You are on page 1of 12

This article has been accepted for inclusion in a future issue of this journal.

Content is final as presented, with the exception of pagination.

IEEE TRANSACTIONS ON SMART GRID 1

Fault Type Classification in Microgrids


Including Photovoltaic DGs
Ali Hooshyar, Ehab F. El-Saadany, Senior Member, IEEE, and
Majid Sanaye-Pasand, Senior Member, IEEE

Abstract—Protective devices of smart and fault-resilient micro- which account for the majority of faults. On the other hand,
grids are not expected to trip the healthy phases during unbal- single-phase protective devices are increasingly installed in
anced short-circuits. Thus, some utilities and relay manufacturers modern distribution systems. That is why several proposals
have started contemplating single- and double-pole tripping for
distribution systems. Selective phase tripping demands fault type have been put forward by the industrial community to apply
classification. This paper reveals that existing industrial methods selective phase tripping in distribution systems [6], [7]. With
misidentify the fault type in microgrids that include photovoltaic the prospect of substantial improvement to system reliability,
distributed generations (DGs). Due to interface similarities, this this plan has already been put into practice by some utilities
paper pertains to systems with type IV wind DGs as well. Two and relay manufacturers [8]. The Alabama Power Company is
new classifiers proposed in this paper determine the fault type
accurately for not only microgrids with photovoltaic DGs, but for a case in point [9].
any three-phase system. With low computational burden, they Sustained unbalanced operation of a microgrid during per-
require only local information and operate successfully for high manent faults needs to be investigated for realizing any
resistance faults. Furthermore, these techniques are not affected selective phase tripping scheme. For instance, the capacity of
by the system imbalance and different DG power factors over the neutral current return path has to be taken into account
disturbances.
for selective phase tripping of four wire systems, and unbal-
Index Terms—Fault resiliency, fault type classification, micro- anced operation during permanent faults may be permitted
grid protection, photovoltaic distributed generation (PVDG). only when the neutral current is limited to a certain level.
However, 50%–80% of actual distribution system faults are
I. I NTRODUCTION temporary [10], for which the relays reclose the breakers after
TEMMING from the different operation modes and a short period and overheating of neutral conductors is not
S the diversity of generation technologies, the protection
of a microgrid can be challenging [1]. Traditional relaying
normally a concern.
On the other hand, the internal protection of most of the
schemes for distribution systems may fail to protect a micro- existing PVDG inverters trip during unbalanced conditions in
grid, particularly if converter-interfaced renewable distributed order to meet the current islanding protection requirements.
generations (DGs), such as photovoltaic DGs (PVDGs), are However, if a fault-resilient microgrid with high renewable
involved, as is often the case. PVDGs have limited fault energy penetration and the capability of islanded operation
currents to which the overcurrent elements are normally is to materialize, then PVDGs must ride through unbalanced
insensitive [2]. Various publications offer protection solutions faults and let the relays protect the system, i.e., similar
for microgrids by means of adaptive and communication- to renewable sources connected to transmission systems. If
assisted techniques [3]–[5]. Despite their successful fault PVDGs are disconnected from the microgrid due to unbal-
detection, these methods do not provide information on the anced voltages, then any asymmetrical fault (irrespective of its
fault type. duration and location) may potentially result in total shutdown
A smart and resilient microgrid should maintain the oper- of an islanded microgrid that includes large PVDGs.
ation of sound phases during the unbalanced short-circuits, Selective phase tripping requires fault type classification by
the microgrid protection system. In transmission system relays,
Manuscript received December 14, 2014; revised January 3, 2015 and fault type classification is an imperative subroutine, the out-
April 24, 2015; accepted June 21, 2015. Paper no. TSG-01220-2014.
A. Hooshyar is with the Electrical Engineering and Computer Science put of which is needed for several functions, e.g., single-pole
Department, York University, Toronto, ON M3J 1P3, Canada (e-mail: autoreclosure and blocking of ground distance elements dur-
hooshyar@eecs.yorku.ca). ing phase faults. An early fault type identification method still
E. F. El-Saadany is with the Department of Electrical and Computer
Engineering, University of Waterloo, Waterloo, ON N2L 3G1, Canada (e-mail: used by some manufacturers is based on the magnitudes of
ehab@uwaterloo.ca). the impedances measured for different fault loops [11]. The
M. Sanaye-Pasand is with the School of Electrical and Computer inaccuracy of this approach for short lines, among other short-
Engineering, College of Engineering, University of Tehran,
Tehran 14395-515, Iran (e-mail: msanaye@ut.ac.ir), and also with the comings, led to the development of several classifiers exploit-
Control and Intelligent Processing Center of Excellence, College of ing the phase differences between the superimposed sequence
Engineering, University of Tehran, Tehran 14395-515, Iran. currents [12]–[14], which have been proven effective for con-
Color versions of one or more of the figures in this paper are available
online at http://ieeexplore.ieee.org. ventional power systems. Some of these methods, however,
Digital Object Identifier 10.1109/TSG.2015.2451675 need high-bandwidth communication infrastructure, which is
1949-3053 c 2015 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission.
See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for inclusion in a future issue of this journal. Content is final as presented, with the exception of pagination.

