Keywords: Micro-grid; protection relay; fault characteristic; PCC; Wide-area protection relay
Ključne riječi: mikro-rešetka; zaštitni relej; karakteristika greške; PCC; zaštitni relej širokog područja
reliability of MG. Domestic and foreign researchers have 2 Fault features of new energy sources generators and
made extensive studies on the relay protection of MG [13 protection adaptivity
÷ 18]. Ref. [8] proposed to use the negative sequence and 2.1 Fault features of single supply
zero sequence current protection to reflect the asymmetry
and grounding fault in MG. In [14], a protection scheme MG has multiple type micro-powers, such as:
using digital relays with a communication network is photovoltaic power generator [23], wind power (including
proposed for the protection of the MG system. The double-fed induction generator and direct-driven wind
increased reliability of adding an additional turbine generators) [24], micro-turbine generator [25],
communication line to form a closed information loop is fuel cell [26], BESS [27], diesel generators, etc.
explored. In [15], the authors detailed the assignment of Depending on the way that micro power sources are
two parameters which are critical for proper operation of connected into the grid, the power supply within MG can
a MG protection system. The first parameter, the fault be divided into three categories:
current coefficient, represents the fault current supplied The first category of new energy sources is connected
by any DG to any point inside the network whereas the into the network by rotating machines and converters. The
second parameter is the adjustment of relay hierarchy for representative for this kind of new energy sources
selective operation of relays. The automated assignment generating system is the doubly-fed induction generating
of these parameters serves the notion of self-operating system.
MG protection system. Ref. [17] investigates the The second category of new energy sources is
efficiency of under/over frequency relays for protection of connected into the network merely by converters. The
distributed synchronous generators considering islanding major applications of this kind of new energy sources
detection and frequency-tripping requirements. In Ref. include direct-drive wind power generation system,
[18], the authors proposed faulted section detection using photovoltaic power system, battery, micro gas turbine, etc.
time over current protective relays. Ref. [19] proposed a The third category of energy is connected into the
laboratory MG protection system implemented using an network merely by rotating machines. The major
industrial computer. However, the hardware platform application of this kind of new energy sources is the
based on rapid data acquisition is complicated and costly. diesel engine system. We will not elaborate on the fault
Ref. [20] proposed a communication-free low voltage features of this kind of new energy sources since it is
inverse time overcurrent protection scheme (UAITOC). similar to the main grid.
However, this system will not function correctly in some
cases when the new energy sources faults cannot be 2.1.1 Fault features of the first kind of new energy sources
located by the current magnitude. Ref. [21] proposed the
branch directional variation protection of AC MG. Ref. This kind of new energy sources is mainly used in the
[22] proposed to use the hierarchical compromise scheme doubly-fed induction generating system. The fault
to resolve the challenges brought by the MG to the relay features of this kind of new energy sources are radically
protection of distributing network. One common problem different from those of conventional generators. The fault
with these schemes is that they are proposed for one current is high, and in the early fault period there is the
specific MG and thus cannot be applied universally. attenuating non power frequency component.
Therefore, it is necessary to conduct a comprehensive 1) Whether the Crowbar circuit pickup or not will affect
analysis of the relay protection of MG based on a the strength of fault current.
thorough study of the fault features of the MG. 2) After the Crowbar circuit acts, the frequency of the
Instead of building special relay protection system, output current from generating system is similar to
most of the demonstrative projects mentioned above still the frequency of the rotor rather than to the power
use the automation and protection devices designed for frequency. At this time, the directional element which
common distribution power system. The MG without calculates according to power frequency cannot
relay protection system will fail to trip the internal and accurately reflect the fault. The component will be
external fault effectively, which may cause the anti- completely attenuated within 200 ms.
islanding protection of new energy sources to act. Even 3) Crowbar circuit parameter (mainly the parameter of
worse, if the new energy sources do not have the function resistant) determines the features of fault current,
of low voltage ride through, the new energy sources will such as the magnitude and attenuation time, etc.
