Department
4. Expected number of patients to attend OPD. Doctors table with Side Rack Two Attendants
5. The average duration of the consultation. Chairs
6. Timing of the OPD. If the OPDs are being Doctors Chair Examination
Couch
conducted throughout the day, the chamber
Height adjustment revolving Step Stool
sharing system can be adopted, hence less stool for patient
number of OPDs will be required.
7. The number of referrals and transfers from
other regions or hospitals.
17.12.6 Instruments and Equipment
17.12 Consultation Room All the necessary equipment and gadgets shall be
provided like.
17.12.1 Size of the OPD Room B.P. Apparatus Tongue depressor
Stethoscope Weighing machine
The exact size of the consultation room depends Torch Finger Pulse
on factors like expected visitors, the policy of the Oximeter
hospital and Furniture to be placed in the consul- Knee hammer Intercom
tation room. But the ideal size shall not be less View Box Computer with a
Printer and UPS
than 4267 mm × 3658 mm with arrangements of Special equipment required for different types of
the running water. OPDs should also be provided.
17.12.2 Doors
17.12.7 Electrical Points
in Consultation Room
The Door of the OPD Room shall not be less than
1219 mm wide, unobstructed. The door shall be
The following electrical points shall be provided
on the other side of the examination couch to
in the consultation chamber:
avoid patient exposure in Consultation and
Treatment rooms.
1. Main Switchboard at the entrance wall (other
than the wall on which door will open) for
control of fan and lights of the room along
17.12.3 Windows with one 6 Amp Switch/Socket.
2. Air Conditioning Control button with tem-
The windows shall be preferred in the room, but
perature adjustment.
direct sunlight shall be avoided. The window glass
3. One point on the wall 610 mm above the
can be tinted or curtains/blinds shall be provided.
examination table for examination light along
with the switch.
4. Two 6 Amp Switches/Sockets above on the
17.12.4 Hand Washing wall 1 ft. above the doctor’s table shall be pro-
vided. Also, one 15 Amp Switch/Socket shall
A Hand Basin shall be provided in the room.
be provided adjoining this.
5. Three 6 Amp Switches/Sockets above on the
wall 1 ft. above the doctor’s side rack for the
17.12.5 Furniture computer and printer. Also, one 15 Amp
Switch/Socket shall be provided adjoining to
The following furniture shall be placed in the
this for other equipment or heater.
consultation room:
17.13 Design of OPD 151
The following communication points shall be To avoid direct and close contact with the patient,
provided in the consultation chamber: it is advised to use wireless and touch-free medi-
cal devices to replace the current BP apparatus,
1. RJ 45 point for Computer networking. Stethoscope, Pulse Oximeter, Thermometer etc.
2. RJ 11 for Intercom and extension line.
3. HDMI point for computer display at other
locations. 17.13.2 O
PD Consultation Rooms
with Videoconferencing
Solutions
17.12.9 Curtain Partitions
It is evident that in the near future, patients would
The examination table in the OPD shall be pro- avoid going to hospitals until and unless it is
vided with hanging curtain partitions. Following really necessary. This would result in patients
should be kept in mind when using curtain adopting more and more video consultations
partitions: rather than OPD visits, thereby allowing OPDs to
be less crowded. This would completely change
1. The couch shall be placed in front of one wall the layout and design of the OPD consultation
of the OPD. rooms, which would now need to incorporate
2. The couch shall have a curtain on all the other more elements for videoconferencing solutions.
three sides.
3. The ceiling suspended curtain track is fixed at
2133 mm above the floor level. 17.13.3 Creating Virtual OPD
4. Curtains shall be hung on these tracks and
shall be moveable and collapsible. We recommend adopting and introducing the
5. At the bottom of the curtain, there shall be a concept of Virtual OPD, wherein IT infrastruc-
clear area of about 457 mm from the floor for ture shall play a major role in designing. The
cleaning of the floor. patient to doctor communication interface and
doctor-to-staff communication will be carried out
through AV controls. In today’s world, the widely
17.13 Design of OPD available technologies such as video chat and vir-
tual reality headsets will have to be incorporated
The design of an OPD shall have the provision to to help patients stay connected to friends and
maintain distancing and avoid direct contact with family.
patients. For this, some type of acrylic or glass
partitions can be used, wherein on one side the
staff will be seated and on the other side of the 17.13.4 Sterilization and Pressure
partition the patient. For communication between
the two, a two-way audio-visual system shall be A provision shall be made to protect the OPD by
preferred for easy interaction. Doctors can see the UV-C light disinfection and sanitization from
patient remotely on video, conduct examinations time to time. Also, the OPD should be positively
remotely using IoT-enabled devices (Fig. 17.3). pressurized.
152 17 Outpatient Department
Fig. 17.3 Sample
layout of consultation
chamber in OPD
form the procedure etc. But the ideal size shall 17.14.6 Instruments and Equipment
not be less than 4267 mm × 3658 mm. However,
the size may be increased as per requirement. All the necessary equipment and gadgets as
required by the respective departments or respec-
tive procedures shall be provided.
17.14.2 Doors
2. RJ 11 for Intercom and extension line. 2021 Jun 18]. Available from: https://www.money-
3. HDMI point for computer display at other life.in/article/covid-19-smart-opds-to-help-keep-our-
doctors-safe/60092.html
locations. Design and application of a new doctor workstation
system in outpatient department--《Information of
Medical Equipment》2006年09期 [Internet]. [cited
Further Reading 2021 Jun 18]. Available from: https://en.cnki.com.cn/
Article_en/CJFDTotal-YLSX200609011.htm
Donnellan F, Hussain T, Aftab AR, McGurk C. Reducing
10 hospital design changes, post COVID [Internet]. unnecessary outpatient attendances. Int J Health Care
Health Care Radius. [cited 2021 Jun 18]. Qual Assur. 2010 Jan 1;23(5):527–31.
Available from: https://www.healthcareradius.in/ Fleming RW. outpatient care: Design of outpatient areas.
projects/26279-10-hospital-design-changes-post-covid Hosp Top. 1973 Oct 1;51(10):45–9.
Athula Wijewickrama A K., Soemon Takakuwa. Designing Madsen NB. Framework for Layout Design Supporting
outpatient appointment systems with patient charac- Patient Flow in Outpatient Departments.:144.
teristics: a case study. Int J Healthc Technol Manag. Tabish SA. outpatient services in a hospital. In 2011.
2012 Jan 1;13(1–3):157–69. The patient-centered new outpatient building process
Broberg O, Edwards K. User-driven innovation of an out- design--《Journal of Medical Postgraduates》2009
patient department. Work. 2012 Jan 1;41(Supplement 年04期 [Internet]. [cited 2021 Jun 18]. Available
1):101–6. from: https://en.cnki.com.cn/Article_en/CJFDTotal-
Contributor G. Healthcare Facilities Design After JLYB200904022.htm
COVID-19 [Internet]. Facility Executive - Creating Vahdatzad V, Griffin J. Outpatient clinic layout design
Intelligent Buildings. 2020 [cited 2021 Jun 18]. accounting for flexible policies. In 2016. p. 3668–9.
Available from: https://facilityexecutive.com/2020/06/ Zhao Y, Mourshed M. Patients’ Perspectives on the
healthcare-facilities-design-after-covid-19/ Design of Hospital Outpatient Areas. Buildings. 2017
COVID-19: Smart OPDs To Help Keep Our Doctors Dec;7(4):117.
Safe [Internet]. Moneylife NEWS & VIEWS. [cited
Intensive Care Units
18
© The Author(s), under exclusive license to Springer Nature Singapore Pte Ltd. 2022 155
A. Garg, A. Dewan, Manual of Hospital Planning and Designing,
https://doi.org/10.1007/978-981-16-8456-2_18
156 18 Intensive Care Units
to be collected by the management before plan- Last are the departments which rarely use the
ning the ICUs. The answers will come from the ICU. Hence the ICUs for these departments
data about the number of patients expected; with shall be planned if unavoidable. The patients of
which disease and how many such patients; the these departments shall be adjusted with other
physicians, nurses and paramedical staff required ICUs. But still, if ICUs for these departments
to treat them etc. have to be provided, the bed strength shall not
Based on the answers, it has to be decided be more than 5.
which all ICUs have to be planned, how many Also, it shall be noted that more than 20 beds
beds in each ICU are to be planned and what in each ICU are not recommended in any case,
facilities and equipment are to be provided in otherwise, the required care cannot be provided
each ICU. and justified.
At times, the designers also design the ICU of
different levels like Level-1, Level-2 and Level-3.
These levels are based on the number of beds in 18.3 L
ocation of Intensive Care
ICU, Equipment facility and the staffing pattern Units
of ICU.
There are two schools of thought relating to the
location of ICUs. First recommends that all the
18.2 N
umber of Beds in a Single ICUs should be at a centralized place so that they
Unit of ICU are readily accessible to one another. The reason
is that hygiene can be maintained much more
Once the number of ICUs and types of ICUs to be effectively, control of visitors shall be more effec-
established has been decided, the next question tive and if the patient develops any complications
that arises is ‘How many beds in each unit of suddenly, the specially trained professionals and
ICU?’. As stated earlier, the management has to equipment are immediately available to patients
assess the number of patients expected to arrive from other ICUs.
in each ICU. While assessing the number of The second school of thought favours that the
patients the management shall also assess the location of such intensive units shall be depen-
expected increase in the number of patients in dent on the type of disease or patient. For exam-
future. Also, the assessment has to be done ple, the surgical ICU should be close to the
regarding the average duration of a patient’s stay operating theatre while the medical ICU should
in ICU. Accordingly, a final decision has to be be in close proximity to the medical ward to facil-
made about the number of beds to be placed in itate easy follow up for progressive care.
ICU. We can agree with both the thoughts as there
Another important factor to be considered is are pros and cons for each thought. However, we
that there are few departments in which the suggest that if one to five sets of ICUs are required
patient turnover ratio is very high as compared to and the hospital is in a single block of the build-
others, e.g. the patient’s turnover in Medical ICU, ing, it is better if the ICUs are located at a central-
Surgical ICU shall be very high as compared to ized place and on one floor, referred to as the
others. For these types of ICUs, the bed strength ‘Intensive Care Floor’.
can be somewhere between 10 and 15 in each If the design of the hospital is spread in mul-
ICU unit of Medicine and Surgery. tiple buildings and different departments are
Then there are departments that may have a placed in different buildings, then it is better to
moderate turnover of patients like Cardiology, build the ICU of that particular department in the
Neurology, Neuro Surgery, Paediatric and building or the floor where the parent department
Respiratory. The ICUs of these departments can is located.
be planned with a bed strength of about 6 to 10 But one thing for sure is that, whatever be the
each. location of ICUs, it has to exclude through-traffic
18.5 Size of the ICU 157
and strong provision of infection control shall be The following are the room/areas required for
provided. Particular care has to be taken about an ideal setup of ICU:
the movement and access of ICUs to the public
Patient Care Intensive Care Beds
and visitors. ICUs being restricted areas, the
Zone Isolation Rooms
access and movement of visitors and the public
Examination and Treatment room
should be very restricted. Nursing Station
Regarding the floor at which the ICU shall be Public Utility for Patients
located, again there are different opinions. Some Clinical Support Clean Utility
people prefer to have ICUs on the top floor of the Zone Dirty Utility / Sluice Room
building. The reason stated behind this thought is Medication Rooms
that the traffic can be controlled effectively and Equipment Park / Store
the chances of infections are reduced. The other Radiology
thought is that the ICUs shall be sandwiched Sample Collection Room
Unit Support Change Room—Male
between two floors somewhere between the
Zone Change Room—Female
buildings. The reason is that due to heavy thermal
Resident Doctors and Student
losses on the top floor, the air conditioning has to Duty Room
be more effective resulting in higher operational Nurses Night Duty Room
costs. Night Duty Room for On-Call
Another factor to be considered while decid- Junior Residents
ing the location of the ICUs is that it should be Staff Lounge
adjacent to and not far off from Emergency, Staff Restrooms
Ward Pantry
Operating Room, Radiology etc.
Lockers
As the diagnostic department and Emergency Family Support Family Lounge
are mostly on the ground floor, hence this can be Zone Consultation Rooms
one justification to locate ICU somewhere on the Meditation Spaces
second or third floor of the building. Family Nourishment
Public Utility for Attendants
Family Laundry
18.4 Infrastructure of ICU Family Sleep Rooms
1. Patient Care Zone Before deciding and designing the ICU, the
This zone consists of Patient Rooms, designer has to understand in depth the equip-
Isolation Rooms and adjacent areas and its ment to be placed in ICU; support functions to be
main function is direct patient care only. provided; the movement of men and material;
2. Clinical Support Zone inventory of tools, instruments, consumables and
This Zone consists of functions closely supplies; staff ratio and distances from support
related to direct patient care. rooms etc. This designer shall also keep in mind
3. Unit Support Zone the current and future requirements. Ample
This is a Zone from where the administra- spaces shall be planned to adjust future expan-
tive, materials management and staff support sions without any major alterations.
functions shall be provided. The design shall be such that can reduce the
4. Family Support Zone travel distances of staff by placing mostly needed
This is the zone designed to support fami- spaces and equipment as close as possible to the
lies and visitors. site of use.
158 18 Intensive Care Units
18.6 Sizing Considerations patient unit. Hence, the total area per bed in ICU
shall be 10.87 Sq. Mtr. + 40% of 10.87 Sq. Mtr. =
How much area per bed is needed in ICU along 15.24 Sq. Mtr.
with movement spaces? How to answer this ques- Therefore, the per bed area of any ICU shall
tion? There are different thoughts on this issue. be somewhere between 13.94 and 16.26 Sq. Mtr.
Even some countries or the governing bodies and This figure is always subjected to variation
regulating authorities have specified different depending on the criticality of the patient. If very
norms for such areas. sick patients are to be treated, where more equip-
Let us calculate the area scientifically: ment, material and manpower will be required,
the area can go up to 18.58 Sq. Mtr. If it is felt
• Dimensions of Bed (H × W): that the patients in any ICU will not be very sick
1829 mm ×914 mm = 1.672 Sq. Mtr. and the requirement of equipment will be less,
• The distance of the head end of the bed from the area can be reduced to 13.0–13.94 Sq. Mtr.
wall: 610 mm. If instead of Open ICU, a closed cubical with
• Free space for bed at foot end: 1524 mm. a single bed is planned, the area shall not be less
• Left and right bed to bed distance 914 mm on than 23.23 Sq. Mtr. per bed. Same is the case with
each side. the isolation chamber/room.
• Now the total width space required: Now about the issues of all four zones one
914 + 914 + 914 = 2742 mm. by one.
• Total Length space required:
1829 + 610 + 1524 = 3963 mm.
• Total area per bed: 3963 ×2743 mm = 10.87 18.7 Patient Care Zone
Sq. Mtr.
The Patient Care Zone is the area where direct
Add at least 45% for other movement spaces patient care is provided and includes Patient
including Nursing Station that has to be in the Units/Rooms/Cubicles. It also includes immedi-
18.7 Patient Care Zone 159
ately adjacent areas like Treatment/Procedure sion for normal beds and few beds for infected
Room and the Nursing Counter. patients called Isolation cabin/unit/cubical.
Therefore, it is recommended that Negative
pressure isolation rooms/units/cubicles shall be
18.7.1 Patient Unit created in the ICU. The Isolation room/units shall
have a separate entry other than the normal entry
18.7.1.1 Bed Layout in ICU Hall of the ICU. It is recommended that about 25% of
The bed in the ICU shall be laid out in such a the beds in ICU can be reserved for isolation
fashion, that it allows easy and smooth working beds/rooms/units. Isolation rooms should have
all around the bed, also the inter-bed spaces shall separate attached toilets.
be appropriate for easy working and reduce The isolation shall be properly air-tightened
cross-infection rate. Some issues that shall be and negatively pressurized. These isolation cab-
kept in mind while laying down the beds in ICU: ins/rooms/units shall not be mixed up with other
beds in the same hall, but shall be a separate zone
1. The head end of the Bed shall be at least with a barrier in between. Separate staff shall take
610 mm away from the wall. care of the patients in isolation cabins. Or other-
2. The Head support panel of the bed shall be wise, if there is a shortage of space for separate
removable. rooms/units, few particular beds in the ICU can be
3. On the foot end, a clear space shall be about converted to an isolation unit. For this, at some
1524 mm so that the stretcher trolley can eas- particular bed, with the help of collapsible shut-
ily be turned around and the patient can be ters around the bed or fixing temporary acrylic
transferred from/to bed. partitions, an isolation bed can be created.
4. Most important, distance from the bed to bed For negatively, pressurizing the isolation
shall not be less than 1829 mm, i.e. 914 mm room/unit/bed please refer to the chapter of
on either side of each bed. ‘HVAC’ (Chap. 38) of this book.
Multi-para Vital Sign Suction Machine The Door of the ICU shall not be less than
Monitor 1829 mm wide, unobstructed. The door shall be
Invasive Mechanical Portable X-Ray openable on both the sides in and out.
Ventilator Machine
Non-invasive Ventilator Blood Gas Analyzer
High Flow Nasal Canula Cardiac Marker
Analyser 18.7.7 Windows
Infusion Pump B.P. Apparatus
DVT Pumps Pulse Oximeter As natural light helps in early recovery and avoid
Nebuliser Glucometer disorientation and sense of claustrophobia of
Defibrillator Laryngoscope patients, windows shall be preferred in the room
ECG Machine Oxygen Cylinders but direct sunlight shall be avoided. Further, if the
with Masks
patient is provided with a window to have an out-
View Boxes Ambu bag
side view, like looking at a garden, trees, court-
Blood Gas Analyzer with Cardiac Marker
Electrolytes Analyzers yard or another natural setting, may help to
Air Mattress Ambu Mask different relieve anxiety and stress, improve care, enhance
sizes patients’ comfort and improve patient orienta-
Chest drainage equipment ETO sterilization tion. As the bed head panels have to be fixed on
CRRT Fibreoptic the wall above the patients, the bottom of the
Bronchoscope
window shall not be less than 1829 mm from
Dialysis Machines IABP, Intra-Aortic
Balloon Pulsation floor level. The window glass can be tinted or
End-tidal Intubating Video curtains/blinds shall be provided.
CO2 monitor—Capnography scope If cost is not a criterion, even electronic
Invasive BP, SPO2, NIBP, Pacemaker windows that are opaque when the switch is
ECG, RR, Temp Probes with on and transparent when switched off, can be
trays
Spinal Board Transport Ventilator
thought of.
Computers Ultrasound and Echo
machine
18.7.8 Nursing Station
18.7.5 Tools and Instruments Nursing is a crucial factor for the treatment of the
patient in an ICU. It is the Nurse who is available
to the patients most of the time. The nurse has to
Sterilizing Drums Torches
keep a rigorous watch on the patient and skilfully
Walkers/Crutches Examination Light
Splints Chetal Forceps notice the vitals of the patient. Nurse, therefore,
Extension Cord and Forceps of all styles and shall have a continuous watch on the patient in
Boxes sizes the unit/room.
Operating Light Needle Holders Therefore, the proper location of the nursing
Refrigerator Tray of all styles and sizes station is very crucial. The location shall be such
Instrument Boxes Scissors of all styles and so that the nursing staff can have a continuous
sizes
look at the patients in the entire unit. If we place
Proctoscope Suture Sets
Weighing Machine All other required
a nursing station on one side or corner of the unit,
instruments he/she may not be able to see the patients on the
other end of the unit or rooms.
18.7 Patient Care Zone 161
4. Temperature shall be between 18 and 24 tor and also the utility basket can be fixed on the
degree Celsius. front wall. The pendant can revolve at 270
5. Depending on the type of room/unit the degrees. Further, the pendant can be a single arm
choice of positive or negative operating pres- or dual-arm. The single-arm revolves at its own
sures has to be adopted. For the Isolation axis only, whereas the dual-arm pendant can
room, the concept of Negative pressure shall revolve on both arms hence covering more area
be adopted. around the bed.
For full details on Air-conditioning, heat- In ICU, each bed shall have the following
ing and air exchanges, please refer to the outlets:
chapter of ‘HVAC’ (Chap. 38) in this book.
1. 2 outlets for Oxygen
2. 1 outlet for Compressed Air
18.7.12 C
entral Piped Medical Gas 3. 2 outlets for Suction
Supply
On the bed head panel or the pendent both, the
As the critical patients arrive in the ICU, usually electrical and communication points and ports
they are in need of oxygen. Also for some patients shall be provided. Details are given in the electri-
invasive or non-invasive ventilation may be cal point and Communication point below.
required. Hence, the supply of Piped Centralized
Medical Supply is a must. The gases supplied
are: 18.7.13 Electrical Points in ICU
Similarly, at the Nursing Station, the follow- The following shall be the considerations for
ing points shall be provided: deciding the location of the Treatment/Procedure
Room:
1. Point for Nurse Call Control Console
2. RJ 45 point for Computer networking 1. Treatment/Procedure Room shall be either
3. RJ 11 for Intercom and extension line attached to ICU or otherwise very near to
4. HDMI point for computer display at other ICU.
locations 2. Treatment/Procedure Room should not be far
off from the other support services like
Radiology and other necessary support
18.7.15 Curtain Partitions services.
• Oxygen
18.8.5 Equipment
• Compressed Air
• Suction
Multi Para Vital Sign Portable Operating Light
Monitor Single Dome
Infusion Pump Laryngoscope
The Ceiling suspended pendant should be pro-
Suction Machine Oxygen Cylinders with vided. This panel is to be fixed on the ceiling and
Masks is suspended below such that the bottom of the
Defibrillator B.P. Apparatus pendant shall be 1524 mm from the floor.
View Boxes Ambu bag with Mask of In Treatment/Procedure Room shall have the
different sizes following gas outlets:
of the pendant. These points shall be on UPS (a) Soiled linen collection hamper.
supply. (b) The waste collection as per the norms of
4. On three walls of the Treatment/Procedure Biomedical Waste Management.
Room (leaving the wall on which door is pro- (c) A Wall Clock on the foot end of the
vided) in the centre of each wall, a pair of two patient.
6/16 Amp. switches/sockets is to be provided (d) Calendar.
at the height of 457 mm from the floor level. (e) Tack Boards.
Out of these two, one pair shall be on UPS. (f) Whiteboards.
(g) Horizontal surfaces to keep greeting
cards and photos.
18.8.12 Other Communication (h) Mobile/ Laptop charging points.
Points in Treatment/ (i) Internet Connection / Wi-Fi.
Procedure Room (j) Intercom with facility for an outside call.
(k) Cabinet for storage of personal
The following communication points shall be belongings.
provided in the Treatment/Procedure Room at (l) A television, if it is a room but not in an
any convenient place/wall: ICU hall.
(m) Secure storage space for patients’ and
1. RJ 45 point for Computer networking family clothing and limited personal
2. RJ 11 for Intercom and extension line effects.
3. HDMI point for computer display at other 3. Room Decor
locations Pleasant aesthetic surroundings for patients
and increased comfort results in improved
outcomes. The care to be taken shall be:
18.8.13 O
ther Issues on Patient (a) Good Colour schemes affect mood and
Care Zone and Procedure/ stress levels. Particularly light green and
Treatment Room blue colours decrease the stress levels of
patients.
1. Clear Floor Space (b) Wall furnishings shall be excellent with
Clear floor space is a space not utilized by waterproof washable paints.
the patient, equipment and fixed room fur- (c) Pictures, paintings, murals and artwork
nishings. As sometimes a lot of medical shall be placed appropriately for patients,
equipment may be required for treatment of families and caregivers.
patients, it is advisable to keep the maximum (d) For bed-ridden patients, the ceiling is
floor clear around the bed to be used for most often what is seen. The ceiling can
equipment like portable X-ray, echocardiog- be painted with pictures and sceneries.
raphy and dialysis machines. That is the rea- Even 3D laminated ceilings can be opted.
son why it is recommended to keep 1828 mm
the distance between two beds.
2. Patient Room Furnishings 18.8.14 Lighting in the ICU
ICU rooms or units shall have a decent and
aesthetic finish and look. It helps a lot for the Lighting for general illumination and specific
early recovery of the patient and leaves a long- tasks has to be carefully planned. Few issues
term effect on the patient about the q uality of related to lighting, to be considered are:
service. Hence, the furnishing of the patient
room/unit shall be designed carefully. In the 1. The Lights shall not be too bright or too dull.
room/unit, apart from the furniture as mentioned Proper lumens have to be planned as per the
above, the room shall also be furnished with: standards.
166 18 Intensive Care Units
parameter bedside monitor located near the Echocardiography machine shall also be placed
patient. in the ICU. These machines shall be for the
Secondly, the hearing of sound, the patient can exclusive use of ICUs only and shall be parked in
be monitored through the conversation with the the equipment room of ICU.
patient or screams of the patient. Through touch, For all other services of imaging, the radiol-
the temperature of skin abnormality can be moni- ogy department shall be located at such a place
tored. Through Smell the patient can be moni- that has easy and quick access to the patients of
tored for the hygienic condition. Similarly, ICU. Another issue is the report of the imaging
through taste, the food being served to the patient procedures. As it takes time to print the film and
can be monitored. Therefore, it becomes impera- send it to the ICU, the system of online transmis-
tive for the nurse to continuously monitor the sion of images is the answer. By using PACS
patient. (software), the images from the radiology depart-
As far as arrangements are concerned, a place ment can be easily transmitted at the computer
and means shall be provided to fix the monitor at screen placed in ICU.
the bedside of the patient. This can be done by
providing a monitor tray on the bed head panel or
on the hanging pendant. If it is not possible, the 18.9.3 Laboratory
monitor tray can be fixed on the wall by fasten-
ers, where a monitor can be installed. ICUs must have access to clinical laboratory ser-
At times some physicians opt for centralized vices round the clock. As the equipment of
monitoring through CNS (Central Nursing Central Clinical Laboratory is installed in the
Station). For this, the cabling (Cat 6) has to be department at a place other than ICU and the
laid down from all the beds individually and all patient need not be moved to the laboratory, it
the cables to end at the nursing station, where the hardly matters if the laboratory is not placed in
CNS is installed. the ICU Complex.
Ever-changing technology has introduced However, a full-fledged Sample Collection
Remote Monitoring. In this technology, the live Room shall be located near the ICU, with a facil-
data parameters are sent to the physicians online ity of specimen collection, short-time storage and
for continuous monitoring and giving necessary pre-processing of the specimen can be done here.
instructions. To facilitate this, cabling has to be Apart from the routine specimens that need to
done from each bed to the computer placed at the be sent to the laboratory, a few lab investigations
nursing station, from where the data will be have to be done in the ICU itself, such as arterial
transmitted to the physician. blood gas analysis and mixed venous blood gas
analysis. Hence, a convenient space shall be
allotted in the ICU itself for placing such
18.9.2 Radiology machines. This space shall fulfil all the require-
ments for installation like the electrical point,
The service of the radiology department is an water supply/drain and temperature required to
important service that helps to diagnose and run the machine.
access progress during treatment. The services of Pneumatic tube systems may be used for rapid
Radiology can be X-Ray, CT Scan, MRI, transport of specimens to and from the
Ultrasound Mammography, PET CT, PET MRI laboratory.
etc. Similarly, the DSA has an important role in
the peripheral intervention of ICU patients.
Services of Radiology therefore should be 18.9.4 Medication Rooms
readily accessible to the ICU. As far as X-ray is
concerned, a portable X-ray machine shall be While designing the ICU setup, the designer shall
placed in the ICU. Similarly, the Ultrasound cum consider the location of the Medication Room
168 18 Intensive Care Units
just near the ICU. The medication room serves and radiology. The networking of the plastic
the purpose of storage of medicines and distribu- pipe is installed in the hospital which opens at
tion to the patient. Considering the fact that, as the desired stations. Then there are boxes in the
most of the patients are sick in ICUs, the phar- shape of a capsule, which carries the material
macy services should be readily accessible and and documents. These boxes run in the pipeline
operative round the clock. The room with the and carry the desired material to a specific
approx. Size of 3658 mm × 3658 mm shall be location.
placed near the ICU. However, the size of the It is very easy to operate. The user has to just
room can be increased depending on the require- put the desired material to be transported in these
ment. The room shall have the facility for cabi- capsules and give the command to the system and
nets, drawers and racks for storage of medicines. feed the station ID where the material has to be
The room shall be provided with an ample coun- sent. In seconds, the material or document is
tertop for disbursing medicines. If the medication transported to the desired location.
room is attached to the ICU, a window can be
given which shall open in the ICU, from where
quick communication can be done. Also, the pro- 18.9.6 Clean Utility
vision of a refrigerator shall be made in the room.
Similarly, the provision of the Telephone line and The clean utility is a room attached to ICUs or
intercom shall also be done. Nowadays, the auto- any other service unit, which is used for storage
mated dispensing machines are also used for dis- of the clean linen. The sterilized material like
pensing medicines. drums and drapes is also stored in this room.
The medication room should be large enough Normally, the room shall not be less than
to accommodate at least a staff of two, a nurse 3658 mm × 3658 mm. But depending on the
and a pharmacist who shall double-check the requirements, the size of the room can be
accuracy of medicines being supplied. changed. The room is provided with closed cabi-
The medicines and drugs can be transferred nets, drawers and racks. This room shall have
from the main pharmacy store by a messenger only one door of about 914 mm.
which takes a long time. An alternative to this is
Pneumatic Tube Systems (PTS). What is PTS
and how it works is explained below? 18.9.7 Dirty Utility/Sluice Room
18.10.2 Doctors Duty Rooms in ICU 3. Furniture wise, the room shall have a bed and
cupboard.
Generally, depending on the size of ICU, and the 4. Apart from the light and fan, the room shall
number of beds in each ICU, the physicians from have a point for Intercom.
different disciplines shall be placed in the ICU to 5. Also, the room shall be Air Conditioned and
provide immediate care to the patients. In that the Control button with temperature adjust-
case, one or more than one Doctors duty room ment shall be provided in the room.
shall have to be provided in the ICU complex.
The following issues shall be considered regard-
ing provided duty rooms in ICU: 18.10.4 N
ight Duty Room
for On-Call Junior Doctors
1. One or more rooms for the physicians of each
department shall be allotted. During the daytime, all the physicians are in the
2. The room shall be of the size hospital to take care of the patient in ICU, but this
4267 mm × 3658 mm. is not true for the night. Hence for the night,
3. Rooms shall have a provision of an attached junior doctors are posted and they are supposed
toilet. to be on duty in the ICU or near ICU. Hence a
4. Furniture wise, the room shall have one office room has to be allotted to them for taking rest.
table, chair, bed and cupboard. The following issues shall be considered regard-
5. Apart from the light and fan, the room shall ing provided duty rooms in ICU:
have points for a computer with Internet con-
nection and Intercom point etc. 1. One or more rooms for the junior doctors
6. Also, the room shall be Air Conditioned and shall be provided.
the Control button with temperature adjust- 2. The room shall be of the size
ment shall be provided in the room. 4267 mm × 3658 mm.
3. Rooms shall have a provision of an attached
toilet.
18.10.3 N
urses Night Duty Rooms 4. Furniture wise, the room shall have one office
in ICU table, chair, bed and cupboard.
5. Apart from the light and fan, the room shall
At times, due to the heavy load of work in the have points for a computer with internet con-
ICU, or due to overwork, the Nurses feel tired. nection and Intercom point etc.
Otherwise, it also happens due to the shortage 6. Also, the room shall be Air Conditioned and
of nursing staff they may have to perform dou- the Control button with temperature adjust-
ble duties. Under both circumstances, the ment shall be provided in the room.
nurses need to take rest. Generally, depending
on the size of ICU and the number of beds in
each ICU, the nurse’s night duty room shall be 18.10.5 Ward Pantry
planned. At least one such room shall be pro-
vided with each ICU. The following issues As the patients admitted in ICU have to be served
shall be considered regarding provided nurses a full day diet, there shall be a space for storage
with duty rooms in ICU: of diet and further distribution. This space is
called the Ward Pantry. It is not necessary that the
1. The room shall be of the size diet has to be cooked in the ICU premises; the
3658 mm × 3658 mm. diet is prepared in the kitchen and then sent to the
2. Rooms shall have a provision of an attached ward pantry for further distribution. The diet is
toilet. sent in bulk from the kitchen either packed for
18.11 Family Support Zone 171
direct distribution or otherwise in an unpacked For this, a Family Support Zone is placed at a
position. distance from the main ICU Complex, consisting
The size of the ward pantry shall be about of those spaces and functions outside of the
3658 mm × 3658 mm, with a single door opening patient room to serve family and visitors.
outside in the corridor. The ward pantry shall The Family Support Zone should have the
have a countertop for packing the food. Along following:
with the countertop, a sink with hot and cold
water shall be available. The waste bin/s has to be
kept in the ward pantry and a trolley for collect- 18.11.1 Family Lounge
ing soiled utensils. A microwave oven may be
useful. A family and visitor’s lounge should be provided
adjacent to or near ICU Complex. If the ICUs are
scattered at different places, a lounge shall be
18.10.6 Staff Lounge provided for each ICU. Lounges shall be placed
at such places which do not disrupt the patient,
After long hours of tiring working, the staff def- staff and supply circulation system of the
initely needs some rest and refreshment. hospital.
Therefore, a staff lounge shall be provided near A lounge must have a comfortable space to
the ICU Complex. The capacity shall depend on wait, reclining chairs to relax, the privacy of con-
the number of ICUs and staff. An ideal lounge versations, telephone and intercom facility. The
shall be having a seating of about 25–30 per- Lounge shall also have basic amenities like a
sons. The lounge should be well ventilated to small snacks bar, television, newspaper and mag-
remove food smells from the ICU complex. azine stand and a small play area for children.
Preferably an attached toilet shall be provided Coffee and tea vending machines shall also be
with the lounge. provided. Visitor access should be controlled
Lounge shall provide a private, comfortable, from a separate reception area provided in the
spacious and relaxing environment. The lounge lounge itself.
should have a comfortable seating arrangement, a Shelves, closets and secured lockers shall also
table with chairs for dining and food storage be provided in the lounge to avoid scattering the
facilities, including a refrigerator, microwave personal belongings here and there around the
oven and coffee dispenser or maker. Additionally, lounge. Accessible toilets for males and females
a television and a computer with internet access shall be close to or part of the lounge (Fig. 18.3).
can also be provided. In the lounge, a notice
board shall be provided, as it is the best place to
display any information relevant to the staff. 18.11.2 Consultation Rooms
The staff lounge should be connected to ICU
by telephone or intercom so that in case of emer- Family members and friends being anxious to
gency they can be contacted immediately. know the position and development in the condi-
tion of the patient need to meet the treating physi-
cian and have an interaction with him. Therefore,
18.11 Family Support Zone the Consultation Rooms are provided for this
purpose. This room shall be about
Along with the patients, anxious family members 4572 mm × 4267 mm with a provision of a doc-
or friends also usually visit the hospital. While tor’s table, chairs and a sofa set. The physician
the patient is in ICU, it is not advisable to allow goes to that room, calls for the family members
these family members or friends to visit patients. of the patient and has an interaction with them.
But family support has been recognized as an At times there can be hot discussions between
important factor in a patient’s recovery and the physicians and the visitors of the patient.
reduced morbidity. Therefore, some security personnel shall be
172 18 Intensive Care Units
placed outside the room. Furthermore, this room hours when hospital coffee shops or food ser-
shall be under CCTV surveillance from inside vices may not be available.
with audio-video recording. In both cases, care shall be taken to provide
arrangements for disposal of utensils and main-
tain hygiene. The arrangement shall be made in
18.11.3 Meditation Spaces such a fashion that the smell of the food does not
spread in the hospital complex.
Disturbed family members of the patient are nor-
mally under fear and often seek blessings from
the Almighty. Therefore, it is advised that near 18.11.5 Family Sleep Rooms
the ICU space shall be provided for a Medic
Room for meditation, reflection and spiritual It has been seen that some patients need to stay in
contemplation. Particular attention should be ICU or other units of the hospital for a long time,
paid while designing the space that there shall be maybe weeks or months. Even for some diseases,
space for all religions and not particularly for any the patient may have to visit the hospital for a few
one religion. hours for treatment like chemotherapy or radio-
therapy. Under such circumstances, the patient
and or the family members are really in a con-
18.11.4 Family Cafeteria fused state of mind about where to stay.
Particularly for the long-distance patients, it is
For the convenience of the family members, ade- not always possible to return home to rest.
quate provision of cafeteria shall be made in the It is recommended that on the availability of
hospital. Usually, a cafeteria is provided on the land, a separate guest house shall be provided,
ground floor of the hospital where they can get which can be allotted to family members on a
the refreshment. Drinking fountains or another paid basis. These guest houses may have all the
fresh water supply should be conveniently located amenities like mess, toilet, bed, TV, fridge and
within or near the cafeteria and lounge. bedding.
Some hospitals provide food trays to families If the space for a guest house is not available,
at mealtimes. In that case, a separate space or the hospital can enter into an agreement with a
dining hall shall be provided where the family nearby hotel to accommodate visitors and fami-
members can be served the meals. Vending lies coming from out of town, the rent of which
machines can also be helpful, particularly at late shall be paid by the family member.
18.12 Specialized Intensive Care Units 173
18.11.6 Family Laundry Hence, the provision for ABG machines shall be
done in the ICU itself.
This can be an extra facility provided to the fam-
ily members of the patient, particularly the
patients who have to stay long in the hospital. For 18.12.3 Neurosurgical Intensive
such a facility, a separate counter can be dedi- Care Unit
cated where the clothes can be given to and col-
lected from. The unwashed clothes can be sent to Most of the patients in this ICU are suffering
the central laundry of the hospital for a wash and from Head Injuries which can be either conserva-
returned to the same counter from where they tive or post-operative. Being head injury, the
were collected. This service shall be payable to chances of immediate deterioration of the
the visitors. patient’s condition cannot be ruled out. Hence,
the extensive monitoring of the vitals of patients
has to be done continually.
18.12 S
pecialized Intensive Care
Units
18.12.4 Burn Unit
Apart from the generalized ICUs like Medical
and Surgical ICUs, there are some specialized Burn Unit is another specialized intensive care
ICUs that are designed to provide treatment for a facility for treating patients of burn. This ICU has
particular disease or discipline like Cardiology, to be very sophisticated and shall be carefully
Respiratory, Neuro Surgery, CTVS, Neonatal and planned because this is one of the highly infected
Burn A few of them are as mentioned below: ICU. All beds in this ICU shall be the isolation
beds and shall be under negative pressure. Apart
from this, a shower room and sterile dressing
18.12.1 I ntensive Coronary Care room have to be provided along with this
Unit ICU. Even if needed, Hyperbaric Chambers are
also provided in the burn ICUs.
Intensive Coronary Care Unit (ICCU) is designed
and used mainly for cardiac patients like mayo
cardiac infarction etc. This ICU is also called 18.12.5 Geriatric ICU
ICCU. While designing the ICCU care shall be
taken to handle any emergency and tools like This ICU is for the treatment of elderly patients.
Pacemaker and Echocardiography machines are In addition to the normal medical ICU or surgical
readily available. In the case of an ICCU, exces- ICU, certain features need to be added to make a
sive noise and visual clutter shall be ruled out, geriatric ICU. Because the elderly people are
otherwise, it can have an adverse effect on heart short of hearing and vision, the design shall avoid
rates, arrhythmias and blood pressure. unnecessary noise in the ICU and provide a sys-
tem with which the patient can understand the
command easily. Because of diminished vision,
18.12.2 Respiratory Care ICU lighting should be such that can avoid glare. This
also means reducing highly reflective surfaces to
This ICU is designed to treat patients suffering a minimum.
from respiratory diseases like COPD and respira- Another risk with the elderly is to fall down
tory distress. Most of the sick patients of this ICU because of low muscle power or weak nerves.
may require ventilated support. Hence the design Hence, the bed shall be adjustable to floor level.
shall give sufficient backup for the supply of Also, proper handrails have to be provided in the
medical gases. These patients may also require walking area. Toilets shall be handicapped toilets
Arterial Blood Gas tests done occasionally. with proper supports and railings.
174 18 Intensive Care Units
18.12.6 N
eonatal Intensive Care 7. Formula Room
Unit Used to prepare the milk and diet of the
babies.
As compared to any other ICUs, the Neonatal 8. Store
Intensive Care Unit (NICU) has a different 9. Clean Supply Room
setup altogether. As this ICU is to be exclu- 10. Dirty Linen / Sluice Room
sively used for newborns, there are no beds in 11. Nurse Station
this ICU. Instead of the bed’s bassinets are pro- 12. Change Room
vided. Nowadays, bassinets have been replaced 13. Scrub Station
by the Servo Controlled Radiant Heat Warmers. 14. Medication Room
The main considerations while designing the 15. Doctors Duty Room
NICU are: 16. Nurses Duty Room
17. Staff Toilet
18.12.6.1 Location of NICU
Preferably NICU shall be located near to the 18.12.6.3 Placement of Warmers
department where births occur like the depart- 1. Area per patient space shall be about 11.15
ment of Obs. & Gynae., so that after the delivery, Sq. Mtr. per bassinet.
the baby can be shifted to NICU without much 2. The radiant warmers are placed on the wall at
exposure to the infected atmosphere. a distance of about 610 mm from the wall.
3. Inter-distance between two warmers shall
18.12.6.2 T he Infrastructure of NICU be about 1219 mm for easy working of the
NICU shall have the following rooms/areas staff.
(Fig. 18.4): 4. Each warmer shall be supplied with Medical
gas points as has been described above in case
1. Inside baby clean ICU of ICU.
The babies delivered in the same hospital
and/or who are considered to be free from 18.12.6.4 Equipment of NICU
any type of infection. Following are the main equipment used in NICU:
2. Outside or infected baby ICU
Multi-para Vital Sign Slow Suction Machine
Babies who come from outside and the Monitor
state of affairs about infection is unknown. Neonatal Mechanical Servo Controlled
3. Ventilation room Ventilator with a low Tidal Radiant Heat Warmer
Room used for taking the baby on Volume starting from 5 to mounted with the baby
10 onwards trolley
mechanical Ventilation and who have to be
Non-invasive Ventilator Paediatric
rigorously monitored. B.P. Apparatus
4. Step down ICU High-flow Nasal Canula Defibrillator
For the babies who are stable or who Infusion Syringe Pump Skin Sensor
recover from ICUs but still need to be kept Thermometer
under monitoring. Electronic Weighing Oxygen Cylinders with
Machine Basket type Masks
5. Mothers’ Feeding Room
Phototherapy unit on the Ambu bag with Pediatric
Separate room for breastfeeding the baby stand—Upper Surface Masks
by mother. Please ensure the privacy of this Phototherapy unit on the Laryngoscope
room and no outsider shall be allowed to stand—Under Surface
visit this room when in use. Humidifiers Transport Incubator
6. Nappy Wash area View Boxes Bilirubin meter
Used to wash the soiled napkins of the Oxygen Hoods of various Vein Finder
sizes
babies. Nowadays, this is not being used
Other small tools and Resuscitation Units for
much because these days the disposable instruments required Delivery Suites
absorbent baby napkins are used.
18.12 Specialized Intensive Care Units 175
ICU Complex shall have a limited and dedicated The ICU design should provide adequate storage
entrance which shall be guarded properly with for all equipment, supplies, consumable materials,
the provision of surveillance with CCTV. Only medical disposables and other items currently
authorized visitors with official passes shall be being used. The designer shall also consider future
allowed to enter the ICU complex. The entrance requirements while designing the storage space.
shall be provided with the proper communication Storage is needed for personal items belonging to
systems like Intercom or Mobile to allow com- staff, patients and visitors. Equipment and supplies
munication between the ICU staff. Even the storage shall be designed to be stored as close as
entrance from visitors lounge to the ICUs shall be possible to point of use. The storage shall be lock-
guarded so that unrequired movement of visitors able as far as possible and shall be free from
to and from ICUs shall be controlled. If due to humidity, termite proof and fire safe. Particular
financial restraints, it becomes difficult to place care shall be taken for storage of medicines and
guards round the clock, an option is to provide injectable etc. and shall be properly marked and
the visitors with a Card-key to open the door. under the strict control of an authorized person.
most of the admissions in ICUs are either through • There must be adequate overhead and task
the emergency department or from the operating lighting, and a wall-mounted clock should be
rooms following major surgery. These depart- present.
ments shall not be too far from the ICU complex
as patients may have to be transferred to any of
these departments as and when required. Close/ 18.13.8 Patient Records
easy proximity is also desirable to diagnostic
facilities, blood bank, pharmacy etc. Adequate space and seating shall be provided
for the physicians and nurses to sit and com-
plete medical record charting Shelving, file
18.13.7 Central Nursing Station cabinets and other storage for medical record
forms must be located nearby so that they are
• This is the nerve centre of ICU, hence with the readily accessible by all personnel requiring
changing technologies, the design of nursing their use.
stations also changes from time to time.
• Most important is the location of the nursing
station in the ICUs. Preferably the nursing sta- 18.13.9 X-ray Viewing Area
tion shall be located such that all or nearly all
monitors and patients must be observable Some physicians or the management prefer a sep-
from there, either directly or through the cen- arate room or distinct area near ICUs for viewing
tral monitoring system. and storage of patient radiological films. An illu-
• Ensure that there is enough space and chairs to minated viewing box of appropriate size shall be
meet the requirement of the staff. The space provided in this room for viewing X-ray films.
shall also be available to accommodate com-
puter terminals and printers.
• In case of space constraint, collapsible desk- 18.13.10 Reception Area
tops or shelves that can flip up on the wall can
be planned. The ICUs should have a reception area to control
• Sufficient cupboards shall be provided to keep visitor access. Ideally, the reception shall be located
the necessary items that may be required for at such a place that visitors must pass by this area
nursing care. All these cupboards should be before entering the ICU complex. The receptionist
labelled and lockable. should be connected with the ICUs by telephone
• By the bedside of the patient, over-bed tables and/or other intercommunication systems.
shall be able to accommodate vital charts and
cupboards shall be sufficient to store medi-
cines, disposables investigations and records 18.13.11 Corridors in ICU Complex
of the patient.
• If the concept of the sub-nursing station is fol- An ICU complex shall have:
lowed, provisions shall be made that each
nursing substation should be capable of pro- 1. A separate corridor for entrance and move-
viding most, if not, all functions of a central ment of the visitors and shall be separate from
station. that being used by healthcare professionals.
178 18 Intensive Care Units
Med Peer-Rev Off Publ Indian Soc Crit Care Med. for intensive care unit design*. Crit Care Med. 2012
2020 Jan;24(Suppl 1):S43–60. May;40(5):1586–600.
SALUS - Article - Critical care design of tomorrow: how Tripathy S, Acharya SP, Sahoo AK, Mitra JK, Goel K,
technology fits in [Internet]. [cited 2021 Jun 18]. Ahmad SR, et al. Intensive care unit (ICU) diaries
Available from: https://www.salus.global/journal/ and the experiences of patients’ families: a grounded
view/article/critical-care-design-of-tomorrow-how- theory approach in a lower middle-income country
technology-fits-in-1 (LMIC). J Patient-Rep Outcomes. 2020 Jul 23;4(1):63.
Sessler CN. Evolution of ICU Design: Smarter Is Better. Valentin A, Ferdinande P, ESICM Working Group on
CHEST. 2014 Feb 1;145(2):205–6. Quality Improvement. Recommendations on basic
Technology and the Future of Intensive Care Unit Design requirements for intensive care units: structural and
[Internet]. [cited 2021 Jun 18]. Available from: organizational aspects. Intensive Care Med. 2011 Sep
//www.nursingcenter.com/journalarticle?Article_ 15;37(10):1575.
ID=1236265&Journal_ID=54003&Issue_ID=1236032 White RD, Smith JA, Shepley MM. Recommended
Thompson DR, Hamilton DK, Cadenhead CD, Swoboda standards for newborn ICU design, eighth edition. J
SM, Schwindel SM, Anderson DC, et al. Guidelines Perinatol. 2013 Apr;33(1):S2–16.
Operation Theatre Suite
19
Operating Theatre (O.T.) is a place where the ment that O.T. complex should be on the top
operations, surgical procedures and other inva- floor of the hospital. But considering the ther-
sive interventions are carried out. It offers a ster- mal losses because of the high temperature in
ile environment, with all personnel wearing summers, the Air Conditioning has to be
protective clothing including shoe covers, masks, much more powerful, resulting in more opera-
caps, eye shields and other coverings to prevent tional costs. Another drawback by O.T. com-
the spread of germs and microorganisms. The plex being on the top floor is that this complex
environment is brightly lit, and the temperature will be away from other support services like
and humidity are maintained as per pathology, radiology and Blood Bank.
requirements. 4. Two connected corridors opposite to each
However, only the Operating Theatre does not other shall be available—one which can be
complete the definition of the ‘Operating Theatre used as an entry to O.T. complex and the other
Suite/Complex’. It is more like a set of different to be used as an exit from the O.T. complex.
rooms located in different zones of the whole 5. Elevators and lifts shall be available near the
complex. O.T. complex.
6. Lesser the outer wall in the O.T. complex, bet-
ter it will be.
19.1 Location of Operating 7. Intensive Care Units (ICU) shall be in close
Theatre (O.T.) Complex proximity to the O.T. complex.
1. It shall be in a restricted area, where the gen- Normally, the O.T. complex is divided into four
eral movement is not allowed. zones:
2. Complete O.T. complex shall be located at the
same place as a cluster, ideally on the same
floor. Avoid scattering it into different areas. 19.2.1 Unsterile Zone
3. This complex shall be somewhere in the mid-
dle of the building and shall be sandwiched This is a zone that is normally unsterile and the
between two floors. There is often an argu- movement is allowed without any change.
© The Author(s), under exclusive license to Springer Nature Singapore Pte Ltd. 2022 181
A. Garg, A. Dewan, Manual of Hospital Planning and Designing,
https://doi.org/10.1007/978-981-16-8456-2_19
182 19 Operation Theatre Suite
arrangement of office tables, executive chair, vis- cal points, intercom connection, I.T. network and
itor chairs and side rack. The room shall have an air conditioning.
attached toilet. The room shall also have an
attached P.A. room for a clerk to be seated. If
required and long working hours are expected, a 19.4.5 Trolley Bay
small restroom/lounge can also be provided with
this room. The room shall have proper arrange- An area shall be provided in this zone, which
ments for electrical points, intercom connection, shall be reserved for the stretcher trollies and
I.T. network and air conditioning. wheelchairs allotted to the O.T. complex.
Normally these stretcher trollies are used to move
out the patient from O.T. complex after surgery.
19.4.3 Room for Head of Anaesthesia As far as bringing the patient to the O.T. complex
is concerned, usually, the patient is brought by
Officially, the anaesthetist being the medico per- the staff of the concerned ward or ICU. He/She
son is also treated as the in-charge of the O.T. uses the stretcher trollies allotted to his/her own
complex. However, his/her scope of work is lim- ward. After dropping the patient in the Pre-
ited to the medical administration. The non- operative ward, he/she takes the stretcher trollies
medical administration is left to the manager. or wheelchairs back to his/her own ward. Hence,
This room shall be located adjacent to the man- the stretcher trollies and wheelchairs are gener-
ager’s room. The size of this room shall be about ally not required at the entry point of O.T. com-
4572 mm × 4267 mm. The room shall contain an plex. Therefore, this trolley bay is located in the
arrangement of office tables, executive chair, vis- unsterile zone at the exit point of the O.T.
itor chairs, side rack etc. The room shall have an complex.
attached toilet. The room shall also have an
attached P.A. room for a clerk to be seated. If
required and long working hours are expected, a 19.4.6 Frozen Section Biopsy
small restroom/ lounge can also be provided with Laboratory
this room. The room shall have proper arrange-
ments for electrical points, intercom connection, It is the lab where the biopsy sample is quickly
I.T. network and air conditioning. frozen and the histopathological findings can be
reported. Usually, it takes only half an hour for
the total process. At times it happens that while
19.4.4 Surgeons Room performing the surgery, the surgeon is not sure
for Office Work about the disease and desires re-confirmation of
the diagnosis. For example, in the case of
This room is for the surgeons and their assistants Mastectomy, the surgeon wants to be sure that the
to carry out the official work of the surgeries per- patient is a confirmed cancer case before com-
formed, to prepare notes of surgery etc. An O.T. pletely removing the breast. Therefore, while
register is usually kept here for daily entry. This performing the surgery, he/she takes a small
room shall be located adjacent to the anaesthetist specimen of the part as a biopsy and sends it to
room. The size of this room shall be about the frozen section lab for a confirmed diagnosis.
4572 mm × 4267 mm. The room shall contain an While the investigation is in process, the patient
arrangement of office tables, executive chair, vis- is kept anaesthetized. Once the confirmed report
itor chairs, side rack etc. The room shall have an is received, the surgeon can take the final deci-
attached toilet. The room shall also have an sion. As an immediate report is required under
attached P.A. room for a clerk to be seated. The such circumstances, the sample is not sent to the
room shall have proper arrangements for electri- central lab to avoid wastage of time.
19.4 Unsterile Zone 185
The Laboratory shall be provided with a coun- system placed in the O.T. complex for listening to
tertop for working and placing the equipment and the announcements made from the O.T. This area
shall have an arrangement of lab sink and suffi- shall also have an Intercom facility so that the
cient electric points. O.T. staff can contact the family members in case
of requirement. This area shall be guarded by the
security to control the unnecessary movement of
19.4.7 Shoe Change Area family members in the O.T. complex and shall be
under CCTV surveillance.
Space shall be provided in this zone for changing
shoes. The staff desirous of entering the complex
has to remove the outside shoes and change with 19.4.10 Public Utility for Attendants
the sleepers/shoes kept for use in the O.T. com-
plex. This area shall be provided with a sufficient Along with the waiting area for the family mem-
number of shoe racks and a chair for sitting while bers, the facility of toilets shall be provided. If
removing or wearing shoes. possible, separate toilets shall be provided for
males and females. The facility of drinking water
shall also be provided. It will still be better if the
19.4.8 Entry Door tea/coffee vending machine is placed in this area.
for Changing Room
In the O.T. complex, different types of change 19.4.11 Linen Pre-wash Room
rooms are provided for Doctors, Technicians,
Nurses and class four workers required to work This room is used to give a pre-wash to the soiled
in the sterile zone of the complex. The change linen used in the O.T. before sending them to the
rooms have to be separate for males and females. laundry. As said earlier, no back movement is
The number of the change room to be provided allowed in the O.T. complex, the used linen has to
depends on the size of the O.T. complex and the move out from the exit gate or the corridor behind
number of staff required in the complex. It is rec- the O.T. complex. Therefore, this room has to be
ommended that the change room should have provided near the exit gate of the O.T. complex or
dual doors—one for entry and the other for exit. the exit of the corridor behind the O.T. A room
The philosophy behind this is, that after the shall be provided with the sink, drainboard and a
change, the staff shall not come to the unsterile low-height water tap to wash the clothes. Special
zone. Hence, the entry door of a change room is care shall be taken about the slope in this room so
provided in this zone. that the water does not spill outside the room.
This area is for the attendants and family mem- This room is used to give a pre-wash to the soiled
bers of the patient undergoing surgery/interven- surgical instruments used in the O.T. before send-
tion in the O.T. The family members being very ing them to the CSSD for sterilization. As no
curious, do not prefer to be seated at a faraway back movement is allowed in the O.T. complex,
place and always want to sit near the O.T. com- the used instruments have to move out from the
plex. Therefore, the waiting area shall be provided exit gate. Therefore, this room has to be provided
outside the main entry door of the O.T. complex. near the exit gate of the O.T. complex. The room
The waiting area shall be provided with chairs for shall be provided with a large size sink, drain-
a comfortable sitting of the family members. This board and a countertop for drying up the
area shall have a speaker connected to the mike instruments.
186 19 Operation Theatre Suite
through the entry gate of Pre-operative Ward. The the requirements of the doctor’s lounge or the
width of the door of the pre-operative ward shall staff lounge. Apart from tea/coffee, it can have
be 1829 mm. the provision of pre-cooked light snacks and bis-
cuits. Infrastructure wise, the pantry shall be
about 3658 mm × 3658 mm in size. It shall be
19.5.3 Unsterile Store for Equipment provided with the countertop slab for cooking
Storage and to place gas burners or inductions. The provi-
sion of a sink with a drainboard shall be made for
O.T. is a highly sensitive place and requires extra washing utensils. A microwave and refrigerator
equipment and instruments to be stored. These shall also be provided in the pantry. A sufficient
are not generally used but are kept in stock for number of electric points shall be provided to
providing a backup of the main equipment and operate these machines.
instruments. The store shall be at least
4572 mm × 6096 mm in size. Adequate lockable
cupboards, racks and drawers shall be provided 19.6 Clean Zone
in the store. The store shall also have multiple
electric points to charge the equipment when not This area is cleaner than the protective zone and
in use. This store shall be in charge of the store- the entry to this zone shall be more restricted.
keeper of O.T. complex. Entry into this zone shall be allowed after the
change of outside clothes. This area is located
just after the protective zone and shall be sepa-
19.5.4 Store for Medicines, rated from the protective zone with the help of
Consumables and Disposables the door which shall be guarded. Details of the
rooms located in this zone are:
During surgery, a surgeon can raise demand for
medicines, consumables and disposables depend-
ing on the patient’s condition. As the surgeon will 19.6.1 Pre-operative Room
not be in a waiting position, his/her requirement
has to be fulfilled immediately. To avoid any The pre-operative ward is the area where the
untoward incident, generally, all the required patient is kept for examination before taking him
medicines, consumables and disposables are to the operation theatre. Depending on the
stocked in the O.T. complex. A separate store requirement, a few beds can be placed in this
shall be provided to keep such items in the pro- ward. As the stay of the patient is very less in this
tective zone of the O.T. complex. The room shall ward, a large number of beds are not required.
be at least 4572 mm × 6096 mm in size. Adequate Normally, one to two beds per O.T. room shall be
lockable cupboards, racks and drawers shall be placed.
provided in the store. The store shall also have a The size will depend on the number of beds to
countertop to prepare the drugs if required. This be placed. Generally, 7.43–9.29 Sq Mtr. space
store shall be in charge of the storekeeper of O.T. per bed is sufficient. Not all but a few beds shall
complex. have the provision for the supply of Medical Gas
Pipeline mounted on the bed head panel. Each
bed shall be provided with at least two electrical
19.5.5 Pantry points to connect the medical devices. Along
with the Pre-operative ward, an adjoining toilet
Pantry is provided in the O.T. complex to facili- shall be provided. The ward shall also have a
tate the staff to have tea/coffee whenever there is cloth changing room, where the patient can
a break from surgeries. This pantry can also serve change to the O.T. dress. This ward shall have
188 19 Operation Theatre Suite
two doors, entry and exit. As mentioned earlier, activities take about 30 min to an hour. Till that
the entry door shall be in the protective zone and time, the surgeon can relax in the lounge and com-
the exit gate in this clean zone. plete the patient file, prepare operative notes and
post-operative prescriptions. The lounge shall be
provided with an attached toilet and a provision of
19.6.2 Preparation Room tea/coffee, which can be served from the pantry.
Size-wise the lounge shall be about
Though instructions are given to the wards to prepare 6096 mm × 4572 mm, with a sofa set and a centre
a patient before sending him/her to the O.T., some- table. On the request, a single bed can also be
times it is found that the patient has not been properly placed in the lounge for surgeons to lay down for
prepared, for example the patient has not been some time (Fig. 19.3).
shaved, the dress has not been changed etc. Therefore,
a preparation room is provided in this zone to com-
plete the formalities of preparation before sending the 19.6.4 Restroom for Staff: Males
patient to the O.T. This room shall be about and Females
3658 mm × 3658 mm in size, with an examination
couch. The room shall have a cabinet to keep the nec- As in the case of surgeons, a lounge shall also be
essary items, a sink and a portable O.T. light. provided for the staff. But the lounge for males
and females shall be separate. The size of the
room shall depend on the requirement and num-
19.6.3 Surgeons Rest Room ber of staff members to be accommodated at any
particular moment of time. All other facilities as
This area is also called the ‘Surgeons Lounge’. provided in the surgeon’s lounge shall also be
Usually, in a running hospital, the surgeries are provided here.
planned in a series which can range between 2 and
5 in a single O.T., by the same or different sur-
geons. Once the surgery is performed in an O.T., 19.6.5 Exit Doors of all Change
the patient has to be transferred from the O.T., it Rooms
has to be cleaned and disinfected, a fresh set of ster-
ilized instruments and linen has to be kept, and the The exit of all change rooms shall be in the clean
new patient has to be shifted in the O.T. All these zone. The logic is that, after a change, the staff is
in sterilized dress and shall not be allowed to go the recovery of the patient, he/she is transferred
back to the unsterile areas. From here, the staff to the respective ward or ICU as the case may be.
and surgeon either move forward to the sterile The number of beds in the Post-operative
zone or remain in this zone. The exit doors shall Recovery Ward shall be in proportion to the oper-
be 914 mm wide and swing type so that it closes ating room. For each O.T., there shall be two
automatically. recovery beds. The Post-operative Recovery
Ward shall have a setup exactly as per the ICU,
i.e. the beds shall be placed at an appropriate dis-
19.6.6 Pre-anaesthetic Check-up tance, all beds shall have the provision of Central
Room (PAC) Medical Gas Pipeline, and there shall be electric
points similar to ICU. The ward shall have a nurs-
PAC is a check-up performed on a patient by the ing station in the centre, attached general store,
anaesthetist to ensure that the patient is fit to medicine store, clean utility room, dirty utility
administer anaesthesia. He/She performs differ- room and a toilet. The size of the Post Operative
ent investigations like blood tests, X-rays or Recovery ward shall depend on the number of
sometimes echocardiography. Usually, it is per- beds to be placed in the ward.
formed in the ward, a day before the surgery, but
at times, re-examination is required before
administering the anaesthesia. This is the place 19.7 Sterile Zone
where it shall be done. This room shall be about
3658 mm × 3658 mm in size, with an examination This is the most sensitive zone in the whole O.T.
couch. The room shall have a cabinet to keep the complex. This area has to be totally sterile and
necessary tools and instruments, a sink and a por- aseptic. It is separated from the Clean Zone by
table O.T. light. providing a swing-type door that shall not be less
than 1829 mm wide. These doors shall be sealed
so that any unwanted organisms cannot enter the
19.6.7 Dirty Utility sterile zone. On the exit side of this zone, similar
doors shall be provided. The movement in this
After completion of the surgery, a lot of used zone shall be strictly restricted and only autho-
items like linen, instruments, covers of dispos- rized persons shall be allowed in this zone that
ables, soiled drapes, cotton and gauze have to be too after a proper change and with caps and
removed. Out of this, the linen is sent to linen masks. Just at the entry of this zone, a shoe rack
pre-wash area and instruments to the instrument is placed which contains sterilized shoes or
washroom. Therefore, this dirty utility room is slippers to be worn before entering this zone. At
provided at the exit end of the O.T. complex. The the exit end of this zone, a double door with air
room shall be about 3048 mm × 3048 mm and lock shall be provided to transfer the patient out
provided with bins as per the biomedical waste of the recovery room. If possible, one exit shall
management rules for other waste products. be given in the corridor which connects to the
ICU complex so that the patient can be moved to
the ICU directly with any outside atmosphere
19.6.8 Post-operative Recovery Ward exposure. The details of rooms located in this
zone are as follows:
Once the surgery is complete, the patient is
moved to the Post-operative Recovery Ward. This
ward is used to provide specialized care to the 19.7.1 Clean Supply Room
patient until he/she is out of anaesthesia. The
location of the Post-operative Recovery Ward This room is also termed as Clean Store. This
shall be at the exit end of the O.T. complex. After room is mainly used to store the instruments and
190 19 Operation Theatre Suite
linen received from CSSD after proper steriliza- 19.7.3 Scrub Station
tion. It is also used for storing sterile consum-
ables and disposables that are normally used in The scrub station is used for washing up before
the Operating Rooms (OR). This room shall be entering the OR to perform a surgery or interven-
located near the OR so that it can serve the needs tion. Every person involved in the surgery shall
effectively. Better if it is placed somewhere in the be scrubbed in this area. This area should be
centre of all the OR. The access to this room shall adjoining to the OR. The scrub station can be
be strictly restricted. either in an open area or in a closed room. If it is
This room shall be about 4572 mm × 3658 mm in a closed room, the doors of this room shall be
in size with a single entry and the door shall be able to easily swing in either direction just by the
swing type openable on both sides. It is still bet- tap of the foot and should have a see-through
ter if the door is hermetically sealed door opera- glass in the middle.
tional with sensors. The room shall not have any The scrub area shall be provided with a stain-
window; however, if the window is not avoidable, less steel scrub station which could be operated
it shall be a sealed with double glazing glass. by foot and/or sensors. Hand-operated taps are
There should be no water supply or drain in this not allowed in the scrub station. It shall have a
room. minimum of two bays, with the provision of both
The room shall have stainless steel racks hot and cold water to wash hands. The number of
divided into bins, to store the sterilized material scrub stations depends on the number of OR in
stacked set wise of surgery wise or OR wise. The the complex. It is better if each OR has its own
sterilized material is brought into this room scrub station. No more than two OR can share
through sterilized covered carts and the material one scrub station.
is unloaded in the racks. From here, the stored The water outlet of the scrub station shall be
material shall either move directly to OR or oth- designed to allow the water to fall in the centre of
erwise to the Instrument Trolley Lay-up room. the scrub and not spill around. There shall be a
provision for dispensing the soap using a wall
hanging soap dispenser, which shall be elbow
19.7.2 Instrument Trolley Lay Up operated. Similarly, an elbow-operated wall-
hung antiseptic solution dispenser shall be pro-
This room is for preparing the trolley for a par- vided with the scrub station. A nail brush should
ticular type of surgery or a particular OR. As the be provided, along with a nail cutter and a nail
requirement of the linen and instruments is dif- file.
ferent for different surgeries, this room eases out
the preparation of the trolley. The material is
brought in this room from the Clean Supply 19.7.4 Sterilization Room
Room and laid on the trolley which in turn shall
move to the concerned OR. The trollies for layout Proper sterilization is the backbone of any O.T.
are also wheeled from the same OR where it has complex, thus special care needs to be given to the
to go back after lay-up. sterilization department. The main sterilization
This room shall be about 3658 mm × 3658 mm jobs are carried out in the Central Sterile Supply
in size with a single entry and the door shall be Department (CSSD) located somewhere in the
swinging type openable on both sides. The door vicinity of the O.T. complex, or at any other con-
shall be a sealed door. The room shall not have venient place with a proper transport facility, like
any window; however, if the window is not avoid- goods lift, to transport the sterilized material to
able, it shall be sealed with double glazing glass. O.T. complex. In CSSD, bulk sterilization is car-
There should be no water supply or drain in this ried out to cater to the needs of the O.T. complex
room. and other departments of the hospital.