2 IEEE TRANSACTIONS ON SMART GRID

(a)
Fig. 1. Single line diagram of the test microgrid.

not normally available at the distribution level. Another group


of relays utilize overcurrent-based methods with satisfactory
performances for conventional systems [15], [16].
This paper reveals that the existing fault type classifiers
malfunction for microgrids that include PVDGs. The anal-
ogy between the grid-side converters makes this paper equally (b)
applicable to the systems with type IV wind DG. The unveiled
problem can also be encountered in transmission systems to Fig. 2. PVDG voltage for a bolted AG fault at bus 2. (a) Voltage on the
which converter-interfaced renewable power plants are con- low-voltage side of the transformer. (b) Voltage across the inverter’s LC filter.
nected. Two new methods are developed to determine the fault
type for not only a microgrid with PVDG, but any three-phase superimposed sequence currents of R14 for a bolted phase A
system. The proposed classifiers perform successfully for both to ground (AG) fault at bus 2 are within 4◦ of each other.
islanded and grid-connected modes of a microgrid, and do not Hence, the method of [13] identifies the fault type accurately.
require communication facility. Their other salient features Proper classification for this AG fault when the PVDG
include robustness against fault resistance, Rf , and indepen- is in service entails aligned sequence components for the
dence from PVDG’s power factor (PF) in the course of faults. superimposed currents flowing from the PVDG. Conventional
power plants connected to transmission networks, where the
II. T EST M ICROGRID method of [13] has been utilized for years, deploy syn-
Simulated by PSCAD/EMTDC, the 34.5 kV, 60 Hz sys- chronous generators with excitation systems, which maintain
tem of Fig. 1 is used for this paper. The specifications of the the machine voltage during short-circuits. Therefore, such
system, which is balanced at this stage, are shown in the fig- power plants or DGs are modeled by voltage sources for fault
ure. The 9.2 MW PVDG at bus 4 along with a synchronous studies [19], and the characteristics of fault currents, including
DG (SDG) at bus 3 can supply all of the loads. Therefore, their angles, are determined by the fault properties, such as its
the substation breaker can be opened, allowing the system to type and impedance. A PVDG, in contrast, is connected to
operate as an isolated microgrid. During the grid-connected the grid/microgrid through a voltage source converter (VSC),
mode, the SDG is normally open. R14 is the relay located which operates as a current source [20]. If the neutral of the
next to bus 1 and protects the feeder between buses 1 and 4. PVDG transformer’s grid side is grounded, then the angle of
The fast dynamics of the PV source are essentially decou- the PVDG zero-sequence current is still mainly determined
pled from the grid by the dc capacitor. Thus, the PV source by the fault properties. The positive and negative sequence
together with the dc–dc converter are represented by a con- currents, however, are regulated by the control system of the
trollable current source. The specifications of the PVDG trans- converter and its internal references.
former are 14 MVA, 4.16/34.5 kV, X = 0.1 p.u. and dYG. The Feed-forward compensation using the voltage at the grid-
PVDG can ride through faults using a chopper circuit [17]. side of the VSC’s LC filter, denoted by Vg , is an integral part
PVDGs operate at 0.95 plus PF in North America. Meanwhile, of the control systems used in PVDGs, as it allows independent
requirements for reactive current generation up to the rated control of the active and reactive power and improves the tran-
capacity during faults have been put in place for renew- sient response of the VSC by making the disturbances of Vg
able sources by some European grid codes [18]. The modeled also appear in the voltage of the converter-side of the LC filter,
PVDG can satisfy both of these requirements. designated by Vt [21]. To examine the effect of feed-forward
compensation on fault classification, consider the aforemen-
tioned AG fault at t = 2 s when the PVDG is in service
III. P ERFORMANCE OF E XISTING FAULT
and generates its rated power at unity PF before the fault.
T YPE C LASSIFIERS
After the fault inception, the converter generates equal active
A. Current Angle-Based Methods and reactive powers, meeting the requirements mentioned
The relative angles of the superimposed sequence currents in [18]. The unbalanced voltages on the low-voltage side of
are utilized by many relays (see [13]), to determine the fault the PVDG transformer are displayed in Fig. 2(a). As a result
type. The approach adopted by [13] ensures accuracy for all of the feed-forward compensation, Vt exhibits similar imbal-
conditions, including a microgrid with conventional sources. ance. Therefore, the difference between the power-frequency
Take, for instance, the system of Fig. 1 in grid-connected mode content of Vg and Vt , which is the voltage across the VSC’s LC
when the PVDG is not in service. The angles of the three filter and determines the converter current, becomes balanced.
This article has been accepted for inclusion in a future issue of this journal. Content is final as presented, with the exception of pagination.

HOOSHYAR et al.: FAULT TYPE CLASSIFICATION IN MICROGRIDS INCLUDING PVDGs 3

(a)
Fig. 3. Angles of R14 superimposed sequence currents for the fault of Fig. 2.

Fig. 2(b) shows this voltage for the above fault after being
passed through a low-pass filter to eliminate the switching
pulses.
This disturbance-free voltage leads to converter currents
with practically zero negative and zero sequence components,
denoted by I − and I o . Moreover, the positive sequence cur- (b)
rent, I + , increases by only 20% following the fault inception,
Fig. 4. PVDG current at the grid side of the transformer during a BCG
as the PVDG control system limits the converter overcurrents fault when the PVDGs PF is unity. (a) Instantaneous current. (b) Angle of
to protect the switches. sequence components.
Since the currents injected by the PVDG do not follow the
regular pattern of AG fault currents, the angles of the superim-
posed sequence currents of R14, shown in Fig. 3, do not select
the faulted phase correctly. The  sign in the figure designates
the superimposed signals. I − leads I + by 128.0◦ , which
falls under the sector defined for phase B to ground (BG)
faults in [13]. Meanwhile, I o lags I − by 110.6◦ , indicat-
ing a phase C to ground (CG) or phases A to BG (ABG)
fault. Hence, the method of [13] is unable to identify the fault (a)
type. The same scenario applies to other current angle-based
classifiers as well.

