Professional Documents
Culture Documents
Abstract—Protective devices of smart and fault-resilient micro- which account for the majority of faults. On the other hand,
grids are not expected to trip the healthy phases during unbal- single-phase protective devices are increasingly installed in
anced short-circuits. Thus, some utilities and relay manufacturers modern distribution systems. That is why several proposals
have started contemplating single- and double-pole tripping for
distribution systems. Selective phase tripping demands fault type have been put forward by the industrial community to apply
classification. This paper reveals that existing industrial methods selective phase tripping in distribution systems [6], [7]. With
misidentify the fault type in microgrids that include photovoltaic the prospect of substantial improvement to system reliability,
distributed generations (DGs). Due to interface similarities, this this plan has already been put into practice by some utilities
paper pertains to systems with type IV wind DGs as well. Two and relay manufacturers [8]. The Alabama Power Company is
new classifiers proposed in this paper determine the fault type
accurately for not only microgrids with photovoltaic DGs, but for a case in point [9].
any three-phase system. With low computational burden, they Sustained unbalanced operation of a microgrid during per-
require only local information and operate successfully for high manent faults needs to be investigated for realizing any
resistance faults. Furthermore, these techniques are not affected selective phase tripping scheme. For instance, the capacity of
by the system imbalance and different DG power factors over the neutral current return path has to be taken into account
disturbances.
for selective phase tripping of four wire systems, and unbal-
Index Terms—Fault resiliency, fault type classification, micro- anced operation during permanent faults may be permitted
grid protection, photovoltaic distributed generation (PVDG). only when the neutral current is limited to a certain level.
However, 50%–80% of actual distribution system faults are
I. I NTRODUCTION temporary [10], for which the relays reclose the breakers after
TEMMING from the different operation modes and a short period and overheating of neutral conductors is not
S the diversity of generation technologies, the protection
of a microgrid can be challenging [1]. Traditional relaying
normally a concern.
On the other hand, the internal protection of most of the
schemes for distribution systems may fail to protect a micro- existing PVDG inverters trip during unbalanced conditions in
grid, particularly if converter-interfaced renewable distributed order to meet the current islanding protection requirements.
generations (DGs), such as photovoltaic DGs (PVDGs), are However, if a fault-resilient microgrid with high renewable
involved, as is often the case. PVDGs have limited fault energy penetration and the capability of islanded operation
currents to which the overcurrent elements are normally is to materialize, then PVDGs must ride through unbalanced
insensitive [2]. Various publications offer protection solutions faults and let the relays protect the system, i.e., similar
for microgrids by means of adaptive and communication- to renewable sources connected to transmission systems. If
assisted techniques [3]–[5]. Despite their successful fault PVDGs are disconnected from the microgrid due to unbal-
detection, these methods do not provide information on the anced voltages, then any asymmetrical fault (irrespective of its
fault type. duration and location) may potentially result in total shutdown
A smart and resilient microgrid should maintain the oper- of an islanded microgrid that includes large PVDGs.
ation of sound phases during the unbalanced short-circuits, Selective phase tripping requires fault type classification by
the microgrid protection system. In transmission system relays,
Manuscript received December 14, 2014; revised January 3, 2015 and fault type classification is an imperative subroutine, the out-
April 24, 2015; accepted June 21, 2015. Paper no. TSG-01220-2014.
A. Hooshyar is with the Electrical Engineering and Computer Science put of which is needed for several functions, e.g., single-pole
Department, York University, Toronto, ON M3J 1P3, Canada (e-mail: autoreclosure and blocking of ground distance elements dur-
hooshyar@eecs.yorku.ca). ing phase faults. An early fault type identification method still
E. F. El-Saadany is with the Department of Electrical and Computer
Engineering, University of Waterloo, Waterloo, ON N2L 3G1, Canada (e-mail: used by some manufacturers is based on the magnitudes of
ehab@uwaterloo.ca). the impedances measured for different fault loops [11]. The
M. Sanaye-Pasand is with the School of Electrical and Computer inaccuracy of this approach for short lines, among other short-
Engineering, College of Engineering, University of Tehran,
Tehran 14395-515, Iran (e-mail: msanaye@ut.ac.ir), and also with the comings, led to the development of several classifiers exploit-
Control and Intelligent Processing Center of Excellence, College of ing the phase differences between the superimposed sequence
Engineering, University of Tehran, Tehran 14395-515, Iran. currents [12]–[14], which have been proven effective for con-
Color versions of one or more of the figures in this paper are available
online at http://ieeexplore.ieee.org. ventional power systems. Some of these methods, however,
Digital Object Identifier 10.1109/TSG.2015.2451675 need high-bandwidth communication infrastructure, which is
1949-3053 c 2015 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission.
