You are on page 1of 9

This article has been accepted for inclusion in a future issue of this journal.

Content is final as presented, with the exception of pagination.

IEEE SYSTEMS JOURNAL 1

Data-Mining Model Based Intelligent Differential


Microgrid Protection Scheme
Susmita Kar, Student Member, IEEE, S. R. Samantaray, Senior Member, IEEE, and M. Dadash Zadeh

Abstract—This paper presents a data-mining-based intelligent contributing to the fault. It is observed that inverter-based
differential protection scheme for the microgrid. The proposed DGs contributes twice the rated current of the inverter to the
scheme preprocesses the faulted current and voltage signals us- fault, whereas synchronous and doubly fed induction generator
ing discrete Fourier transform and estimates the most affected
sensitive features at both ends of the respective feeder. Further- (DFIG) DGs can contribute 4 to 10 times greater than the
more, differential features are computed from the corresponding inverter-based DGs [4] to fault. This happens due to the current
features at both ends of the feeder and are used to build the limiting property of the inverter-based DGs. Furthermore, the
decision tree-based data-mining model for registering the final operating conditions and network topology of the microgrid
relaying decision. The proposed scheme is extensively validated for may change regularly to provide a quality and reliable power to
fault situations in the standard IEC microgrid model with wide
variations in operating parameters for radial and mesh topology the consumers. Under such varying operating conditions, there
in grid-connected and islanded modes of operation. The exten- will be wide variations in the fault current seen by the relay for a
sive test results indicate that the proposed intelligent differential fault occurring at a specific location in the microgrid. The relays
relaying scheme can be highly reliable in providing an effective placed at both ends of the lines must be selective and reliable
protection measure for safe and secured microgrid operation. as there is bidirectional power flow due to the presence of DGs
Index Terms—Decision tree (DT), discrete Fourier transform in the microgrid. Thus, the conventional overcurrent relays with
(DFT) preprocessor, distributed generations (DGs), fault detec- fixed setting, normally employed for microgrid protection, does
tion, microgrid protection. not provide an accurate and reliable protection measure for the
microgrid considering both radial and mesh topology for grid-
I. I NTRODUCTION connected and islanded modes of operation [4]–[7].
Several microgrid protection techniques have been proposed

P ENETRATION of distributed generations (DGs) through


microgrid has gained momentum due to its ability in
offering on-site power generation at the consumption point
previously. The authors in [8] proposed an adaptive relay-
ing strategy for microgrid protection with high penetration of
DGs, which does not consider islanded mode of operation.
with improved reliability and reduced distribution losses. On Communication-based protection schemes for grid-connected
the other hand, the use of renewable energy sources such as microgrids with an assumption of a large amount of fault
wind energy, photovoltaic cells, and fuel cells in microgrid current contributed from the utility grid is proposed in [9]
provides a solution to the problems of greenhouse gas, growing and [10]. In [11], an effective microprocessor-based protection
energy demand, and the depletion of conventional fossil fuel- scheme is proposed; however, it does not consider standard mi-
based energy sources [1], [2]. Despite numerous benefits of the crogrid structure for the study. It is observed that the aforemen-
microgrid with DG integration, including the ability to operate tioned referenced works have not developed a comprehensive
in islanded mode, the protection challenges become a serious protection measure considering wide variations in operating
concern, where the performance of the conventional relays [3] conditions, including modes of operation (grid-connected and
degrade and cease to operate. islanded) and topology of the microgrid (radial and mesh).
The protection relay faces serious challenges as the mi- In another work [12], the authors derived sequence com-
crogrid operates with different types of DGs, including syn- ponents to design the protection relay. Multiple settings are
chronous, induction and inverter-based DGs. The fault current applied on the derived sequence components for relay co-
magnitude varies significantly depending upon the type of DG ordination, making the relaying scheme more complex. The
voltage-based protection scheme is proposed in [13], which
uses synchronous reference frame to compare the reference
Manuscript received July 24, 2014; revised September 29, 2014; ac- of the phase voltage at the DG source. The voltage deviation
cepted December 7, 2014. This work was supported by the Central Power against the reference initiates the tripping of switching device.
Research Institute, Bangalore, Government of India, through the Project RSOP-
IITB-028.
In [14], authors proposed overcurrent-differential protection on
S. Kar and S. R. Samantaray are with the School of Electrical Sciences, each line with back-up voltage and frequency protection at
Indian Institute of Technology, Bhubaneswar 751013, India (e-mail: susmita. each DG. A current-differential scheme [15] has been proposed
bit@gmail.com; sbh_samant@yahoo.co.in).
M. D. Zadeh is with the Department of Electrical and Computer Engineer- for microgrid protection, including grid-connected and islanded
ing, University of Western Ontario, London, ON N6A 5B9, Canada (e-mail: modes with different topologies. However, the scheme has not
mdadash@uwo.ca). been extensively tested considering wide variations in fault con-
Color versions of one or more of the figures in this paper are available online
at http://ieeexplore.ieee.org. ditions. Recently, a differential energy-based protection scheme
Digital Object Identifier 10.1109/JSYST.2014.2380432 has been proposed by the presenting authors [16], which works

1932-8184 © 2015 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission.
See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for inclusion in a future issue of this journal. Content is final as presented, with the exception of pagination.

