You are on page 1of 12

IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 32, NO.

1, FEBRUARY 2017 441

A Comprehensive Digital Protection Scheme for


Low-Voltage Microgrids with Inverter-Based and
Conventional Distributed Generations
Seyed Fariborz Zarei and M. Parniani, Senior Member, IEEE

Abstract—Microgrid (MG) protection is one of the main chal- devices (PDs) in presence of conventional DGs [5]. In islanded
lenges in proliferation of microgrids. Due to limited fault current mode, fault current levels significantly decrease because of iso-
feeding of inverter-based distributed generations (DGs), in islanded lation from main grid, and conventional fuse and overcurrent
operation of MG, protection problems become more complicated;
and, therefore, conventional protection strategies cannot be ap- (OC) relay protection may not operate [6]. This problem is
plied. Hence, new protection methods that are applicable in is- more troublesome for MGs with inverter-based distributed gen-
landed and grid-connected modes of operation are necessary. In erations (IBDGs), since their fault current contribution is limited
this paper, a comprehensive digital-relay based protection is intro- [7]. Furthermore, conventional DGs with low inertia are com-
duced for the protection of MGs. The proposed method includes monly utilized in MGs [8]. Because of their low inertia, it can be
protection of lines, distributed generations, and the point of com-
mon coupling. The structure and graphical schematic of the pro- expected that transient instability occurs in islanded mode of op-
posed digital relays are also presented. The proposed method is eration. The MG protection strategy should then be fast enough
independent of the MG operation mode and benefits from single- to isolate the faulty section [9]. Inasmuch as conventional PDs
phase tripping. In this method, due to fault isolation from both such as fuses and OC relays take long time to operate, alteration
sides of a line, downstream loads and DGs can operate after fault of protection strategy will be necessary.
clearance. To demonstrate the effectiveness of the proposed pro-
tection method, numerous simulations are carried out on an MG In spite of abundant number of researches in the field of MG
test system in the PSCAD/EMTDC environment. protection, there is no comprehensive method that is applicable
in grid connected mode as well as islanded mode. In [10], the
Index Terms—Digital relay, distributed generation (DG),
inverter-based distributed generation, microgrid, microgrid
effects of high penetration of DGs on coordination of PDs has
protection. been explored and an adaptive protection scheme that is based
on communication links has been suggested. This strategy is
I. INTRODUCTION applicable only for grid-connected mode and is not effective for
HE low voltage microgrid (MG) is a three-phase asym- systems with low penetration of DGs. Reference [11] describes
T metric system that has many distributed energy resources
(DERs) and loads, such as distributed generators (DGs), stor-
a voltage measurement based protection strategy for microgrids
with high penetration of inverter-coupled resources. The pro-
age devices, and controllable loads [1]. By introduction of MG posed strategy does not rely on communication; but considers
concept and its proliferation, it is expected that customer ser- only the islanded mode of operation. In [12], the efficiency of
vice continuity increases and power quality indices enhance [2]. under/over frequency relays is investigated for protection of
Moreover, due to grid-connected and islanded operation capa- distributed synchronous generators. In this study, islanded op-
bility of MGs, system reliability increases [3]. In spite of these eration is not considered and the effects of inverter-based DGs
benefits, it changes the fundamental concepts of distribution are not included. In [13] current sequence components are used
systems, and grid protection and control methods should be for fault detection in islanded operation of MG. Reference [14]
adapted accordingly [4]. Without considering these challenges, proposes a method based on monitoring the output voltages of
the aforementioned benefits will be inaccessible. inverter-based DGs. By transformation of voltage signals from
In grid connected mode of operation, large current contribu- abc coordinate to rotating dq-frame, disturbances are extracted,
tion of the main grid causes the amplitude of fault current to and occurrence of fault is detected. This scheme seems suitable
become large, and it may lead to miscoordination of protective for islanded MG, but not for grid-connected mode of operation.
In addition, noise immunity of this method has not been proved.
Central control and monitoring unit is used in [15], [16] for pro-
Manuscript received July 31, 2015; revised January 13, 2016 and March 17,
2016; accepted May 7, 2016. Date of publication May 10, 2016; date of current tection of MG. It updates all of the relays settings upon any con-
version January 20, 2017. Paper no. TPWRD-01015-2015. figuration changing of MG. Installation of a new DG completely
The authors are with the Department of Electrical Engineering, Sharif Uni- disorders the previous settings, and new ones would be required.
versity of Technology, Tehran, Iran (e-mail: zarei_fariborz@ee.sharif.edu;
parniani@sharif.edu). Moreover, IBDGs are not considered in these studies. Reference
Color versions of one or more of the figures in this paper are available online [17] investigates protection issues related to LV microgrids and
at http://ieeexplore.ieee.org. elaborates LV microgrid protection concepts comprehensively.
Digital Object Identifier 10.1109/TPWRD.2016.2566264

0885-8977 © 2016 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission.
See http://www.ieee.org/publications standards/publications/rights/index.html for more information.
442 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 32, NO. 1, FEBRUARY 2017