See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for inclusion in a future issue of this journal. Content is final as presented, with the exception of pagination.
(a)
Fig. 1. Single line diagram of the test microgrid.
(a)
Fig. 3. Angles of R14 superimposed sequence currents for the fault of Fig. 2.
Fig. 2(b) shows this voltage for the above fault after being
passed through a low-pass filter to eliminate the switching
pulses.
This disturbance-free voltage leads to converter currents
with practically zero negative and zero sequence components,
denoted by I − and I o . Moreover, the positive sequence cur- (b)
rent, I + , increases by only 20% following the fault inception,
Fig. 4. PVDG current at the grid side of the transformer during a BCG
as the PVDG control system limits the converter overcurrents fault when the PVDGs PF is unity. (a) Instantaneous current. (b) Angle of
to protect the switches. sequence components.
Since the currents injected by the PVDG do not follow the
regular pattern of AG fault currents, the angles of the superim-
posed sequence currents of R14, shown in Fig. 3, do not select
the faulted phase correctly. The sign in the figure designates
the superimposed signals. I − leads I + by 128.0◦ , which
falls under the sector defined for phase B to ground (BG)
faults in [13]. Meanwhile, I o lags I − by 110.6◦ , indicat-
ing a phase C to ground (CG) or phases A to BG (ABG)
fault. Hence, the method of [13] is unable to identify the fault (a)
type. The same scenario applies to other current angle-based
classifiers as well.
(a)
Fig. 6. Superimposed LL currents of the PVDG for the fault of Fig. 2.
(a)
Fig. 10. δ + and δ o versus fault resistance for an AG fault on bus 2 during
unity PF operation of PVDG.
(b)
Fig. 9. R14 voltage angles for the fault of Fig. 2. (a) Rf = 0 . Fig. 11. Sequence circuits connection for a BCG fault.
(b) Rf = 100 .
Fig. 9(b) depicts the angles of R14 sequence voltages during in order for Vf − 3Rf If to be aligned with Vf− in (7) dur-
o o
the AG fault of Fig. 9(a). The high Rf makes the voltage drop ing resistive faults, Vfo advances in phase and raises δ o in the
at the PVDG terminal small, and the converter continues to negative direction. To study a severe condition, the fault of
operate at unity PF. δ + has reduced to −108.5◦ compared to Fig. 12(a) is resimulated with Rf = 100 , and the angles
Fig. 9(a). are shown in Fig. 12(b), where δ + remains unchanged, but δ o
To study extreme scenarios, significantly larger fault resis- has decreased by 77.6◦ compared to Fig. 12(a). Akin to SLG
tances were also tested. It was found that variations of faults, increasing Rf further for LLG faults does not alter the
Vf− and Vfo with respect to Rf do not follow a linear pattern, voltage angles. δ + and δ o of R14 for the above BCG fault,
and increasing Rf further has virtually no effect on the angles plotted versus Rf in Fig. 13, exhibit uniform curves for large
between the sequence voltages. Fig. 10 plots δ + and δ o versus fault resistances.
This article has been accepted for inclusion in a future issue of this journal. Content is final as presented, with the exception of pagination.
(a)
Fig. 15. Logic circuit of the voltage angle and magnitude-based classifier.
TABLE I
R41 M EASUREMENTS FOR B US 5 FAULTS D URING G RID -C ONNECTED
M ODE W HEN PVDG S PF IS U NITY
A. Grid-Connected Mode
Fig. 17. Logic circuit of the voltage angle-based classifier.