2 IEEE SYSTEMS JOURNAL

Fig. 2. Fault current in the distribution lines at grid-connected and islanded


modes (radial topology).

Fig. 1. IEC microgrid structure with multiple DGs interface [17].

for the microgrid in grid-connected and islanded modes. How-


ever, the same scheme suffers from the high computational
burden of the S-transform in computing differential energy,
leading to a slower response time of 4 cycles from the fault
inception. Looking at the aforementioned protection issues, Fig. 3. Fault current in the distribution lines for radial and mesh structure
there is a strong motivation in building an intelligent protection (islanded mode).
relay that can provide a comprehensive protection measure for
the microgrid. smaller due to limited current contribution from the local DGs
only. Overall, there is a significant difference in fault currents
between grid-connected and islanded modes of operation, as
II. P ROTECTION C HALLENGES
observed in Fig. 2.
The possible protection challenges stated in Section I are Similar observations are made for radial and mesh topology
observed as follows while studying the test system (IEC mi- (connected through CB_LOOP1 and CB_LOOP2), as shown in
crogrid) [17] shown in Fig. 1, for different fault scenarios. Fig. 3. It is observed that the fault current contribution becomes
Considering the conventional protection strategy, the relays higher in mesh topology compared with the radial topology for
R1, R3, R5, R7, and R9 are employed for the protection of the same fault situation [18]. The fault current level also goes
DL1, DL2, DL3, DL4, and DL5, respectively, for the microgrid high for grid-connected mode compared with islanded mode
with synchronous, inverter, and induction-based DGs, as shown for mesh topology. For observing the impact of DG penetration
Fig. 1 (the details are given in Appendix). Fig. 2 shows the fault level, if one or some DGs are lost or disconnected due to some
currents (per unit) seen by the relays (at R1, R3, R5, R7, and other reason, the fault current contribution is reduced compared
R9) in the faulted distribution lines at different operating modes with the situation when those were existing. Fig. 4 shows the
for line–line–line faults (LLL) on the respective feeders. fault currents seen at R1, R3, R5, R7, and R9 for the faults
It is observed that the fault current in grid-connected mode simulated at different distribution feeders when all the DGs are
is higher compared with the islanded mode as the fault current present and DG1 out in case of islanded mode of operation.
is contributed from utility and the local DGs. The fault current Table I depicts the fault current seen by the relays placed
contribution from utility is higher due to its high short circuit at both ends of distribution lines for the LLL fault at different
megavolt ampere compared with that of the local DGs in the operating conditions. For the fault in grid-connected mode, the
microgrid. It is also observed that the fault current decreases for fault current seen by the relays placed at End1 are greater than
the faults occurring on the feeders away from the utility (DL-3, End2. But for the islanded mode, the fault current seen by relays
DL-4, and DL-5). The fault current in islanded mode becomes placed at End1 (R1, R3, R9) are smaller than End2 (R2, R4,
This article has been accepted for inclusion in a future issue of this journal. Content is final as presented, with the exception of pagination.

KAR et al.: DATA-MINING MODEL BASED INTELLIGENT DIFFERENTIAL MICROGRID PROTECTION SCHEME 3

Fig. 5. Proposed Data-mining model based intelligent differential protection


scheme.
Fig. 4. Fault current in the distribution lines when all DGs are present and
DG1 is disconnected (Islanded mode, radial topology).
(pu/s), the reactive power change with time (pu/s), the rate-
TABLE I of-change of power angle difference (ROCPAD), the rate of
FAULT C URRENT M EASURED AT D IFFERENT D ISTRIBUTION L INES change negative sequence voltage, and the rate of change nega-
tive sequence current at both ends of the feeder. The differential
features are computed from the respective features at both ends
of the feeder. These differential features are used to build the
DT-based data-mining model for registering the fault status and
to issue the tripping command. Fig. 5 shows the schematic dia-
gram of the proposed data-mining based intelligent differential
microgrid protection scheme.

