CHAPTER V
CALCULATIONS FOR THE CONDITIONED AIR SUPPLY
Among the important questions that must be set-
tled when designing air conditioning systems are
those relating to the quantity and condition of the
air supply, and the size of the refrigerating plant
when one is to be installed. In this chapter, methods
are developed for answering these questions for a
wide variety of conditions. However, in order to
understand and apply the methods that are pre-
sented and finally used in the solution of actual
problems, the preliminary material that follows
should first be understood.
Heating or Cooling With Air
When heating rooms with a warm air supply, the
air is heated to a higher point than the temperature
to be maintained in the heated rom. As the warm
air supply cools down to the ro6m temperature, it
surrenders sufficient heat to‘offset the heat losses
from the room. The temperature in a room is always
equal to the temperature to which the air supply
cools in giving up a quantity of heat equal to the
heat losses. The amount of heat that an air supply
surrenders in cooling from its initial to its final tem-
perature can be calculated by means of Formula 1-2
of Chapter I. Obviously, if the room temperature is
to be maintained, the amount of heat that the air
can thus release must be equal to the heat losses of
the room, or in formula form, ~
ag 0.24 x Wx TD \s-1)
where
45 =change in the sensible heat content of the air supply,
Bish
ight of wir delivered to the heated room, Ib per hr
tange in the dry bulb temperature of the air supply
w
a)
In the actual work of designing air conditioning
systems, air quantities are expressed directly in cfm
of standard air; weight of air is seldom used. If the
symbol Q is used to express the volume of air in cubic
feet per minute (cfm) delivered to the conditioned
92
room, it must be converted into pounds of air per
hour in order to use Formula 6-1. Therefore, 60Q
equals the cubic feet of air delivered per hour. The
volume of one pound of air under standard condi-
tions is 13.34 cu ft. Dividing 60@ by this figure
gives the weight of air delivered to the conditioned
room each hour, or
W=_60_Q
13.34
w= 459
If the volume of air delivered to a room each min-
ute is known, this formula can be used to find the
number of pounds of air delivered to the room
each hour.
Example 5-1:
‘An air supply of 3000 cfin is delivered to a condi-
tioned room. Find the number of pounds of air de-
livered to the room each hour.
Solution:
W=459
= 45 x 3000
13,500 Ib per hr
In order to simplify arithmetical work, W can be
eliminated entirely from Formula 6-1. This is ac-
complished by substituting the quantity 4.5Q for W
in Formula 5-1. By means of this substitution,
Formula 5-1 becomes:
Qs =0.24x4.5xQx TD
ds = 1.08 x Qx TD cs
Example 5-2:
How much heat can an air supply of 2600 cfm
provide if its initial temperature is 120 F and the
room temperature is to be maintained at 70 F?CHAPTER V—CALCULATIONS FOR THE CONDITIONED AIR SUPPLY 93
20-70
0
Q = 1.08xQx TD
08 x 2600 x 50
= 140,400 Buh, heat that the air
supply can provide
In actual practice, the problem is rarely one of
finding how much heat a given air supply can pro-
vide. Usually, the problem is one of finding the
quantity of air required and the temperature at
which it should be supplied, in order to maintain a
given temperature in a room, which has‘a certain
heat loss. In actual heating practice the quantity of
air delivered to a room is frequently fixed by the
ventilating requirements. Under these conditions
Formula 5-1a may be used to find the required tem-
perature of the air supply. When Formula 5-1a is
used to find the required temperature of the air de-
livered to a heated room, it can be transposed to
read as follows:
(S-1a)
(5-1b)
Example 5-3:
‘The heat loss of a room is 150,000 Btuh. The venti-
lating requirements of the room make it necessary
to provide an air supply of 5000 cfm. At what tem-
perature should the air be supplied to the con-
ditioned room if itis to be maintained at 70 F?
Solutior