Table I reports the angles of the sequence voltages and the
changes in the phase voltage magnitudes for R41 during differ-
Positions of δ o and δ + inside the zones in ent SLG and LLG faults at bus 5 of Fig. 1. The microgrid is in
Figs. 14 and 16 are the basis for the classification logic the grid-connected mode, and the PVDG operates at unity PF.
proposed in Fig. 17. No δ + and δ o pair follows more than one It was found that Rf = 50 sufficed to observe the maximum
of the patterns in Figs. 14 and 16 so this classifier can reliably effect of fault resistance on the voltage angles, a conclusion
identify the fault type. As in Fig. 15, |V − | and |V o | are used in line with the findings from Figs. 10 and 13. LL faults are
to determine balanced faults and discriminate between LL excluded because they result in almost the same δ + and voltage
and LLG faults. The logic to detect other asymmetrical faults changes that are given for LLG faults. The results in Table I
is similar to the logic shown for AG, BC, and BCG faults in identify the fault type correctly with a high margin between
Fig. 17. δ + and δ o and their corresponding zone boundaries. For exam-
Unlike the classifier proposed in the last section, this new ple, for the AG fault shown in the second row, δ + and δ o
method exploits the angle of the positive sequence voltage, maintain distances of 23.4◦ and 28.3◦ from the boundaries of
which varies along the path from the fault location to the relay the associated zone boundaries.
due to load flow. Phase difference between positive sequence
voltages along a feeder is small, as its large amounts harbor B. Autonomous Mode
the risk of instability. For distribution systems, in particular,
Similar correct classification is observed for the bus 2 faults
voltage phase differences along feeders are in the order of
of Table II, which displays the angles and magnitudes of
a fraction of a degree, as the load levels are not high [26]. Even
R14 voltages during the islanded mode of the system in Fig. 1.
for transmission systems with larger loads and phase varia-
The PVDG complies with the reactive current requirements
tions, enough allowance has been made through sufficiently
of [18] during the faults. Sustained voltages below 90% are
large security margins in the δ + zones of Fig. 16.
categorized as undervoltage disturbance by [25]. Since the
SDG at bus 3 is a weak source, the voltage level before the
V. P ERFORMANCE E VALUATION fault is 86.6% of the rated value. Although such a weak volt-
The proposed methods were tested for a variety of condi- age support is not practical, it is considered to study the worst
tions in the microgrid of Fig. 1 as well as other benchmark case scenario. As a sample case in Table II, the angles for the
distribution systems. The studies included various fault and BCG fault with Rf = 50 and Rph = 0 are displayed in
relay locations, fault resistances and PVDG’s PF, and were Fig. 18. δ + and δ o equal 0.9◦ and −67.6◦ , respectively, iden-
carried out for both autonomous and grid-connected modes. tifying a BCG fault. Also, VB and VC are substantially
The fault type could be identified within a cycle after fault lower than VA . Similar to the cases studied in Section III,
inception. This speed is enough even for instantaneous over- current-based methods malfunction for most of the cases in
current relays. The angle and magnitude-based classifier can Table II.
make a decision in half a cycle if the system is not severely Some relays that specify the fault type using the angles
unbalanced. of the superimposed currents switch to the angles of the
This article has been accepted for inclusion in a future issue of this journal. Content is final as presented, with the exception of pagination.
TABLE II
R14 M EASUREMENTS FOR AUTONOMOUS M ODE W HEN PVDG
G ENERATES R EACTIVE C URRENT
(a)
(b)
Fig. 19. Angles of R14 superimposed voltages during the fault of Fig. 18.
(a) PVDG generates reactive current. (b) PVDG operates at unity PF.
Fig. 20. R14 voltage angles for the fault of Fig. 18 when the PVDG operates
at unity PF.
Fig. 18. R14 voltage angles for the autonomous microgrid when the PVDG TABLE III
generates reactive current during a BCG fault at bus 2 with Rf = 50 . L OADS OF THE U NBALANCED M ICROGRID IN MW AND MVAR
TABLE IV
R14 M EASUREMENTS FOR AUTONOMOUS M ODE OF U NBALANCED
M ICROGRID W HEN PVDG G ENERATES R EACTIVE C URRENT
Fig. 23. Layout of the IEEE 34 bus system with a PVDG at bus 848 [27].
TABLE V
R ESULTS O BTAINED FOR IEEE 34 B US T EST S YSTEM
Fig. 21. R14 voltage angles for the autonomous unbalanced microgrid when
the PVDG generates reactive current during a bolted AG fault at bus 5.
Fig. 22. Angles of R14 superimposed voltages during the fault of Fig. 21.
IEEE 34 bus system, displayed in Fig. 23 [27]. Single-phase
laterals were modeled by equivalent loads so as to simulate
the system by the educational version of PSCAD/-EMTDC.
accurate operation of the proposed methods for highly unbal-
The PVDG generates reactive power during faults, propor-
anced systems. As an example, the angles of the sequence
tional to the voltage drop. The operations of several relays
voltages during the bolted AG fault of Table IV are plotted in
were inspected for different faults throughout the system.