III. I MPLEMENTATION OF THE P ROPOSED


R10) and the fault current seen by relays placed at End1 (R5, D IFFERENTIAL P ROTECTION R ELAY
R7) are greater than End2 (R6, R8). This happens due the DGs
A. Feature Extraction
penetration level for the respective fault situation [18]. Looking
at the aforementioned issues, it can be concluded that most The DFT based preprocessor [19] is used to estimate funda-
commercially used overcurrent relay with a preset threshold to mental phasor such as amplitude, phase angle, and frequency
operate in grid-connected mode may fail or may take a longer of the voltage and current signals retrieved at the ends of the
time to operate in islanded mode. Furthermore, the performance faulted feeder. The fundamental phasors estimated are used to
is significantly affected in case of radial and mesh topology, and compute the most sensitive features during the fault process at
the case when DG is lost due to some other reason. both ends of the feeder. The differential features between the
The microgrid protection scheme must guarantee safe and feeder ends are computed to build the data-mining model.
secured operation of the microgrid with radial or mesh distri- In the proposed study, seven differential features are derived,
bution network against faults in islanded and grid-connected which could be mostly affected during the fault condition and
modes. Considering the aforementioned challenges, there is a are measured locally as follows: Xi = Xi,S − Xi,T , where Xi
strong motivation to design an effective protection scheme that is the differential feature, i = 0, 1, 2 . . . , 7 and (no. of features),
can provide a reliable protection measure for safe and secure Xi,S is the ith feature estimated at bus-S, and Xi,T is the ith
microgrid operation. The proposed scheme develops a data- feature estimated at bus-T. S and T are the buses at both ends
mining-based intelligent differential protection relaying scheme of the target feeder, on which the fault occurs. The complete
for microgrid protection. The scheme considered shunt faults feature extraction block is shown in Fig. 6.
(L–G, L-L, LL-G, and LLL) at various locations of distribution X1 = Δ(df /dt), the differential ROCOF (Hz/s).
lines with grid-connected and islanded modes of microgrid X2 = Δ(dV /dt), the differential ROCOV (pu/s).
operation with radial and mesh topology. The no-fault cases, X3 = Δ(dP hi/dt), the differential ROCPAD.
which could be close to that of the fault transient such as sudden X4 = Δ(dP/dt), the differential active power change
load change at PCC and load bus, capacitors switching, etc., at with time (pu/s).
different operating conditions, are considered. X5 = Δ(dQ/dt), the differential reactive power change
The proposed scheme retrieves the fault currents and voltages with time (pu/s).
at both ends of the respective feeders and preprocesses through X6 = Δ(dVneg /dt), the differential rate of change negative
DFT-preprocessor [19] to extract sensitive features such as the sequence Voltage.
rate-of-change of frequency (ROCOF Hz/s), the rate-of-change X7 = Δ(dIneg /dt), the differential rate of change negative
of voltage (ROCOV pu/s), the active power change with time sequence current.
This article has been accepted for inclusion in a future issue of this journal. Content is final as presented, with the exception of pagination.

4 IEEE SYSTEMS JOURNAL

Fig. 6. Complete Feature extraction block.

Some of the differential features derived for single-line–


ground (L–G) fault situation are presented in Fig. 7. It is clearly
visible that the features are highly sensitive to the occurrence
of the fault event. While looking at the some pairs of features
for the fault detection task, as shown in Fig. 8, it is observed
that the features are highly overlapping and thus resulting much
below classification accuracy. Thus, the proposed approach
considers multiple features-based data-mining decision making
for effective and reliable microgrid protection relay.