19.7 Sterile Zone 191
At times during surgery, the surgeon may 4. Will the OR be common to all or will it be
require some instrument or if accidentally some dedicated to a OR, i.e. will a particular OR be
instrument drops down and gets contaminated, it reserved for a specific department?
has to be quickly sterilized to send it back to the 5. How many surgeries are expected per day?
surgeon. Therefore, a small sterilization room is (Both Major and Minor).
provided in the Sterile Zone of the O.T. complex 6. How many patients are generally referred to
which is usually called Theatre Sterile Supply this hospital for surgeries/interventions per
Unit (TSSU). This room is located near the OR day?
clean supply room. The size of the room shall be 7. What is the load of trauma patients per day?
about 3658 mm × 3658 mm. It shall have a quick 8. Does the hospital plan for specialized surger-
steam sterilizer, a hot air oven, and a formalin ies like robotic surgeries or organ
chamber. The room shall have a proper supply of transplants?
soft water to be used in the sterilizer and the Ideally, a hospital of 500 beds shall have a
required drain. The room shall have adequate set of 10 OR, i.e. one OR for every 50 bed.
arrangements for exhaust and air exchanges. It This is not a standard, but the practical experi-
shall also be provided with the required electrical ence recommends the same. Out of these, one
point to connect the machines. A compressed air O.T. can be reserved for advanced surgeries,
point shall also be provided to remove the debris one for Robotic Surgery, one for Organ
from the instruments if required. Transplant, one for CTVS, one for Obs and
one for Eye Surgery. The balance OR shall be
common for other departments.
19.7.5 Operating Theatres/Rooms But if the departments performing surger-
ies/interventions are more, the number of OR
It is this room where the actual surgeries/inter- shall be increased, which can even go up to 20
ventions are carried out. This room has to be the or more.
most sterile and aseptic area in the whole of the
hospital. No person is allowed in the Operating
Theatres/Rooms (OR) without wearing protec- 19.7.7 Location and Layout
tive clothing, including shoe covers, masks, caps, of the ORs
eye shields and other coverings to prevent the
spread of germs. The location of the OR shall be in the most sterile
and restricted zone. This is the last zone of the
O.T. complex.
19.7.6 Number of OR The layout of the OR can be in different
designs. The first can be that in the centre of this
How many OR are to be made? This is the ques- zone there shall be a corridor and OR can be pro-
tion normally faced by the owners. There is no vided on both ends of the corridor. The second
thumb rule to decide the number of OR to be design is that all the OR can be on one side of the
made. It will entirely depend on factors like: corridor and the services on the other side. The
third design can be the cluster of OR in a specific
1. How many surgical departments does the hos- area connected through small corridors. Despite
pital plan to have? Like General Surgery, all three designs being acceptable, the first act is
ENT, EYE, Gynae & Obs, Orthopaedic, the best. In this case, the corridor shall be at least
Urology, Neurosurgery, CTVS, Pedia Surgery, 3048 mm wide.
G.I. Surgery, Onco Surgery etc. The doors can open either directly in the cor-
2. How many surgeons will be operating ridors or side opening can also be considered.
simultaneously? The disadvantage of opening the doors directly in
3. What will be the timings of O.T.? the corridor is that there will be no barrier in
192 19 Operation Theatre Suite
between and any person moving in the corridor 6. For Air Conditioning, Split Air-conditioners
shall have direct access inside the OR. Therefore, are used.
the designer shall design the OR in such a way 7. In the centre of the room, an O.T. light is
that there shall be a gallery between two OR, and fixed at the ceiling.
doors of both these OR shall open in that gallery. 8. The O.T. table is just placed in the centre of
Another advantage is that at the end of such a gal- the room.
lery, a common scrub station for both these OR 9. Proper pipeline for medical gases is not laid
can be fixed. down.
10. There is no specific size of such OR.
In an empty area between both the sheets, a panels fixed earlier to avoid corners. Then all
puffing of polyurethane is filled up to make it a these slanted panels are welded to each other and
puff panel. This makes the panel tough to protect also welded to the wall panel. The required grind-
itself from any dents and reduces thermal loss. ing is done.
Due to financial restraints if any, the asbestos The space left in between the slanting panel
sheet can also be filled in between two sheets of and the plenum is filled up with the straight puff
the panel. panel by hanging these panels from the ceiling
These panels are then arranged on the walls using screw rods. These panels are welded to
and fixed with rod fasteners about 152 mm to each other. Also, the welding of these straight
254 mm away from the wall, creating a vacuum panels is done with the slanting panel and the
between the wall and the panel to further reduce plenum.
the thermal losses. Please note that the corners
are kept empty for fixing the return air duct.
Space shall be about 305 mm on both sides of the 19.9.4 Corners of OR
corner.
Now all the panels are welded to each other so All four corners of the OR shall be covered. First
that no space is left in between the panels. The of all, the return air duct, which is a vertical duct
extra welding spots are ground to smoothen the made of Aluminium sheet, is fixed with clamps
panel surface. screwed to the wall on all the four corners. The
In this panel, no corners are allowed, so at the leftover corners, where the wall panels were not
bends, the panels are welded at an angle of 45 fixed earlier, are covered with the same type of
degrees instead of 90 degrees. puff panel as was fixed to the wall, and all panels
are welded to each other. These corner panels
shall also be installed at a 45-degree angle to
19.9.3 Ceiling of the OR avoid corners.
There are various arguments regarding providing The LED view box is recessed in the panelled
a window in the OR. One thought says not to pro- wall, which will be in front of the surgeon while
vide windows as it distracts the surgeon and can operating. Usually, the surgeons operate from
also be a source of infection in the OR. The sec- the right-hand side of the patient, so this view
ond thought is to provide windows as it relieves box shall be fixed on the wall which is on the
the surgeon from stress due to long hours of sur- left hand side of the patient. The bottom height
gery. But nowadays, the designers prefer to pro- of the view box shall be about 4 ft. so that it
vide windows in OR. reaches the surgeon’s eye level. Both single film
The window in the OR is fixed in the outer and double film view boxes are available, but it
wall of the OR. The size of the window can be is recommended to use a double film view box
610 to 1000 mm in width and about 610 mm in as it has a dimmable LED white light. The con-
height. The windows shall be a fixed type and not trol of the view box is given on the view box
openable. The glass of the windows shall be itself.
double-glazed glass with a vacuum in between.
In the vacuum space, between two layers of glass,
vanishing blinds can be fixed, which shall be 19.9.9 Writing Board
motorized and controlled by a switch button or
remote. The glass can also be tinted and coated so A Magnetic White Writing Board is also recessed
that no direct sunlight or ultraviolet rays can in the panelled wall adjoining the view box. The
enter the OR. bottom height of the board shall be about 4 ft. so
that it reaches the surgeon’s eye level.
19.9.17 Surgeon Pendant exchanges. Suitable and safe air quality must
always be maintained in the OR. Following
On the right-hand side of the patient, a surgeon issues are important while designing the Air
pendant can be given, if required. This is gener- Conditioning System in the OR:
ally a fixed arm pendant that can only revolve on
its own axis. This pendant is mainly used by the 1. Either opt for Chilled Water Pipe Line with
surgeon and has electrical outlets on the side- AHUs (Air Handling Units), or if the number
walls and 2–3 trays. of OR is less than opt for Ductable Split
system.
2. Air Flow, direction and air exchanges have to
19.9.18 Flooring be as per the industry norms.
3. Heating shall be done using water pipeline
These OR have an anti-static flooring, i.e. they and AHUs having hot water generator instead
have adequate earthing properties. It is a PVC of water chillers. Also, room heaters can be
flooring with a layer of carbon coating at the bot- opted; however, they are generally not recom-
tom. It is available in form of tiles mended to be used in the OR (Fig. 19.4).
(610 mm × 610 mm) and rolls. While fixing the
flooring, a copper strip is pasted on the corners,
which is ultimately connected to the earthing 19.9.21 Supply Air Ducts
wire. After that, the PVC tile or roll is glued to
the flooring of the OR. A skirting of about 3 The AHU shall push out clean, sterilized and cool
inches is also made from the same tile or roll. To air at a particular velocity and quantity. This air
ensure that there are no 90-degree corners, plastic has to be carried to the HEPA Filters and ulti-
corners are fixed and the tile or roll is pasted mately in the OR. This job is done with the help
of air ducts which are insulated aluminium ducts
above that. Once the tile or roll is glued, the joints
are thermo welded with a PVC cord to fill any fabricated as per the design. This duct on one end
gaps in the flooring. is connected to the AHU and on the other end to
the HEPA filters. The main duct is split into a
number of ducts equal to the number of HEPA
19.9.19 Painting Filters. The air then passes through the HEPA
Filters in the plenum. As an equal number of
All surfaces (walls and ceiling) of the OR are HEPA Filters are placed opposite to each other,
painted. First of all, a coat of primer is applied. the airwaves coming from both directions hit
Then the metal putty is applied to fill any gaps. each other and the final stream bends down and is
Once the putty dries up, the surfaces are scrubbed released from the plenum. Thus, forming a unidi-
with sandpaper. If needed, a second coat of putty rectional flow of air in the shape of an umbrella,
can be applied. This is followed up with at least which then rushes towards the return air duct fit-
two coats of washable antibacterial and anti- ted in the corners of the OR.
fungal paint. Please make sure that the colour of
the OR is light and attractive. Dark colours shall
be avoided. 19.9.22 Return Air
pressure inside the OR, and ultimately the excess The minimum fresh air component of the air
air has to exhaust to maintain a particular pres- change shall be a minimum of 4 out of 20 air
sure. The air which moves to the return air duct is changes.
sent to the AHU, filtered, mixed with fresh air, If the designer chooses to have a 100% fresh
cooled and again released from the AHU into the air system, then appropriate energy saving
OR, and the same process continues. devices like heat recovery wheel and run-around
pipes should be installed.
19.9.23 S
pecial Air Requirements 19.9.23.2 Air Velocity
for OR The airflow needs to be unidirectional and down-
wards on the OR table. The air face velocity of
19.9.23.1 Air Changes Per Hour 25–35 FPM (feet per minute) from non-aspirating
Minimum total air changes should be 20 based on unidirectional laminar flow diffuser/ceiling array
biological load and the location. is recommended.
198 19 Operation Theatre Suite
pline to other. However, generally, the following 19.10 Septic Operation Theatre
equipment shall be placed in the OR:
It is the OR where infected cases are operated.
Anaesthesia ventilator Mobile Ultrasound
The construction, specifications and design of
Anaesthesia work stations/ Morcellator
Boyle’s machine this OR are the same as any other. However, the
Blood pressure Apparatus Multi Para Monitor equipment and furniture of this OR are separate,
with ET Co2 and shall not be used in the normal OR.
Cryogun Navigators for Hip /
Knee
Cryophthalmic Unit Nephroscopes
CUSA Nerve Stimulator
19.11 Endoscopy Suite
Defibrillator Operating Instruments
ECT Machine Operating light It is used for the Upper G.I. endoscopy, colonos-
Electro Surgical Cautery Operating Microscope copy and other related procedures like
Emergency light Operating table ERCP. Some hospitals keep the endoscopic suites
attachments in the O.T. complex, whereas others keep it out-
Femto Lasix Ophthalmic Laser side the O.T. complex. Irrespective of the place,
Fetal Doppler Phaco- fragmentation the design and requirements of the suite remain
Unit
Head Light Pneumatic Tourniquet
the same. A complete endoscopy suite shall have
Electrical the following:
Heart-Lung Machine Portable O.T. Light
Heating Block Sternum Saw
Operation table 19.11.1 Endoscopy Room
Holmium Laser Saw, Drill and Remer
Sets
It is an OR like structure where the endoscopy
Hysteroscopy Pump Suction machine
electrical procedure is actually performed. This room has
Hysteroscope Telescopes an operating table placed in the centre. On the
Image Intensifier (C-Arm) UPS 10 Kva right-hand side of the patient is a monitor and the
Intra-Aortic Balloon Pump Uretero-Renoscope processing unit of the endoscope. The doctor/
Laparoscope set Vaporizer technicians perform the procedure from the left
Lithotripter Vitreous Aspiration hand of the patient and the images captured by
the camera (in the scope), and processed by the
processor, are displayed on the monitor. All the
19.9.26 Furniture OR design, parameters and specifications of a pre-
fabricated modular OR shall be followed for this
The following furniture shall be placed in the room. Apart from this, an endoscope storage cab-
OR: inet shall be provided in the room, which is spe-
cially designed to hang the endoscopes saving
1. Instrument Trolleys. them from being damaged.
2. Mayo stand.
3. Swab rack.
4. Steel bucket with lid Footstool. 19.11.2 Endoscope Washroom
5. Doctor stool.
6. I.V. stand. After every procedure, the endoscope needs to be
7. Sterilization drums. washed and disinfected. Therefore, an endoscope
200 19 Operation Theatre Suite
washroom shall be provided with the endoscopy so that the unidirectional flow of the air can be
room. This room has a long and deep sink with a achieved.
drainboard. The size of the sink shall be about
914 mm in length, 610 mm in width and 305 mm
deep. 19.13 Modular OR
This room is used by post endoscopy patients till It is an OR where multi-disciplinary integration
they are stabilized. This room is provided only if is done by combining advanced imaging diag-
the endoscopy room is out of the O.T. complex. nostics and surgery, which allows the surgeons,
radiologists and other healthcare providers to use
real-time images for guidance and assessment
19.11.6 Consultation Room during complex surgeries. Before Hybrid OR,
mobile imaging equipment was used, but it does
This room is used for consultation and interac- not produce high-quality images that are required
tion with the family members of the patient. This for delicate procedures. This allows conducting
room is provided only if the endoscopy room is more accurate, safe and less invasive surgical
out of the O.T. complex. procedures, leading to quicker patient recovery.
If an emergency arises during an interventional
procedure, it can quickly be revised to an open
19.12 Semi-modular OR procedure since the room is set up as a fully func-
tional OR. No critical time is lost in changing
At times due to some financial constraints, it is equipment or transporting the patient to a differ-
not possible to provide a full-fledged pre- ent operating room.
fabricated OR. In such cases, a semi-modular OR As different types of procedures such as car-
can be designed. In these OR, the modular wall diac, vascular and neurosurgery are performed in
structure is avoided. Also, all other fittings like a hybrid OR, it requires a variety of imaging
control panel, reassessed view box, whiteboard, equipment to be used. Some examples of com-
PRD, window and hermitical door are avoided. monly installed imaging equipment in a hybrid
Only the ceiling structure with the proper plenum OR are Angiography Equipment (Cathlab),
and HEPA filters with proper AHU are provided Computed Tomography (CT) Scanners, Magnetic
Further Reading 201
Resonance Imaging (MRI) Scanners, C-arm, Harry. General Operating Theatre Design [Internet].
X-ray and Digital Subtraction Angiography Hospital Design Tips. [cited 2021 Jun 21]. Available
from: https://hospitaldesigntips.com/2017/12/07/
System (DSA). general-operating-theatre-design/
When designing these types of facilities, it is Harsoor SS, Bhaskar SB. Designing an ideal operat-
critical to determine the primary use of the hybrid ing room complex. Indian J Anaesth. 2007 May
OR. It shall be at least 1.5 times larger than a nor- 1;51(3):193.
HCD Mag [Internet]. [cited 2021 Jun 21]. Available from:
mal OR, i.e. about 55.74 Sq Mtr. However, if a https://healthcaredesignmagazine.com/architecture/
CT scan or MRI has to be integrated into the integrated-operating-room/
Hybrid OR, the space requirement can go up to Humphreys H. Infection control and the design of a
74.32 Sq Mtr. An ancillary room for these modal- new operating theatre suite. J Hosp Infect. 1993 Jan
1;23(1):61–70.
ities shall also be provided, which may require Indmedica - Journal of the Academy of Hospital
additional space. Some examples of the ancillary Administration [Internet]. [cited 2021 Jun 21].
room are control room, UPS room and machine Available from: https://www.indmedica.com/journals.
panel room. php?journalid=6&issueid=72&articleid=907&action
=article
As far as the shape of the hybrid OR is con- Kameel R, Khalil E. Energy Efficient and Hygienic
cerned, it is more of a rectangular shape as com- Operating Theatres’ Hvac Airside Design:
pared to the regular OR, which is almost square Architectural and Engineering Consideration. In:
in shape. Even the length may vary from first International Energy Conversion Engineering
Conference (IECEC) [Internet]. American Institute
7620 mm to 9144 mm. The reason is that both of Aeronautics and Astronautics; [cited 2021
the imaging equipment and the actual operating Jun 21]. Available from: https://arc.aiaa.org/doi/
table are in length to each other. Considering the abs/10.2514/6.2003-5997
movement area of staff, such length is required Kavic MS. Operating Room Design: “The Devil is in the
Details”. JSLS. 2001;5(4):297–8.
in the hybrid OR. Krupka D, Sandberg W. Operating room design and its
Construction-wise, the hybrid OR shall follow impact on operating room economics. Curr Opin
similar norms to a pre-fabricated modular OR, Anaesthesiol. 2006 May 1;19:185–91.
i.e. walls, ceiling, doors, windows, air- Kumar S. Designing an ideal operating room complex.
[cited 2021 Jun 21]; Available from: https://www.
conditioning and control panel. academia.edu/29223685/DESIGNING_AN_IDEAL_
OPERATING_ROOM_COMPLEX
Acknowledgement I am grateful to Dr. Rohit Varshney B. T. Mayes M.V.O. Frcog MB,BS,FRCSE,FRACS. Inst
for his great support in compiling this chapter. I wish to allations in Operating Theatres. Archit Sci Rev. 1961
convey my thanks and gratitude to him for the time and Mar 1;4(1):2–5.
efforts he has put in. Ng I. Integrated Intra-operative Room Design. In:
Pamir MN, Seifert V, Kiris T, editors. Intraoperative
Imaging [Internet]. Vienna: Springer; 2011 [cited
2021 Jun 21]. p. 199–205. (Acta Neurochirurgica
Further Reading Supplementum). Available from: https://doi.
org/10.1007/978-3-211-99651-5_31
Agnew GH. Designing the Operative Suite. Can Med Planning and constructing a hybrid operating room:
Assoc J. 1965 Nov 13;93(20):1071–9. Lessons learned [Internet]. Building Design +
Blowers R, Crew B. Ventilation of operating-theatres.*. Construction. [cited 2021 Jun 21]. Available from:
Epidemiol Infect. 1960 Dec;58(4):427–48. https://www.bdcnetwork.com/blog/planning-a nd-
Chow TT, Kwan A, Lin Z, Bai W. Conversion of operat- constructing-h ybrid-o perating-r oom-l essons-
ing theatre from positive to negative pressure environ- learned
ment. J Hosp Infect. 2006 Dec 1;64(4):371–8. Sánchez-Barroso G, García Sanz-Calcedo J. Evaluation
Different Types of Operating Rooms: Hybrid, Integrated, of HVAC Design Parameters in High-Performance
Digital O.R. [Internet]. Brainlab. [cited 2021 Jun 21]. Hospital Operating Theatres. Sustainability. 2019
Available from: https://www.brainlab.com/journal/ Jan;11(5):1493.
hybrid-integrated-digital-o-r-differences-similarities/ Smylie HG, Dudley HAF. Some Principles in
Essex-Lopresti M. Operating theatre design. The Lancet. Operating Theatre Design. Scott Med J. 1961 Dec
1999 Mar 20;353(9157):1007–10. 1;6(12):588–96.
Gupta S, Bharti AA. Interior designing for general Weldon S-M, Korkiakangas T, Bezemer J, Kneebone
operation theater (An architectural approach). R. Music and communication in the operating theatre.
2018;05(11):6. J Adv Nurs. 2015;71(12):2763–74.
Delivery Room/Labour Room
20
The Delivery Suite or the Labour Room is a place 20.2.1 Unsterile Zone
where childbirth takes place. It is also termed as
‘Birthing Unit’. This unit provides facilities for This is a zone that is normally unsterile and the
safe prenatal care, delivery and immediate post- movement is allowed without any change.
natal care of mothers and infants. For a better
understanding of this chapter, we will refer to this
as ‘LDR’ (Labour, Delivery and Resuscitation). 20.2.2 Protective Zone
© The Author(s), under exclusive license to Springer Nature Singapore Pte Ltd. 2022 203
A. Garg, A. Dewan, Manual of Hospital Planning and Designing,
https://doi.org/10.1007/978-981-16-8456-2_20
204 20 Delivery Room/Labour Room
arrangement of cabinets, drawers, and racks for 20.4.5 Shoe Change Area
smooth working. Office tables and chairs shall
also be provided. Preferably the room shall have Space shall be provided in this zone for changing
an attached toilet. If required, a separate store shoes. The staff desirous of entering the complex
shall be attached to this room. The room shall has to remove the outside shoes and change with
also have proper arrangements for electrical the sleepers/shoes kept for this purpose. This area
points, intercom connection, I.T. network, CCTV shall be provided with a sufficient number of
surveillance and air conditioning. shoe racks and a chair for sitting while removing
or wearing shoes.
20.4.8 Public Utility for Attendants clothes. It is a set of the pre-sterilized dress (nor-
mally a full-length bottom pants and half-sleeved
Along with the waiting area for the family mem- long top) kept in the change rooms. The dresses
bers, the facility of toilets shall be provided. If of different sizes are stitched for different staff
possible, separate toilets shall be provided for members. Different Change rooms are provided
males and females. The facility of drinking water for different categories of staff members. Also,
shall also be provided. It will still be better if the the change rooms for males shall be separate
tea/coffee vending machine is placed in this area. from females. Following change rooms are gen-
erally provided in the LDR Complex.
electric points to charge the equipment when not alternative seating areas and shelves for
in use. The store shall also have a countertop to patients to lean on at standing and sitting
prepare the drugs if required. This store shall be heights.
in charge of the storekeeper of LDR Complex. 7. Space for patients to walk around the room
with sufficient support.
8. Designated areas for the mother’s belong-
20.5.3 Pre-labour Room/Ward ings, gifts and flowers.
9. Provision of soothing music or aromas.
The pre-labour room/ward is the area where 10. Provision of grab rails for patients.
pregnant women are kept during the labour pain 11. Temperature control within the room.
until the cervix is dilated, and the patient is ready
for delivery. The definite time of stay in this room
is very difficult to access, therefore, there shall be 20.5.4 Eclampsia Room
a sufficient number of beds in the ward/room.
Based on experience, it is recommended to have The pre-labour eclampsia room shall be provided
four beds per labour table. However, it is advised in the LRD. Some designer believes in having a
not to keep more than four beds in one ward, and single ward with 2–3 eclampsia bed. As the eclamp-
if more beds are required, an additional ward/ sia patient is very disturbed, it is recommended to
room shall be provided. have a single bed eclampsia room instead of a sin-
At times the patient may not like to stay in the gle ward with multiple beds. Number wise, one
ward along with other labour patients and may eclampsia room shall be provided with each labour
demand a single room. Also, if the patient is in table. Size-wise the room size shall be about
unrest and disturbing other patients, she should 4267 mm × 3658 mm. The facilities in the room
be shifted to a single room. Therefore, a better shall be similar to the pre-labour room.
combination will be to provide a ward of three
beds and a single room for each labour table.
If we consider three beds in one ward, size- 20.5.5 Examination/
wise, generally, 7.43–9.29 sq.m space per bed is Preparation Room
sufficient, i.e. the room size can be
4572 mm × 6096 mm. For a single bedroom, the This room is used to examine the patient during
size shall be about 4267 mm × 3658 mm. labour pain for cervix dilation and bleeding. This
The room/wards shall also have the following room shall also work as a Preparation Room to
provisions: complete the formalities of preparation before
sending her to the labour room. This room shall
1. Supply of Medical Gas Pipeline mounted on be about 3658 mm × 3658 mm in size, with an
the bed head panel on a few beds. examination couch. The room shall have a cabi-
2. Each bed shall be provided with at least two net to keep the necessary items, a sink and a por-
electrical points to connect the medical table light.
devices.
3. An adjoining toilet and bathroom with bath
and shower facility shall be provided. 20.5.6 Surgeons Rest Room
4. Individual nurse call button shall be provided
on all beds. This area is also called as the ‘Surgeons Lounge’.
5. The facility of foetal monitoring such as car- This room is used by the gynaecologists to relax,
diotocograph (CTG) monitors should be complete the patient file, prepare labour notes
located to provide ready access to the patient and post-labour prescriptions. The lounge shall
and the monitor. be provided with an attached toilet and a provi-
6. Provisions within the room to support a vari- sion of tea/coffee, which can be served from the
ety of pain relief methods such as bean bags, pantry.
208 20 Delivery Room/Labour Room
Size-wise the lounge shall be about The post-operative recovery ward shall have
3658 mm × 4572 mm, with a sofa set and a centre an attached general store, medicine store, clean
table. On the request, a single bed can also be utility room, dirty utility room and a toilet. Also,
placed in the lounge for gynaecologists to lay it shall have all other facilities as is provided in
down for some time. the pre-labour room.
After the recovery of the patient, she is trans-
ferred to the respective ward or ICU as the case
20.5.7 Dirty Utility may be. Thus, the location of the post-operative
recovery ward shall be at the exit end of the LDR
After the delivery, a lot of used items like linen, complex.
instruments, covers of disposables, soiled drapes,
cotton and gauze have to be removed. Out of this,
the linen is sent to linen pre-wash area and instru- 20.5.9 Doctors Night Duty Rooms
ments to the instrument washroom. Therefore,
this dirty utility room is provided at the exit end As LDR has to be operative round the clock,
of the LDR complex. The room shall be about there is a need to post a doctor on duty day and
3048 mm × 3048 mm and provided with bins as night. Hence, a doctor duty room is required in
per the biomedical waste management rules for the LDR complex. Separate rooms shall be pro-
other waste products. vided for the males and females. The room shall
be of the size 3658 mm × 4267 mm, with an
attached toilet. Furniture-wise, the room shall
20.5.8 Post-labour Recovery Ward have one office table, chair, bed and cupboard.
Apart from the light and fan, the room shall have
Once the delivery is complete, the mother and the points for computer with Internet connection and
baby have to be sent out of the labour room, and intercom. Also, the room shall be air-conditioned
usually the mother is shifted to the post-labour and the control button with temperature adjust-
ward/room. This ward is used to provide special- ment shall be provided in the room.
ized care to the mother until she is stable.
Generally, two beds per labour table are suffi-
cient. However, at times the patient may not like 20.6 Delivery Zone
to stay in the ward along with other patients and
may demand a single room. Therefore, the provi- This is the zone where the actual vaginal birth
sion shall be provided for a single bed post-labour takes place. This is the most sensitive zone in the
room. LDR Complex. This area has to be totally sterile
Size-wise, if we consider three beds in one and aseptic. Delivery zone is separated from the
ward, generally, 7.43–9.29 sq.m space per bed is protective zone by providing the swing-type
sufficient, i.e. the room size can be doors, which shall not be less than 6 ft wide.
4572 mm × 6096 mm. For a single bedroom, the These doors shall be sealed so that any unwanted
size shall be about 4267 mm × 3658 mm. organism cannot enter this sterile zone. On the
If the baby is normal and stable, he/she may exit side of this zone, similar doors are provided.
be shifted to the mother’s side, or if sick he/she The movement in this zone shall be strictly
shall be transferred to NICU. Thus, a provision restricted and only authorized persons shall be
for keeping the baby shall also be provided in the allowed, that too after the proper change, with cap
post-labour recovery ward. Bassinets can be used and masks. Just at the entry of this zone, a shoe
along each bed for this purpose. rack is placed which contains sterilized shoes or
The Nursing station shall be provided in the slippers to be worn before entering this zone. At
centre of post-labour recovery ward or outside the exit end of this zone, a double door with air
the rooms in case of the single bedroom. lock shall be provided to transfer the patient out of
20.6 Delivery Zone 209
the post labour recovery room. Details of the There should be no water supply or drain in this
rooms located in this zone are as follows: room.
This room is also termed as Clean Store. This The scrub station is used for washing up before
room is mainly used to store the instruments and entering the labour room for delivery. Every per-
linen received from CSSD after proper steriliza- son involved in the delivery process shall be
tion. It is also used for storing sterile consum- scrubbed in this area. This area should be adjoin-
ables and disposables that are normally used in ing the Labour Room. The scrub station can be
the labour room. This room shall be located near placed either in an open area or in a closed room.
the labour room so that it can serve the needs If it is in a closed room, the doors of this room
effectively. shall be able to easily swing in either direction
This room shall be about 4572 mm × 3658 mm just by the tap of the foot and should have a see-
in size with a single entry and the door shall be through glass in the middle.
swing type openable on both sides. It is still bet- The scrub area shall be provided with a stain-
ter if the door is hermetically sealed door opera- less steel scrub station, which could be operated
tional with sensors. The room shall not have any by foot and/or sensors. Hand-operated taps are
window; however, if the window is not avoid- not allowed in the scrub station. It shall have a
able, it shall be sealed with double glazing glass. minimum of two bays, with the provision of both
There should be no water supply or drain in this hot and cold water to wash hands. The number of
room. scrub stations depends on the number of labour
The room shall have stainless steel racks rooms in the complex. It is better if each labour
divided into bins, to store the sterilized material. room has its own scrub station. No more than two
The sterilized material is brought into this room labour rooms can share one scrub station.
through sterilized covered carts and the material The water outlet of the scrub station shall be
is unloaded in the racks. From here the stored designed to allow the water to fall in the centre of
material shall either move directly to LDR or the scrub and not spill around. There shall be a
otherwise to the Instrument Trolley Lay-up provision for dispensing the soap using a wall
room. hanging soap dispenser, which shall be elbow
operated. Similarly, an elbow-operated wall hung
antiseptic solution dispenser shall be provided
20.6.2 Instrument Trolley Layup with the scrub station. A nail brush should be pro-
vided, along with a nail cutter and a nail file.
This room is for preparing the trolley for deliv-
ery. The material is brought in this room from the
Clean Supply Room and laid on the trolley which 20.6.4 Sterilization Room
in turn shall move to the concerned Labour
Room. The trollies for layout are also wheeled At times during delivery, the surgeon may require
from the same Labour Room where it has to go some instrument or if accidentally some instru-
back after lay-up. ment falls down and gets contaminated, it has to
This room shall be about 3658 mm × 3658 mm be quickly sterilized to send it back to the sur-
in size with a single entry and the door shall be geon. Therefore, a small sterilization room is pro-
swing type openable on both sides. The door vided in the Sterile Zone of the LDR complex
shall be a sealed door. The room shall not have which is usually called the Theatre Sterile Supply
any window; however, if the window is not avoid- Unit. This room is located near the LDR clean
able, it shall be sealed with double glazing glass. supply room. The size of the room shall be about
210 20 Delivery Room/Labour Room
4. Stainless steel IV rod. the infant wearing a tag around the ankle and sen-
5. Mobility: swivelling castor wheels and brakes. sor panels located at every access and exit point
6. The mattress should be washable, waterproof, to the unit and possibly the entire hospital.
seamless, divided into three parts, have thin
cushioning at the joints, detachable at the per- Acknowledgement I am grateful to Dr. Rohit Varshney
for his great support in compiling this chapter. I wish to
ineal end and a spare set shall be kept. convey my thanks and gratitude to him for the time and
7. Disposable draw sheet. efforts he has put in.
8. Steel basins attachments.
9. Calf support, handgrip and leg support.
Further Reading
12VAC5-410-442. Obstetric service design and equip-
20.8.2 Shifting Baby to NICU ment criteria. [Internet]. [cited 2021 Jun 22]. Available
from: https://law.lis.virginia.gov/admincode/title12/
Preterm infants are at greater risk and often agency5/chapter410/section442/
require additional personnel, equipment and time Atmaca H. Patient Centered Approaches in Labor and
Delivery Room Design in Hospitals: Case Study in
to optimize resuscitation and stabilization, thus
Dokuz Eylül University Hospital. 2013;130.
requiring care as per the NICU standards. Such Austin N, Kristensen-Cabrera A, Sherman J, Schwandt
babies shall be immediately shifted to NICU just D, McDonald A, Hedli L, et al. Analyzing the het-
after the resuscitation. For shifting a ‘Transport erogeneity of labor and delivery units: A quantitative
analysis of space and design. PLOS ONE. 2018 Dec
Incubator’ shall be kept near the delivery room.
26;13(12):e0209339.
ECG | Obstetrics Unit Labor and Delivery Design: LDR Vs.
LDRP [Internet]. [cited 2021 Jun 22]. Available from:
20.8.3 Access to the Operating Room https://www.ecgmc.com/thought-leadership/articles/
obstetrics-unit-labor-and-delivery-design-ldr-vs-ldrp
Esfeh B, Kazemi A, Shamsaie A. Designing architecture
At times it may happen that during the vaginal of soothing labor–delivery–recovery–postpartum unit:
delivery, the patient suddenly gets serious and a study protocol. Reprod Health. 2020 Dec 10;17.
immediately requires a Caesarean Section. Jullien JM. Planning the Labor-delivery Unit in the General
Hospital. U.S. Department of Health, Education, and
Therefore, the approach and access to the
Welfare, Public Health Service, Division of Hospital
Obstetrics operating room shall be quick. Hence, and Medical Facilities, Architectural and Engineering
it is advised that the Obstetrics Operating Room Branch; 1964. 28 p.
shall be in the LDR Complex. Wrønding T, Argyraki A, Petersen JF, Topsøe MF,
Petersen PM, Løkkegaard ECL. The aesthetic nature
To increase the safety of newborns, the use of
of the birthing room environment may alter the need
electronic tagging may be implemented immedi- for obstetrical interventions – an observational retro-
ately after birth. This involves a combination of spective cohort study. Sci Rep. 2019 Jan 22;9(1):303.
Intermediate Care Area
(Patient Rooms) 21
In any hospital setup, the importance and utility ery rate, leading to higher patient satisfaction.
of the Patient Rooms cannot be ignored. It is a This, in turn, results in the increased business of
zone where a patient is admitted for the required the hospital.
treatment and recovery. This is also one of the General issues to be considered while design-
places where the patient or family members get ing the Patient room/ward in the hospital
to know about the quality of care and services
provided by the hospital.
Patients rely on staff to respond quickly to an 21.1 I mprove Patient and Staff
emergency situation, check them frequently and Safety
ensure a full recovery. However, the staff can
treat patients effectively only when they perform While designing the patient room spaces, the
their tasks efficiently and have adequate equip- safety of the staff and patients shall be the prior-
ment and supplies that are easily accessible. ity. The staff shall be able to protect themselves
Thus, the design, interiors, comfort, cleanliness and the patient in case of any adverse condition.
and safety of the room, and alertness and care The following measures shall be taken while
provided by the nursing staff are the main factors designing or constructing such spaces:
contributing towards patient satisfaction.
One of the greatest challenges faced by the 1. If a patient is deemed to be at a higher risk
designers while designing a hospital room is the for self-harm, self-injury or suicide, the room
need to accommodate the following three impor- shall be designed in such a way that each cor-
tant functions. First, the room shall be comfort- ner of the room is visible from the outside
able and calming for the patient. Second, health corridor. This allows nurses and other hospi-
workers must be able to navigate the space, tal staff to continuously watch the patient.
quickly and efficiently. And finally, family mem- 2. One-on-one observation by the staff or the
bers and other visitors must have an area where patient’s attendants shall be arranged.
they can comfortably sit or sleep without disrupt- 3. CCTV can be used for surveillance of the
ing the staff workflow or the patient’s recovery. patient inside the room.
This may not always be possible for small hospi- 4. There shall be no hiding places, sharp-edged
tals; however, the designer shall always try to furniture or tools for patient to use any equip-
accommodate such spaces. ment or furnishings in the room, as a weapon
Such designs not only streamline the staff against staff or self.
workflow but also help to improve patient recov-
© The Author(s), under exclusive license to Springer Nature Singapore Pte Ltd. 2022 213
A. Garg, A. Dewan, Manual of Hospital Planning and Designing,
https://doi.org/10.1007/978-981-16-8456-2_21
214 21 Intermediate Care Area (Patient Rooms)
5. Curved angles, hidden and pull-out equip- 3. Similarly, humidity shall be kept at average
ment and furniture in the room can greatly as higher humidity levels will cause suffoca-
reduce the risk of using them as weapons to tion to the patient.
harm staff or self. 4. The room shall be silent and free from
6. Glass shall be avoided in the room; however, unwanted sounds and noise.
if it cannot be avoided, tempered glass shall 5. The room shall be designed to allow cross
be used instead of normal glass. ventilation and be odourless.
7. Plastic silver-coated mirrors shall be used 6. The room shall have sufficient natural light-
rather than glass mirrors. ing. However, glaze shall be minimized in
8. Bottom height of the windows shall be more the room. As natural light shifts throughout
so that the patient cannot jump out of the the day (and throughout the year), proper sun
windows. shades shall be provided to the building.
9. Double glazing or grills shall be fit on all 7. The room shall be provided with windows
windows. through which natural landscapes like trees,
10. Ceiling fans shall be avoided. gardens etc. are visible.
11. Curtain rod or cloth hanging rods shall be 8. Single-patient rooms with private toilets
avoided. shall be preferred.
12. Shower rod and showerheads shall be short 9. The room shall have a provision for the
with no weight-bearing capacity. patient’s family and friends to be seated
13. The flooring of the room and the bathroom comfortably.
shall be non-slippery and at zero levels. 10. The room shall be designed to allow easy
14. Bathroom shall be provided with the proper cleaning. For example, provide wipeable sur-
grab bars. faces, washable paints, easy-clean flooring
15. Since most of the falls occur between the bed and a proper garbage disposable system in
and the toilet, designers shall try to reduce the rooms.
this distance. Grab bars shall be added in this 11. The room shall provide entertainment facili-
distance. ties like television or small indoor/board
games like Ludo, Playing Cards and Chess.
12. The room shall have attractive wall paint-
ings, wall arts and sceneries.
21.2 I ncrease Patient and Staff
13. The hospital can also think of providing free
Satisfaction
Internet facility to patients with a smartphone
or laptop.
One of the most important factors in a hospital
14. The hospital can also think of providing por-
setup is the satisfaction level of the patients,
table electronic media to allow patients to
which helps to increase the business. Above this,
make an audio-video call to his/her family
is the staff satisfaction level. If they are satisfied,
members.
they will give more input, and efficiency, result-
ing in good patient care and treatment. This care
will again increase patient satisfaction, and this 21.3 Provide Amenities
vicious cycle will continue. The following factors and Comfort for the Family
in a patient room contribute to increased patient
and staff satisfaction: Often anxious family members/friends visit a
hospital with the patient. Moreover, the family’s
1. The room shall have excellent facilities and support plays a significant role in the patient’s
shall be pleasant looking. recovery and reduces morbidity. For this reason,
2. Environmental conditions such as the tem- a Family Support Zone shall be placed near the
perature of the room shall not be too high or patient rooms. This zone shall have the following
too low. facilities:
21.3 Provide Amenities and Comfort for the Family 215
A family and visitor’s lounge should be provided Usually, a cafeteria is provided on the ground
adjacent to the patient room. For a few rooms put floor of the hospital, from where the family mem-
together, a single-family lounge can be created. It bers can obtain refreshments. Drinking water
must have a comfortable waiting area with reclin- fountains or other freshwater supply facilities
ing chairs, privacy during conversations and a should be located within or near the cafeteria and
telephone/intercom facility. It shall also have lounge. Some hospitals provide food trays to the
basic amenities like a television, newspaper and family members at different meal times. In such
magazine stand and a small play area for chil- cases, a separate space or dining hall shall be pro-
dren. Snack, tea and coffee vending machines vided, where the family members can be served
shall also be provided. Visitor access should be their meals. Vending machines can also be help-
controlled from the receptionist area. Shelves, ful, particularly at late hours when the hospital
closets and secure lockers shall also be provided coffee shops or food services may not be avail-
to avoid scattering personal belongings around able. However, in both the cases, care shall be
the lounge. Accessible toilets for males and taken to provide arrangements for adequate dis-
females should be reasonably close to, or a part posal of used utensils and maintain hygiene
of, the lounge. standards.
Anxious family members often need to see the At times, a family member needs to stay with the
treating physician to obtain an update on patient patient for providing special care. Therefore, it is
condition/recovery. Therefore, consultation recommended that an individual patient’s room
rooms shall be provided in the patient rooms shall have a provision for a family member to
area. One such room for 20–30 beds is sufficient. stay. If that cannot be provided, then a separate
This room shall be about 4572 mm × 4267 mm guest house shall be arranged, which can be allot-
with the provision of a table, chairs and a sofa set. ted to the family members on payment. These
At times there can be hot discussions, thus, a guest houses may have the amenities like bed,
security personnel shall be placed outside the bedding, toilet, TV, fridge and mess. The hospital
room. Further, this room shall be under CCTV can also enter into an agreement with a nearby
surveillance. hotel to accommodate visitors and families, the
rent of which shall be paid by the family
member.
21.3.3 Meditation Spaces
laundry of the hospital and returned to the same bringing the chart to the patient room and
counter from where they can be collected. This turning the pages to see the chart. It is even
service shall be payable by the family member. better if the physicians’ instructions are
immediately recorded in the system through
the same monitor. Another advantage is that
21.4 Increase Staff Efficiency the access to lab reports, vital signs and med-
ications throughout the course of the patient’s
The hospital staff is under a great deal of tired- treatment and other details of the patient
ness and pressure as they have to run throughout shall be immediately available to the physi-
the day to provide care and treatment to patients. cians on the monitor next to the patient’s
The following factors can help reduce staff run- bed.
around and increase their efficiency:
2. Wall furnishings shall be excellent with water- the wall. This light shall be switched on only
proof and washable paints. during any procedure.
3. Pictures, paintings, murals and artwork shall 11. Night low-level illumination shall be pro-
be placed appropriately for patients, families vided at the height of 18 in. from the floor,
and caregivers. near the patient’s bed.
4. The ceiling is the most often observed space 12. Emergency battery operated light shall be
by a bed-ridden patient. Thus, it can be painted provided in the corridors and patient unit.
with pictures and sceneries. Even 3D lami- 13. It will be better if the light controls are done
nated ceilings can be opted for. through variable-control dimmers at the user
end.
21.6.1 Single Bed Occupancy Semi- Patient Beds (Twin Sharing) with Toilet
private Nurse Desk
Ward (Twin Store
These rooms are also known as ‘Private Ward’
Sharing) Dirty Utility/Sluice Room
and have one patient bed with other amenities.
Clean Supply Room
They can be sub-categorized as follows:
Examination and Treatment Room
1. Normal Private Room Ward Pantry
Resident Doctors and Student Duty
2. Deluxe Room
Room
3. Super Deluxe Room Nurses Duty Room
4. Suites Extra Rooms for Future expansion
Public Utility for Staff
Visitors Bay
21.6.2 Sharing Rooms Private Patient Beds (Single Bed) with Toilet
Ward Nurse Desk
These are also known as ‘Semi-Private Rooms’ (Single Bed) Store
and usually have 2–4 patient beds shared in a Dirty Utility/Sluice Room
single room. Clean Supply Room
Examination and Treatment Room
Ward Pantry
21.6.3 General Wards Resident Doctors and Student Duty
Room
These are the wards having multiple beds, gener- Nurses Duty Room
Extra Rooms for Future expansion
ally between 6 and 30 beds in a single hall.
Public Utility for Staff
Visitors Bay
Deluxe Patient Beds (Single Bed) with Toilet
21.6.4 Isolation Ward/Rooms Ward Nurse Desk
(Single Bed) Store
These are separately demarcated areas for hous- Dirty Utility/Sluice Room
ing infectious patients. Under this category as Clean Supply Room
well, there can be Private Rooms, Semi-private Examination and Treatment Room
Rooms and General Wards. Ward Pantry
Resident Doctors and Student Duty
Room
21.7 Infrastructure Details Nurses Duty Room
Extra Rooms for Future expansion
of the Indoor Patient Units
Public Utility for Staff
General Patient Beds Visitors Bay
Ward Nurse Desk Family Patient Beds (Single Bed) with Toilet
(Multiple Suites Family Room
Nurses Duty Room
beds) (Single Bed) Nurse Desk
Store
Dirty Utility/Sluice Room Store
Clean Supply Room Dirty Utility/Sluice Room
Examination and Treatment Room Clean Supply Room
Ward Pantry Examination and Treatment Room
Resident Doctors and Student Duty Ward Pantry
Room Resident Doctors and Student Duty
Extra Rooms for Future expansion Room
Public Utility for Staff Nurses Duty Room
Public Utility for Patients and Extra Rooms for Future expansion
Attendants Public Utility for Staff
Visitors Bay Visitors Bay
21.10 Single Patient Room (Private Room) 219
21.8 Location of the Indoor where the zoning of the indoor patient area shall
Patient Areas be a necessity. A separate zone shall be provided
for infected patients. All types of ward/rooms
Zoning of the indoor hospital area has to be care- shall be created in this zone only. For example,
fully planned. It has to be kept in mind that the the isolation zone shall have a separate set of the
indoor area is a Limited movement zone, and only general ward, semi-private rooms, private rooms,
the patient and family members are allowed to deluxe rooms, suites etc. If needed, a separate
enter this area. Hence, it is advisable to plan this Intensive Care Unit shall also be provided in this
area on the upper floors of the building. As per zone for infected patients. It is recommended that
the 12 storey building design explained earlier, all the categories of isolated indoor units of a par-
the suggested indoor area can be planned between ticular zone shall be in a cluster (maybe on the
fourth and seventh floors. same floor/block/building or adjoining floors/
As we have different categories of indoor blocks/buildings).
rooms and wards to be located, two options for
allocating space to each one of them across floors
have been suggested below. 21.10 S
ingle Patient Room (Private
The first option is to plan all single room types Room)
in a cluster on a single floor. For example, all the
single bedrooms (private/deluxe/suite) on one Multiple occupancy rooms are on their way out.
floor, all semi-private room on another floor etc.Most of the patients nowadays prefer to have a
The second option is that each floor shall havesingle-occupancy room to ensure privacy, com-
a mixture of all the wards/rooms. For example, a fort and availability of family members nearby.
few private rooms, semi-private rooms and one or Also, patients prefer to have better care and treat-
more general wards on each floor. ment, irrespective of the cost. Any patient, who
Both systems have their own pros and cons. can afford the costs, always prefers to choose a
However, opting for the first option is reasonablysingle-occupancy private room than multiple
better as the rooms will ideally be of identical occupancies. This increases the revenue of the
size; thus, the room design will be better placed hospital because the charges of single occupancy
for family lounges can be planned better, the rooms are more than other low category w ards/
nursing station can be at a better place, toilets can
rooms. Therefore, the hospital owners shall pre-
be planned wall to wall in the same length, move- fer to have a greater number of single bed units.
ment of the staff and people can be better con- This cannot be true for the charitable hospitals, as
trolled etc. their motive is to provide treatment to the poor
Ideally, in a 12 storey building, all general for free or at a negligible cost. Under this sce-
wards can be placed on the fourth floor, semi- nario, the concept of the general ward with mul-
private rooms on the fifth floor and the sixth andtiple beds is better. Otherwise, single occupancy
seventh floors can be reserved for all private wards.
rooms considerably help in controlling the spread
Along with these, required attachments and spaces of infections such as COVID-19, methicillin-
shall also be planned on the same floor. resistant Staphylococcus aureus, Gram-negative
bacteraemia in burn patients, and respiratory and
enteric infections requiring contact isolation in
21.9 Zoning of the Isolation Areas paediatric units.
A well-designed patient room has also been
One potential response is dedicating specific found to be a factor in improved patient care by
areas, either within hospitals where infectious providing better patient consultations, improved
patients are managed or in dedicated non- patient and clinician satisfaction, decreased
infectious facilities, where elective care may be length of stay and continuity of care during the
delivered. Post-COVID-19 designs shall be such hospital stay.
220 21 Intermediate Care Area (Patient Rooms)
21.10.1 Room Layout suggested for easy movement of the bed in and
out of the room in case of emergency.
The single patient occupancy room shall be
divided into three zones—a) staff zone located at
the room entrance to allow efficiency in perform- 21.10.5 Windows
ing their tasks, b) patient zone where the patient’s
bed is placed and c) family zone for providing As natural lights help in early recovery and avoid
comfortable seating for visitors. disorientation and a sense of claustrophobia in
patients, windows shall be preferred in the room;
however, direct sunlight shall be avoided. Further,
21.10.2 Size of the Room a window with an outside view such as gardens,
trees, courtyard, or other natural settings, may
A private single room shall have an area of about help to relieve anxiety and stress, improve care,
23.22 sq.m including the family space and toilet. enhance patients’ comfort and improve their ori-
While designing a single occupancy private entation. The window shall be located on the front
patient room, the following points shall be wall, or any sidewall (left/right) so that the patient
considered: can see outside the window even in lying position.
The window may be openable or non-open able,
depending on the design. However, the glass shall
21.10.3 Walls be tinted or curtains/blinds shall be provided. If
cost is not a criterion, then electronic windows,
The room shall be covered with walls on all the which are transparent when switched off and turn
four sides except the area for windows and door. opaque when switched on, can be fixed.
The wall thickness shall not be less than 120 mm
with plaster on both sides of the wall. The walls
can either be made out of clay bricks or hollow 21.10.6 Toilets
blocks, as per the design and technical civil con-
struction details. A separate toilet and bathroom with a handwash-
ing station shall be provided in all rooms. For
21.10.3.1 Headwall single occupancy rooms, shared or common toi-
The wall behind and the ceiling over the patient’s lets are not allowed. As far as the location of the
head are the most important spaces for incorporat- toilet is concerned, there are three models for it as
ing clinical care elements. Provisions for medical suggested below:
gases, power, information systems, monitoring
and critical equipment storage are located here. 21.10.6.1 Mid-board Toilet Model
Under this concept, toilets are located back to back
21.10.3.2 Footwall between two patient rooms. i.e. the toilets of both
It displays those items that the patient will the rooms are sandwiched between two rooms.
directly view, such as television, clock and tack- This design allows the rooms to be of square or
board with different information. It is an ideal rectangular shape, the best shape for any acuity
location for artwork. Most hospitals nowadays level. The full-width wall along the corridor allows
incorporate a flat screen television monitor with maximum visibility at the patient, while the full-
computer capabilities on the footwall. width window wall allows maximum space for
family seating and outside viewing. The bed can
also be nearer to the corridor door for easy staff
21.10.4 Doors access. The toilet door is on the foot side of the
bed. The negative point of such a design is that
The door of the room shall not be less than each pair of rooms generate approximately 6 ft of
1829 mm wide, unobstructed. A wide door is additional corridor length (Fig. 21.1).
21.10 Single Patient Room (Private Room) 221
Fig. 21.1 Sample
layout drawing of
mid-board single
occupancy room
21.10.6.2 Inboard Toilet Model bed and the corridor. However, the window and
Under this concept, toilets are located on the cor- family area are a setback from the patient, reduc-
ridor side, adjacent to the patient room door. This ing views and light, and making family interac-
type of design allows the toilet to be more acces- tion more difficult. The housekeeping must
sible to the patient and the housekeeping. It also traverse the room to clean the toilet room
allows the window wall to be open to its full (Fig. 21.3).
width, maximizing natural light and views, and After comparing the advantages and disadvan-
allows more space for a family. By placing the tages of all three concepts, it is recommended to
toilet inboard, there is more sound attenuation opt for the Mid-board Toilet Model concept
from corridor noise and more privacy. A draw- because:
back is a reduced visibility from the corridor and
the distance of the patient’s bed from the door 1. It gives a proper rectangular shape to the
makes this room type less ideal for patients. room.
Another drawback is difficulty of moving the 2. On the corridor side, a wide window can be
patient out of the room in case of emergency. The provided to view and keep a watch on the
design shall be such where the staff moving in the patient’s condition.
corridor can have an easy look at the patient’s 3. On the back wall, bigger windows can be
condition and provide immediate help if needed provided for better natural light and outer
(Fig. 21.2). views. This can relieve the patient from land-
ing into claustrophobia.
21.10.6.3 Outboard Toilet Model 4. Toilet being sandwiched between a pair of
Under this concept, toilets are placed on the back rooms, shall provide the space for water sup-
side of the patient room, on the outer wall. This ply and drain line to be taken directly outside
allows maximum visibility of the patient from the the building and terminate them in the ser-
corridor and reduces the distance between the vice shafts provided for this purpose.
222 21 Intermediate Care Area (Patient Rooms)
Fig. 21.2 Sample
layout drawing of
in-board single
occupancy room
Fig. 21.3 Sample
layout drawing of
out-board single
occupancy room
21.10 Single Patient Room (Private Room) 223
3. Air flow, direction and air exchanges have to 2. Air Conditioning Control button with tem-
be as per the industry norms. perature adjustment.
4. Heating shall be done with water pipeline and 3. On each of the Bedhead Panels, the electrical
FCUs having hot water generator instead of points are provided. There shall be at least
water chillers. Otherwise, room heaters can be three pairs of 6/16 Amp switches/sockets, i.e.
opted; however, they are generally not six points. Half of these points shall be on
recommended. UPS supply.
5. Temperature shall be between 21 and 24 °C. 4. On the left and right sides of the patient, and
6. Depending on the type of room/unit, the at a distance of 1219 mm from the centre of
choice of positive or negative operating the bed, one pair of 6/16 Amp. switches/sock-
pressures shall be made. For isolation rooms, ets shall be provided at the height of 457 mm
negative pressure shall be adopted. from the floor level, i.e. four points. Two pairs
For full details on Air-conditioning, heat- shall be on UPS supply.
ing and air exchanges, please refer to the
chapter of ‘HVAC’ (Chap. 38) in this book.
21.10.12 Other Communication
Points in Patient Room
21.10.10 Central Piped Medical Gas
Supply
1. Point for Nurse Call device
2. RJ 45 point for computer networking
In all the patient rooms, Piped Centralized
3. RJ 11 for intercom and extension line
Medical Supply shall be provided to handle any
4. Point for reading light for patient
emergencies. Usually, the provision of mechani-
cal ventilation is not provided in the patient room,
as it is difficult to handle ventilated patients in the
rooms. Therefore, such patients need to be trans- 21.10.13 Curtain Partitions
ferred to the ICU for further management. The
following gases are supplied: The patient bed in the room shall be provided
Oxygen with hanging curtain partitions. Following points
Wall-mounted Suction shall be considered for the same:
In patient rooms, the facility of supply of these
1. The bed shall have a curtain on all other three
lines shall be on every bed. In some hospitals, the
sides.
outlets of these gases are fixed on the wall itself.
2. The ceiling suspended curtain track is fixed at
Nowadays, the bedhead panel is used for this. It
2134 mm above the floor level.
is a 1219-mm panel made of extruded sections of
3. Curtains shall be hung on these tracks and
aluminium. This panel has a provision for fixing
shall be moveable and collapsible.
the gas outlets and the electrical points. Also, this
4. The bottom of the curtain shall have a clear
panel has a service railing on which the IV rod,
area of about 457 mm from the floor to allow
monitor tray and utility basket can be fixed. This
easy cleaning of the floor.
panel is fixed at the height of 1524 mm above the
floor level and goes up to 1829 mm. The panel is
fixed on the head side wall of the patient.
21.10.14 IV Track
21.10.11 Electrical Points in Patient The patient bed in the room shall be provided
Room with a ceiling suspended IV track. Following
points shall be considered for the same:
1. Main Switch board shall be at the entrance
wall for controlling fans and lights of the hall 1. In the centre of the bed, the track shall be
along with one 6 Amp Switch/Socket. mounted length wise.
21.12 Family Suite with Single Patient Room (Suite Room) 225
2. The track is mounted and screwed to the ceil- 1. Size of the deluxe room shall be about
ing/false ceiling of the room. 27.87 sq.m.
3. The IV hanger shall be fixed in the track, 2. Size of the toilets can be bigger, and they can
which shall be moveable in the track. be designed to look more appealing by fixing
4. The IV hanger can be with the provision of patterns on the wall instead of pain tiles. The
three, four or five hooks. chinaware and the sanitary fittings shall be of
better quality.
3. Bedhead panel can be 1524 mm long with
21.10.15 Psychiatric Patient Rooms more electrical points.
4. Ceiling finishes can be better.
Psychiatric patients are normally in a disturbed 5. The patient bed shall be a multi-positional
state of mind and may have aggressive behaviour, ICU bed on lockable wheels, with bedside
resulting in incidents of violence and may cause safety rails.
psychological harm, and often physical injury, to 6. Other patient furnitures like over bed table
themselves and staff. Therefore, while preparing and the bedside lockers shall be more elegant
the psychiatric patient rooms, special attention and of good quality.
shall be paid to the following points: 7. A small kitchenette equipped with an electric
kettle and a microwave shall be provided to
1. The light fixtures, air vents, sprinkler heads make tea/coffee, snacks etc.
and other appurtenances shall be 8. Size of the refrigerator can be bigger.
tamper-resistant. 9. Good quality pull-out bed or sofa set shall be
2. The bedrooms must have a private toilet with a provided for visitors.
non-lockable door that is capable of swinging 10. More space shall be provided for family and
outward, with a tamper-resistant ceiling and visitors.
tamper-resistant light fixtures, air vents etc. 11. The quality of dining table and chairs can be
3. The room for psychiatry patients shall be sep- improved.
arate and shall not be mixed with other 12. The cupboards can be bigger and designer.
patients. It is recommended that the psychia- 13. Better quality artwork and sceneries can be
try ward/rooms shall be located on the lower provided.
floors of the hospital building.
4. Avoid providing windows in the psychiatric All other details and requirements shall be the
patient rooms. If provided, the bottom height same as for a single patient room in this chapter.
shall not be less than 6 ft from the floor level.
5. All the windows shall have a provision of
grills. 21.12 F
amily Suite with Single
6. The corridors leading to the psychiatry room Patient Room (Suite Room)
shall be provided with the barriers or doors
and shall be kept locked. These barriers or Family suite differs from other single bed patient
doors shall also be guarded. rooms as one additional room for the family is
7. Proper CCTV camera surveillance shall be provided, which is attached to the patient room.
provided. Apart from this, it has a few additional amenities
like:
21.11 D
eluxe Single Patient Room
(Deluxe Room) 21.12.1 Patient Room of the Suite
The deluxe single bedroom is more or less the 1. Size of the deluxe room shall be about
same as a single bed patient room, however, it has 27.87 sq.m.
a few additional amenities like:
226 21 Intermediate Care Area (Patient Rooms)
2. Size of the toilets can be bigger, and they can 21.12.2 Family Room of the Suite
be designed to look more appealing by fixing
patterns on the wall instead of pain tiles. The 1. Size of the family room shall be about
chinaware and the sanitary fittings shall be of 18.58 sq.m.
better quality. 2. The family room shall be attached to the
3. Bedhead panel can be 1524 mm long with patient room.
more electrical points. 3. The family room can be separated from the
4. Ceiling finishes can be better. patient room either by a solid wall or by a
5. The floorings shall be better. glass partition (Fig. 21.4).
6. The patient bed shall be a multi-positional 4. The family room may or may not have a sep-
ICU bed on lockable wheels, with bedside arate door. If only one door is provided for
safety rails. the suite, the family room shall be in the
7. Other patient furnitures like over bed table front and the patient room at the back.
and the bedside lockers shall be more elegant 5. Separate toilet in the family room shall be
and of good quality. preferred.
8. A small kitchenette equipped with an electric 6. A small kitchenette equipped with an electric
kettle and a microwave shall be provided to kettle and a microwave shall be provided to
make tea/coffee, snacks etc. make tea/coffee, snacks etc.
9. Size of the refrigerator can be bigger. 7. In the kitchenette, a working slab shall be
10. Good quality pull-out bed or sofa set shall be provided along with a washing sink and
provided for visitors. drainboard.
11. More space shall be provided for family and 8. Family room shall have a sofa set for seating
visitors. 5–7 people, along with a centre table.
12. The quality of dining table and chairs can be 9. Dining table and chairs shall be provided in
improved. the family room.
13. The cupboards can be bigger and designer. 10. One extra refrigerator shall be provided in
14. Better quality artwork and sceneries can be the family room.
provided.
Fig. 21.4 Sample
layout drawing of family
suite
21.13 Sharing Patient Room (Semi-private Room) 227
21.13 S
haring Patient Room (Semi-
private Room)
opposite to the door side. The window may be 21.13.7 Air Conditioning System
openable or non-openable depending on the of Patient Rooms
design. The glass can be tinted, or curtains/blinds
shall be provided. It shall remain the same as that of a single occu-
pancy patient room.
21.13.12 IV Track There are a few issues with the multiple bed
wards, such as:
It shall remain the same as those of a single occu-
pancy patient room, but the tracks shall be pro- 1. Maximum chances of spread of infection in
vided on both the beds. the wards.
2. Environmental conditions may be compro-
mised, and wards can have a foul smell.
21.13.13 Lighting 3. Proper hygiene is difficult to be maintained.
in the Patient Room 4. Toilets are shared among different patients.
5. Reduced privacy of the patients.
It shall remain the same as those of a single occu- 6. No proper entertainment source, as televi-
pancy patient room. sions cannot be provided in such wards.
7. Wards may be noisy, as a lot of people tend to
be inside the ward at once.
21.14 G
eneral Ward (Multiple Beds 8. Reduced inter-bed spaces.
Room) 9. No proper space for the family members to
stay along with the patient.
In earlier days, multiple occupancy rooms were
very popular, but slowly their demand decreased. Still some hospitals have a setup of multiple
Patients usually opt for this ward as the treatment bed wards to cater to financially hampered
cost is very low and they do not mind compro- patients. However, a well-designed multiple bed
mising on privacy. However, as the living stan- ward can curtail the above issues to some extent.
dards and income of patients increased over the
period of time, the demand for multiple bed
wards reduced. Still some charitable hospitals 21.14.1 Location of the Multiple Bed
and free hospitals prefer more number of multi- Wards
ple wards as compared to the paid wards. Patients
with limited financial resources prefer to stay in a All the multiple bed wards shall be located in a
multiple bed general ward (Fig. 21.6). cluster, in a particular zone and a particular floor
of the hospital. Isolation ward shall be located in not be less than 9.29 sq.m, so the ward size shall
the isolation zone of the hospital. be about 22,860 mm × 12,192 mm.
21.14.7 Bed Layout in Ward AHU and ducting shall be used in the multiple
bed wards.
The beds in the ward shall be laid out in such a
manner that it allows easy and smooth working 21.14.10 Central Piped Medical Gas
all around the bed. The following points shall be Supply
considered while laying down beds in the ward:
It shall remain the same as that of a single occu-
1. The beds shall be laid down along both the pancy patient room and preferably it shall be pro-
large-sized walls opposite to each other. vided on all the beds of the ward.
Hence, leaving the free movement area in
between. 21.14.11 Electrical Points in Ward
2. Headend of the bed shall be at least 610 mm
away from the wall. 1. Main switchboard shall be at the entrance
3. On the foot end of both the beds, a clear space wall for controlling fans and lights of the hall
shall be about 1829 mm so that a stretcher along with one 6 Amp. switch/socket.
trolley can easily be turned around and patient 2. Air Conditioning control button with temper-
can be transferred from/to bed. ature adjustment.
4. Inter-bed distance shall not be less than 3. On each of the bed head panels, there shall be
914 mm. at least two pairs of 6/16 Amp. switch/socket,
5. If the width of the ward is more, say i.e. four points. Half of these points shall be
12,192 mm, a low height wall can be pro- on UPS supply.
vided in the centre of the hall and beds be 4. Between two beds, in the centre, two pairs of
laid down on both sides of the low height 6/16 Amp. switches/sockets shall be provided
wall. It means there will be four rows of the on the wall at the height of 457 mm from the
bed in a ward. Two on each side of the low floor level. Out of these, one pair shall be on
height wall and two on both the long walls UPS supply.
of the hall.
WC positive-pressure differential, ensuring that Air-handling unit (AHU) serving the isolation
the patient is protected from airborne contamina- rooms shall have proper pre-filters, and high-
tion regardless of whether an anteroom is used. efficiency particulate air (HEPA) final filters.