B. Current Magnitude-Based Methods


Another classification approach is based on the magnitudes
of the phase or line-to-line (LL) currents after a fault. This
section starts by analyzing the basic current magnitude-based
(b)
approach, according to which the phases with the largest over-
currents are the faulted ones [22]. This method is employed Fig. 5. PVDG current at the grid side of the transformer during a BCG fault
by the selective phase tripping devices currently utilized in when the PVDG generates rated reactive current. (a) Instantaneous current.
distribution systems [8], [9], but it is not used by modern (b) Angle of sequence components.
transmission system relays, as it is vulnerable to weak infeeds
and might suffer from high resistance faults and system imbal- 0.138 kA, respectively. The angles of sequence components,
ance. However, it will be unveiled that the presence of PVDGs measured with respect to phase A, are plotted in Fig. 4(b). The
makes this method unreliable even for bolted faults in balanced positive sequence current of phase B lags the −2.9◦ positive
microgrids with no weak infeed. The following demonstrates sequence angle in Fig. 4(b) by 120◦ . As a result, the phase
that the unfaulted phases may have larger overcurrents when difference between the positive and zero sequence components
the system includes PVDGs; the overcurrent levels are highly for phase B current becomes 139.7◦ , whereas the same quan-
dependent on PVDG’s reactive current level during faults. tity for phase A is 100.4◦ . In other words, the two sequence
Fig. 4(a) shows the grid-side current of the PVDG trans- components nearly cancel each other in phase B current, which
former when the PVDG operates at unity PF during a bolted drops below even the prefault level. Unlike the case of weak
phases B to CG (BCG) fault at bus 2 of the grid-connected infeed, for which the close phase current magnitudes make
microgrid. Although phase A is healthy, its current is 0.27 kA, phase selection difficult, the basic overcurrent-based classi-
exceeding phase B’s current by about 0.1 kA. The larger phase fier clearly misidentifies the fault type, even though the zero
A current originates from the angle between the converter- sequence component does not dominate the PVDG current
generated fault current and the zero sequence current flowing in Fig. 4(a).
through the ground of the PVDG transformer. As discussed, Fig. 5 depicts the PVDG current for the same fault when the
the converter’s negative sequence current is negligible, and PVDG complies with the requirements of [18] by generating
the current of Fig. 4(a) consists of only the positive and the rated reactive current during the fault. Fig. 5(a) shows
zero sequence components, whose magnitudes are 0.267 and that the change in the reactive current of the PVDG raises
This article has been accepted for inclusion in a future issue of this journal. Content is final as presented, with the exception of pagination.

4 IEEE TRANSACTIONS ON SMART GRID

(a)
Fig. 6. Superimposed LL currents of the PVDG for the fault of Fig. 2.

phase B current beyond the other currents. The magnitudes


of sequence components are virtually identical with the mag-
nitude of sequence components for the fault of Fig. 4. In
addition, the zero sequence angle in Fig. 5(b) is similar to that
in Fig. 4(b). Conversely, the angle of the positive sequence (b)
component is shifted backwards by about 90◦ to meet the
reactive current requirement. As a result, the phase difference Fig. 7. Parameters of [16] for the fault of Fig. 4. (a) DEL. (b) DEL1.
between the zero and positive sequence terms of phase B cur-
rent has reduced to 43.3◦ , i.e., these two components do not
cancel each other anymore. The classification provided by the
basic current magnitude-based method is thus unreliable, as it
depends on the PF of the PVDG’s converter.
To address the impact of weak infeeds, current magnitude-
based classifiers of commercial relays normally remove the
zero sequence current. Hence, the angle between the pos- Fig. 8. Sequence circuits connection for an AG fault.
itive and zero sequence currents should no longer affect
fault type classification. Meanwhile, these methods select
incorrect phases for other reasons. Take, for instance, the sequence current have made the DEL of all phases identical in
classifier of [15], which compares the magnitudes of the Fig. 7(a). Hence, DEL1 signals are checked for an LLG fault.
superimposed LL currents. In a conventional system, a single- Since DEL1 includes the zero sequence term, it is affected
line-to-ground (SLG) fault results in two large superimposed by the angle between the positive and zero sequence currents,
LL currents that include the faulted phase, and the third signal which was previously proved to be dependent on the PVDG’s
is zero. However, the magnitude of superimposed LL currents reactive current level. That is why the relation between the
of the PVDG for the AG fault of Fig. 2, displayed in Fig. 6, are DEL1 curves of Fig. 7(b) is similar to the current magnitudes
identical since the zero sequence component is not present in of Fig. 4, and the method of [16] mistakes them for the DEL1s
the LL quantities and the negative sequence term is removed of a phases C to A to ground (CAG) or a balanced fault,
from the PVDG current by the feed-forward compensation. depending on when the decision is made. Even for the BCG
A three-phase fault would consequently be detected by [15]. fault of Fig. 5, where phase A has a lower current, 2.25DEL1A
Similar maloperation is observed for LL to ground (LLG) is larger than DEL1C , and the fault type is misidentified again.
faults.
The current magnitude-based method of [16] defines the IV. P ROPOSED S OLUTIONS
following delta signals for each phase current:
This section presents two new fault type classifiers that
 2
DEL = I − I−prf − I o  (1) work for not only the microgrids with PVDGs, but for any
 2 three-phase system. The relations between the angles of the
DEL1 = I − I−prf  . (2) sequence voltages for two SLG and LLG faults are first
The prf subscript denotes prefault quantities, and  is the investigated. Unlike the methods reviewed in the last sec-
respective phase. To detect an SLG fault, DEL of the faulted tion, which relied on superimposed quantities, the following
phase must be larger than 2.25 times DEL of each of the analysis focuses on total fault voltages, as the angles of the
remaining phases. For an LLG fault, 2.25 DEL of the unfaulted superimposed voltages will later be shown to be affected by
phase is lower than the DEL of the other phases. If DEL the PVDG’s PF over faults. As shown in Fig. 8, the sequence
signals do not identify an unbalanced fault, then DEL1 signals circuits calculated with respect to phase A are connected in
are used with the same rule to identify an LLG fault. If none series for an AG fault [19]. Therefore, Kirchhoff’s voltage
of these conditions are met, a balanced fault is deduced. law (KVL) for the circuit of Fig. 8 is
DEL and DEL1 for the PVDG current during the BCG fault Vf+ + Vf− + Vfo − 3Rf Ifo = 0 (3)
of Fig. 4 are shown in Fig. 7. The base to per-unitize the
currents is the rated current of the PVDG. The removal of in which the f subscript designates the fault location.
the zero-sequence term in (1) and the absence of the negative Neglecting Rf at this stage, the sum of the negative and zero
This article has been accepted for inclusion in a future issue of this journal. Content is final as presented, with the exception of pagination.