B. Building a Data-Mining Model for Microgrid Protection


The proposed data-mining-based differential protection
scheme is shown in Fig. 5. The instantaneous current and
voltage signals are retrieved using CT/PT at ends of the target
feeder and then preprocessed through the DFT preprocessor.
The DFT preprocessor estimates the fundamental amplitude,
phase and frequency and subsequently related differential fea-
tures. These features are used to train the data-mining models
for final decision making. This study includes DT and support
vector machine (SVM) as data-mining models for developing
Fig. 7. Sample differential features affected during Single-Line to Ground
the fault protection relays. The studied microgrid system for the fault at grid-connected mode with radial structure, between feeder B1 and B2
proposed protection scheme is shown in Fig. 1, which includes (a) Feature X2 . (b) Feature X3 . (c) Feature X5 . (d) Feature X7 .
synchronous (DG-1, DG-2), inverter (DG-3) and induction
(DG-4)-based DGs. and the details of the studied system are in the feature space, the optimal hyperplane is found out to
given in the Appendix. The proposed study simulated different maximize the generalization ability of the classifier. SVM has
faults and no-fault cases with wide variations in operating attracted widespread attention due to its higher classification
conditions, as shown in Table II. accuracy and has been successfully applied to many power
DT [20], being the most transparent data-mining model, system applications [26], [27] and thus, selected for extensive
attracts wide spread attention for most engineering applications, performance comparison.
including power engineering [21]–[23] for classification and Building the data-mining models starts at retrieving one
decision making. DT, being rule based, is more transparent cycle postfault current signal and voltage signal samples at
and human friendly. The proposed method uses the powerful both the ends of the respective feeders and processed through
open-source data-mining software package “R” for generating DFT-preprocessor to estimate the differential features for the
the DTs [24]. On other hand, SVM [25], a machine learn- particular jth instance. While building the data-mining model,
ing technique, where the input space is mapped into a high- all the seven differential features are set as input against one
dimensional dot product space called a feature space; and target output of 1 (for fault) and 0 (for no-fault situation) for
This article has been accepted for inclusion in a future issue of this journal. Content is final as presented, with the exception of pagination.

KAR et al.: DATA-MINING MODEL BASED INTELLIGENT DIFFERENTIAL MICROGRID PROTECTION SCHEME 5

Fig. 9. DT generated for fault detection.

Fig. 8. Feature plots. (a) Feature X1 against feature X3. (b) Feature X2 against
feature X5.

TABLE II
S AMPLE O PERATING C ONDITIONS FOR FAULT AND N O -FAULT S ITUATION

Fig. 10. Degree of correlation between candidate features.

a particular jth instant. The feature set at jth instant is passed in Table II. Similarly, the total number of no-fault cases is 415,
through the data-mining models and the process continues until considering all operating conditions, as mentioned in Table II.
convergence. During the building of data-mining models (DT Out of this complete data set, 80% of the total data (1148) are
and SVM), it is observed that the data-mining models converge used to train the DT and rest 20% (287) are used for testing.
well within the 80% of the total data samples. Once the model The DT generated for fault detection is shown in Fig. 9.
is built (trained), then testing is carried out using the remain- A correlation analysis provides insights into the indepen-
ing 20% unseen data sets and subsequently the performance dence of the candidate features participating in the decision-
assessed. The feature set for the proposed study includes the making process. Dendrogram is used to provide a visual clue
total number of 1435 cases, which includes both fault and to the degree of closeness between the features or variables.
no-fault situations. The total of fault cases is 1020, which is The hierarchical correlation dendrogram [24] shown in Fig. 10
derived from the different operating conditions, as mentioned presents a view of the degree of correlation between candidate
This article has been accepted for inclusion in a future issue of this journal. Content is final as presented, with the exception of pagination.

6 IEEE SYSTEMS JOURNAL

Fig. 11. Performance comparison between DT and SVM for dependability, Fig. 12. Performance of DT for fault detection in grid-connected and islanded
security, and accuracy (grid-connected and islanded modes). modes (radial and mesh topology).

features and those take part in the decision-making process.


It can be seen that X2 and X4 are highly correlated, whereas
X5 and X3 has a similar relationship. Furthermore, X6 and X7
are with a similar correlation. Thus, one feature from each pair
participates in the DT building along with X1 .
It is observed that X1 (Δ(df /dt)), X2 (Δ(dV /dt)),
X3 (Δ(dP hi/dt)), and X5 (Δ(dQ/dt)) are taking part in the
final decision-making process. Thus, these are the most impor-
tant features impacting the decision-making process providing
fault and no-fault classification. While testing the trained DT
using the rest of the 20% unseen data (287 cases), it provides
classification accuracy of 99.11%. Out of the testing data set of
287 cases, 74 no-fault cases are classified as no-fault and one
no-fault case is classified as fault, whereas 221 fault cases are
classified as fault and 1 fault event is misclassified as no fault. Fig. 13. Performance of SVM for fault detection in grid-connected and
islanded modes (radial and mesh topology).