Fig. 21.
Table V reports the voltage angles and magnitudes of the
The failure of superimposed voltages to classify faults was
relays at buses 808 and 842 for faults at buses 816 and 832,
earlier shown for a high impedance fault. Similar inaccu-
i.e., relay measurements close to both the PVDG and the
racy is observed for faults with lower resistances as well.
main substation are covered. The rated voltage at the loca-
For example, the angles of the superimposed voltages for the
tion of these two relays is 24.9 kV. A 50 ground resistance
above AG fault are shown in Fig. 22. The 73.1◦ difference
has been considered for all of the faults in Table V. The
between V − and V + signifies a CAG fault and leads
LLG faults also include a 10 resistance between the faulty
to misclassification by [13].
phases. Using the proposed classifiers, the values presented
in Table V can correctly specify the fault type. As a repre-
D. Further Results sentative case, the angles of the sequence voltages and the
The performance of the proposed fault type classifiers was magnitudes of the phase voltages of the relay at bus 808 for
also examined for two other test systems with renewable-based a CG fault at bus 832 are plotted in Fig. 24. V − leads V o by
DGs. A PVDG rated at 1 MW was added to bus 848 of the 93.2◦ , situating δ o in zone 3 of Fig. 14. In addition, phase C
This article has been accepted for inclusion in a future issue of this journal. Content is final as presented, with the exception of pagination.
(a) (a)
(b) (b)
Fig. 24. Measurements of the relay at bus 808 of the IEEE 34 bus system Fig. 26. Measurements of the relay at bus 8 of the CIGRE MV distribution
for a CG fault at bus 832. (a) Sequence voltage angle. (b) Phase voltage system for an ABG fault at bus 3. (a) Sequence voltage angle. (b) Phase
magnitude. voltage magnitude.
(a)
Fig. 25. Layout of the CIGRE MV distribution system with three DGs [28].
(b)
exhibits the largest voltage drop among the three phases. Fig. 27. Measurements of the relay at bus 6 of the CIGRE MV distribution
Thus, the voltage angle and magnitude-based classifier selects system for a CG fault at bus 10. (a) Sequence voltage angle. (b) Phase voltage
phase C as the only faulty phase. On the other hand, the 93.2◦ magnitude.
phase lead of V − over V o is accompanied by δ + = 82.5◦ ,
and the voltage angle-based classifier detects a CG fault
as well. As an example for the relays in the proximity of the PVDG,
The proposed classifiers were also tested for the Fig. 26 shows the angles and magnitudes of the voltages at
North-American version of the CIGRE medium-voltage (MV) bus 8 for an ABG fault at bus 3 during the grid-connected oper-
distribution system rated at 12.47 kV [28]. As depicted in ation of the system when switches S1–S3 are open. V − leads
Fig. 25, three DGs are connected to the system: 1) a 2 MW V o by 115.7◦ , so δ o is in zone 3 of Fig. 14. Phases A and B
PVDG at bus 8; 2) a 2.5 MW type I wind DG at bus 6; also have the largest voltage drops. Hence, the voltage angle
and 3) an 8 MW SDG at bus 4. The latter is connected to and magnitude-based classifier detects an ABG fault. The
the system during islanded operation. Switches S1–S3 can be voltage angle-based classifier also selects the faulty phases cor-
closed to study a meshed distribution system. The PVDG oper- rectly since the zone 3 δ o is accompanied by δ + = −120.8◦ ,
ates at unity PF during faults, and the wind DG is equipped located in zone 1 of Fig. 16. For the relay next to the wind-
with PF correction capacitors to prevent reactive power con- based DG at bus 6, Fig. 27 plots the voltage angles and
sumption by the induction generators. Extensive simulations magnitudes for a CG fault at bus 10 during islanded oper-
were carried out for a variety of conditions. Tables VI and VII ation when the switches are closed. V − leads V o and V + by
report the voltage angles and magnitudes of the relays at 109.7◦ and 62.3◦ , resulting in δ o and δ + located in zone 3 of
buses 6 and 8 during solid faults at buses 3 and 10 for the grid- Figs. 14 and 16, respectively. Furthermore, phase C exhibits
connected and islanded operation and both open and closed the largest voltage drop. Therefore, both methods determine
status of switches S1–S3. a CG fault.