HOOSHYAR et al.: FAULT TYPE CLASSIFICATION IN MICROGRIDS INCLUDING PVDGs 5

(a)
Fig. 10. δ + and δ o versus fault resistance for an AG fault on bus 2 during
unity PF operation of PVDG.

(b)

Fig. 9. R14 voltage angles for the fault of Fig. 2. (a) Rf = 0 . Fig. 11. Sequence circuits connection for a BCG fault.
(b) Rf = 100 .

Rf for unity PF operation of the PVDG during the above AG


sequence voltages is out of phase from Vf+ in (3) by 180◦ . On fault. The saturation-like curve of δ + arises from the fact that
the other hand elevated levels of resistance to the ground result in lower zero
Vf− = −Ztot
− −
If (4) sequence current, thereby preventing the 3Rf Ifo term in (3)
from growing unboundedly large. Also, δ o is shown to be
Vfo = −Ztot
o o
If . (5) independent of Rf .
− o are the total impedances of the negative and As shown in Fig. 11, the sequence circuits calculated
Ztot and Ztot
zero sequence circuits, respectively. Since If− and Ifo are equal with respect to phase A are connected in parallel for BCG
for an AG fault, phase lead of the negative sequence volt- faults [19]. The resistance between the two phases at the fault
age over the zero sequence voltage, denoted by δ o , is similar location is denoted by 2Rph , the middle of which is grounded
− o , which is very through Rf . KVL for the left loop of Fig. 11 is
to the phase difference between Ztot and Ztot
small [23]. Consequently, δ and the phase lead of the negative
o  
sequence voltage over the positive sequence voltage, desig- Vf+ = Vf− + Rph If+ − If− . (6)
nated by δ + , are around 0◦ and 180◦ , respectively, for a bolted
AG fault. The phase differences between the sequence volt- Rph consists of mainly the arcing resistance, which is small
ages of R14 for the AG fault of Fig. 2, plotted in Fig. 9(a), for distribution systems and microgrids due to the short spac-
are in close proximity of 0◦ and 180◦ . Stronger sources in ing between the conductors. Thus, the effect of Rph will later
a system provide stiffer positive sequence voltages, as a result be analyzed by simulations and is neglected at this point. As
of which δ + and δ o equal these angles more precisely. a result, δ + becomes zero for a BCG fault. KVL for the right
In the presence of fault resistance, 3Rf Ifo leads the aligned loop of Fig. 11 is

Vf and Vfo by the zero sequence impedance angle. Thus, in  
order for Vf− + Vfo − 3Rf Ifo to be out-of-phase from Vf+ by Vf− = Vfo − 3Rf Ifo + Rph If− − Ifo . (7)
180◦ in (3), Vf− and Vfo advance in phase. The higher Rf is,
the larger δ + should be. Following the Rural Electrification Neglecting Rph , Vf− and Vfo are aligned for zero Rf , and
Administration’s guidelines, the North-American distribution δo is zero for a solid BCG fault as well. As an example, the
utilities traditionally consider 40  as the maximum resistance similar angles of R14 sequence voltages for the BCG fault of
between a downed conductor and the ground [10]. Larger fault Fig. 4 are displayed in Fig. 12(a).
resistances have also been reported in [24]. For Rf = 100 , The zero sequence current leads Vfo by Ztot o . Therefore,

Fig. 9(b) depicts the angles of R14 sequence voltages during in order for Vf − 3Rf If to be aligned with Vf− in (7) dur-
o o

the AG fault of Fig. 9(a). The high Rf makes the voltage drop ing resistive faults, Vfo advances in phase and raises δ o in the
at the PVDG terminal small, and the converter continues to negative direction. To study a severe condition, the fault of
operate at unity PF. δ + has reduced to −108.5◦ compared to Fig. 12(a) is resimulated with Rf = 100 , and the angles
Fig. 9(a). are shown in Fig. 12(b), where δ + remains unchanged, but δ o
To study extreme scenarios, significantly larger fault resis- has decreased by 77.6◦ compared to Fig. 12(a). Akin to SLG
tances were also tested. It was found that variations of faults, increasing Rf further for LLG faults does not alter the
Vf− and Vfo with respect to Rf do not follow a linear pattern, voltage angles. δ + and δ o of R14 for the above BCG fault,
and increasing Rf further has virtually no effect on the angles plotted versus Rf in Fig. 13, exhibit uniform curves for large
between the sequence voltages. Fig. 10 plots δ + and δ o versus fault resistances.
This article has been accepted for inclusion in a future issue of this journal. Content is final as presented, with the exception of pagination.

6 IEEE TRANSACTIONS ON SMART GRID

(a)

Fig. 15. Logic circuit of the voltage angle and magnitude-based classifier.

inside zone 1 during both AG and BCG faults. Meanwhile, the


(b) change in the magnitude of phase A voltage compared to that
for the other two phases is a characteristic difference between
Fig. 12. R14 voltage angles for the fault of Fig. 4. (a) Rf = 0 .
(b) Rf = 100 .
these two faults. This feature, along with the value of δ o , is
the basis for the proposed classification logic illustrated by
Fig. 15. Magnitudes of phase voltages are inspected using (8)
 