IV. R ESULTS AND A NALYSIS islanded modes with radial and mesh network topologies. The
data-mining models (DT and SVM) are developed using the
The following statistical metrics are used to assess the per- most widely used open-source software R [24]. It is found that
formance of the proposed fault protection relay. the performance indexes are very close to each other, except
1) Dependability: Total number of fault cases predicted/ security, which is 4% apart. The most important performance
Total number of actual fault cases. index is dependability and both data-mining models provide
2) Security: Total number of no-fault cases predicted/Total highly improved performance for fault detection.
number of actual no-fault cases. The performance comparison at different operating modes
3) Accuracy: Total number of correctly predicted (fault + (grid-connected or islanded) of operation are shown in Figs. 12
no fault) cases/Total numbers of actual (fault + no fault) and 13, respectively. This includes 510 fault cases and 170 no-
cases. fault cases in grid-connected mode, whereas 510 fault cases and
For the fault protection relay, dependability is the important 155 no-fault cases at islanded mode. It is observed that the DT
index to be assessed, which directly provides the fault cases has accuracy of 99.02% (with 99.8% dependability and 98.24%
predicted against the actual numbers of fault cases (shows security) for fault detection in grid-connected mode compared
misdetection). This shows the reliability of the scheme in with an accuracy of 99.475% (with 99.6% dependability and
detecting faults. Security shows the false alarm, which indicates 99.35% security) in islanded mode. For the same situations,
the number cases that actually do not belong to fault events and SVM provides accuracy of 98.33% (with 99.6% dependability
predicted as fault. Thus, misdetection is more critical compared and 97.06% security) for fault detection in grid-connected
with the false alarm. Finally, accuracy is measured, which mode and accuracy of 99.03% (with 100% dependability and
shows the predicted cases against the actual cases considering 98.06% security) in islanded mode. It is observed that even
both fault and no-fault cases together. if security and accuracy are marginally affected in islanded
The performance comparison between DT and SVM is mode, the dependability stays almost the same in both oper-
depicted in Fig. 11 (for the 20% testing dataset-287 cases). ating conditions. Thus, both the data-mining models provide a
While building the data-mining models (DT and SVM), the similar performance with grid-connected and islanded modes
mixed data set is used, including faults in grid-connected and of operation.
This article has been accepted for inclusion in a future issue of this journal. Content is final as presented, with the exception of pagination.

KAR et al.: DATA-MINING MODEL BASED INTELLIGENT DIFFERENTIAL MICROGRID PROTECTION SCHEME 7

TABLE III
P ERFORMANCE (D EPENDABILITY ) C OMPARISON B ETWEEN P ROPOSED
AND E XISTING R ELAYS IN G RID -C ONNECTED AND I SLANDED M ODES

TABLE IV
P ERFORMANCE (D EPENDABILITY ) C OMPARISON B ETWEEN P ROPOSED
AND E XISTING R ELAYS IN R ADIAL AND M ESH T OPOLOGY

Fig. 14. Performance of DT for fault detection in radial distribution network


and mesh network (grid-connected and islanded modes).

TABLE V
P ERFORMANCE A SSESSMENT OF THE P ROPOSED DT-BASED R ELAY W ITH
THE E XISTING OVERCURRENT AND C URRENT-D IFFERENTIAL R ELAY

Fig. 15. Performance of SVM for fault detection in radial distribution network
and mesh network (grid-connected and islanded modes).

Figs. 14 and 15 show the performance comparisons for fault


detection in different network topologies (radial and mesh net-
work topology). This includes 450 fault cases and 140 no-fault
cases in the radial distribution network, whereas 450 fault cases
and 125 no-fault cases in the mesh network. It is observed
from Fig. 14 that DT has an accuracy of 99.08% (with 99.67%
dependability and 98.49% security) for fault detection in radial
topology and has accuracy of 99.045% (with 98.89% depend-
ability and 99.2% security) in mesh topology. While assessing
the performance of SVM, as shown in Fig. 15, it is observed that
SVM has an accuracy of 98.38% (with 99.78% dependability
and 96.98% security) for fault detection in radial topology and
accuracy of 99.26% (with 98.52% dependability and 100% 23.89% in grid-connected and islanded modes of operation,
security) in the mesh topology. The performance of both models respectively, as depicted in Table III. Although the current-
is almost same except security where SVM falls close 2% differential relay performance improves over overcurrent relay,
behind the DT. but stays at far below the performance level of the proposed
The proposed data-mining-based differential relaying data-mining-based differential relays. Similar observations are
scheme is found to be highly effective for microgrid protection made for radial and mesh topology, as depicted in Table IV.
considering wide variations in operating conditions. The A qualitative performance comparison of the proposed relay
performance indexes such as dependability are close to 99% is made with the existing overcurrent and current-differential
considering radial and mesh topology with grid-connected and relays for specific fault situations, as depicted in Table V. It
islanded modes of operation, as depicted in Tables III and IV. can be seen that in certain critical cases where overcurrent and
While comparing the performance with existing overcurrent current-differential relays fail, the proposed data-mining-based
relay, it is found that the relay dependability is 79.63% and differential scheme succeeds in providing protection measure.
This article has been accepted for inclusion in a future issue of this journal. Content is final as presented, with the exception of pagination.