Typically, positive-pressure rooms are designed For detailed air conditioning system of the
to maintain an even stricter set point of positive isolation rooms, please refer to the chapter
0.03-in. WC. The positive-pressure relationship ‘HVAC’ (Chap. 38) in this book.
to the corridor should be preserved; however, it is
not required to be maintained at the minimum of
positive 0.01-in. WC. 21.16 Supporting Room/Units
When an anteroom is used, airflow must be for Indoor Patient Service
from the patient room into the anteroom and from
the anteroom out into the corridor. As with the Apart from the patient units/rooms/wards, there
AII negative room, typically a minimum airflow are a few other rooms and utilities that are
difference of 150–200 CFM is adequate to main- required to serve patients and provide them with
tain a pressure differential in a well-sealed room. good care and treatment. Some of these are:
Positive-pressure rooms are required to be sup-
plied with HEPA-filtered air, with the filters 1. Nurse Station/Desk
installed at the main air-handling unit or at the 2. Nurses duty rooms
supply terminals in the room. 3. Doctors duty rooms
Supply air for the room must be located in the 4. Procedure and Treatment Room
ceiling above the patient bed, with return air 5. Clean Utility
taken from the ceiling near the patient room door. 6. Dirty Utility/Sluice Room
The supplied diffuser shall be a non-aspirating, 7. Store for medicines, consumables and
laminar-flow device and should be designed to disposables
limit the air velocity at the patient bed, to reduce 8. Medication Area
the possibility of patient discomfort. Airflow to 9. Equipment Park/Store
the PE isolation room shall be maintained at a 10. Trolley Park Area
constant volume to provide consistent ventilation 11. Ward Pantry
in the room.
ficient. It will be better if this nursing counter is operation. The sensor-controlled and/or foot-
placed somewhere in the centre of these rooms, operated scrub stations shall be used. It shall have
so that the distance from all the rooms is as less the provision of both hot and cold water.
as possible.
For general multiple bed wards, the nursing
station shall be at some height so that the nurse 21.17.2 Alcohol Gel/Sanitizer
can easily see the patients. For this, a platform of Dispensers
about 305 mm height can be provided on which
the counter can be placed. Alcohol gel/sanitizer dispensers should be
Nurse station design shall be such that the located in the patient room as well as at other
caregivers also maintain adequate distance. staff locations around the unit. In the patient
Normally, hospitals have a nurse counter, from room, this can be hung with the help of a holder
where the patient/visitors interact with the nurse. at the foot end of the bed.
This type of counter can be more prone to spread-
ing infection because of no barrier in between. To
overcome this issue, consider going away from 21.18 Nurses Duty Rooms
open nurse stations and enclosing them in ‘glass
bubbles’. It is advised to make a proper 1829 mm These rooms allow the nurse to take rest/breaks
high acrylic or glass partition at the top of the and store their personal belongings, while on
nurse counter so that the staff is always on the duty. Each nursing station shall have one nursing
other side of the partition while interacting with duty room. The following issues shall be consid-
the patient/visitor. We can also use technology ered while designing nurses duty rooms:
like Audio-Video Controlled Nurse Call System.
Nursing station shall have sufficient storage 1. The room shall be of the size 3048 mm
facility for instruments, tools, patient files and × 3048 mm.
stationery. Sufficient electrical and communica- 2. It shall have an attached toilet.
tions points shall be provided. A view box shall 3. It shall have one bed and a cupboard.
also be fixed on a wall near the nursing station. 4. Apart from light and fan, the room shall have
Each nursing station shall be provided with the points for computer with Internet connection
following: and Intercom facility.
5. It shall be air-conditioned and the control but-
1. At least 5–7 numbers of 6 Amp. switches/ ton with temperature adjustment shall be pro-
sockets. vided in the room.
2. Point for Nurse Call Control Console.
3. RJ 45 point for Computer networking.
4. RJ 11 for Intercom and extension line. 21.19 Doctors Duty Rooms
5. HDMI point for computer display at other
locations. It shall be provided with a group of patient rooms.
As per experience, one such room shall be pro-
vided for 30–50 patients. This number can be
21.17.1 Hand Hygiene increased or decreased as per the requirement.
The following issues shall be considered while
For hand hygiene, in the indoor patient area, two- designing doctors duty rooms:
way scrub stations shall be used and placed near
the nursing stations. Soap dispensers, paper towel 1. The room shall be of the size
dispenser and trash receptacle should be next to 4572 mm × 4267 mm.
the scrub station. It should enable hands-free 2. It shall have an attached toilet.
236 21 Intermediate Care Area (Patient Rooms)
3. It shall have one office table, chair, bed and a 3. It shall have a single-entry door.
cupboard. 4. A gowning and scrub station shall be attached
4. Apart from light and fan, the room shall have to the treatment room.
points for computer with Internet connection
and Intercom facility.
5. It shall be air-conditioned and the control but- 21.20.4 Furniture in Treatment/
ton with temperature adjustment shall be pro- Procedure Room
vided in the room.
Patient Furniture
OT Table Scrub Station
21.20 Procedure Stretcher Trolley IV Stand
and Treatment Room Dressing Trollies IV Rod
Instrument Trollies Crash Cart
At times, patients may require undergoing minor Step Stool Oxygen Cylinder Trolley
procedures like catheterization, suturing of small
wounds, dressing and bandaging. However, it is Equipment
difficult to do these procedures in the patient Multi-para Vital Sign Laryngoscope
room, due to high chances of getting infected, the Monitor
privacy of the patient, or the procedure requires Portable Operating Light Suction Machine
anaesthesia. Therefore, a treatment room or pro- Single Dome
Infusion Pump Oxygen Cylinders With
cedure room shall be attached to each set of
Masks
patient rooms. One such room shall be sufficient Defibrillator View Boxes
for 50 patients in the indoor area.
21.20.8 Central Piped Medical Gas A clean utility shall be attached to each nursing
Supply station of the indoor areas, which shall be used
for the storage of clean linen. Sterilized material
As surgical interventions have to be done in like a drum and drapes is also stored in this room.
Treatment/Procedure Room, the following gas Normally, the room shall not be less than
outlets shall be mounted on the ceiling suspended 3658 mm × 3658 mm, but depending on the
pendant: requirements, the size of the room can be
changed. The room shall be provided with closed
1. two outlets for Oxygen cabinets, drawers and racks. This room shall have
2. two outlets for Compressed Air only one door of about 3 ft.
3. two outlets for Suction Oxygen
21.20.10 Other Communication All nursing stations shall be provided with a gen-
Points in Treatment/ eral store to keep ample stock of required medi-
Procedure Room cines, consumables and disposables. The room
shall be at least 3048 mm × 3048 mm in size.
1. RJ 45 point for Computer networking. Adequate lockable cupboards, racks and drawers
238 21 Intermediate Care Area (Patient Rooms)
shall be provided in the store. It shall also have a ward pantry for further distribution. The diet is
countertop. It shall be in charge of the Ward sent in bulk from the kitchen either packed for
Supervisor. direct distribution or otherwise unpacked.
The size of the ward pantry shall be about
3658 mm × 3658 mm, with a single door opening
21.24 Medication Areas outside in the corridor. The ward pantry shall
have a countertop for packing food. Along with
While designing the nursing station, an area shall it, a sink with hot and cold water shall be avail-
be provided in the shape of the room, or a cup- able. A waste bin has to be kept in the ward pan-
board to keep patient medications in clear plastic try and a trolley for collecting the soiled utensils.
boxes. These boxes are marked with the patient’s A microwave oven may be useful.
name, and the room or bed number of the patient.
A separate box shall be prepared for each patient.
Depending on the requirement, the medicine is Further Reading
taken out of these boxes and given to the patient.
The medication room or the cupboard shall be Brown KK, Gallant D. Impacting Patient Outcomes
lockable. A refrigerator shall also be provided for Through Design: Acuity Adaptable Care/
Universal Room Design. Crit Care Nurs Q. 2006
this medication room. Dec;29(4):326–41.
Choi J-H, Beltran LO, Kim H-S. Impacts of indoor day-
light environments on patient average length of stay
21.25 Equipment Park/Store (ALOS) in a healthcare facility. Build Environ. 2012
Apr 1;50:65–75.
Cullinan K, Wolf M. The Patient Room: what is the ideal
Each nursing station shall be provided with an solution? 60.
equipment storage area, where the less required Design and Management of Negative Pressure Isolation
equipment can be stored. For this, a small room Room for Infectious Disease--《Chinese Journal
of Nosocomiology》2007年12期 [Internet]. [cited
with a size of not less than 2438 mm × 2438 mm 2021 Jun 22]. Available from: https://en.cnki.com.cn/
shall be provided, attached to the nursing station. Article_en/CJFDTotal-ZHYY200712041.htm
This area can be a closed room with a door or Design, Construction and Regulation of the Negative
otherwise open area attached to the nursing sta- Pressure Isolation Room--《Chinese Medical
Equipment Journal》2004年01期 [Internet]. [cited
tion. The room shall have the provision of 2021 Jun 22]. Available from: https://en.cnki.com.cn/
grounded electrical charging points for charging Article_en/CJFDTotal-YNWS200401023.htm
the unused medical equipment. Eijkelenboom A, Bluyssen PM. Comfort and health of
patients and staff, related to the physical environ-
ment of different departments in hospitals: a literature
review. Intell Build Int. 2019 May 18;0(0):1–19.
21.26 Trolley Park Area Griffin CH, Joint Commission, Joint Commission
Resources, Inc, Joint Commission International,
Each nursing station shall be provided with a AIA Academy of Architecture for Health, editors.
Planning, design, and construction of health care
trolley park area for parking wheelchairs and facilities: addressing Joint Commission and JCI stan-
stretches when not in use. dards and other considerations--from planning to
commissioning. Third edition. Oak Brook, IL: Joint
Commission Resources; 2015. 138 p.
Hendrich AL, Fay J, Sorrells AK. Effects of Acuity-
21.27 Ward Pantry Adaptable Rooms on Flow of Patients and Delivery of
Care. Am J Crit Care. 2004 Jan 1;13(1):35–45.
As the patients admitted in rooms/wards have to Hyttinen M, Rautio A, Pasanen P, Reponen T, Earnest GS,
be served full-day diet, there shall be a space for Streifel A, et al. Airborne Infection Isolation Rooms –
A Review of Experimental Studies. Indoor Built
storage of diet and further distribution. This space Environ. 2011 Dec 1;20(6):584–94.
is called Ward Pantry. It is not necessary that the Lee JK, Jeong HW. Rapid expansion of temporary, reli-
diet has to be cooked in the premises; the diet can able airborne-infection isolation rooms with negative
be prepared in the kitchen and then sent to the
Further Reading 239
air machines for critical COVID-19 patients. Am J Room The Effect of Doorway Size on the Negative
Infect Control. 2020 Jul 1;48(7):822–4. Pressure in Airborne Infection Isolation Room. J
New treatment room design model for future hospi- Occup Saf Health. 2010 Sep 15;18:307–19.
tals [Internet]. ScienceDaily. [cited 2021 Jun 22]. Waydhas C, Herting E, Kluge S, Markewitz A,
Available from: https://www.sciencedaily.com/ Marx G, Muhl E, et al. Intermediate care units :
releases/2016/05/160526092743.htm Recommendations on facilities and structure. Med
Plate JDJ, Leenen LPH, Houwert M, Hietbrink Klin Intensivmed Notfallmedizin. 2017 Nov 7;113.
F. Utilisation of Intermediate Care Units: A Systematic Weng C-L, Kau L-J. Planning and Design of a Full-
Review. Crit Care Res Pract. 2017;2017:8038460. Outer-Air-Intake Natural Air-Conditioning System for
Smith TJ. Occupancy and patient care quality benefits Medical Negative Pressure Isolation Wards. J Healthc
of private room relative to multi-bed patient room Eng. 2021 Mar 26;2021:e8872167.
designs for five different children’s hospital inten- Zhang Y, Han O, Li A, Hou L, Olofsson T, Zhang L, et al.
sive and intermediate care units. Work. 2016 Jan Adaptive wall-based attachment ventilation: A com-
1;54(4):853–72. parative study on its effectiveness in airborne infection
Stichler JF. The New Standard: Single Family Room isolation rooms with negative pressure. Engineering
Design. JONA J Nurs Adm. 2012 Oct;42(10):447–50. [Internet]. 2021 Jan 23 [cited 2021 Jun 22]; Available
Tsao T, Chang cheng-ping, Chuang C-Y, Juang Y-J, Lin from: https://www.sciencedirect.com/science/article/
S-J, Dai Y-T. The Effect of Doorway Size on the pii/S2095809921000059
Negative Pressure in Airborne Infection Isolation
Radiology
22
Radiology is the department that uses medical ing techniques, and the treatment part is left to
imaging to diagnose and treat diseases. There are the physicians. Here, diagnostic imaging helps
a variety of imaging techniques upon which physicians to accurately diagnose a disease.
imaging modalities are based: Therapeutic Radiology is a science where in
addition to diagnosis, the treatment part is also
1. X-Ray based taken care of, for example peripheral shunting.
2. Ultrasound Waves based Interventional radiology is a part of therapeutic
3. Magnetic Fields based radiology, which allows performing (usually
4. Nuclear Medicine based minimally invasive) medical procedures with the
guidance of imaging technologies.
Imaging modalities based on these techniques
are:
1. X-ray Radiography 22.2 Location of the Radiology
2. Ultrasound Machines Department
3. Computed Tomography (CT)
4. Magnetic Resonance Imaging (MRI) Radiology services are often used by:
5. Mammography Imaging
1. OPD
6. Nuclear Positron Emission Computed
2. Emergency
Tomography (PET CT)
3. IPD
7. Nuclear Positron Emission Magnetic
4. ICU
Resonance Imaging (PET MRI)
5. Operating Rooms
8. SPECT CT
9. Cyclotron/Radio Pharmacy It is essential to understand that the depart-
10. Densitometer, Bone ment is at a place which is easy and convenient
11. Digital Subtraction Angiography (DSA) for patients to access. Importantly, it shall have
adequate facilities to ensure protection from
radiation exposure and does not interfere with the
22.1 Diagnostic vs Therapeutic working of the other departments. Hence, it is
Radiology better if the department is located on the ground
floor. The second justification is, as the flow to
Diagnostic Radiology is a science where a dis- this department is more, it has to be in a fast-
ease is diagnosed with the help of various imag- moving zone. The radiology department shall be
© The Author(s), under exclusive license to Springer Nature Singapore Pte Ltd. 2022 241
A. Garg, A. Dewan, Manual of Hospital Planning and Designing,
https://doi.org/10.1007/978-981-16-8456-2_22
242 22 Radiology
near the OPD complex, emergency department X-ray Radiography Rooms for DR
and Intensive Care Units. or X-Ray Machine
As X-rays are hazardous, and most of the Radiography Room IITV
System and Fluoroscopy
machines are based on X-Ray technology, ade-
Room for 60 mA Mobile
quate protection has to be given to the public. X-Ray System
The protection has to be to an extent where the Change Rooms
rays shall not penetrate out of the walls of the Sub-waiting
machine room. If we talk about CT Scans, PET Patient Preparation Room
CT, DSA and Radiotherapy, the radiation dose CR Room
rate is much higher and harmful to the public. Ultrasound Ultrasound Room
Thus, it is reasonable to locate radiology depart- Change Room
ment in the basement, so that the outside radia- Toilets
Sub-waiting
tion can be protected as beyond the outer wall
CT Scan Examination Room
there will only be soil, and any penetrating rays
Control Room
will be absorbed by it. UPS room
While designing the department of radiol- Change room
ogy, special care shall be taken about the size of Store
the corridors. Corridor dimensions (clear width Sub-waiting
and height) should be sized to permit the move- MRI Examination Room
ment and installation of all pieces of the equip- Control Room
ment. If the size of the corridors and the corners UPS room
are not well planned, it will create a big prob- Machine Room
Change room
lem to transport the equipment to the respective
Store
point of installation. The route of transport of Sub-waiting
equipment shall be well planned at the time of Mammography Examination Room
designing the spaces. If need be, the sizes, Change room
weight and space required for transport, shall Store
be checked from the manufacturers of the Sub-waiting
equipment. DEXA Scan Examination Room
Sub-waiting
PET CT/MRI Scan/ PET CT Room
SPECT CT
22.3 Infrastructure on Centralized PET MRI Room
SPECT CT Room
Radiology Department
Console Rooms for all
machines
The Department of Radiology consists of the UPS rooms
following: Machine Panel Rooms
Utility Area Reception and Enquiry Technologist Room
Registration Physician Consultation Room
Record Room Post-drug Administration
Reporting Room Holding cubicles
Store for unused films and Active Toilet
Related material Dose administration Room
Store for used films Hot Lab cum Radio
Public Utility for Faculty Pharmacy Room
Public Utility for Patients and Radioactive Store
Attendants Medicine Preparation Room
Report Delivery Room Radioactive waste Room
Sub waiting Change room
Extra Rooms for Future General Store
expansion Sub-waiting
22.5 Utility Area 243
ing lobbies, to make it comfortable for patients where. LCDs can be provided at various loca-
and attendants to wait. Now post-COVID-19, the tions across the hospital, wherein a token
waiting areas will have to be planned carefully holder can see the status of his/her token num-
and designed to create a greater physical separa- ber. We can even use advanced technology
tion between people with appropriate queuing. like SMS service, which will be sent to the
Few suggestions for doing so are: mobile number of the token holder as and
when his/her token number arrives.
1. The foremost principle to be followed is that
individual seats shall be provided to maintain
social distancing. 22.5.4 Reporting Room
2. Sub-waiting lobbies
It is recommended that instead of a single Most of the hospitals have a central reporting
large waiting lobby, sub-waiting lobbies shall room, where reporting of all the modalities is
be designed for each imaging modality. For done. The size of the room will depend on the
example, MRI shall have a different sub- number of people to be accommodated in the
waiting area and CT scan shall have another room at a particular time, but ideally, it shall not
sub-waiting area. However, such measures be less than 6096 mm × 4572 mm. The room
may not be practical in all situations, espe- shall be provided with a required set of comput-
cially for small healthcare facilities, nursing ers and printers, sufficient tables and comfortable
homes, clinics etc. The number of people who chairs. Wall-mounted big-size view boxes
can be allowed to wait in hospital lobbies may (maybe up to four films) shall also be provided to
be limited to a certain maximum with a spe- examine the films. The room shall have space for
cific spacing between their seats. So, future a typist to sit.
waiting lobbies could be smaller in size and Most importantly, all computers shall be con-
scattered across the department. nected to PACS (Picture Archiving and
3. Minimize Interaction with others Communication System) through a secured net-
Trends like self-check-in and self-rooming work. PACS is a medical imaging software to
will accelerate to minimize interactions with communicate and transfer images either through
other people. The concept of a smaller enclave a closed network or through the Internet. The
waiting space that separates the sick from images of all the modalities of radiology (except
other patients or visitors will be preferred. Ultrasound) are archived and stored in a separate
The seating has to be in clusters of small num- server, called PACS server. When required, the
bers of chairs, say 2–3 chairs per cluster. images can be retrieved anywhere either for
Further, each cluster shall be portioned from reporting by radiologists or for diagnosis by the
the other with a 1524-mm acrylic or glass par- physicians.
tition to reduce exposure with other patients/
visitors.
4. Outside waiting 22.5.5 Stores for Unused
Patients and families shall be encouraged Consumables and Films
to wait outside or in their car, instead of wait-
ing in the lobby. The department has to be ready for investigation
5. Adopting a Token system round the clock. Therefore, it is essential to
To reduce the crowd in waiting lobbies, a always have ample stock of consumables and
token system shall be introduced. With this films, and for this, the department needs a store.
system, the patient or visitor is issued a token This store shall be of the size of
at the time of registration, so that they are well 3658 mm × 3658 mm, but depending on the num-
aware of their turn, and need not wait in the ber of items, the size may vary. The store needs to
lobby near the service room, but can wait else- have a sufficient number of countertops, cup-
22.6 X-Ray Zone 245
boards and drawers. It is highly recommended acrylic sheet of about 914 mm height shall be
that for storage of films (as films are highly provided to protect staff from infectious diseases.
inflammable), a fireproof cabinet is provided. On the back wall of the counter, proper pre-
The light switch of such a store shall be given numbered bins shall be provided to keep the
outside the room and a single light shall be pro- reports ready for delivery.
vided, to avoid the chances of fire caused by
sparks. The temperature of the room shall be
between 17 and 21 °C, and it shall not have any 22.6 X-Ray Zone
window or other source of direct sunlight.
This zone of the radiology department is related
to X-rays and X-ray-related investigations and/or
22.5.6 Stores for Used Films procedures, including fluoroscopy. As X-rays are
and General Items harmful, special care has to be taken while
designing the investigation rooms. This zone
At times the department needs to store exposed includes the following:
films, particularly those related to medico-legal
cases or interesting cases for studies and refer-
ences. Apart from this, waste films and other 22.6.1 Radiography Rooms
items like machine accessories also need to be
stored. Thus, there shall be a dedicated space for These are the actual rooms where the X-ray
storing such items. This store shall be of the size machine is installed, and the exposure of X-rays
of 3658 mm × 3658 mm, but depending on the is given to the patient. As far as the number of
number of items, the size may vary. The store radiography rooms is concerned, it depends on
needs to have a sufficient number of countertops, the number of machines required to be installed
cupboards and drawers. It is highly recommended at once, and also on the plans of adding more
that for storage of films (as films are highly machines. There are different varieties of
inflammable), a fireproof cabinet is provided. machines starting from conventional X-ray
The light switch of such a store shall be given machines to Digital Radiography (DR) machines.
outside the room and a single light shall be pro- Further, the capacity of the machine may vary
vided, to avoid the chances of fire caused by from 60 mA to 1000 mA. Also, X-ray tables are
sparks. The temperature of the room shall be available in a wide variety starting from fixed
between 17 and 21 °C, and it shall not have any tables to multi-positional motorized tables
window or other source of direct sunlight. (Fig. 22.1).
Some of the important points related to the 11. A warning light (red colour bulb) shall be
designing of the radiography rooms are as provided outside the door. This light must be
follows: connected to the generator in a way that it
illuminates only during the tube activation.
1. Before designing the radiography rooms, the 12. The chest stand or the chest frame can be
guidelines and norms of the controlling fixed on the wall opposite to the entrance
authority of the country must be taken into door and the control console.
account. e.g. in India, Baba Atomic Research 13. A shielded barrier should be placed at the
Institute issues all such norms and X-ray control console to protect the staff
guidelines. from radiation exposure.
2. A separate room shall be provided for each 14. Depending on the machine capacity, the
machine. power load required by the machine shall be
3. Irrespective of the types of machines and calculated, and the main switch and cable
tables, the size of the radiography rooms shall be separately terminated in each radi-
remains the same. ography room.
4. A rectangular room is suggested, and the size 15. If a Digitalized Radiography (DR) type of
of the room shall not be less than 25 sq.m. machine is planned, then a separate small
5. All the walls of the room shall be at least control room, adjoining the DR room shall
229 mm thick, with plaster on both sides. be provided. Between the two rooms, a lead
The ideal thickness for the primary wall of glass shall be fixed in a wooden frame with a
an X-ray room is at least 250 mm solid baked 2-mm lead lining.
clay bricks, and 150 mm mortar/concrete 16. Lighting shall be provided using normal
walls for plain radiography. Hollow bricks LED, with sufficient lumen. No extra illumi-
should be plastered with a thickness of 6 mm nation is required in the room.
barium plaster and should be protected up to 17. The temperature in the room shall range
2200 mm from the floor level. between 18 and 21 °C, and the humidity level
6. No single wall dimension of the X-ray room shall not be more than 60%. Before finalizing
shall be less than 4 m. the humidity level or temperature, environ-
7. Flooring can be of tiles/marble/granite, but it mental requirements shall be confirmed with
shall not be slippery to avoid accidents and the equipment supplier, as some machines
injury to the patient. may require varied environmental standards.
8. The room shall have a single door with a 18. All machines shall have proper ground earth-
width of about 1524 mm, to ease the move- ing provisions.
ment of trollies. 19. A stand with heavy-duty hangers shall be
9. The door should be at least 1500 mm long provided outside all rooms to hang the lead
and 2000 mm high. The door and its frame apron.
need to have a 2-mm thick lead lining. There 20. A cabinet shall be provided in each room to
shall be no leakage of the radiation from the keep other radiation safety devices like lead
door. Doors should overlap by a minimum of gloves, lead goggles, groin guards and lead
100 mm on each side when closed. The over- collar.
lap requirement applies to flap doors that
make a single entrance door but close from a
different side. Doors should have handles 22.6.2 Room for Mobile X-Ray
and locks, both on the inside and on the out- System
side so that they are always closed during
exposure and access can be controlled. Usually, hospitals have mobile X-ray units for
10. Windows are not allowed in the radiography bedside X-ray of immobile patients. These
room. machines are generally placed in the units where
22.7 Ultrasound Zone 247
they are required, but in some hospitals, they are Radiographer can then modify the image param-
centrally located in the department of Radiology. eters, followed by printing the image on a film.
Therefore, a store shall be provided in the depart- The size of the CR room shall be about
ment for storing these machines. Size-wise, the 4267 mm × 3658 mm. The room shall have a
store can be 3658 mm × 3658 mm, but the size countertop or table to keep the CR system or
can be increased depending on the number of alternately it can be placed on a wooden table.
machines. Although a countertop is better as the unit can
generate vibrations on a wooden table. For a PC,
a table with chair is required. The camera can
22.6.3 Change Rooms either be a tabletop model or a floor model. If it is
a tabletop model, it can be placed on both the
Patients often need to change clothes before countertop and the table. But if it is a floor model,
entering the X-Ray room as the clothes may have a small foundation shall be required. The tem-
some metal parts which shall disturb the imaging. perature in the room shall be about 18–21 °C and
Hence, change rooms are provided in the depart- the RH shall be 40–50%. Lighting shall be nor-
ment to enable the patient to remove all outside mal as in other rooms.
clothes and change to a hospital dress. The room
shall be approximately 3048 mm × 3048 mm in
size. It shall have an adequate provision of per- 22.6.6 Sub-waiting for Radiography
sonal lockers to keep patient belongings. Also,
hooks, hanger rod and hangers shall be provided Shall be the same as for the Utility area.
to hang clothes. There shall be a cabinet to keep
sterilized dresses.
22.7 Ultrasound Zone
rails fixed on the ceiling. The temperature in the of adding more machines. The CT Scan machines
room shall be about 18–22 °C and the RH shall be are available in different configurations, but irre-
50%. The light of the room shall be dimmable. spective of it, the design and size of the room
shall remain the same. The machine comes with a
long slide table (Fig. 22.2).
22.7.2 Change Rooms Some of the important points related to the
designing of the CT rooms are as follows:
At times, a patient’s cloth makes it difficult to
perform an ultrasound. Hence, change rooms are 1. Before designing the CT Scan room, the
provided in the department to enable the patient guidelines and norms of the controlling
to remove all outside clothes and change to a hos- authority of the country must be taken into
pital dress. The room shall be approximately account. e.g. in India, Baba Atomic Research
3048 mm × 3048 mm in size. It shall have an Institute issues all such norms and
adequate provision of personal lockers to keep guidelines.
patient belongings. Also, hooks, hanger rod and 2. A separate room shall be provided for each
hangers shall be provided to hang clothes. There machine.
shall be a cabinet to keep sterilized dresses. 3. If the machine is to be installed horizontally,
a rectangular room shall be designed. If the
machine is to be installed diagonally, a
22.7.3 Toilets square room design would be better.
However, we suggest installing the machine
Each Ultrasound room shall have an attached toi- horizontally, in a rectangular room. In this
let. This is required as some of the scans need to case, the room space shall not be less than
be done post void, particularly the ultrasound of 42 sq.m, and the room size shall be
the lower abdomen. The toilet shall have a WC, 9144 mm × 4572 mm.
urinal and washbasin. Exhaust must be given in 4. All the walls of the room shall be at least
the toilet. 229 mm thick, with plaster on both sides.
The ideal thickness for the primary wall of
an X-ray room is at least 250 mm solid baked
22.7.4 Sub-waiting for Ultrasound clay bricks, and 150 mm mortar/concrete
walls for plain radiography. Hollow bricks
Shall be the same as for Utility area. should be plastered with a thickness of 6 mm
barium plaster and should be protected up to
2200 mm from the floor level.
22.8 CT Scan Zone 5. Flooring can be of tiles/marble/granite, but it
shall not be slippery to avoid accidents and
This zone of the radiology department is related injury to the patient.
to the Computerized Tomography. This machine 6. It is advised to provide Air Interlocks by
is also X-ray based and very high doses of X-Rays placing an additional door before the CT
are produced when exposure is given. Hence spe- room door.
cial care has to be taken while designing the CT 7. The CT room shall have a single door with a
Room. This zone includes the following: width of about 1524 mm, to ease the move-
ment of trollies.
8. The door shall have to be with a proper 2 mm
22.8.1 CT Scan Machine Room thick lead lining. The lining has to be done
even on the door frame. There shall be no
As far as the number of CT rooms is concerned, leakage of the radiation from any place in the
it depends on the number of machines required to door. Doors should overlap by a minimum of
be installed at once, and also on the future plans 100 mm on each side when closed. The door
22.8 CT Scan Zone 249
should be at least 1500 mm long and calculated, and the main switch and cable
2000 mm high. The overlap requirement also shall be separately terminated in each CT
applies to flap doors that make a single Scan room.
entrance door but closing from different 13. As the weight of the machine is more and the
sides of the door. The door should have han- movement of the machine is very fast, it is
dles and locks on the inside and the outside advised to check the weight-bearing capacity
so that they may always be closed during of the floor. If needed, provide a foundation
exposures thus controlling access. for the machine as per the suggestions of the
9. Windows are not allowed in the CT Scan machine manufacturer.
room. 14. The equipment should be mounted on a base
10. A warning light (red colour bulb) shall be plate only with desired mounting anchor fas-
provided outside the door. This light must be teners as specified by the manufacturer of the
connected to the generator in a way that it equipment.
illuminates only during the tube activation. 15. Any shortcuts will result in vibrations of the
11. While installing the machine, care shall be unit during its operation and compression
taken to leave at least 1829 mm space behind artefacts in the image, resulting in poor
the machine for the Gantry of the machine to image quality, repetition in diagnostic tests
tilt, and for easy maintenance of the machine. and leading to eventual reinstallation of the
The machine shall be installed in the centre unit.
of the width of the room. 16. Lighting shall be provided using normal
12. Depending on the machine capacity, the
LED, with sufficient lumen. No extra illumi-
power load required by the machine shall be nation is required in the room.
250 22 Radiology
CT Scan room. For better protection of these pan- example, a room size of 0.25T MRI shall be
els, it is advised to install these panels in a differ- small as compared to the 1.5T MRI, and it will be
ent room or enclosure, which is attached to the even more for a 3T MRI. The MRI machine
CT Scan room. Hence, such an area shall be comes with a long slide table (Fig. 22.3).
designed after consulting the equipment manu- Some of the important points related to the
facturer. The size and temperature etc. shall be designing of the MRI rooms are as follows:
confirmed by the manufacturer of the machine.
1. A separate room shall be provided for each
machine.
22.8.5 Change Rooms 2. Magnetic field safety applies to MRI instal-
lations. Care should be taken to shield the
Patients often need to change clothes before magnet and procedure room from external
entering the CT room as the clothes may have magnetic interference, ensuring magnetic
some metal parts which shall disturb the imaging. fields specified are not exceeded.
Hence, change rooms are provided in the depart- 3. RF Shielding
ment to enable the patient to remove all outside MRI systems are highly sensitive to radio
clothes and change to a hospital dress. The room frequencies. Therefore, the MRI machine is
shall be approximately 3048 mm × 3048 mm in enclosed in an RF shield. It is essentially a
size. It shall have an adequate provision of per- six-sided copper-lined box around the room
sonal lockers to keep patient belongings. Also, called ‘Faraday Cage’ which protects the
hooks, hanger rod and hangers shall be provided MRI system from exterior radio frequencies
to hang clothes. There shall be a cabinet to keep for the clarity of scan. RF shielding can also
sterilized dresses. be done with the galvanized steel and alu-
minium, but copper is considered to be the
best. The footprint for the RF shield is set by
22.8.6 Sub-waiting for CT Scan the designer during the designing process.
Also, the design of the RF shield has to be
Shall be the same as for Utility area. checked with the vendor, to establish where
things like ductwork, conduits, plumbing
and others, penetrate the shield.
22.9 MRI Zone RF shields often require three partitions,
including the parent wall, RF shield wall,
This zone of the radiology department is related and interior finishing wall. Parent wall means
to Magnetic Resonance Imaging. As this machine the brick or concrete wall already built. RF
has a strong magnetic field, special care has to be Shield is the actual metallic sheet, and the
taken while designing the MRI rooms. This zone inner finishing is the artificial decorative
includes the following: interior. The inner interior can be done using
wallpapers, wooden or PVC panels.
The floor in MRI exam room often
22.9.1 MRI Machine Room requires a structural subfloor, RF shielding, a
protective layer and other finishing materi-
As far as the number of MRI rooms is concerned, als. Subfloor means the originally con-
it depends on the number of machines required to structed floor, then the metallic cage, and
be installed at once, and also on the future plans then the protective layer. This layer can be
of adding more machines. The MRI machines are made of wood, as it does not affect the mag-
available in different configurations, and depend- netic field.
ing on the configuration of the machine, the An RF shield ceiling is often suspended
design and size of the room shall change. For from the structural deck overhead. Any ser-
252 22 Radiology
vices that pass above the MRI scanner room from the iso-centre to the 5-gauss line is dan-
(power, piping, cabling and ductwork) gerous for anyone wearing ferrous metal, or
should do so in the plenum above the RF for any metal objects. Anything metal within
shield ceiling. Items that penetrate into the the 5-gauss line will essentially become a part
RF shield enclosure will require special fit- of the magnet. To avoid this and keep every-
tings and materials to maintain the shield one safe, designers intentionally design barri-
integrity. RF filters and waveguides are com- ers to deter people from getting too close.
mon materials used at the shielding feed- Pacemakers, cell phones and credit cards are
through points. The bottom of the ceiling can severely damaged when inside the 5-gauss
be decorated with LED lights or 3D illumi- line.
nated sceneries. 5. Maintain the desired minimum clearances
The window between the magnet room from the objects, such as water-cooling sys-
and control/console room usually requires tems, wheelchairs, carts, transformers, over-
RF shielding, which is often two layers of head power lines and vehicles including cars,
copper screens or perforated sheets. as specified in the installation prerequisites
4. The next thing a hospital needs to consider supplied by the manufacturer to ensure
when designing an MRI suite is protecting the trouble-free performance of the magnet. If
public from a high magnetic field. Designer accidentally it is taken near the magnet, the
shall work with MRI vendors to establish a machine will pull it with a tremendous force,
precise location of the iso-centre of the mag- which can either damage the machine or
net. From there, they design protective provi- cause injury to the patient.
sions to keep the public away from the most 6. In an event of such an emergency, the
dangerous magnetic fields. Imagine an invisi- machine may have to be stopped by pushing
ble shield radiating out from the magnet’s iso- the emergency stop button. If this is done, the
centre. This is called the Gauss Field. Distance magnet will quench, which means is the sud-
22.9 MRI Zone 253
den loss of superconductivity in the magnet. special lights made of non-ferrous material
A cryogen vent is required to be able to expel for MRI room.
the super-cooled helium gas that the MRI 17. The temperature in the room shall range
uses. There is a huge expense behind reviv- between 18 and 21 °C, and the humidity
ing the machine in such cases. level shall not be more than 40%. Before
7. It is advised to provide Interlocks before finalizing the humidity level or temperature,
entering the MRI room. This can be done by environmental requirements shall be con-
providing another door before the MRI room firmed with the equipment supplier, as some
door. machines may require varied environmental
8. The size of an MRI room shall depend on the standards.
size of the RF cage. It is advised that while 18. All machines shall have proper ground earth-
finalizing the configuration of the machine, a ing provision.
bigger-sized RF cage shall be taken if space 19. Inside the room, a cabinet made of wood,
allows. The designer shall take a specifica- Polycarbonate or other non-ferrous material
tion of the room sizes from the vendor before has to be provided. This is required to store
planning the MRI room. the MRI coils and any other non-ferrous
9. All the walls of the room shall be at least material.
229 mm thick, with a plaster on both sides. 20. The MRI room needs the following outlets
10. The room shall have a single door, made for medical gas supply: one outlet for
from a material that does not interfere with Oxygen, one for Vacuum and one for Air.
the magnetic field, and it must be a sealed However, these outlets cannot be given
door. The size of the door shall be verified directly in the room; instead, they are given
from the vendor of the machine. in the RF cage, from where a rubber tube is
11. Windows are not allowed in the MRI room. provided inside the MRI room up to the
12. While installing the machine, care shall be patient table.
taken to leave at least 1829 mm space behind 21. The proper two-way audio system shall be
the machine for the MRI Table to move provided in the MRI room, so that the patient
behind and for easy maintenance of the can be directed by the technician sitting in
machine. The machine shall be installed in the control room, without entering the MRI
the centre of the width of the room. room.
13. As the weight of the machine is more, it is
advised to check the weight-bearing capacity
of the floor. If needed, provide a foundation 22.9.2 MRI Control Room
for the machine as per the suggestions of the
machine manufacturer. Attached to the MRI Scan room, a control room
14. The equipment should be mounted on a base has to be provided. While the procedure is going
plate only with desired mounting anchor fas- on, no person shall be allowed to enter the
teners as specified by the manufacturer of the machine room. All controls shall be done from
equipment. the control room only. The size of this room shall
15. Any shortcuts will result in vibrations of the be 3658 mm × 3658 mm. It shall be provided
unit during its operation and compression art with a table to install the Control Unit of the
facts in an image, resulting in poor image machine. This table is usually supplied along
quality, repetition in diagnostic tests, leading with the machine. Apart from this, there shall be
to eventual reinstallation of the unit. the provision of a secondary computer for trans-
16. Lighting shall be provided using normal
ferring the MRI images, for preparing reports.
LED, with sufficient lumen. However, ordi- Some hospitals have a separate reporting room.
nary light fittings are not allowed. There are In that case, the space for a secondary computer
is not required in the control room. A meshed
254 22 Radiology
glass (provided with the machine) of about connected to the machine. These panels control
1200 mm × 1000 mm shall be fixed in a wooden the working of the machine but are not directly
frame with a 2-mm lead lining between the MRI needed in the MRI room. For better protection of
room and the control room to ensure no leakage these panels, it is advised to install these panels in
of the radiation. A camera (printer) shall also be a different room or enclosure, which is attached
provided in the Control Room to print MRI films. to the MRI room. Hence, such an area shall be
designed after consulting the equipment manu-
facturer. The size and temperature etc. shall be
22.9.3 UPS Room confirmed from the manufacturer of the machine.
in size. It shall have an adequate provision of 4. All the walls of the room shall be at least
personal lockers to keep patient belongings. Also, 229 mm thick, with plaster on both sides.
hooks, hanger rod and hangers shall be provided The ideal thickness for the primary wall of
to hang clothes. There shall be a cabinet to keep an mammography room is at least 250 mm
sterilized dresses. solid baked clay bricks, and 150 mm mortar/
concrete walls for plain radiography. Hollow
bricks should be plastered with a thickness of
22.9.7 Sub-waiting for MRI 6 mm barium plaster and should be protected
up to 2200 mm from the floor level.
Shall be the same as for Utility area. 5. No single wall dimension of the mammogra-
phy room shall be less than 3000 mm.
6. Flooring can be of tiles/marble/granite, but it
22.10 Mammography Zone shall not be slippery to avoid accidents and
injury to the patient.
This zone of the radiology department is related 7. The room shall have a single door with a
to the X-ray of breasts for females. As this is also width of about 1000 mm.
an X-ray-based machine, hence care has to be 8. The door should be at least 1000 mm long
taken while designing the mammography room. and 2000 mm high. The door and its frame
This zone includes the following: need to have a 2-mm thick lead lining.
There shall be no leakage of the radiation
from the door. Doors should overlap by a
22.10.1 Mammography Rooms minimum of 100 mm on each side when
closed. The overlap requirement applies to
Mammography rooms are the actual room where flap doors that make a single entrance door
the mammography machine is installed, and the but closes from a different side. Doors
exposure of X-rays is given to the patient. As far should have handles and locks, both on the
as the numbers of mammography rooms are con- inside and on the outside so that they are
cerned, generally one is sufficient, but the always closed during exposure and access
designer has to take into account the future plans can be controlled.
as well. 9. Windows are not allowed in the mammogra-
Some of the important points related to the phy room.
designing of the mammography rooms are as 10. A warning light (red colour bulb) shall be
follows: provided outside the door. This light must be
connected to the generator in a way that it
1. Before designing the radiography rooms, the illuminates only during the tube activation
guidelines and norms of the controlling 11. A shielded barrier should be placed at the
authority of the country must be taken into mammography control console to protect the
account. e.g. in India, Baba Atomic Research staff from radiation exposure.
Institute issues all such norms and 12. Depending on the machine capacity, the
guidelines. power load required by the machine shall be
2. A separate room shall be provided for each calculated, and the main switch and cable
machine. shall be separately terminated in each mam-
3. The room can either be a rectangular or mography room.
square room as designed by the designer and 13. Lighting shall be provided using normal
the size of a room shall not be less than LED, with sufficient lumen. No extra illumi-
10 sq.m. nation is required in the room.
256 22 Radiology
6. The room shall have a single door with a 16. A cabinet shall be provided in each room to
width of about 1000 mm. keep other radiation safety devices like lead
7. The door should be at least 1000 mm long gloves, lead goggles, groin guards and lead
and 2000 mm high. The door and its frame collar.
need to have a 2-mm thick lead lining.
There shall be no leakage of the radiation
from the door. Doors should overlap by a 22.11.2 Sub-waiting for DEXA Scan
minimum of 100 mm on each side when
closed. The overlap requirement applies to Shall be the same as for Utility area.
flap doors that make a single entrance door
but closes from a different side. Doors
should have handles and locks, both on the 22.12 PET CT/MRI Zone
inside and on the outside so that they are
always closed during exposure and access This zone of the radiology department is related
can be controlled. to the Positron Emission Tomography (PET)
8. Windows are not allowed in the DEXA scan scanners with the fusion of morphological
room. imaging in the form of CT or MRI. This inte-
9. A warning light (red colour bulb) shall be grated system is called PET CT and PET
provided outside the door. This light must be MRI. Hence, we have to design the facility to
connected to the generator in a way that it incorporate the basic infrastructure of CT and
illuminates only during the tube activation. MRI, and also the requirements and regulations
10. A shielded barrier should be placed at the of the PET Scanner, in which nuclear isotopes
DEXA scan control console to protect the are used.
staff from radiation exposure. As the hot area consisting of the cyclotron and
11. Depending on the machine capacity, the
the radiopharmacy areas are the same, it is rec-
power load required by the machine shall be ommended that both the PET CT and PET MRI
calculated and the main switch and cable shall be installed in the same area. With such an
shall be separately terminated in each DEXA arrangement, we can save a lot of space in the
scan room. department.
12. Lighting shall be provided using normal
As far as the number of PET CT and PET MRI
LED, with sufficient lumen. No extra illumi- is concerned, usually one machine each is installed,
nation is required in the room. but the designer shall also take into account the
13. The temperature in the room shall range
future expansion plans of the hospital.
between 18 and 21 °C, and the humidity
level shall not be more than 60%. Before
finalizing the humidity level or temperature, 22.12.1 Location of the Zone
environmental requirements shall be con- in Hospital
firmed with the equipment supplier, as some
machines may require varied environmental As the PET area is a high positron emitter, it is
standards. essential to provide proper shielding and safety
14. All machines shall have proper ground earth- mechanisms like reinforced cement concrete
ing provisions. (RCC) walls. Hence, it is advised to locate this
15. A stand with heavy-duty hangers shall be zone in the basement, as the room will be sur-
provided outside all rooms to a hang the lead rounded by soil, which will reduce the risk of
apron. emission outside the zone.
258 22 Radiology
The infrastructure of this zone includes As technology changed, SPECT came into the
(Fig. 22.4): picture. It can capture images by cutting slices of
the parts to be investigated. The infrastructure of
PET CT/PET MRI/ PET CT Room
the machine room shall be the same as a normal
SPECT CT PET MRI Room
CT or PET CT machine room.
SPECT CT Room
Console Rooms for all
machines
UPS rooms 22.12.5 Operating Console Rooms
Machine Panel Rooms
Technologist Room For each imaging modality, a separate console
Physician Consultation Room room shall be provided. Therefore, a wall sepa-
Post-Drug Administration rating the console room from the PET CT scan-
Holding cubicles
ner, PET MRI and SPECT CT room shall be
Active Toilet
Dose administration Room provided. This shall be a 300-mm-thick RCC
Hot Lab cum Radio-pharmacy wall with a 4-mm lead equivalent glass window.
Room Before planning the rooms for PET CT, PET
Radioactive Store MRI and SPECT CT, it is essential to meet the
Medicine Preparation Room requirements and room specifications such as
Radioactive waste Room weight-bearing capacity, temperature stability,
Change room
adequate power supply, as well as the issues con-
General Store
cerning radiation safety, as advised by the
Sub-waiting
machine manufacturer.
Fig. 22.4 Sample layout drawing of PET CT/PET MRI/Gamma Camera Zone
nation he/she is undergoing. This room shall be room which opens in the radiopharmacy. The
close to the waiting room and adequately patients are made to sit in the injection room and
equipped. The outlets for the supply of oxygen the staff prepares the injection in the adjoining
and vacuum shall be provided. The size of this radiopharmacy room. Through this aperture, the
room shall be about 4267 mm × 4572 mm. radiopharmaceutical is injected into the patient.
This room shall roughly be 12–16 sq.m for each
22.12.6.4 Store PET CT/PET MRI/SPECT CT installed. Patients
A small store of size 3658 mm × 3658 mm shall after injection are a relatively intense source of
be provided to store the materials like QC phan- radiation (of the order of 30–50 μSv/h per patient
toms, consumables and disposables. The room at 1000 mm just after the administration).
shall be provided with the worktops, cabinets and
drawers for storage. 22.12.7.3 Post-dose Waiting Area
The injected patient is then made to wait in the
22.12.6.5 Technologist Room post-dose waiting area, where he/she can rest
A technologist room cum office shall be located comfortably during the uptake period. The walls
near or opposite to the physician consultation of post-dose waiting area are made up of 300-mm-
room for planning the investigation and arrang- thick RCC, resulting in an exposure rate of about
ing resources for the department. 1.22 uSv/h (for a patient injected with 300 MBq
of 18F radiopharmaceutical at a distance of about
1000 mm). The assembly of several patients in
22.12.7 High-Risk Areas or Radiation the uptake room area is a radiation protection
Exposure Hot Areas problem that should not be overlooked; ensure
proper positioning and shielding of the uptake
22.12.7.1 H ot Lab Cum rooms.
Radiopharmacy Room
This room is required when the department has
its own production unit (cyclotron and radio- 22.12.8 Toilet
chemistry lab). This allows for mono-dose
syringes to be delivered to each injecting room in
After injection and an uptake period depending
lead containers. The walls of the room shall be on the protocol, patients are asked to void their
300 mm thick RCC. bladder before starting the actual PET scan pro-
cedure. Hence, a toilet must be located adjacent
22.12.7.2 Injection Room to the Post Dose Waiting Area. The discharge of
An injection room is constructed with a 220-mm- this toilet is taken in a separate settlement tank
thick RCC wall. An aperture is provided in this where it is allowed to settle down and the effects
260 22 Radiology
A ‘Clinical Laboratory’ is a place where clinical diagnosis based on a study of the individual as
pathology tests are carried out on clinical speci- a whole.
mens to obtain information about the health of a The Clinical Laboratory of a hospital should
patient to aid in diagnosis, treatment and preven- have the following sections:
tion of disease. Clinical Pathology Anatomical Pathology
The efficiency of the hospital to a large Clinical Pathology
extent depends on the promptness and accuracy Cytopathology
of the reports of pathological investigations. Derma Pathology
The clinical laboratory is one of the main inves- Forensic Pathology
tigative services of the hospital and should lend Hematopathology
Histopathology
wholehearted support to the clinical services. In
Molecular Pathology
the hospitals it is also termed as the ‘LAB’.
Neuropathology
The laboratory provides the facilities to Oral and Maxillofacial Pathology
apply scientific techniques to the diagnosis and Pulmonary Pathology
control of disease and for scientific investiga- Renal Pathology
tions of clinical phenomena associated with a Surgical Pathology
disease. Hence, this department should be well Toxicology
designed and supervised to assure it is being Biochemistry Cell Biology
used to the greatest advantage. Pathology labo- Clinical Biochemistry
ratory examinations are invaluable in support- Enzymology
Genetics
ing and supplementing clinical findings, but a
Immunology
diagnosis by the laboratory which deals with Metabolism
only selected functions of the human body Molecular Biochemistry
must never be allowed to replace the clinical
© The Author(s), under exclusive license to Springer Nature Singapore Pte Ltd. 2022 263
A. Garg, A. Dewan, Manual of Hospital Planning and Designing,
https://doi.org/10.1007/978-981-16-8456-2_23
264 23 Clinical Laboratories
testing a blood sample for DNA markers from ment prefer a separate enclosure for auto-
specific organisms can produce results in an mated and sophisticated machines to
afternoon, rather than overnight or over several maintain a better dust-free environment.
days. Based on specific genetic markers in the Under such circumstances, partitions of glass
sample, technicians can determine what type of or aluminium can be designed.
bacteria, virus or parasite is present and whether 5. All the walls of the laboratory room shall be
or not it’s carrying, say, the genes for amoxicillin at least 9-in.-thick with plaster on both sides.
resistance. 6. Flooring
The floor must be non-porous and stain
proof. It is recommended that floor tiles of
23.9 Laboratories large size, like 600 mm × 600 mm, shall be
used. The only condition is that there shall
All the laboratories, i.e. Biochemistry, be no spaces between the tiles, which means
Microbiology and Pathology (including the sub- the tiles shall be joint less. Otherwise,
divisions of these labs) have common norms for optionally granite can be used as it is a hard
designing and construction except a few specifi- stone. Marble is not recommended as it is
cations which may differ from lab to lab. Once porous and soft and gets stained easily.
the size of the lab is finalized, the actual design Some designers also prefer to use hot
shall be worked out (Fig. 23.1). welded vinyl flooring or epoxy-coated con-
Some of the important issues relating to the crete slab etc. The disadvantage with these
design of the Clinical Laboratories are as floorings is that if the chemicals and con-
follows: taminated water seep under the vinyl floor-
ings, slowly complete flooring will be
1. Before designing the Laboratory rooms, the damaged and will come out.
guidelines and norms of the controlling 7. Doors
authority of the country must be taken into Preferably each laboratory shall have a
account. Like NABL (a laboratory accredita- single door with a width of about 1829 mm
tion agency) prescribes the standards of clin- to ease control, like the movement of men
ical laboratories in India. and material, carrying the equipment in and
2. We have seen the advantages of Open type out of the laboratory. The laboratory doors
laboratory design. There shall be no doubt shall be automatically self-closing.
that the open design is the best. But it is 8. Windows shall be provided in the laboratory
advised that for some particular divisions as per the design and elevation of the
which deal with infectious or hazardous building.
investigations, a close type of laboratory 9. The lightning in the room shall be normal
shall be designed. It means that the labora- LED lights with sufficient lumens. No extra
tory shall be designed considering both the illumination is required in the room.
options, i.e. open type laboratory and closed 10. The temperature in the room shall be between
type laboratory. 18 and 22 °C and the humidity level shall not
3. If separate rooms are required for some par- be more than 40%. Before finalizing the RH
ticular division of the laboratories, it shall be level or the temperature, the environment
planned accordingly. Before designing, the requirement shall also be confirmed from the
space required for equipment and movement equipment supplier as some machines may
of staff shall be considered. require varied standards of the environment.
4. At times even if the equipment is installed in 11. All the machines shall have proper ground
an open hall, the manufacturers of that equip- earthing provisions.
23.9 Laboratories 267
23.9.1 Working Slabs Now between the upper surface of the plat-
form and the lower surface of the slab, there will
For an efficient working in the laboratory, the be vacant space. This space shall be used for pro-
role of working slabs shall not be underestimated. viding cabinets. These cabinets are the most used
These working slabs are used for placing small spaces than any other spaces. This space can be
tabletop machines, preparing the reagents and used for storing reagents, chemicals, consum-
chemicals, preparing the slides or blocks etc. It ables, stationery etc. Even some shelves and
means the working slabs are of multiple uses. If drawers can be provided for more storage space
the open type of laboratory is designed, the work- and the safety of the material.
ing slabs shall be provided on the walls of the
laboratory.
The top level of the working slab is normally 23.9.2 Sinks
36–38 in. from the ground level. The width of the
slab shall be about 762 mm, which can be reduced Each laboratory must contain a sink for washing.
or increased depending on the requirement. On Exposure to hazardous materials and/or pathogenic
the top surface of the slab, granite stone can be organisms can occur by hand-to-mouth transmis-
fixed with round or half-round edges. Similarly, sion. It is extremely important that hands are
the vertical stone shall also be fixed on the wall washed before leaving the laboratory. Therefore,
starting from the top of the slab. The height of the sink should be located close to the egress.
this vertical stone shall be between 305 mm and The sinks shall be provided at appropriate
610 mm. This vertical stone prevents the wall places in the working slab itself. The sink shall be
from getting damaged and stained. a deep laboratory sink and shall be about 610 mm
Below the working slab, on the floor, a plat- long × 457 mm wide. The sink shall be of china
form shall be provided. The thickness of the plat- clay as metal sinks are not recommended for lab-
form shall be about 183 mm. On the upper surface oratories. The sink shall be recessed in the work-
and throughout the thickness of the platform, ing slab. The tap shall be about 305 mm in height
stone or tiles shall be fixed. from sink level and the drain shall be on the floor
268 23 Clinical Laboratories
platform. Laboratory sinks shall have collars that nets, drawers and racks. This room shall have
protect sink drains from spills. Sink collars or only one door of about 914 mm.
brims should be ≥6 mm and designed to com-
pletely separate the lab bench from the sink drain.
23.9.6 Biohazard/Trash/
Recycle Room
23.9.3 Equipment Park/Store
The Biohazard/Trash/Recycle room is attached to
Generally, in laboratories, there can be equip- laboratories which are used for storage of the
ment that is not always in use but has to be ready soiled material. Normally, the room shall not be
all the time to be used whenever required. Hence, less than 3658 mm × 3658 mm. But depending on
storage of these equipment shall be done at a the requirements, the size of the room can be
separate place in the laboratories so that the floor changed. This room shall have two doors of about
space of the laboratory is not unnecessarily occu- 914 mm. One door opens in the laboratory and
pied with this equipment. Therefore, the equip- the other in the corridor from where the staff can
ment storage room/area is provided in the collect the material and he/she need not come to
laboratories. the laboratory for collection of material.
Normally, a room of size not less than
4267 mm × 4267 mm shall be provided attached
to each laboratory. This area can be a closed room 23.10 Pneumatic Tube Systems
with a door or otherwise open area attached to a (PTS)
laboratory. The room shall have a provision of
grounded and electrical charging points for One station of the PTS shall be provided in each
charging the unused medical equipment. laboratory for receiving the specimens and requi-
sition forms from different locations of the hospi-
tal. Similarly, it shall be used for sending the
23.9.4 Emergency Eyewash Station reports to the respective place.
done for electrical points. The main issues to be cation can be done by the machine through bar-
considered while designing the electric points are coding. Some of these machines may or may not
as follows: have wireless connectivity. If there is no provi-
sion of wireless connectivity in the machine, a
1. Main Switchboard shall be at the entrance networking cable shall be provided to the
wall for controlling fans and lights of the hall machine. This can be provided through the floor
along with one or more 6 Amp Switch/Socket. as was done with the electrical point. The net-
2. Air Conditioning Control button with tem- work cable can also be provided from the ceiling
perature adjustments. through the suspended conduit.
3. At least a pair of two 6/16/Amp switches/ The following communication points shall be
sockets shall be provided on the wall above provided:
the working slab. Such points shall be pro-
vided in series at a distance of 3048 mm from 1. RJ 45 point for Computer networking
each other. Half of these should be on UPS 2. RJ 11 for Intercom and extension line
supply.
4. 5 Amp switches/sockets shall be provided at a
suitable place for refrigerators and deep
freezers. 23.14 A
ir Conditioning System
5. As the equipment will be scattered throughout of Laboratories
the laboratory hall, they have to be provided
with a power supply. First of all, the specifica- Laboratories should be fully air-conditioned
tion of the power requirement shall be taken which allows control of temperature, humidity
from the manufacturer of the machine along and air exchanges. Suitable and safe air quality
with the dimensions of the machine. Then the must be maintained at all times. Following issues
location for placement of the machine has to are important while designing the Air
be finalized. The required supply of the power Conditioning System:
shall be given through the floor. For this, the
floor is chased and conduit is fixed in the 1. For Air Conditioning of laboratories, either
chase. The wiring is done and the supply shall Chilled Water Pipe Line with AHU’s can be
be given. These power points shall be on UPS opted or the Ductable Split or VRV system
supply. This electrical supply can also be can be opted. All the systems have their own
given from the ceiling with a suspended advantages and disadvantages.
conduit. 2. The return air of the laboratories shall be kept
6. The power supply may also be required on the separate for all the laboratories. Under no cir-
Office table for Microscopes. This can also be cumstances the return air of any laboratory
given through the floor supply. shall be mixed with another laboratory.
3. Air Flow, direction and air exchanges have to
be as per the norms of the industry.
23.13 O
ther Communication Points 4. The temperature of the laboratories shall be
in Laboratories between 18 and 22 °C, until and unless some
machine requires varied temperature.
Nowadays most of the laboratory equipment
comes with the communication ports for interfac- For full details on Air-conditioning, heating
ing with the Hospital Management Software so and air exchanges, please refer to the chapter
that the reports can be generated and the identifi- ‘HVAC’ (Chap. 38) in this book.
270 23 Clinical Laboratories
more such space is required, a separate store may shall be provided with proper block storage cabi-
be provided to all the laboratories separately. The nets for storage of blocks. Similarly, for storage
size of the room shall be 3658 mm × 3658 mm. of slides, slide storage cabinets shall be provided
There shall be no window in the room, no water in the room. The working top and sinks shall also
outlet and no moisture. The room shall have an be provided in the room. The size of the room
electric point for light and fan. depends on the number of samples that have to be
stored. Generally, a room with a size of
4267 mm × 3658 mm shall be sufficient.
23.17.7 Flammable Storage
This store is used for storing flammable and haz- 23.17.10 Penta Head/Deca Head
ardous materials like acids, spirit and alcohol. Microscope Room
The room shall be located away from the general
movement area. The room shall be of size This room is necessarily required in the teaching
3658 mm × 3658 mm and the wall shall have institutes, or in the hospital where more than one
glazed acid-proof tiles. Only one electric point person has to examine the same slide. The Penta
for light shall be given in the room. The racks Head Microscope has five different binocular
shall be of metal and not wood. outlets connected through a pipe fitted with
prisms and mirrors in between. Each head is
focused on the common platform where the
23.17.8 Specimen Storage/Recycle object is placed. Similarly, the deca head micro-
scope has ten such outlets. Separate rooms shall
This room is used for the storage of specimens be provided for both the microscopes. The room
that have been collected from the patients. shall be square in shape. In the centre of the
Normally, the specimens are stored for a few room, a table is placed which shall be sufficient
days, because at times a repeat test may have to be to accommodate the microscope. On all the five
performed. The specimens can be of blood, urine, or ten, as the case may be, laboratory stools are
stool, body fluids, semen etc. Each specimen may placed in front of the outlet from where they can
require a different environment and methods for sit and use the microscope. Proper electric points
storage. Therefore, adequate arrangements shall shall be given on the table where the microscope
be made for refrigeration and humidity. Similarly, is placed.
proper bins, racks, cabinets or racks shall be pro-
vided. The working top and the sinks shall also be
provided in the room. The size of the room 23.18 Utility Area
depends on the number of samples that have to be
stored. Generally, a room with a size of This is the administrative area for controlling and
4267 mm × 3658 mm shall be sufficient. coordinating the working of the laboratories.
Some of the spaces are:
visitor chairs, side rack etc. The room shall have are concerned, in some hospitals the phleboto-
an attached toilet. The room shall also have an mist is deputed, who at a fixed time collects the
attached P.A. room for the clerk to be seated. The specimens of indoor patients. But at some places,
room shall have proper arrangements for electri- the nurses and/or technicians have to draw the
cal points, intercom connection, IT network and specimens. Normally, a phlebotomy room is
air conditioning. planned in the OPD complex of the hospital. The
following rooms are provided for phlebotomy in
the OPD:
23.18.2 Laboratory Manager
This room is for the manager of the laboratories 23.19.1 OPD Phlebotomy Room
and shall be located on the laboratory premises.
The size of this room shall be about Normally, a single or more than one such phle-
4572 mm × 4267 mm. The room shall have an botomy rooms are provided at a convenient place
arrangement for office tables, executive chair, in the OPD complex. The Phlebotomist is placed
visitor chairs, side rack etc. The room shall have in the room along with helpers to draw speci-
an attached toilet. The room shall also have an mens. Size-wise the room shall be about
attached P.A. room for the clerk to be seated. If 4572 mm × 4267 mm.
required and long working hours are expected a Attached to the phlebotomy room a separate
small restroom can also be provided with this space/room, called as Sample Collection Room/
room. The room shall have proper arrangements Space, shall be provided where the patient is
for electrical points, intercom connection, IT net- seated or laid down and the specimens are drawn.
work and air conditioning. This space shall be about 2438 mm × 2438 mm.
Sample collection room/space contains one phle-
botomy chair and one examination couch. There
23.18.3 Technicians Room has to be a working top with the sink for keeping
the drawn specimens. The couch shall have a cur-
This room is for the technicians working in the tain partition for the privacy of the patient.
laboratories to carry out the official work of the Sufficient stock of needles, vacutainer tubes,
laboratories. The size of this room shall be about holders etc. shall be kept in this specimen collec-
4572 mm × 4267 mm. The room shall have an tion room, hence proper cupboards, shelves and
arrangement for office tables, office chair, visi- racks shall be provided.
tor chairs, side rack etc. The room shall have As far as the phlebotomy room is concerned,
proper arrangements for electrical points, inter- the room shall be a normal room with a working
com connection, IT network and air top having sinks. Sufficient electrical points shall
conditioning. be provided on the working top. The provision of
a refrigerator shall be provided. One office table,
chairs, computer with printer and barcode printer
23.19 Outpatient Phlebotomy shall be provided to complete the work like bar-
code fixing and taking consent. The specimens
Phlebotomy is the collection of specimens of the drawn are initially processed in the room and
patient for investigation. A person drawing the stored there to be sent to the laboratories in
specimens is called the Phlebotomist. Normally batches. The outlet point of the PTS shall be pro-
the specimens are collected in the hospital at a vided in the phlebotomy room so that the speci-
number of locations like OPD, IPD, ICU, OR and mens along with the requisition forms can be sent
Emergency. As far as the specimens from indoors to the laboratories without any delay.
274 23 Clinical Laboratories
This room is provided for drawing the specimens The area for the facility of the staff. This area
through fine needle aspiration. It can also be includes:
called the biopsy sample room. Normally, one
such room is provided at a convenient place in
the OPD complex. Size-wise the room shall be 23.20.1 Staff Lounge
about 4572 mm × 4267 mm. As the collection of
the specimen is through a fine needle, it is a kind This lounge is given in the laboratory area for the
of intervention. Therefore, the room has to be staff to sit and relax in their spare time. The
under sterile conditions. Attached to this room lounge shall be provided with an attached toilet
shall be a changing room for the patient and the and with the provision of tea/coffee which can be
staff. A scrub station shall be provided outside served from the pantry.
the room. A shoe rack has to be provided outside
the room. Inside the room shall be the examina-
tion table covered with hanging curtain parti- 23.20.2 Lockers
tions. As it is an intervention procedure, the
provision of the crash cart along with emergency Lockers shall be provided in the staff area for
medicines shall be kept in the room. One small facilitating the staff to keep their personal belong-
storeroom shall also be provided attached to the ings safely under lock and key. Each staff mem-
room to maintain sufficient stock of needles, vac- ber shall be allotted a separate locker.
utainer tubes and holders etc.
Emerging Practices in Clinical Laboratory Design [Internet]. Singh M. PLANNING PREMISES AND DESIGN
Clinical Lab Manager. [cited 2021 Jun 28]. Available CONSIDERATIONS FOR HOSPITAL
from: https://www.clinicallabmanager.com/features/ LABORATORY. Glob J Health Sci. 2019 May
emerging-practices-in-clinical-laboratory-design-341 14;8:1–6.