V = |V | − V−prf . (8)
To identify an AG fault, δ o must be in zone 1, and VA has
to be lower than both VB and VC . For a BCG fault, a zone 1
δ o is accompanied by a VA exceeding both VB and VC .
To differentiate between LL and LLG faults, |V o | is compared
with the unbalance threshold, UBth , which equals the %imbal-
Fig. 13. δ + and δ o versus fault resistance for a BCG fault on bus 2 during ance, defined by [25], before the fault plus a safety factor, say
unity PF operation of PVDG. 2% of the rated voltage. UBth is thus immune to load imbal-
ance and does not need to be set by the user. The %imbalance
portion of UBth is measured using two-cycle old memorized
voltage phasors. This two-cycle delay ensures that the %imbal-
ance is related to before the fault, since the length of the digital
filters used by commercial relays for phasor measurement is
normally less than 1.25 cycles. It should also be noted that the
memorized voltage is available in modern relays to accurately
identify the fault direction during three-phase faults. To iden-
tify an unbalanced fault, |V − | must be higher than UBth . Fault
Fig. 14. δ o zones for different fault types. classifiers of commercial relays raise a VOID flag if the fault
signals follow none of the known signatures [13]. The same
approach is adopted by the proposed method. The logic to
A. Voltage Angle and Magnitude-Based Classifier specify other asymmetrical faults is similar to the logic shown
for AG, BC, and BCG faults in Fig. 15.
Similar values are obtained for δ o during other fault types
if the sequence components are calculated with respect to the
faulted phase for SLG faults and the unfaulted phase for LLG B. Voltage Angle-Based Classifier
faults. As a result, when phase A is the reference phase, δ o lies The values of δ + for other fault types are similar to those
in the vicinity of 240◦ and 120◦ during BG and CG faults, of the previously discussed AG and BCG faults if sequence
respectively. For ABG and CAG faults, δ o is close to 120◦ and components are calculated with respect to the faulted phase for
240◦ , respectively. Hence, three zones, each corresponding to SLG faults and the unfaulted phase for LLG faults. Therefore,
one SLG and one LLG fault, are defined around the mentioned when phase A is the reference phase, δ + is close to 120◦ and
angles for δ o in Fig. 14. Given that Rf makes the zero sequence 240◦ for CAG and ABG faults, respectively. For BG and CG
voltage lead the negative sequence voltage during LLG faults, faults, δ + lies in the neighborhood of 300◦ and 60◦ , respec-
the three zones of δ o have been shifted backward from the tively. Fig. 16 defines appropriate zones for δ + around these
symmetrical position around the above angles by 30◦ . angles. The δ + zones for SLG faults are shifted forward from
A key feature of δ o zones in Fig. 14 is that the two the symmetrical position about the respective angles to take
faults associated with each zone include opposing phases. the effect of fault resistance into account. Rf does not affect
Classification of such faults can effectively be carried out by δ + during LLG faults, so the zones in Fig. 16 are symmetrical
means of phase voltage magnitudes. For instance, δ o is situated about their corresponding angles.
This article has been accepted for inclusion in a future issue of this journal. Content is final as presented, with the exception of pagination.

HOOSHYAR et al.: FAULT TYPE CLASSIFICATION IN MICROGRIDS INCLUDING PVDGs 7

TABLE I
R41 M EASUREMENTS FOR B US 5 FAULTS D URING G RID -C ONNECTED
M ODE W HEN PVDG S PF IS U NITY

Fig. 16. δ + zones for SLG and LLG faults.

A. Grid-Connected Mode
Fig. 17. Logic circuit of the voltage angle-based classifier.
Table I reports the angles of the sequence voltages and the
changes in the phase voltage magnitudes for R41 during differ-
Positions of δ o and δ + inside the zones in ent SLG and LLG faults at bus 5 of Fig. 1. The microgrid is in
Figs. 14 and 16 are the basis for the classification logic the grid-connected mode, and the PVDG operates at unity PF.
proposed in Fig. 17. No δ + and δ o pair follows more than one It was found that Rf = 50  sufficed to observe the maximum
of the patterns in Figs. 14 and 16 so this classifier can reliably effect of fault resistance on the voltage angles, a conclusion
identify the fault type. As in Fig. 15, |V − | and |V o | are used in line with the findings from Figs. 10 and 13. LL faults are
to determine balanced faults and discriminate between LL excluded because they result in almost the same δ + and voltage
and LLG faults. The logic to detect other asymmetrical faults changes that are given for LLG faults. The results in Table I
is similar to the logic shown for AG, BC, and BCG faults in identify the fault type correctly with a high margin between
Fig. 17. δ + and δ o and their corresponding zone boundaries. For exam-
Unlike the classifier proposed in the last section, this new ple, for the AG fault shown in the second row, δ + and δ o
method exploits the angle of the positive sequence voltage, maintain distances of 23.4◦ and 28.3◦ from the boundaries of
which varies along the path from the fault location to the relay the associated zone boundaries.
due to load flow. Phase difference between positive sequence
voltages along a feeder is small, as its large amounts harbor B. Autonomous Mode
the risk of instability. For distribution systems, in particular,
Similar correct classification is observed for the bus 2 faults
voltage phase differences along feeders are in the order of
of Table II, which displays the angles and magnitudes of
a fraction of a degree, as the load levels are not high [26]. Even
R14 voltages during the islanded mode of the system in Fig. 1.
for transmission systems with larger loads and phase varia-
The PVDG complies with the reactive current requirements
tions, enough allowance has been made through sufficiently
of [18] during the faults. Sustained voltages below 90% are
large security margins in the δ + zones of Fig. 16.
categorized as undervoltage disturbance by [25]. Since the
SDG at bus 3 is a weak source, the voltage level before the
V. P ERFORMANCE E VALUATION fault is 86.6% of the rated value. Although such a weak volt-
The proposed methods were tested for a variety of condi- age support is not practical, it is considered to study the worst
tions in the microgrid of Fig. 1 as well as other benchmark case scenario. As a sample case in Table II, the angles for the
distribution systems. The studies included various fault and BCG fault with Rf = 50  and Rph = 0  are displayed in
relay locations, fault resistances and PVDG’s PF, and were Fig. 18. δ + and δ o equal 0.9◦ and −67.6◦ , respectively, iden-
carried out for both autonomous and grid-connected modes. tifying a BCG fault. Also, VB and VC are substantially
The fault type could be identified within a cycle after fault lower than VA . Similar to the cases studied in Section III,
inception. This speed is enough even for instantaneous over- current-based methods malfunction for most of the cases in
current relays. The angle and magnitude-based classifier can Table II.
make a decision in half a cycle if the system is not severely Some relays that specify the fault type using the angles
unbalanced. of the superimposed currents switch to the angles of the
This article has been accepted for inclusion in a future issue of this journal. Content is final as presented, with the exception of pagination.