Voltage and frequency relays are used as a point of common Generally, there are three configurations for earthing which
coupling (PCC) relay, and directional OC (DOC) relay is uti- are TT, TN, and IT systems [21]. These configurations are differ-
lized for feeder protection. DOC takes a long time to operate. ent in connection of transformer neutral and electrical equipment
Besides, with its operation, all of the feeder elements should be to the earth. References [21]–[23] denote that TN system is the
tripped. In [7] a protection strategy for LV microgrids is pre- most suitable for MG application. In this configuration, trans-
sented. The proposed strategy is applicable for both modes of former neutral and electrical equipment frame are connected to
operation and is independent of fault current magnitude. Single the earth. This system provides large amount of fault current by
phase tripping is another feature of this work. In this method, all which PDs can sense the fault and interrupt it. Also, by using
of a feeder elements should be tripped for a fault in that feeder, TN system, touch voltage value will be in a range that satisfies
which is undesirable for sensitive loads. Shortcomings of the the safety margin.
previous studies can be summarized as follows:
Some of the proposed methods are dependent to the mode
C. Distributed Generations
of operation [10], [18], [19]. In some others, PDs act in one
direction, and therefore all of downstream DGs should be tripped Conventional DGs and IBDGs are commonly used in MGs.
[5]. This results in imbalance of production and consumption, In this section, their operations are briefly described, and the
which is an important issue in islanded MG. Also, some of the proposed protections for them will be presented in Section III.
previous researches do not consider all types of fault, and/or do 1) Conventional DGs: This type of DGs is chiefly syn-
not have single phase tripping capability [13]. chronous machine based DGs that have low inertia and
This paper proposes a comprehensive protection strategy their fault current contribution is larger than IBDGs. Pres-
based on digital relays, which is applicable to both grid con- ence of these DGs in MG can disturb the protection coor-
nected and islanded modes of operation. The proposed strategy dination and MG stability [5]. Thus their effects should be
covers all elements of MG and considers various types of fault. considered carefully.
In this method, downstream DGs and loads can be maintained in 2) Constant Power Controlled Inverter-Based DGs: Con-
service when a fault occurs in an upstream feeder. Furthermore, stant power controlled IBDGs operate in constant power control
it works properly even with low magnitudes of fault current. mode, and exchange predefined real and reactive powers with
This research is organized as follows. Section II briefly re- the rest of MG or main grid. They do not contribute to volt-
views the structure of low voltage microgrids. In Section III, age and frequency control, and it is assumed that other sources
novel protective relays and protection strategy for LV microgrid control the voltage and frequency [24]. Therefore, they can be
are proposed, and Coordination among the protective relays is simulated as constant current sources that inject power to the
covered in Section IV. Simulation results for grid connected and grid. For correct operation, an appropriate synchronization al-
islanded modes are presented in Section V. Finally, the study is gorithm is required [25]. Upper-level controllers, such as max-
concluded in Section VI. imum power point tracking in wind turbines and photovoltaic
cells may provide the power sharing [26]. This type of IBDG is
II. STRUCTURE OF LOW VOLTAGE MICROGRIDS known as grid-feeding voltage source inverter, and has an inter-
nal current control loop. Basic control block diagram of these
In this section, characteristics of different elements of low IBDGs are thoroughly described in [27].
voltage MG will be reviewed; in order to present appropriate 3) IBDGs With Voltage and Frequency Control: This type of
protective relays for them in the next section. IBDGs operate as controllable voltage sources, in which their
voltage and frequency references are obtained from superior
A. Configuration controls such as droop controls [24]. As a result of their contri-
LV-network contains a number of LV feeders initiating from bution in controlling the voltage and frequency, MG voltage and
LV busbars. LV feeders include many branches, and loads may frequency controls are enhanced. This type of IBDG is known
be installed anywhere along the feeder. Due to the presence as grid-forming voltage source inverter, and possesses two in-
of single-phase loads and lines, LV networks are unbalanced ternal voltage and current control loops. Basic control block
networks. Main substation of LV network often connects to diagrams of this type of IBDGs are comprehensively explained
upstream network through a single transformer with rating of in [27], [28].
up to 1MVA, and its connection group is usually DYn11 [20]. LV To control the aforementioned IBDGs, rotating dq-frame co-
side of the transformer has Y connection windings that provides ordinate is commonly used. In this coordinate, balanced signals
ground connection for single-phase loads. appear as constant quantities. Therefore, controller design in
dq-frame is straightforward. In this paper, for proper opera-
tion of IBDGs in faulty and unbalanced conditions, negative
B. Earthing
sequence filtering and elimination is assumed. Using this ap-
Effective earthing system is necessary in electrical systems proach, three phase IBDGs can feed the single phase and unbal-
to increase human safety and reduce electrical hazards. Proper anced three phase loads, a capability which is not accessible by
earthing system reduces long term over-voltages and diminishes conventional controllers. Some papers such as [29]–[31] have
the electrical shocks. In addition, earthing system provides a explored the issue of power converters control in unbalanced
return path for leakage currents, so that PDs can detect and condition. In this paper, a voltage controller similar to that pre-
interrupt the fault [21]. sented in [30] is utilized to control IBDGs with voltage and fre-
ZAREI AND PARNIANI: A COMPREHENSIVE DIGITAL PROTECTION SCHEME FOR LOW-VOLTAGE MICROGRIDS WITH INVERTER-BASED 443

quency control. The method is based on elimination of negative


sequence voltage by feeding the necessary negative sequence
current. This voltage control ensures balanced voltage in load
buses. Also, a current control loop similar to that proposed in
[32] is used to simulate constant power controlled IBDG. For
the sake of brevity, these mentioned controllers are not further
described here.

D. Point of Common Coupling


Point of common coupling (PCC) is defined as the point that
several loads are connected to each other or several generators.
In case of MG, PCC is the interface between MG and main grid.
Usually the PCC comprises one isolation transformer and a fast
switch that can be of static type [13]. In the faulty condition and
disturbances in main grid, this switch operates and isolates the
MG from grid.