be shut down immediately when internal and external
faults occur. The action of anti-islanding protection or the 2.1.2 Fault features of the second kind of new energy
shutdown of new energy sources will affect the operation sources
of the MG, which goes against our intention to enhance
the reliability by MG. The second kind of new energy sources is connected
Based on a thorough study of the fault features of into the network merely by converters. The majority
new energy sources, the paper proposes three MG applications of this kind of new energy sources include
protection schemes according to the scale of the MG and direct-drive wind power generation system, photovoltaic
discusses the stability of MG in each scheme. power system, battery, micro gas turbine, etc. Through the
simulation and theoretical analysis of various types of
faults, we come to the following conclusion:
1) The direction of the power output from inverter can
accurately reflect fault type in all cases.
2) A short transient occurs during the fault period, and
in the transient process a harmonic component exists. will occur. The protection range of the timed fast trip
3) A short period after the fault, the inverter output at upstream of the distribution power system will
approaches toward stable state. The steady-state value shrink, which may cause maloperation when the
of short circuit current is approximate to the rated capacity of the distribution power is large enough.
current and the exact amount depends on the inverter When the short circuit occurs at upstream the added
controlling strategy. distribution power, the reverse current may occur,
4) The duration and the peak value of the transient which will cause misoperation.
process is subject to a number of factors, including
the DC bus capacitance, outer-loop power parameter, 2.3 Protection adaptability analysis
input power, etc.
5) Whether it is a single phase fault, two-phase fault, or The commonly used protections in the electrical grid
three-phase fault, the current for each fault is similar. include overcurrent protection, distance protection,
Therefore, it is impossible to identify the faulty phase differential protection, pilot protection, voltage protection,
by current. frequency protection, etc. Not all these protections can be
6) Due to the clipping effect of inverter, we cannot applied to the MG due to the distinguishing characteristics
determine the distance of the fault by the intensity of of the micro power fault and the special structures of the
the current. MG.
2.3.3 Variable quantity protection channels. However, the pilot protection does not apply to
the MG with doubly-fed induction generators.
The variable quantity protection is mainly used to
increase the action speed of the 66 kV and above voltage. 3 Protection structure for MG
But since most of the new energy sources generators in
the MG are equipped with current limiting module The relay protection system for the MG can be
devices, the quantity change value will be unable to divided into two parts: the protection for the connection
reflect the real conditions of the fault, making it point and the protection within MG.
inappropriate for MG protection. It is essential to configure protection at the
connection point (PCC) regardless of the types of MG,
2.3.4 Voltage protection and frequency protection because the PCC protection provides the last resort of
protection for the operation of main grid. The PCC
The voltage protection and frequency protection are protection configuration includes overcurrent protection,
rarely used alone in the main grid. They are mainly used anti-islanding protection (voltage protection and
in the stability control equipment. Considering the need of frequency protection) and anti-back flow protection.
anti-islanding, they can be used as the main protection at The protection devices such as fuse are installed
the network tie point within the MG according to the specific conditions of MG.
Different protection configuration schemes can be
2.3.5 Differential protection deployed depending on the scale and importance of the
MG, include the wide area protection scheme, the
Differential protection has the advantage of fast distribution protection scheme, and the protection relying
action. It can act as quickly as within 5ms. The threshold on primary equipment, etc.
of differential protection can be easily rectified, and it can
be adapted to both the grid-connected operation mode and 3.1 Wide area protection scheme
islanded operation mode, making it appropriate for the
protection of MG. The disadvantage of differential In the wide area protection scheme, a central unit is
protection is its high requirement for communication used to implement the function of wide area protection
channels. and the intelligent remote terminal units are installed on-
site to implement the function of real-time data collection
2.3.6 Pilot protection and backup protection. The solution applies to the
relatively high importance, larger MGs, usually important
Pilot protection adopts the two-end power direction 10 kV MG, while according to the degree of importance
rather than the current threshold as the protection criteria; and the communication channel’s availability, a single
therefore it can be applied to MG. In the meantime, the central unit and single process-layer-network, single
pilot direction protection does not require as much for central unit and dual process-layer-network, and dual
communication channels as differential protection. It can central unit, dual process-layer-network and other
use the multiplexed channel, public communication configurations.