8 IEEE TRANSACTIONS ON SMART GRID

TABLE II
R14 M EASUREMENTS FOR AUTONOMOUS M ODE W HEN PVDG
G ENERATES R EACTIVE C URRENT

(a)

(b)

Fig. 19. Angles of R14 superimposed voltages during the fault of Fig. 18.
(a) PVDG generates reactive current. (b) PVDG operates at unity PF.

Fig. 20. R14 voltage angles for the fault of Fig. 18 when the PVDG operates
at unity PF.

Fig. 18. R14 voltage angles for the autonomous microgrid when the PVDG TABLE III
generates reactive current during a BCG fault at bus 2 with Rf = 50 . L OADS OF THE U NBALANCED M ICROGRID IN MW AND MVAR

superimposed voltages if the current-based approach does not


recognize any of the known fault patterns [13]. The classi-
fication criterion for the superimposed voltages is the same
as that of the currents. The following studies the superim-
posed voltage-based approach. Take, for instance, the angles
of the superimposed sequence voltages for the above BCG
yield δ + = −4.2◦ and δ o = −68.2◦ , which are similar to
fault, plotted in Fig. 19(a). V − leads V + by 120.5◦ ;
those of Fig. 20 and inside their respective zones for a BCG
the signature of a BG fault in [13]. In addition, V − −
fault. Also, VA , VB , and VC are −1.999, −14.335, and
V o = −67.6◦ , which is closer to the sector of ABG
−12.943 kV; i.e., proposed methods select the faulted phases
and CG faults in [13]. This method’s failure stems from the
correctly.
fact that the angles of the superimposed voltages are deter-
mined by the superimposed PVDG currents, whose angles
differ from those of conventional sources, and are regulated C. Unbalanced Microgrid
by the PVDG control system. Thus, changing the reactive cur- Microgrids might not be perfectly balanced during normal
rent of the PVDG alters the phase difference between the operation. To verify the performance of the proposed classi-
superimposed voltages. If the PVDG operates at unity PF, fiers for an unbalanced system, the loads at different buses of
the angles of the superimposed voltages change to the curves the microgrid in Fig. 1 were changed to the values displayed
of Fig. 19(b). The 170.1◦ phase difference between V − in Table III. The resultant voltage and current imbalances at
and V + indicates a BCG fault in [13], whereas V − lags R14 location for the autonomous mode exceed 6% and 80%,
V o by 68.2◦ , which is closer to the sector of BG and CAG respectively, which are categorized as severe imbalance [25].
faults in [13]. The weak SDG, again, results in low prefault phase voltages,
Proper operation of the proposed method, however, equal to 26.590, 24.174, and 24.483 kV in phases A, B, and C,
is unaffected by changes in the PVDG’s reactive cur- respectively. The angles and magnitudes of R14 voltages for
rent level. The angles of the sequence voltages for the bus 5 faults when the PVDG meets the reactive current require-
above fault during unity PF operation, shown in Fig. 20, ments of [18] are displayed in Table IV. These results indicate
This article has been accepted for inclusion in a future issue of this journal. Content is final as presented, with the exception of pagination.

HOOSHYAR et al.: FAULT TYPE CLASSIFICATION IN MICROGRIDS INCLUDING PVDGs 9

TABLE IV
R14 M EASUREMENTS FOR AUTONOMOUS M ODE OF U NBALANCED
M ICROGRID W HEN PVDG G ENERATES R EACTIVE C URRENT

Fig. 23. Layout of the IEEE 34 bus system with a PVDG at bus 848 [27].

TABLE V
R ESULTS O BTAINED FOR IEEE 34 B US T EST S YSTEM

Fig. 21. R14 voltage angles for the autonomous unbalanced microgrid when
the PVDG generates reactive current during a bolted AG fault at bus 5.

Fig. 22. Angles of R14 superimposed voltages during the fault of Fig. 21.
IEEE 34 bus system, displayed in Fig. 23 [27]. Single-phase
laterals were modeled by equivalent loads so as to simulate
the system by the educational version of PSCAD/-EMTDC.
accurate operation of the proposed methods for highly unbal-
The PVDG generates reactive power during faults, propor-
anced systems. As an example, the angles of the sequence
tional to the voltage drop. The operations of several relays
voltages during the bolted AG fault of Table IV are plotted in
were inspected for different faults throughout the system.
Fig. 21.
Table V reports the voltage angles and magnitudes of the
The failure of superimposed voltages to classify faults was
relays at buses 808 and 842 for faults at buses 816 and 832,
earlier shown for a high impedance fault. Similar inaccu-
i.e., relay measurements close to both the PVDG and the
racy is observed for faults with lower resistances as well.
main substation are covered. The rated voltage at the loca-
For example, the angles of the superimposed voltages for the
tion of these two relays is 24.9 kV. A 50  ground resistance
above AG fault are shown in Fig. 22. The 73.1◦ difference
has been considered for all of the faults in Table V. The
between V − and V + signifies a CAG fault and leads
LLG faults also include a 10  resistance between the faulty
to misclassification by [13].
phases. Using the proposed classifiers, the values presented
in Table V can correctly specify the fault type. As a repre-
D. Further Results sentative case, the angles of the sequence voltages and the
The performance of the proposed fault type classifiers was magnitudes of the phase voltages of the relay at bus 808 for
also examined for two other test systems with renewable-based a CG fault at bus 832 are plotted in Fig. 24. V − leads V o by
DGs. A PVDG rated at 1 MW was added to bus 848 of the 93.2◦ , situating δ o in zone 3 of Fig. 14. In addition, phase C
This article has been accepted for inclusion in a future issue of this journal. Content is final as presented, with the exception of pagination.