Medical laboratory safety management [Internet]. Tan SS, Yan B, Saw S, Lee CK, Chong AT, Jureen R,
Medical Laboratory Observer. 2018 [cited 2021 et al. Practical laboratory considerations amidst
Jun 28]. Available from: https://www.mlo-online. the COVID- 19 outbreak: early experience from
com/management/lab-s afety/article/13017071/ Singapore. J Clin Pathol. 2021 Apr 1;74(4):257–60.
medical-laboratory-safety-management Technological Revolution in Hospital Design and
Planning Premises And Design Considerations Care Delivery Will Bring Changes for Clinical
For Hospital Laboratory, GJRA - Global Pathologists and Medical Laboratories [Internet].
Journal For Research Analysis(GJRA), GJRA Dark Daily. 2017 [cited 2021 Jun 28]. Available
| World Wide Journals [Internet]. [cited from: https://www.darkdaily.com/2017/07/12/
2021 Jun 28]. Available from: https://www. technological-revolution-in-hospital-design-and-care-
wo r l d w i d e j o u r n a l s . c o m / g l o b a l -j o u r n a l -f o r- delivery-will-bring-changes-for-clinical-pathologists-
research-analysis-GJRA/article/planning-premises- and-medical-laboratories/
and-design-considerations-for-hospital-laboratory/ Yoong NW. Transforming the 24/7 Clinical Laboratories -
MTA5MjQ=/?is=1 Design Considerations, Workflow and Relocation
Race GJ, Tillery GW, Dysert PA. A history of pathol- to New Diagnostics Building. [cited 2021 Jun 28];
ogy and laboratory medicine at Baylor University Available from: https://clinmedjournals.org/articles/
Medical Center. Proc Bayl Univ Med Cent. 2004 ijpcr/international-journal-of-pathology-and-clinical-
Jan;17(1):42–55. research-ijpcr-2-024.php?jid=ijpcr
Blood Bank
24
Blood Bank is a place where blood is collected As the Blood Bank is a regulated department
from donors, tested, separated into components, in the hospital, it is advised to consider the rules,
stored and prepared for transfusion to recipients. regulations and norms of the controlling author-
ity of the respective country before planning and
designing the blood bank.
24.1 L
ocation of the Blood Bank
in Hospital
24.3 Functions of Blood Bank
The Blood Bank shall be located at the most eas-
ily accessible place in the hospital particularly in Blood banks have four major functions:
case of emergency. It shall be near to the
Emergency, Operating Theatre Complex and 1. Receiving
Intensive Care Units. Preferably the blood bank 2. Storage
shall be on the ground floor. The blood bank shall 3. Testing
be a unitary complex and rooms of blood bank 4. Distribution
cannot be scattered into different areas.
24.3.1 Receiving
24.2 Controlling Authority
Area designated for the collection of the blood
Mostly in all the countries, the Blood Banks are from the donor and providing facilities to the
controlled by some or the other controlling donor after bleeding.
authority under a specified act, e.g. in India, it is
controlled by the Drug Act. The norms, rules and
regulations are prescribed by the controlling
authorities.
© The Author(s), under exclusive license to Springer Nature Singapore Pte Ltd. 2022 277
A. Garg, A. Dewan, Manual of Hospital Planning and Designing,
https://doi.org/10.1007/978-981-16-8456-2_24
278 24 Blood Bank
Hence, the area shall not be less than 165 sq.m. 24.7.2 Reception
After adding the movement area, the total area
shall not be less than 200 sq.m. Reception shall be near the entrance of the blood
bank. The reception shall be kept open. The
Reception counter or the reception table can be
24.6 Equipment in the Blood Bank
provided with chairs for the receptionist. The
reception counter shall have a provision for suf-
Normally, the following equipment is provided in
ficient electric points, computer networking
the blood bank:
jacks, intercom points and an emergency tele-
Apheresis Machine Elisa Reader with phone line. The reception shall have sufficient
Washer
space for storage of stationery and other useful
Blood Bag Tube Sealer HB Meter
items. This storage can be provided in the cabinet
Blood Bank Refrigerator ID Centrifuge
Blood Collection Monitor Mechanical Shaker
or drawers on the counter. Otherwise, a side rack
Blood Collection System, Oven Universal can be provided for storage. The area shall be
Vacuum-Assisted 3658 mm × 3658 mm.
Blood Donor Couch Plasma Extractor
(Mobile)
Blood Mixing and Blood Platelet Agitator 24.7.3 Registration
Weighing Device
Cryo Bath Unit Platelet Incubator
Deep Freezer −40 °C Processing System for On the registration counter, the donor form is
Frozen Blood given and consent is taken from the donor. The
Deep Freezer −80 °C Refrigerated Centrifuge registration counter can also be combined with
Dielectric Sealer Thawing Bath the reception if required. An area of
Double Pan Balance Water Bath Serological 2438 mm × 2438 mm shall be sufficient.
280 24 Blood Bank
24.9 Storage and Processing Area be rounded off with the help of the puff panel
or GI sheet. The walls and ceiling shall be fin-
This area pertains to the storage of the blood pre- ished with anti-bacterial and anti-fungal
and post-screening. There are different storages washable paints.
of the blood. The blood is usually stored in the 2. Flooring
blood bank refrigerators, until and unless the The floor must be non-pervious and stain
quantity of the blood is huge and can be stored proof. It is recommended that floor tiles of
only in refrigerated rooms. This area is also for large size, like 600 mm × 600 mm shall be
processing the blood to separate the components used. The only condition is that there shall be
out of the blood. no spaces between the tiles it means the tiles
shall be joint less. Otherwise, optionally gran-
1. The storage of untested blood (which has still ite can be used as it is a hard stone. Marble is
to be screened) is generally kept either in the not recommended as it is a porous and soft
bleeding room or otherwise in a separate stone and easily gets stained. Some designers
enclosure provided for this purpose. A blood also prefer to use hot-welded vinyl flooring or
bank refrigerator shall be provided in the epoxy coated concrete slab etc. The disadvan-
bleeding room or the enclosure as the case tage with these floorings is that if the water or
may be. Wherever it may be, an electrical chemical seeps under the vinyl floorings,
point shall be provided for connecting the slowly and gradually complete flooring will
blood bank refrigerator. be damaged and will come out.
2. The storage of tested blood, ready for distri- 3. Doors
bution, is done away from untested blood. Preferably a component room shall have a
This area is provided either in the delivery single door with a width of about 1219 mm to
room or in a separate enclosure near to the ease the control, like the movement of men
delivery counter. A blood bank refrigerator and material, carrying the equipment in and
shall be provided in the delivery room or the out of the component room. The door shall be
enclosure as the case may be. Wherever it automatic and self-closing.
may be, an electrical point shall be provided 4. The lightning in the room shall be normal
for connecting the blood bank refrigerator. LED light with sufficient lumens. No extra
3. The numbers and capacity of blood bank illumination is required in the room.
refrigerators shall depend on the quantum of 5. The temperature in the room shall be between
blood bags to be stored. 18 and 22 °C and the humidity level shall not
be more than 40%.
6. All the machines shall have proper ground
24.9.1 Blood Component Room earthing provisions.
and no person shall be allowed to enter these taken for storage of medicines and injectable etc.
rooms without changing. Therefore, the staff and shall be properly marked and under the strict
must change into sterilized clothes by changing control of an authorized person.
the outside dress. The following issues shall be
considered regarding the Change room:
24.11.4 Record Room
1. The room shall be of the size
2438 mm × 2438 mm. Adequate storage space shall be allotted in the
2. Almirah shall be provided with the provision blood bank for storage of records. The size of the
for hanging clothes. room shall be about 2438 mm × 2438 mm. The
3. In the change room, staff lockers shall also be storage shall be lockable as far as possible and
provided where the staff can keep their per- shall be free from humidity, should be termite
sonal belongings. Individual lockers shall be proof and fire-resistant. The record room shall be
about 305 mm × 305 mm. Each locker shall provided with sufficient shelving, file cabinets
be lockable separately. One such locker shall and other storage for medical records. Donor
be allotted to one staff. record storage requirements will vary greatly
4. Handwashing and gowning facilities shall be according to local regulations. Typically current
provided in the change room. records (two to five years) will be held on-site.
Archival donor record storage of up to 20 years
will also be required.
24.11.2 Doctors Rest Rooms
Generally, a doctor is deputed in shifts who shall 24.11.5 Medical Officer Room
be available round the clock. Therefore, to facili-
tate the doctor on duty, a small doctor’s restroom It is desirable to have a space for administrative
is provided in the blood bank. control of the blood bank. As the in-charge of the
blood bank is the Medical Officer, hence a
1. The room shall be of the size Medical Officer Room shall be provided in the
2438 mm × 3048 mm. blood bank. The size of the room shall be about
2. Furniture wise, the room shall have one office 4267 mm × 3658 mm. The room shall be pro-
table, chair, bed and cupboard. vided with an office table, chairs, cupboard etc.
3. Apart from the light and fan, the room shall Electrical points shall be provided near to the
have points for a computer with Internet con- doctor’s table for a view box and a computer.
nection and Intercom point etc. Communication ports shall be given for a com-
4. Also, the room shall be Air Conditioned and puter and the intercom.
the Control button with temperature adjust-
ment shall be provided in the room.
24.11.6 Sterilization Room Cum
Washing Room
24.11.3 Store
A small washing cum sterilization room shall be
Store shall be provided in the blood bank for provided with the blood bank. The size of the
equipment, supplies, consumable materials, med- room shall be about 3048 mm × 3048 mm. For
ical disposables and other items in current use. washing, a countertop with deep sink shall be
The designer shall also consider future require- provided where the instruments can be washed.
ments while designing the storage space. The For sterilization, a single vertical autoclave with
storage shall be lockable as far as possible and a capacity of two drums shall be provided.
shall be free from humidity, should be termite Necessary electric points shall be provided for
proof and fire-resistant. Particular care shall be the sterilizer.
286 24 Blood Bank
Further Reading
1. Health Services Department, Michael Okpara
University of Agriculture, Umudike, Abia State,
Nigeria. 2. Family Health International (FHI 360)
Country Office, Garki Abuja Nigeria 3. Department
Other Investigations
and Procedures 25
Apart from the Clinical Laboratories and tion leakages. The main issues to be considered
Radiology, there are lots of other investigations, while designing the Cath Lab spaces are:
tests and procedures that are being carried out in
the hospital. These investigations, tests and pro-
cedures may vary from one department to 25.1.1 Location of the Cath Lab
another.
All the special investigations, tests and proce- Cath Lab shall be preferably located near the
dures may or may not need special spaces in the ICCU and shall be a sterilized and clean area.
hospital. Hence, it has to be planned well in
advance as to which of these the hospital wants to
set up immediately or maybe later in the future. 25.1.2 Number of Cath Lab
The designer shall plan well in advance for pro- Procedure Rooms
viding spaces for them so that the hospital does
not face problems in introducing them in future. The number of Cath Labs shall depend on the
Most of these special investigations, tests and number of Cath Lab machines required to be
procedures may normally require some extra installed as on date and also the future plans of
room with general facilities like adequate space, the addition of more machines. The Cath Lab
electrical outlet points and air-conditioning; but machine comes with a long slidable table.
some of them may require specially designed Some of the important issues relating to Cath
rooms or complexes. The spaces which require lab rooms are as follows:
special design have been described below: Before designing the Cath Lab rooms, the
guidelines and norms of the controlling
authority of the country must be taken into
25.1 Coronary Catheterization account. In India the authority is Bhabha
(Cath Lab) Atomic Research Institute.
A separate room shall be provided for each
The Cath lab, used for interventional cardiology, machine. More than one machine is not allowed
is an X-ray-based imaging machine and a very in a single room.
high dose of the rays are produced when expo- For Cath Lab, if the machine is to be installed
sure is given. Hence, it requires the design con- horizontally, a rectangular room shall be
sidering the norms of the regulatory authority. designed. If the machine is installed diagonally, a
Proper designing has to be done to avoid radia- square room can also be considered. But the
© The Author(s), under exclusive license to Springer Nature Singapore Pte Ltd. 2022 287
A. Garg, A. Dewan, Manual of Hospital Planning and Designing,
https://doi.org/10.1007/978-981-16-8456-2_25
288 25 Other Investigations and Procedures
s uggestion is to install horizontally in a rectangu- Depending on the capacity of the machine, the
lar room. The space of the room shall not be less power load required by the machine shall be cal-
than 42 sq. mtr. The approx. Size can be culated and the main stitch and cable shall be ter-
9144 mm × 4572 mm. minated in each Cathlab room separately.
All the walls of the room shall be at least As the weight of the machine is more and the
229 mm thick with a plaster on both sides. The movement of the machine is very fast, it is
ideal thickness for the primary wall of an X-ray advised to check the weight-bearing capacity of
room should be at least 250 mm solid baked clay the floor. If needed to provide a foundation for
bricks or 150 mm in case of mortar/concrete the machine as per the suggestion of the machine
walls for plain radiography. Hollow bricks should manufacturer. If the machine is ceiling suspended
be plastered with a thickness of 6 mm barium model, care shall be taken to access the load-
plaster and should be protected up to 2200 mm bearing capacity of the ceiling. If required proper
from the floor level. treatment with the help of guarders of angle shall
The flooring shall be either tiles/marble/gran- be done to increase the load-bearing capacity of
ite. But the flooring shall not be slippery to avoid the ceiling.
the chances of an accident causing injury to the The lightning in the room shall be normal
patient. LED light with sufficient lumens. No extra illu-
The room shall have a single door with a width mination is required in the room.
of about 1829 mm, to ease the movement of The temperature in the room shall be between
trollies. 17 and 21 °C and the humidity level shall not be
The door shall have to be with a proper more than 40%. Before finalizing the RH level or
2000 mm thick lead lining. The lining has to be the temperature, the environment requirement
done even on the door frame. There shall be no shall also be confirmed from the equipment sup-
leakage of the radiation from any place in the plier as some machines may require varied stan-
door. Doors should overlap by a minimum of dards of the environment.
100 mm on each side when closed. The door All the machines shall have proper ground
should be at least 1800 mm long and 2000 mm earthing provisions.
high. The overlap requirement also applies to Inside the Cath Lab room, outlets for medical
flap doors that make a single entrance door but supply shall be given. The outlets shall be 1 of
close from different sides of the door. The door Oxygen, 1 for Vacuum and 1 for Air.
should have handles and locks on the inside The proper two-way audio system is provided
and the outside so that they may always be in the Cath Lab, from here the patient can be
closed during exposures thus controlling directed by the technician from the control room.
access. Position the gantry and couch such that the
It is advised to provide air interlock spaces by patient is completely visible from the control
providing an additional door before the Cath Lab console during scanning.
room door. Stand with heavy-duty hangers shall be pro-
Windows are not allowed in the Cath Lab. vided outside the Cath Lab to hang the Lead
Outside the room, a Warning light shall be apron.
given by providing a Red colour bulb outside the Also, a cabinet shall be provided, for keeping
door. The light must be connected to the genera- other radiation safety devices like, lead gloves,
tor in such a way that it will illuminate only dur- lead goggles, groin guards and lead collars.
ing the activation of the tube.
While installing the machine, care shall be
taken to leave at least 1829 mm space behind the 25.1.3 Cath Lab Console Room
machine for the movement of the C Arm of the
machine to move. The machine shall be installed Attached to the Cath Lab room a console room
in the centre of the width of the room. has to be provided. There shall be a provision of
25.1 Coronary Catheterization (Cath Lab) 289
Secondary Computer for transfer of images of designed after consulting the equipment manufac-
the procedure which has been completed for turer. The size and temperature etc. shall be con-
starting the reporting. The size of the console firmed from the manufacturer of the machine.
room shall be a minimum 3658 mm × 3658 mm.
4. There shall be adequate hooks on the wall to quantity and number of items, the size may vary.
hang the clothes. The store needs to have sufficient countertops,
5. Also, a hanger rod shall be provided with cupboards and drawers. The Temperature of the
hangers to hang the clothes. room shall be between 17 and 21 °C.
6. There shall be a cabinet to keep the sterilized
dresses.
7. The hamper for dirty linen shall also be pro- 25.1.11 Consultation Rooms
vided in the change room.
Family members and friends of the patient,
being anxious to know the position and develop-
25.1.8 Waiting for Cath Lab ment in the condition of the patient need to meet
the treating cardiologist and have an interaction
Cath Lab shall have a separate waiting area near with him. Therefore, Consultation Rooms are
the Lab for the family members of the patient provided for this purpose. This room shall be
whose procedure is being performed. The num- about 4572 mm × 4267 mm with a provision of
ber of persons that can be allowed to wait in this a doctor’s table, chairs and sofa set. The cardi-
lobby may be limited with proper spacing ologist goes to that room, calls for the family
between their seats. members of the patient and has an interaction
with them.
At times there can be hot discussions, for this,
25.1.9 Stores for Unused some security personnel shall be placed outside
Consumable the room. Furthermore, this room shall be under
CCTV surveillance from inside with audio-video
Cath Lab procedures require a lot of consumable recording (Fig. 25.1).
materials like catheters, guide-wires and fluid.
Hence ample stock of these consumables shall
be available in the Lab. To stock these items, the 25.2 Thallium Scan
department needs a store. This store shall be of
the size of 3658 mm × 3658 mm. But depending Thallium Scan is a high positron emitter, it is
on the quantity and number of items, the size essential to provide the proper shielding and
may vary. The store needs to have sufficient safety mechanisms like RCC walls. Hence it is
countertops, cupboards and drawers. The advised that Thallium Scan areas shall be clubbed
Temperature of the room shall be between 17 with the areas where PET CT/MRI machines are
and 21 °C. installed.
For details, please refer to the chapter
‘Radiology’ (Chap. 22).
25.1.10 Stores for Records and CDs
25.3.1 Location of the Audiometry door of the room shall also be airtight so that no
Room outer sound can enter the patient room.
The Technician room shall be a normal room
This room shall be located near to the ENT OPD with a glass window between the patient room
and in the general movement area. Clean and and the technician room. This room shall have a
sterilized areas are not required for this. working top below the glass window so that the
technician can see the patient in the other room
while the procedure is going on (Fig. 25.2).
25.3.2 Room Designing
Fig. 25.2 Sample layout drawing of Audiometry Room sterilized and clean area. Therefore, it is preferred
to get them done in the OT Complex (Fig. 25.3).
allotted for the bronchoscopy in the OT complex. The details of the Endoscopy room have
If the procedure has to be done outside the OT been described in the chapter ‘OT Complex’
complex, an OR type of setup has to be created at (Chap. 19).
another place where the bronchoscopy has to be
performed. The setup will require, sterilized
bronchoscopy room, change rooms for staff, 25.6 Neurology
change room for the patient, store, bronchoscope
wash area, patient recovery room etc. Most of the neurological investigations like
The design of the rooms shall be exactly as Electromyography (EMG), Neuropsychological
described in the chapter ‘OT Complex’ Tests, NCV /EP Studies and Transcranial mag-
(Chap. 19). netic stimulation (TMS) are OPD-based investi-
gation and space shall be provided in the OPD
complex.
25.5 C
apsule Endoscopy, In the OPD Complex, a space called Neuro
Cholangioscopy, Lab shall be created and all such investigations
Colonoscopy, Duodenoscopy, shall be done in this lab. For convenience, a
Endoscopic Ultrasound, separate cabin for each investigation shall be pro-
Upper Gastrointestinal vided to maintain the privacy of patients.
Endoscopy etc. The size of the Lab shall depend on the num-
ber of such machines to be placed in the room
All these procedures are basically invasive proce- and the number of cabins to be provided. Further,
dures performed by using the different types of the size of the room shall also depend on the
endoscopes. Hence, they have to be done in a number of patients investigated at a particular
25.8 Ophthalmology 293
moment of time. There shall also be ample space The patient room has to be completely sound-
for movement of the staff in the Lab. It is advised proof and with slight darkness to make the patient
that at least a space of 3658 mm × 3658 mm shall sleep comfortably. The door of the room shall
be provided for each machine to be installed in also be airtight so that no outer sound can enter
the lab. the patient room. The room shall have a bed for
Attached to the Neuro Lab a proper waiting the patient.
area and a reception shall be provided for the As this machine is usually portable, some hos-
convenience of the patients and family members. pitals prefer to use a private single occupancy
The facility of toilets shall also be provided for room to perform this procedure. This can also be
the patients and family members. done if preparing a separate room is not
Regarding the temperature and the humidity possible.
in the Lab, normally it shall be between 18 and The Technician room shall be a normal room
22 °C and humidity of about 40–45%. But still, with a glass window between the patient room
the equipment manufacturers shall be contacted and the technician room. This room shall have a
for specific environmental conditions of the working top below the glass window so that the
room. technician can see the patient in the other room
Proper electric and communication points while the procedure is going on. The machine is
shall be provided for the machines. placed on the countertop and the technician
records the findings of the patient while he/she is
asleep.
25.7 Polysomnography Proper electric and communication points
(Sleep Lab) shall be provided for the machines.
Radiation Therapy (RT) is a speciality of the or steel. The wall thickness of the bunker is usu-
Oncology Department and is used for the treat- ally 2400 mm. Similarly, the roof is also
ment of cancer through radioactive rays gener- 2400 mm thick. Another important issue is that
ated through Linear Accelerator (LINAC). the LINAC is a very heavy machine weighing
Through radiation, specific malignant cells are about 8–9 tonnes. Hence, the flooring has to be
damaged through external beams of radioactive very strong to bear such a weight. Usually, the
waves. High-energy waves, such as X-rays, bunker occupies 1.5 floors till the top of the
gamma rays, electron beams or protons, are bunker.
accelerated in the LINAC to destroy or damage Taking into account the above factors, the
cancer cells. Bunkers cannot be provided on any upper floors.
In the Radiation Therapy Unit, the facilities It has to be on the ground floor. Still, it is prefer-
and equipment for radiotherapy treatment are able if the bunkers can be provided in the base-
provided. The Radiation Oncology Unit contains ment. The added advantage with the basement is
spaces to support patient consultation, treatment that the wall thickness reduces because of the soil
simulation and planning, and the administration filled along the bunker walls. As the outer walls
of treatment. The Radiation Oncology Unit gen- of bunkers are exposed to the outer surface,
erally contains both external and internal radio- where the soil is backfilled, the thickness reduces,
therapy (brachytherapy) treatment areas. as the radiations penetrate the filled up soil.
Hence, the Radiotherapy department, particu-
larly the bunkers shall be located either on the
26.1 Location of Radiotherapy ground floor or in the basement. If basements are
Unit chosen, proper access and road connectivity shall
be provided to transport the LINAC to the bunker
The Radiotherapy department has two main site.
machines. One is the LINAC and the other is the The Unit shall be provided with facilities for
Brachytherapy. Because of the high radiation, it ready access for outpatients, including people
is mandatory to install these machines in the with disabilities, people arriving by patient trans-
Bunkers. What is the Bunker? A bunker is made fer services and ambulances, and for inpatients in
out of High-density RCC materials like concrete wheelchairs and on beds or trolleys.
© The Author(s), under exclusive license to Springer Nature Singapore Pte Ltd. 2022 297
A. Garg, A. Dewan, Manual of Hospital Planning and Designing,
https://doi.org/10.1007/978-981-16-8456-2_26
298 26 Radiation Therapy
5. The trolley bay shall be provided outside the inside the treatment area, because it is a high
lobby for parking of wheelchairs and stretcher radiation area.
trolley so that the patients dropping on the 4. The waiting area shall not be very big, and
porch can use them. distancing has to be followed.
5. The chairs shall be laid down at distancing.
6. There must be facilities available such as tele-
26.3.3 Reception and Enquiry phones, public address systems to call rela-
Counter tives of patients to inform them about the
patient’s condition etc.
Immediately after the arrival of the patient in the 7. Near to the waiting area shall be provided
department, this is the first area of contact. The Toilets, both for males and for females sepa-
Reception provides the required information to rately. The provision of cold drinking water
the visitors, guide the visitors to the required shall also be provided.
place, book an appointment or treatment sched- 8. Mobile charging points shall also be provided
ule etc. Hence, the reception counter has to be in the waiting area.
placed just at the entry of the radiotherapy depart-
ment. The reception shall be at such a place that
it is easily approachable. 26.3.6 Store
26.4 Treatment and Planning safety of staff, patients and visitors. They pro-
Area vide scientific support for all treatment
machines like CT Simulators, LINAC,
This area includes: Brachytherapy, computer planning systems,
and equipment as well as dosimetry, quality
assurance and radiation safety. The spaces shall
26.4.1 Mould Room be provided for offices and workstations for
physicists. The size of the room shall be about
The mould is a kind of photon and electron 4267 mm × 3658 mm. The room shall be pro-
shielding that is prepared to protect the patient vided with an office table, chairs and an exami-
from radiation exposure to other parts of the body nation couch. The room shall also be provided
except the area to be treated with radiation. The with computer workstations connected to the
mould has to be prepared for each and every hospital network. Physics laboratory shall be
patient and the design and sizes vary from patient provided to manufacture equipment not avail-
to patient. The mould room is to take the sizes able commercially for patient treatment such as
and design of the mould to be prepared. The room the installation of rigid attachments for patient
shall be about 4267 mm × 3658 mm and shall be hoists, calibration jigs for physics and mask
provided with the office table, chairs and the creation appliances. Storage for Medical
examination couch. The room shall also be pro- Physics equipment including bulky water tanks
vided with computer workstations connected to and phantoms.
the hospital network. The connection to the PACS
shall also be done.
26.4.4 CT Simulators
26.5.1 External Beam Radiation system design, and for installing additional
Therapy electrical supply cabling.
11. A maze width of 2000–2200 mm shall be
For external beam radiation therapy, the LINAC provided to ensure an adequate turning circle
is used. With LINAC, an electron beam is typi- for equipment delivery.
cally created which is used for killing cancer 12. LINAC is a very heavy machine weighing
affected tissues by radiation while sparing the about 8–9 tonnes. Hence the flooring has to
surrounding healthy tissue. Using these high- be very strong to bear such a weight.
energy electrons (particle) beam accelerators, the 13. While installing LINAC for the first time,
patient’s malignant cells and tumours of varying provision for the base-frame shall be pro-
size and shape can be killed. While designing the vided. This base frame shall be measured
External beam radiation unit, the following issues from the centre to the back and shall be
shall be considered: 6000 mm × 2000 mm × 610 mm deep
excavation.
1. The external beam radiation therapy LINAC 14. Two or more bunkers shall be designed adja-
is installed in the bunkers. Bunkers are made cent to each other to reduce costs by sharing
out of High-density RCC materials like con- the primary shielding structures.
crete or steel. 15. The door shall be provided at the end of the
2. The wall thickness of the bunker is usually maze, i.e. entry of the bunkers, just to avoid
2400 mm. Similarly, the roof is also 2400 mm accidental entry in the bunkers, while the
Thick. radiation is in progress. This door need not
3. The bunkers shall have a Maze type of have the shielding as this door is not for pro-
design. tection from radiation, but to provide a phys-
4. The size inside the bunkers shall be ical barrier and restrict the entry in the
7000 mm × 7000 mm with the iso-centre bunkers.
positioned approximately in the centre of the 16. Access during radiation shall be prevented
room. with a combination of light sensors and/or
5. The bunkers shall provide space for the push gates or barriers that are interlocked to
structure of the LINAC unit and the maxi- the control panel.
mum longitudinal extension of a typical 17. Usually, the bunker occupies 1.5 floors till
patient treatment table. the top of the bunker. Access to the roof of
6. The gantry and the patient treatment table the bunkers shall be restricted and cordoned
shall be engineered to rotate around an off, with a security entrance, interlocked to
iso-centre. the treatment machine.
7. The width shall enable comfortable access 18. However, the equipment like water chillier
around the gantry and the patient for all and the air-conditioning plants are placed on
angles of rotation. the roof, as these types of equipment require
8. The plane of gantry rotation shall be parallel controlled access.
to the treatment control panel area. 19. Linear accelerator bunkers require radiation
9. While designing the orientation of the bun- protection that may include lead shielding
kers, the issues of high occupancy areas shall and concrete walls, floors and ceilings to
be taken into account. specified thicknesses, a neutron door may
10. The minimum structural room height shall also be required depending on the type of lin-
be 4 m, including along the maze. This height ear accelerator used.
is necessary for ease of access when equip- 20. The radiation protection needs of the unit
ment is delivered, to provide for the air con- shall be assessed by a certified physicist or
ditioning, heating, exhaust and ventilation appropriate agency. This assessment is to
302 26 Radiation Therapy
specify the type, location and amount of pro- 29. After the installation of the machine, false
tection to be installed in accordance with the ceilings shall be provided in the bunkers.
final approved department layout and equip- 30. Each bunker shall be provided with Control
ment selection. The radiation protection Areas. These areas shall be located outside
requirements shall be incorporated into the the maze of the bunker.
final plans and specifications. Early consulta- 31. The bunkers shall be provided with a patient
tion with the manufacturers of radiotherapy intercommunication device and at least two
equipment is recommended. closed-circuit television monitors, to com-
21. For LINAC with a maximum energy of 10 municate with the patient while the therapy
MV, the neutron shielding is not required. is in progress.
22. The lifespan of the facility and the need to 32. The working top in the control area shall be
upgrade technology should be considered of adequate length to provide spaces for
when specifying the radiation shielding installation of all the monitors and other con-
required. It is likely that the machines will be trol equipment along with the patient infor-
upgraded and newer machines may or may mation files, sheets and images to be used
not emit stronger radiation. Therefore, it is while therapy is in progress.
sensible to allow for the highest energy 33. Electrical power points shall be provided
machine and widest beam that is likely to be along the whole length of the worktop to
used in the future. allow multiple devices to be powered, includ-
23. The bunker shall be provided with the plumb- ing additional emergency switches.
ing and electrical provisions. The under- 34. The X-ray viewing box with ambient light-
ground conduits for these lines shall not be ing shall be provided in the control area.
straight but have to be angulated at an angle 35. Space shall be provided along with the con-
of 45 degrees. trol room area for networked imager or
24. The bunker shall be provided with the provi- printer. This facility can also be shared with
sion of power supply to the LINAC as per the brachytherapy (Fig. 26.1).
requirement of the machine. Hence the man-
ufacturer of the equipment shall be contacted
beforehand while designing the bunkers. 26.5.2 Internal Beam Radiation
25. Provisions for joints, ducting and sleeves
Therapy
should not follow the divergence of the pri-
mary beam, and this is easily achieved by For internal beam radiation therapy, the
placing these in the secondary shielding and Brachytherapy is used. Brachytherapy is a
using a curved path. method of delivering radiation to tumours where
26. The issues relating to the mechanical, electri- radioactive sources are placed either within or
cal and safety shall all be considered like, immediately adjacent to tumour tissue. While
providing dimmable lights in the room, designing the Brachytherapy Unit, the following
emergency switches and the provision of issues shall be considered:
standby lighting.
27. Provision for ducting shall be provided in the 1. The Brachytherapy treatment room is used
bunker for connection between the gantry for delivery of a radiation source through a
structure and the treatment control panel. tube or applicator, implanted during
28. In addition, isolated ducts should be pro- surgery.
vided for dosimeter cables and connectivity 2. The Brachytherapy room is similar to that of
to the chillier system. the External Radiation therapy unit, i.e. for
26.6 Radiotherapy Ward 303
brachytherapy, the bunker has to be provided. (ceiling height of 3000 mm) in order for
Hence all the issues relating to the bunkers as there to be enough space around the unit to
mentioned above in LINAC have to be taken manoeuvre a C-arm and a procedure trolley
care of. if the patient is prepared in the treatment
3. Along with the Brachytherapy Unit, an room.
equipped operating room along with other 8. Because the source emits radiation isotopi-
services like anaesthetic induction room, cally, a shielded roof is required.
scrub area, patient recovery room and clean 9. Except for the wall thickness and the dimen-
room shall be provided. sions of the Brachytherapy bunkers, all other
4. C-arm shall be provided in the Brachytherapy issues of LINAC bunkers shall be taken care
to be used for applicator placement and there- of while designing the bunkers for
fore will need to be installed in the appropri- Brachytherapy.
ate room, either the procedure room or the
treatment room depending on the local
practice. 26.6 Radiotherapy Ward
5. The brachytherapy bunker shall have wall and
ceiling thicknesses of at least 1000 mm. Though generally, a ward is not required in the
6. The maze shown is 1800 mm wide to allow radiotherapy department, but still some hospitals
for easy access in the event of an emergency prefer to have a small setup of radiotherapy ward
and the design shown has no door. for any emergency. Hence a small ward with
7. The inside dimensions of the room shall be about 2 to 4 beds can be planned. The setup of the
4000 mm × 4000 mm × 3600 mm height wards will be similar to any ward as mentioned in
304 26 Radiation Therapy
the chapter of Intermediate Care Area (Patient The designer shall also consider the future
Rooms). requirements while designing the storage space.
For other details about Radiotherapy Ward Storage is needed for personal items belonging to
about construction details, Furniture, staff, patients and visitors. Equipment and sup-
Equipment, Instruments and Tools, Doors, plies storage shall be designed to be stored as
Windows, Central Medical Gas Supply, close as possible to point of use. The storage shall
Electrical Points, Other Communication be lockable as far as possible and shall be free
Points etc. please refer to the chapter from humidity, should be termite proof and fire-
‘Intermediate Care Area (Patient Rooms)’ resistant. Particular care shall be taken for stor-
(Chap. 21) in this book. age of medicines and injectable etc. and shall be
properly marked and under the strict control of an
authorized person.
26.7 Trolley Bay
For the convenience of the patient, the Radiation 26.10 Signage and Wayfinding
therapy shall be provided with an area reserved
for the stretcher trolley and wheelchairs. The area Proper Signage shall be provided in the depart-
shall be enough to park at least two stretcher trol- ment, which will make the visitors understand
lies and two wheelchairs. The trolley park area the layout of the department. Provide a simple
shall be somewhere at the corner of the depart- and clear way finding solutions. This can be done
ment so that it does not create hindrances in the with proper signage or with design and material
routine working of the department. solutions, such as colour-coordinating paths or
accent lighting.
26.13 Dirty Utility/Sluice Room Care Co-ordinators and Specialist Nurses. The
size of these rooms shall be about
The dirty utility shall be provided in the depart- 3658 mm × 3658 mm. The room shall have an
ment which shall be used for storage of the soiled arrangement for office tables, chairs, visitor
linen. From here the linen is moved for pre-wash chairs, side rack etc. The room shall have
before sending it to the laundry. Normally, the proper arrangements for electrical points,
room shall not be less than 3658 mm × 3658 mm. intercom connection, IT network and air
But depending on the requirements, the size of conditioning.
the room can be changed. The room is provided
with covered linen collection hampers or contain-
ers to collect the dirty linen. This room shall have 26.16 Other Issues
two doors of about 914 mm. One door opens in on Infrastructure
the department and the other in the corridor from of the Radiation Therapy
where the laundry staff can collect the linen. Air Unit
from this room shall be exhausted hence the
exhaust fans are a must. 26.16.1 Acoustics
The following communication points shall be The following electrical points shall be provided
provided at all the required places in the in the consultation chamber, Administration
department: rooms, Planning rooms and other areas except for
the treatment rooms.
1. RJ 45 point for Computer networking.
2. RJ 11 for Intercom and extension line. 1. Main Switchboard shall be at the entrance
3. HDMI point for computer display at other wall (other than the wall on which door will
locations. open) for control of the fan and lights of the
4. Voice/data outlets and wireless networks. room along with one 6 A Switch/Socket.
5. Telephone and video conferencing capacity 2. Air Conditioning Control button with tem-
for meeting rooms. perature adjustment.
6. PACS imaging system, electronic records and 3. Two 6 A Switches/Sockets above on the wall
radiotherapy information management 1 ft. above the doctors/administrator table.
systems. Also, one 15 A Switch/Socket shall be pro-
vided adjoining to this.
4. Three 5 A Switches/Sockets above on the wall
26.17 Heating Ventilation and Air 305 mm above the doctor/administrator side
conditioning rack for computer and printer. Also, one 15 A
Switch/Socket shall be provided adjoining to
General air conditioning shall be provided in the this for equipment or heater.
whole department. The temperature of the unit 5. Proper switch/sockets shall be provided in the
should be maintained within a comfortable range treatment planning rooms for providing power
between 18 and 24 °C and shall be comfortable to the required machinery.
for the patient. 6. Regarding the Power in the treatment rooms
The temperature of the treatment rooms shall and the LINAC/Brachytherapy machines,
be from 17 to 20 °C and the humidity level shall the same shall be as per the requirement of
not be more than 40%. Before finalizing the RH the manufacturer of the machines.
level or the temperature, the environment require- Therefore, before finalizing the electrical
ment shall also be confirmed from the equipment planning of these rooms, it shall be con-
supplier as some machines may require varied firmed from the equipment supplier as some
standards of the environment. machines may have varied power
requirements.
26.18 C
entral Piped Medical Gas
Supply 26.20 Power Backup
Each of the treatment room, treatment planning The power backup is very essential for the treat-
room shall be provided with the Piped Centralised ment rooms, where the machines are installed.
Medical Supply system. The gases supplied are: These machines shall have their own power back
up, which should start automatically in the event
• Oxygen. of a power failure. If possible the machine shall
• Compressed Air. have a backup with the connected UPS. Also, the
• Wall-mounted Suction. department shall have its own backup of an Auto
Further Reading 307
Start Diesel Generator. Also, the necessary provi- van der Merwe D. Planning a Radiotherapy Department.
sion for the regulation of voltage or power sup- Clin Oncol. 2017 Feb 1;29(2):105–9.
Mc Morrow A. Radiation Shielding and Bunker Design.
plied to the department shall be made. Biomed J Sci Tech Res [Internet]. 2019 May 17 [cited
2021 Jul 7];18(1). Available from: https://biomedres.
us/fulltexts/BJSTR.MS.ID.003106.php
Further Reading Wu S, Zheng D, Liu Y, Hu D, Wei W, Han G. Radiation
Therapy Care During a Major Outbreak of
COVID-19 in Wuhan. Adv Radiat Oncol. 2020 Jul
Baskar R, Lee KA, Yeo R, Yeoh K-W. Cancer and 1;5(4):531–3.
Radiation Therapy: Current Advances and Future Internationale Atomenergie-Organisation. Radiotherapy
Directions. Int J Med Sci. 2012;9(3):193–9. facilities: master planning and concept design con-
Bonett J. Ceiling art in a radiation therapy department: its siderations. Vienna: IAEA; 2014. 31 p. (IAEA human
effect on patient treatment experience. J Med Radiat health reports).
Sci. 2015;62(3):192–7. Acosta R, Brick W, Hanna A, Holder A, Lara D, McQuilen
Horton P, Eaton D. Design and Shielding of Radiotherapy G, et al. Radiotherapy optimAl Design: An Academic
Treatment Facilities: IPEM Report 75 second Edition: Radiotherapy Treatment Design System. Math Fac
IPEM Report 75, second Edition [Internet]. IOP Res. 2009 Jan 1;47.
Publishing; 2017 [cited 2021 Jul 7]. Available from: Mohan G, T P AH, A J J, K M SD, Narayanasamy A,
https://iopscience.iop.org/book/978-0-7503-1440-4 Vellingiri B. Recent advances in radiotherapy and its
Ashby D, Peterson F, Atterbury D. Designing chemo- associated side effects in cancer—a review. J Basic
therapy and radiation therapy facilities. Health Care Appl Zool. 2019 Feb 27;80(1):14.
Strateg Manage. 1986 Oct;4(10):9–16. Spencer K, Jones CM, Girdler R, Roe C, Sharpe M,
Designing the New-age Oncology Radiation Therapy Lawton S, et al. The impact of the COVID-19 pan-
Department [Internet]. Healthcare Executive. [cited demic on radiotherapy services in England, UK: a
2021 Jul 7]. Available from: https://www.healthcare- population-based study. Lancet Oncol. 2021 Mar
executive.in/blog/tdesigning-the-new-age-oncology- 1;22(3):309–20.
radiation-therapy-department
Rehabilitation and Allied Health
Therapies 27
© The Author(s), under exclusive license to Springer Nature Singapore Pte Ltd. 2022 309
A. Garg, A. Dewan, Manual of Hospital Planning and Designing,
https://doi.org/10.1007/978-981-16-8456-2_27
310 27 Rehabilitation and Allied Health Therapies
If the department is located in a separate build- The Reception of the department shall be at
ing, it shall have a separate entrance. The main the entrance of the department. For details
issues relating to the reception shall be seen in of the reception, please refer to the chapters
the chapter of ‘Entrance Lobby’ (Chap. 15) as ‘Entrance lobby’ (Chap. 15) and ‘Out-Patient
given in this book. Department’ (Chap. 17) given in this book.
27.7 Patient Therapy Areas 311
14. Nurse and Emergency Call Systems 8. Provide Pinboard and whiteboard for
Nurse call systems in all individual cabins displays.
including the Exercise area shall be 9. A sufficient number of electrical outlets shall
provided. be provided for the tools and machinery to be
used in the therapy.
For the Exercise zone, the following issues 10. Workshop areas shall have suitable air
shall be kept in mind: extraction and supply in the room. Air
exchanges shall be preferred.
1. This zone can be accommodated in a single
hall having sufficient spaces for installing all
the equipment and modalities used in the 27.8 Administrative Area
exercise.
2. All the wall-mounted exercise modalities The Rehabilitation department shall have the
shall be properly screwed to the wall. rooms to be used for general administrators,
3. The required mirrors shall also be provided on managers and clerical staff managing the depart-
the walls. ment. The room shall be provided for:
department and the temperature shall be socket points shall be provided and all the
between 18 and 23 °C. computer points shall be backed up by UPS
4. Natural Light/Lighting supply.
Wherever possible, the use of natural light 7. For the safety of the patients, handrails, grab
shall be maximized for easy working of the bars and other support mechanisms shall be
staff. provided in the department.
5. Information Technology/Communications 8. The department shall be provided with wall
The department shall be provided with guards and corner guards.
Intercom Lines at all the required places.
Also, computer networking points shall be
provided in the examination cubicles, recep- Further Reading
tion and the cabins where the machines are
required to be connected to the computers. At PRIME PubMed | Planning a new physiotherapy
department--a personal experience [Internet].
all the required places RJ45 jacks shall be pro- [cited 2021 Jul 7]. Available from: https://www.
vided in the department. unboundmedicine.com/medline/citation/7323205/
6. Electrical Services Planning_a_new_physiotherapy_department__a_
Apart from the electrical points, at all the personal_experience_
required places the pair of 6/16 A switch/
Pharmacy Unit
28
In the hospital, the Pharmacy has an important 2. A Private Retail Pharmacy is provided both
role as it is the centre to disburse medicines, for inpatient and for outpatients.
injectable, surgical disposables like catheters, 3. Hospital has a self-owned pharmacy for inpa-
cotton and bandage to all the inpatients and out- tients and a Private Retail shop for
patients of the hospital. outpatients.
Let us understand the working of the phar-
macy department. In the hospital, there are two Whatever the case may be, the hospital shall
places where drugs have to be disbursed. One is have two pharmacies, one for inpatients and the
for the inpatients and the second is for the second for outpatients.
outpatients.
Generally, for the inpatients, drugs are dis-
bursed directly from the pharmacy store to the 28.1 Location for the Pharmacy
respective wards and there is no requirement of a
separate drug distribution counter. Whereas in For Outpatients, the pharmacy shall have a retail
the case of Outdoor patients, a retail pharmacy counter somewhere near the OPD block and shall
counter needs to be provided. be easily accessible to the patients. The best loca-
The Pharmacy store or counter basically is a tion can be at the exit point of the OPD block.
licensed facility and the Licence has to be taken For inpatients, the pharmacy shall be provided
for all the stores separately. A separate licence at any place in the hospital where access is not
shall be required for outdoor pharmacy retail common. It can either be in the basement or on
counter and the inpatient pharmacy. Both these the service floors.
licenses shall be for retail shops. If the hospital
disburses drugs in wholesale, another license
shall be required for wholesale pharmacy. 28.2 Size of the Pharmacy
Similarly, for dealing with the scheduled
Narcotics drugs like Ketamine separate licenses The size of the pharmacy shall depend on the
will be required. number of patients to be served, numbers of for-
There are various combinations of providing mulations to be disbursed, the quantity of items
Pharmacy services in the hospital. Those can be: to be stored etc. What is more important is that
the size of the stores shall be large enough for
1. The hospital has a self-owned Pharmacy both storage of the drugs and disposables equal to the
for inpatients and for outpatients. consumption of at least one month.
© The Author(s), under exclusive license to Springer Nature Singapore Pte Ltd. 2022 315
A. Garg, A. Dewan, Manual of Hospital Planning and Designing,
https://doi.org/10.1007/978-981-16-8456-2_28
316 28 Pharmacy Unit
28.3 Infrastructure of Pharmacy staff. The receiving area shall be provided with a
workstation for recording initial receiving/vali-
The requirements of inpatient pharmacy and the dation of medication orders.
outpatient pharmacy are more or less the same
except for a few differences. Generally, the fol-
lowing are required in the pharmacy: 28.4.3 Disbursing Hall
Pharmacy Entrance Disbursing hall is the main place where the rou-
Storage and Disbursing Hall tine drugs and disposables are stored and are dis-
Bulk Storage
bursed to the patients. The following are the
Cooled Storage
issues relating to designing of disbursing hall:
Expiry Drug Room
Costly Drug Room
Drug Sorting Room 1. The size of the hall shall depend on the num-
Narcotics Drug Store ber of patients being served, the quantity and
Pharmacist Office number of drug formularies to be disbursed.
Public Utilities for Staff 2. The hall shall have the provision of racks
divided into shelves for storage of the drugs.
The racks shall either be made out of wood
28.4 Pharmacy for Outpatients or stainless steel. The height of the racks
shall not be more than 2134 mm the depth of
The Outpatient Pharmacy of the hospital shall be the shelf shall be about 305 mm and the
centralized (all spaces in one complex) and shall height from shelf to shelf shall be about
be connected to key departments of the hospital 305 mm.
like OPDs and emergency. The pharmacy shall 3. As an alternative to the racks, built-in cup-
have the following infrastructural facilities: boards can be provided on the walls of the
hall which are divided into shelves.
4. The shelves shall be able to bear the load of
28.4.1 Entrance the drugs stored in them.
5. For bulky material like cotton, pads, splints
There shall be one single entrance to the phar- and walkers space can be provided above the
macy unit. The entrance shall have a single door rack above the height of 2134 mm. To oper-
with a width of about 1829 mm. The door shall ate this a double stand step ladder can be
be openable on both sides. The door shall be used.
guarded round the clock. 6. For small and costly drugs lockable drawers
and cabinets shall be provided.
7. On the front wall of the pharmacy, transac-
28.4.2 Drug Receiving Area tion/pass-through windows shall be pro-
vided. At least one such window shall be
Within the Pharmacy, space or enclosure shall be provided for every 50 patients being served
provided where the drugs received from the sup- during a day.
pliers shall be placed. After proper counting and 8. Below these transaction/pass-through win-
quality verification, the drugs shall be moved to dows, a working counter shall be provided
the respective store for shelving. This enclosure for working of the staff. This counter shall be
shall be about 3658 mm × 3658 mm. The area used for installing computers to be used for
shall be provided with racks and shelves, an billing.
office table and chairs. The area or enclosure 9. The counter shall have lockable drawers for
shall be lockable with restricted access of the keeping some collected cash.
28.4 Pharmacy for Outpatients 317
10. Proper electrical points shall be provided on temperatures. This cold room shall be located
the working counter to supply power to the very near to the disbursement hall. It shall be
computers and printers. better if the door of the cold room opens in the
11. Above the transaction or pass through win- disbursement hall. This room is also called the
dows, or on sides of such windows, a display refrigerated room. The size of the room shall be
case can be provided to display the general about 3048 mm × 3048 mm. The walls and the
items being sold in the pharmacy. ceiling of the room shall be made out of a puff
12. An office table and chair shall be provided in panel which acts as a thermal barrier. Inside the
the hall for the Pharmacist, who shall keep a room, the air-conditioning is done and the tem-
watch on the working of pharmacy. perature is kept between 5 and 12 °C and is
13. The pharmacist shall be provided with a
adjustable as per requirement. The door of the
computer system connected to the hospital room is also made out of the puff panel and is
network. hermetically sealed. The flooring is generally
14. This area shall have restricted entry and shall made out of wooden planks. For storage, open
be guarded. racks are provided along the walls. The room
15. Some refrigerators shall be provided in the shall be provided with a temperature monitoring
room to store drugs requiring cold chains. system and connected to a centralized alarm/
warning system. All access doors to this room
shall be lockable.
28.4.4 Bulk Storage
Usually, the pharmacies place orders in bulk for 28.4.6 Expiry Drug Room
fast-moving items like fluids. Once the stock is
received, it becomes difficult to store the entire Usually in any pharmacy, the expiry of the drugs
lot in the disbursing hall and has to be stored at is the main issue, and if not controlled properly,
another place. Therefore, a bulk store shall be huge losses may occur. Efficient management
provided. This bulk store can either be located always keeps a close track of the expiry of the
within the pharmacy complex or at any other con- drugs. As most of the drug manufacturers have a
venient place. The size of the bulk store shall policy of replacing the near to expiry drugs, the
entirely depend on the requirements. This store pharmacist shall return the near expiry drugs
shall have heavy-duty racks to store the cartons well in time. To keep track of expired and near
of the material. Accordingly, racks shall be expiry drugs, most of the pharmacy software’s
designed. The room shall have a single door and have a provision of keeping track of the expiry
the width of the door shall be about 1219 mm. dates and giving warning well in time. Once the
The store shall be lockable and free from any pharmacist knows which drug is near expiry the
kind of moisture. Special care shall be taken that same shall be removed from the shelf and kept in
the store is fire resistant, hence the electrical a separate place. This space shall be a separate
points shall be provided outside the store. In the room under lock and key. This place is termed as
store, only one or two light fittings shall be pro- Expiry Drug Store. The store shall be about
vided. Windows are not required in this store. 3658 mm × 3658 mm. The room shall be pro-
Direct sunlight shall be avoided in the store. vided with racks and shelves to store the drugs.
This store shall be near to the disbursing hall.
The room shall have a single door and the width
28.4.5 Cold Store of the door shall be about 1067 mm. The store
shall be lockable and free from any kind of mois-
A cold walk-in store shall be provided in the ture. Special care shall be taken that the store is
pharmacy for storing specific drugs which fire protected, hence the electrical points shall be
require a cold chain or are to be kept under cool provided outside the store. In the store, only one
318 28 Pharmacy Unit
or two light fittings shall be provided. Windows 28.4.9 Narcotics and Controlled Drug
are not required in this store. Direct sunlight Store
shall be avoided in the store.
The pharmacy dealing with Narcotics and
Controlled drugs shall always be alert to pur-
28.4.7 Costly Drug Room chase, disburse and store these drugs. Hence such
drugs shall be stored in a separate room and shall
Some drugs in any pharmacy are very costly, and always be under lock and key. Only authorized
there are a lot of chances of pilferage of such persons shall be allowed to enter the room. This
drugs, and if not controlled properly, huge losses room shall be termed as Narcotic Drug Room.
may occur. Efficient management always keeps a The room shall be about 3048 mm × 3048 mm.
close track of the costly drugs. Hence such drugs The room shall be provided with racks and
shall be stored in a separate room and shall shelves to store the drugs. This room shall be
always be under lock and key. Only authorized attached to the disbursing hall. The room shall
persons shall be allowed to enter the room. This have a single door and the width of the door shall
room shall be termed as Costly Drug Room. The be about 1067 mm. The room shall be lockable
room shall be about 3048 mm × 3048 mm. The and free from any kind of moisture. Special care
room shall be provided with racks and shelves to shall be taken that the room is fire protected.
store the drugs. This room shall be attached to the Windows are not required in this room. Direct
disbursing hall. The room shall have a single door sunlight shall be avoided in the room.
and the width of the door shall be about 1067 mm.
The room shall be lockable and free from any
kind of moisture. Special care shall be taken that 28.5 Pharmacy for Inpatients
the room is fire protected. Windows are not
required in this room. Direct sunlight shall be The Inpatient Pharmacy of the hospital shall be
avoided in the room. centralized (all spaces in one complex) and shall
be connected to key departments of the hospital
like ICUs, Emergency, Operating Unit and IPD.
28.4.8 Drug Sorting Room The pharmacy of inpatients shall have the
same design, except that, in the disbursing hall
While disbursing the stripped medicines in retail, the disbursing counters and windows are not
at times it happens that the cut strips are left out. required. Except this, all other areas/rooms, as
Secondly, due to the return of the medicines, mentioned above in outpatient pharmacy shall be
these returned medicines have to be kept back on provided.
the shelf. Before placing these cut strips and
returning drugs back on the shelves, they need to
be sorted out. Therefore, a separate room shall be 28.6 Pneumatic Tube Systems
provided to sort out such drugs and strips. This
room shall be termed as a Drug Sorting Room. For a fast and efficient service of the pharmacy,
The room shall be about 3048 mm × 3048 mm. the Pneumatic Tube Systems (PTS) systems shall
The room shall be provided with racks and be provided in the inpatient pharmacy.
shelves to store the drugs. Also, the working The PTS is an air-operated system having the
counter along with the chairs shall be provided air pump attached to the control station. This sys-
where the staff can sit and sort out the drugs. This tem is used as a transport system of documents,
room shall be attached to the disbursing hall. The material and medicines. This is the best, accurate
room shall have a single door and the width of the and quickest mode of transport for documents,
door shall be about 1067 mm. specimens, material and medicines.
Further Reading 319
In this system, at all the important points of to the automation. If need be the manufacturer of
the hospital (called stations) where the drugs the automation equipment shall be contacted
have to be sent or from where the drugs have to before planning.
be transported, the outlet of this system is
installed along with the control unit. These areas
can be ICUs, Emergency, Operating Room, Further Reading
Indoor wards etc. The carrier box (Capsule) car-
ries the documents from the user department and ADVANCES IN HOSPITAL PHARMACY SERVICES:
supplies drugs to the user department. AN OVERVIEW [Internet]. PharmaTutor. [cited
2021 Jul 7]. Available from: https://www.pharma-
It is very easy to operate. The user department tutor.org/articles/advances-i n-h ospital-p harmacy-
has to just put the drug indent in the capsule and services-an-overview
send it to the pharmacy. The pharmacy shall pack Swensson ES. An Innovative Design in Hospital Pharmacy
the drugs as required and send back the drugs to Facilities. Am J Hosp Pharm. 1971 Jun 1;28(6):440–6.
Taylor EN. Obesity, Weight Gain, and the Risk of Kidney
the same user. In seconds, the material or docu- Stones. JAMA. 2005;293(4):455.
ment is transported to the desired location. Blum A, Merino GSAD, Merino EAD. Design strate-
gies in hospital pharmacy department: Mapping
a medication system. Strateg Des Res J. 2018 Jan
15;11(1):15–20.
28.7 Pharmacist Offices Kay BG, Boyar RL, Raspante PS. Designing a modern
hospital pharmacy. Am J Hosp Pharm. 1986 Feb
Offices shall be provided for the Pharmacist near 1;43(2):339–43.
to or inside the pharmacy complex. These rooms Carroll N, Richardson I. Enablers and barriers for hospital
pharmacy information systems. Health Informatics J.
shall be separate for inpatient pharmacy and out- 2020 Mar 1;26(1):406–19.
patient pharmacy. The size of these rooms shall Five pharmacy automation trends [Internet]. [cited 2021
be about 4572 mm × 4267 mm. The rooms shall Jul 7]. Available from: https://www.hfmmagazine.
have an arrangement of office tables, executive com/articles/2345-five-pharmacy-automation-trends
Gones V. HOSPITAL PHARMACY MANAGEMENT:
chair, visitor chairs, side racks etc. The rooms AUSTRALIAN AND INDONESIAN
shall have an attached Toilet. The rooms shall PERSPECTIVES.: 196.
also have an attached P.A. room for the clerk to Pharmacy design can streamline patient care - Architecture
be seated. If required and long working hours are [Internet]. Healthcare Facilities Today. [cited 2021 Jul
7]. Available from: https://www.healthcarefacilities-
expected, a small restroom can also be provided today.com/posts/Pharmacy-design-can-streamline-
with these rooms. The rooms shall have proper patient-care%2D%2D2720
arrangements for electrical points, intercom con- Pharmacy Design, Design a Pharmacy [Internet]. [cited
nection, IT network and air conditioning. 2021 Jul 7]. Available from: https://www.pharma-
cydesign.org/Articles-PharmacyDesignTrends-0608.
htm
Augusto V, Xie X. Redesigning pharmacy delivery pro-
28.8 Automation in the Pharmacy cesses of a health care complex. Health Care Manag
Sci. 2009 Jun 1;12(2):166–78.
Sabzghabaee AM, Badri S, Ashari HE, Hosseini SM. The
The pharmacies are undergoing a lot of automa- design and equipments of hospital pharmacies in
tion like using robots for filling up and disbursing Isfahan, Iran. J Res Med Sci Off J Isfahan Univ Med
the drugs and use of drug dispensing machines. Sci. 2010;15(4):219–24.
Coblio NA. The Impact of Pharmacy Work Design on
The designer while designing the pharmacy shall Pharmacist Productivity.: 176.
consider all the requirements and issues relating
CSSD
29
The importance of sterilization cannot be over- 1. Cleaning of the instruments and the linen
emphasized in any of the hospitals. Sterilization before preparing for sterilization and
is a process through which the instruments, linen, Preparation for sterilization.
O.T, Rooms and other parts of the hospital are 2. Pre-sterilization packing.
made free from microorganisms and hence the 3. Sterilization.
prevention of infections in the hospital is made 4. Storing after sterilization.
sure. The process of sterilization destroys all the 5. Distribution of the sterilized material to the
microorganisms, whether disease producing or users.
non-disease producing. In the hospital, while dis-
charging its duties, one should safeguard human Normally the following items are sterilized in
life, and that operative skill may be made as the CSSD
effective as possible. Hence it is necessary that
adequate sterilization procedures be carried out. 1. Surgical Instruments.
The Central Sterile Services Department 2. Dressing drums.
(CSSD) in the hospitals is an integrated place that 3. Linen of O.T and Emergency.
performs sterilization of medical devices, instru- 4. Disposables.
ments, linen and consumables. This is a support 5. Bedding.
department for other hospital departments. The 6. Equipment.
main operations of this department are cleaning,
preparing, disinfecting, packing and sterilization
of reusable medical devices, linen and surgical 29.1 Methods of Sterilization
instruments. Processes
A Central Sterile Supply Department (CSSD)
should be established in the hospital to supply As the effectiveness of the sterilization depends
sterile dressings and sets to the wards and depart- upon the methods used for sterilization. Some of
ments, including the operation theatre. The CSSD them being:
department should be a centralized department
with all the modern equipment for effective 1. Dry Heat sterilization.
sterilization. 2. Steam sterilization.
The process of the sterilization can be broadly 3. Chemical sterilization.
divided into the following categories: 4. Gas sterilization.
© The Author(s), under exclusive license to Springer Nature Singapore Pte Ltd. 2022 321
A. Garg, A. Dewan, Manual of Hospital Planning and Designing,
https://doi.org/10.1007/978-981-16-8456-2_29
322 29 CSSD
1. Manual cleaning of instruments and Linen 8. The air-exhaust system shall be provided in
etc. not suitable for automated cleaning. this area.
2. Disassembly and inspection of contaminated 9. Sufficient wall-mounted brackets for hang-
materials. ing cleaning chemicals and brushes shall be
3. Rinsing of instruments and equipment. provided.
4. Sorting and loading of medical instruments 10. Space to park trolleys shall be provided.
and equipment into trays/washer-disinfectors 11. Hatch window for the transfer of hand-
and other automated cleaning equipment. washed items to the packing area and return
of empty trays.
This area shall have 12. Deionized, distilled or reverse osmosis (RO)
water for final rinsing is required.
1. Space for installation of the Automatic 13. Drying rack—workspace must be available
Instrument washer (Single door or double for drying manually cleaned instruments.
door) with a provision of the water supply
line and required drain. The machine shall be
mounted on the prescribed foundation. The 29.9 Packaging Area
required electrical outlets shall be provided.
The earthing of the machine shall be done. After decontaminating and washing the instru-
2. Similar arrangements shall also be done for ments, they are forwarded to the packing area for
the Ultrasonic cleaner. assembling them into pre-defined sets or trays.
3. The size of the decontamination and washing Instruments and other items that are prepared for
area shall be about 4267 mm × 3658 mm for sterilization must be packaged so that their ste-
both of them. rility can be maintained to the point of use.
4. For manual cleaning, a double bay sink (one
for cleaning and one for rinsing) along with
the drain board fixed in the benches shall be 29.9.1 Location
provided. The sink shall be deep by at least
1 ft. and made out of 304-grade stainless Packing area shall be located between the
steel. The size of the sink shall be about Decontamination area and the Sterilization area,
457 mm × 610 mm. Proper arrangement for with a unidirectional workflow from contami-
hot and cold water supply and drain shall be nated to clean areas.
done. The benches shall also be made out of
stainless steel.
5. The washing area shall also be provided with 29.9.2 Role of the Packing Room
the outlet of compressed air (can be supplied
from the piped medical pipeline) blowguns. 1. Inspecting, functionality testing, assembling
6. If need be, the pre-treatment area can be pro- and packing cleaned and disinfected medical
vided, where removal of pollutants is done devices and accessories, according to prede-
with the help of an automatic cycle. This area termined required standards, in preparation
shall be at “negative pressure” compared with for sterilization.
the surrounding environment to reduce the risk 2. Packs are checked, reassembled, double-
of contaminating the other areas of treatment. wrapped, labelled, dated and signed on the
7. Handwashing facility with liquid soap dis- checklist by the packer.
penser and paper towel dispenser shall be 3. Delivering items to the sterilizer loading area.
provided. 4. Returning racks to the decontamination area.
29.10 Sterilization Area 325
The size will be dependent on the number and Ethylene oxide is used to sterilize items that are
type of sterilizers installed and whether single or heat or moisture sensitive. Ethylene oxide (EO) is
double-door. However, on average, the area per a chemical agent that kills microorganisms,
sterilizer shall not be less 9.29 Sq. Mtr. including spores, by interfering with the normal
metabolism of protein and reproductive pro-
cesses (alkylation) resulting in the death of cells.
29.10.4 Methods and Types Used in the gaseous state, EO gas must have
of Sterilizers direct contact with microorganisms on or in items
to be sterilized.
Depending on the methods or load of the material
to be sterilized, the type and size of the sterilizers
are decided and provided. The sterilizers can be; 29.10.7 Dry Heat Sterilizer
29.11 Clean Storage Area 450 mm below the ceiling or sprinkler heads and
at least 50 mm from side walls to allow for air
After sterilization of items is complete, these circulation in the room and to prevent contamina-
have to be stored in the sterile area. Therefore, a tion during cleaning.
room shall be provided for the storage of The following issues shall be kept in mind
processed sterile material, including trays and while designing the clean storage room;
drums etc.
1. The size of the storage shall depend on the
quantity of the material to be stored and also
29.11.1 Location of the Clean on the time period for which generally the
Storage Room material is held in the storage.
2. No window shall be provided in the room.
The sterile storage area should be located adjacent 3. Direct sunlight shall be avoided in the room.
to the sterilization area, preferably in a separate, 4. The entry to the storage should be restricted,
controlled, enclosed, limited-access area, the only and a person should be allowed to this area
function of which is to store sterile supplies. only after he has washed up and changed the
clothes.
5. In this area, there shall be racks (as described
29.11.2 Designing of the Storage earlier) of different sizes and the sterilized
Shelves materials are kept in the racks for the use.
6. All the sets kept in the sterilized area should
The storage room shall be provided with Stainless be marked for the date of sterilization so that
steel racks and/or alternately lockable cupboard if the set is not used within the sterilization
made out of stainless steel. Some of these racks life, it can be re-sterilized.
or the cupboards, as the case may be, shall be 7. Ventilation, humidity and temperature con-
divided with the bins. Others can have open trol are required. The temperature of the
shelves. These racks shall be adjoining the walls room shall be between 18–22 degree and the
of the storage room. The height of the racks can RH around 40%.
be about 1829 mm, and the width shall be accord- 8. The room shall be positively pressurized
ing to space in the room. Better is if the width is with filtration as in the case of OR’s.
kept to 914 mm each. Then multiple racks of 9. The storage shall be fitted with doors and
914 mm the width can be placed side by side. The shall be lockable.
shelves shall be 375 mm deep, easily cleaned and 10. This room shall be attached to the delivery
allow air to circulate around stored packs. counter. The material required to be deliv-
Freestanding or mobile shelving provides a prac- ered shall be moved from this room to the
tical solution for handling the flow of products in delivery counter.
and out of storage and cleaning. If the room size 11. The sterile area shall have arrangements for
is bigger, the racks can be placed in the centre of washing of the room and fumigation.
the room to allow access from all sides of the
racks. Open shelving is more commonly used as
it allows dust to pass through making them easier 29.12 Delivery Counter
to clean than solid shelves. For bins, the size of
bins can be 305 mm × 305 mm × 305 mm each. The delivery counter shall be at the extreme end
Packs should be stored away from direct sun- of the CSSD from where the sterile material shall
light and water and should not be stored next to be delivered to the users. This area shall have a
or under sinks or on the floor where they are delivery counter to place the material to be imme-
likely to get wet or damaged. Sterile packs should diately issued. Upon demand, the staff shall bring
be stored at least 250 mm above the floor, and the required material from the sterile store, place
29.14 Finishing Details of the CSSD 329
it on the delivery counter, make the proper entries 2. The room shall be of the size
and deliver the material. The counter shall have a 3048 mm × 3048 mm.
delivery window for the delivery of material. The 3. The room shall have a provision of an attached
size of the window can be 914 mm–1219 mm in toilet.
length and 914 mm height. 4. Furniture wise, the room shall have chairs and
Outside the delivery windows, sufficient space cupboard.
shall be provided for parking of the trolleys that 5. Almirah shall be provided with the provision
arrive to collect the material. Here a computer for hanging the clothes.
station is provided for managing the delivery of 6. Also, the room shall be Air Conditioned and
materials and the transport documentation. the Control button with temperature adjust-
ment shall be provided in the room.