E. Control of Micro-Grid
As already stated in part C of this section, MG generally
comprises three types of distributed generations having their
own internal controls. To assure stable operation of MG and
appropriate power sharing among the DGs, another outer power
control loop is necessary. Droop control is a prevalent method
utilized in the literature, and hence is used in this paper. For
conciseness, the concept of droop control is not elaborated in
this paper, and detailed explanations can be found in [27], [33]. Fig. 1. (a) Characteristic of differential current protection (b) schematic illus-
tration of protection.
III. PROPOSED PROTECTIVE RELAYS AND PROTECTION
STRATEGY FOR LOW VOLTAGE MG ation, downstream DGs control the voltage and frequency of
their loads, and a new MG is formed. If a connection ring is
In most of existing protection methods for LV grids, a large
utilized at the end of feeders, the new MG can be connected to
area should be isolated in faulty condition. For instance, upon
the main MG or to the main grid. For this operation to fulfill,
a fault in one feeder, all of energy resources and loads of this
appropriate synchronization means should be employed. Using
feeder should be interrupted and the faulty feeder is separated
this protection strategy, all of downstream loads can be operated
from the rest of the grid. In this situation, if the feeder protection
normally without any interruption, creating a better condition
fails, the whole MG should be tripped and all of its loads lose
for MG with sensitive loads. To accomplish this aim, current
electricity. This problem arises from unidirectional operation of
information in both sides of the protected line is collected and
conventional PDs employed in these methods. These PDs are
fault occurrence is detected based on their differences. The pro-
coordinated in a way that for a forward fault, the nearest PD to
tection scheme based on information of two sides of line is
the fault operates with a time delay and isolates the fault from
much faster than the conventional PDs that are coordinated with
one side. In the presence of DGs, downstream network is active,
load protections.
and in faulty condition, all of the downstream DGs of the faulty
Fastness of the suggested protection helps the MG stability
feeder should be tripped to isolate the fault. In other words, in
and operation continuity of sensitive loads. Capacitor charging
this situation, by operation of upstream relay, a trip signal is
current and CT saturation are the main issues of differential
sent to all of its downstream DGs. Besides, in the former studies
current based protections. In LV microgrids with short lines and
for asymmetrical faults, three-phase tripping had been applied
low voltage levels, the former problem is not critical, and for
rather than single phase tripping. However, for a LV MG with
the latter, one-slope differential relay characteristic is utilized.
many unbalanced and single phase loads, three-phase tripping
Fig. 1 shows graphical representation of this relay. For grid-
is not the best remedy.
connected mode of operation, owing to the large fault current
In the following, the proposed protections for lines, DGs and
supplied by main grid, a high set region is considered.
PCC are presented.
A digital relay is also suggested to be utilized as backup for the
load and line protections. This relay is installed at the beginning
A. Protection of Microgrid Lines and Feeders of feeders, and hereafter is called MG feeder protection relay or
This research proposes a protection strategy based on double- MGFPR. By operation of this relay, the corresponding feeder
end disconnection of faulty line, in which downstream DGs and is disconnected and one trip signal is sent to all downstream
loads are allowed to work after fault clearance. In this situ- DGs on the feeder. MGFPR consists of two modules, namely
444 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 32, NO. 1, FEBRUARY 2017

Fig. 2. Microgrid feeder protection relay (MGFPR).

directional overcurrent, and directional negative sequence


current modules. Fig. 2 demonstrates graphical illustration of
the proposed MGFPR. The description of the two modules in
Fig. 2 are provided in the following.
Directional Overcurrent Module Due to the large fault cur- Fig. 3. First type DG trip command generation unit.
rent contribution of the main grid in grid connected mode, OC
relay is the best remedy to identify faults. To distinguish the fault in one direction. For this aim, the MGFPR can be used at
faults behind the relay, directional elements are incorporated the sending end of these lines.
in the module. Furthermore, for proper coordination, a definite
time delay tdr−OC is added in the reverse mode. Also, OR logic
is used to calculate the trip signal of this module. As a result, B. Distributed Generations
with occurrence of a fault in either of three phases, the relay In this paper, two types of trip command are used for DG
output will be activated. Due to the inverse time characteristic protection. First, trip command from external protections, and
of the relay, it operates faster for the currents with larger am- the second, trip command from their self-protective relays.
plitude. However, due to the reduced fault current in islanded The first type DG trip command comes from MGFPR and
mode, the module will not operate in a reasonable time. This lines protection. The first type trip command generation unit is
deficiency is overcome by the next module. displayed in Fig. 3. With regard to the feeder protection strat-
Directional Negative Sequence Current Module This mod- egy, by operation of MGFPR, one trip signal is sent to all of
ule uses negative sequence component to detect faults. There- DGs which are installed in the feeder downstream. To issue this
fore, it is highly sensitive to asymmetrical faults. This module command, some important points should be noted.
does not depend on large fault current amplitude. Thus, it can op- 1) If the line differential current protection scheme faces
erate properly in the islanded mode as well as the grid connected some hardware problems like connection wires defect and
mode. For correct detection of fault direction (forward/reverse), so forth, the MGFPR operates and sends a trip command
directional negative sequence element is employed. This se- to the DGs on the feeder, and disconnects them. In this
quence current is fed to its corresponding instantaneous OC situation, trip command should be sent without any con-
relay (Block 50 in Fig. 2). Afterwards, the outputs together with straints. (trip signal number 1 in Fig. 3)
its directional elements is passed through AND logic, to dis- 2) If the main protection (i.e., the line protection) operates
criminate the direction of fault. Different definite time delays properly and the sending end circuit breaker of that line
are also utilized to provide the necessary coordination. fails to operate, the faulted line will be isolated from down-
Description of the negative sequence directional element used side and supplied from upside. Therefore, downstream
in this work is available in Appendix A. DGs and loads operate properly, but due to operation of
Two aforementioned modules have overlaps in some types MGFPR a trip signal will be sent to the relevant DGs and
of faults, but their operational time is different from each other. loads. Hence, this trip command should be restrained with
Therefore, they provide a redundant protection, which improves sending end circuit breaker failure (SECBF) signal. (trip
reliability of MG. signal number 2 in Fig. 3)
It should be noted that differential current-based protections 3) If the main protection is operating properly and the re-
are only exerted to the lines with at least one DG controlling ceiving end circuit breaker fails to operate, the sending
the voltage and frequency in their downstream side. For protec- end will be isolated and the MGFPR does not act. As a
tion of the lines in which there is no source with voltage and result, the fault is fed through the receiving end DGs. In
frequency control in their downstream, it is allowed to clear the this case, receiving end circuit breaker failure (RECBF)
ZAREI AND PARNIANI: A COMPREHENSIVE DIGITAL PROTECTION SCHEME FOR LOW-VOLTAGE MICROGRIDS WITH INVERTER-BASED 445

Fig. 5. Proposed relay for conventional DGs.