10 IEEE TRANSACTIONS ON SMART GRID

(a) (a)

(b) (b)

Fig. 24. Measurements of the relay at bus 808 of the IEEE 34 bus system Fig. 26. Measurements of the relay at bus 8 of the CIGRE MV distribution
for a CG fault at bus 832. (a) Sequence voltage angle. (b) Phase voltage system for an ABG fault at bus 3. (a) Sequence voltage angle. (b) Phase
magnitude. voltage magnitude.

(a)

Fig. 25. Layout of the CIGRE MV distribution system with three DGs [28].

(b)
exhibits the largest voltage drop among the three phases. Fig. 27. Measurements of the relay at bus 6 of the CIGRE MV distribution
Thus, the voltage angle and magnitude-based classifier selects system for a CG fault at bus 10. (a) Sequence voltage angle. (b) Phase voltage
phase C as the only faulty phase. On the other hand, the 93.2◦ magnitude.
phase lead of V − over V o is accompanied by δ + = 82.5◦ ,
and the voltage angle-based classifier detects a CG fault
as well. As an example for the relays in the proximity of the PVDG,
The proposed classifiers were also tested for the Fig. 26 shows the angles and magnitudes of the voltages at
North-American version of the CIGRE medium-voltage (MV) bus 8 for an ABG fault at bus 3 during the grid-connected oper-
distribution system rated at 12.47 kV [28]. As depicted in ation of the system when switches S1–S3 are open. V − leads
Fig. 25, three DGs are connected to the system: 1) a 2 MW V o by 115.7◦ , so δ o is in zone 3 of Fig. 14. Phases A and B
PVDG at bus 8; 2) a 2.5 MW type I wind DG at bus 6; also have the largest voltage drops. Hence, the voltage angle
and 3) an 8 MW SDG at bus 4. The latter is connected to and magnitude-based classifier detects an ABG fault. The
the system during islanded operation. Switches S1–S3 can be voltage angle-based classifier also selects the faulty phases cor-
closed to study a meshed distribution system. The PVDG oper- rectly since the zone 3 δ o is accompanied by δ + = −120.8◦ ,
ates at unity PF during faults, and the wind DG is equipped located in zone 1 of Fig. 16. For the relay next to the wind-
with PF correction capacitors to prevent reactive power con- based DG at bus 6, Fig. 27 plots the voltage angles and
sumption by the induction generators. Extensive simulations magnitudes for a CG fault at bus 10 during islanded oper-
were carried out for a variety of conditions. Tables VI and VII ation when the switches are closed. V − leads V o and V + by
report the voltage angles and magnitudes of the relays at 109.7◦ and 62.3◦ , resulting in δ o and δ + located in zone 3 of
buses 6 and 8 during solid faults at buses 3 and 10 for the grid- Figs. 14 and 16, respectively. Furthermore, phase C exhibits
connected and islanded operation and both open and closed the largest voltage drop. Therefore, both methods determine
status of switches S1–S3. a CG fault.
This article has been accepted for inclusion in a future issue of this journal. Content is final as presented, with the exception of pagination.

HOOSHYAR et al.: FAULT TYPE CLASSIFICATION IN MICROGRIDS INCLUDING PVDGs 11

TABLE VI
R ESULTS O BTAINED FOR FAULTS AT B US 3 OF CIGRE MV D ISTRIBUTION T EST S YSTEM

TABLE VII
R ESULTS O BTAINED FOR FAULTS AT B US 10 OF CIGRE MV D ISTRIBUTION T EST S YSTEM

VI. C ONCLUSION microgrids with PVDG. Distinctive zones were defined for the
The existing fault type classifiers that operate based on the phase difference between the total sequence voltages. The first
angles of the superimposed sequence currents or the mag- proposed classifier relied on the fact that each zone defined
nitudes of phase/line currents were shown to malfunction in for δ o corresponded to two SLG and LLG faults that included
This article has been accepted for inclusion in a future issue of this journal. Content is final as presented, with the exception of pagination.