7. In the change room, staff lockers shall also be
29.13 Support Areas provided where the staff can keep their per-
sonal belongings. Individual lockers shall be
The support area to the CSSD are such areas that about 305 mm × 305 mm. These individual
are not directly involved in the sterilization pro- lockers can be combined and the locker almi-
cess, but directly or indirectly support the CSSD rah can be fabricated. Each locker shall be
department. These are like; lockable separately. One such locker shall be
allotted to one staff.
29.14.3 Floors
29.14.7 Electrical Points
1. Carpet or similar soft flooring should be
avoided. 1. The sufficient number of 6/16 Amp electrical
2. Impermeable, non-slip floor flooring shall be outlets shall be provided to supply power to
used. If tiles are used, there shall be no gaps in all the appliances.
between and the tiles shall be joint less. PVC 2. For higher load appliances, the connection
welded sheet vinyl coved up the wall can also shall be done with the help of the starters or
be used. directly with the proper rated MCB.
1. Door shall be wide enough to allow trolley 1. Light fittings shall be fully recessed and
movement, and doors and corridors should be selected to prevent dust and insects from
wide enough to accommodate trolley turning entering.
circles and protruding trolley fittings. 2. LED type of light fittings shall be used and the
2. Door frames and door leaves should be light levels shall be not less than 400 lux.
designed and finished with protection clad-
ding and bumper rails to withstand the inevi-
table bumps by trolleys. 29.14.9 Air Conditioning
3. Doors shall be adequately sized to allow clear
passage of current as well as possible future The air conditioning and ventilation systems in
equipment. the CSSD have an important role that can have an
4. Automatic/semi-automatic doors make it eas- effect on air bacterial contamination. While dur-
ier for the collection and distribution of trol- ing the design and implementation, particular
leys. If not automated doors should be attention shall be paid to the following issues;
self-closing. If the design allows it, doors shall
open towards the higher pressure side where 1. The air conditioning of the areas such as
possible to overcome problems with weaken- changing rooms, administrative areas shall be
ing door closers, which may lead to lock-outs. without air recirculation and shall be designed
5. Vision panels shall be provided in the doors. as for other such areas of the hospital.
Further Reading 331
2. For clean areas like decontamination areas, Gonzalez P, Jacob MO. CENTRAL SERVICE: A system-
packing areas, sterilization and clean storage atic approach to design of efficient facilities layout.
Hosp Top. 1969 Apr 1;47(4):119–26.
areas, the provision shall be made for the Hospaccx. Central Sterile Services Department Planning
required air exchanges. The design of such & Designing [Internet]. hospital and healthcare con-
areas shall be the same as is done in the case sultancy in india. 2019 [cited 2021 Jul 10]. Available
of clean rooms. from: https://hhbc.in/central-sterile-services-
department-planning-designing/
3. To ensure proper air exchanges, a dedicated Banu A. Central Sterile Supply Department – Need Of
air-handling unit complete with primary air The Hour.:5.
heating, cooling, humidification, dehumidifi- Sen DJ, Saha DM. Central Sterile Supply Department: A
cation and filtration shall be used. Concept.:2.
CENTRAL STERILE SUPPLY DEPARTMENT:
4. The temperature in the CSSD shall be between Planning Considerations | Healthcare Architecture
18–22 °C and the Rh shall be about 40%. [Internet]. [cited 2021 Jul 10]. Available from: https://
5. Airflow should be designed so that air flows healthcarearchitecture.in/central-s terile-s upply-
out of clean areas into dirty areas via positive department-planning-considerations/
Swenson D. Designing and Developing a Central Sterile
pressure. Positive air pressure is required in Supply Department. Biomed Instrum Technol. 2013
the “clean” areas of the unit to reduce air May 1;47(3):259–65.
movements into these areas from the “dirty” Allison VD. Hospital Central Sterile Supply Departments.
areas of the unit. Br Med J. 1960;2(5201):772–8.
By JZ, Cao Y, Zhao H, Liran, Huang J, Zhu L, et al.
MODERN CENTRAL STERILE SUPPLY
Acknowledgement I am grateful to Dr. Rohit Varshney DEPARTMENT ARCHITECTURAL DESIGN
for his great support in compiling this chapter. I wish to CONCEPT AND PRACTICE-NAVY GENERAL
convey my thanks and gratitude to him for his time and HOSPITAL CSSD DESIGN PRACTICE. Chin Hosp
efforts he has put in. Archit Equip. 2014;(7):79–81.
Basu D, Bhattacharya S, Mahajan A, Ramanan VR,
Chandy M. The Importance of the Central Sterile
Supply Department in Infection Prevention and
Further Reading Control. Infect Control Hosp Epidemiol. 2014
Oct;35(10):1312–4.
3 Design Considerations for Sterile Processing The Leaflet Article [Internet]. [cited 2021 Jul 10].
Departments [Internet]. HALYARD. [cited 2021 Jul Available from: https://www.hcarefacilities.com/
10]. Available from: https://www.halyardhealth.com/ newsletter/article.asp?id=1596
articles/sterilization/3-d esign-c onsiderations-f or-
sterile-processing-departments/
Piped Medical Gas Supply System
(MGPS) 30
Medical gases are one of the main support ser- 30.2 Nitrous Oxide (N2O)
vices used in hospitals. Medical gases are spe-
cific gases that are separated from the air Nitrous oxide is a medical gas administered via
individually for various medical applications. an anaesthesia machine. It is mixed with oxygen
Commonly used medical gases in hospitals are: and various anaesthetic agents. Therefore, oper-
ating rooms are the sole location where nitrous
1. Oxygen (O2). oxide gas is used. Usually, a manifold supply sys-
2. Nitrous oxide (N2O). tem is the source of nitrous oxide gas. Cylinders
3. Medical air 400 KPa or 4 bar (MA 4). and the pipelines for Nitrous Oxide are coded
4. Medical air 700 KPa or 7 bar (MA 7). with blue colour.
5. Carbon dioxide (CO2).
6. Nitrogen (N2).
7. Medical vacuum. 30.3 C
ompressed Medical Air
4 Bar
© The Author(s), under exclusive license to Springer Nature Singapore Pte Ltd. 2022 333
A. Garg, A. Dewan, Manual of Hospital Planning and Designing,
https://doi.org/10.1007/978-981-16-8456-2_30
334 30 Piped Medical Gas Supply System (MGPS)
Carbon dioxide is a medical gas used for insuffla- The bulk system may consist of specially insulated
tions purpose in the laparoscopy procedures. vessels, vaporizers etc. These systems can be con-
Usually, portable cylinders are the source of CO2, structed with cryogenic vessels or a high-pressure
which are coded with grey colour. manifold, depending on the usage. Typically, oxy-
gen, nitrous oxide and carbon dioxide are supplied
to large hospitals in cryogenic tanks.
30.6 Nitrogen (N2)
Source is the system by which the gases are pro- The oxygen is also produced by the Oxygen con-
duced for flow through piping networks. There centrators. These concentrators take air from the
are different sources for medical gases, which atmosphere, separate the oxygen component and
vary from gas to gas. Each gas has a different fill up the tanks, from where it is supplied to the
source of production. These can be: pipeline.
30.10 Piping Networks 335
with the help of screws and the pipe is There are usually 2 types of alarms. One is the
supported on these saddles. Supports for sur- Master Alarm and second is the Area alarm.
face mounted pipework shall provide clear- Master alarm monitors the main gas lines and
ance to permit painting of the surface. sources conditions. Area alarms are used to moni-
12. For easy identification of the pipelines, the tor the conditions of specific smaller areas. For
pipes shall be painted and with the prescribed each gas service, there shall be pressure switches
colour and colour banding. Colour band for high and low pressure. These conditions of
identification shall be applied near to valves, pressure shall be clearly indicated on the alarm
junctions, walls etc. A band shall be 150 mm system with the facility to provide a common
wide. audio-visual alarm. All visual signal panels shall
be permanently labelled having clear identification
Oxygen
of the areas, rooms or departments served. Flashing
Nitrous Oxide visual signals shall have alternate periods on and
off mode. When a warning or alarm signal occurs
Oxygen/Nitrous Oxide Mixture
and the system condition subsequently reverts to
Medical Air normal, the corresponding visual and audible sig-
nals shall automatically reset to normal. The signal
Medical Vacuum
must re-sound after a nominal 15-minute period if
the fault condition still exists.
Area Line Pressure Alarm Boxes are available
according to the number of gases for which it has
30.10.2 Valves
to be used. Some are like:
Valves are provided in the MGPS system to con- Area line Pressure Alarm up to 5 gases
trol the flow of the gases. Basically, two types of Area line Pressure Alarm up to 4 gases
valves are provided in the system. Those are zone Area line Pressure Alarm up to 3 gases
valves and service valves. Zone valves are used to Area line Pressure Alarm up to 2 gases
isolate large areas of the system, like halls of
floors. These valves are usually required to switch
off the gases for maintenance or repair of the sys- 30.10.4 Gas Outlets
tem. Whereas service valves are used to isolate
small parts of the system like room for modifica- Outlets are the last endpoints of the MGPS from
tion and/or repair. where the gases are delivered to the patients. The
Valve Boxes are available according to the terminal units may be either wall- or pendant-
number of gases for which it has to be used. mounted. The connectors are plugged in these
Some are like: outlets which in turn are connected to the deliv-
ery pipes through which the gases are delivered.
5 Services
4 Services
Outlets shall be gas-specific and also colour
3 Services coded as per standards.
1 Services
30.11 Designing the MGPS System 11. Location of the building expansion plans
also has to be analyzed.
Before installation of the MGPS system, the most 12. Determine the locations where the source of
important factor is to design the system based on gases has to be installed. Like a manifold
the present requirements as well as the future room, pump room and liquid oxygen tanks.
planning of increasing the outlets. There are a 13. Check the availability of refilling of the Gas
few issues to be considered before designing the cylinder related to the number of empty cyl-
system. inders available, the capacity of the supplier
While designing the MGPS system certain to supply filled cylinders and distance of the
norms, as issued by the competent authorities supplier from hospital etc.
shall be followed. Usually, these norms are coun- 14. The average stock of filled cylinders which
try specific. Hence while designing the MGPS the hospital wants to maintain at any particu-
system, these country-specific norms shall be lar time.
taken into account and adhered to. 15. Check the estimated consumption of the
The factors to be considered are such as: gases, considering the type of patients that
are expected in the hospital. Out of them how
many are expected in the critical units.
30.11.1 Analysis of the Area 16. Checks the estimated number of surgeries
of the Hospital expected in the hospital.
17. After analysis, schematic drawings shall be
First of all, the area where the outlets have to be prepared for piping layout locating zone
provided shall be analyzed with respect to: valves, area valves, master alarms and area
alarms.
1. Numbers of beds in that area/hall/room. 18. Design of the technical details of the plant
2. Out of total beds, how many beds have to be and machinery with their capacities shall be
provided by MGPS. prepared. While designing, issues like esti-
3. Location of those beds in the hall/area/room. mated length of pipelines, the pressure at the
4. The purpose for which that area/hall/room delivery point shall be kept in mind.
has to be used. Whether it is an ICU or a nor-
mal patient room.
5. If ICU, what all medical equipment depen- 30.12 Infrastructure for MGPS
dent on gas supplies are to be used, like
Invasive Ventilators, Non-invasive ventila- The MGPS system shall have:
tors and High Flow Nasal Cannula.
6. Depending on these uses and equipment 1. Liquid Oxygen Tank Area with Landing Bay
decide the type of gases to be supplied, like (If Liquid Oxygen Tank is to be installed).
Oxygen, Air or Vacuum. 2. Manifold Room for Oxygen and Nitrous
7. Number of outlets to be provided on each Oxide.
bed. 3. Plant room for Compressor, Vacuum units.
8. What type of outlets shall be provided? 4. Medical Gases Control Room.
Whether it will be push type or sliding type. 5. Public Utility for Staff (Fig. 30.1).
9. How the outlets shall be fixed. Whether these
will be mounted on the wall directly or
mounted in the bed head panel or in the ceil- 30.13 Manifold Room
ing hanging pendant.
10. Anticipate the expansion plans of the hospi- The manifold room is provided to install the
tal relating to building, number of beds manifold for oxygen and Nitrous Oxide gases in
where the MGPS has to be supplied. the hospital. The manifold is basically a system
338 30 Piped Medical Gas Supply System (MGPS)
where more than one cylinder is connected in a common connecting copper pipe is fixed on the
series and then is connected to a common outlet. wall, and the outlet’s sockets are provided on this
This set of cylinders connected in a series is common pipe at a distance of about 305 mm from
called a BANK. Usually, ‘D’ type of jumbo cyl- each other. One socket shall be provided for each
inders are used for the manifolds. cylinder.
A bank of cylinders may have 2 to 20 cylin- The total storage capacity of the manifolds is
ders. The number of cylinders to be installed in usually planned on the basis of one week’s
each bank shall be decided as per the design that consumption of gases. Preference shall be that
has been decided as mentioned above. Based on each bank of the manifold shall hold gases equiv-
the number of cylinders to be installed in a bank, alent to at least two days’ consumption. Similarly,
30.13 Manifold Room 339
the unconnected cylinders in stock shall have From the Control panel, the outlet is given
gases equivalent to at least three consumptions. which is connected with the copper pipe of the
The copper tailpipe is attached to these sock- main supply line of the gas. The main supply line
ets, which in turn are connected to the regulator is the line that transports the gas to the hospital
of the cylinders. Each cylinder shall have a sepa- building.
rate tailpipe and regulator. This regulator shall be To be on the safer side, it is anticipated that an
fixed on the cylinders. Now the common con- emergency may arise at any time due to failure of
necting pipe, on which all the cylinders of the the manifold system. To overcome such an emer-
bank are attached, is connected to the control gency, an emergency manifold with two to four
panel, which controls the flow of the gas. cylinders is also provided. The design of the
The pig tail-pipe cylinder connector for oxy- emergency manifold shall be the same as that of
gen, nitrous oxide/oxygen mixture (50% v/v) and the main manifold, with the difference that no
medical air must be a pin-index yoke connector control panel is provided on the emergency
in accordance with laid down standards. manifold.
Similarly, the connector for nitrous oxide shall be The output of the emergency manifold is
a side outlet valve connector in accordance with directly connected to the main supply line where
the standards. the main manifold is already connected. In case
It shall be kept in mind that, the temperature of of failure of the main manifold system, and as
the gas may fall as low as −30 °C as the gas passes soon as the emergency manifold is switched on,
through the regulator at maximum capacity, and the gas flow starts in the same main pipeline. A
the equipment shall be designed accordingly. non-return valve and isolating valve shall be
To complete the manifold, TWO such banks installed immediately upstream of the reserve
are installed and both are connected to the control manifold connection to the pipeline distribution
panel. One bank is termed as ‘Duty Bank’ and the system.
other as ‘Standby Bank’. The control panel func- In the event of loss or failure of the primary
tions to control the flow of gases. As both the source of supply, the emergency/reserve system
banks are connected to the control panel, this shall be able to maintain (at least for a short time)
panel allows one bank to be operated at a time. the total system flow.
As soon as the pressure of the current bank drops, The manifold system is prepared for Oxygen
the control panel automatically switches to the Supply and Nitrous Oxide Supply. So for both
other bank. This job is done with the help of pres- the gases the main bank and the emergency sup-
sure regulating valves fitted on each bank. Once plies shall be provided (Fig. 30.2).
the empty bank is cut off, the cylinders of that
bank are replaced with the filled cylinders and
make ready for the next use. 30.13.1 Purging of the System
The Control Panel can either be Automatic or
Semi-auto type. The Automatic Control Panel The manifold shall have a facility of nitrogen
automatically switches between ‘Duty Bank’ to purging, to purge any air introduced during cylin-
‘Standby Bank’ and visa-versa. Whereas in the der changeover on each tailpipe. The purging
case of Semi-auto panel, the warning is issued as system shall be provided with venting outside to
soon as the bank pressure drops and the operator allow purging with the working gas before the
has to manually shift to the other bank. manifold is made ready for service. The pressure
The manifold headers shall be fitted with a of the nitrogen supply used for purging needs to
non-return valve to allow removal and replace- be set below the minimum operating pressure of
ment of any cylinder and to prevent the discharge the manifold, to prevent the supply of nitrogen to
of a bank of cylinders in the event of pig tail-pipe the patient and to prevent overriding of the alarm
rupture. system.
340 30 Piped Medical Gas Supply System (MGPS)
A system of manifolds shall be designed based on the shall also be considered. Roughly, 0.28 Sq. Mtr.
number of outlet points and the requirement of gases. of area per cylinder shall be allotted.
Based on the experience, it is recommended that the fol-
lowing patterns can be considered:
Cylinders (per Cylinders (per bank)
Number of bank) for Primary for Emergency 30.13.4 Fixing the Manifold
Outlets Supply Supply Systems in the Hall/Room
For Oxygen
Up to 50 4 + 4 1 + 1 Three walls of the room/hall shall be used for fix-
50–100 6 + 6 2 + 2 ing the manifold systems. One wall (of maximum
100–200 10 + 10 3 + 3 Length) shall be used for Oxygen manifold.
200–500 15 + 15 4 + 4
Opposite wall to this shall be used for Nitrous
Above 500 20 + 20 5 + 5
oxide and the third wall for emergency manifolds
For Nitrous Oxide
Up to 5 1 + 1 1
of both the gases. Depending on the size of the
6–10 2 + 2 1 + 1 walls the arrangement can also be changed.
10–20 4 + 4 2 + 2
Above 20 6 + 6 3 + 3
30.14 Compressed Medical Air
30.13.2 Location of the Manifold
Medical air is used mainly for operating the
Invasive Ventilators and the Nebulizers, as the
The manifolds shall be installed in the room/hall.
compressed air is mixed with the oxygen in the
The location of the manifold shall be outside the
ventilator and is provided to the patients.
hospital building. Most important is that there
Secondly, it is also used to provide power to cer-
shall be an approach road for the vehicles to
tain medical equipment for its operations. The
reach up to the door of the manifold room. If not,
equipment can be like Drill machines and
it will be difficult to transport the jumbo cylin-
Surgical Saws. Apart from this, it is also used to
ders to the manifold room.
operate the dental chairs and also used for clean-
Secondly, the room/hall shall be near to the
ing the instruments in the CSSD.
shaft in the hospital building from where the ris-
Medical air shall be provided at two different
ing main pipeline can be distributed in the hospi-
pressures: One is at a pressure of 400 kPa,
tal building.
required to drive ventilators and for other respira-
At the cylinder unloading point, where the
tory applications; Second is at a higher pressure
cylinders will fall from the vehicle, a thick
of 700 kPa which is required to drive surgical
wooden plank shall be inserted in the floor, so
tools.
that the cylinders fall on the wooden plank, hence
saving the floor from damage. The size of the
wooden plank shall be about 1219 mm in length,
30.14.1 Compressor Air Plant
610 mm in width and at least 152 mm thick.
The production of the medical air is done with
the help of the compressor. The plant consists of
30.13.3 Size of the Manifold Room
the Electric Motors, Air Compressors, Air
Reservoirs, Automatic/Semi-Automatic Control
The size of the manifold room shall entirely
Panel, Bacteria Filter and the Air Dryer along
depend on the size of the manifold which in turn
with the required non-return valves, isolating
shall depend on the number of cylinders in the
valves, gauges and pressure switches, an operat-
manifold system. Also, it will depend on the
ing and indicating system, an exhaust system and
space required for storage of the filled cylinders
a test point.
and the empty cylinders. The movement area
342 30 Piped Medical Gas Supply System (MGPS)
First of all, the Electric Motor and the air com- ture and oils. These contaminants can enter the
pressor is mounted on the base frame, are fabri- compressed air system from three sources: the
cated for this purpose. The coupling of both is atmosphere, the compressor and the pipeline dis-
done with the help of V-Belts. This base frame tribution system. Each potential source must be
(mounted with motor and compressor) is fixed on taken into account when specifying the type and
the pre-constructed foundation with the help of location of air treatment equipment. Filtration
Fasteners. Please ensure to provide the anti- equipment may include pre-filters, coalescing fil-
vibration pads while fixing the base frame as the ters, carbon filters, particulate filters and any
unit creates a lot of vibration when operative. It other additional filtration equipment necessary to
has to be ensured that the compressors shall be provide the appropriate quality.
Oil Free Compressors, failing which there are Similarly, the dirt particles in the environment
chances that the produced air may have traces of cover a wide range of sizes, but approximately
oil, which may be harmful to the patients or med- 80% are less than 0.2 μm and are therefore not
ical devices. The compressors shall either be air- removed by the intake filter to the compressor.
cooled or water-cooled as the design may be. The Although particles smaller than 40 μm are
plant shall have all-round access for maintenance unlikely to cause mechanical damage, a 5-μm
purposes and allowance shall be made for chang- intake filter is preferred, to avoid blockage of
ing major components. internal air/oil separators.
The capacity of the compressors and motors The filtration system can be in different stages
shall depend on the air required and the number depending on the type of filters. It can be from
of outlets. It is measured in cfm. the single-stage filter to four-stage filter.
There shall be a set of two such units as both After passing through the filters the air passes
will be operative reciprocally one after the other to the Air Dryers. As the air contains moisture, it
after a fixed interval of time. needs to be dried before sending it further to the
The outlets of both the compressors are com- user. If it is not dried, the wet air can be danger-
bined and connected to the Air Reservoir. The air ous for the patients and also harmful for the med-
reservoir is a tank made out of thick MS steel and ical equipment where it shall be used. The dryer
is provided with the Air inlet, Air Outlet and the system shall be a twin system so only one is oper-
gate valve to drain the water (collected in the tank ational at a time and the other is on standby. From
due to the moisture in the air). The tank’s capac- time to time switching is done from one to
ity is measured in litres. The capacity for each another. There shall be separate power supplies
design varies as per requirement. It can be from for the ‘duty’ and ‘standby’ dryer assemblies
1000 Ltr. to 5000 Ltr. This tank is installed on the taken from the same phase.
raised foundation (say by 152 mm to 305 mm). Thereafter, the air is connected to the main
From the Compressor, the air is stored in the supply line of the Compressed Air.
reservoir. When required, the air comes out of the The functioning of the air compressors is con-
reservoir through the outlets and is passed trolled by the Automatic / Semi-Automatic con-
through the Filters by increasing the pressure of trol panels. The electric connections to the motors
the air. are done through this control panel. The control
panel switches from one set of compressor units
to the other automatically at the pre-set interval
30.14.2 Air Filtration of time. At any moment of time, both the com-
pressors shall be in a working condition. If one
The air normally contains traces of impurities unit goes out of order, the other unit of compres-
like carbon monoxide, carbon dioxide, sulphur sors shall be able to take the entire load of the air
dioxide, nitrogen monoxide and dioxide, mois- requirement.
30.15 Vacuum 343
30.14.3 Medical Air 400 kPa designing the system. The overall system shall be
designed to provide a minimum of 700 kPa at the
The medical air with a pressure of 400 kPa, is front of each terminal unit at a flow of 350 L/min.
mainly used for the operation of the Invasive
Ventilators. Medical air is also directly inhaled
by patients during ventilation and it may also be 30.15 Vacuum
used to dilute oxygen before administration
because of the potentially toxic effects of pure The medical vacuum pipeline system provides
oxygen. Patient ventilators fall into two main cat- suction facilities for medical needs, particularly
egories—those used during anaesthesia and those in operation theatres and ICUs.
used during intensive therapy. Pneumatically
powered ventilators can use up to 80 l/min free
air continuously. The exact flow requirements 30.15.1 Vacuum Plant
will depend on the design of the ventilator.
Medical air 400 kPa is also used for other The creation of the vacuum is done with the help
equipment such as anaesthetic gas mixers, of the vacuum pumps. The plant consists of the
humidifiers and nebulizers. The flow rates nor- Electric Motors, Vacuum pumps, Vacuum
mally required would not exceed 10 l/min, and Reservoir, Automatic/Semi-Automatic Control
this flow is always in excess of the actual volume Panel and Bacteria Filter with drainage traps
respired. along with the required non-return valves, isolat-
The minimum pressure required at terminal ing valves, gauges and pressure switches, an
units for respiratory use is 355 kPa at flows of operating and indicating system, an exhaust sys-
80 L/min in intensive therapy units and coronary tem and a test point.
care units; 40 L/min in special care units and First of all, the Electric Motor and the vacuum
operating suites and 20 L/min in ward areas. pumps are mounted on the base frame, fabricated
While calculating the flow, the diversity shall for this purpose. The coupling of both is done
also be taken into account considering that only with the help of V-Belts. This base frame
33% of the total points shall be operative at a (mounted with a motor and pump) is fixed on the
time. pre-constructed foundation with the help of
Fasteners. Please ensure to provide the anti-
vibration pads while fixing the base frame as the
30.14.4 Surgical Air 700 kPa unit creates a lot of vibration when operative. It
has to be ensured that the vacuum pumps shall be
The pressure requirements of surgical tools are Oil-Free. Water-sealed pumps shall not be used.
between 600 and 700 kPa and flows may vary It is desirable if the Rotary vane pumps are used
between 200 and 350 L/min. Most surgical tools instead of reciprocating vacuum pumps which
are designed to operate within this pressure are now obsolete. The plant shall have all-round
range. Higher pressures are likely to cause dam- access for maintenance purposes and allowance
age to tools. shall be made for changing major components.
The pipeline systems shall be designed to pro- The capacity of the pumps is measured in lpm.
vide a flow of 350 L/min at 700 kPa at the termi- The exact capacity of the pumps to be installed
nal unit. shall depend on the requirement and number of
Surgical air 700 kPa is only required where vacuum outlets.
surgical tools are to be used like orthopaedic, There shall be a set of two such units as both
neurosurgery theatres and possibly plaster rooms. will be operative reciprocally one after the other
However, to facilitate maximum flexibility, surgi- at a fixed interval of time.
cal air shall be provided in all theatres. The diver- The outlets of both the vacuum pumps are
sified factor of 25% shall be considered while combined and connected to the Vacuum
344 30 Piped Medical Gas Supply System (MGPS)
Reservoir. The vacuum reservoir is a tank made For Operating Rooms, instead of the ward
out of thick MS steel and is provided with the vacuum units, theatre suction units are used.
inlet connected to the vacuum pump, and an out-
let connected to the filtration system. The tank’s
capacity is measured in litres. The capacity for 30.16 Issues While Designing
each design varies as per requirement. It can be the Plant Room
from 1000 Ltr. to 5000 Ltr. This tank is installed and the Manifold Room
on a raised foundation (say by 152 mm to
305 mm). The following issues shall be taken care of:
30.17 M
edical Gases Outlet points. Also, this panel has a service railing on
Terminals which the IV rod, tray and utility basket can be
fixed. This panel is fixed at the height of 1524 mm
The gas outlets are the endpoint of the MGPS above the floor level and goes up to 1829 mm
system. The pipelines carrying the gases termi- (Fig. 30.3).
nate at this point and are connected to the gas out- Another option can be the Ceiling suspended
lets. For further supply of the gases to the user, pendant. This also has the same facilities as in the
the probe is plugged into the gas outlet and gases case of the Bedhead Panel. This panel is fixed on
are provided to the patient. the ceiling and is suspended below so that the
The medical gases outlets are provided bottom of the pendant shall be a 1524-mm from
depending on the type of gasses like O2, N2O, Air the floor.
and Vacuum. It means the outlets shall be sepa- The Gas outlet points are fixed on the back
rate and marked properly for each type of gas. wall of the pendant. On both, the side walls are
The Outlet shall be installed at the patient bed. electrical points and on the front wall shall be the
Some hospitals prefer to affix the outlets of these utility tray for bedside multi-parameter vital sign
gases directly on the wall itself. But nowadays, monitor and also the utility basket can be fixed on
Bedhead panel is used for fixing the gas outlets. the front wall. The pendant can revolve at 270
Bedhead panel is a 1524-mm panel made of degrees. Further, the pendant can be a single arm
extruded sections of aluminium. This panel has or a dual-arm. The single-arm revolves at its own
provisions for fixing the gas outlets and electrical axis only, whereas the double arm pendant can
revolve on both the arms hence covering more on a pre-constructed foundation and is properly
area around the bed. screwed to the foundation with the help of heavy-
duty fasteners. The plant shall be located inside
a fenced compound, which may also house the
30.18 B
ulk Liquid Oxygen Gas control panel and the standby manifold.
System The plant has to be installed outside the hospi-
tal building in the open area only.
In hospitals where the consumption of oxygen is The area required for the vessel shall be about
quite high, it practically becomes difficult to han- 18 m × 9 m. On the front side, the space of about
dle the cylinders. Also, if the availability of the 9 m × 9 m. Shall be left empty for parking the
cylinders is not adequate, the hospital may face vehicle carrying the liquid oxygen to unload the
problems in fulfilling the demand of the oxygen liquid gas into the tank. On all other sides of the
required. Hence, the best option is to consider the tank, a space of 3 m. Shall be left vacant before
installation of a bulk liquid oxygen tank. fixing the fencing. The Vessel area shall have
This tank is used for the storage of any cryo- fencing all around. The vessel area shall have a
genic liquid which can include oxygen, nitrogen 6 m. Door in the front from where the vehicle
and nitrous oxide. The tank is a cryogenic pres- will enter. Normally this door shall be locked and
sure vessel made of stainless steel supported opened only when the vehicle arrives for unload-
within an outer vessel, similar to a vacuum flask. ing the gas. On the side, one small door shall be
The Liquid Oxygen plant consists of the provided, which shall be used for regular moni-
Cryogenic tank, and the coils. The coils have a toring of the plant. This door shall be about
gas outlet, which is connected to the copper pipe- 914 mm wide.
line. Passing through the valves, pressure moni- The flooring of the vehicle parking area on the
tors and pressure controller, this pipeline is front side shall be made out of concrete, which
ultimately connected to the main oxygen supply shall be capable of bearing the load of the
line of the hospital. Working wise, the liquid oxy- vehicle.
gen in the vessel flows to the coils, where it is In the plant enclosure, a running water tap
converted into the gaseous form. This gas then shall be provided, for melting the ice accumu-
flows to the main pipeline for further supply to lated on the copper pipeline from time to time.
the endpoint. Before installing the plant, it may be neces-
sary to comply with local authority planning con-
straints in some areas. Even before installations,
30.18.1 Liquid Oxygen Vessel the drawings have to be approved by the compe-
tent authority like the Explosive Department.
The vessel, as mentioned, is a vacuum flask-type Once completed, an inspection may be done by
capsule made out of stainless steel. Vessels of the department before issuing the licence to oper-
various capacities are available varying from ate the plant (Fig. 30.4).
500 litres to 20,000 litres. The vessel is installed
30.18 Bulk Liquid Oxygen Gas System 347
The Hospital Kitchen shall the following: 31.2 Location of Hospital Kitchen
© The Author(s), under exclusive license to Springer Nature Singapore Pte Ltd. 2022 349
A. Garg, A. Dewan, Manual of Hospital Planning and Designing,
https://doi.org/10.1007/978-981-16-8456-2_31
350 31 Hospital Kitchen
4. Furniture wise, the room shall have a bles which may require good ventilation etc. The
cupboard. following storages are generally required;
5. Almirah shall be provided with the provision Bulk Storage For storage of utensils,
for hanging the clothes. cooking accessories etc.
6. In the change room, staff lockers shall also be Fruit/vegetable storage For storage of vegetables,
provided where the staff can keep their per- fruits etc.
Refrigerator/s, cool For storage of milk and
sonal belongings. Individual lockers shall be rooms and freezers dairy products, meat and
about 305 mm × 305 mm. These individual fish etc.
lockers are combined, and the locker almirah Storage areas for dry For storage of dry ration
can be fabricated. Each locker shall be lock- ration/goods
able separately. One such locker shall be allot- As far as the sizes of the storage rooms are
ted to one staff. concerned, it shall depend on;
Immediately at the exit of the change rooms, 1. The size of the kitchen.
the handwashing area shall be provided. For hand 2. The volume of business.
washing, the sinks shall be provided with a provi- 3. Delivery frequency.
sion of running hot and cold water. The drains 4. The length of storage.
shall be immediately below the wash sink. On 5. The type of storage (frozen, refrigerated or
average, one sink per 10 workers shall be dry).
provided.
31.7 Storage Area This store is used for the storage of perishable
food such as fruit and vegetables. The most
There are different storage rooms depending on important point for this storage is to control the
the properties of the item, like dairy products temperature and humidity level so that the vege-
which may require a cold environment, vegeta- tables and fruits last long. The store shall have the
352 31 Hospital Kitchen
capacity to store material sufficient for at least 4 placed in such a fashion that the air circulation is
days’ consumption. The room shall be provided easy all around the racks. The store shall be at
with bins or baskets made out of stainless steel least 3658 mm × 3658 mm in size, which may be
wire mesh. These wire mesh baskets shall be increased or decreased according to the require-
placed on the racks. The racks shall be placed in ment. Proper care shall be taken for temperature
such a fashion to make air circulation easy all and humidity levels. Also, precautions shall be
around the racks. The baskets of wire mesh bins taken for preventing the store from rodents, for
shall not be overloaded, and spaces shall be left this door brushes can be used.
for proper air circulation. The store shall be at Common to all the storage areas is that the
least 3658 mm × 658 mm in size, which may be food storage components shall be grouped for
increased or decreased according to the convenient access from receiving areas to the
requirement. food preparation areas. All food shall be stored
clear of the floor. The lowest shelf shall be not
less than 305 mm above the floor or shall be
31.7.3 Refrigeration, Cool Rooms, closed in and sealed tight for ease of cleaning.
Freezers
Cool rooms and freezers shall be used for the 31.8 Preparation Areas
dairy products like milk, cheese, butter, cream,
ice cream, meat, fish and frozen vegetables like Food Preparation areas are for preparing the
peas, corn etc. It is also called the refrigerated ingredient before starting the actual cooking pro-
room. The store shall be provided with the cold cess. The food preparation areas shall be separate
room with the temperature ranging from −20 to from the cooking area. The processes normally
2 °C, which shall be adjustable as per require- done in the processing zones are like;
ment. The size of the cold room shall be about
3048 mm × 3048 mm. The walls and the ceiling 1. Peeling and cutting the vegetables
of the room shall be made out of a puff panel 2. Grinding the condiments
which acts as a thermal barrier. The flooring is 3. Meshing the boiled vegetables
generally made out of wooden planks. The door 4. Mixing the items
of the cold room shall also be made out of puff 5. Kneading the flour dome
panel and shall be hermetically sealed. For stor- 6. Meat, Fish and Poultry preparation
age, open racks are provided along the walls. The 7. Pastry/dessert preparation
material is stored either on the shelves of the rack
or otherwise in the baskets made of stainless steel Food preparation areas shall be located at such
wire mesh. Apart from this top-loading deep a place that it has ready access to vegetable/ration
freezer may also be provided if required. storage areas, refrigeration area for supplies. It
shall also be near to the cooking areas, boiling
water units and ice dispensing machines.
31.7.4 Storage Areas for Dry Ration/ The preparation area shall be provided with
Goods the working counters (with granite stone on top),
sinks, shelving and mobile trolleys for utensils.
This storage is used to store the dry goods such as The equipment like food processors, slicers, mix-
pulses, wheat, flour, spices, dry ingredients and ers, grinders, cutters etc. shall be provided. For
cooking condiments etc. The store shall have the the operation of this equipment, the required
capacity for storing materials sufficient for at electrical points shall be provided on the wall
least 15 days’ consumption. The room shall be above the working top. For this, the 6/16 Amp
provided with racks or bins/shelves/drawers etc. switch/sockets shall be provided at a height of
made out of the stainless steel. The racks shall be 305 mm from the top of the working counter. All
31.10 Reheating Areas 353
equipment must be installed according to manu- avoid mixing up and hampering the work of oth-
facturer’s specifications. If possible a few impor- ers. On the backside of these areas, the working
tant equipment shall be connected through the tables (made out of stainless steel) shall be pro-
UPS in the event of power failure. Each prepara- vided to keep the unprocessed material.
tion area shall have one single sink per station for The gas stoves of other such cooking appara-
washing of the food and ration. Hand basins shall tus shall be kept at least 305 mm. away from the
also be provided in these areas with a provision wall. Each such apparatus shall be provided with
of paper towels and soap dispensers. The peeling an area of at least 3.72 m2.
and cutting station shall be provided with a big- Chapattis can either be made on the flat plate
sized waste bin also. designed for this purpose or if the quantity of
Food preparation areas are provided as dis- chapattis is huge, the automatic chapati making
crete areas for the separation of food types. machine shall be installed.
Vegetarian, religious and cultural practices Cooking areas must be properly ventilated,
demand the preparation and serving of food with with an exhaust hood covering the entire area.
strict storage, preparation and serving require- Exhaust hoods must be designed and installed to
ments. Vegetarian and vegan food may need to be prevent grease or condensation from collecting
prepared, cooked and stored separately. Foods for on walls, ceilings and from dripping into food or
particular health issues may include diabetes, onto food-contact surfaces. The exhaust ducts of
food sensitivities or allergies such as lactose and these hoods shall be opened out of the kitchen
glucose intolerance or nut, shellfish or egg pro- area.
tein allergies. The wall of the cooking areas shall have
smooth and washable surfaces. Therefore, it is
better to affix glazed tiles on the walls up to the
31.9 Cooking Areas height of 1524–2134 mm. Similarly, the floors of
the cooking area shall not be slippery, particu-
The cooking area is the most crucial area in the larly after the grease spills and washable. For this
whole kitchen and shall be provided with the matt finish tiles can be used.
maximum area, as there are different means of
cooking the food like boiling, frying, pan cook-
ing etc. Different modes of cooking are used 31.10 Reheating Areas
depending on the menu and may use convection
or conduction heating. Cooking equipment must Reheating means again heating the cooked food
be of commercial quality and will require instal- before it is served in the dining areas. The heating
lation according to manufacturer’s specifications, can be done with the help of the gas burners or
particularly with attention to services required, through devices like microwaves/induction
which may include power, gas, water or steam plates/grills etc.
supply and drainage. If it has to be done with the gas burners, the
Cooking areas will be located in close proxim- same burners can be used, which have been used
ity to food preparation areas and with convenient for cooking. But if the other devices are used, a
access to plating areas. Different sections in the separate area shall be provided. This area shall
cooking area have to be provided for different have a working counter for the tabletop devices
modes of cooking. Say for boiling, a separate to be placed. For the operation of these devices,
space is required to install the boilers. For deep the required electrical points shall be provided on
frying, a separate space for electric deep frying the wall above the working top. For this, the
machine or a gas burner for deep frying, Gas 6/16 Amp switch/sockets shall be provided at a
stove area for preparing the vegetables etc. and a height of 305 mm from the top of the working
flat pan (Tawa) for making chapatis etc. Each counter. All devices must be installed according
section shall have proper low-height partitions to to manufacturer’s specifications. If possible few
354 31 Hospital Kitchen
important devices shall be connected through the For this, the food has to be transported to the
UPS in the event of a power failure. desired location with the help of the trolleys.
If any of these devices are floor mounted, then And as the food has to be loaded from the pack-
adequate foundations and electrical points shall ing/plating area, the trolley/cart parking area is
be provided. If required another working counter required. Therefore, Trolley/Cart parking space
shall be provided opposite to such counter to shall be provided adjoining the plating/packing
keep the pre-heated and post-heated food items. area for temporarily parking the meal trolley
that shall carry the food to the respective
location.
31.11 Packing/Plating The packed food is then loaded in the trolleys/
cart. Service windows shall be provided between
Once the meals are ready after cooking and heat- the plating/packing area to pass on the plates/
ing, the next is to pack the meals or lay them on trays to the trolley parking area to be loaded in
plates to be served to the patients, staff or visi- the trolleys.
tors. In the hospitals, there are different types of If the number of trays to be loaded is more, an
diets to be supplied to the patients as prescribed automatic loading conveyor can be used for quick
by the physicians. Those can be the Normal Diet, loading the trolleys.
Diabetic Diet, Salt-Free Diet, Oil-free diet, Semi- The size of the area will be dependent on the
Solid Diet or Liquid diet etc. number of trolleys to be accommodated.
Hence the packing or the plating has to be done There can be trolleys that keep the food warm,
accordingly with a clear marking on the plate. The and also there can be refrigerated trolleys to keep
Plate shall have a tag where the name, bed num- the food cold to be used for desserts. Therefore,
ber, ward and type of diet are mentioned. to keep the trolleys/carts hot and cold, power is
For such packing/plating, a separate area shall required. So the trolley/cart parking area shall be
be provided in the kitchen. This area shall have a provided with the electrical PowerPoint for plug-
different working counter with granite top. The ging in the trolleys/carts so that they are ready at
cooked food is brought in the packing rooms and the time of loading.
the meals are filled up in the respective trays, The trolley shall also be provided with chains
plates or crockery. These plates/trays/crockery is of other mechanisms like hooks etc., to hold the
properly covered with the silver foil or the wrap- trolleys at a place so that these trolleys/carts do
ping slings. not unnecessarily move.
The plating area equipment will be dependent
on the number of meals to be plated and delivered
to ensure meals are delivered at the correct time 31.13 Food Distribution
and a suitable temperature. In case the high num-
ber of plates have to be prepared, the Plating area After loading the trays/plates in the trolleys/carts,
may be provided with automated plating con- the trolleys/carts are unhooked and moved to the
veyor systems supported by food serving trol- respective wards/rooms or dining areas. The dis-
leys, tableware and utensil trolleys. tribution service must ensure food is delivered to
The tag is fixed on the tops of the plate and the patient hot or cold as required.
kept ready for loading in the service trolley to be The trolleys/cart are wheeled to the respec-
served. tive ward/room/dining rooms and the trays/
plates/ crockery are unloaded at the respective
place.
31.12 Meal Trolley/Cart Parking Once the meals are over and the plates/trays/
crockery is free, these plates/trays/crockery is
The food is required to be distributed in the reloaded in the trolleys/cart and is wheeled back
respective wards, room of the dining rooms. to the trolley wash area in the kitchen.
31.17 Pot Washing 355
The trolleys/carts returning from the wards/ The trays/plates/crockery/cutlery received back
rooms/dining areas after serving food and filled after use have to be washed. Therefore, a dish-
up with the unwashed utensils, shall be brought washing area shall be provided in the kitchen.
to the Trolley Return area. Trolleys will then be This area shall be located near the trolley strip-
taken into the trolley stripping area where the ping area.
dishes, trays, plates, crockery and waste shall be For washing, separate stainless steel sinks and
removed, and the trolley is thus sent to the drainers shall be provided, which shall be fixed
Trolley/Cart Washing area. on the working counter. The sinks shall be deep,
The Trolley Return/Stripping area shall be long and wide enough to wash the utensils. Along
located adjacent to the Dishwashing and the with the sink, a drain board shall also be provided
Trolley/Cart Washing area. There shall also be to drain out the excess water. The sinks shall have
convenient access to the Waste Disposal area. the provision of running hot and cold water with
The Trolley Return/Stripping area shall have a a flexible hose spray. Also, a provision shall be
provision of proper wall guards and corner guards made on the wall for detergent dispensers and
to prevent edges of the walls being damaged due sponge holders.
to the impact of the trolleys hitting the walls. After washing and drainage, space shall be
The provision of handwashing shall also be provided for sorting the utensils. Once sorted,
given in the trolley stripping area. there shall be a space for stacking the utensils. For
stacking, a wooden stripped cupboard can be
fixed on the wall or alternately racks can be pro-
31.15 Trolley/Cart Wash vided. The stacking can either be done in the dish-
washing area or otherwise in the packing/plating
After unloading the trolleys/cart, they shall be area. If the number of utensils to be washed is
moved to the trolley washing area. This area shall more, automatic dishwashers may be used.
be provided for washing/disinfecting and drying of Crockery, utensil and cutlery washing facili-
trolleys and carts making them ready for the next ties shall be located as far as possible from the
use and sending them to the parking area for load- food preparation and serving area. Washing facil-
ing. There must be a clear flow from dirty to clean ities shall be designed to prevent contamination
to prevent cross-flow of dirty with clean items. of clean wares with soiled wares through cross-
The Trolley Wash area shall be located traffic. The clean wares shall be transferred for
remotely from the food preparation and storage storage or used in plating, serving or dining areas
areas with convenient access from the Trolley without having to pass through food preparation
Return/Stripping area. The Trolley Return/ areas.
Stripping area shall have a provision of proper
wall guards and corner guards to prevent edges of
the walls being damaged due to the impact of the 31.17 Pot Washing
trolleys hitting the walls.
The trolley wash area shall have the provision The kitchen shall also have a pot washing area for
of running hot and cold water. Also, a compressor washing and cleaning the pots and big utensils
system shall be provided to pressure clean the used for cooking the food. For this, a separate
trolleys and to remove dirt or greasy components enclosure shall be provided near to the cooking
on the trolley. Similarly, the area shall have a pro- area.
vision for trolley drying area, may with the hot In this area, low-level taps are provided at the
air blowing system. If the trolleys to be washed is height of about 610–914 mm from the floor level
more, an automated trolley/cart washing equip- giving enough space to move and rotate the pots
ment may be provided. below the taps. The taps shall have a provision of
356 31 Hospital Kitchen
running hot and cold water. If required, an arrange- provision of fixing 6 to 10 cylinders at a time. From
ment for pressure cleaning can also be provided. the manifold, the copper pipeline is laid down on
On the backside, a stripped stainless steel rack the wall from which it is then connected to the
shall be provided which shall work as a drain burner by the flexible gas pipe. But now a days, the
board to drain out the excess water from the pots. cooking gas is provided through the piped gas lines
Once the pots are dry, they are sent back to the (PNG). If so, the cylinders are not required and the
cooking area. burners can be directly connected to the gas pipe-
If the number of pots is more and manual line with the help of the flexible pipe.
cleaning is not possible, an automatic pot wash- For storage of the stock of filled cylinders and
ing machine can also be provided. the empty cylinders, a separate enclosure shall be
provided near the manifold room. Both these
areas, the manifold room and the gas store shall be
31.18 Waste Disposal enclosed with the help of wire mesh structure. No
wall shall be constructed for these areas. Be very
In the kitchen, a lot of waste is generated from careful while designing these areas and that it shall
the cutting/peeling areas and the leftover waste in be fully protected from any chances of fire nearby.
the utensils. The waste can be either wet or dry. The size of the manifold shall depend on the
Hence a proper provision shall be made for regu- number of cylinders. But on average, for a mani-
lar removal and disposal of such waste in accor- fold of 10 cylinders, the room size shall be about
dance with the Waste Management guidelines 3658 mm × 3658 mm. Similarly, the size of the
and policies. gas store shall also be 3658 mm × 3658 mm.
For handling and disposal of such waste, a
separate waste disposal area shall be provided
near and adjoining the kitchen. This room shall 31.20 Staff and Support Areas
be about 3048 mm × 3048 mm and shall have a
door that shall open outside the kitchen. The There shall be a small administrative area to con-
room shall contain big-sized waste bins with a trol and monitor the functioning of the kitchen.
disposable biodegradable polythene bag. In the Hence the following rooms shall be provided in
kitchen side, a window shall be provided from the kitchen.
where the waste can be thrown in the bin placed Offices shall be provided for
in the waste disposal room.
All garbage, and in particular wet waste, shall 1. Kitchen Manager
be stored in sealed bins. A provision shall be 2. Dietician
made for the removal and cleaning of these waste 3. Dietetics Staff
bins from time to time. Inside the room, space
shall also be provided to wash the bins before the These rooms are for the general administra-
next use. For this, a tap shall be provided in the tors and clerical staff managing the kitchen. The
waste disposal area. staff can be like Managers, Dieticians, Asstt.
Dieticians etc. The size of these rooms shall be
about 4572 mm × 3658 mm. But depending on
31.19 Gas Storage Closet the requirement and number of persons likely to
sit, the size can be increased or decreased. The
Usually, the cooking gas is required in the kitchen. room shall have an adequate arrangement of cab-
The best way to supply the gas to these burners is inets, drawers and racks for a smooth working.
through pipelines instead of keeping gas cylinders The office tables and chairs shall also be pro-
at each point. Therefore, a gas manifold room shall vided. Preferably the room shall have an attached
be provided at a convenient place outside the Toilet. If required a separate room for the staff
kitchen. This area shall be open to the sky and shall shall be provided. The room shall also have
not be a closed room. The manifold shall have a proper arrangements for electrical points, inter-
31.21 General Issues About Infrastructure Requirements 357
(a) Voice and data points for telephones and Fire extinguisher Refrigerators
computers with internet access. Flat cooking pan Rubber floor mats
(b) Wireless internet provision for Offices, Fryer Shredders
Meeting rooms. Glass washer Spatulas
(c) Data provision for management and Griddles Stainless steel tables, benches
quality systems as required. Grill Vegetable cutters/choppers
Grinders Waste bins large size
13. Hand Basins
Sufficient number of Handwashing basins
shall be provided in all clean-up, preparation,
cooking, serving areas of the Unit. Staff in Further Reading
food preparation and serving areas shall not
JK B. Cafeteria Design Guide | Architectural Design
be more than 6000 mm from a hand washing
[Internet]. Architecture Student Chronicles.
basin. Basins shall be hands-free operation 2012 [cited 2021 Jul 10]. Available from: http://
with a paper towel and soap dispensers. www.architecture-s tudent.com/design-g uide/
Mirrors shall not be installed over basins in cafeteria-design-guide-architectural-design/
Andersen BM. Hospital Kitchen. In: Andersen BM,
food preparation areas where contamination
editor. Prevention and Control of Infections in
from touching hair may occur. Hospitals: Practice and Theory [Internet]. Cham:
1 4. Grease Traps Springer International Publishing; 2019 [cited
Grease traps shall be provided in the 2021 Jul 10]. p. 995–9. Available from: https://doi.
org/10.1007/978-3-319-99921-0_77
kitchen area to prevent Food, oil and grease
Hospital kitchen design - Hospital kitchen layout | Food
from entering the drainage system. These Strategy [Internet]. Commercial Kitchen Designers
grease tanks shall have odour tight lids/air- Brisbane | Food Strategy Australia. [cited 2021 Jul
tight to stop airborne bacteria from contami- 10]. Available from: https://www.foodstrategy.com.
au/projects/hospital-kitchen-design-ideas/
nating preparation/cooking surfaces.
Hospital Kitchen Design For Optimal Foodservice | LaBel
[Internet]. LaBel Foodservice Equipment & Design.
[cited 2021 Jul 10]. Available from: https://labelfood-
31.22 Fixtures, Fittings service.com/blog/hospital-kitchen-design-planning
Hospitals take a fresh look on cafeteria design [Internet].
and Equipment [cited 2021 Jul 10]. Available from: https://www.hfm-
magazine.com/articles/3181-hospitals-take-a-fresh-
Some of the equipment, devices and cookware look-on-cafeteria-design
required for the kitchen are Moatari Kazerouni A, Chinniah Y, Agard B. Integration
of occupational health and safety in the facility layout
Blenders Induction stove planning, part II: Design of the kitchen of a hospital.
Boilers Juicer Int J Prod Res. 2014 Oct 27;53:1–15.
Burners Kettles Kitchen Design: Intermountain Hospital’s Efficient
Chapati maker Kitchen knives Kitchen and Bistro [Internet]. Foodservice Equipment
Cookers and steamers Ladles Reports, Articles & News | FER Magazine. 2019 [cited
Cooking ranges Microwave ovens 2021 Jul 10]. Available from: https://www.fermag.
com/articles/9541-k itchen-d esign-i ntermountain-
Cooking utensils Mixers
hospitals-efficient-kitchen-and-bistro/
Deep freezers Nutcracker Principles of Commercial Kitchen Design [Internet].
Dish warmer Ovens WebstaurantStore. [cited 2021 Jul 10]. Available
Dish washer Pans and cooking spoons from: https://www.webstaurantstore.com/article/6/
commercial-kitchen-design.html
Laundry
32
Laundry service is responsible for providing an Hospital Laundry Central Storage Area
adequate, clean, sterilized and constant supply of Dirty Receipt
linen to all users. Their basic tasks include sort- Mending and Tailoring
ing, washing, extracting, drying, ironing, folding, Sorting/Weighing
Washing
mending and delivery. The main purpose of this
Ironing
department is to provide clean material to the
Packing
patients and ensure that hygiene is maintained in Clean Storage
the process. General Storage
Hospitals can set up laundry in three ways: Public Utility for Staff
First, the hospital can purchase laundry equip-
Laundry shall have the facilities for the fol-
ment and employ workers to operate the laundry
lowing areas;
inside the hospital premises. Second, the hospital
can provide space for laundry and hire a contrac- 1. Central storage space for collecting linen
tor for setting up the equipment and operate laun- from interim storage.
dry. Third, the hospital can enter into a contract 2. Space for installation of equipment like
with a local laundry service, in which case the washing machine, extractor, dryer etc.
contractor carries dirty linen to the off-site/local 3. Provision for an adequate supply of hot and
laundry and brings it back after washing and cold water.
processing. 4. Provision for power supply.
5. Place for installing the boilers (if required).
6. Storage place for cleaning agents and
32.1 Facilities and Space detergents.
Requirements 7. Space for sorting the soiled linen.
8. Clothesline to dry washed linen in the sun.
Laundry infrastructure has the following setup: 9. Place for sewing and mending area.
10. Place for ironing.
11. Office space for the management of the
laundry.
© The Author(s), under exclusive license to Springer Nature Singapore Pte Ltd. 2022 359
A. Garg, A. Dewan, Manual of Hospital Planning and Designing,
https://doi.org/10.1007/978-981-16-8456-2_32
360 32 Laundry
32.2 Location of the Laundry Complex, OPDs etc. This soiled linen has to be
replaced by washed and sterilized linen for the
The Laundry shall be located in the service area next use.
of the hospital, with close access to the clean and Following are the various types of linen that
dirty loading dock areas. The surrounding area are normally used and washed in the hospital
should have ample daylight and natural ventila- laundry:
tion. Ideally, it should be on the ground floor of Bedsheets Doctors OT dress and Gowns
an isolated building connected or adjacent to the Draw Sheets Theatre drapes
water and power plant. Blankets Napkins
Towels Kitchen Cloths
Patient dress Curtains
Patient gowns Uniform of the staff
32.3 Size of the Unit Pillow Covers Screens Cloths
Doctors Apron Staff Apron
The size of the Laundry area will depend on the
size of the hospital, the total load of the linen to Infrastructure of Laundry
be washed per day, and the number and type of (Figure 32.1)
laundry equipment to be installed. The size shall
also depend on factors like the amount of storage
required for standard conditions, allowance for 32.5 D
irty and Soiled Linen
reserve clean linen and dirty holding in emergen- Interim Storage
cies, and the frequency and reliability of linen
supply and collection services. The sorting of dirty and soiled linen starts right
from the point of use of linen. As mentioned at vari-
ous places in this book, Dirty Utility has to be pro-
32.4 D
irty and Soiled Linen vided at different location of the hospital, which
Generation contains a hamper to collect all dirty linen. It is also
a place where contaminated linen is initially sepa-
During routine hospital operations, soiled linen is rated, which shall be put in the colour-coded plastic
generated from various departments like Indoor bags. From here, the linen is collected using a trol-
patient wards/rooms, Operation Theatre ley and carried to the Central Storage Area.
32.6 Central Storage Area received daily and the average time for which the
dirty linen stays in this room. However, a room of
This is an area where soiled linen is exchanged 3658 mm × 4267 mm shall be sufficient. The
with the washed linen. room shall have two doors, one from where the
As linen is stored in the central storage area linen shall be received and the second that opens
for a short time before it is taken to the hospital in the sorting and weighing area. As the linen is
laundry, one portion of the central storage area is delivered through the trolleys, there shall be suf-
demarcated for the soiled linen, collected from ficient space outside the room for parking the
various interim storages of the hospital. This area trolleys. If required, racks or shelves shall be pro-
can be provided at a convenient place either vided to store the linen. This linen is then trans-
inside or outside the hospital building. The size ferred to the sorting and weighing room for
of the room shall depend on the quantity of the further processing.
linen received daily and the frequency of trans-
porting the soiled linen to the laundry. The room
shall be provided with racks to store the sorted 32.8 Sorting and Weighing
and packed linen. The room shall also possess
transport trolleys for transporting the soiled linen As mentioned earlier, the initial sorting of the
to the laundry. Adequate trolley parking bay shall soiled linen is done in the central storing area of
also be provided with this room. the hospital. Further, different items requiring
This Central Storage area shall also have a different washing conditions such as tempera-
separate room which shall be used only for the ture, detergent, and length of wash cycle are
storage of clean linen. Please ensure there shall sorted here. The received linen is divided into
be no mixing of clean and soiled linen, else it two basic loads: a load that will require drying
may lead to cross-contamination. The entrance to after washer-extracting and a load that will
this room shall be totally separate and managed require ironing.
by separate staff. The size of the room shall Items that need mending or stain removal will
depend on the quantity of washed linen received be separated so that they can be dealt with accord-
daily from the laundry and the frequency of issue ingly. Depending on the size and type of facility,
of washed linen to the departments. The most soiled linen should be pre-sluiced, either in a
important thing to consider is that as per the hos- suitable sluicing machine or in stainless steel
pital policy, how many day’s stocks the manage- tubs, which must be provided in this area.
ment desires to keep for emergency situations. The linen is also sorted according to the type
The room shall be provided with racks to store of fabric, item, colour, degree and type of soiling,
washed linen. The room shall also possess trans- and load sizes to suit the washer-extractors capac-
port trolleys for transporting linen to the user ity. For this, the room shall be provided with
department. Adequate trolley parking bay shall stainless steel tables. After sorting, items should
also be provided. Please ensure that trolleys for be placed in trolleys compatible with the loads
the supply of washed linen shall be separate from allowed in the washer-extractors.
the trolleys used for soiled linen. It is better if The size of the room shall depend on the quan-
closed trolleys are used for this purpose. tity of the linen. However, a room of
3658 mm × 4267 mm shall be sufficient. The room
shall have two doors, one attached to the receiving
32.7 Dirty Receipt room and the second opening in the washing area.
This area also includes processes like extraction, extractor. Earlier, hydro extractors were used as a
drying, and ironing. The main areas required for separate machine, in which linen was taken out of
the working of different machines are: the washer and loaded in the extractor for drain-
ing water. But nowadays, most washers have an
inbuilt extractor. However, if separate extractors
32.9.1 Loading and Washing are used, they shall be installed on a pre-
constructed foundation and shall be screwed
Once the linen has been sorted, weighed, and has using fasteners. Also, vibrations occur during the
arrived in the washing area, it shall be loaded into operative of the washer; thus, appropriate anti-
the washers. The washers are generally front- vibration pads shall be provided to protect the
opening washing machine. Machines are avail- machine. As balancing and levelling is an impor-
able different in capacities and shall be chosen tant thing to consider while installing an extrac-
according to the requirement. tor, the alignment of the extractor must be
Washers are installed on a pre-constructed accurate. For operating the extractor, adequate
foundation and shall be screwed using fasteners. power supply shall be provided. For draining the
Also, vibrations occur during the operative of the water from the extractor, drain pipes shall be pro-
washer; thus, appropriate anti-vibration pads vided which shall terminate in a common drain.
shall be provided to protect the machine. The Like washers, extractors are also installed at a
washer shall be connected to separate hot and distance of about 610 mm from the wall for better
cold water supply. There are different options cleaning of the laundry. A common drain pipe of
available for heating the water required for wash- about 152 mm diameter shall be provided on the
ing, like steam heating, gas-fired burners or elec- back of the washers to which all drain pipes shall
tric heaters. If steam is to be used, the washer be connected. In front of the washer, a clear space
shall be connected to the boiler, if gas-fired burn- of 1829 mm shall be provided for easy loading
ers are to be used, the connection is done with the and unloading of the linen.
gas supply system, and if the electric heater is to Usually, at least two such extractors shall be
be used, adequate power supply shall be provided provided in the laundry. But depending on the
to the washer. Washer-extractors are normally linen load and the future expansion plans, space
arranged against the perimeter of the laundry for more than two washers shall be planned well
wall, and the drain-off is discharged into a floor in advance.
drain channel, which is covered by a gate. The
washers shall be installed at a distance of about
610 mm from the wall for better cleaning of the 32.9.3 Tumble Drying
laundry. A common drain pipe of about 6 inches’
diameter shall be provided on the back of the This process entails reducing the moisture con-
washers to which all drain pipes shall be con- tent of the washed linen, for making it suitable
nected. In front of the washer, a clear space of for ironing. Tumbler dryer is loaded from the
1829 mm shall be provided for easy loading and front, with the linen, which has been processed in
unloading of the linen. the extractor and is then dried in the dryer through
Usually, at least two such washers shall be heat. Dryers operate and heat with gas, steam, or
provided in the laundry. But depending on the electricity. They are installed on the pre-
linen load and the future expansion plans, space constructed foundation and shall be screwed
for more than two washers shall be planned well using fasteners. Like washers, dryers are also
in advance. installed at a distance of about 610 mm from the
wall for better cleaning of the laundry. In the
front of the dryer, a clear space of 1829 mm shall
32.9.2 Extractors be provided for easy loading and unloading of the
linen.
After washing, excessive water has to be drained Dryers must be vented directly outside of the
out of the linen. This is done with the help of the building, and these should preferably be located
32.10 Inspection and Repairing 363
next to an external wall. They can be placed side linen comes into contact with approximately
by side or in a separate room that is well venti- 300° of its circumference. The linen is fed into
lated at the back. Dryers generate the most heat the iron by a series of belts that span across the
of all the equipment in the laundry, and all hot air bed and the contact surface of the roller.
should be relayed outside. The machines have a return-feed but can be
Usually, at least two such dryers shall be pro- set up for through-feed. With a return-feed ironer,
vided in the laundry. But depending on the linen a single person can operate the machine, which
load and the future expansion plans, space for can be positioned against a wall to conserve
more than two washers shall be planned well in space. The temperature of the roller and the
advance. degree of contact of linen with the roller ensures
adequate ironing and drying process. An auto-
matic folding process can also be fitted.
32.9.4 Ironing Another type of calendar machine is the bed
and chest heating calendar, in which instead of
This is the last stage of the washing process, and rollers, the bed and chest of the machine are
a separate area shall be provided in the laundry heated. These irons can have up to four large diam-
for ironing. In this zone, various types of ironing eter rollers. The bed is lined with ‘clothing’ to
machines are installed, which depends on the transfer the heat from the bed to the linen and
type of linen to be ironed. Some examples of ensure a clean and smooth passage of the flatwork
ironing machines are: through the machine. Most of these machines are
through-feed machines. The linen has approxi-
32.9.4.1 Pressing Machines mately 180° contact with the rollers. In the end,
This is used to iron clothes like shirts, pants, uni- the linen can be folded manually or automatically.
forms, curtains etc. This machine is available Dry irons with a return-feed mechanism are
with either single or double heated bucks and usually placed near the perimeter wall, but the
may use electricity or steam for heating the multi-roller heated-bed irons are free-standing
bucks. Compressed air is used to rotate and lift and require considerably more space. In the front,
the bucks, as well as for the pressing operation; a clear space of 1829 mm shall be provided for
thus a compressed air point shall be provided in easy working of the personnel. Usually, one
the laundry near the pressing machine. These machine is enough in the laundry. But depending
machines are usually operated manually or by on the linen load and the future expansion plans,
foot in conjunction with a pneumatic system for space for more than two washers shall be planned
the pressing operation. well in advance.
The pressing machine is a floor mounting
model and is screwed to the floor using the help 32.9.4.3 Flat Irons
of fasteners. It shall be installed at a distance of This is the normal domestic iron and is used for
about 610 mm from the wall for better cleaning the small cloths and dresses of the hospital (which
of the laundry. In the front of the machine, a clear are not possible to be done on the pressing
space of 1829 mm shall be provided for easy machine). This iron requires electric power point
working of the personnel. Usually, one machine and a wooden table of size 1219 mm × 914 mm
is enough in the laundry. But depending on the and can be installed at any convenient place in the
linen load and the future expansion plans, space ironing area adjoining the wall.
for more than two pressing machines shall be
planned well in advance.