8 IEEE SYSTEMS JOURNAL

The proposed scheme considers one cycle postfault data for 60 Hz, rated kV = 575 V, Inertia constant H =
preprocessing through DFT-processor and less than 1/2 a cycle 0.685 s, friction factor F = 0.01 pu, Rs = 0.023 pu,
for deriving differential features plus data-mining processing Lls = 0.18 pu, Rr = 0.016 pu, Llr = 0.16 pu,
for each specific fault case (takes more time for training and Lm = 2.9 pu.
testing while considering the complete data sets). Thus, the 3) Transformer (TRs):
response time of the scheme is close to 1 and 1/2 cycles, which 1) TR1: rated MVA = 15, f = 60 Hz, rated kV =
is well accepted for relaying applications. 120/25, Vbase = 25 kV, R1 = 0.00375 pu, X1 =
Although SVM provides similar performance compared with 0.1 pu, Rm = 500 pu, Xm = 500 pu.
DT, the model complexity makes the implementation difficult 2) TR2, TR3: rated MVA = 12, f = 60 Hz, rated kV =
on the digital signal processor/field-programmable gate array 2.4 kV/25 kV, Vbase = 25 kV, R1 = 0.00375 pu,
board. At the same time, DT, being the transparent tool, can X1 = 0.1 pu, Rm = 500 pu, Xm = 500 pu.
be implemented based on the set thresholds of the decision 3) TR4: rated MVA = 10, f = 60 Hz, rated kV =
variables and thus attracts widespread attention as one of the 575 V/25 kV, Vbase = 25 kV, R1 = 0.00375 pu,
emerging data-mining tools for engineering applications and X1 = 0.1 pu, Rm = 500 pu, Xm = 500 pu.
their commercial implementations. 4) Distribution lines (DL): DL1, DL2, DL3, DL4,
and DL5: PI-Section, 30 km each, Vbase = 25 kV,
R0 = 0.1153 Ω/km, R1 = 0.413 Ω/km, L0 = 1.05 e −
V. C ONCLUSION
3 H/km, L1 = 3.32 e − 3 H/km, C0 = 11.33 e −
A data-mining model-based differential intelligent protection 9 F/km, X1 = 5.01 e − 9 F/km.
scheme for microgrid protection has been proposed. The pro- 5) Total loading (sum of L1 to L6) considered: 22 MW,
posed scheme develops protection function for the microgrid 10 MVAR.
operating at different modes and topology. The differential
features derived at respective feeders are used to build the data- R EFERENCES
mining models, which are used for a final relaying decision. [1] M. Stadler, A. Siddiqui, C. Marnay, H. Aki, and J. Lai, “Control of
The proposed data-mining model is extensively tested on the greenhouse gas emissions by optimal DER technology investment and
standard IEC microgrid model, including synchronous, induc- energy management in zero-net-energy buildings,” Eur. Trans. Electr.
Power, vol. 21, no. 2, pp. 1291–1309, Mar. 2011.
tion and inverter-based DGs with wide variations in operating [2] G. Venkataramanan and C. Marnay, “A larger role for microgrids,” IEEE
conditions and provide performance accuracy (dependability) Power Energy Mag., vol. 6, no. 3, pp. 78–82, May/Jun. 2008.
of 99% with a relaying speed of less than 1 and 1/2 cycle. The [3] A. Girgis and S. M. Brahma, “Effect of distributed generation on protec-
tive device coordination in distribution system, system,” in Proc. Large
performance comparison with existing relays indicates that the Eng. Syst. Conf. Power Eng., Jul. 2001, pp. 115–119.
proposed scheme can provide a highly reliable and effective [4] E. Casagrande and L. N. Woon, “A differential sequence component pro-
protection measure for the microgrid. tection scheme for micro-grids with inverter based distributed generators,”
IEEE Trans. Smart Grid., vol. 5, no. 1, pp. 29–37, Jan. 2014.