In this module, voltage and current THDs are first calculated


and compared with the corresponding threshold values using
instantaneous relays. The resultant trip signals of three phases
Fig. 4. Self-protection of IBDGs with V&f control.
are passed through OR logic. For the purpose of coordination,
definite time delays are also utilized in the module.
signal is used for interruption of its downstream DGs. (trip 2) IBDGs With Constant Power Control: This type of DG
signal number 3 in Fig. 3) does not regulate voltage and frequency. If islanding condition
The second type of trip command comes from DG’s own occurs after clearing the fault by MGFPR, voltage and frequency
protection. The proposed DG protection is set according to the will change widely. Thus, for this type of DGs, voltage and fre-
fault behavior of DGs, as explained in the following. quency relays can be used to protect them against such excur-
1) IBDGs With Voltage and Frequency Control: For this type sions. Reference [17] proposes features of the relevant voltage
of DG, three different features are introduced. Based on these and frequency relays.
features, three different modules are used in the proposed re- 3) Conventional DGs: To protect synchronous DGs from
lay. The suggested self-protection of IBDGs with voltage and faults and imbalances, the following two modules are suggested
frequency control are depicted in Fig. 4. to be used.
Under Voltage Module: Solid faults in islanded MG with IB- Overcurrent Module Due to large fault current contribution
DGs extremely decrease the voltage. Therefore, voltage drop of these DGs, in comparison to IBDGs, OC relays are used
can be used for fault detection. Characteristics of voltage relay as primary protection. These relays operate with a time delay
are extracted from CBEMA curve, in which allowable over- relative to the main PDs and should be coordinated with them.
voltage and under-voltage ranges for a computer system are Imbalance Detection Module It should be noted that syn-
specified [34]. chronous generator-based DGs (SGDGs) cannot operate in an
Overcurrent and Overload Module: For high impedance unbalanced condition; hence, single phase tripping is not per-
faults and overload condition, heating effect of the current can mitted for OC relays. Furthermore, unbalanced currents cannot
be used for fault detection. This feature yields a delayed char- be supplied from SGDGs, because the flow of negative sequence
acteristic and the IBDG relay operates with a long delay in this currents through the stator windings creates a rotating magneto
case. The proposed module comprises an instantaneous overcur- motive force (mmf) in counter direction of the main mmf. Hence,
rent relay and a definite time delay for each phase. The outputs the rotor sees the mmf with twice the synchronous speed and
of three phases are connected to the OR logic, and the final out- high eddy current and associated losses arise. In this module,
put yields the trip command of the module. As a consequence, trip signal is issued using an instantaneous relay whose pick up
the module operates for asymmetrical overcurrent and overload current is the maximum allowable negative sequence current. To
condition as well as symmetrical ones. consider the heating effect of negative sequence current, which
Voltage and Current Total Harmonic Distortion (THD) is a slow phenomenon, a definite time delay is used.
Module: The third module is based on the output voltages Outputs of the two modules are connected to OR logic, and
and currents THD. In the IBDGs, inner control loop is current the final output is the DG trip signal. Graphical illustration of
control loop. To protect inverter switches from overload and the proposed relay for conventional DGs is presented in Fig. 5.
faulty conditions, the current reference is limited to 1.5–2 times C. Point of Common Coupling: A MG is normally operated
of nominal current. In faulty condition, this limiter is saturated in grid connected mode. To enhance the power quality of loads
and output voltages and currents get distorted. As this distorted in faulty condition and abnormal events of the main grid, the
voltages and currents are fed back to the voltage and current MG is disconnected from the grid. Isolation of MG from the
controllers, more distortion is caused in the output voltages and grid is performed by PCC relay. For the faults in the main grid,
currents, leading to significant rise in THDs. Then, the THD the PCC relay should operate quickly, and delayed mode is used
rise can be used as a feature for fault detection. This feature has as a backup for protections of MG. Perfect operation of the
a great appearance in solid and medium impedance faults. PCC relay in the grid and MG faults entails employment of an
446 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 32, NO. 1, FEBRUARY 2017

performance in this case. As a result, this module is only suit-


able for MG faults (reverse mode). For this reason directional
element is not utilized in this module.
Directional Under-Voltage Module For three phase sym-
metrical faults in the main grid, both of the aforementioned
modules fail to operate. Considering severe voltage drop during
this fault, then, an under-voltage relay accompanied by direc-
tional element can be used for proper diagnosis. Also, definite
time delays are utilized for coordinated operation of the mod-
ule in forward and reverse directions. By using the module, for
solid three phase faults, the under voltage relay operates with
minimum delay and isolates the MG from the grid.