32.10 Inspection and Repairing
32.9.4.2 Calendar Dryer Irons
The calendar ironing machine is basically used An important function carried out by the laundry
for ironing bed sheets. Flatwork irons usually department is the mending and repairing of torn
have a single large diameter heated roller, and the linen. As said earlier, the linen requiring repairs
364 32 Laundry
or mending are is sorted separately. Mending is patched either to the user department or the
done after washing the linen, as handling soiled central storage provided in the hospital. This
linen involves a high risk of infection. Please note room shall be about 3658 mm × 3658 mm in size,
that the linen to be mended is washed separately provided with a dispatch counter or an office
and not mixed with the other linen. A separate table with chair for administrative work. It shall
mending room is provided in the laundry which have two doors, one shall open in the clean stor-
is equipped with a stainless steel working coun- age room, and the other shall open outside the
ter, foot-operated sewing machine, and patching dispatch room from where the linen will be dis-
machine. The size of the mending room shall be patched. As linen is delivered through trolleys,
about 4267 mm × 3658 mm, and adequate elec- there shall be sufficient space for parking the trol-
tric points shall be provided to operate sewing leys outside the room.
machines or cutters. Storage supplies such as
threads, needles, repair fabrics and other haber-
dashery requirements shall be provided. 32.13 Trolley Washing
32.15 Staff and Support Areas other particle contaminants cannot enter the clean
linen processing area and settle on the shelves,
The laundry shall be provided with an administra- carts, or clean linen that is packed and delivered.
tive room to control and monitor the functioning of
the laundry. The size of the rooms shall be about
4572 mm × 3658 mm, but depending on the 32.16.3 Floors
requirement and number of persons likely to sit, the
size can be increased or decreased. The room shall Floors of the entire laundry shall be impervious,
have an adequate arrangement of cabinets, draw- non-slip in wet areas, easily cleaned, and robust to
ers, and racks for a smooth working. Office tables allow equipment to be moved over them without
and chairs shall also be provided in the room. The lifting or cracking. In the washing area and areas
room shall have an attached toilet. If required, a where the release of water may be occasionally
separate room for the staff shall be provided. The unavoidable, floors should be adequately drained.
room shall also have proper arrangements for elec-
trical points, intercom connection, IT network,
CCTV surveillance, and air conditioning. 32.16.4 Walls
through the ducts which shall be terminated out- such as a sprinkler system, hydrant supply, smoke
side the wall of the laundry. These include tum- detectors and fire extinguishers shall be installed
ble-drying, where dryers should ideally be in the laundry.
accommodated in a separate section.
32.16.12 Communications
32.16.8 Compressors
The following IT/Communications systems may
Certain washer-extractors in the laundry require be provided within the Linen Handling Unit:
compressed air for their operation. A separate
compressed air supply should be used for this 1. Telephones in linen holding areas, linen
purpose instead of medical compressed air. inspection and mending rooms, offices and
Compressed air needs to dry, as required by the workstations.
equipment suppliers. Moisture-trapping arrange- 2. Data outlets for computers/internet access to
ments must be provided in the system design. offices, workstations and delivery rooms.
3. Scanning systems for registering received
supplies or dispatch.
32.16.9 Steam
Quality Assurance Hospital Linen and Laundry Services. 2021 Jul 10]. Available from: https://www.cleanin-
2015;6(3):4. diajournal.com/time-to-relook-at-infection-control-
Time to relook at infection control practices for hospital practices-for-hospital-linen/
laundry [Internet]. Clean India Journal. 2020 [cited
Medical Record Department (MRD)
33
Medical Record is the systematic documentation enables to enter patient data at the point of care
of a patient’s medical history and current treat- and allows authorized clinicians to access
ment and care given to the patient. It serves as a patient’s records from any online location, at any
basis for planning future patient care, document- time, for assessments and further treatment of the
ing communication between the hospital and any patient. An EMR system also requires scanning
other health professionals contributing to the of miscellaneous paper records that may be
patient care, and assisting in protecting the legal sourced from outside the facility or brought in by
interest of the patient and the hospital responsible the patient.
for patient care.
It also serves as a document to educate medi-
cal students and resident physicians, to provide 33.2 Location of MRD
data for internal hospital auditing and quality
assurance, and to provide data for medical As several departments may have to refer or visit
research. the MRD frequently, it shall be located within the
In earlier days, most of the medical records hospital building, in a low activity area. The loca-
used to be in hard copies and were to be stored. tion necessarily need not be in direct access to the
Now with the development of the information patient. If the hospital has a basement, the MRD
technology, most of the records are being shifted can be located in there, or otherwise on floors that
to electronic and digital modes. But still, 100% are not a fast movement zone. Sometimes, due to
record cannot be maintained digitally, and some shortage of space, the department can be located
of the records have to be maintained in hard cop- in another building but in close vicinity to the
ies. Therefore, the MRD shall have an excellent hospital building. MRD shall be located within
set up of information technology for the effective easy walking distance from the admitting or out-
preservation of the medical records. patient department to ensure that the staff can
easily refer files and retrieve records on an emer-
gency basis.
33.1 E
lectronic Medical Records
(EMR)
© The Author(s), under exclusive license to Springer Nature Singapore Pte Ltd. 2022 369
A. Garg, A. Dewan, Manual of Hospital Planning and Designing,
https://doi.org/10.1007/978-981-16-8456-2_33
370 33 Medical Record Department (MRD)
shall be provided for temporarily storing the cupboard to temporarily store the files that are
records until they are sent for further processing. being used for the statistical analysis.
The room shall have a computer with a printer
connected to the computer network of the
hospital. The record-keeper shall check the
33.9 Computer Lab
record and confirm it with the checklist provided
in the system. As maximum records are on electronic digital
The sorting and compilation room shall have a media, the data in the medical records have to be
proper partition for storing the sorted and fed in the workstations. Hence, a separate room
unsorted files separately. This room shall have of about 4572 mm × 3658 mm shall be provided
access to the dictation room and photocopy and to be used as a computer lab. The room shall be
scanning room. provided with working tops for installing work-
stations connected to the hospital network to
carry out the work of data feeding and retrieval.
33.7 Indexing and Coding The number of workstations shall depend on the
requirement and workload of the MRD. The suf-
This desk may be used for medical records, cod- ficient number of chairs to sit and storage cup-
ing forms, coding books, and compiling disease boards shall also be provided in the room to
and operative indexes manually. As most of the temporarily store the files that are being used for
indexing and coding work is done on a computer, the data feeding or the retrieval of the data.
the room shall have a computer with a printer
connected to the computer network of the hospi-
tal. After sorting and compilation, the record is 33.10 Medical Record
indexed and coded as per the ICD codes. Storage Room
For indexing and coding, a separate room
shall be provided in the MRD. This room shall be Depending on the country’s local statutory
located adjoining the compilation room so that requirements/guidelines, medical records have to
the record can be easily transferred from there. be stored for a long time which can anywhere
The size of the room shall be about between 7 and 15 years after last attendance,
4267 mm × 3658 mm. The room shall have one whereas the Medico-Legal Records may have to
door, which shall open in the MRD. The room be stored for a longer period. Thus, records must
shall be provided with office tables and chairs. A be stored in a fire-rated construction as indicated
filing rack shall be provided for temporarily stor- in the local building bylaws. Active medical
ing the records until they are sent for further records in constant use shall be stored in open
processing. metal shelving units to provide easy access. The
size of the storage room shall depend on the load
of the patients and the beds in the hospital.
33.8 Statistical Analysis However, the recommended size is about 93 m2
for a 300-bed hospital.
A room shall be provided in the MRD for statisti- For storing medical records, compact slidable
cal analysis of the data relating to the medical units may be used. Storage cabinets shall be lock-
records. As maximum records are on electronic able, and storage of records in the open shelves or
digital media, the analysis is done on and from racks shall not be allowed. The systems shall
the workstations. Hence, a separate room of have 7 shelves. On an average, if the shelf is
about 3658 mm × 3658 mm, with an office table 1219 mm long and proper adjustable partitions
and chairs, shall be provided. The room shall also are given, it can accommodate about 1000 records
be provided with workstations connected to the files. If there are 7 such shelves, it can house
hospital network. The room shall have a storage about 7000 record files. The highest shelf should
372 33 Medical Record Department (MRD)
not exceed 2134 mm and be reachable by staff be of size 4267 mm × 3658 mm and shall be
using a library step stool. The highest shelf for noise and echo proof, so that the staff can listen to
staff reach, without a step stool, should not be the transcription machines. This room should be
higher than 1829 mm. Aisle between bays of located between the entry area and the sorting
shelving should have a minimum width of room. The room shall be provided with an office
762 mm, however, 914 mm is recommended to table, chair, computer and transcription machine.
allow space for records trolleys, library stools, The required power and data provisions shall be
and staff transit. provided.
If the management of the hospital does not
want to use the compacted slidable system, the
open file rack system shall be opted for; however, 33.13 Photocopying/
the adequate arrangement shall be done to pre- Printing Room
vent the record from fire, termite, and pilferage.
The storage area shall have a properly air- A room for photocopying and printing shall be
conditioned room of about 3048 mm × 3048 mm provided in the MRD. The room shall be about
for storage of CDs/DVDs and hard disks on 3658 mm × 3658 mm with a photocopy machine,
which the data backup of electronic digital computer workstation, office table, and chairs.
records has been taken. The room shall be pro- This space may also be used for generating bar
vided with a properly sealed, fireproof cabinet to code labels and stationary storage. The room
keep these items. shall also be provided with cupboards for storing
The room shall also be provided with step stationery to be used in the MRD.
stools, chairs and working tops made out of stain-
less steel. The doors of the room shall be properly
sealed and provided with the door brushes to pre- 33.14 Scanning Room
vent rodents from entering the room. All electric
cables shall be properly covered to prevent any At times, some of the documents, particularly
short-circuiting. Fire sprinklers shall not be the documents brought from outside by the
installed in the storage area. Records storage patients or the paper documents created in the
areas must be temperature and humidity con- hospital, need to be scanned to record them in
trolled for the preservation of records. the electronic digital records. Therefore, a scan-
ning room shall be provided in the MRD. This
room shall be about 3658 mm × 3658 mm with
33.11 Dictation Room/Cubicles a provision of the office table, chairs, worksta-
tion, and a good quality multi-sheet high-resolu-
This area is used by the medical staff and others tion scanner.
to view and research medical records, as well as
dictating and completing the discharge summa-
ries. The cubicles should be located on the perim- 33.15 Binding Room
eter of the unit, adjacent to, but inside the
reception area. The number of cubicles will As medical records have to be stored for a long
depend on usage. The auditory separation of per- period, they shall be properly indexed and bound
sonnel is preferred, as extraneous noise will be before storage. Therefore, a binding room shall
distracting to the person dictating. The required be provided in the MRD. The room shall be about
power and data provisions shall be provided. 3658 mm × 3658 mm with a provision of at least
one office table, chair, and working top for bind-
ing of the records. Binding shall be done for
33.12 Transcription Room paper-based medical records. For electronic digi-
tal record, hard disks, CD’s or DVD’s shall be
A room in the MRD shall be provided for the packed in the binding room and kept ready for the
transcription of medical records. The room shall storage. The room shall also have a storage cup-
33.19 Other Issues About the Infrastructure of MRD 373
board to temporarily store the files, registers or room. The room shall also have proper arrange-
any other paper-based records that have to be ments for electrical points, intercom connection,
bound. IT network, CCTV surveillance, and air
conditioning.
For other staff members, smaller rooms of size
33.16 Waste Holding Room 3658 mm × 3658 mm shall be provided. The
room shall have an adequate arrangement of cab-
The documents discarded in the MRD shall be inets, drawers, racks, office tables, and chairs for
destroyed in this room by shredding. The room a smooth working. The room shall also have
shall be about 3658 mm × 3658 mm with a provi- proper arrangements for electrical points, inter-
sion of the office table, chairs, a high capacity com connection, IT network, CCTV surveillance,
shredding machine and waste holding bins. and air conditioning.
The secretarial room shall be about
6096 mm × 4572 mm in size. The room shall
33.17 Store have an adequate arrangement of cabinets, draw-
ers, racks, office tables, and chairs for a smooth
A store shall be provided in the MRD for stor- working. The room shall have an attached toilet.
age of general items, stationery, unused old If required, a separate store shall be attached to
equipment, and other daily used items. The store this room. The room shall also have proper
size shall be 3048 mm × 3048 mm, which may arrangements for electrical points, intercom con-
be increased or decreased according to the nection, IT network, CCTV surveillance, and air
requirement. Adequate lockable cupboards, conditioning.
racks, drawers and countertops shall be pro-
vided in the store.
33.19 O
ther Issues About
the Infrastructure of MRD
33.18 Administrative Area
1. Temperature, Colour and Lighting
The MRD shall have separate rooms to be used Care shall be taken about environmental
for general administrators, managers and clerical factors such as temperature, humidity, and
staff managing the MRD. The rooms shall be ventilation. These factors have a direct effect
provided for: on the records stored in the MRD.
2. Protection from Fire
1. In-charge MRD The entire MRD, especially the filing area
2. Medical Record Officer of records and X-rays, should be fire protected
3. Coders by installing fire extinguishers and smoke
4. Data Analyst detector. Important documents like medico-
5. Secretarial staff legal cases should be preserved in fire-proof
cabinets. All electrical lines should be cov-
The size of the room shall depend on the des- ered to avoid short-circuiting.
ignation of the staff. The rooms of the In-charge 3. Protection from Rodents and Termite
and Medical Record Officer shall be about The MRD section shall be designed to
4572 mm × 4267 mm. The room shall have an make it free from vermin, silverfish and other
adequate arrangement of cabinets, drawers, insects likely to attack and destroy the records.
racks, office tables, and chairs for a smooth work- Provision shall be made for proper wire mesh
ing. The room shall have an attached toilet. If or door brushes. Also, MRD shall have a
required, a separate store shall be attached to this sealed ceiling with no air gaps or leakage.
374 33 Medical Record Department (MRD)
Regular pest control treatment must be carried the best, accurate, and quickest mode of trans-
out in thein MRD. portation for documents, specimens, materials
4. Natural Light/Lighting and medicines. One station of the PTS shall
Wherever possible, use of natural light be provided in the MRD for receiving docu-
shall be maximized for easy working of the ments and records from different locations of
staff. However, storage areas shall not be pro- the hospital.
vided with natural light as it may enhance the
deterioration of paper records.
5. Safety and Security Further Reading
Records in the MRD are confidential, thus,
Moghaddasi H, Hosseini A, Sheikhtaheri A. A New Model
to prevent their loss or damage, the security of for the Organizational Structure of Medical Record
the MRD must be carefully considered. Entry Departments in Hospitals in Iran. Perspect Health Inf
and exit points of MRD shall be limited and Manag AHIMA Am Health Inf Manag Assoc. 2006
fitted with access control—manual or May 23;3:4.
Vlayen A, Marquet K, Schrooten W, Vleugels A, Hellings
electronic. J, De Troy E, et al. Design of a medical record review
6. Information Technology/Communications study on the incidence and preventability of adverse
MRD section shall be provided with inter- events requiring a higher level of care in Belgian hos-
com lines, computer networking points con- pitals. BMC Res Notes. 2012 Aug 29;5:468.
Wadhwa M. Electronic Health Records in India.:23.
nected to the central server of the hospital, Dugar D. Future of Electronic Medical Records 2021 | EMR
and RJ45 jack at all the required places. Trends [Internet]. 2021 [cited 2021 Jul 10]. Available
7. Electrical Services from: https://www.selecthub.com/medical-software/
A pair of 6/16 Amp switch/socket shall be emr/electronic-medical-records-future-emr-trends/
Publication I. MEDICAL RECORD DEPARTMENT:
provided at all the required places in the AN ANALYTICAL STUDY. [cited 2021 Jul 10];
MRD, and all computer points shall be backed Available from: https://www.academia.edu/19864782/
up by the UPS supply. M E D I C A L _ R E C O R D _ D E PA RT M E N T _ A N _
8. Pneumatic Tube Systems (PTS) ANALYTICAL_STUDY
He X, Cai L, Huang S, Ma X, Zhou X. The design of
It is an air-operated system having an air electronic medical records for patients of continuous
pump attached to the control station. This is care. J Infect Public Health. 2021 Jan 1;14(1):117–22.
Mortuary
34
Hospital Mortuary is the place where dead bodies either be the same building or some annexure
are temporarily kept, under the specified climatic building to the main hospital. Also, the mortuary
conditions, until either post mortem is carried out shall have a separate route that is not generally
or it is handed over to the police or family, or it is used by the patients or staff. The best solution is
finally disposed of. Thus, hospital mortuary can to have a separate back door from the hospital
be either used only for storage and disposal of building, from where the bodies can be moved to
bodies or as a post mortem facility with adequate the mortuary.
provisions. The mortuary shall ideally be located on the
ground floor or basement of the hospital for easy
Mortuary and discrete access for ambulances, police, and
It is primarily used for the storage of bodies and funeral vehicles to deliver and/or remove bodies
includes a refrigerated body storage facility and through an exit door.
may include a body viewing and preparation
room.
Autopsy Unit
34.2 Infrastructure of Mortuary
It is a facility attached to the mortuary which is
The following areas shall be incorporated in a
used to investigate the cause of death. It com-
mortuary which operates with post mortem
prises an autopsy room, change room and obser-
facility:
vation area. Additional autopsy functions may be
provided at large hospitals or as per the country’s Mortuary Entry Lobby
Body Wash
guidelines.
Body Holding Area
The size of the mortuary shall depend on the
Waiting/Viewing Area
number of cabinets/body storage spaces required Administration
and the death rate in the hospital. As a general Exit Lobby
rule, space for four bodies per 300 beds is work- Staff Area
able, excluding isolation storage.
If post mortem is to be conducted in a mortu-
ary, it shall have the following facilities in a sepa-
34.1 Location of the Mortuary rate autopsy area:
© The Author(s), under exclusive license to Springer Nature Singapore Pte Ltd. 2022 375
A. Garg, A. Dewan, Manual of Hospital Planning and Designing,
https://doi.org/10.1007/978-981-16-8456-2_34
376 34 Mortuary
Fig. 34.1 Sample
layout drawing of
mortuary
34.3 Mortuary 377
shall be maintained. The main gate of the mortu- wooden flooring is used for thermal control. The
ary shall be at least 1829 mm wide, openable door of the chamber is also insulated and sealed,
both sides. The size of the reception/waiting hall so that outside air shall not enter the chamber.
shall be about 6096 mm × 4267 mm. The size of the chamber shall depend on the
It shall have direct access to the Body Wash expected number of bodies to be placed at once
and Body Holding Area. The lobby shall be pro- and the average holding time of bodies. Generally,
vided with a hand wash basin with the soap dis- 3 m2 space is required for a body placed on a
pensers and towel. loose tray or trolley in a cool room. The tempera-
Outside the entrance, adequate space shall be ture of the chambers shall be maintained between
provided for parking ambulances and trolleys 2 and 4 °C.
bringing the body to the mortuary. A trolley bay
shall also be provided, where stretcher trolleys can 34.3.3.2 Refrigerated Cabinets
be placed to unload bodies from the ambulances. In this system, refrigerated body storage cabinets
are provided, which have inbuilt slidable drawers
to place the body. Generally, a cabinet has two
34.3.2 Body Wash such drawers in one row, i.e. one above the other,
and the multiple numbers of such cabinets can be
At times it may happen that the bodies are dirty installed. If more than two are provided, it
or soiled due to roadside accident, death due to becomes difficult to lift the bodies at height. Still,
stabbing etc. Under such cases, the body shall be if cabinets have to be stacked vertically to opti-
thoroughly washed before taking it in the body mize the use of space, provision of suitable lifting
holding area. The body wash area shall have a equipment and consideration of equipment turn-
platform with a size 2134 mm (L) × 914 mm ing circles shall be provided. However, this
(W) × 914 mm (H). The top of the platform shall method of storage is not appropriate for bariatric
be slightly curved. The platform shall also have (obese) bodies. Manoeuvring space shall be
the proper drain, to drain out the water after the provided in front of refrigerated cabinets to pull
wash. On the entire platform, glazed tiles shall be and push the drawers. The temperature of the
provided for an easy drain of water and proper cabinets shall be maintained between 2 and
cleaning of the platform. 4 °C. Please note, separate spaces/cabinets shall
For washing the bodies, showers shall be pro- be allocated for isolation bodies, and consider-
vided on top of the platform. Also, a tap with ation shall be given to storage and handling of a
hose pipe shall be provided in the body wash bariatric body.
area. If required, the body can be packed in the The body holding area shall be about
body bag here. 6096 mm × 4877 mm in size. However, depend-
ing on the requirement, the area can be increased
or decreased. The area shall be provided with a
34.3.3 Body Holding Area power backup system, either by a separate self-
start generator or UPS.
This is the area where a refrigerated space is pro-
vided for the temporary storage of bodies. For
this, the following options are available: 34.3.4 Waiting/Viewing Area
1. Provide a walk-in Cool Room for individual The mortuary and autopsy room shall be pro-
trolleys. vided with a waiting area for police and relatives
2. Install refrigerated cabinets of the deceased. This area shall be just at the
entrance of the mortuary and shall have the
34.3.3.1 Walk-in Cool Room capacity to accommodate 20–30 people.
In this concept, a chamber is built where the walls However, the capacity can be increased or
and ceiling are made of insulated panels, and decreased depending on the requirement. An
378 34 Mortuary
accessible toilet shall also be provided near the quate space shall be provided for parking ambu-
waiting area. lances and vehicles taking the body.
As mortuary and autopsy rooms do not have
access for the public, the waiting area shall be
provided with a viewing area, which shall have a 34.4 Autopsy Area
window/partition that it is revealed when a cur-
tain is drawn. 34.4.1 Pre Autopsy Room
34.4.3 Autopsy Room (Outdoor) for this purpose. The size of the room shall be
about 2438 mm × 3048 mm. The room shall be
This room is required for the post mortem of provided with a large-size sink with drain board
infected or decomposed bodies, which cannot be and countertop for drying up the instruments.
handled in the main autopsy room. The room
shall have all the facilities as in an indoor autopsy
room, except the roof, which is generally covered 34.4.7 Viscera Preparation Room
with net.
This room is required for the preparation of vis-
cera taken after the post mortem. The size of this
34.4.4 Post Autopsy Room room shall be about 3658 mm × 3048 mm. The
room shall be provided with a countertop, hand-
This room is required for shifting bodies after wash basin, soap dispenser, and towel hanger.
completing the post mortem. The body is kept
here until it is handed over to the investigating
officer, who subsequently handovers the body to 34.4.8 Viscera Stores
the relatives for final disposal. The size of the
room shall be about 4267 mm × 4572 mm, and it The viscera store shall be a lockable room of the
shall have a platform of about 914 mm × 2134 mm size 3658 mm × 3048 mm. This is used for the
to lay down the bodies. storage and preservation of the viscera and vis-
cera packing material. The store needs to have
sufficient countertops, cupboards, and drawers.
34.4.5 Autopsy Surgeon’s Room The temperature of the room shall be between 17
and 21 °C. The store shall not have any window,
This room shall be provided where the autopsy and direct sunlight shall be avoided.
surgeon/medical officer can discuss details of the
case with police and relatives and write reports.
The size of the room shall be about 34.4.9 Surgeon Change Room
3658 mm × 4267 mm. But depending on the
requirement and number of persons likely to sit, Along with the autopsy room, separate change
the size can be increased or decreased. The room rooms shall be provided for males and females.
shall have an adequate arrangement of the office The rooms shall be of the size
table, chairs, cabinets, drawers and racks for a 3048 mm × 3658 mm, and provided with cup-
smooth working. It shall also have an attached boards and cloth hangers. It shall also have staff
toilet. If required, a separate store shall be lockers to store personal belongings.
attached to this room. The room shall also have
proper arrangements for electrical points, inter-
com connection, IT network, CCTV surveillance 34.5 O
ther Infrastructural Issues
and air-conditioning. Along with the surgeon’s Relating to the Mortuary/
room, a small room shall be provided as a staff Autopsy Room
office to the surgeon. The size of this room shall
be about 3658 mm × 3048 mm. While designing the mortuary/autopsy room, the
following issues shall be considered:
34.4.6 Instrument Wash Room 1. The hot and cold water supply shall be pro-
vided in all handwash basins.
After every post mortem, the used instruments 2. The entire complex shall be air-conditioned
need to be washed thoroughly before the next with a separate system for the autopsy rooms to
use. Hence, an instrument washroom is required prevent foul air permeating the rest of the area.
380 34 Mortuary
No air should be re-circulated in the mortuary Brassil KE, Zillman MA. Design for a hospital mortuary.
in order to ensure a clean air environment. Pathology (Phila). 1993 Oct;25(4):333–7.
Malik AR, Rizvi IH, Ibrahim S. Design and Layout of
3. The complex should have the adequate Standard Autopsy Suite. Ann King Edw Med Univ
arrangement for fire detection and firefight- [Internet]. 2019 Oct 12 [cited 2021 Jul 12];25(3).
ing, including fire sprinkler, smoke/thermal Available from: https://annalskemu.org/journal/index.
detector in all rooms and a fire alarm system. php/annals/article/view/3042
Sirohiwal BL, Pk P, Sharma L, Chawla H. Design and
4. The mortuary complex should have all ade- Layout of Mortuary Complex for a Medical College
quate arrangement for the disposal of different and Peripheral Hospitals. 2011;2(6):4.
types of waste products according to the coun- Chawla H, Sirohiwal B, PK P, Sharma L. Design and
try’s waste disposal rules and regulations. Layout of Mortuary Complex for a Medical College
and Peripheral Hospitals. J Forensic Res. 2011 Jul
21;2:4.
3 ways to maximize postmortem spaces in medical facili-
ties [Internet]. [cited 2021 Jul 12]. Available from:
Further Reading https://www.hfmmagazine.com/articles/2114-3 -
ways-to-maximize-postmortem-spaces-in-medical-
facilities
Hospital Mortuary / Autopsy Unit. Part B. 2015;29.
Administration Area
35
In any organization, there is a set of people who Dy. Medical Superintendent’s Office
manage the day to day affairs of the hospital. This Office Toilet
set of people is jointly named as the ‘administra- P.A Room
tive team’, who reports to the management or the Secretarial staff
Waiting area for
owners of the organization.
visitors
As this team has to look after the daily activi-
ties of the hospital, their daily presence is required
in the hospital. Hence, space has to be allotted in Nursing Administration
the hospital for accommodating their offices. This Nursing Superintendent’s Office
Office Toilet
space together is known as the ‘Administrative
P.A Room
Area’.
Secretarial Staff
This area provides spaces for offices, work-
Waiting Area For
spaces, and associated facilities for supporting Visitors
the management of the hospital and includes both Dy. Nursing Superintendent’s Office
clinical and non-clinical support staff. Office Toilet
The size, number, and level of offices will
depend on the size of the hospital.
General Administration
Director’s Office Office
Personnel Office Personnel Manager
Toilet
Training and Skill Development
P.A Room Manager
Secretarial Staff Attendance Management
Waiting Area For Leaves record
Visitors
Clerks
Medical Superintendent’s Office
Toilet
Office Toilet
Accounts Office Finance manager
P.A room
Chief cashier
Secretarial staff
Accounts officers
Waiting area for
Clerks
visitors
Stores
Sub-waiting
Public utility for staff
© The Author(s), under exclusive license to Springer Nature Singapore Pte Ltd. 2022 381
A. Garg, A. Dewan, Manual of Hospital Planning and Designing,
https://doi.org/10.1007/978-981-16-8456-2_35
382 35 Administration Area
likely to take place in offices, meeting and con- 35.8.3 Lighting in the Offices
ference rooms.
Lighting for general illumination and specific
tasks has to be carefully planned. The following
35.8 Offices of the Senior points shall be considered while finalizing the
Executive Level light plan in the offices:
Management
1. Lights shall not be too bright or too dull.
Each and every senior executive shall be pro-
Proper lumens have to be planned as per the
vided a separate room as his/her office. The size
standards.
of this room shall be about 4572 mm × 4267 mm,
2. Use of LED lights is always recommended
but depending on the designation; the size of the
because of their long life and lower energy
room can be increased or decreased. The room
consumption.
shall have an adequate arrangement of cabinets,
3. Lights shall be equally distributed in the unit/
drawers and racks for a smooth working.
room.
Preferably the room shall have an attached Toilet.
4. Ceiling flush-mounted lights shall be used
The room shall have proper arrangements for:
instead of surface-exposed lights.
5. Avoid wall lights as they are not effective.
35.8.1 Electrical Points 6. Fancy lights can be used.
7. To prevent burns, incandescent and halogen
1. Main switch board at the entrance wall (other light sources should be avoided.
than the wall on which door will open) for 8. Flexible arms, if used with this light source,
control of fan and lights of the room along must be mechanically controlled to prevent
with one 5 Amp Switch/Socket. the lamp from contacting linen.
2. Air-Conditioning Control button with tem- 9. Emergency battery-operated light shall be
perature adjustment. provided in the corridors and offices.
3. Three 6/16 Amp Switch/Sockets on the wall 10. It will be better if light controls are done
adjoining the office table. If the table is placed through variable-control dimmers at the user
in the centre of the room, an underground end.
cable shall be carried to the table, and electri-
cal points shall be provided on the table.
4. Two 5 Amp Switch/Socket on the wall 35.8.4 Doors
305 mm above the office table. Also, one
15 Amp Switch/Socket shall be provided Preferably the door of the offices shall be made
adjoining this. out of wood, or flush doors shall be used. The
5. USB charging points shall be provided on the width of the doors shall not be less than 1219 mm
table. wide, unobstructed. The door shall be provided
with a door closer and stopper. The door shall
35.8.2 Other Communication Points have a provision of being locked both from inside
in the Room and outside.
1. RJ 45 point for Computer networking. The window shall be as wide as possible and fit-
2. RJ 11 for Intercom and extension line. ted with tinted glass, maybe with a double vac-
3. HDMI point for computer display at other uum glass. The windows shall be covered either
locations. with curtains or vanishing blinds.
35.9 Offices of the Executive Level Management 387
The flooring of the offices can be either laid with 35.10.1 Electrical Points
simple marble or some other stone.
1. Main switch board at the entrance wall (other
than the wall on which door will open) for
35.9.7 Air-Conditioning control of fan and lights of the room along
with one 5 Amp Switch/Socket
The office shall be provided with air-conditioners. 2. Air-Conditioning Control button with tem-
The system shall be connected to the central perature adjustment
HVAC system, with separate AHU’s for the 3. Each workstation shall have Two 6/16 Amp
administrative area. Ducts can be provided in the Switch/Sockets on the modular wall of the
rooms which shall be connected to the desk
AHU. Alternatively, Fan Coil Units can be pro-
vided in the room individually. The temperature
in the offices shall be between 18 and 24 °C and 35.10.2 Other Communication Points
RH of about 45–50%.
The following communication points shall be
provided on each workstation
35.9.8 Furniture in the Executive
Offices 1. RJ 45 point for Computer networking
2. RJ 11 for Intercom and extension line
The following furniture shall be provided in the 3. HDMI point for computer display at other
offices: locations
35.11 Support Room/Facilities 389
The window shall be as wide as possible and fit- 35.11.2 Secretarial Staff
ted with tinted glass, maybe with a double vac-
uum glass. Separate rooms are not required for the secre-
tarial staff, but they shall be provided with a hall
where multiple desks/workstations are installed.
35.10.6 Flooring Each workstation shall have an adequate arrange-
ment of cabinets, drawers and racks for a smooth
The flooring of the offices can be either laid with working. Each workstation shall be provided
simple marble or some other similar stone or with electricity and communication points, and
tiles. air-conditioning shall be common in the hall.
The office shall be provided with air-conditioners. A small kitchenette shall be provided in the
The system shall be connected to the central administrative area for preparing tea/coffee for
HVAC system, with separate AHU’s for the the guests and the staff. This kitchenette shall
administrative area. Ducts can be provided in the also have the provision for warming food which
rooms which shall be connected to the the staff brings from home as lunch. The size of
AHU. Alternatively, Fan Coil Units can be pro- the kitchenette shall be about
vided in the room individually. The temperature 3658 mm × 4267 mm. It shall be provided with a
in the offices shall be between 18 and 24 °C and working top for cooking and installing kitchen
RH of about 45–50%. gadgets. The countertop shall have a deep stain-
less steel sink with a drainboard for washing
utensils. A gas burner shall also be provided
35.11 Support Room/Facilities within a connection to a gas cylinder. The kitch-
enette shall have a refrigerator, microwave oven,
The following support rooms/facilities are gener- induction heating pad, OTG, utensils, and other
ally required in the administration area: required items like a mixer, juicer etc.
390 35 Administration Area
35.11.5 Staff Toilets 1. The meeting room shall be provided with tele-
conference or video-conference facilities.
They shall be separate for males and females. 2. At all seats, conference audio system shall be
The toilets shall have WC’s, urinals, and washba- provided.
sin. If required, the bathing facility can also be 3. Speakers connected to the audio system shall
provided. be installed in the ceiling.
4. A projector and projector screen shall be pro-
vided in the room.
35.11.6 Store 5. If possible, a smart board shall be provided.
6. A stage or podium with audio system connec-
Stores shall be located at a conveniently accessi- tion shall be provided.
ble place for storing all required files and statio-
nery. It shall be 3658 mm × 3658 mm in size, but
the size may vary depending on the quantity and 35.12.1 Electrical Points
number of items to be stored. The store needs to
have a sufficient number of countertops, cup- 1. Main switch board at the entrance wall (other
boards, and drawers. The temperature of the than the wall on which door will open) for
room shall be between 17 and 21 °C. It shall be control of fan and lights of the room along
lockable and secure to keep confidential adminis- with one 6 Amp Switch/Socket.
tration, finance, and human resources records. 2. Air-Conditioning Control button with tem-
perature adjustment.
3. On the conference table, a module of electri-
35.11.7 Notice Boards cal points shall be provided. The module shall
have, three 6/16 Amp Switch/Sockets, 1 USB
A notice board shall be planned near the recep- charging point, RJ 45 point and 1 HDMI
tion so that it is visible to all those arriving in the point.
administrative area. The board shall be made out 4. 1 electrical point for projector shall be pro-
cork to allow easy use of board pins. If possible, vided at the podium.
a light shall be provided above the notice board to 5. If a smartboard is used, the required electrical
make it more readable. outlet shall be provided near the board.
1. RJ 45 point for Computer networking. uum glass. The windows shall be covered either
2. RJ 11 for Intercom and extension line. with the blackout curtains or vanishing blinds.
3. Connection to the CCTV surveillance
system.
35.12.6 Flooring
The stores are a vital part of all industrial under- 4. Storage is the process of storing the materi-
takings, including the hospitals. It is the centre of als in warehouse, stockyards etc.
activities from where materials used in the hospi- 5. Stock control is the process of provisioning
tal are controlled. which means continuously arranging recoup-
The main objectives of the store are: ment, receipts and issues of stocks to ensure
required service is consistent with the econ-
1. Availability of a balanced and timely flow of omy. The store has to keep the materials in
all materials like consumables, medical dis- safe custody.
posables, spare parts and components, tools 6. Issues and dispatch is the process of receiv-
and equipment and other general supplies. ing demand from different hospital depart-
2. Receive, inspect and issue the above supplies/ ments and issuing the demanded materials
stores to the hospital. without losing time.
3. Accept, store and arrange disposal of scrap 7. Stock records have to be maintained, show-
and unwanted supplies/stores. ing day-to-day position of receipt issues and
stock balances.
8. Stores accounting is entering each receipt
36.1 Functions of Stores and issue a voucher in a manner so that the
balance material in-store can be worked out
The following functions need to be performed by and also know the funds spent on each
the stores: department of the hospital. This also
includes passing the bills of the received
1. Identification is the process of codifying and materials.
describing all items required to be stocked. 9. Stocktaking is the process of physically veri-
2. Receipt is the process of receiving the mate- fying the quantities of materials and their
rials ordered by the purchase department condition in the stock at specified intervals
after verification and inspection of quality and to compare it with the quantities shown
and quantity of all materials received in the in stock records.
stores. 10. Raising demand to the purchase department
3. Inspection is checking of all incoming mate- for materials to be procured.
rials for quality and quantity.
© The Author(s), under exclusive license to Springer Nature Singapore Pte Ltd. 2022 393
A. Garg, A. Dewan, Manual of Hospital Planning and Designing,
https://doi.org/10.1007/978-981-16-8456-2_36
394 36 Stores in the Hospital
For secretarial staff, rooms are not required, but 36.5.7 Cold Room
they shall be provided with a hall where multiple
desks/workstations are installed. Each worksta- A cold walk-in store/refrigerated room shall be
tion shall have an adequate arrangement of cabi- provided in the medical and drug store for storing
nets, drawers, and racks for a smooth working. specific drugs which require a cold chain or are to
Each workstation shall have proper arrangements be kept under cool temperature. The size of the
396 36 Stores in the Hospital
room shall be about 3048 mm × 3048 mm. The control of fan and lights of the room along
walls and ceiling of the room shall be made out of with one 6 Amp Switch/Socket.
puff panel, which acts as a thermal barrier. The 2. Air-Conditioning Control button with tem-
door of the room shall also be made out of puff perature adjustment.
panel and shall be hermetically sealed. The floor- 3. The suitable electrical point with 6 Amp
ing is generally made out of wooden planks. For Switch/Sockets shall be provided on the
storage, open racks shall be provided along the vacant walls of the stores to help testing of
walls. Inside the room, air-conditioning shall be items, charging of machinery, or otherwise for
done, and the temperature shall be kept between miscellaneous use. If required, 16 Amp
5 and 12 °C, which might be adjusted as needed. switch/sockets can also be provided.
The room shall be provided with a temperature
monitoring system and shall be connected to a
centralized alarm/warning system. All access 36.6.2 Other Communication Points
doors to this room shall be lockable. in the Room
The store shall have an issue counter near the 1. RJ 45 point for Computer networking.
entrance door. The user shall remain at the issue 2. RJ 11 for Intercom and extension line.
counter while the material is being taken out and 3. Connection to the CCTV surveillance
issued to the user. Sufficient space shall be pro- system.
vided outside the issue counter for the user to be
seated, and there shall be adequate space for
parking trolleys carrying material. 36.6.3 Lighting in the Stores
Material Handling [Internet]. [cited 2021 Jul 12]. HMC Architects. 2019 [cited 2021 Jul 12]. Available
Available from: https://www.mhi.org/fundamentals/ from: https://hmcarchitects.com/news/facility-layout-
material-handling and-material-management-in-the-healthcare-industry-
Facility Layout and Material Management in the 2019-09-13/
Healthcare Industry | Thought Leadership [Internet].
Engineering and Maintenance Unit
37
© The Author(s), under exclusive license to Springer Nature Singapore Pte Ltd. 2022 399
A. Garg, A. Dewan, Manual of Hospital Planning and Designing,
https://doi.org/10.1007/978-981-16-8456-2_37
400 37 Engineering and Maintenance Unit
Workshop type Size of the workshop room sin. If required, a bathing facility can also be
Biomedical workshop 9144 mm × 6096 mm provided.
Electrical workshop 6096 mm × 6096 mm
HVAC workshop 9144 mm × 6096 mm
MGPS workshop 6096 mm × 4572 mm 37.12.5 Receiving/Issue Counter
Low voltage workshop 6096 mm × 4572 mm
Building maintenance 30,480 mm × 15,240 mm
The workshop shall have a receiving and issue
Mechanical workshop 12,192 mm × 6096 mm
counter near the entrance door of the workshop.
Firefighting workshop 6096 mm × 4572 mm
Automobile workshop 30,480 mm × 15,240 mm The user shall submit the item to be repaired at this
with service duct counter, and after repairs, the same shall be handed
over to the user at the same counter. Sufficient
space shall be provided outside the counter for the
user to be seated, and there shall be adequate space
37.12.2 Workshop In-charge Room
for parking trolleys carrying material.
A separate room shall be provided for the
workshop-in-charge. This room shall either be
37.13 Other Infrastructure Issues
attached to the workshop premises or shall be in
close vicinity to the workshop. Depending on the
While designing the workshops, the following
requirements, there can be one or more rooms for
shall be considered:
different workshop-in-charge. Some hospitals
prefer to have a separate room for each type of
workshop. The size of this room shall be about
37.13.1 Electrical Points
4267 mm × 3658 mm, but depending on the
requirement, the size of the room can be increased
1. Main switchboard at the entrance wall (other
or decreased. The room shall adequate arrange-
than the wall on which door will open) for
ment of cabinets, drawers, and racks for a smooth
control of fan and lights of the room along
working. The room shall also have proper
with one 5 Amp Switch/Socket.
arrangements for electricity, communication
2. Air-Conditioning Control button with tem-
points and air-conditioning.
perature adjustment.
3. The suitable electrical point with 6 Amp
Switch Sockets shall be provided on walls
37.12.3 Workshop Engineers above the working counter of the workshops to
help testing of items, charging of machinery,
For engineers and assistant engineers, rooms are or otherwise for miscellaneous use. If required,
not required, but they shall be provided with a 16 Amp switch/sockets can also be provided.
hall where multiple desks/workstations are
installed. Each workstation shall have an ade-
quate arrangement of cabinets, drawers, and 37.13.2 Other Communication
racks for a smooth working. Each workstation Points in the Room
shall have proper arrangements for electricity and
communication points, with air-conditioning The following communication points shall be
being common to the hall. provided near the office table of the workshop
in-charge:
Lighting for general illumination and specific Flooring of the workshop shall be steady to toler-
tasks has to be carefully planned. The following ate a heavy load of material. On the other hand, it
points shall be considered while finalizing the shall look aesthetic, give a clean appearance, and
light plan in the workshops: shall provide a positive and welcoming atmo-
sphere. The flooring of the offices can be either
1. Lights shall not be too bright or too dull. laid with marble, Kota stone, or tiles.
Proper lumens have to be planned as per the
standards.
2. The use of LED lights is always recommended 37.13.7 Air-Conditioning
because of their long life and lower energy
consumption. If required, workshops shall be provided with air-
3. Lights shall be equally distributed in the hall conditioners. The system shall be connected to
and particularly the working countertop. the central HVAC system, with separate AHUs
4. If the workshop has been provided with a for workshops area. Ducts can be provided in the
false ceiling, ceiling flush-mounted lights stores which shall be connected to the AHU. The
shall be used; however, if the false ceiling has temperature in the workshops shall be between
not been provided, then surface mounted ceil- 18 and 24 °C and RH of about 45–50%.
ing lights can be used.
5. Avoid wall lights as they are not effective.
6. To prevent burns, incandescent and halogen 37.13.8 Furniture in the Workshop
light sources should be avoided.
7. Emergency battery-operated light shall be The following furniture shall be provided in the
provided in the workshop. workshop rooms:
HVAC (Heating, ventilation, air-conditioning), isms and pathogens may travel with the air cur-
in a hospital, is one of the most complicated rent. There are certain spaces in the hospital
systems, as compared to any other commercial (such as ICUs, neonatal unit, OR etc.) where it is
building. It involves a lot of functionalities when necessary to restrict the arrival and growth of
used in a hospital setting than commercial set- pathogens. Hence, air-conditioning system has to
tings, where it is used just for thermal comfort. be highly sensitive to accumulate and filter such
HVAC systems in hospitals involve providing pathogens. This can be achieved with a perfectly
comfortable climatic conditions for patients and designed HVAC system, so that the patients, staff
employees while also providing a germ-free and and visitors of the hospital are protected from
clean environment to prevent the spread of dis- exposure to such microorganisms and
ease. Further, medical equipment in hospitals is pathogens.
highly sensitive and their performance might be It is also important that the system shall have
affected due to the uncontrolled temperature and the provision of an exhaustive level of air filtra-
humidity levels. Therefore, perfect air control is tion, particularly external air supply, which is
essential to make the equipment work accurately. inducted into the system for fresh air and air
Therefore, the designer needs to pay special exchanges. This exercise prevents the growth,
attention to these issues while designing the spreading and accumulation of micro-particles/
HVAC systems for the hospitals. pathogens.
Additionally, different rooms in the hospital Following are some designing factors that
have different uses, which add to the complexity may help in reducing the spread of airborne
of the HVAC system design. First of all, it infection:
becomes necessary to clearly define different
zones and spaces and their uses. For example cer- • Proper Air Change Rates can reduce the time
tain patient rooms may be required to isolate the air particles stay in the space.
patients exposed to infectious-contagious dis- • Microbes can be filtered and removed from
eases, and some shall be required for patients the air using proper filters.
who may be immune-compromised. Hospitals • The use of Ultraviolet Germicidal Lights can
have a high concentration of microorganisms and inactivate microorganisms in the space and
pathogen accumulation compared to any other prevent their growth.
commercial building, and some of these organ- • Proper control of temperature and humidity.
© The Author(s), under exclusive license to Springer Nature Singapore Pte Ltd. 2022 407
A. Garg, A. Dewan, Manual of Hospital Planning and Designing,
https://doi.org/10.1007/978-981-16-8456-2_38
408 38 HVAC (Air-Conditioning) System
• Hundred per cent air shall be exhausted from water plant shall have multiple or a minimum of
the high-risk areas to remove infected foreign two chillers, as a single chiller will be overloaded
particles. due to continuous operation. Also, if there are
• Proper distribution of air in the air-conditioned two chillers, one can act as a standby.
space can reduce the accumulation of such While chilling the water, the chillers heat up
particles on the surfaces and provide a clear and need to be cooled. Chillers can either be
path for air to exit. cooled with water (known as water-cooled chill-
ers) or air (known as air-cooled chillers).
There are two options for HVAC system in the To provide heating in the building, hot water is
hospitals: transported to the AHU. As a result, warm air is
supplied by the AHU instead of cool air. All other
1. Central Water Chilled Plant processes remain the same.
2. DX (Direct Expansion) Chilling
38.1.1.1 Water-Cooled Chillers
There are different types of water-cooled chill-
38.1 Central Water Chilled Plant ers and they can be either centrifugal/screw chill-
ers or absorption chillers. However, centrifugal
If the hospital project is large, it is advisable to chillers, either with a single compressor or dual
select a Chilled Water Central Plant to install the compressors, are most commonly used for water-
HVAC system. This type of system reduces the cooled chiller plants. The number of compressors
initial capital cost and increases the overall effi- shall depend on the total tonnage of the chillers.
ciency of the system.
Under this type of system, water is chilled by 38.1.1.2 Air-Cooled Chillers
central chillers, which then travel to the coils of Where the tonnage of the chillier plant is over and
Air Handling Units (AHU) through insulated above 100 tons, the screw-type air-cooled chill-
pipelines. In AHU, the air is blown by fans placed ers can be used. If the installations are smaller,
behind the coils. The blown air gets cooled, and scroll-type chillers can be used. However, recip-
the same travel through the ducts to the terminal rocating types of chillers are not recommended
point, which is thrown in the spaces via diffusers. for HVAC system in hospitals.
The chilled water central plant’s capacity shall
be calculated based on the size of the spaces and
the air-conditioning requirements of the particular 38.1.2 Cooling Towers
area. The designer shall also consider the simulta-
neous peak load and not only the total of the indi- 1. While the chillers are operative, they produce
vidual system loads. In addition to this, diversity lot of heat and the body of the chillers also
factors such as head load of the machinery in the heat up. Therefore, before re-circulating the
spaces, number of people in the spaces, heat load water in the chillers, it has to be cooled. This
of the lighting, thermal loss due to sunlight in the is done using cooling towers.
room etc. shall also be considered while calculat- 2. Only factory fabricated and tested cooling
ing the capacity of the central cooling plant. towers shall be used and they shall be induced
draft-type with counter-flow.
3. The structure and basin of the cooling tower
38.1.1 Chillers shall be made out of stainless steel 304 grade,
with FRP removable louvers.
Chillers are that part of the system which cools 4. Basin cleaning system shall be provided with
the water to be sent to the AHUs. The chilled the cooling towers.
38.1 Central Water Chilled Plant 409
38.1.3 Air Handling Systems 10. The provision of Ultraviolet Light can also
be provided in the AHU for disinfecting the
38.1.3.1 Air Handling Units (AHU) air.
AHU is a box-type structure, which takes in the 11. The design of the AHU shall depend on the
air, cools/warms the air to the desired tempera- CFM and air-conditioning requirement in the
ture, and sends it to the diffuser for throwing it spaces (in Tonne).
in the designated spaces. The AHU shall have 12. The capacity of a single AHU shall not be
provisions for: more than 50,000 m3/hour.
13.
To avoid cross-contamination, separate
1. Taking fresh air from the atmosphere. The AHUs shall be provided at places like
quantity of the air to be taken can be con- Operating Rooms, Mortuary/Autopsy Room,
trolled by the damper fitted in the AHU. Clean Room, Lab and component rooms of
2. AHU shall also be connected to the return air Blood Bank and isolation areas.
duct, or a return air vent shall be provided in 14. Each AHU shall be installed as a stand-alone
the AHU to collect the returning air from the unit and it shall have no interface with
spaces. another AHU. Vertical stacking of AHUs is
3. Fresh air and return air should not get mixed not recommended.
in the AHU. 15. The return air fan for each AHU shall be sep-
4. A blower fan shall be provided in the AHU to arate and shall not be combined with the
throw the exhaust air out from the unit. return air fan of other AHU.
5. Chilled water circulates in the coils provided 16. Use of Variable Frequency Drives (VFD) shall
in the front of the AHU. When the air blown be encouraged for AHUs. VFDs shall be
by the fan passes between these coils, it gets designed and configured in a way that in case
cooled and moves out from the AHU to the one VFD fails, it shall not disable the entire
supply duct. unit. For this, a bypass switch can also be used.
6. Each cooling coil of AHU shall have maxi- 17. Service access doors shall always open
mum of six rows and ten fins per inch (FPI). In inside the AHU, i.e. on the positive side of
case the cooling requirement is more, AHU the door. The opening shall not be blocked
shall be designed with twin coil sets of six by internal parts of the AHU.
rows instead of increasing the rows and fins in 18. These doors shall be provided with the micro
a single coil. Care shall be taken that the chilled switches or safety switch interlocks to pro-
water supply line is piping through both the tect maintenance personnel from possible
coils and is in series with an access section of injuries.
1067 mm between two equal-sized coils.
7. Discharge face velocity of the cooling coil 38.1.3.2 Fan Coil Units
and heating coil shall not be more than 1. For smaller area or for a particular area like
450 fpm and 800 fpm, respectively. private patient room, instead of AHU, a Fan
8. If cooling and heating are required simulta- Coils Units (FCU) can be used. Both have the
neously, AHU can use a two-coil system, same working system; however, the only dif-
where there are two separate coils, one for ference is that AHU supplies air in large quan-
cold water and other for hot water. This sys- tity to a larger area, whereas FCU supplies
tem is used for specific areas like Operating less air in small area.
Rooms, where controlling humidity is an 2. FCU is suitable for spaces like single patient
important factor. rooms, computer rooms, communication
9. AHU also contains filters such as Pre Filter rooms, offices, machine rooms of lifts/eleva-
and Micro V filters fitted in the return path- tors, IT Rooms, electrical rooms, EPABX
way of the air to filter it air before it is sent rooms, pharmacy, stores, restrooms, OPD,
out. administration areas etc.
410 38 HVAC (Air-Conditioning) System
38.1.7 Air Intake and Exhaust This space shall be away from the clinical or
patient areas. It can be the basements, roof-
1. Positioning of the air intake and exhaust lou- top, or outside the building (in main or
vers or vents in the hospital shall be planned annexure building).
carefully and ensured that there is no chance 2. Before finalizing the location of the chiller,
of undesired recirculation of air. the weights of chillers and other allied equip-
2. Adequate distances for separation between ment, it shall be ensured that the structure of
intake and exhaust shall be maintained. the building is capable of handling the load
3. In case of harsh climatic conditions, special of the HVAC equipment.
attention shall be paid to air intake louvers. At 3. As a standard, a set of two chillers shall
least, the intake of outside air shall be drawn always be provided so that both of them can
into the system through sand trap louvers. work alternately. It will also give a buffer in
4. Washable aluminium filters shall be installed at case of failure of one chiller. Though initially
the rear end of the sand trap louver. Care shall only two chillers are installed but consider-
be taken to provide access to clean these filters. ing the future expansion of air-conditioning
If there are restrictions in providing access, the plants, spaces shall be provided for installing
system shall allow for removing the filters more such chillers at the same location in the
without the need to shut down the AHU. If the future.
filters are not cleaned, it may result in clogging 4. The size of the chiller may vary with its
the air stream and higher pressure may drop, in capacity.
turn reducing the air volume. 5. Spaces for chiller pumps and supply pumps
shall be allotted near the chiller.
6. Space shall also be provided for pipeline of
38.1.8 Filtration the chiller water supply and the pipelines for
transportation of chilled water to AHUs.
1. First stage filtration of not less than MERV 8/ 7. Spaces shall be provided for equipment
ePM10 60% rating shall be provided with all removal and maintenance.
AHUs. Similarly, the final filter of not less 8. For air-cooled chillers, sufficient open space
than MERV 14/ePM1 70% rating shall be pro- shall be provided for fresh air to cool the
vided downstream of all wet-air cooling coils chillers.
and supply fan. 9. Space shall be allotted for installation of Hot
2. Ultraviolet (UV-C) shall also be used as a dis- Water Generator for warm air.
infection method to inactivate the microor- 10. Emergency chilled water pipeline system
ganisms. The use of UV-C is recommended covered with blind flanges and isolation
for cooling coil surfaces to avoid fungal valves shall be provided to be used in future
amplification. Use of upper air UV for patient or in case the additional chillers need to be
rooms in critical care or isolation rooms shall installed.
be provided to reduce the virus spread. 11. Proper raw water pipelines shall be provided
3. Filters like Pre-Filters, Sand Filters, Micro V fil- to connect the raw water supply line to chill-
ters and HEPA filters shall be used in the HVAC ers and cooling towers.
system wherever the design recommends. 12. Higher delta T shall be used to save energy
by lowering the cost of pumping.
13. For additional energy saving, equipment
38.2 Installation of Central driven with VFD shall be considered for
Chilled Water Plant pump consuming over 7.5 kW.
14. A space shall be provided for the make up
38.2.1 Chillers (Fig. 38.1) tank of water, which makes up the level of
water to be used for cooling the chillers and
1. Adequate spaces shall be provided in the also for chilling the water to be transported
hospital building for installation of chillers. to the AHUs.
412 38 HVAC (Air-Conditioning) System
Fig. 38.1 Sample
drawing of HVAC
Chiller Plant
38.3 DX (Direct Expansion) Chilling 413
15. A space shall be provided for the electrical installing the air ducts and an opening for tak-
panel and main switches for supplying power ing the fresh air from the atmosphere.
to the system. 3. Alternately, if the height of the floor permits
and the ceiling of the floor has enough load-
bearing capacity, ceiling suspended AHUs shall
38.2.2 Cooling Towers be installed, which are suspended from the ceil-
ing with the help of screw rods and fasteners.
1. An open space shall be allotted either on the 4. In case of Fan Coil Units, these are suspended
rooftop or in an open sky area for the installa- from the ceiling at any convenient place in
tion of a pair of cooling towers. the room, preferably at the entrance of the
2. The cooling towers shall be connected to the room.
water pipelines for receiving and supplying 5. Required electrical power supply points shall
water to the chillers. Also, a water pipeline be provided to the AHU/FCU.
shall be provided to make up the water in the
cooling tower.
3. Power supply shall be provided for operating 38.3 D
X (Direct Expansion)
the cooling towers. Chilling
38.3.1 The Plant Room side of the room, which is then transported to the
AHU. This air is re-circulated by the AHU.
The plant room contains equipment like refrig-
eration system (gas), condensers, and compres-
sors (open type compressor or semi-hermetically 38.3.4 B
enefits of DX Air-
sealed compressor). Conditioning Systems
The cooling of the semi-hermetically sealed com-
pressors is done by the air blown by the fan, while 1. DX systems has a flexibility for installation.
water is used to cool the open-type compressors. This system can either be installed inside or
Condenser is a structure having shells and outside the building.
tubes, and is water cooled. Inside a condenser, the 2. The system has a great flexibility for expan-
refrigerant gas flows along the tube side, and sion in order to increase the capacity or add a
water flows along the shell side. With this process, new building to the system.
the refrigerant is cooled faster. The cooling tower 3. These systems, once installed, do not require
kept at the top of the plant room is used for cool- much maintenance, hence reduce the repair
ing the condenser and the compressor. If required, costs.
a cooling tower can also be kept at other conve- 4. Occupies less space as compared to any other
nient location instead of the top of the plant. cooling systems.
5. Saves energy and reduces electricity bill.
6. This system has a provision to reduce or stop
38.3.2 Air Handling Unit Room the flow of refrigerant to any desired indoor
unit with the help of DX valve. Hence, indi-
After leaving the condenser, the refrigerant enters vidual room can be controlled.
the thermostatic expansion valve and ultimately
the AHU, kept at a different place. The AHU is a
box-like structure consisting of an evaporator or so- 38.3.5 Disadvantages of DX system
called ‘cooling coil’, air filters and a large blower.
After entering the AHU, the refrigerant enters
1. This system can be used only for small
the cooling coil, where it cools the air, which in buildings, or otherwise if the rooms are
turn is thrown into the room. To increase the effi- located on a single floor. It is not practically
ciency of heat transfer from refrigerant to air, the feasible to lay the refrigerant piping for a
coil is covered with fins. large distance.
Two types of ducts are usually connected to 2. Another disadvantage is that if the piping is
the AHU; one for return air and other for trans- long, more amount of refrigerant will be needed,
porting the cool air to the rooms. The blower of which in turn will make the system expensive.
the AHU absorbs the return air, which then passes 3. More the length of the piping, more are the
through the filters and then over the cooling coil. chances of leakage of the refrigerant.
Thereafter, the blower blows the air in the ducts 4. The AHU and the refrigerant piping shall be
of the room to pass the chilled air in the rooms. close by, failing which the pressure of the
refrigerant will drop, resulting in less cooling.
and the indoor unit consists of blower fan and the 8. While designing the HVAC system, low-
refrigerant coil. One of the main advantages of this temperature requirements of ORs, par-
kind of air-conditioning is that it allows to control ticularly cardiac and orthopaedic, shall
the temperature in each room individually. be considered. This can be achieved
These systems are generally preferred for a using a low-temperature chilled water
small area or a particular room. circuit.
9. Temperature and humidity sensors shall be
provided in the rooms for system control. It
38.5 HVAC—Room Side Design will be better if such sensors are provided in
the return air duct.
The key design elements of various spaces in the 10. OR’s AHUs shall be designed at the air
hospital are as follows: velocity of 2 m/s at the coil to reduce the
temperature of the air leaving the AHU.
11. Chilled water pipes coming to the AHU shall
38.5.1 Operating Rooms
be designed at higher velocities and be in the
range of 1.8–2 m/s.
The ORs shall have the following for the com-
fort of doctors, staff, and patients and to reduce
the chances of growth and transmission of
38.5.2 Intensive Care Units
microorganisms:
HVAC for different ICUs shall have:
Temperature Humidity Ventilation system
18–22 °C 20–60% RH 20ACH SA/4 ACH OA
Temperature Humidity Ventilation System
18–24 °C 30–60% RH 6ACH SA/2 ACH OA
1. Each OR shall be provided with a dedicated
AHU. The design and size of the AHU shall
depend on the size of the OR. 1. For these areas of the ICU, AHUs shall be
2. To allow variable speed to cater to HEPA fil- used instead of FCU.
ter loading, AHU of OR shall be provided 2. For infective ICUs, the air exhaust shall be
with VFDs. 100%.
3. AHU shall supply constant volume of air- 3. The exhaust air of one ICU shall not be mixed
flow. However, if continued positive room with the return air of other ICU, i.e. the supply
pressure is to be provided in the OR, variable AHU and the return of each ICU shall be
systems shall be used. separate.
4. Air shall be introduced from the ceiling and
exhausted through the exhaust diffusers pro-
vided on all the four corners of the OR. 38.5.3 Patient Rooms
5. HEPA filters shall be provided in the plenum of
the OR, and the airflow shall be dissipated HVAC of Patient Rooms shall have:
through laminar airflow diffusers fixed in the
plenum. Temperature Humidity Ventilation system
6. Laminar airflow must be designed in such a 21–24 °C 60% RH 6ACH SA/2 ACH OA
fashion that clean air moves over the OT table
and within the operating field at a maximum
face velocity to sweep away particles in its path. 1. For Single rooms, FCU shall be used instead
7. As an additional measure, Ultraviolet of AHU.
Germicidal Irradiation shall be provided to 2. A thermostat linked to the BMS system shall
reduce infection risks. be provided in each patient room.
416 38 HVAC (Air-Conditioning) System
38.5.4 Isolation Rooms 2. In addition, the room shall have a dirty utility.
Air of the dirty utility shall be exhausted out-
Isolation rooms are classified as: side, as is being done for bedroom, anteroom,
and toilet.
1. Negative Pressure Isolation Room—Generally
used as Airborne Infection Isolation Rooms. Positive Isolation Room
2. Negative Pressure Isolation Room with dirty
and clean utility—Generally used as Temperature Humidity Ventilation system
Quarantine Isolation Room. 21–24 °C 60% RH 12ACH SA/2 ACH OA
3. Positive Pressure Isolation Room—Generally
used as Protective Environment Isolation Rooms. • These rooms are mainly for immuno-
4. Standard Neutral Isolation Room—Generally compromised patients such as those with
used as Contact Isolation Room. organ transplant, BMT, leukaemia, burn, late-
stage HIV etc.
Negative Isolation Room • Inflow of the air shall be more than the outflow
of the air.
Temperature Humidity Ventilation System • Inflow of the air shall be through HEPA
21–24 °C 60% RH 12ACH SA/2 ACH OA filters.
• The flow shall be from the diffusers and in a
1. The room generally consists of a patient area, laminar flow.
toilet and anteroom. • Supply diffusers shall be installed in the ceil-
2. Inflow of the air shall be less than the outflow ing above the patient bed, and exhaust shall be
of the air. on the opposite side of the room, at a lower
3. Close monitoring and control of airflow direc- level.
tion are required. • Differential pressure monitor along with alarm
4. Negative pressure shall be maintained through points connected to BMS shall be provided.
the communicating air valve even if the unit is • Seal the room if the air leakage is below 0.5 ft2
unoccupied. (465 cm2).
5. Differential pressure monitor along with
alarm points connected to BMS shall be Standard Neutral Isolation Room
provided.
6. Seal the room if the air leakage is below 0.5 ft2 1. This is basically a simple air-conditioned
(465 cm2). room in a separate zone of the hospital.
7. Exhaust air grill shall be placed above the 2. These isolation rooms are for patients having
patient's head end or otherwise at a low level a non-airborne communicable disease and is
near the head end of the patient. used only for physical isolation of the patient.
8. Air shall be exhausted through HEPA filter,
directly in the atmosphere with designed high
plume dilution fans and released at 10 feet 38.5.5 Recovery (Post-Anaesthesia
above roof level. Care Unit)
9. Recirculation of air is not recommended in
negative isolation rooms. Following shall be the requirements of HVAC for
these spaces:
Triage
1. Room shall be positively pressurized.
Temperature Humidity Ventilation system
2. Inflow of the air shall be more than the out-
21–24 °C 60% RH 12ACH SA/2 ACH OA
flow of the air.
3. Inflow of the air shall be through HEPA
1. The room shall be negatively pressurized. filters.
2. 100% air shall be exhausted with dedicated 4. The flow shall be from the diffusers and in a
exhaust ducting. laminar flow.
38.5.10 Imaging Rooms • General exhaust shall be provided in all the labo-
ratories to exhaust 100% air from the work areas.
Following requirements must be taken care of • The exhaust of the Fume hoods and Bio-
while designing the HVAC system of Imaging Safety cabinets shall be outside the building,
Rooms, i.e. X-Ray, CT, Ultrasound, MRI, PET through high plume dilution fans after proper
CT Scan, PET MRI, Mammography, DSA etc. filtration.
• Labs containing Fume Hoods or BSC cabinets
Temperature Humidity Ventilation system
shall have laminar flow diffusers.
18–21 °C 60% RH 6ACH SA/2 ACH OA
• Ventilation system of the sterilization room of the
laboratory shall be at 10 ACH SA/2 ACH OA.
1. For Imaging rooms, separate AHUs are not
necessary. Depending on the requirement and
the area to be cooled, one or more AHUs can 38.5.12 Pharmacy
be designed.
2. For the specialized imaging rooms like Cath HVAC of Pharmacy shall have:
Lab, EP room, Fluoroscopy Room etc. it is
Temperature Humidity Ventilation system
recommended that the design standards of
21–24 °C 60% RH 6ACH SA/2 ACH OA
HVAC shall be the same as of an OR, because
38.5 HVAC—Room Side Design 419
1. It shall be positively pressurized. Variable sys- 1. This zone shall have 100% dedicated exhaust
tems can be used in the pharmacy. and negative pressure.
2. Clean room for hazardous drugs shall have
BSC cabinets. The exhaust of BSC shall be Clean Area
filtered with carbon filters and HEPA filter
Temperature Humidity Ventilation system
before discharging.
20–23 °C 60% RH 4ACH SA/2 ACH OA
departments are the standards laid down by vari- through recirculation of air, and if the supply
ous designers. However, the same may differ with and return of air are common in a large space,
the Temperature, Humidity and Ventilation sys- the chances of such spread would further
tem shown at various places in the book in increase.
respective chapters. The reason is that as per the 5. Use of fresh air
practical experiences of the authors, these sug- It is important to consider the air quality
gestions are appropriate. It is left to the actual while designing the HVAC. Designs will
designer that the standards may be revised have to ensure that based on the air quality,
depending on the requirement of a particular the filtration of the air to be thrown inside is
project. proper and free from any type of foreign par-
ticles/pathogens/virus/bacteria/fungus.