This article has been accepted for inclusion in a future issue of this journal. Content is final as presented, with the exception of pagination.
TABLE VI
R ESULTS O BTAINED FOR FAULTS AT B US 3 OF CIGRE MV D ISTRIBUTION T EST S YSTEM
TABLE VII
R ESULTS O BTAINED FOR FAULTS AT B US 10 OF CIGRE MV D ISTRIBUTION T EST S YSTEM
VI. C ONCLUSION microgrids with PVDG. Distinctive zones were defined for the
The existing fault type classifiers that operate based on the phase difference between the total sequence voltages. The first
angles of the superimposed sequence currents or the mag- proposed classifier relied on the fact that each zone defined
nitudes of phase/line currents were shown to malfunction in for δ o corresponded to two SLG and LLG faults that included
This article has been accepted for inclusion in a future issue of this journal. Content is final as presented, with the exception of pagination.
opposing phases. The voltage magnitude was thus exploited [23] G. Ziegler, Numerical Distance Protection: Principles and Applications,
to differentiate between the two possible faults. The unique 4th ed. Erlangen, Germany: Publicis, 2011, ch. 3.
[24] P. Maezono et al., “Very high-resistance fault on a 525 kV transmis-
pair of δ o and δ + zones associated with each fault type sion line—Case study,” in Proc. 62nd Annu. Conf. Protect. Relay Eng.,
was utilized to devise the second classification logic. Correct Austin, TX, USA, Mar. 2009, pp. 322–332.
operation of the proposed methods for the grid-connected [25] IEEE Recommended Practice for Monitoring Electric Power Quality,
IEEE Standard 1159, 2009.
and autonomous modes of a microgrid, together with their [26] A. Borghetti et al., “Synchronized phasors monitoring during the island-
robustness against various PVDG control strategies, fault resis- ing maneuver of an active distribution network,” IEEE Trans. Smart
tance, system imbalance, and load levels were validated by Grid, vol. 2, no. 1, pp. 82–91, Mar. 2011.
[27] IEEE PES Distribution Systems Subcommittee’s Distribution Test
simulation studies. Feeder Working Group. [Online]. Available: http://ewh.ieee.org/soc/pes/
dsacom/testfeeders/index.html
R EFERENCES [28] E. Abbasi et al., “Benchmark systems for network integration of
renewable and distributed energy resources,” CIGRE, Paris, France,
[1] A. Oudalov, T. Degner, F. Overbeeke, and J. Yarza, “Microgrid Tech. Rep. C6.04.02, Aug. 2008.
protection,” in Microgrids: Architectures and Control, 1st ed. Hoboken,
NJ, USA: Wiley, 2014, pp. 117–164.
[2] H. Zeineldin et al., “A protection coordination index for evaluating
distributed generation impacts on protection for meshed distribution
systems,” IEEE Trans. Smart Grid, vol. 4, no. 3, pp. 1523–1532,
Sep. 2013.
[3] L. Che, M. Khodayar, and M. Shahidehpour, “Adaptive protection
system for microgrids: Protection practices of a functional microgrid
system,” IEEE Electrific. Mag., vol. 2, no. 1, pp. 66–80, Mar. 2014. Ali Hooshyar received the B.Sc. degree in elec-
[4] E. Casagrande, W. L. Woon, H. H. Zeineldin, and D. Svetinovic, “A dif- trical engineering from the Isfahan University of
ferential sequence component protection scheme for microgrids with Technology, Isfahan, Iran, in 2006; the M.Sc. degree
inverter-based distributed generators,” IEEE Trans. Smart Grid, vol. 5, in electrical engineering from the University of
no. 1, pp. 29–37, Jan. 2014. Tehran, Tehran, Iran, in 2009; and the Ph.D. degree
[5] I. Xyngi and M. Popov, “An intelligent algorithm for the protection in electrical engineering from the University of
of smart power systems,” IEEE Trans. Smart Grid, vol. 4, no. 3, Waterloo, Waterloo, ON, Canada, in 2014.
pp. 1541–1548, Sep. 2013. He was a Postdoctoral Fellow with the Centre for
[6] J. Agüero, J. Wang, and J. Burke, “Improving the reliability of power Applied Power Electronics, University of Toronto,
distribution systems through single-phase tripping,” in Proc. IEEE PES Toronto, ON. He is currently an Assistant Professor
Trans. Distrib. Conf. Exp., New Orleans, LA, USA, Apr. 2010, pp. 1–7. with the Department of Electrical Engineering and
[7] T. Fahey and N. Burbure, “Single-phase tripping,” IEEE Power Energy Computer Science, York University, Toronto, in 2015. His current research
Mag., vol. 6, no. 2, pp. 46–52, Mar. 2008. interests include protection and control of renewable energy systems and
[8] G. Hataway and R. Moxley, “Distribution single-phase tripping and smart grids.
reclosing,” in Proc. Protect. Autom. Control World, 2009, pp. 28–33.