IV. COORDINATION OF PROTECTIVE RELAYS


In Section III, individual protective relays were introduced for
different elements of MG, i.e., lines, feeders, IBDGs, SGDGs
and PCC. For full coverage of MG protection, these relays must
be employed in a coordinated manner. Otherwise, unwanted trip
commands will be issued for out of zone faults.
For better description of the coordination method, the test
microgrid system of Fig. 7 is utilized. This test system is a low
voltage (400 volt) network containing all components (includ-
Fig. 6. Graphical illustration of the proposed relay for PCC.
ing all relays and MG elements) discussed earlier. Line and load
protections are the fastest PDs in the system, which operate in-
efficient fault detection method and protection strategy. Thus, dependent of other protections. On the other side, the rest of
because of low amplitude fault current contribution of MG in the protections such as MGFPRs, DG relays and PCC relay are co-
main grid faults, conventional OC relay which is solely based ordinated with them. In this system, there are three MGFPRs as
on current amplitude is not a suitable tool for fault detection. To backup for their corresponding line and load PDs. For this rea-
overcome this problem, the PCC relay shown in Fig. 6 is utilized son, the minimum trip time of 80 msec is selected for the fastest
in this work. This relay consists of three modules described MGFPRs (i.e., MGFPR1 and MGFPR3). Furthermore, the PCC
as follows. relay and MGFPRs of neighboring feeders in their reverse mode
Directional Negative sequence Current Module In this mo- are backup for the specified MGFPR. For example MGFPR2,
dule, negative sequence component of current is employed as MGFPR3 and the PCC relay are back up for MGFPR1 in their
fault detection means. The module detects asymmetrical faults reverse mode.
in the main grid as well as the MG. To discriminate between Fig. 8 shows the coordination of MGFPRs and PCC relay.
the main grid and MG faults, negative sequence directional Each of these relays has individual forward and reverse modes
element is used. Also, two definite time delays are utilized and the corresponding trip times. Trip time of each relay depends
for forward and reverse operation. Very small time delay is on the modules incorporated in that relay. For example, trip time
selected for forward operation, such that the PCC relay rapidly of MGFPR1 depends on its two mentioned modules. Due to the
isolates the MG from grid in response to the faults in main OR logic used in the relay, its trip time is the minimum of
grid. On the other hand, time delay of reverse operation should the two modules trip time. Parameters of Fig. 8 are described
be very long, so that coordination between the PCC relay and in Table I.
MG protections is maintained. Inasmuch as this module takes Fig. 9 displays t-I characteristics of OC relays. It should be
the same time to operate for all types of faults in the reverse noted that OC relays are depicted with number 51 in Figs. 2, 5,
mode, this feature is not appropriate for solid faults with high and 6. In this paper, extremely inverse OC relay based on IEC
amplitude currents. Also, this module cannot respond to three 60255 is utilized. Fig. 9 shows that OC module of MGFPR3 is
phase symmetric faults. The following two modules overcome the fastest one among all. This module should be coordinated
these challenges. with downstream load protections. For this reason, it is assumed
Overcurrent Module for MG Faults In the grid connected that the OC module of MGFPR3 operates in 80 msec for the fault
mode, the main grid contributes a large current for faults in in Bus4. By this assumption, OC module of MGFPR3 operates
the MG. Thus, OC relay can be used as a redundant protection. with enough delay, allowing load protections to isolate faults,
In this paper, an OC relay is used for each of three phases, as main protection. Above all, this assumption leads to fast
and their outputs joined with OR logic produce the trip signal. operation of OC module for faults within Line22, due to their
Due to the inherent inverse time characteristic of the relay, solid higher fault current as compared to the end of line fault current.
faults can be removed faster. Low fault current contribution of While coordinating the OC module, it is supposed that SGDG
the MG to grid faults causes the OC relay not to have desirable is in service and contributes to fault current. This assumption
ZAREI AND PARNIANI: A COMPREHENSIVE DIGITAL PROTECTION SCHEME FOR LOW-VOLTAGE MICROGRIDS WITH INVERTER-BASED 447

Fig. 7. Test system.

TABLE I
DESCRIPTION OF FIG. 8 PARAMETERS

Parameter Description

t1 f Trip time caused by module 1 in forward direction


t2 f Trip time caused by module 2 in forward direction
t1 r Trip time caused by module 1 in reverse direction
t2 r Trip time caused by module 2 in reverse direction
t3 f Trip time caused by module 3 in forward direction
t3 r Trip time caused by module 3 in reverse direction
tO C Trip time caused by directional OC relay
tU V Trip time caused by under voltage relay

coordination. When calculating the setting, it is assumed that


SGDG is out of service; otherwise the calculated margin will
not be achieved when SGDG is out of service. It should be
noted that presence of SGDG causes MGFPR2 to sense less
fault current than MGFPR3 for a fault in Line22.
To find the setting of OC module in MGFPR1, it is necessary
to consider the most delayed PDs in Feeder 1. Considering this
point, the OC module should operate at least with 80 msec delay
to preserve coordination with downstream load PDs. Hence, the
Fig. 8. Coordination among MGFPRs and PCC relay. setting of OC module is calculated in a way that for a fault in
Bus1, it takes 80 msec to operate. This setting ensures that for a
fault within Line11, with higher currents, OC module operates
prevents miscoordination, which is a common problem in MGs with reduced time and isolates the fault faster. In this case, it is
with conventional DGs. also assumed that SGDG is in service and contributes in fault
The setting of MGFPR2’s OC module is calculated based on current; otherwise operation time of OC relay for the fault will be
the assumption that for a fault at location just after MGFPR3 (in smaller than 80 msec when SGDG is in service. Finally, to select
Line22), OC module of MGFPR2 should operate with enough the PCC relay setting, it is necessary to note that PCC should
margin with respect to OC module of MGFPR3 to preserve be coordinated with OC modules of MGFPR1 and MGFPR2.
448 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 32, NO. 1, FEBRUARY 2017

a coordinated manner. In addition, they allow DGs and loads to


remain in service after fault clearance in both modes of opera-
tion. Performance of the proposed protection scheme in the two
modes of operation is examined in the following subsections.