[5] H. Al-Nasseri, M. Redfern, and F. Li, “A voltage based protection for
micro-grids containing power electronic converters,” in Proc. IEEE Power
A PPENDIX Eng. Soc. Gen. Meet., Jun. 2006, pp. 1–7.
[6] T. Loix, T. Wijnhoven, and G. Deconinck, “Protection of micro-grids with
The base power has been chosen as 10 MVA. The details of a high penetration of Inverter-coupled energy sources,” in Proc. IEEE
the studied IEC microgrid [24] are given as follows: Power Energy Soc./CIGRE Symp., Jul. 2009, pp. 1–6.
1) Utility: rated short-circuit MVA = 1000, f = 60 Hz, [7] P. Mahat, Z. Chen, B. Bak-Jensen, and C. L. Bak, “A simple adaptive over
current protection of distributed systems with distributed generations,”
rated kV = 120, Vbase = 120 kV. IEEE Trans. Smart Grid, vol. 2, no. 3, pp. 428–437, Sep. 2011.
2) DGs: [8] S. M. Brahma and A. Girgis, “Development of adaptive protection scheme
1) DG1, DG2: synchronous generator with rated MVA = for distribution systems with high penetration of distributed deneration,”
IEEE Trans. Power Del., vol. 19, no. 1, pp. 56–63, Jan. 2004.
9, f = 60 Hz, rated kV = 2.4, Inertia constant H = [9] H. Wan, K. K. Li, and K. P. Wong, “An adaptive multiagent approach
1.07 s., friction factor F = 0.1 pu, Rs = 0.0036 pu, to protection relay coordination with distributed generators in indus-
Xd = 1.56 pu, Xd = 0.296 pu, Xd = 0.177 pu, trial power distribution system,” IEEE Trans. Ind. Appl., vol. 46, no. 5,
pp. 2118–2124, Sep./Oct. 2010.
Xq = 1.06 pu, Xq  = 0.177 pu, Xl = 0.052 pu, T d = [10] B. Hadzi-Kostova and Z. Styczynski, “Network protection in distribu-
3.7 s, T d = 0.05 s, T qo = 0.05 s. tion systems with dispersed Generation,” in Proc. IEEE PES Transmiss.
2) DG3: (inverter base DG) Wind farm consisting of Distrib. Conf. Exhib., May 2006, pp. 321–326.
[11] M. A. Zamani, T. S. Sidhu, and A. Yazdani, “A protection strategy and
three 2 MVA wind turbines (6 MVA, pf = 0.9), microprocessor-based relay for low-voltage micro-grids,” IEEE Trans.
f = 60 Hz, rated kV = 575 V, inertia constant H = Power Del., vol. 26, no. 3, pp. 1873–1883, Jul. 2011.
0.62 s, friction factor F = 0.1 pu, Rs = 0.006 pu, [12] H. Nikkhajoei and R. Lasseter, “Micro-grid protection,” in Proc. IEEE
Power Eng. Soc. Gen. Meet., Jun. 2007, pp. 1–6.
Xd = 1.305 pu, Xd = 0.296 pu, Xd = 0.252 pu, [13] M. A. Redfern and H. Al-Nasseri, “Protection of micro-grids dominated
Xq = 0.474 pu, Xq  = 0.243 pu, Xl = 0.18 pu, T do= by distributed generation using solid state converters,” in Proc. IET 9th
4.49 s, T do = 0.0681 s, T q = 0.0513 s. 575 V, 60 Hz. Int. Conf. Develop. Power Syst. Protection, 2008, pp. 670–674.
[14] H. H. Zeineldin, E. F. El-Saadany, and M. M. A. Salama, “Distributed
The synchronous generator with inverter interface to generations micro-grid operation: Control and protection,” in Proc.
main grid has been considered for the proposed study Power Syst. Conf., Adv. Metering, Protection, Control, Commun. Distrib.
(Type-4 detailed model in MATLAB/SIMULINK). Resources, Mar. 2006, pp. 105–111.
[15] E. Sortomme, S. S. Venkata, and J. Mitra, “Microgrid protection using
3) DG4: DFIG-based wind farm consisting of six communication-assisted digital relays,” IEEE Trans. Power Del., vol. 25,
1.5-MVA wind turbines (9 MVA, pf = 0.9), f = no. 4, pp. 2789–2796, Oct. 2012.
This article has been accepted for inclusion in a future issue of this journal. Content is final as presented, with the exception of pagination.