6. Filtration of fresh air
38.6 Effects of COVID-19 For filtration of air, filters have to be installed
on the Design at the entry point of the fresh air. Many types
of Air-Conditioning of filters are available in the market which
can filter the particles up to a defined depth
It is also important to understand that in the past, and size. Sand and Dust Filters, Pre-Filters,
the world has dealt with various types of infec- Micro V filters, HEPA filters, ULVA filters
tions caused by fungus, bacteria, parasites, and etc. are widely used. But going a few years
viruses, and today it is under a huge pressure to ahead, we can foresee that as the air quality
tackle the Novel Coronavirus. Tomorrow it might worsens and induction of Biological and
have to deal and fight with some biological infec- Nuclear particles in the air takes place, we
tions, and there can also be some nuclear hazards may require additional filters to filter out
that can be dangerous for the human race. these particles. Therefore, the provision of
It is also true that day by day, the air quality of such filters has to be kept in mind while
our planet will worsen and will be full of unre- designing the HVAC.
quired particles. And it will become a necessity 7. Treated Fresh Air Units (TFA) is also known
to filter such particles for the healthy survival of as Fresh Air-Handling Units (FAHU). TFAs
human beings. are used when the requirement of fresh air is
Therefore, it becomes necessary to design the much higher, and that of recirculation is less,
HVAC system that is more flexible and sustain- or when AHUs need to be fed to fulfil their
able to accommodate the addition and modifica- fresh air requirements. For example if the
tion according to the need of the hour. ambient temperature (the outside air) is
Following issues require special consideration 36–40 degrees Celsius and after treatment,
in hospitals post-COVID-19: the temperature is brought down to 22–24
degrees Celsius, so that it does not increase
1. Greater flexibility and movability should be the air-conditioning load. We recommend
taken care of while designing the HVAC. using Two-stage TFA to provide complete
2. Designs that can maximize infection control solution for the Quality of Indoor
through filtration and induction of fresh air. Environmental and Energy Saving. This sin-
3. If possible, lobbies of hospitals can be left gle modular unit shall control features like
without air-conditioning, but shall be semi- cooling, heating, high-efficiency filtration
open and well-ventilated. However, this may humidification, mixing, sound attenuation
not always be true for extremely hot and/or etc. Two-stage TFAs can also provide the
cold localities. facility of heat recovery between incoming
4. It is a well-known fact that there is a high ambient air and building exhaust air without
possibility of virus and bacteria being spread any cross-contamination.
38.6 Effects of COVID-19 on the Design of Air-Conditioning 421
ters and sterilized with UV. It is recom- Higher air humidity can also reduce the air-
mended that the air which has been exhausted borne transmission of various type of viruses.
from such units should also be treated and i. One of the biggest concerns with equip-
passed through the filters and sterilized with ment and humidity is the formation of
UV before being thrown to the outside atmo- electrostatic discharge (ESD). Although it
sphere. This can be done by installing filters is a general phenomenon, but it is more
and UV lamps in the exhaust duct of such important in hospitals because it might be
units. the reason for the life or death of a patient
15. Conversion to Isolation if the equipment malfunctions or fails due
If the need be, hospital can also try to convert to uncontrolled humidity.
an additional wing (either the whole ICU or
a few beds) of the ICU to a negative-pressure
isolation ward to provide more space for
accommodating additional infected patients. Further Reading
i. If the whole ICU is being converted, then
it has to be negatively pressurized, for The importance of HVAC systems in hospitals [Internet].
Keyter. 2020 [cited 2021 Jul 12]. Available from:
which special centrifugal fans can be https://www.keyter.com/la-i mportancia-d e-l os-
installed while designing, which becomes sistemas-hvac-en-los-hospitales/
operational when required. Apart from New ASHRAE reference guides hospital HVAC design -
the ICU, this can be true for other areas as Environmental Services [Internet]. Healthcare
Facilities Today. [cited 2021 Jul 12]. Available from:
well like Emergency Rooms, Pre-and https://www.healthcarefacilitiestoday.com/posts/
post-OP units etc. New-A SHRAE-r eference-g uides-h ospital-H VAC-
ii. If particular beds are to be converted, it design%2D%2D2389
can always be done with the help of col- Reijula J, Holopainen R, Kähkönen E, Reijula K,
Tommelein I. Intelligent HVAC systems in hospitals.
lapsible shutters around the beds or fixing Intell Build Int. 2013 Feb 17;5:101–19.
temporary acrylic partitions. For HVAC, Editor. HVAC System Design for Multi-Specialty
Micro air-conditioning can be installed. Hospital | Cooling India Monthly Business Magazine
In such technology, micro angle adjust- on the HVACR Business | Green HVAC indus-
try | Heating, Ventilation, Air conditioning and
able outlets are installed to induce the air Refrigeration News Magazine Updates, Articles,
inside, separately for each bed, above the Publications on HVACR Business Industry | HVACR
patient, and a separate exhaust is given Business Magazine [Internet]. [cited 2021 Jul
(with separate duct) for each bed. When 12]. Available from: https://www.coolingindia.in/
hvac-system-design-for-multi-specialty-hospital/
this exhaust becomes operational, the HVAC design requirements for medical spaces [Internet].
common return duct is bypassed with the [cited 2021 Jul 12]. Available from: https://www.
help of diffusers fixed in the exhaust duct. hfmmagazine.com/articles/1755-h vac-d esign-
1 6. Humidity control requirements-for-medical-spaces
Ocana G. HVAC Design Manual for Hospitals and
Properly controlled air humidification in Clinics Second Edition. [cited 2021 Jul 12]; Available
hospitals provides a great comfort to the from: https://www.academia.edu/14124488/HVAC_
patients and staff, apart from efficient work- Design_Manual_for_Hospitals_and_Clinics_Second_
ing of equipment, by reducing the dry air. Edition
HVAC Design Manual for Hospitals and Clinics
Also, humidity is regulated to protect patients [Internet]. [cited 2021 Jul 12]. Available from: https://
from nosocomial infections, bacterial attacks www.ashrae.org/technical-r esources/bookstore/
and prevent the spread of other infections. hvac-design-manual-for-hospitals-and-clinics
Further Reading 423
Saran S, Gurjar M, Baronia A, Sivapurapu V, Ghosh PS, Engineered Systems | For facility, consulting & mechani-
Raju GM, et al. Heating, ventilation and air condition- cal engineers [Internet]. [cited 2021 Jul 12]. Available
ing (HVAC) in intensive care unit. Crit Care. 2020 from: https://www.esmagazine.com/
May 6;24:194. 5 Hospital HVAC Design Strategies for the Post-COVID-19
Lenzer B, Rupprecht M, Hoffmann C, Hoffmann P, World [Internet]. Facilitiesnet. [cited 2021 Jul 12]. Available
Liebers U. Health effects of heating, ventilation and from: https://www.facilitiesnet.com/healthcarefacilities/
air conditioning on hospital patients: a scoping review. article/5-Hospital-HVAC-Design-Strategies-for-the-Post-
BMC Public Health. 2020 Aug 26;20(1):1287. COVID-19-World%2D%2D19123
Electrical Services
39
© The Author(s), under exclusive license to Springer Nature Singapore Pte Ltd. 2022 425
A. Garg, A. Dewan, Manual of Hospital Planning and Designing,
https://doi.org/10.1007/978-981-16-8456-2_39
426 39 Electrical Services
Power supply shall be received from the con- The connections from the main panel to these
cerned Electricity Supply Board/Company either panels are done through LT Armoured XLPE,
through the LT line or the HT line. If it is an HT aluminium cables or Rising Main Bus-bar.
line, it shall be 11 KV single circuit feeder two- The power supply from individual floor pan-
pole structure and shall be terminated at the els, located on each floor of each section, shall be
metering panel room located at the entrance of terminated at the LDB/PDB installed at different
the hospital premises. The 11 KV supply from locations of the floor. The LDB/PDB shall be
the metering room shall be terminated at the main separate for lighting and power application. It
HT VCB panel located at the sub-station area. shall have incoming MCB cum ELCB and also
Further, the HT power supply shall be connected outgoing MCBs. The rating of the MCBs shall be
to the transformers through 11 KV XLPE (E) designed according to the load factor on a par-
cable which is laid underground or trenched. ticular MCB.
The sub-station comprises of one number From the MCBs, the power is distributed at
11 KV indoor type 630 Amp VCB (may vary as various locations and to the electrical outlets
per the load calculation) as incoming cum outgo- through the underground LT copper cable. If
ing, and one oil-cooled OLTC type transformer, required, cable trays can be used instead of going
the capacity of which shall depend on the load underground. Cable trays usually travel above the
calculated for the hospital. false ceiling, and the route shall be through the
corridors. Avoid laying cable trays in the rooms.
ber of lifesaving machines installed in the hospi- The DG sets shall be installed on a raised
tal. While creating a contingency plan, special foundation, which shall be strong enough to tol-
attention has to be paid to the area. There may be
erate the load and vibrations of the DG set. The
some areas like OPD where power failure may DG set is fixed to the foundation with the help of
not leave any detrimental effect related to fasteners, and anti-vibration pads shall be
patient’s safety as compared to the power failureinstalled.
in an ICU where it can have disastrous conse- An independent exhaust pipe from each DG
quences. While designing the power system in set shall be connected to the chimney of 30-metre
the hospital, the designer shall address the risks
height from the ground to let the smoke out in the
that may be involved because of power failure. atmosphere. Silencer shall be provided with each
Therefore, the designer shall design an optimum DG set. The ambient noise level from DG set
solution that can minimize the risk to the patient’s
shall not be more than 72 dB(A) during operation
safety and ensure the efficient operation of the from one-metre distance. Maximum stack height
hospital facility. of the DG set shall be as per the norms.
Keeping in mind the consequence of power One of the main components of DG set is the
failure which may affect the working of units or batteries used for cranking the engine. Therefore,
equipment in the critical areas like ICU, special consideration shall be given to the choice
Emergency, OR, Diagnostic etc. a more robust of starting batteries, and either VRLA or Ni-Cd
power infrastructure shall be planned, which type shall be used; however, the use of Ni-Cd bat-
shall incorporate additional provisions of second-
teries is highly recommended.
ary and/or tertiary power supplies. Facility for onsite storage of diesel for genera-
tor sets shall be provided. The quantity of the die-
sel to be stored shall depend on the estimated
39.8 Emergency Power running hours of the DG set. However, to be on
Generation System the safer side, it is recommended that hospitals
shall provide storage capacity of diesel equiva-
Radiator cooled Silent Diesel Generating sets lent to a minimum of 2 days of fuel consumption
shall be provided as a secondary source of power at 80% average loading on the DG sets.
to meet the power backup for all services (con- As far as the air-conditioning plant is con-
sidering 100% power backup). To make the DG cerned, it is not necessary to provide 100% power
power supply more flexible and economical, it is supply backup. However, few spaces like OR,
proposed to install two or more numbers of DG ICU and emergency shall be provided with the
sets. The rating of the DG sets shall be decided backup. If the hospital has a single air-
and calculated based on the peak load and normal conditioning plant for the entire building, it will
non-peak load of the power required. become necessary to provide backup to the entire
The DG sets shall be located near the sub- plant. Therefore, the designer can plan to have
station, compatible with Programmable Logic one separate air-conditioning plant for each criti-
Control (PLC) system panel. These DG sets shall cal area like OR, ICU, and emergency, so that the
provide power automatically in the absence of power backup can be provided to the plant dedi-
primary electricity supply or when the supply cated solely for these areas. However, DG set
voltage drops below the pre-set value. The num- shall have enough capacity to serve at least that
ber of DG sets running at any particular moment part of the HVAC system, including the central
of time shall depend upon the load requirement chilled and heating plant, that can fulfil the
through PLC. If all DG sets are synchronized requirements of cooling and heating of the criti-
together, the PLC can automatically control the cal areas like ICU and OT.
running of DG Sets. All the DG sets shall have Separate and dedicated main DB rooms shall
the facility of auto start and auto shut down. be provided for critical care facilities like OR,
428 39 Electrical Services
emergency, and ICU, to segregate primary and is laid down in the building to provided power
secondary main DBs from other spaces. backup to all IT equipment like Computers,
CCTV, Wi-Fi routers, Fire Panel, alarms etc. The
rating of the UPS shall be designed as per the
39.9 Uninterrupted Power requirement.
Supply System (UPS) For Major sensitive medical equipment like
MRI, CT, PET CT, PET MRI, Cath Lab, Gamma
UPS system is an important source of uninter- Camera, LINAC, Brachytherapy etc. separate
rupted power supply in the hospital. It shall be machine dedicated UPS system shall be pro-
used to provide power supply to all emergency vided. The UPS for these machines shall be able
lighting. Most importantly, the UPS system is to take the entire load of the machine while it is
provided in the critical units and for sophisticated operational. This UPS can save the machine from
machines like MRI, CT and LINAC. getting damaged due to sudden power failure. It
As far as critical care units like ICU, NICU, is normal, that due to sudden power failure, the
emergency etc. are concerned, each unit shall software of these machines corrupts. Also, this
have a dedicated UPS system connected to the UPS helps to avoid hampering the ongoing pro-
concerned unit. Few light points (it is not neces- cedure at the time of power failure.
sary to include all) and approximately half of the For emergency lighting in the hospital build-
electrical outlets shall be connected through the ing, single UPS or floor UPS can be used. The
UPS circuit. These outlets shall be used for con- rating of the UPS shall be designed based on the
necting life-saving machines like monitors, inva- load requirement.
sive and non-invasive ventilators, etc. It is Preferably, at least a battery backup of
recommended that in ICUs, a three-phase on-line 20–30 min shall be provided with each
UPS shall be provided. The rating of the UPS UPS. Sealed maintenance free type of batteries
shall be designed as per the requirement. On an shall be used for storage.
average, for a 10 bed ICU, the rating of the UPS It is recommended that the static, double con-
shall be about 5–10 KVA. version type of UPS units, which is either mono-
Each OR shall have a dedicated UPS system. lithic or modular, shall be used.
The plenum and peripheral lights shall be con- For better performance, VRLA type batteries
nected through the UPS circuit. All the electrical shall be connected in a dual string arrangement.
outlets and sockets shall also be connected to the By providing multiple string battery connection,
UPS, so that power could be supplied to the it is easy to maintain the batteries while the UPS
machines and equipment in the OR in case of is in working condition as all the cables need not
failure of primary power. Also, there is a short be disconnected, and a part of battery bank keeps
time lag between the failure of primary power giving back up to the UPS.
and time to switch on the secondary power. In Since, life of the batteries largely depends on
this time, UPS plays an important role in power the room temperature, it shall be maintained
supply. It is recommended that in ORs, a three- between 18 and 22 °C in the UPS rooms. Alarm
phase on-line UPS shall be provided. The rating systems shall also be provided in the UPS room
of the UPS shall be designed as per the require- in case the temperature is above the normal range.
ment. Generally, the rating of the UPS for each UPS units shall be provided with external
OR shall not be less than 10 KVA. bypass panel so that in case of total failure of
Apart from this, a UPS shall also be provided UPS, power can be bypassed to maintain contin-
for the hospital server and to the working nodes uous supply.
at different locations of the hospital. For server, All UPS units can be kept at a common place
one dedicated UPS shall be provided, and for in the hospital. However, UPS connected to
working nodes, a small off-line UPS shall be special medical equipment like MRI, CT, LINAC
installed. Otherwise, a dedicated UPS supply line etc. shall be placed near the respective machine.
39.13 System of Wiring and Cabling 429
39.14 Switches/Sockets supplied from the main DB and not from the sub-
and Boxes distribution panels shared with others.
2. In case the supply from MDB is not possible,
White/coloured rocker switches 6/16 Amp shall power can be supplied from the sub-main dis-
be used for primary power supply sockets. tribution board (SMDB), provided a dedicated
Faceplate to be used can be made out of either appropriately sized SMDB is installed in the
plastic or metal. For aesthetic purpose, plastic/ MDB room to serve a group of such
metal faceplates shall be of same colour as of the equipment.
switch/socket. For DG set power supply, the 3. Surge protection devices shall be provided in
colour of the sockets and switches can be changed the panels and also in the UPSs’ to get a pure
like red colour which helps in easy identification sine wave. The chances of damage to elec-
of the switches. Similarly, for UPS power supply tronic boards of medical equipment can be
sockets/switches blue colour can be used. reduced to a great extent, if the supplied
If the switches/sockets are being provided in power is with the pure sine waves.
the bed head panel or the hanging pendent, 4. To install harmonic filters, provision of breakers
wherein gas outlets are also provided, ensure that shall be made in the main DB’s, and such spare
there is a proper partition between the switch/ breakers, designated for these filters, shall be
socket and medical gas outlets, so that there are clearly labelled as ‘For Harmonic Filter Only’.
no chances of sparking a fire. Though it is not practically possible to accu-
rately estimate the rating of harmonic filters in
advance, power system harmonics of order 3rd,
39.15 Lightning Protection 5th, 7th, 9th, 11th and 15th order can create sig-
nificant problems of over current and overheat-
The entire hospital premises shall be protected ing of cables, bus-bars and transformers.
from sky lightning by providing suitable light- 5. Harmonics shall be finally measured once
ning arrestors connected to copper tape/cable. majority of the medical equipment, mechani-
Suitable protected zone shall be formed through cal, and electrical appliances are operational.
the mast and connected to earthing stations
through cable/copper tape.
Special consideration shall be given to protect 39.17 Power Factor Correction
electronic devices and medical equipment in the
hospital from damages due to lighting strike. Capacitor banks including reactor shall be pro-
Therefore, it is advised to provide Surge Protection vided in the main capacitor panels at the central
Devices (SPDs) for sub-main electrical branch power station for controlling the power factor as
circuits serving critical medical equipment. well as the harmonics. As per regulations, all bulk
users are required to maintain a power factor of 0.9
and above, failing which stringent penalties are
39.16 Power Quality imposed by the power distribution companies.
ICT, Information and Communication the former. The following issues shall be consid-
Technologies, the system focuses on the services ered while designing the nurse call system:
relating to processing information (data, voice,
video) and connecting devices.
ELV, Extra Low Voltage, systems focuses on 40.2.1 Desktop Console
the services like connectivity, security, safety and
automation. The function of this unit is to a receive call and
Both the systems play an important role in the alarm from different locations of patients and
operation of the hospital. The LAN infrastructure staff. The unit is programmed in such a manner
in a hospital shall provide IP connectivity for that if the patient activates the call from the bed,
various services in hospital, which may actually the console receives the call and displays the
be located at some other spaces in the building, unique ID (may be room number or bed number)
but it requires connectivity with the main source on the panel screen fixed on the console.
through the same physical network for sharing Simultaneously, the alarm starts beeping. The
the data or command. The applications can be nurse immediately comes to know caller’s loca-
CCTV, data, public address, voice, video, nurse tion. If the unit has bi-direction speech facility
call, queuing systems, HIS, PACS etc. with the patient, the nurse can talk to the patient.
The system shall be designed in a manner that the
nurse shall not be able end the call from her end
40.1 Data System and has to go the patient bed for resetting and
ending the call. This unit shall be placed at the
All data cables shall be terminated at floor patch nursing station and shall be in direct eye contact
panel and then data shall be transmitted to the with the nurses.
server through a backbone fibre optic cable.
© The Author(s), under exclusive license to Springer Nature Singapore Pte Ltd. 2022 433
A. Garg, A. Dewan, Manual of Hospital Planning and Designing,
https://doi.org/10.1007/978-981-16-8456-2_40
434 40 ELV, ICT and IBMS Services
the patient who has activated the call. The light 40.2.6 Emergency Call
switches on when the call is activated and once
the call is attended and the reset button is pressed, This button is for the staff to raise alarm in case
the light is switched off. of an emergency to alert other staff members
for help. Once the emergency call is activated,
the system generates an audible alarm at the
40.2.3 Patient Call with Handset concerned staff station or designated mobile
devices along with an alphanumeric display to
This is a device called Patient Hand Set which indicate the location from where the call is
comprise of various buttons like staff assistance initiated.
and emergency call buttons, microphone, speaker
etc. to activate the call. This device has a jack for
plugging the patient handset. This jack is plugged 40.2.7 Wireless Handset
into the socket of the nurse call system. The
socket is located at the head end of the patient, Nowadays, the patient unit is provided with a
either on the wall or in the bed head panel. This wireless handset to activate the call. This handset
device is provided at all locations where the is connected using Bluetooth or infrared connec-
patients are admitted and not continuously tion and functions similarly to that of a wired
attended by a nurse. handset.
The call button shall help the patients to com-
municate with the staff and to alert a nurse for
any assistance, which in turn increases a sense of 40.2.8 Wireless Console
security in the patient.
Mobile wireless nurse call consoles work on
Bluetooth or Wi-Fi technology. It allows the
40.2.4 Patient Call—in Toilets nurse to be aware of the call from a patient, other
than the patient she is attending, or if the nurse is
These units are used to initiate an alarm call in not present at the nursing station where the con-
emergency situation from inside the toilet. These sole is located.
units are usually fixed at a low height and within
easy reach of the patient. These units shall have
minimum buttons so that the patient is not in a 40.2.9 Audio-Video Nurse Call
confused state of mind while initiating the call. System
These units shall be waterproof and shall be able
to be installed even at wet locations. This device is largely under development, which
shall have an audio-video communication facil-
ity. Under this technology, the nurse console will
40.2.5 Staff Assist Call have a small video screen, microphone, and a
speaker. Similarly, at the head end of the patient,
This device is for the staff who is present at the a small camera shall be mounted, and the handset
patient location and requires additional help from shall have a small video screen along with a
other staff members, may be other nurses or doc- microphone and speaker. As soon as the patient
tors. The system has pre-configured locations, as activates the call, the audio and video are acti-
to where the call will reach as soon as the call is vated and the nurse can see the patient and talk to
activated. Once the call is activated, the alarm him/her. Further, the mobile of the patient can be
beeps at the other integrated place and a visual ID connected to the nurse console through a dedi-
(from where the call is active) is displayed. cated IP.
40.3 Electronic Security and Video Surveillance System 435
7. Due to operational and security authority dles, push bar, keypad etc. In a hospital, these
requirements, separate and dedicated IT touch points can create a hazardous source of
network shall be provided for IP CCTV net- spreading infection. Hence, it is advised to reduce
work and access control. physical touch points and adopt touch-free
devices like door readers, which reads and
authenticates credential from a distance and then
40.4 Access Control System opens automatically.
The following sections describe the architec-
A network shall be created within the campus for ture and functional requirements of an integrated
various systems to be deployed with the Integrated security alarm management system. The com-
Security Management System (ISMS). mand and control system shall be the heart of the
In hospital, at times, patients or family mem- system, with all the system components reporting
bers of patients may become aggressive or even to it, and shall be modular and must have a highly
violent due to the anxiety and trauma the patient scalable architecture.
is undergoing. Further, the cases of quarantined
patients need to be handled quickly and effi- 1. Access control system shall consist of prox-
ciently to prevent the spread of infection. imity readers for entry to common doors,
Hospitals are also concerned about patient safety, which will eliminate the risk of un-authorized
as adverse issues can lead to patients being entry in the building premises. Main entry
abducted, harmed, missing or committing doors to the building through staircase and lift
suicide. lobbies are ideal for implementing this sys-
Furthermore, in hospitals, there is high risk of tem. The exit from these doors shall be
theft and abuse, particularly the expensive equip- planned through a card reader.
ment distributed throughout the premises and 2. Biometric face readers shall be used at impor-
pharmaceutical drugs. Therefore, a strong, com- tant locations, i.e. server rooms, control room
prehensive access control system shall be pro- and highly secured documentation area.
vided to improve the overall security, avoid 3. Access control system shall be integrated with
hospital losses, and increase patient and staff IP CCTV and fire alarm system.
safety. 4. RFID cards/tags and reader-based access con-
These days different types of access control trol system shall be used.
systems are available with different features and 5. Fingerprint biometric readers, which requires
designs. Out of all these, there are a few which touching a figure to scan the fingerprints, shall
are suitable for hospital setup and can be used for not be used in the hospital.
restricting access to sensitive areas of the hospital 6. ‘Infant Protection System’ shall be used in the
like ICU's, OR, record room, isolation areas etc. hospital in NICU and paediatric wards. This
which may prevent the spread of disease. The system shall have trackable tags, which shall
restricting access can also help in tracking and be employed on the forearm of the infant and
preventing the theft of medical equipment and mother. This system shall be interfaced with
drugs and can also protect both staff and patients. access control system to disallow the access
in case of any breach of security.
7. Discrete Panic Alarms shall be provided at all
40.4.1 No-Touch Access important locations like emergency triage
area, cash counters, reception, ICU etc.
Touch points are the points of access control sys-
tem, which need to be necessarily touched in Electronic access control shall be provided at
order to get through. These can be the door han- the following locations:
40.5 Telecommunication System 437
Radiotherapy LINAC Intensive Care Units wire or patch cords shall be used for patching
Bunkers between incoming and outgoing patch panels.
Server room or data Entrances to staff only areas Following issues shall be considered while
centres
designing the telecommunication system:
CT Scan/MRI Room Clean Storage of CSSD
Pharmacy Dirty utility
1. There shall be a central intercom EPABX sys-
Cash counters All entries and exits to
outside tem installed at a particular location in the
Medical records Entrances to back offices, hospital.
insurance offices 2. The telephone cable of the CAT 5 or 6 cable
Isolation rooms Staff only corridors shall be laid down in the entire hospital
Neonatal Units building.
3. Each location shall be allotted a unique inter-
1. Entry doors locked with electronic access com number and connected to a cable/wire.
control system shall be accessible only for
people with valid access cards. Access to Telecommunication also includes the concept
these areas shall only be allowed by a desig- of the telemedicine and telemonitoring wherein
nated door operator. Some of these areas are: home or remote healthcare facilities are provided
(a) Doors between the control room and the by allowing real-time monitoring of off-site
patient treatment room of the radio ther- patients, visualize the investigation reports, pro-
apy department. viding general prescription etc. The efficiency and
(b) Windows in the hot lab between the drug timely delivery of the results can only be achieved
preparation and drug administration with telecommunication if an effective communi-
room. cation system is established between the patients,
(c) Doors between the control room and the equipment, and healthcare personnel.
patient imaging room of the CT Scan or Until recently, Radio frequency (RF) was the
MRI. most preferred technology to provide an effective
(d) Outside entry door and patient room in communication channel for connecting the
Isolation area/units. patients, equipment, and healthcare personnel.
(e) Doors between dirty and sterile area of However, RF possesses issues relating to secu-
CSSD. rity, privacy, safety, interference generation, tol-
(f) Window between the OR and dirty utility erance, spectrum congestion etc. Due to these
room attached to the OR. shortcomings, wireless technology is being
adopted now a days.
Then came in the Visible Light Communications
40.5 Telecommunication System (VLC) technology. VLC uses the lighting infra-
structure of solid-state light sources like white
In hospitals, either a combined audio/video inter- LEDs for light-based wireless connectivity. VLC
com system or an audio intercom system shall be is an effective technology, particularly for hospital
provided for a fast and easy two-way communi- applications to provide services like telecommu-
cation. IP-based solutions shall be preferred for nication and remote health monitoring.
better operational flexibility. Further, a hybrid optical-radio network is con-
Telephone and data points shall be connected sidered to be the perfect connectivity infrastructure
through four pair CAT 6 cables from the patch for hospitals. This hybrid network works with the
panel located on each floor. All the floor patch combination of both radio and optical platforms to
panels in turn shall be connected to the main provide a high performance, highly secure, flexi-
patch panel installed in the LV rooms. Hook-up ble, private, and safe communication network.
438 40 ELV, ICT and IBMS Services
40.6 Patient Entertainment counter or room number where the person has
and Information Systems to report as their turn arrives. These screens
shall be integrated with the IPTV systems of
Patients in the hospital shall be provided with the hospital.
an entertainment facility in their room. The 3. The calling station from where the call for
patient entertainment and infotainment sys- token is raised shall be software controlled,
tems shall have the provision to view main- and that could be operated from workstation
stream TV channels, videos, videos on patient of computer system, rather than using conven-
awareness and education, health awareness tional hardware with keypad.
shows, hospital informatics, diet menus, mov-
ies and shows on demand etc. based on the
facility available in the hospital. The main 40.8 Public Address System
points to be considered while designing this
system are as follows: Communication plays an important role in pro-
viding better healthcare services and save lives
1. A smart TV shall be located on the wall just in in a hospital. Staff must be able to reach the
front of the patient in the patient room. required medical professionals at all times. Also,
2. The height of the TV shall be such that the the staff must be able to make general and emer-
patient in head-up position can easily view it. gency announcements hospital-wide and know
Generally, the bottom of the TV shall be about that the correct people are hearing it. This is
1524 mm from the floor. where the hospital communication systems like
3. An operating remote shall be provided at the intercom and public address (PA) system are of
bed of the patient. importance.
4. The television shall be connected to the IPTV As technology has improved, so have commu-
network. Also, it shall have the facility for nication systems. More and more communication
multiple television channels by connecting it systems are going IP by replacing old wired sys-
through satellite dish. tems. This not only gives hospitals more flexibil-
5. Use of mobile phones shall be allowed in the ity but also provides better sound quality and
hospital. However, in critical areas like ICUs, more integration with other systems, like video
the use of mobile phones shall be restricted. surveillance, access control, and nurse call
systems.
Apart from announcements in case of emer-
40.7 Queue Management System gencies, public address system can be used in
hospitals for broadcasting prayers, playing back-
Areas where the patient/visitors have to wait for ground music, announcements etc. in waiting
their turn like registration, billing, cash counter, areas and corridors.
OPD, investigations, pharmacy etc. shall have a
queue management system in place. 1. System Description
The public address system shall be
1. Token system can be implemented wherein designed in such a manner that the voice
each person will be provided with a token reaches all desired areas in the hospital. The
mentioning a serial number for their turn. To quality of sound also matters, and the voice
facilitate this, token dispensing machines shall be clearly audible with no disturbances
shall be provided at suitable locations under and echo.
the supervision of a staff member. 2. Zoning
2. Waiting area display: Suitably sized LED Public-address system shall be zoned in
panel screens shall be provided in the lobbies, the hospital building to suit the operational
which shall display the token number and the requirements of the hospital.
40.9 Integrated Building Management Systems (IBMS) 439
3. PA equipment shall include microphones for energy conservation control schemes, which in
announcement, processing circuits, sound turn helps in reducing manpower requirement for
amplifiers, pre-mixers, ambient noise reduc- operating and maintaining the building services
tions, speakers, cabling and all other required without compromising on the quality of services.
equipment. IBMS also acts as a strong Management
4. Microphones shall be highly sensitive, with Information System (MIS) by keeping the man-
minimum noise distortion and low sensitivity agement informed about the critical operation of
to feedback. They shall be connectable to the various equipment connected to IBMS and make
zone selection consoles, each with its own available data required for analysing the working
selectable priority, from which each operator and further possibilities of conserving the energy.
shall send announcements to specific audio The system shall be based on Micro Processor
zones. Control System, using various Energy
5. Distribution Equipment Management Programmes to save energy with
The distribution equipment shall primarily the latest techniques of controlling the environ-
comprise line attenuators with line transform- ment. BAS shall be capable of performing the
ers and rotary/digital controls for selecting the following main functions:
output power of a line speaker.
6. Speakers 1. HVAC System
The speakers shall be of various design, In a hospital setup, HVAC system con-
depending on the requirement of the area allo- sumes maximum energy. If IBMS is used for
cated/usage. If there is no false ceiling, the HVAC, it can provide the opportunity to save
speakers can be column type and fixed on the lot of energy.
wall of corridors at a specific distance. 2. Precision AC System
Wherever false ceiling exists, the speakers The IBMS can monitor and control the
shall be of concealed mounting type with a actual on/off status of the precision AC and
wide bandwidth. display it on the BMS screen.
7. Central Announcement Cell 3. Diesel Generator Set
The hospital shall have a central announce- The IBMS can monitor the status of alarm
ment cell which shall be manned round the like low lubricant oil pressure low, fuel level
clock. This cell shall have a microphone, low etc. for DG set. The status can also be dis-
amplifier and zone controller. played on the DG screen of the IBMS
system.
4. UPS System
40.9 Integrated Building Through IBMS, the UPS can be monitored
Management Systems (IBMS) via serial interface, and user can view the
input, output, and interface parameters.
It is the pinnacle of automation controls that 5. Water Management
helps in the effective and efficient usage of vari- IBMS can control the water levels in the
ous electro-mechanical systems in a building. tanks through the automatic level sensors and
With more emphasis on optimized energy con- can automatically switch on/off the water sup-
trols and green building norms being the new ply motors.
focus area, IBMS helps in achieving the stringent 6. Lift Monitoring
norms by proper monitoring and control of the Through IBMS, the lifts can be easily con-
systems used like HVAC, electrical, DG, sprin- trolled. It can control functions like floor posi-
klers, hydrant and security systems for optimized tion, alarm, and maintenance modes.
energy usage. 7. Firefighting System
Building Automation System helps in conserv- IBMS can easily monitor the pressure sta-
ing energy by planning and executing various tus in the hydrant and sprinkler line of the fire-
440 40 ELV, ICT and IBMS Services
fighting system. If the pressure goes down in [cited 2021 Jul 14]. Available from: https://www.
the line, it can automatically switch on/off the asmag.com/rankings/m/content.aspx?id=30879
Hospital Building management system (BMS)
fire pumps to recover the pressure. [Internet]. Med & Tech. [cited 2021 Jul 14].
8. If the IBMS is connected and integrated with Available from: http://hospital-tech.com/solutions/
the fire control panel, it can monitor the status hospital-building-management-system-bms/
of the firefighting system. Emergency Public Address System Requirements &
Maintenance [Internet]. Jensen Hughes. [cited
2021 Jul 14]. Available from: https://www.jensen-
hughes.com/insights/public-address-systems-what-
you-need-to-know
Further Reading Aswin S, Narayanamurthy G, Jeyender S, Prasanna R,
Kumar SP. Design development and implementation
Almotaeryi R, Khan F, Bouridane A, Jiang R. SMART of wireless nurse call station. 2011 Annu IEEE India
CCTV SURVEILLANCE SYSTEM FOR Conf INDICON. 2011 Dec 1;
HOSPITALS. 2017 Jan 1;Volume 72:.213-225. CCTV in healthcare - The MDU [Internet]. [cited 2021
Smart Building Technology | Optergy Best-in-Class Jul 14]. Available from: https://www.themdu.com/
BMS & EMS Solutions [Internet]. Optergy. [cited guidance-and-advice/guides/cctv-in-healthcare
2021 Jul 14]. Available from: http://optergy.com/ Building Management System (BMS) Research Papers -
smart-building-technology/ Academia.edu [Internet]. [cited 2021 Jul 14]. Available
Public Address and Intercom System Design Guidelines from: https://www.academia.edu/Documents/in/
| Clock | Telephone [Internet]. Scribd. [cited 2021 Building_Management_System_BMS_
Jul 14]. Available from: https://www.scribd.com/ Building management systems and integrated building
doc/295754458/Public-A ddress-a nd-I ntercom- management [Internet]. i-SCOOP. [cited 2021 Jul
System-Design-Guidelines 14]. Available from: https://www.i-scoop.eu/building-
Miller ET, Deets C, Miller RV. Nurse call systems: impact management-building-management-systems-bms/
on nursing performance. J Nurs Care Qual. 1997 Building Management System - an overview |
Feb;11(3):36–43. ScienceDirect Topics [Internet]. [cited 2021 Jul 14].
Nurse call system upgrades [Internet]. [cited 2021 Jul Available from: https://www.sciencedirect.com/
14]. Available from: https://www.hfmmagazine.com/ topics/engineering/building-management-system
articles/1664-nurse-call-system-upgrades Zapatán RA, Armijos EE, Serpa-Andrade L, Pinos
Editor. Integrated BMS for Healthcare Building | Cooling E. Analysis of a Nurse Call System Implementation
India Monthly Business Magazine on the HVACR using a Wireless Sensors Network. In: Torres I,
Business | Green HVAC industry | Heating, Ventilation, Bustamante J, Sierra DA, editors. VII Latin
Air conditioning and Refrigeration News Magazine American Congress on Biomedical Engineering
Updates, Articles, Publications on HVACR Business CLAIB 2016, Bucaramanga, Santander, Colombia,
Industry | HVACR Business Magazine [Internet]. [cited October 26th -28th, 2016. Singapore: Springer;
2021 Jul 14]. Available from: https://www.coolingin- 2017. p. 638–41. (IFMBE Proceedings).
dia.in/integrated-bms-for-healthcare-building/ Advances in nurse call systems help to put patients in
Dašić P, Dašić J, Crvenković B. Improving patient control [Internet]. [cited 2021 Jul 14]. Available
safety in hospitals through usage of cloud supported from: https://www.hfmmagazine.com/articles/2790-
video surveillance. Maced J Med Sci. 2017 Apr advances-in-nurse-call-systems-help-put-patients-in-
15;5:101–6. control
How to Create the Perfect Public Service Announcement Rai M, Husain AA, Maity T, Yadav RK. Advance Intelligent
[Internet]. GovTech. 2021 [cited 2021 Jul 14]. Video Surveillance System (AIVSS): A Future Aspect
Available from: https://www.govtech.com/educa- [Internet]. Intelligent Video Surveillance. IntechOpen;
tion/news/how-to-create-the-perfect-public-service- 2018 [cited 2021 Jul 14]. Available from: https://www.
announcement.html intechopen.com/books/intelligent-video-surveillance/
How good public address and intercom systems help save advance-intelligent-video-surveillance-system-aivss-
lives in hospitals - asmag.com Rankings [Internet]. a-future-aspect
Information Technology
and Computerization 41
The IT or computer network has to be efficiently 4. Furthermore, another set of off-site backup
created in the hospital. This is necessary because servers can be provided either in another
the software required for operating the hospital, room of the hospital or other building or
generally called HIS (Hospital Information location. As the data is very crucial for hospi-
System), is used at all the locations and depart- tals, nobody wants to encounter the risks of
ments of the hospital. losing data due to any breakdown, fire or
As the software is loaded in the central servers flooding etc. in the main server.
of the hospital, all the working places have to be 5. All the servers shall be provided with a sepa-
connected to the servers to complete the network. rate UPS power backup of the required
The following issues shall be considered while rating.
designing the network system and providing the 6. An arrangement shall be made for additional
IT hardware. backup of the data on the external devices
like HDD, DVDs etc.
1. The main server shall be provided in the hos- 7. A separate room shall be provided to store
pital and shall be located in a separate server these backup dives in or near the server
room. This room shall be away from the room. For this, a separate air-conditioned
patient area and the entry shall be restricted room shall be provided. The room shall have
to this room. The flooring of the room shall a fireproof cabinet to store such devices.
be raised with a stage type floor free from the 8. The connectivity shall be done with the help
bottom. All the wires and cables shall be laid of CAT 6 cables or optical fibre cables. From
down under the floor. The temperature and the main server the optical fibre cables shall
humidity of the server room shall be pro- be laid down and shall terminate at each floor
vided as per the requirements of the manu- of the hospital building. This cable shall be
facturers of the server. connected to the floor switch boxes. From
2. Server cabinets shall be provided in the the switch boxes, the cables shall be laid
room, and the servers shall be placed in these down till the user point and shall terminate at
cabinets. the connector jack RJ 45. The required work
3. As a precautionary measure, a second server station shall be connected to this jack and
shall also be provided, which shall be a mir- ultimately it will be connected to the main
ror server to the main server, and the data of server of the hospital.
the main server shall be copied on the mirror 9. The technology and design shall be based on
server in real time. set standards and only IEEE or IETF certi-
© The Author(s), under exclusive license to Springer Nature Singapore Pte Ltd. 2022 441
A. Garg, A. Dewan, Manual of Hospital Planning and Designing,
https://doi.org/10.1007/978-981-16-8456-2_41
442 41 Information Technology and Computerization
fied protocols shall be used. The system shall for framing policies and decision making, based
be operative with the systems of other ven- on this analysis, for further improvement in the
dors also, hence the same standards such as hospital.
HL7 and DICOM shall be used. Hospital information system is also known as
10. The IT network shall be capable of support- Hospital Management System (HMS).
ing multiple virtual IP addresses and shall HMS is a common source of recording and
allow multicast routed domains having a retrieving information about a patient’s health
complete traffic separation. history kept at a secure place electronically and
11. The solution shall be provided with adequate used or recovered as and when required. These
security options to protect the network from systems help to enhance the ability and depend-
hacking and exposure of IP. The security of ability of health care workers to provide care by
IT shall be the main concern while designing keeping the track of the patient’s history, dis-
the system. eases, medication, surgeries, visits, and health
12. Bandwidth requirements shall be carefully information that may be needed when required.
designed considering the network and data Patient’s diagnostic investigation like pathology
storage requirements. and even visual images such as X-ray, will be
13. Requirements of the Bandwidth and data
available electronically to the health care profes-
storage shall be worked out based on the sionals as and when required.
software and number of working nodes to be
used in the hospital. Some software like
PACS may require higher bandwidth, while 41.2 Modules of Hospital
software like Laboratory modules may Information Software
require very less bandwidth.
14. Data storage capacity shall be planned in The HIS is basically a bundle of softwares put
such a fashion that the space equivalent to together in one software and integrated to each
data of minimum of 6 years’ operation of the other. Each such software, called ‘Module’,
hospital can be stored. relates to the working of one activity. The HIS
15. If WIFI access is provided to the public in normally has the following modules:
the hospital, Captive Portals shall be used to
implement the system.
41.2.1 Information Desk Module
41.1 H
ealth Information System This module is to provide answer to all types of
(HIS) enquiries relating to the hospital and also relating
to the patients who are registered or admitted in
A Hospital Information System (HIS) is a com- the hospital like:
prehensive and integrated information system for
managing the hospital activities like Finance and 1. Patient’s enquiry
accounts, in-patient treatment admission and dis- 2. Appointment’s enquiry
charge, Investigation departments like radiology 3. Appointment for Investigation enquiry
and pathology, operation theatre, nursing care, 4. Consultant’s/Doctors enquiry
outpatient management, procurements, asset 5. In-patient’s enquiry
management, materials management, pharmacy 6. Tariff information
management, blood bank and payroll manage- 7. Estimates of treatment
ment. Most important is the reporting systems 8. Package’s information
and analysis of the data to provide information to 9. Investigations enquiry
the management about actual performances and 10. Visitor pass management etc.
41.2 Modules of Hospital Information Software 443
41.2.2 Patient Registration Module 1. Schedules for available doctors with date and
time.
Each patient who visits the first time to the hospi- 2. Appointment schedule.
tal shall be registered before he/she goes in for 3. Generating Token for consultation.
consultation. Under this module, the registration 4. Recording Patient Basic parameters.
staff fills up the patients’ personal, medical, fam- 5. Diagnosis.
ily, and demographic details during registration. 6. Result of the Lab orders.
These details are filled up in the system. 7. Results of the Radiology reports.
Thereafter a unique ID is generated for each 8. Prescription of Medication.
patient. This ID is used to maintain the patient’s 9. Cross referral if required.
medical history and diagnosis and also facilitate 10. Details of the Procedures to be carried out.
the tracking of records. This module also helps 11. Reports based on activities of user, patient
generate the token numbers for doctor’s consulta- and doctor.
tion, print the patients’ case sheets with barcode 12. Reports on OPD billing, revenue received
and photograph for easy tracking. Also the bills and number of patient registered at the
for registration charges and doctor’s consultation counters.
can be raised through the module only. This mod-
ule also contains information about the rosters of
physicians and doctors and checks the availabil- 41.2.4 In-Patient Management
ity of those physicians and doctors at any particu- Module
lar time and makes it easy for booking an
appointment. The In-Patient Department module mainly deals
with the indoor activities of the patients and helps
to monitor the activities and complete details of
41.2.3 Outpatient Management treatment for the entire duration of the indoor
Module patients, i.e. from admission to discharge. It has a
facility to count the beds occupied, class-wise
The Outpatient Department module helps in bed allocation and also allot the bed to the patient
booking the consultations with the date and time after searching for a vacant bed. The IPD staff
of such consultation. It also facilitates the regis- can view patient occupancy status of rooms/
tration of the appointment along with the pre- wards, which in turn can help the staff to make
scription and the receipt of the consultation fee quick decisions about cleaning the vacant rooms
deposited. This module also maintains a list of and also the patient placement—from admission,
appointments for each day along with the time of inter ward transfer and discharge.
consultation. Also, the booking of appointments It also sends requests for interdepartmental
is possible for investigating departments like lab- consultations and maintains the record of the
oratory and radiology. From this module, only same. It also provides the link between new-
the SMS and alerts can be sent to patients, borns’ medical records with maternal data
informing them about their scheduled appoint- records. The role of this module begins as soon as
ments. This module mainly deals with recording the patient is registered at the registration counter
of the patients’ medical treatment details along and a bed is allotted in the ward.
with the diagnosis and the investigation reports.
The module is interfaced with other modules 1. Admission of the patient
such as Registration, Laboratory test reports and 2. Bed allotment
Radiology reports to acquire the data from those 3. Inter-departmental consultation requests
modules. 4. Records of Interdepartmental consultations
444 41 Information Technology and Computerization
OT and helps in effectively managing the respec- bill post-surgery. The module also maintains the
tive ward. The module can keep records and records of the pre-operative and post-operative
tracks for all the services rendered to the patient conditions of the patient.
in ward.
1. Scheduling the surgeries by managing OR
1. Information about the upcoming patient’s bookings
arrival, status of the present patients etc. 2. Preparing Pre-operative checklists
2. Recording the vitals charts for monitoring 3. Maintaining the Anaesthesia record
the patient’s vitals. 4. Maintaining the Surgery record like proce-
3. Investigations, tests and procedure to be per- dure/surgery performed, time taken for sur-
formed and generating the request to the con- gery, surgeons and assistants details,
cerned department. complication during surgery if any etc.
4. Ordering, receiving and recording the medi- 5. Taking electronic multilingual consent forms
cines given to the patient. 6. Recording and management of inventory and
5. Booking theatre for surgeries. stock OR
6. Recording and preparing patient for surgery. 7. Sterilization schedules, checks and audits etc.
7. Recording admissions, discharge and inter-
departmental/inter-ward transfers to update
the bed census. 41.2.11 Laboratory Module
8. Communicating with support departments
like security, housekeeping, maintenance etc. The Laboratory module manages record and
9. Recording notes of the procedure maintains the details of various investigations
performed. conducted for both OPD and IPD patients.
10. Maintain Medication chart. Facility to email the results of these investiga-
11. Maintain IN-take and Out-put Chart. tions directly to the patients and also sharing with
12. Prepare Temperature Chart. the treating physician/surgeon for quick refer-
13. Recording other events happening with the ence. It also allows the laboratory staff to manage
patient during treatment. their workflows smoothly. This module can also
14. Recording any adverse reaction or adverse receive online orders of investigations from treat-
incidence to the patient. ing doctors.
1. Capturing data on patient’s condition on the 1. Medicines, Drugs and consumables order to
arrival of the patient. pharmacy
2. Sending alerts to the corresponding depart- 2. Laboratory investigation order
ments, with the data on patient condition for 3. Radiology investigation Order
planning and management of the patient. 4. Diet order
3. Recording and booking the Medico-Legal 5. Blood order to Blood Bank
Cases, preparing Police Information, Injury 6. Invasive/non-invasive Procedure order
Report etc. 7. Order to nurse for ward services
4. Consulting details.
5. Clinical follow-up scheduling.
6. Raising bills for emergency services and the 41.2.18 The Birth/Death
receipt of the same. Registration Module
about patient in terms of patient’s history, demo- 7. Helps the staff to manage cash inflow and out-
graphic details, observation, complaint history, flow, accounts receivables and payable, issue
diagnosis, treatment provided, surgery/procedure and process purchase orders, Bank reconcilia-
observation, diagnosis, investigations done with tion, daily cash day book, preparing hospital
reports, treatment provided, surgery/procedure budgets and comparing the actuals with the
performed and other therapeutic conclusions, it budgets etc.
becomes easy for communication between hospi-
tal and patient and follow-up.
41.2.21 Insurance and Medi-Claim
1. Medical record structure based on UHID Module
2. Scan hard copies of the reports and save in
patient record This module deals with cashless patients and also
3. Checking and completing the patient record the patients of empaneled organizations. The
based on the checklist provided by the module helps for evaluation of the eligibility of a
module patient to get admissions for cashless treatment,
4. ICD codification based on diagnosis for reimbursement in case of TPA or empanelled
5. Access controlled workflow institutions, and process the settlement of bills
6. Indexing the record/data parameters like area, online with the payee.
sex, problem, doctor, clinical department,
diagnosis, lab parameter value, surgery/proce-
dure, MLC, allergies, discharge type, sum- 41.2.22 Human Resources Module
mary etc.
The Human Resources (HR) module manages all
the issues related to hospital manpower like doc-
41.2.20 Billing and Finance Module tors, nurses, consultants, house-keeping staff,
technicians and non-medical staff. It facilitates
The Billing module is for managing the billing of services like daily attendance, salary and incen-
the patient towards the services provided in the tives, leave records, resource engagement and
hospital during the course of treatment. scheduling. It also generates payslips for
employee and payroll reports. It also includes
1. Generate and issue bills for services availed preparing duty rosters and assessing staffing
by the patient in OPD and IPD. needs, recruiting, training and awareness towards
2. Collect advance payments from the patient. various regulations and policies of the hospital
3. Collect payments at the time of final settle- and defining shift rotation.
ment of the bills and issue receipts of the
same. 1. Interfacing with the biometrics machine for
4. Issue refunds if any against the advance daily attendance
payments. 2. Leave entitlements, records of the leave
5. Creating daily estimated billing till date for availed and leave sanctioned
collecting further advances from the patient. 3. Salary calculation taking into effect the provi-
6. Generate MIS reports of collection from OPD sions of PF, TDS, staff advances and loans etc.
and IPD billing, cash flow analysis, calcula- 4. Pre-defined Duty roster and comparison of
tion of the doctors share, summary of dis- actual duties with the roster
counts offered, department-wise or 5. Bonus and incentive calculation
service-wise billing done, and also aging 6. Overtime records and management
reports that give useful insights into the hospi- 7. Outsource employee details, records and
tal’s financials. management
41.2 Modules of Hospital Information Software 449
Water is life. The supply of water and a proper 42.1 Water Supply System
drainage system is necessary for the survival of
the human beings. Particularly in case of hospi- 42.1.1 Source of Water Supply
tals, where it is the question of treating the ill
and critical patients, the water supply and The following can be sources of water for
drainage system has to be excellent, and the hospitals:
importance of clean hygienic, good quality of
water and drainage is critical. The quality of 1. Supply from the Water Network Supplier by
water supplied and the drainage system leaves a connecting to their distribution network (may
great impact on the issues like infection con- be Govt. Supply or others)
trol, life of the medical equipment, staff, 2. Bore Hole
patients hygiene etc. 3. Underground Water Wells
In the hospitals, many systems and operations 4. Connection for Portable Water Trucks
are fully or partially dependent upon clean and
treated water supplied for patients and staff. Also, The following issues shall be considered
the performance of some of the medical equip- related to the water source;
ment depends on the quality of water being sup-
plied to the said medical equipment. Similarly, 1. Generally, the TDS/PPM of the raw water var-
the drainage and treatment of the wastewater are ies from 80 PPM to 2000 PPM. However, it
equally important. may vary depending on the water source.
The reliability of the water supply system is Hence the water needs to be treated so that the
also important. Thus, it has to be ensured that un- TDS/PPM reaches the level of 0–150 PPM.
interrupted water supply is available at all times 2. Hospitals shall arrange for at least two sources
in the building. On the other side, it has to be of water so that a backup is available in case
ensured that the volume of the water shall not be one source of water fails to supply water.
more than required and water stagnation in the Apart from this, one more source of water
tanks shall be avoided. supply shall be arranged as an Emergency
backup for water supply.
© The Author(s), under exclusive license to Springer Nature Singapore Pte Ltd. 2022 451
A. Garg, A. Dewan, Manual of Hospital Planning and Designing,
https://doi.org/10.1007/978-981-16-8456-2_42
452 42 Water Supply and Drainage System
3. The water supplied to the hospital shall be 2. To ensure the proper pressure of water supply
protected, so that the hospital is free from on all the floors, one shall not fully depend on
water-induced infections. the approach of a gravity-driven roof water
4. Before designing, the designer must calculate tank, but booster pumps shall be connected to
the maximum foreseeable water consumption emergency power.
daily along with the average as well as peak 3. The tanks shall be watertight so that the water
flow requirement of water and pressure inside the tank is not contaminated. Also, all
required from the source of water. around and beneath the tank sufficient space
5. While designing the water supply system, the shall be provided for inspection and mainte-
designer shall take into consideration the nance of the tank.
expansion of the hospital that may occur in 4. Each tank shall have
the future. On an average at least 25% spare (a) A drain valve just at the bottom of the
water capacity to the system shall be consid- tank. The drain pipe invert shall be located
ered as a buffer for future expansion. at the extreme bottom of the tank to fully
6. For the water to be supplied, the temperature drain the tank.
shall not be more than 40 °C. If so, the bacte- (b) An overflow pipe connected to the tank.
rial growth such as pseudonymous legionella Overflow pipe shall be directly connected
shall grow in the water and it becomes risky. to the drainage.
Many of the dangerous bacterias thrive in (c) Internal and External access ladders.
such an environment. The designer shall (d) An air vent pipe along with an air inlet
ensure that the water temperature shall be properly covered with corrosion resistant
between 15 and 20 °C. mesh.
Hospital shall have storage of water equivalent to In hospitals, the treatment of water is essential for
3 days consumption. The main storage tank shall controlling the microbiological growth in water.
be made of concrete or Glass-reinforced plastic Hence the arrangement shall be provided for
(GRP) tanks. Water storage calculation shall be treatment of the water depending on the purpose
based on the peak demand vis-à-vis the quantity for which it has to be used.
of water available from the main external water For controlling the microbiological growth in
source. the water, methods shall be provided to control
the temperature, chemical components of the
water. The methods that can be used are the
42.3 Water Storage Tank following:
Locations
is a bit costly as a lot of energy will be required 42.4.6 Reverse Osmosis Treatment
to heat the water. Also, if this method is adopted,
the entire water supply system, including sani- This is the most commonly used treatment pro-
tary fitting, shall have to be shut down for those cess in hospitals. This is a technology that removes
5 min, which can be difficult for medium to large maximum contaminants in the water by passing it
hospitals, but smaller hospitals can use this through a semipermeable membrane under pres-
technique. sure. This water can be used in critical units like
ICU’s, Dialysis NICU etc. and can also be used
for drinking. RO filtration has various methods of
42.4.2 Chemical Treatment filtration like pre-filter, sand filters, charcoal fil-
ters, reverse osmosis and Ultraviolet filtration.
For chemical treatment, Chlorine Dioxide is
used. As Chlorine dioxide is an oxidizing biocide
that reacts with the organic substances in the 42.4.7 Ultraviolet Treatment
water, it oxidizes the entire growth in the pipe-
lines and the sanitary fittings of the system. Ultraviolet (UV) is used to deactivate or kill the
bacteria in water. This is achieved with the help of
UV light, which disrupts the natural makeup of
42.4.3 Chlorine Water Treatment bacteria. For proper treatment, Ultraviolet light
with optimum wavelength close to 254 nm shall
Under this method, Chloramine is used for be used for the destruction of biological matters.
water treatment, as chloramine provides anti-
bacterial activity with low levels of chlorine. As
compared to free chlorine, which is rapidly lost, 42.4.8 Ozone Water Treatment
chloramines remain for much longer time hence
more effective. But care has to be taken not to For Ozone treatment, an unstable gas made up of
use this water for some of the procedures like 3 oxygen atoms is used, which lasts for a few mil-
dialysis unit, as it can cause haemolysis to the liseconds. Ozone Water Treatment has proved to
patient. be a good disinfection method as it reduces the
concentration of iron and manganese elements in
the water. Under this technique, an ozone con-
42.4.4 Water Softener Plants centration is created by passing dry and clean
water through a high voltage electric discharge.
This method is used where the contents of When the raw water is passed through the venturi
Magnesium and Calcium are higher in the water, throat, it creates a vacuum and pulls the ozone
as it can lead to deposition of scales in the pipe- gas into the water for treatment of water.
lines and the sanitary fittings. This method is
used for water being supplied to Steam Boilers,
Laundry, Hot Water Systems, Cooling Towers 42.4.9 Distilled Water
and toilets of the hospital.
It is made from condensed steam after it is cooled
and liquefied.
42.4.5 Silver–Copper Ionization
1. The quality of drinking water, even after 42.7.1 Electrical Hot Water
Chemical treatment, shall be safe for human Generation
consumption.
2. To prevent the temperatures of drinking water Under this system, a hot water generator is pro-
from exceeding 20 °C and stagnation of the vided to heat the water. This is a cylindrical tank
water, the water shall be supplied from a cen- made out of stainless steel and is insulated to
tral water storage tank that is made for drink- avoid any thermal losses. At the bottom of the
ing water only. tank, high-rated heating elements are provided,
3. If a central drinking water system is not which heat up the water in the tank. These ele-
available, then the provision shall be made ments are controlled by the thermostat, which
for bottled drinking water through water monitors the temperature of the water. Once the
coolers. water temperature falls below the set temperature,
the elements are switched on and switched off
when the water reaches the preset temperature.
42.6 Water Booster Pumps
In hospitals, high flow of water is essential for 42.7.2 Hot Water Generation
hygienic hand wash and cleaning. Therefore, the from Boiler/Steam by
hospital shall have a system for constant and high Burning Fuel
flow water pressure to ensure hygienic and clean
infection-free environment. Hence the following In this technique, a steamer or a boiler is pro-
shall be provided; vided for heating up the water. Below the water
tank, fire place is provided for burning the fuel.
1. The pressure at fixtures of cold water supply As the fuel burns, water gets heated. The fuel that
shall be appropriate. can be used is Gas, Wood, Coal or waste oil etc.
2. The flow velocity of the cold water piping
shall be appropriate.
3. A booster pump shall be provided to ensure 42.7.3 Solar Hot Water Generation
that an adequate pressure of water is available
throughout the hospital. In this system, solar cells having conductive copper
4. Multi-stage booster pumps shall be used pipe capillary lines are installed on the rooftop
instead of single-stage pumps. where solar cells are exposed to sun rays. The water
5. An emergency power supply shall be pro- flows in these copper tubes within the solar cells
vided to the booster pumps. and gets heated. This water is then stored in an insu-
lated water tank, from where it is supplied to desired
places. The biggest disadvantage of this system is
42.7 Hot Water System that when the sun rays are poor or on any rainy day
when sun rays are not available, water cannot be
In hospital, hot water is needed at a number of heated. Hence solar water systems shall be backed
places like Hand Wash Basins, Scrub Sinks, up by providing a standby system for heating water.
CSSD, Kitchen, Patient’s bathrooms, Mainte-
nance Areas and Instrument washing area. The
following issues shall be kept in mind while 42.7.4 Stand-Alone Hot Water
designing the hot water facility; Geysers
There are different types of hot water systems
that are generally provided in the hospitals as In small hospitals, where it is not feasible to
follows: install a central hot water system, individual
42.11 Steam System 455
stand-alone geysers are used to supply hot water. water, the flow restrictors or aerators shall not
These geysers are installed at different locations be used in the taps and the mixers.
and the inlet pipeline and outlet pipeline have to 6. Adjustable spray options shall not be pro-
be laid down. At the location of the geysers, the vided in the shower heads as this can lead to
required power switch/socket shall be provided. water stagnation issues.
As compared to any other commercial building, There are various locations in the hospital where
the sanitary fittings of the hospitals are different. the steam is required like laundry, food and bev-
The goal is to have an environment that is free erages, laboratories, sterile store, CSSD etc. As
from any infection and shall be safe and hygienic. the usage of different units is different, the qual-
The following issues shall be considered while ity of steam to be supplied to a unit will depend
designing the sanitary fittings; on the application for which it will be used, e.g.
the areas like laundry or food and beverages
1. In hospitals, the design shall provide leverage may have ordinary plant steam, the CSSD and
for future maintenance of the sanitary system critical areas shall be provided with clean steam
and shall be durable. and the sensitive areas like laboratories or phar-
2. Isolation valves shall be provided at the main maceutical preparation may require pure and
entrance of sanitary fixtures in toilets. filtered steam. The following are the important
3. In hospitals sensor taps should be preferred points that shall be considered while designing
for hand wash basins. the steam system;
4. Spray-type mixer taps shall not be provided in
the hospitals. 1. Source of Steam System
5. As some of the mixing taps are provided with Generally, in hospitals, there are two
the flow restrictors at the point of discharge. sources from where the steam can be gener-
As these restrictors can be a source of bacte- ated. These are Central Steam Boiler System
rial growth, and also hampers the free flow of or Local or Central Electrical Steam Generator
456 42 Water Supply and Drainage System
1. Considering the location of the hospital, the This type of drainage contains human waste and
nearby network of drainage, main holes and is created from WC’s, Urinals and Dirty Linen
connection points shall be assessed. washrooms etc.
42.15 Methods of Drainage 457
42.15.1 Vent Pipes In hospitals, usually there are drainages that may
consist of bio hazardous material with suspended
To avoid the foul smell of the effluent coming out living organisms which may create a risk of infec-
of the drainage, all the drainage systems shall be tion. These types of drainage can be from the areas
provided with the vent pipes in the drainage sys- like isolation rooms etc. For these types of effluents,
tem to vent out the odour in the atmosphere. the holding tank, called ‘Kill Tank’, shall be con-
nected to all the concerned areas from where the bio
hazardous material is discharged. This kill tank is
42.15.2 Floor Drains injected with a chemical to attack the hazardous
organisms before finally draining the effluent.
Floor drain and clean out drains shall be through
the trap to prevent odours. As the floor drains
usually dries out due to evaporation, there is a 42.15.6 Radiation Drainage
need to make arrangements that the trap is refilled
with water if it dries. It can be done by providing Radiation tank shall be provided at a location
the primer valve connected to the water supply to where it is harmless for radiation exposure. If the
timely refill the trap. Local municipality does not allow for radiation
drainage in the external drainage network before
being diluted, a holding tank shall be provided.
42.15.3 Soil Water Drainage
Soil drainage is usually the discharge from Toilets 42.15.7 Kitchen Grease Drainage
(WC’s), urinals and dirty utilities. This can be
drained using the S-Trap or P-Trap discharge sys- The drainage system of the kitchen shall be pro-
tems. However, the use of a P-trap system is rec- vided with the grease interceptor before discharg-
ommended as it is easier to maintain. ing the effluent to the external drainage network.
458 42 Water Supply and Drainage System
Once the drainage system is complete and is Paleologos EK, O’Kelly BC, Tang C-S, Cornell K,
connected to the main holes of the buildings, the Rodríguez-Chueca J, Abuel-Naga H, et al. Post
Covid- 19 water and waste water management to
drain water has to be treated before it is finally protect public health and geoenvironment. Environ
drained in the main sewerage network provided Geotech. 2021 May 1;8(3):193–207.
by the municipality or to be discharged in the Hospital plumbing systems [Internet]. [cited 2021 Jul
soak pits. 14]. Available from: https://www.hfmmagazine.com/
articles/2260-hospital-plumbing-systems
For water treatment, please refer to the chapter Emergency Water Supply Planning Guide for Hospitals
of ‘BIO-MEDICAL WASTE MANAGEMENT’ and Healthcare Facilities | Water, Sanitation, &
(Chap. 46) in this book. Hygiene-related Emergencies & and Outbreaks |
Healthy Water | CDC [Internet]. 2020 [cited 2021 Jul
14]. Available from: https://www.cdc.gov/healthywa-
ter/emergency/ewsp.html
Further Reading Council NR. Drinking Water Distribution Systems:
Assessing and Reducing Risks [Internet]. 2006 [cited
Galowin LS. Water supply and drainage in buildings.:252. 2021 Jul 14]. Available from: https://www.nap.edu/
Balwani KS, Nagarnaik DPB. Water and Waste Water catalog/11728/drinking-water-distribution-systems-
Management of a Hospital- A Review. 2015;6(4):4. assessing-and-reducing-risks
Altin A, Altin S. Sustainable Water and Wastewater
Management in Hospitals. Turk J Occup Environ Med
Saf. 2017 Jul 14;2:1–7.
Vertical Transportation System
43
In any multi-storey hospital, everyone is greatly patients on wheelchairs. Main issues relating to
dependent on the vertical lifts for providing an passenger lifts are:
efficient vertical transport system amongst differ-
ent floors and it is essential for movement of 1. The clear internal minimum dimension of the
patients, medical equipment, support services, lift car shall
staff and visitors. a. Width—2000 mm
Lifts are essential to provide firefighting and b. Depth—1700 mm
evacuation facilities in case of fire or accident. In c. Loading Capacity—1250 kg
most of the countries, lifts are subjected to pre- d. Door Opening—1100 mm
scribed statutory regulations of the country. Hence e. Internal Height—2100 mm
the lifts shall meet the statutory regulations as pre- 2. It is advisable to provide a separate lift
scribed by the concerned municipality. intended for housekeeping services.
3. As far as practically possible, the passenger lifts
shall be separate from the Bed, Service and
43.1 Lift Categories Goods lifts and shall have separate lifts
lobbies.