A. Grid Connected Mode


It is observed that for line faults, differential current based
protection operates as main PD. It also detects faults in less than
1 cycle. MGFPR and PCC relays are backups to this protection.
Simulation results show that OC relay and current sequence
component relay operate in an acceptable time range. Due to
space limitation, few number of simulation results for grid con-
nected mode are tabulated in Table II. Columns one and two
of the table specify location and type of faults, respectively. In
column 3, activated relays to the fault are listed according to
their operation sequence. Also, column 4 represents operation
times of the relays. To clarify the results presented in the table,
LL fault at location Fault2 is explained as an example.
The first two top waveforms in Fig. 10 illustrate the fault cur-
rent supplied from upstream and downstream of fault location. In
the upstream, the main grid and DGs of neighboring feeder con-
tribute to the fault current, and in the downstream, IBDG1 feeds
the fault. As expected, the currents supplied by IBDG1 present
reduced magnitudes and distorted shapes, which is caused by
Fig. 9. t-I characteristics of OC relays. hard limiter incorporated in IBDG1 to reduce its fault current
feeding capability. Also, other Boolean type waveforms in Fig.
10 are related to trip signals issued by different relays in the
system. In order to analyze performance of all relays, the trip
It should be noted that the protection relays for DGs are commands are intentionally blocked, and therefore the fault re-
dependent on load and line protections. To clarify the operation mains active. As shown in the figures, upon occurrence of Fault2
of DGs relays, coordination manner of SGDG and IBDG1 relays at t = 1.6 sec, the current differential based protection first de-
are presented here. tects the fault and issues trip command after 3 msec. After 56
As shown in Fig. 7, for a fault in Line22, MGFPR3 is re- msec, MGFPR1 operates with its OC module. The second mod-
sponsible to create trip signal and isolate the fault; therefore, ule of MGFPR1 responds to the fault in 83 msec. Later, THD
in this situation SGDG relay is back up protection. Consider- and UV modules of the IBDG1 relay create trip signals 150 msec
ing 80 msec definite time delay for negative sequence module and 112 msec after fault occurrence, respectively. Afterwards,
of MGFPR3 and also using t-I characteristic of its OC module, the PCC relay, MGFPR2 and MGFPR3 respond to the fault in
setting of SGDG relay is calculated. To do the job, it is enough to 308, 352, and 504 msec by their reverse mode. This sequence of
coordinate SGDG relay with MGFPR3 for fault at Line22 right operation demonstrates coordinated operation of the proposed
after MGFPR3, having maximum value of fault current along protection strategy and protective relays.
the feeder. In addition, to assure coordination of IBDG1 relay
with load protections, 150 msec definite time delay is utilized B. Islanded Mode
for THD modules.
Tables IV to VIII in Appendix B demonstrate the settings of In this case, due to the presence of IBDG in the MG and
relays used in this work. In the next section, various simula- disconnection from main grid, fault current level decreases sig-
tion results are presented to verify the correct and coordinated nificantly. Simulation results show that current differential based
operation of proposed relays. protection operates as main PD and detects the fault in less than
one cycle. This fast operation reinforces transient stability of the
MG especially when it comprises synchronous machine based
V. SIMULATION RESULTS
DGs with low inertia. MGFPR acts as a backup PD and isolates
To evaluate the effectiveness of the proposed method, the test the faulty feeder from rest of the MG. Due to space limitation, a
microgrid system is simulated in PSCAD/EMTDC environment few number of simulation results for islanded mode are shown
[35]. All types of fault (including LG, LL, LLG, and 3phase) in Table III. To clarify the results the LG (phase A to ground)
have been examined on the test system for different locations in fault in location Fault3 is explained as follows.
both grid-connected and islanded modes of operation. Based on Upon occurrence of the fault, the line protection sents out trip
the simulation results, the proposed relays isolate the faults in signal in 3 msec. Similar to the grid connected mode, to analyze
ZAREI AND PARNIANI: A COMPREHENSIVE DIGITAL PROTECTION SCHEME FOR LOW-VOLTAGE MICROGRIDS WITH INVERTER-BASED 449

TABLE II
SIMULATION RESULTS FOR GRID-CONNECTED MODE

Fig. 10. Fault current waveforms and relays trip signals for LL fault at location
Fault2 in grid-connected mode.
450 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 32, NO. 1, FEBRUARY 2017

TABLE III TABLE IV


SIMULATION RESULTS FOR ISLANDED MODE DIFFERENTIAL CURRENT BASED PROTECTION SETTINGS

diff. relay parameter Value(A)

Diff relay for Line 11 I dmi fi fn 15


It h 15
Id i f f 2 1200
Diff relay for Line 12 I dmi fi fn 10
It h 10
Id i f f 2 600
Diff relay for Line 21 I dmi fi fn 28
It h 13
Id i f f 2 1100
relays slope = 0.3

VI. CONCLUSION
This research suggests a comprehensive protection strategy
for low voltage microgrid. In this strategy different protective
relays (based on digital relays) were introduced for all of mi-
crogrid components, such as lines, feeder, conventional and
inverter-based DGs, and PCC. Schematic illustration of new
digital relays was also presented. The proposed method does
not rely on microgrid central protection and adaptive protec-
tion methods, and thus, avoids their associated problems. Since
the suggested strategy is credible in both grid-connected and
islanded modes of operation; there is no need for mode switch-
ing. The applied method benefits from double side fault clearing
and single phase tripping capabilities to increase service conti-
nuity of loads. To demonstrate the effectiveness of the proposed
method, numerous simulations in both grid-connected and is-
landed mode of operation have been conducted on the test MG
system. Simulation results verify safe, selective and reliable op-
eration of protective devices in both modes of operation for
internal and external faults in microgrid.

APPENDIX A
NEGATIVE SEQUENCE DIRECTIONAL ELEMENT [36]
The principle behind the Negative Sequence Directional El-
ement is that for a forward fault, negative sequence impedance
would be negative and for a reverse fault, it would be positive.
Considering the source behind the relay terminal is strong, this
may result in a very low negative sequence voltage. To over-
come such situations, a compensating quantity is added to boost
the negative sequence voltage.
the performance of other protective relays the trip command
Applying the compensating quantity introduces a forward
is deliberately blocked. Therefore, the fault will remain active.
and reverse threshold. Then the criteria is that if Z2 < Z2f , then
MGFPR2 and the SGDG relay respond to fault in 124 msec
the fault is forward and if Z2 > Z2r , then the fault is reverse.
and 181 msec in their forward modes, respectively. Afterwards,
The forward threshold must be less than the reverse threshold
MGFPR1 and MGFPR3 create trip signals in 361 msec and
to avoid any overlap. The output will be generated only if the
505 msec after fault occurrence in reverse mode. For the sake
ratio of negative sequence current to positive sequence current
of brevity, the waveforms and trip signals of the relays are not
exceeds the specified limit.
shown in this case.
In summary, simulation data demonstrate the effective, coor-
dinated and selective operation of the proposed relays in both APPENDIX B
RELAYS SETTINGS
modes of operation. It is worth mentioning that the proposed
protection does not need mode switching from grid connected The parameters of the proposed protections are reported in
mode to islanded mode or vice versa. Tables IV–VIII. It should be noted that current settings of relays
ZAREI AND PARNIANI: A COMPREHENSIVE DIGITAL PROTECTION SCHEME FOR LOW-VOLTAGE MICROGRIDS WITH INVERTER-BASED 451