KAR et al.: DATA-MINING MODEL BASED INTELLIGENT DIFFERENTIAL MICROGRID PROTECTION SCHEME 9

[16] S. Kar and S. R. Samantaray, “Time-frequency transform-based differ- S. R. Samantaray (M’08–SM’10) received the
ential scheme for micro-grid protection,” IET Generation Transmiss. B.Tech. degree in electrical engineering from the
Distrib., vol. 8, no. 2, pp. 310–320, Feb. 2013. University College of Engineering Burla, Burla,
[17] T. S. Ustun, C. Ozansoy, and A. Zayegh, “Modeling of a centralized India, in 1999 and the Ph.D. degree in power system
micro-grid protection system and distributed energy resources according engineering from the Department of Electronics and
to IEC 61850-7-420,” IEEE Trans. Power Syst., vol. 27, no. 3, pp. 1560– Communication Engineering, National Institute of
1567, Aug. 2012. Technology, Rourkela, India, in 2007.
[18] T. S. Ustun, C. Ozansoy, and A. Zayegh, “Fault current coefficient and He holds the position of Assistant Professor with
time delay assignment for microgrid protection system with central pro- the School of Electrical Sciences, Indian Institute of
tection unit,” IEEE Trans. Power Syst., vol. 28, no. 2, pp. 598–606, Technology Bhubaneswar, Bhubaneswar, India. He
May 2013. is a Visiting Professor with the Department of Elec-
[19] A. Samui and S. R. Samantaray, “Assessment of ROCPAD relay for trical and Computer Engineering, McGill University, Montréal, QC, Canada.
islanding detection in distributed generation,” IEEE Trans. Smart Grid, His major research interests include intelligent protection for transmission
vol. 2, no. 2, pp. 391–398, Jun. 2011. systems [including Flexible AC Transmission Systems (FACTs)] and microgrid
[20] J. Abonyi and B. Feil, Cluster Analysis for Data Mining and System protection with distributed generation and dynamic security assessment in large
Identification. London, U.K.: Birkhauser, 2007, p. 319. power networks.
[21] S. Kar and S. R. Samantaray, “Data-mining-based intelligent anti- Dr. Samantaray is the recipient of the 2007 Orissa Bigyan Academy Young
islanding protection relay for distributed generations,” IET Generation Scientists Award, the 2008 Indian National Academy of Engineering Best
Transmiss. Distrib., vol. 8, no. 4, pp. 629–639, Apr. 2014. Ph.D. Thesis Award, the 2009 Institute of Engineers (India) Young Engineers
[22] K. El-Arroudi, G. Joós, I. Kamwa, and D. T. McGillis, “Intelligent-based Award, the 2010 Samanta Chandra Sekhar Award, and the 2012 IEEE PES
approach to islanding detection in distributed generation,” IEEE Trans. Technical Committee Prize Paper Award. He serves as an Editor of IET,
Power Del., vol. 22, no. 2, pp. 828–835, Apr. 2007. Generation, Transmission and Distribution, IEEE C ANADIAN J OURNAL OF
[23] K. Mei and S. M. Rovnyak, “Response-based decision trees to trigger one- E LECTRICAL E LECTRONICS AND C OMPUTER E NGINEERING , E LECTRIC
shot stabilizing control,” IEEE Trans. Power Syst., vol. 19, no. 1, pp. 531– P OWER C OMPONENTS AND S YSTEMS.
537, Feb. 2004.
[24] D. Williams, Rattle (the R Analytical Tool to Learn Easily), Dec. 2010.
[Online]. Available: http://rattle.togaware.com/ M. Dadash Zadeh received the B.S. and M.Sc.
[25] T. Hastie, R. Tibshirani, and J. Friedman, The Elements of Statistical degrees from the University of Tehran, Tehran, Iran,
Learning: Data Mining, Inference, Prediction, 2nd ed. New York, NY, in 2002 and 2005, respectively, and the Ph.D. degree
USA: Springer-Verlag, 2009, p. 745. from the University of Western Ontario, London,
[26] P. K. Dash, S. R. Samantaray, and G. Panda, “Fault classification and ON, Canada, in 2009, all in electrical engineering.
section identification of an advanced series-compensated transmission From 2002 to 2005, he was with Moshanir Power
line using support vector machine,” IEEE Trans. Power Del., vol. 22, Engineering Consultants and served as a System
no. 1, pp. 67–73, Jan. 2007. Study Engineer. From 2009 to 2010, he worked as
[27] F. R. Gomez, A. D. Rajapakse, U. D. Annakkage, and I. T. Fernando, a Postdoctoral Fellow with the University of West-
“Support vector machine based algorithm for post-fault transient stability ern Ontario, London, ON, Canada. From 2010 to
status prediction using synchronized measurements,” IEEE Trans. Power 2011, he was with GE Multilin active in design and
Syst., vol. 26, no. 3, pp. 1474–1483, Aug. 2011. production in the areas of microgrid automation and control, synchrophasor
measurement system and protective relays.

Susmita Kar (S’14) received the M.Tech degree


from Birla Institute of Technology, Mesra, India.
She is currently working toward the Ph.D. degree in
the School of Electrical Sciences, Indian Institute of
Technology Bhubaneswar, Bhubaneswar, India.
Her research interests include microgrid protec-
tion, including islanding detection and fault protec-
tion, signal processing, and data-mining applications
to microgrid protection.

You might also like