Usually the lifts are a box type square or rectangular
structure called car. This car moves inside the lift
shaft and the doors are provided at each floor. 43.1.2 Bed Lifts
Another option can be the slope elevators or the
stair elevators. Both these elevators takes lot of 1. These lifts are used to carry patients on patient
space, hence generally not provided in the hospitals. beds or stretchers along with the necessary
However, if ramp has to be provided in the hospital, support equipment and staff.
the designer can think of providing slope elevator. 2. The clear internal minimum dimension of the
The lifts in hospital buildings can be categorized lift car shall
and provided based on the function as below: a. Car Width—1800 mm
b. Depth—2700 mm
c. Loading Capacity—2500 kg
43.1.1 General Passenger Lifts d. Door Opening—1400 mm
e. Internal Height—2500 mm
These lifts are used for the general passengers
like staff, doctors and visitors, including the
© The Author(s), under exclusive license to Springer Nature Singapore Pte Ltd. 2022 459
A. Garg, A. Dewan, Manual of Hospital Planning and Designing,
https://doi.org/10.1007/978-981-16-8456-2_43
460 43 Vertical Transportation System
compared to side opening doors. Hence the 15. Power supply to lifts shall be directly from
lifts being used by patients and clinical staff the MDB provided near the machine room of
shall have centre opening doors. Side open- the lifts.
ing lifts shall be used for goods lifts or ser- 16. Handrails shall be provided in the cars on at
vice lifts. For general passengers and visitors, least two long sides of the car for patient
either of the two lifts can be chosen. safety.
4. The Machine Room Less (MRL) lifts shall 17. The flooring of the car shall not be slippery
be preferred as in these lifts, the machine and shall be easily cleanable.
room on the top floor is not required. 18. Fire-rated doors shall be preferred in for the
5. Emergency lighting shall be provided in lifts lifts.
with at least 1hr battery backup. 19. The lift shall have a provision of Overload
6. The hall buttons shall be provided on each device to warn when the lift is overloaded.
floor to call the lifts. Similarly, all the floors 20. The lift shall have provision of Emergency
shall have the lift indicator to know the posi- Firemen’s service.
tion of the lift car. 21. The lift shall also have a provision of auto-
7. Lift shafts, including walls and ceiling, shall matic Belt Inspection device.
be properly sealed and painted to reduce the
risk for the transmission of infection across
the floors as the lift well penetrates all floors Further Reading
of a hospital.
8. Lift car doors shall have Infrared Curtain Vertical Transportation - Lift System Design | WSP
[Internet]. [cited 2021 Jul 14]. Available from: https://
Door Sensor protection device for contact- www.wsp.com/en-GB/services/vertical-transportation
free detection of the obstruction to avoid the Al-Sharif L. The Design of Elevator Systems in High Rise
risk of accident due to door collisions. Buildings, Part 1. Lift Rep. 2017 Oct 1;43:46–62.
9. The lifts shall be provided with an intercom Shrestha A. Safety Considerations for the Design of
Modern Elevator Systems. Honors Theses [Internet].
line so that in case of emergency, the passen- 2019 Jan 1; Available from: https://egrove.olemiss.
gers may contact the emergency service edu/hon_thesis/1195
department. Health C for D and R. Patient Lifts. FDA [Internet].
10. The lift shall also be provided with a hooter, 2019 Apr 26 [cited 2021 Jul 14]; Available
from: https://www.fda.gov/medical-devices/
so that the passenger can press the hooter general-hospital-devices-and-supplies/patient-lifts
button in case of emergency. Going up: Hospital lift technologies [Internet].
11. There shall be provision of CCTV cameras in [cited 2021 Jul 14]. Available from: https://build-
the lifts to record live images inside the lift car. i n g b e t t e r h e a l t h c a r e . c o m / n ew s / a r t i c l e _ p a g e /
Going_up_Hospital_lift_technologies/102242
12. The ARD (Automatic Rescue Device) shall Elevator | vertical transport [Internet]. Encyclopedia
be provided in the lifts so that in case the lift Britannica. [cited 2021 Jul 14]. Available from:
stops due to power failure, the ARD device https://www.britannica.com/technology/elevator-
shall bring the lift to the nearest lower floor, vertical-transport
Shirley E. Circulation analysis and lift placing in hospi-
and the doors open automatically to rescue tals. Comput-Aided Des. 1974 Oct 1;6(4):206–10.
the passengers. An Architect’s Guide To: Elevators and Escalators -
13. Bed lifts shall be provided with a feature of Architizer Journal [Internet]. Journal. 2018 [cited 2021
priority lift car call option for patients in crit- Jul 14]. Available from: https://architizer.com/blog/
product-guides/product-guide/elevators-escalators/
ical care.
14. As far as possible the lifts shall be provided
with the power backup either by UPS or
other alternate power source.
Pneumatic Tube Systems (PTS)
44
© The Author(s), under exclusive license to Springer Nature Singapore Pte Ltd. 2022 463
A. Garg, A. Dewan, Manual of Hospital Planning and Designing,
https://doi.org/10.1007/978-981-16-8456-2_44
464 44 Pneumatic Tube Systems (PTS)
A details of the carrier movements along with the Zone is a set of stations which are connected
date and time along with the station details are directly to each other by tubing connections. E.g.
stored as a repository in the system for each of a particular floor of the hospital can be one zone,
the PTS systems. and the next floor can be another zone. Further,
the Zones can also be connected to other zones. A
single zone can accommodate about 10 stations,
44.1.5 Inter-Zone Connection whereas a Blower Group Zone can accommodate
about 60 stations.
This is a section of tubing network and is used to
connect one zone with another zone.
44.1.10 Slow Speed Device
Wayfinding or so-called the Signage System is a visitors are generally unaware about the locations
concept that is used to orient and navigate people and passages of the hospital setup, the wayfind-
through the space in a hospital setup. In hospitals, ing systems help a lot in providing the informa-
the purpose of wayfinding systems is to direct tion to these patients and visitors. Visitors may
and guide patients, visitors and staff from entry also include representatives of units providing
points and car parks to reach their destinations commercial service, people arriving in the hospi-
and back again. tal for deliveries of stores, supplies and spaces,
A well-designed wayfinding system can guide medical representatives, equipment suppliers,
the patient, visitors, staff to their destination consumable suppliers, Govt. Officers like police
without any inconvenience or adding to the con- officers and fire brigade officers, other health and
fusion, stress and worry that they are already suf- welfare workers and other official representatives
fering from. Whereas inefficient or poor of various services.
wayfinding systems may cause stress, frustration,
disorientation and helplessness.
An ineffective wayfinding system also leads to 45.1.2 Staff
people becoming lost and wastes the time of staff,
patient and visitor in just enquiring the locations. As such the way finding system is of not much
Effective wayfinding systems make it easy for use for the staff, as being regular users of the sys-
people to use the spaces and areas inside the hos- tem, most of them become familiar with the loca-
pital building. tions of the hospital setup over a period of time.
The wayfinding can help the staff in making peo-
ple aware of the spaces and locations, who are
45.1 Categories Using Wayfinding lost or in need of assistance.
© The Author(s), under exclusive license to Springer Nature Singapore Pte Ltd. 2022 467
A. Garg, A. Dewan, Manual of Hospital Planning and Designing,
https://doi.org/10.1007/978-981-16-8456-2_45
468 45 Signage System
45.1.4 Sensory Impairment colour of the sign board is dark blue, the text
shall be in white colour, so that it is easily
Blind people or the people with low vision and visible.
people with hearing impairment usually find it 7. The indoor sign boards shall be well lit with
difficult to find the way and reach their location. background light to make it more readable,
Those with limited vision have to rely strongly even in the night or low light.
on colour recognition, highlighted and clearly 8. The placement of the sign boards shall be
readable signboards and audible clues etc. such that it comes in eye contact while the
Similarly, people with hearing impairment rely user is moving in the building. E.g. the sign
more on written messages, signboards, lip- boards can be placed at the front wall at the
reading and hand commands to communicate. end of the corridor, in landing of the staircase
and hanging sign boards in the corridors etc.
9. The routes and the paths shall be well struc-
45.1.5 Language and Illiteracy tured and shall be clear and as short as
possible.
Due to illiteracy, the wayfinding systems shall 1
0. Sign boards for the handicapped users shall
have a provision for standardized symbols and be clearly written in text as well as symbols.
pictographs along with alphabetical signage that 11. The use of landmarks shall be promoted to
can support the people to find the way who are provide orientation and memorable points to
functionally illiterate. orientate the user.
12. The fire exit plans shall be provided as per
the norms of the country. Fire exit sign
45.2 Principles for Designing boards shall be specifically well lit with a
Wayfinding System power backup available.
13. The hospital route plan or the site plans can
While designing the wayfinding system, the fol- be printed on the hospital brochure to make
lowing principles shall be followed: the user aware of the routes of the locations
well in advance before landing in the hospi-
1. Create a unique identity, say room number or tal building.
hall number, for each location of the 14. At the main reception, display charts shall be
hospital. provided displaying the details of the depart-
2. Different zones of the regions shall be cre- ments with room number and location, the
ated like Diagnostic zone, Intensive Care list of indoor plans with room number and
Zone, OPD zone etc. Each zone shall be dif- location, the list of doctors with their room
ferentiated either by colour scheme of the numbers, days and timings. Apart from this,
different visual characters. the floor plan indicating the zones, regions,
3. Use of floor or wall strips to show the route and the follow through colour strip coding
and the display what is ahead of this place shall be provided.
shall be considered. 15. Right from the first point like parking lot, the
4. Provide the sign boards right from the entry sign boards shall be provided depicting the
point or from reception onwards so that the main entrance route, emergency route or the
user can follow the wayfinding from that OPD route etc.
point onwards. 16. The entry and exit gate of the hospital build-
5. The sign boards shall be clearly visible, and ing shall also be provided with clear and
the fonts shall be kept in such a size that it is readable sign boards and shall be well lit to
easily visible from a distance. be used at night.
6. The colour scheme of the signboards shall be 17. In hospitals where there are multiple
in contrast colour. E.g. if the background entrances and exits points, the sign boards
45.2 Principles for Designing Wayfinding System 469
shall be provided at all such major entrances angle, angular distortion occurs. If the font
and exits. is distorted by a 45-degree angle, the legi-
18. The emergency department shall have large bility will decrease by 75%. Also poor light-
size sign boards, so that it is visible right ing may further reduce the legibility.
from the entry point of the hospital. Therefore, the letter height of 45–50 mm
19. The sign boards depicting the room number shall be used to make it readable from a dis-
and the purpose of the room shall be pro- tance of 15 m.
vided at the entrance door of all such rooms 28. Along with the text, icons or symbols that
or halls. Also a name plate shall be provided represent the department, facility, object or
at the entrance door of the room or hall to service shall be used for the users who are
show the name and designation of the person not literate. Through the combination of
occupying the room/hall. colour, text, symbols and icons, more infor-
20. The serving counters like the reception coun- mation can be delivered in a small space.
ter, cash counter, help desk or the nursing 29. Messages can be aligned left, centred or
counter etc., shall be clearly marked and right. Out of these left-aligned text is consid-
numbered. ered to be the most effective alignment.
21. Where ever required, the directional arrows However, the justified alignment from both
shall be provided on the sign boards. sides is recommended to be used.
22. Vehicular sign boards shall be displayed on 30. Keep terminology that is simple and
the side of the roads to provide indications to understandable by the user. E.g. for the
the drivers and display signs such as zebra department of ENT, the terminology
crossing, one-way entry, speed limit and stop ‘Otorhinolaryngology’ is not understand-
signs etc. shall be provided. able by the user, hence the terminology
23. Proper sign boards shall be provided in the ‘ENT’ shall be used.
parking lots depicting the parking position 31. Signs boards shall be bi-lingual, one of them
and reserved parking locations for VIP, Staff shall be English and other the Local language
etc. which is easily understandable by the user.
24. Do not place the sign boards too high, mak- The layout shall display both languages one
ing it difficult to read. The maximum top-end above the other.
height shall not be more than 1600 mm above 32. In all the lift lobbies and the staircases, the
the floor level. Generally, sign boards should building levels shall be clearly displayed on
be located within the 1200 mm–1800 mm each and every floor of the building. Hence
band. the marking shall not create confusion about
25. A directory shall be organized as per the user the floors. Therefore, the ground floor shall
needs and not by bureaucratic hierarchy of be termed as ‘Ground Floor’ and not the first
the hospital. E.g. the directory of the doctors floor. Similarly, the Service floor shall be
shall be placed above in the list and not the termed as ‘Service Floor’ and not ‘SF’ as this
CEO or directors of the hospital. As the may give the appeal of the second floor or the
patients are more concerned with the doctors fifth floor because sometimes it looks like 5.
and not with the executives of the hospital. 33. The size of the sign boards shall be carefully
26. Letterforms should be clearly readable, and planned, so that it is visible to the user from
the fonts shall be chosen which are legible. a required distance. Too large sign boards
The capital height ratio of the typeface shall shall also be avoided, as they look shabby
be approximately 3:4. Use of capital letters and are a waste of funds.
shall be preferred for signage. 34. The size proportions of sign boards shall also
27. Size of the letters shall be such that it is leg- be planned well so that it does not look
ible from a distance. The standard size of disproportionate.
25 mm letters is generally legible from 35. Signs should be located keeping sufficient
15 m away. If the sign board is viewed from distance and spacing from each other.
470 45 Signage System
Sign boards can be of different types like: This classification is based on the mounting meth-
ods with which the sign boards are displayed like:
and are generally used as ceiling suspended Guenther R, Vittori G, Atwood C. Values-Driven Design
sign boards. and Construction: Enriching Community Benefits
through Green Hospitals. :40.
3. Illuminated Sign Boards Hospital & Healthcare Signage: Improving Patient
These are the sign boards that are illumi- Satisfaction [Internet]. DGI Communications. 2018
nated with the internal self-illumination from [cited 2021 Jul 14]. Available from: https://www.dgi-
the background, externally illuminated with communications.com/hospital-signage/
admin. Healthcare Wayfinding and the 6 Rules for
the bollard or spotlights. All these sign boards Effective Systems [Internet]. ID Signsystems
require lighting by some means may it be the Architectural Signage, Design & Lighting. 2015 [cited
natural or artificial light. 2021 Jul 14]. Available from: https://idsignsystems.
4. Dynamic or Static com/six-rules-of-healthcare-wayfinding/
Rodrigues R, Coelho R, Tavares JMRS. Healthcare
The static sign board displays the same Signage Design: A Review on Recommendations
information and until replaced physically. for Effective Signing Systems. HERD. 2019
Dynamic signs are used where the informa- Jul;12(3):45–65.
tion changes often. E.g. information regarding Lee S-C, Kim Y-J, Kim T-H, Yun S-J, Lee NK, Kim
W-J. Impact of obesity in patients with urolithiasis and
patient room allocations, token numbers of its prognostic usefulness in stone recurrence. J Urol.
waiting patients and information of the hospi- 2008 Feb;179(2):570–4.
tal facilities etc. Potter JS. Best Practices for Wayfinding in a Hospital
Setting. :60.
Murphy P, Projects SS. 3 Innovative Wayfinding Solutions
for Expanding Healthcare Facilities [Internet]. GNU
Further Reading Group. 2019 [cited 2021 Jul 14]. Available from:
https://www.gnugroup.com/resources-i nnovative-
Devlin AS. Wayfinding in healthcare facilities: contri- wayfinding-s olutions-f or-e xpanding-h ealthcare-
butions from environmental psychology. Behav Sci facilities/
Basel Switz. 2014 Oct 31;4(4):423–36.
Biomedical Waste Management
46
Biomedical Waste Management is governed ables, catheters and other devices used for pene-
by the legislation of individual country or trating the skin. Also, discarded sharps objects
state, which issues their own set of rules and like needles, lancets or blades, are considered to
regulations to manage such waste. be a biomedical waste, as there are all the possi-
In India, the Directorate General of Health bilities of them being contaminated with body
Services, Ministry of Health and Family fluids or blood.
Welfare, has issued such rules known as
‘Biomedical Waste Management Rules, 2016’.
As it is not possible to define and discuss the 46.1 Classification of Hospital
rules and regulations of all countries, we have Waste
tried to highlight the ‘Biomedical Waste
Management Rules, 2016’ issued in India for It is the primary responsibility of the hospital to
understanding this chapter. manage the biomedical waste generated within
The content of this chapter is the synopsis the hospital, which includes collection, segrega-
of the Biomedical Waste Management Rules, tion, storage, transportation, pre-treatment and
2016 and shall not be considered as disposal of such waste.
Plagiarism. The waste generated from the hospitals is
Biomedical waste, also known as ‘Hospital classified as:
waste’, is the waste that may contain infectious
(or potentially infectious) materials. It can also • Biomedical Waste
include waste originating from the laboratory. • General Waste
However, it differs from normal trash, kitchen • Other Wastes
waste or general waste. It also differs from other
hazardous waste, such as chemical, radioactive,
universal or industrial waste. 46.1.1 Biomedical Waste
Biomedical waste can be in any form or shape;
solid, semi-solid or liquid. Some examples of It is the waste generated from a hospital that can
such infectious waste include discarded labora- adversely affect the health of a person or environ-
tory specimens, blood, body parts, amputated ment, if not disposed of properly. These wastes
limbs, other animal or human tissues, removed are generated during diagnosis, treatment and
bandages and materials used for dressing, used other interventions. This is approximately 15% to
surgical gloves or any other medical consum- 20% of the total hospital waste.
© The Author(s), under exclusive license to Springer Nature Singapore Pte Ltd. 2022 473
A. Garg, A. Dewan, Manual of Hospital Planning and Designing,
https://doi.org/10.1007/978-981-16-8456-2_46
474 46 Biomedical Waste Management
Biomedical Waste is disposed in colour coded Such wastes shall be handled and disposed
bags, where each colour defines the type of waste of as per the rules and regulations of the
to be put into it as follows: respective country and/or state.
46.4.2 Packing of Biomedical Waste 2. The waste shall remain there until it is finally
and Labelling disposed.
3. This room shall be at a distance from public
1. Biomedical waste bags shall not be filled spaces and shall be restricted.
more than three quarters. 4. The space shall have the capacity to store
2. Bags shall be tied with a cable tie and never waste generated for at least 2 days.
stapled. 5. This room shall have an RCC roof with the
3. For replacement, empty bags shall be avail- facility to be locked. It shall also be guarded
able at the collection point. round the clock.
4. Biohazard symbol shall be printed on colour 6. The room shall be provided with a ramp to
coded waste bags. transport trolleys.
5. Details like collection date, waste type and 7. Flooring shall be made out of tiles or other
quantity shall be labelled on the filled bags. glazed material, and shall have a slope to
6. The bags shall have a bar coded stickers to wash the room.
allow tracking till final disposal. 8. Exhaust fans shall be provided for
ventilation.
9. Fire extinguisher, smoke detector and sprin-
46.4.3 Interim Storage kler system shall be installed to prevent fire.
10. Tap water shall be supplied to wash the room
1. For interim storage of biomedical waste, dirty and containers.
utilities shall be used and the waste shall not 11. Signboards and logo of Biomedical Waste
be stored in wards or departments. Hazard shall be fixed.
2. Similarly, it shall not be stored in the patient care
area, clinical area, procedures areas and OR.
3. If dirty utilities are not available, waste shall 46.6 Record Keeping
be stored away in a low traffic area.
1. Hospital shall maintain the records of the
location of waste generation point, quantity
46.5 Transportation of the waste generated, details of waste trans-
of Biomedical Waste ported and date and time of disposal.
in Hospital 2. Quantity of waste generated shall be recorded
category wise in the Biomedical Waste
46.5.1 Transportation Trolleys Register/logbook.
3. A weighing machine shall be provided in the
Transportation of such waste shall be done using central waste collection centre.
closed trolleys or containers. 4. Records shall be prepared as an annual report
and submitted to authorities.
5. Records of training provided to the people
46.5.2 Route of Transportation handling and segregating biomedical waste
shall also be maintained.
A route having fewer patients and visitors shall 6. Annual health check-up and immunization
be chosen to transport such waste. records of all the employees shall be
maintained.
7. Records and minutes of Biomedical Waste
46.5.3 Central Waste Collection Management committee meeting shall be
Room for Biomedical Waste maintained.
8. Records of any accident that may have
1. Hospital shall have a central waste collection occurred shall be maintained along with details
room, located on the hospital premises. of corrective and/or preventive actions taken.
476 46 Biomedical Waste Management
Waste Management in Rural Uganda. Front Public Rao D, Dhakshaini MR, Kurthukoti A, Doddawad
Health [Internet]. 2019 [cited 2021 Jul 15];0. Available VG. Biomedical Waste Management: A Study on
from: https://www.frontiersin.org/articles/10.3389/ Assessment of Knowledge, Attitude and Practices
fpubh.2019.00136/full Among Health Care Professionals in a Tertiary Care
Letho Z, Yangdon T, Lhamo C, Limbu CB, Yoezer S, Teaching Hospital. Biomed Pharmacol J. 2018 Sep
Jamtsho T, et al. Awareness and practice of medi- 21;11(3):1737–43.
cal waste management among healthcare pro- Wafula ST, Musiime J, Oporia F. Health care waste man-
viders in National Referral Hospital. PloS One. agement among health workers and associated fac-
2021;16(1):e0243817. tors in primary health care facilities in Kampala City,
Peng J, Wu X, Wang R, Li C, Zhang Q, Wei D. Medical Uganda: a cross-sectional study. BMC Public Health.
waste management practice during the 2019-2020 2019 Feb 18;19(1):203.
novel coronavirus pandemic: Experience in a general
hospital. Am J Infect Control. 2020 Aug;48(8):918–21.
Fire Safety
47
© The Author(s), under exclusive license to Springer Nature Singapore Pte Ltd. 2022 479
A. Garg, A. Dewan, Manual of Hospital Planning and Designing,
https://doi.org/10.1007/978-981-16-8456-2_47
480 47 Fire Safety
47.2 S
tructural Elements for Fire 5. Outside storage and other tanks shall be cov-
Safety ered with slabs and shall be strong enough to
take heavy vehicle load.
The following structural elements shall be pro- 6. Open space left for this purpose shall not be
vided while designing a hospital building: used for any other purpose like parking etc.
7. Access roads shall be provided around the
building and shall not be terminated with dead
47.2.1 Compartmentalization ends.
used in case of fire. Exits shall land in an 15. The travel distance of exit shall be as
open space near/outside the building. described in the rules and regulations of the
2. Width, height and number of exits shall be in country or state.
accordance with the rules and regulations of
the country or state.
3. Exit doors shall open in the direction of exit, 47.2.5 Corridors and Passageways
and not inside, so that in case of hurry, the
door can be pushed outside than pulling 1. The width and height of corridors and pas-
inside. sageways shall be as described in the rules
4. Exit doors shall open in an enclosed and regulations of the country or state.
stairway. 2. The width of the exit corridor and passage-
5. Exit doors shall be openable without any ways shall never be less than the width of the
key. exit doorways.
6. Fire-rated doors, assembly and hardware 3. Corridors shall be well ventilated and shall be
shall be certified and labelled by the manu- free from any obstruction.
facturer giving details about the type of door, 4. In cases where the door of rooms open in the
serial/batch number of door, manufacture corridors, such doors shall open inside the
details like year/month, fire resistance rating room and not in the corridors, to permit free
etc. flow of traffic in the corridor.
7. Access-controlled doors or electro-magnetic
doors, if provided, shall be fire rated as
described in the rules and regulations of the 47.2.6 Staircases
country or state. Manual release device shall
be provided with the access-controlled doors. The hospital building shall have staircases. The
8. Such provisions shall be made that boom numbers of staircases required, width of the stair-
barriers, turnstiles, access-controlled exit case, width of the staircase thread, height of the
doors, and other such exits open automati- riser, number of risers per flight, and minimum
cally in case of fire or smoke. headroom shall be as described in the rules and
9. Walking surfaces of exit area shall comply regulations of the country or state.
with the rules and regulations of the country
or state. 1. If internal staircases are provided, they shall be
10. Number of exits access, width of corridors, constructed with an external wall and shall be
aisles or ramps, capacity of exit access, and made out of non-combustible materials. These
travel distance to an exit shall be in accor- staircases shall not be built around the lift shaft.
dance with the rules and regulations of the 2. Metal staircases shall be avoided as they get
country or state. heated in case of fire.
11. Obstruction due to objects like chairs, tables, 3. Pipelines or ducts of chimney, HVAC, gas or
cupboards or any other obstructions shall be electrical lines shall neither be allowed in the
avoided in the exit access. stairway nor shall they pass through the
12. The exit access shall be properly lit with staircase.
floor light strips or fluorescent strips for easy 4. On one side of the staircase, handrail shall be
identification of access. provided, the height of which shall be as
13. Exit signages of adequate size shall be placed described in the rules and regulations of the
in the exit access and suspended on the ceil- country or state.
ing. Evacuation plan shall be affixed on the 5. Lifts shall not open in staircase.
wall of all important places in the building. 6. All external stairs shall directly open on the
14. Exit access shall not pass through any room ground, in an open area.
or hall. 7. Avoid using spiral staircase.
482 47 Fire Safety
1. If a glass façade is used for the elevation of a state. While designing the fire detection and
building, it shall completely be a tempered alarm system, the following points shall be taken
glass with non-combustible assembly. care of:
2. Sprinklers shall be located near the glass
façade and shall provide full coverage to the 1. For fire detection, an intelligent, analogue or
glass. addressable fire detection and alarm system
3. All gaps in the glass façade shall be properly shall be provided in the building. It shall con-
sealed. sist of smoke detectors, heat detectors,
4. Sufficient number of fire openable panels response indicators, manual call stations,
shall be provided in the glass façade. hooters/strobes, fault isolators and control
cabling. The system shall be connected to a
microprocessor-based fire alarm control
47.2.12 Surface Interior Finishes panel.
2. Fire detection and suppression systems shall
Use of non-combustible walls and ceiling surface be so planned, programmed and integrated, so
finish is recommended, and they shall be designed that in case of fire, the control panel can acti-
as per the guidelines described in the rules and vate all systems like alarms, hooters/strobes,
regulations of the country or state. public announcements, sprinklers, pressuriza-
tion fans, opening of access doors, glowing of
way finding lighting, the release of fire barri-
47.2.13 Fire Command Centre (FCC) ers, switching on the fire pumps, AHU filters,
smoke evacuation fans and dampers. The con-
FCC shall be provided on the ground floor, just at trol panel shall also monitor the fire water
the entrance of the building, and shall have a storage tanks and pumps, hydrant and sprin-
direct access to the user. While designing the kler pressures etc.
FCC, the following points shall be taken care of: 3. The smoke detectors, heat detectors, alarms,
hooters, manual call points and response indi-
1. A control room shall be provided with the cators shall be installed as described in the
main fire alarm panel, along with a public rules and regulations of the country or state.
address system. 4. All cabling for installation of the detection
2. All controls and monitoring of the fire detec- system shall be done with conductor FRLS
tion system and the fire suppression system insulated wires in MS conduits.
shall be taken care of from this control room.
This shall also include fire alarm, pressuriza-
tion systems and smoke management. 47.4 Fire Extinguishers/Fixed
3. A CCTV monitoring station shall be provided Firefighting Installations
in this room.
4. The control room shall have a detailed floor
1. Based on the guidelines prescribed in the
plan along with the location of doors and win- rules and regulations of the country or state,
dows, escape route, refuge area, staircases, the hospital building shall be protected by
lifts, ramps etc. which shall be clearly marked providing fire extinguishers of all types:
in these floor plans. Powder, CO2, ABC, Foam, wet risers with
hose reels and nozzles, down-comer, auto-
matic sprinkler installation, yard hydrants,
47.3 Fire Detection and Alarm high/medium velocity water spray, water mist
spray systems, manual/automatic fire alarm
Adequate provision shall be made for providing system etc.
fire detection system in the building as described
2. Extinguishers shall be wall mounted and
in the rules and regulations of the country or accessible to all.
484 47 Fire Safety
3. The specifications and number of extinguish- This chapter discusses the highlights of Fire
ers, wet riser, down-comer, automatic sprin- Safety Management. However, the actual
kler, yard hydrants, high/medium velocity management of fire safety measurements
water spray, water mist spray systems and solely depends on the set of Rules and
manual/automatic fire alarm system to be Regulations as framed by the respective coun-
used shall depend on the guidelines as try or state.
described in the rules and regulations of the Therefore, the designer and the hospital
country or state. management are advised to go through such
rules and regulations before planning and
designing the facilities and infrastructure of
47.4.1 Static Water Storage Tanks Fire Detection, Suppression, and Safety
Management.
Water supply for firefighting devices like hydrant,
sprinklers, downcomers and yard hydrants shall
be provided from form an underground/terrace Further Reading
static storage tank with the capacity as described
in the rules and regulations of the country or Fire safety in healthcare environments [Internet].
[cited 2021 Jul 15]. Available from: https://build-
state. i n g b e t t e r h e a l t h c a r e . c o m / n ew s / a r t i c l e _ p a g e /
Fire_safety_in_healthcare_environments/139696
Fire Safety Management [Internet]. Fire magazine |
47.4.2 Fire-Fighting Pump House Safety magazine | Security magazine | Disaster relief
equipment and services. 2016 [cited 2021 Jul 15].
Available from: https://firesafetysecurityindia.com/
A fire pump house shall be provided for supply- fire-safety-management/
ing water to the hydrant, sprinklers, and yard Fire safety and protection in hospital [Internet]. Scholarly
hydrant. articles on hospital infrastructure, renovation, up-
gradation, refurbishment, setting up new hospital in
The pump house shall have two auto-start India. [cited 2021 Jul 15]. Available from: http://www.
main pumps, two jockey pumps, and one diesel hospitalinfrabiz.com/fire-safety-and-protection-in-
engine operated fire pump set connected to the hospital.html
emergency power supply. Fire safety technologies advance on many fronts [Internet].
[cited 2021 Jul 15]. Available from: https://www.hfm-
magazine.com/articles/3778-fire-safety-technologies-
advance-on-many-fronts
47.4.3 Automatic Sprinkler Loria G, Choudhry N, Sharma K. Fire management in
Installation hospitals. Apollo Med. 2012 Mar 1;9(1):74–6.
Omidvari F, Jahangiri M, Mehryar R, Alimohammadlou
M, Kamalinia M. Fire Risk Assessment in Healthcare
It shall be installed as described in the rules and Settings: Application of FMEA Combined with Multi-
regulations of the country or state. Criteria Decision Making Methods. Math Probl Eng.
2020 Oct 19;2020:e8913497.
Ravenstein HV, Ravenstein HV. Fire safety of hos-
1. The distance between sprinklers shall be as
pitals a guide for designers. Fire Saf Hosp Guide
described in the rules and regulations of the Des [Internet]. [cited 2021 Jul 15]; Available
country or state. from: https://www.academia.edu/41708228/
2. The sprinkler system shall not be installed in Fire_safety_of_hospitals_a_guide_for_designers
Tabish SA. Fire Safety in Hospitals. 2010.
the OR, ICU, record room, CT, MRI, PET or
other such areas, where water spray can dam-
age the medical equipment.
Green Hospitals
48
There is no existing global definition of green environment. Today, the world is talking about
hospital, but it can be defined as a building that is global warming, and scientists, leaders and
planned and designed utilizing maximum natural researchers are struggling to find the solution to
resources in an efficient and environment- curb pollution and improve environmental
friendly manner, which can enhance patient care, conditions.
reduce cross-infection, improve patient’s well- Though, hospitals cannot provide quality ser-
being and provide an aid towards the curative vices without exploiting natural resources, but if
process. all these resources are deployed and utilized in
The main motive of hospitals is to provide the simple, smart and sustainable manner, hospitals
best medical treatment and care to the patient, can reduce carbon footprint up to a great extent.
adopt measures to prevent diseases and create To find the solution for improving the environ-
awareness amongst the community for preven- ment, the concept of green building is being pro-
tion of diseases. To achieve these objectives, hos- moted throughout the world. Government of
pitals have to use various resources like water, various countries is giving a higher rating to
electricity, petroleum products, chemicals, food green buildings, and similarly green hospitals are
articles, construction material and gases. Out of rated higher than ordinary hospitals.
all these, some are natural resources like water, To promote green building, different countries
food articles, energy, petroleum etc., whereas have designated different agencies to frame poli-
others are man-made resources. cies, guidelines, controls, conduct pieces of train-
The painful reality of the day is the deteriorat- ing, provide ratings, certifications and
ing health of our environment, which has become accreditations to such buildings. In the United
an issue of grave national and international States, Canada, China and India, Leadership in
importance, as the environment has a direct effect Energy and Environment Design (LEED) has
on the health of human beings, animals and plan- been granted this responsibility. In India, in addi-
tations. In fact, that in the latter half of the twen- tion to LEED, the Bureau of Energy Efficiency
tieth century, human beings have tinkered with (BEE) and the Indian Green Building Council
the ecosystem of the planet where climatic (IGBC) also work for promoting green buildings.
changes, chemical pollution and contamination Similarly, for the UK and Netherlands—Building
and unsustainable resources are the main factors Research Establishment Environmental
affecting the ecosystem. Assessment Methods (BREEAM); Green Star for
As hospitals use all these resources, they pro- Australia, New Zealand and South Africa;
duce carbon footprint which adversely affects the Comprehensive Assessment System for Building
© The Author(s), under exclusive license to Springer Nature Singapore Pte Ltd. 2022 485
A. Garg, A. Dewan, Manual of Hospital Planning and Designing,
https://doi.org/10.1007/978-981-16-8456-2_48
486 48 Green Hospitals
A Green hospital increases patient care and adds 48.2 Benefits of Green Buildings
to the treatment of patients, while utilizing natu- Hospitals
ral resources in an efficient and environment-
friendly manner. To achieve this objective, the Following are some examples of advantages of
hospital shall take initiative and promote the designing green hospitals:
following:
1. Energy savings, which can extend up to
1. Choose an environment-friendly site, for 40–50% of the ordinary hospitals.
example a location that puts less pressure on 2. Water savings up to 20–30%.
the environment, and where clean air, water 3. Improved indoor ambience.
and soil are available, biodiversity is not dis- 4. Improved productivity of healthcare
turbed, which enhances public health by pro- workers.
tecting wetlands, agricultural land and open 5. Improved indoor air quality.
spaces. 6. Appealing exteriors and interiors of the
2. Utilize sustainable and efficient designs. building.
3. Promote using green building materials and 7. Designs can enhance natural lighting by pro-
products. viding glazing facades, translucent skylights
4. Think green during the construction phase with soothing colours, transparent and oper-
and maintain the greening process. able openings to green courtyards etc.
5. Promote recycling and reuse of materials, 8. More daylight and landscapes create a posi-
reduce waste and produce cleaner air. tive effect on the patient, reduce their stress
6. Take measures to reduce CO2 generation. levels and improve hospital’s overall opera-
7. Use more sustainable building materials. tional efficiency.
8. Avoid products made of mercury, latex, plas- 9. Patient recovery rate is faster.
tic and PVC. 10.
High level of patient and attendant
9. Promote energy conservation. satisfaction.
10. Promote water conservation.
11. Procure environment-friendly tools and
resources. 48.3 Barriers to Create Green
12. Provide maximum outside greenery by
Hospitals
plantations.
13. Integrate pest management. It is easy to say that the planners and designers
14. Provide provisions for proper waste disposal should promote green hospitals, but there are a
and transportation. lot of barriers that restrict the design of an excel-
15. Use more green electronics. lent green hospital. Some of them are as follows:
48.3 Barriers to Create Green Hospitals 487
Hospitals are one of the most infection-prone 48.3.7 Higher Volume of Hospital
buildings; thus, the main motive of hospitals is to Waste
prevent infection by placing strict infection con-
trol protocols, which sometimes becomes a hur- Hospitals generally produce a higher quantity of
dle in creating green hospitals. waste, out of which a vast majority can be haz-
ardous. It is necessary to dispose of this waste as
per the policies and guidelines prescribed by the
48.3.3 Regulatory Compliance regulating authorities, which becomes a hurdle
for creating green hospitals.
As different countries have a different set of
codes, policies, by-laws and standards for design-
ing and constructing hospital buildings, it some- 48.3.8 Chemical Use
times imposes a barrier for creating a perfect
green hospital. Usage of hazardous chemicals are generally
unavoidable in hospitals as these may be neces-
sary for cleaning, disinfecting, sterilizing instru-
48.3.4 Intense Energy and Water ments, disposables and cleaning equipment,
Consumption treating certain diseases, and largely used in clini-
cal laboratories for testing. Some of these chemi-
Hospitals usually consume a large number of cals can be extremely toxic and hazardous, which
resources like energy and water, which can even is another issue in designing green hospitals.
be up to two times as compared to any other com-
mercial buildings, which puts a barrier to creat-
ing a perfect green hospital. 48.3.9 Frequent Upgradations
and Renovations
20. Prefer thermal insulation of exterior walls, 33. Super insulate the roof and wall (exposed to
roof and flooring. direct sunlight) to reduce heat transfer into
21. Replace common manual faucets with fau- the hospital and apply light colours that do
cets controlled by a photocell. not absorb much heat. This will help in uti-
22. Adopt heat recovery systems from the con- lizing less energy to cool rooms in summers
densates with a heat exchanger. Heat recov- and heat rooms in winters.
ery elements can capture heat that goes out
the smokestack or is otherwise lost outside.
23. Introduce an Energy Management System
48.4.2 Alternative Means of Energy
(EMS) to review the current data on a hospi- Generation
tal’s energy usage.
24. Upgrade hospital’s energy-consuming equip- Usually, energy utilized in the hospital is pro-
ment with more energy-efficient equipment cured from energy supply agencies which are
to reduce energy usage. usually produced outside and are wheeled to the
25. The building’s envelope shall be created
hospital. Apart from this, the hospital may have
including structures such as foundation, roof, its energy generation system through a diesel
walls and windows that create a physical bar- generation plant or smoke-belching standby
rier between the outside elements and the power generation sets.
conditioned facility. The energy produced in the thermal plants
26. Adopt cogeneration systems like combined uses coal as raw material, which increases the
heat and power (CHP) systems to convert carbon footprints. Similarly, atomic plants are
the facility’s waste heat into energy. This harmful to the environment.
energy can then be used for heating and To avoid this, the following sources of renew-
cooling. able energy can be deployed:
27. Arrange for periodic energy audits to review
the pattern of energy consumption in the hos- 1. Solar energy can be of three types, photovol-
pital and how the procured energy is con- taic (PV), solar thermal or concentrated solar
sumed. The aim is to detect inefficiencies in power.
a building and comprehensive analysis. (a) Solar power refers to solar PV panels that
28. Usage of variable-frequency drives (VFDs) convert energy from the sun into electric
shall be encouraged. VFDs help to save power. Advantages of solar PV include
energy in pumps and fans run by alternating- the predictability and free availability of
current motors. the sun around the globe. Solar power can
29. Consider using a heat-recovery chiller. In
even be stored in Lithium-ion batteries,
hospitals that require both chilled water for which can be used as and when required.
cooling and hot water for heating, a heat- (b) Solar thermal technology uses energy
recovery chiller can be used to capture and from the sun to heat water that is econom-
use heat that otherwise would be wasted in ically cheaper for heating water and
the environment. buildings or augmenting conventional
30. Promote cold-rinse for cleaning and washing steam or hot water systems.
in kitchen and laundry as hot water rinse is (c) Concentrated solar power (CSP) uses
not required for all washings and cleanings. light-focusing technologies and mirrors
31. Consider planting shaded trees or shading to concentrate the power of the sun, pro-
devices on the exterior to eliminate direct ducing steam that generates electricity or
sunlight from the building. powers other thermal applications.
32. Try replacing the existing magnetic ballasts 2. Wind turbines use the natural flow of air to
(some of which may contain PCBs) with produce power. Moving air passes over blades
electronic ballasts. that create a pressure drop, which spins a shaft
490 48 Green Hospitals
and induces an electrical current within a gen- season. The rainwater of roof and grounds be
erator to create electricity. Wind power may collected in the water storage pits to be used
have negative impacts on birds and bats, and it later when required for irrigation etc.
can create concerns about land use and land- Otherwise, the rainwater can be poured back
scape views if sited inappropriately. into the earth through rainwater soak pits.
3. Hydropower uses the water stored in dams 2. The rainwater collected in the water storage
and flowing in rivers to create electricity. pits can also be recycled and used for flush-
Falling water rotates the blades of a turbine, ing, cleaning or irrigation.
which spins a generator and converts mechan- 3. The collected rainwater can also be used to
ical energy into electrical energy. operate cooling towers, which the hospital
4. Geothermal technology, wherein the earth’s uses for their air conditioning system.
energy is transferred into heat or electricity. 4. The use of low-flow water-efficient fixtures
There are two different geothermal technolo- and technologies shall be promoted to be
gies, geo-exchange and geothermal hydro- used in the urinals, toilets and showers to
thermal power. save millions of gallons of water every year.
5. Biomass energy source comes from organic 5. Promote using sensing devices in sinks to
plant material. Plants capture carbon dioxide turn off the water from devices when not
in the atmosphere and biomass transfers needed.
energy through chemical decomposition such 6. The drained water from the hospital can be
as anaerobic digestion and create biogas, recycled by installing ETP and aerobic/oxy-
which can be burned to generate power. genated Sewage Treatment Plant (STP).
Biomass fuels can be burned in boilers to pro- Even otherwise the STP plants are essential
duce steam to make electricity or heat in hospitals. This recycled water can be used
hospitals. for irrigation, cleaning activities, cooling
6. Biogas is formed when organic material towers etc.
decomposes in an anaerobic environment ver- 7. Stress routinely checks plumbing and pipes
sus decomposing aerobically (with oxygen). to prevent leakages in the water supply line
The main component of biogas is methane. throughout the hospital building.
Biogas can be used in its raw form as a heat- 8. Prefer using drought-resistant plants for
ing fuel or for electricity production with a landscaping and plantation to minimize
turbine or engine. water requirements for irrigation. Also, use
7. Renewable Natural Gas (RNG) can be injected more mulch landscape plantings to help
into the natural gas pipeline and used for heat- retain moisture around the root system.
ing or base-load electricity production. 9. Design landscaping to include rain gardens
as these gardens use storm water runoff gen-
erated from roofs or hardscape/impervious
48.4.3 Water Conservation surfaces.
10. For irrigation use Drip Irrigation and sprin-
Hospitals in the normal course consume large kler irrigation system as it is a more efficient
quantities of water. Globally, due to the climatic method of irrigation with less consumption
changes and glacier melt, water scarcity is of water.
increasing. With little effort or change in designs,
hospitals can conserve water.
The following issues need to be addressed for 48.4.4 Indoor Environmental Quality
the conservation of water: and HVAC Optimization
1. Provide the system for rainwater harvesting Heating, Ventilation and Air Conditioning
by capturing the rainwater in the monsoon (HVAC) is a system used in hospitals for cooling,
48.4 Elements of a Green Hospital 491
heating and ventilation. HVAC is one of the example, the screw chillers. Screw chillers
systems which consumes major energy in the automatically slow down as soon as the
hospital. Further, the HVAC system in the hospi- requirement of chilled water goes down and
tal is operative round the clock throughout the vice versa. These upgraded chillers can
year. If the HVAC system is designed properly, a reduce energy costs to a great extent.
lot of energy can be saved. 9. Install Building Automation System (BAS) to
The following measures can be adopted to control the HVAC system. The BAS keeps
reduce energy costs of the HVAC system: systems running according to operating
schedules, setpoints and fundamental
1. Preventive maintenance service shall be car- sequences of operation. The programming
ried out periodically to make sure that the coordinates the operation of thousands of
HVAC system runs efficiently. components, including everything from boil-
2. HVAC equipment shall be calibrated at regu- ers and chillers, air handlers and exhaust fans,
lar intervals. dampers and valves. One disadvantage of the
3. Timely cleaning replacement of the air fil- BAS is that it typically prioritizes the indoor
ters, canvas, valves, insulation and gaskets environment (i.e. temperature, humidity or
can reduce the energy in the long run. air changes per hour) over energy efficiency.
4. Ensure the quality of water used in the HVAC 10. FDD is another software that helps the man-
chillers. It will increase the life of the chillers agement to reduce energy costs. FDD uses
and also reduce energy costs. analytics software to continuously collect
5. Temperature Control thermostats shall be performance data from the BAS and identify
provided at the patient end wherein the potential faults. Faults are identified by eval-
patient can switch on/off the air-conditioning uating a set of algorithms that are applied
as and when required. This will help the based on the system configuration.
patient to maintain temperature as per his/her 11. Operating rooms in the hospital have very
choice. These thermostats can also help in strict requirements for environmental condi-
energy conservation. tions such as air changes per hour, humidity,
6. Variable Air Volume (VAV) systems shall be pressure and temperature, hence a major
promoted. VAV saves energy when the air- space for energy consumption. A handsome
flow is at the box minimum flow. VAV boxes amount of energy savings can be achieved by
generally increase airflow with cooling reducing their energy consumption by
demand, but designers traditionally set them switching off the HVAC system of OR when
to fixed cubic feet per minute in heating to not in use.
ensure that supply air does not get too warm 12.
The refrigerant devices containing
and stratify. Chlorofluorocarbons (CFC) shall be replaced
7. Usually, the hospital prefers the HVAC sys- with other devices which do not contain CFC
tem which can cater to the needs of the future as a refrigerant. Preference shall be given to
expansion of the spaces in the hospital. But if buy equipment that uses refrigerants that
the airflow demand under the present sce- contain less potent ozone-depleting sub-
nario is less than the capacity of the HVAC stances (ODSs) and with reduced global
plant, the airflow shall be reduced to save warming potentials (GWPs).
energy.
8. Optimization of the chillers is another mea-
sure. The chillers should be upgraded as and 48.4.5 Chemical Management
when necessary. The hospital shall prefer to
install more upgraded chillers, which shall Chemicals are very much prevalent in hospitals.
have the provision to get synchronized with The chemicals are generally used in the hospital
the actual load of cooling on the chillers. For building for maintenance, infection control and
492 48 Green Hospitals
also during the treatment of the patient. Out of all 10. Carefully and safely apply the pesticides and
the chemicals used in the hospital, some chemi- other chemicals for plantation in the exterior
cals or the components of the chemicals are con- or interior of the hospital building.
sidered to be harmful and toxic to human beings 11. Arrange for a good, experienced and reputed
and/or the environment. waste disposal agency if the hospital does
Chemicals and fuels used in or around the not have its own incinerators.
hospital should be used with caution to prevent 12. Strictly follow the national chemical man-
contamination and reduce exposure to staff, agement policy of the country to reduce the
patients, visitors and the surrounding community. purchase and use of hazardous chemicals.
Antibacterial/antimicrobial products and steril- 13. Careful storage of hazardous chemicals with
ization and disinfecting chemicals also are com- limited access is necessary.
monly used in the health sector. 14. Proper training shall be given to the staff and
The following issues shall be addressed to users as to how to handle, store and apply the
manage the chemicals effectively: hazardous chemicals.
15. Correctly label and properly store all
1. Never dispose of liquid waste that contains chemicals as per the manufacturer’s
cleaning or disinfection chemicals and agents recommendations.
down the drains. 16. Try to phase out the use of Ethylene Oxide
2. Necessarily frame the chemicals and materi- and the high-level disinfectant (HDL) glutar-
als policy and protocols to protect patient, aldehyde and other hazardous substances
worker and community health and the envi- and replace them with safer alternatives.
ronment. The policy shall have a specific Alternatives to Ethylene Oxide can be low-
chemicals action plan with benchmarks and temperature sterilization methods such as
timelines. vaporized hydrogen peroxide, hydrogen per-
3. Create Mercury-Free Hospital by substitut- oxide gas plasma, liquid peracetic acid and
ing all mercury thermometers and blood ozone.
pressure devices with safe, accurate and
affordable alternatives.
4. Monitor and manage the use of chemicals 48.4.6 Solid Waste Management
like glutaraldehyde, halogenated fire retar-
dants, solvents and disinfectants, soaps, Hospitals usually generate a lot of waste. The waste
chlorine, radioactive substances, PVC, generated by the hospital can be biodegradable,
DEHP, and BPA. If possible, replace them recyclable or hazardous. Proper segregation, stor-
with other safer alternatives and substitutes. age and safe and effective disposal of such waste
5. Try using chemicals which undergone at are essential to achieve the concept of the green
least basic toxicity testing. hospital. It has been seen that about 10% to 15% of
6. If very high chemicals like carcinogenic, the total waste generated is from hospitals.
mutagenic or toxic for reproduction are used, Improper disposal of such waste, in open
hospitals should make it a high priority to dumps areas or the rivers etc., attracts a lot of dis-
replace them with safer alternatives. ease vectors, release unpleasant odours and may
7. Use equipment that is more efficient and uses also lead to transmission of diseases like malaria,
less hazardous chemicals. typhoid, cholera, HIV and Tuberculosis. The
8. All the chemicals shall be labelled properly sharp instruments, if not handled and disposed of
to avoid and accident or spilling. properly, may lead to infections like Hepatitis B
9. Where ever possible prefer using natural and C through injuries from such sharps contami-
cleaning products instead of chemicals. nated with human blood.
48.4 Elements of a Green Hospital 493
The hospital can reduce waste and emissions etc. shall be composted at a proper place as
through composting, recycling, minimizing demarcated by the local authorities.
packaging, using reusable rather than disposable 13. The infected plastics shall be landfilled after
products, buying recycled products and minimiz- disinfection, rather than incinerating because
ing waste transport. the burning of plastic produces greenhouse
Operating rooms of the hospitals in them- gases and toxic pollutants such as dioxins
selves produces waste of about 20–30 percent of and furans.
total hospital waste. Out of this packaging mate- 14. Reducing inhaled anaesthetic atmospheric
rial used to protect and maintain the sterility of waste by utilizing low fresh gas flows, avoid-
supplies and equipment accounts for a large part ing high impact inhaled anaesthetics like
of the waste. Increased use of disposable supplies Desflurane, Nitrous Oxide and considering
and equipment further adds to this problem. intravenous and regional techniques.
The following issues need to be addressed for 15. Reduce intravenous pharmaceutical waste by
an excellent waste management: preferring prefilled syringes, appropriately
sized vials and disposing of unused medica-
1. Strictly follow the norms, policies and guide- tions and vials as per laid down policy and
lines of the country for handling and disposal regulations.
of hazardous waste. 16. Reduce anaesthesia equipment waste by
2. Reduce the construction waste is also benefi- opening equipment intended for immediate
cial in building green hospitals. use, preferring using reusable or reprocessed
3. Promote using recycled and renewable mate- equipment instead of disposables, and repro-
rials along with more sustainable construc- cessing or recycling suitable disposable
tion methods. items.
4. Try avoiding toxic materials such as mer-
cury, plastic, PVC and unnecessary dispos-
able products. 48.4.7 Environmental Services
5. Set up a waste management committee and
allocate a budget for waste management. A clean environment in and out of healthcare
6. Hospitals shall have a policy of segregation facilities is important to reduce and control
of waste at the source itself and non- infections, provide quality air and reduce pests
hazardous wastes shall be sent for recycling. etc.
7. Implement a comprehensive waste manage- A clean environment protects the healthcare
ment training program and awareness cam- workers, patients and visitors in the hospital from
paigns to control waste. exposure to pollutants and chemicals that could
8. Train and vaccinate the waste handlers and irritate, trigger medical conditions or cause seri-
promote using personal protective equip- ous harm.
ment while handling waste. Some of the measures that can be taken for a
9. Disposal of the waste shall be done in an eco- better environment is as below:
nomical, safe and environmentally friendly
manner. 1. Attention shall be paid to the components of
10. Establish the policies and guidelines to
cleaning agents, pest control chemicals and
achieve zero waste and align the operations all other such materials used inside and out-
and procedures of the hospital to achieve this side the hospital. If any of these are toxic and
goal. harmful to the environment, they should be
11. Storage of the waste shall be in a secured and discouraged.
restricted space. 2. The concept of Integrated Pest Management
12. Biodegradable wastes such as papers, card- (IPM) shall be adopted to reduce the use of
board, vegetable and plant wastes, food items harmful chemicals, target specific pests and
494 48 Green Hospitals
shall increase the use of safer alternatives 12. Improve the lighting and acoustical settings
and techniques and limit exposure of appli- to reduce stress and support health and
cators, humans and other organisms. productivity.
3. Avoid using or minimize the use of products 13. Providing courtyard spaces with native and
that are manufactured with carcinogens, adaptive plant free from allergic effects
mutagens and teratogens; aerosols; respira- improve fresh air of the environment.
tory irritants; neurotoxins; endocrine modi- 14. Ensuring those roof parapets and caps are
fiers; asthma-causing agents, and chemicals properly sealed and do not allow the pests to
that aggravate existing respiratory condi- enter the roof and grow.
tions; benzene-based solvents, highly acidic 15. The bird nests, honey traps are checked regu-
or alkaline products; butoxyethanol, chlori- larly and removed immediately as and when
nated organic solvents, paradichlorobenzene; noticed.
anti-microbial agents in hand soaps; bioac- 16. Repair and plug and orifices, cracks and
cumulative and toxic chemicals (PBTs) and holes in the walls to keep pests out of them.
products requiring disposal as hazardous 17. Inspect the grounds around buildings and fill
waste. burrows with gravel.
4. Minimize atomizing chemicals. 18. Keep vegetation at least 1000 mm away from
5. Reduce use of virgin paper in janitorial paper the main building perimeter.
and prefer using disposable paper products, 19. Use physical barriers to block entry of pets,
such as paper and hand wiping towels which animals inside the hospital premises.
contain recycled content. 20. Prohibit smoking in the hospital. If any
6. Promote usage of microfiber-based cleaning smoking area is designated, make sure it is at
equipment which cut chemical waste, least 50 feet from the hospital to reduce the
increase performance and reduce labour. impact of smoke on patients, healthcare
7. Improve the air quality inside and outside the workers staff and visitors and also to prevent
hospital as it is one of the most vital compo- interior surfaces from absorbing the smoke.
nents of any green building. The environ- 21. Ensure that the smoking area is downwind
ment is suffering from poor quality air due to and away from main entrances/exits, win-
rising pollution. This can be achieved if more dows, air conditioning units and air intakes.
and more indoor plants are provided, which 22. Ensure that all windows are openable to take
produces oxygen and reduces indoor pollut- full advantage of prevailing breezes of air.
ants from the air and are the natural air However, despite the energy savings and
purifiers. reduced environmental impact, it may not
8. As hospitals are exposed to many pathogens always be practical to use natural ventilation
and bacteria, it becomes necessary to have a at all times. In that case, the mechanical sys-
ventilation system and a well-designed tems shall be given for ventilation.
cleanroom to continuously provide fresh and 23. Avoid foam being used in the furniture like
filtered air. chairs, sofa sets, beds etc. as it is likely
9. Protect and restore natural habitat and mini- treated with a variety of flame retardants.
mize the combined footprint of buildings, Prefer using furniture with mesh instead.
parking, roads and walks.
10. Avoid materials such as lead and cadmium-
containing paint and coatings, as well as 48.4.8 Food Services
asbestos.
11. Create facilities for natural ventilation and if Agriculture and food systems have a significant
required the mechanical systems for increas- impact on the environment and human health.
ing the ventilation. Diets habits with increased saturated fats, refined
48.4 Elements of a Green Hospital 495
carbohydrates and processed foods are some of 4. To make hospitals and the overall health
the factors that are increasing the burden of dis- sector more sustainable, it has to be
eases amongst the community. This leads to more ensured that the food products have been
and more long-term therapies and treatments. produced in an environmentally safe and
The treatment and therapies increase the health- sustainable manner and the changes must
care cost and also the healthcare sector’s environ- be made as to how food is prepared, pro-
mental footprint. vided and served.
Hospitals can promote health by providing 5. Implement a sustainable food plan and pol-
fresher, good tasting, nutritious food choices for icy and increase the procurement of locally
patients, healthcare workers and visitors by sup- and regionally produced foods.
porting food production that is local, humane and 6. Examine ways to reduce food waste by
protective of the environment and health. implementing innovations such as room ser-
Large inputs of pesticides and chemicals lead to vice, meals on-demand and just-in-time food
the degradation of soil, water and other natural preparation.
resources. The use of energy such as fire to burn 7. Supporting the habit of donating food that
left out roots in the farms releases pollution in the remains at the end of daily operations to food
atmosphere and contributes a lot to climatic change. banks, churches and other community groups
The farm processes like planting, reaping, rather than disposing of it.
transportation, processing, packaging, shipping 8. If space permits, promote community and
and the use of man-made inputs make the global staff to start an organic garden onsite.
farming system unsustainable. Similarly, live- 9. Declare the hospital as a ‘fast food free zone’
stock, contribute greenhouses gases to the atmo- and as far as possible eliminate sugar-based
sphere and pollute other resources as well. soft drinks in hospital cafeterias and vending
To achieve an environmentally friendly food machines.
system, the hospital shall keep in mind the fol- 10. Encourage vendors to supply food that is
lowing few issues: produced without using synthetic pesticides
and hormones or antibiotics given to ani-
1. Strive to eliminate using disposable food mals. This will support farmers’ health and
containers and bottled water as plastic from welfare, as well as ecologically protective
food services and bottled water will likely and restorative agriculture.
end up in a landfill or incinerated. If still 11. Promote, educate and bring awareness to the
there is a need to use disposable products, patients, healthcare workers, visitors and the
use biodegradable/compostable food service community at large about nutritious, socially
wares. equitable and ecologically sustainable food
2. Paper products such as napkins often used in practices and procedures.
food services consume natural resources and
generate additional waste, hence the use
shall be minimized. Instead of that paper 48.4.9 Environmentally Preferable
products with recycled content offer a better, Purchasing
more sustainable option.
3. Food waste can be removed from the waste During the normal course of operation, the hospi-
can be composted on-site, to other desig- tals have to necessarily purchase a lot of products
nated places and this compost can be reused such as pharmaceuticals, chemicals, reagents,
in farms and add to the overall sustainability disposables, consumables, equipment, fixtures,
of the agriculture sector. Even commercial food and cleaning and other general supplies.
composters are available on the market that These items leave a significant impact on the hos-
can turn discarded food into compost. pital’s carbon footprint.
496 48 Green Hospitals
The term equipment may have different definitions The ultimate objective of equipment planning
in respect to different contexts but for hospital it is is to ensure all products selected are suitable for
generally defined as ‘the articles and implements the hospital functioning, within the allotted bud-
required to perform specific activities’. If analyzed get and are procured, delivered and commis-
for a hospital, the equipment are the tools and sioned within the stipulated time frame and in
methods which facilitates the care providers in accordance with project requirements.
performing the diagnostic investigation to diag- The equipment planner shall plan the require-
nose the disease and help in treatment of the diag- ments either for the medical only or both the
nosed disease. In a true sense, the equipment in the medical and non-medical equipment. An assess-
hospital refers to the medical and mechanical ment of major and minor equipment shall be
machines used for diagnosis and treatment but are made to evaluate the need for equipment in terms
different from the fixtures and fittings. of functionality and cost. While assessing the
Equipment in hospital can be either Fixed requirement of the equipment the following fac-
Equipment or Loose and Mobile Equipment. tors shall be considered:
Fixed equipment is generally the equipment that
is fixed to the building and can be like MRI, CT 1. What is the need for equipment?
Scan, X-ray, LINAC, Mammography or a large 2. Financial cost of equipment.
sterilizer etc. Loose equipment are items that are 3. Functionality of equipment.
not fixed to the building and can be moved easily 4. Frequency of use of equipment.
as and when required to any other place. These 5. Income likely to be generated by the
can be items like monitors, surgical instruments, equipment.
ECG machines and Ultrasound. 6. Useful life of the equipment.
As medical equipment is the most vital com- 7. Period of return of investment for equipment.
ponent in any hospital. Therefore, the planners of 8. Expected technology changes of the
hospital need detailed planning and coordination, equipment.
assess the clinical needs and the equipment 9. Determine equipment reuse and relocation
requirements and then only move forward for options.
procurement.
Efficient planning of the hospital equipment While planning, the planner shall understand
requires a clear understanding of the clinical need equipment preferences, concerns and priorities
along with detailed knowledge about budgeting, after conducting interviews with the departmen-
architectural design and building process. tal heads. He/She shall also review the
© The Author(s), under exclusive license to Springer Nature Singapore Pte Ltd. 2022 501
A. Garg, A. Dewan, Manual of Hospital Planning and Designing,
https://doi.org/10.1007/978-981-16-8456-2_49
502 49 Equipment Planning
a rchitectural drawing and details to ensure that 3. Non-standard devices may have defects or
all the elements of the building fulfil the require- malfunctions that could lead to severe
ment for an efficient functioning of the consequences.
equipment. 4. Quality products are generally safe, and by
that said, free from unacceptable risks for per-
sons, property or environment.
49.1 Choosing the Desired 5. Throughout the globe, the medical equipment
Equipment and devices are subject to extensive rules and
regulations and there are a number of different
Once the list of equipment is finalized, the plan- standards and regulation systems to follow.
ner has to choose the desired equipment out of Hence, the medical equipment and devices
the lot available in the market. shall ensure the standards of the regulating
In today’s competitive market, there are a lot authorities like US Food and Drug
of manufacturers manufacturing the same equip- Administration (FDA); (QSR) to ensure prod-
ment, and each manufacturer has different mod- uct performance and safety; Standard ISO
els of the same equipment. Different models may 13485 complements the Medical Device
have different costs depending on the specifica- Directive etc.
tions, configuration, capacity, size, performance 6. This is true that if the quality of the medical
and facilities. It is the planner who has to decide equipment and devices is as per the laid down
as to what is needed and which model best suits standards, the life of the equipment shall be
the requirement. more as compared to non-standard equipment
and devices.
7. The repair and maintenance cost of the quality
49.1.1 Quality of the Equipment equipment and devices will be less as com-
pared to others.
While choosing the medical equipment, tools and
devices, the issues related to the quality of these
items shall not be compromised. One shall look 49.2 Points to Be Considered
for a vendor with a quality mindset, which While Purchasing
focuses on patient safety, product quality and the Medical Equipment
compliance.
All the healthcare facilities use a lot of medical Finalizing the specification and configuration of
equipment and devices, which are from simple equipment: Before finalizing the equipment the
equipment to a complex machine combined with specification, configuration of the equipment has
different technologies. Whatsoever it may be, the to be finalized and depending on these specifica-
quality of such devices and equipment shall be tions the vendors shall be sorted out. While final-
ensured and shall never be compromised even if izing the specification and configuration of the
the cost of such quality equipment is bit more. The equipment, the planner shall try to choose the
main factors in favour of quality assurance are: equipment with the latest technology and specifi-
cation. On the other hand, the financial feasibility
1. Non-quality products may have defects or dis- of the latest technology shall also be considered
turbances in functioning and may expose before choosing the specifications. Why we insist
patients to serious risks like injury, sickness on the latest technology is that, in today’s world
and even death. the technologies are changing rapidly and the
2. The non-standard equipment may not have present technology may be outdated in a few
been calibrated as per the standards, which years. In such a case, the hospital will be left with
may give wrong results and the physician no other options but to replace the equipment in a
may not be able to diagnose the ailment few years’ time. However, a careful comparison
properly. shall be done between the increased costs of lat-
49.2 Points to Be Considered While Purchasing the Medical Equipment 503
49.2.9 Checking Regulations and dummy tests to be performed for testing the
operation of the equipment. While testing the
As some of the equipment are bound by the regu- issues like electrical safety inspection and radia-
lations of the local building codes, accreditation tion safety shall also be taken care of before giv-
agencies, controlling authorities, other norms and ing the final affirmation.
regulations of the federal and state legislature and
industry standards that the equipment must con-
form to. Therefore, during the planning phase 49.3 Equipment Used
itself, all such norms and regulations shall be in the Hospital
identified and followed while purchasing the
equipment. In hospitals, there are a lot of different equipment
which are required for the efficient working of
the hospitals. Some of them are too small and less
49.2.10 Inspection and Testing costly whereas others may be the big equipment
Before Transfer which requires large spaces and are costly.
of Ownership It is not possible to compile the list of all the
medical equipment available in the market today,
Before transferring the ownership and signing but we have tried to list out a few of them along
the final commissioning reports, the Biomedical with the purpose for which it is used.
Engineer shall inspect and test the equipment. List of Medical Equipment Generally Used
Thereafter, the equipment shall be commissioned in the Hospital
49.4 G
eneral Items Used in Intensive Care Units, Wards,
Pre & Post-Operative Units, Post Labor Wards, Triages Area
and OPD’s Etc.
49.8 Neurosurgery
49.9 Neurology
49.11 Pulmonology
49.13 Urology
49.15 Orthopaedic
49.16 Dermatology
49.17 ENT
49.18 Gynaecology
49.19 Ophthalmology
49.21 Dental
49.23 NICU
49.26 Radiology
49.27 Biochemistry
49.28 Microbiology
49.29 Pathology
49.31 CSSD
49.34 Linen
49.35 Consumables
Further Reading
Bhawan P, Road CIG. MEDICAL EQUIPMENT MAINTENANCE POLICY (2012).:27.
Biomedical Equipment List [Internet]. MedShare. [cited 2021 Jul 15]. Available from: https://www.medshare.org/
biomedical-equipment/
Glossary
© The Author(s), under exclusive license to Springer Nature Singapore Pte Ltd. 2022 529
A. Garg, A. Dewan, Manual of Hospital Planning and Designing,
https://doi.org/10.1007/978-981-16-8456-2
530 Glossary