TABLE V REFERENCES
FEEDER PROTECTION SETTINGS
[1] N. Hatziargyriou, H. Asano, R. Iravani, and C. Marnay, “Microgrids,”
IEEE Power Energy Mag., vol. 5, no. 4, pp. 78–94, Jul./Aug. 2007.
Parameter Description MGFPR1 MGFPR2 MGFPR3 [2] E. Casagrande, W. L. Woon, H. H. Zeineldin, and D. Svetinovic,
“A differential sequence component protection scheme for microgrids
t d r −O C Time delay for OC 300 msec 300 msec 500 msec with inverter-based distributed generators,” IEEE Trans. Smart Grid, vol.
relay in reverse mode 5, no. 1, pp. 29–37, Jan. 2014.
t d f −n e g Time delay for neg. 80 msec 120 msec 80 msec [3] I.-S. Bae and J.-O. Kim, “Reliability evaluation of customers in a mi-
seq. relay in forward
mode
crogrid,” IEEE Trans. Power Syst., vol. 23, no. 3, pp. 1416–1422,
t d r −n e g Time delay for neg. 350 msec 350 msec 500 msec
Aug. 2008.
seq. relay in reverse [4] P. Basak, S. Chowdhury, S. H. N. Dey, and S. Chowdhury, “A literature
mode review on integration of distributed energy resources in the perspective
Ip Pickup current for 220 A 200 A 90 A of control, protection and stability of microgrid,” Renew. Sustain. Energy
OC relay Rev., vol. 16, pp. 5545–5556, 2012.
TMS Time multiplier 0.8 0.94 0.85 [5] A. Zamani, T. Sidhu, and A. Yazdani, “A strategy for protection coordina-
setting (TMS) tion in radial distribution networks with distributed generators,” in Proc.
Ip 2 Pickup current for 20 A 10 A 10 A IEEE Power Energy Soc. Gen. Meeting, 2010, pp. 1–8.
neg. seq. [6] A. R. Haron, A. Mohamed, and H. Shareef, “A review on protection
instantaneous OC schemes and coordination techniques in microgrid system,” J. Appl. Sci.,
relay vol. 12, pp. 101–112, 2012.
[7] M. A. Zamani, T. S. Sidhu, and A. Yazdani, “A protection strategy
and microprocessor-based relay for low-voltage microgrids,” IEEE Trans.
Power Del., vol. 26, no. 3, pp. 1873–1883, Jul. 2011.
TABLE VI [8] T. V. Van et al. et al., “Virtual synchronous generator: An element of future
INVERTER-BASED DG’S PROTECTION SETTINGS grids,” in Proc. IEEE Power Energy Soc. Innovat. Smart Grid Technol.
Conf. Eur., 2010, pp. 1–7.
[9] H. Zeineldin and J. L. Kirtley Jr, “Microgrid stability characterization
Parameter Description Value subsequent to fault-triggered islanding incidents,” IEEE Trans. Power
Del., vol. 27, no. 2, pp. 658–669, Apr. 2012.
Ip v h Pickup value for voltage THD 10% [10] S. M. Brahma and A. Girgis, “Development of adaptive protection scheme
Ip v i Pickup value for current THD 10% for distribution systems with high penetration of distributed generation,”
Ip Pickup current for instantaneous OC relay 350 A IEEE Trans. Power Del., vol. 19, no. 1, pp. 56–63, Jan. 2004.
T d −O C Time delay for instantaneous OC relay 2 sec [11] T. Loix, T. Wijnhoven, and G. Deconinck, “Protection of microgrids
Td v h Time delay for instantaneous voltage THD relay 150 msec with a high penetration of inverter-coupled energy sources,” in Proc. CI-
Td ih Time delay for instantaneous current THD relay 150 msec GRE/IEEE Power Energy Soc. Integr. Wide-Scale Renew. Resources Into
Power Del. Syst Joint Symp., 2009, pp. 1–6.
[12] J. C. Vieira, W. Freitas, W. Xu, and A. Morelato, “Performance of fre-
quency relays for distributed generation protection,” IEEE Trans. Power
TABLE VII Del., vol. 21, no. 3, pp. 1120–1127, Jul. 2006.
SGDG RELAY SETTINGS [13] H. Nikkhajoei and R. H. Lasseter, “Microgrid protection,” in Proc. IEEE
Power Eng. Soc. Gen. Meeting, 2007, pp. 1–6.
[14] M. Redfern and H. Al-Nasseri, “Protection of micro-grids dominated by
Parameter Description Value distributed generation using solid state converters,” in Proc. IET 9th Int.
Conf. Develop. Power Syst. Protect., 2008, pp. 670–674.
I p (for 51) Pickup current for OC relay 209 A [15] M. R. Islam and H. A. Gabbar, “Analysis of microgrid protection strate-
TMS Time multiplier setting 0.167 gies,” in Proc. IEEE Int. Conf. Smart Grid Eng., 2012, pp. 1–6.
td Time delay for Imbalances detection module 2000 sec [16] T. S. Ustun, C. Ozansoy, and A. Zayegh, “Modeling of a centralized
I p (for 50) Pickup current for instantaneous OC relay 0.1 p.u. microgrid protection system and distributed energy resources according
to IEC 61850-7-420,” IEEE Trans. Power Syst., vol. 27, no. 3, pp. 1560–
1567, Aug. 2012.
[17] H. J. Laaksonen, “Protection principles for future microgrids,” IEEE
TABLE VIII Trans. Power Electron., vol. 25, no. 12, pp. 2910–2918, Dec. 2010.
PCC PROTECTION SETTINGS [18] H. Wan, K. Li, and K. Wong, “An multi-agent approach to protection relay
coordination with distributed generators in industrial power distribution
system,” in Proc. 40th Ind. Appl. Soc. Annu. Meeting. Conf. Rec., 2005,
Parameter Description Value pp. 830–836.
[19] B. Hadzi-Kostova and Z. Styczynski, “Network protection in distribution
Ip Pickup current for OC relay 400 A systems with dispersed generation,” in Proc. IEEE/Power Energy Soc.
TMS Time multiplier setting 1.66 Transm. Distrib. Conf. Exhibit., 2006, pp. 321–326.
t d f −n e g Time delay for neg. seq. PCC relay in forward mode 35 msec [20] S. Papathanassiou, N. Hatziargyriou, and K. Strunz, “A benchmark low
t d r −n e g Time delay for neg. seq. PCC relay in reverse mode 350 msec voltage microgrid network,” in Proc. CIGRE Symp.: Power Syst. Dispersed
Ip 2 Pickup current for neg. seq. instantaneous OC relay 20 A Gen., 2005, pp. 1–8.
t d f −U V Time delay for PCC relay (UV) in forward mode 5 msec [21] R. M. Kamel, A. Chaouachi, and K. Nagasaka, “Design and testing of three
t d r −U V Time delay for PCC relay (UV) in reverse mode 200 msec earthing systems for micro-grid protection during the islanding mode,”
Smart Grid Renew. Energy, vol. 1, pp. 132–, 2010.
[22] L. BoTong, L. Yongli, and M. Tao, “Research on earthing schemes in LV
microgrids,” in Proc. Int. Conf. Adv. Power Syst. Autom. Protect., 2011,
pp. 1003–1007.
[23] R. M. Kamel, A. Chaouachi, and K. Nagasaka, “Comparison the perfor-
in the tables are related to grid side currents. In other words, the mances of three earthing systems for micro-grid protection during the grid
settings are related to the primary side of current transformers connected mode,” Smart Grid Renew. Energy, vol. 2, pp. 206–, 2011.
(CTs). This kind of presentation is used only for better judgment [24] J. Rocabert, A. Luna, F. Blaabjerg, and P. Rodrı́guez, “Control of power
converters in AC microgrids,” IEEE Trans. Power Electron., vol. 27,
about the scale and order of currents in the MG. Hence, to apply no. 11, pp. 4734–4749, Nov. 2012.
these settings to relays, they should be multiplied by CT ratios.
452 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 32, NO. 1, FEBRUARY 2017