[9] R. Cheney, J. Thorne, and G. Hataway, “Distribution single-phase trip-
ping and reclosing: Overcoming obstacles with programmable recloser
controls,” in Proc. 62nd Annu. Conf. Protect. Relay Eng., Austin, TX,
USA, 2009, pp. 214–223.
[10] T. A. Short, Electric Power Distribution Handbook, 2nd ed. Boca Raton,
FL, USA: CRC Press, 2014, chs. 8–9.
[11] M. Hori, Y. Saita, and M. Inukai, “Short-circuit distance relay,” Ehab F. El-Saadany (SM’05) was born in Cairo,
U.S. Patent 2011 014 944 8 A1, Jun. 23, 2011. Egypt, in 1964. He received the B.Sc. and M.Sc.
[12] J. Roberts and E. Schweitzer, “Fault identification system for use in degrees from the Ain Shams University, Cairo, in
protective relays for power transmission lines,” U.S. Patent 5 515 227, 1986 and 1990, respectively, and the Ph.D. degree
May 7, 1996. from the University of Waterloo, Waterloo, ON,
[13] D90Plus Line Distance Protection System, GE, Markham, ON, Canada, Canada, in 1998, all in electrical engineering.
Mar. 2012. [Online]. Available: www.gedigitalenergy.com/products/ He is currently a Professor with the Department
manuals/d90plus/gek-113240b.pdf of Electrical and Computer Engineering, University
[14] M. Mynam and Y. Gong, “Fault-type identification for electric power of Waterloo. His current research interests include
delivery systems,” U.S. Patent 2013 008 823 9 A1, Apr. 11, 2013. smart grids operation and control, power quality, dis-
[15] Technical Manual: MiCOMho P446—Fast Multifunction Distance tributed generation, power electronics, digital signal
Protection Relay, Alstom, Stafford, U.K., 2011. [Online]. Available: processing applications to power systems, and mechatronics.
ftp://ftp.alstom.com/Alstom_Manuals/P446_EN_TM_E.pdf
[16] L. Yang, “Fault type classification algorithm,” U.S. Patent 5 783 946,
Jul. 21, 1998.
[17] J. F. Conroy and R. Watson, “Low-voltage ride-through of a full con-
verter wind turbine with permanent magnet generator,” IET Renew.
Power Gener., vol. 1, no. 3, pp. 182–189, Sep. 2007.
[18] M. Tsili and S. Papathanassiou, “A review of grid code technical
requirements for wind farms,” IET Renew. Power Gener., vol. 3, no. 3,
pp. 308–332, Sep. 2009. Majid Sanaye-Pasand (M’98–SM’05) received the
[19] P. M. Anderson, Analysis of Faulted Power Systems, Hoboken, NJ, USA: B.Sc. degree in electrical engineering from the
Wiley, 1995, chs. 3, 6. University of Tehran, Tehran, Iran, and the M.Sc.
[20] J. Rocabert, A. Luna, F. Blaabjerg, and P. Rodriguez, “Control of power and Ph.D. degrees in electrical engineering from the
converters in AC microgrids,” IEEE Trans. Power Electron., vol. 27, University of Calgary, Calgary, AB, Canada, in 1994
no. 11, pp. 4734–4749, Nov. 2012. and 1998, respectively.
[21] A. Yazdani and R. Iravani, Voltage-Sourced Converters in Power He is currently a Professor with the School of
Systems: Modeling, Control, and Applications. Hoboken, NJ, USA: Electrical and Computer Engineering, University of
Wiley, 2010, chs. 7–8. Tehran. His current research interests include power
[22] T. Adu, “An accurate fault classification technique for power sys- system protection, control, and transients.
tem monitoring devices,” IEEE Trans. Power Del., vol. 17, no. 3, Dr. Sanaye-Pasand is an Editor of the IEEE
pp. 684–690, Nov. 2002. T RANSACTIONS ON P OWER D ELIVERY.