12 IEEE TRANSACTIONS ON SMART GRID

opposing phases. The voltage magnitude was thus exploited [23] G. Ziegler, Numerical Distance Protection: Principles and Applications,
to differentiate between the two possible faults. The unique 4th ed. Erlangen, Germany: Publicis, 2011, ch. 3.
[24] P. Maezono et al., “Very high-resistance fault on a 525 kV transmis-
pair of δ o and δ + zones associated with each fault type sion line—Case study,” in Proc. 62nd Annu. Conf. Protect. Relay Eng.,
was utilized to devise the second classification logic. Correct Austin, TX, USA, Mar. 2009, pp. 322–332.
operation of the proposed methods for the grid-connected [25] IEEE Recommended Practice for Monitoring Electric Power Quality,
IEEE Standard 1159, 2009.
and autonomous modes of a microgrid, together with their [26] A. Borghetti et al., “Synchronized phasors monitoring during the island-
robustness against various PVDG control strategies, fault resis- ing maneuver of an active distribution network,” IEEE Trans. Smart
tance, system imbalance, and load levels were validated by Grid, vol. 2, no. 1, pp. 82–91, Mar. 2011.
[27] IEEE PES Distribution Systems Subcommittee’s Distribution Test
simulation studies. Feeder Working Group. [Online]. Available: http://ewh.ieee.org/soc/pes/
dsacom/testfeeders/index.html
R EFERENCES [28] E. Abbasi et al., “Benchmark systems for network integration of
renewable and distributed energy resources,” CIGRE, Paris, France,
[1] A. Oudalov, T. Degner, F. Overbeeke, and J. Yarza, “Microgrid Tech. Rep. C6.04.02, Aug. 2008.
protection,” in Microgrids: Architectures and Control, 1st ed. Hoboken,
NJ, USA: Wiley, 2014, pp. 117–164.
[2] H. Zeineldin et al., “A protection coordination index for evaluating
distributed generation impacts on protection for meshed distribution
systems,” IEEE Trans. Smart Grid, vol. 4, no. 3, pp. 1523–1532,
Sep. 2013.
[3] L. Che, M. Khodayar, and M. Shahidehpour, “Adaptive protection
system for microgrids: Protection practices of a functional microgrid
system,” IEEE Electrific. Mag., vol. 2, no. 1, pp. 66–80, Mar. 2014. Ali Hooshyar received the B.Sc. degree in elec-
[4] E. Casagrande, W. L. Woon, H. H. Zeineldin, and D. Svetinovic, “A dif- trical engineering from the Isfahan University of
ferential sequence component protection scheme for microgrids with Technology, Isfahan, Iran, in 2006; the M.Sc. degree
inverter-based distributed generators,” IEEE Trans. Smart Grid, vol. 5, in electrical engineering from the University of
no. 1, pp. 29–37, Jan. 2014. Tehran, Tehran, Iran, in 2009; and the Ph.D. degree
[5] I. Xyngi and M. Popov, “An intelligent algorithm for the protection in electrical engineering from the University of
of smart power systems,” IEEE Trans. Smart Grid, vol. 4, no. 3, Waterloo, Waterloo, ON, Canada, in 2014.
pp. 1541–1548, Sep. 2013. He was a Postdoctoral Fellow with the Centre for
[6] J. Agüero, J. Wang, and J. Burke, “Improving the reliability of power Applied Power Electronics, University of Toronto,
distribution systems through single-phase tripping,” in Proc. IEEE PES Toronto, ON. He is currently an Assistant Professor
Trans. Distrib. Conf. Exp., New Orleans, LA, USA, Apr. 2010, pp. 1–7. with the Department of Electrical Engineering and
[7] T. Fahey and N. Burbure, “Single-phase tripping,” IEEE Power Energy Computer Science, York University, Toronto, in 2015. His current research
Mag., vol. 6, no. 2, pp. 46–52, Mar. 2008. interests include protection and control of renewable energy systems and
[8] G. Hataway and R. Moxley, “Distribution single-phase tripping and smart grids.
reclosing,” in Proc. Protect. Autom. Control World, 2009, pp. 28–33.
[9] R. Cheney, J. Thorne, and G. Hataway, “Distribution single-phase trip-
ping and reclosing: Overcoming obstacles with programmable recloser
controls,” in Proc. 62nd Annu. Conf. Protect. Relay Eng., Austin, TX,
USA, 2009, pp. 214–223.
[10] T. A. Short, Electric Power Distribution Handbook, 2nd ed. Boca Raton,
FL, USA: CRC Press, 2014, chs. 8–9.
[11] M. Hori, Y. Saita, and M. Inukai, “Short-circuit distance relay,” Ehab F. El-Saadany (SM’05) was born in Cairo,
U.S. Patent 2011 014 944 8 A1, Jun. 23, 2011. Egypt, in 1964. He received the B.Sc. and M.Sc.
[12] J. Roberts and E. Schweitzer, “Fault identification system for use in degrees from the Ain Shams University, Cairo, in
protective relays for power transmission lines,” U.S. Patent 5 515 227, 1986 and 1990, respectively, and the Ph.D. degree
May 7, 1996. from the University of Waterloo, Waterloo, ON,
[13] D90Plus Line Distance Protection System, GE, Markham, ON, Canada, Canada, in 1998, all in electrical engineering.
Mar. 2012. [Online]. Available: www.gedigitalenergy.com/products/ He is currently a Professor with the Department
manuals/d90plus/gek-113240b.pdf of Electrical and Computer Engineering, University
[14] M. Mynam and Y. Gong, “Fault-type identification for electric power of Waterloo. His current research interests include
delivery systems,” U.S. Patent 2013 008 823 9 A1, Apr. 11, 2013. smart grids operation and control, power quality, dis-
[15] Technical Manual: MiCOMho P446—Fast Multifunction Distance tributed generation, power electronics, digital signal
Protection Relay, Alstom, Stafford, U.K., 2011. [Online]. Available: processing applications to power systems, and mechatronics.
ftp://ftp.alstom.com/Alstom_Manuals/P446_EN_TM_E.pdf
[16] L. Yang, “Fault type classification algorithm,” U.S. Patent 5 783 946,
Jul. 21, 1998.
[17] J. F. Conroy and R. Watson, “Low-voltage ride-through of a full con-
verter wind turbine with permanent magnet generator,” IET Renew.
Power Gener., vol. 1, no. 3, pp. 182–189, Sep. 2007.
[18] M. Tsili and S. Papathanassiou, “A review of grid code technical
requirements for wind farms,” IET Renew. Power Gener., vol. 3, no. 3,
pp. 308–332, Sep. 2009. Majid Sanaye-Pasand (M’98–SM’05) received the
[19] P. M. Anderson, Analysis of Faulted Power Systems, Hoboken, NJ, USA: B.Sc. degree in electrical engineering from the
Wiley, 1995, chs. 3, 6. University of Tehran, Tehran, Iran, and the M.Sc.
[20] J. Rocabert, A. Luna, F. Blaabjerg, and P. Rodriguez, “Control of power and Ph.D. degrees in electrical engineering from the
converters in AC microgrids,” IEEE Trans. Power Electron., vol. 27, University of Calgary, Calgary, AB, Canada, in 1994
no. 11, pp. 4734–4749, Nov. 2012. and 1998, respectively.
[21] A. Yazdani and R. Iravani, Voltage-Sourced Converters in Power He is currently a Professor with the School of
Systems: Modeling, Control, and Applications. Hoboken, NJ, USA: Electrical and Computer Engineering, University of
Wiley, 2010, chs. 7–8. Tehran. His current research interests include power
[22] T. Adu, “An accurate fault classification technique for power sys- system protection, control, and transients.
tem monitoring devices,” IEEE Trans. Power Del., vol. 17, no. 3, Dr. Sanaye-Pasand is an Editor of the IEEE
pp. 684–690, Nov. 2002. T RANSACTIONS ON P OWER D ELIVERY.

You might also like