[25] C. Cho, J.-H. Jeon, J.-Y. Kim, S. Kwon, K. Park, and S. Kim, “Ac- [35] “PSCAD/EMTDC V. 4.2,” Manitoba HVDC Research Center, Winnipeg,
tive synchronizing control of a microgrid,” IEEE Trans. Power Electron., MB, Canada.
vol. 26, no. 12, pp. 3707–3719, Dec. 2011. [36] PSCAD master library models H.V.D.C. Manitoba Research Centre Inc.,
[26] Y.-H. Ji, D.-Y. Jung, J.-G. Kim, J.-H. Kim, T.-W. Lee, and C.-Y. Won, Winnipeg, MB, Canada.
“A real maximum power point tracking method for mismatching compen-
sation in PV array under partially shaded conditions,” IEEE Trans. Power
Electron., vol. 26, no. 4, pp. 1001–1009, Apr. 2011. Seyed Fariborz Zarei received the B.Sc. degree in
[27] J. Rocabert, A. Luna, F. Blaabjerg, and P. Rodrı́guez, “Control of electrical engineering from Amirkabir University of
power converters in AC microgrids,” IEEE Trans. Power Electron., Technology, Tehran, Iran, in 2012 and the M.Sc. de-
vol. 27, no. 11, pp. 4734–4749, Nov. 2012. gree in electrical engineering from the Sharif Univer-
[28] A. Yazdani and R. Iravani, Voltage-Sourced Converters in Power Systems: sity of Technology (SUT), Tehran, in 2014, where he
Modeling, Control, and Applications. Hoboken, NJ, USA: Wiley, 2010. is currently pursuing the Ph.D. degree in electrical
[29] M. B. Delghavi and A. Yazdani, “Islanded-mode control of electroni- engineering.
cally coupled distributed-resource units under unbalanced and nonlinear His fields of interest include control and protec-
load conditions,” IEEE Trans. Power Del., vol. 26, no. 2, pp. 661–673, tion of microgrids and renewable energy sources.
Apr. 2011.
[30] M. Hamzeh, H. R. Karimi, and H. Mokhtari, “A new control strategy for
a multi-bus MV microgrid under unbalanced conditions,” IEEE Trans.
Power Syst., vol. 27, no. 4, pp. 2225–2232, Nov. 2012. Mostafa Parniani (SM’06) received the B.Sc. degree
[31] J. P. Lopes, S. A. Polenz, C. Moreira, and R. Cherkaoui, “Identification in electrical power engineering from the Amirkabir
of control and management strategies for LV unbalanced microgrids with University of Technology, Tehran, Iran, in 1987, the
plugged-in electric vehicles,” Elect. Power Syst. Res., vol. 80, pp. 898–906, M.Sc. degree in electrical power engineering from
2010. Sharif University of Technology (SUT), Tehran, in
[32] A. Yazdani and R. Iravani, “A unified dynamic model and control for 1989, and the Ph.D. degree in electrical engineering
the voltage-sourced converter under unbalanced grid conditions,” IEEE from the University of Toronto, Toronto, ON, Canada,
Trans. Power Del., vol. 21, no. 3, pp. 1620–1629, Jul. 2006. in 1995.
[33] J. M. Guerrero, J. C. Vasquez, J. Matas, D. Vicuna, L. Garcı́a, and Currently, he is a professor at the SUT. During
M. Castilla, “Hierarchical control of droop-controlled AC and DC 1988–1990, he was with Ghods-Niroo Consulting
microgrids—A general approach toward standardization,” IEEE Trans. Engineers Co. and the Electric Power Research Cen-
Ind. Electron., vol. 58, no. 1, pp. 158–172, Jan. 2011. ter, both in Tehran, Iran. He was a Visiting Scholar at Rensselaer Polytechnic
[34] S. Elphick and V. Smith, “The 230 V CBEMA curve—Preliminary stud- Institute, Troy, NY, USA, during 2005–2006. His research interests include
ies,” in Proc. 20th Australn Univ. Power Eng. Conf., 2010, pp. 1–6. power system dynamics and control, applications of power electronics in power
systems, and renewable energies.

You might also like