network channels, or even the wireless communication
The structure of the wide-area protection scheme is of distribution lines and buses within the MG. It
illustrated in Fig. 1. This scheme is constituted by the conducts the computation of main protection logic
following equipment: based on the data received from on-site units, and
1) Central unit, which is responsible for the protection then sends controlling commands according to the
medium importance, generally the 10 kV MG and some time coordination diagram until the fault is isolated.
of the 0,4 kV MG. The protection time coordination diagram of
The conceptual structure of the distribution protection distributed protection scheme which uses the main fast
system is illustrated in Fig. 3, in which four kinds of trip protection is shown in Fig. 5.
equipment are included, which are:
1) The bus protection device, which uses the differential
protection as main protection.
2) The MG transformer protection device, which mainly
uses the compound voltage overcurrent protection.
When necessary, it will add the differential protection
as main protection. Meanwhile, it integrates the
function of telemetering, tele-signaling, tele-
regulating, tele-controlling, and equipment operation
condition monitoring, etc.
Figure 5 The protection operation time diagram of distributed protection
3) The MG feeder protection device, which uses the
scheme (2)
optical fiber differential or the pilot protection as
main protection, and the compound overcurrent When a fault occurs within the protected area, the
protection as backup protection. In the meantime, it overcurrent protection relay will serve as the main
integrates the function of telemetering, tele-signaling, protection and detect the fault in around 200 ms, and
tele-regulating, tele-controlling, and equipment isolate the fault. If the fault does not disappear after 500
operation condition monitoring, etc. ms, the backup overcurrent protection, progressively in
action, isolates the fault.
This scheme combines together the process level
network and station level network to form a unified 3.3 The protection scheme with no dedicated protection
station/process level network. The station/process level device
network implements the data association among unit
protection devices, and data communication between unit For the MGs with less importance or those without
protection devices and substation computers through internal communication channels, we shall simplify the
Ethernet. The directional pilot protection and other circuit relay protection system. No dedicated protection devices
breaker position information are exchanged by the need to be installed, and we only rely on the fuse, plastic
GOOSE messages, and the MMS messages are used for casing circuit breaker and air circuit breaker for protection.
data exchange between unit protection devices and This scheme applies to the MGs with less importance,
substation computers. generally the 0,4 kV MG or some 10 kV MGs in remote
Depending on whether the pilot protection is used, areas.
the distributed protection system can be divided into two
categories: First category uses the optical fiber channel 4 The analysis of protection action under different
based differential protection and directional pilot protection scheme
protection as the main fast trip protection; the other
category does not use fast trip protection. Assume that the new energy sources in the MG have
The protection operation timing coordination diagram the capacity of low voltage ride through or even zero
of distributed protection scheme uses the main fast trip voltage rides through. Based on the above analysis, the
protection as shown in Fig. 4. stability of new energy sources MG is closely related with
the action time of anti-islanding protection, the action of
connection points and the voltage at the connection point.
We will conduct the analysis of MG stability in two
scenarios depending on the action time of anti-islanding
protection of new energy sources.
1) The new energy sources use the fast trip anti-
islanding protection (the action time is 0,1 s)
2) The new energy sources do not use the fast trip anti-
islanding protection (the action time is 2,0 s)
Figure 4 The protection operation time diagram of distributed protection
scheme (1) 4.1 The stability of MG with external faults
Distributed protection solutions which use main fast When the external faults occur to the MG, the
trip protection contain the main protection, overcurrent stability of the MG is tested by observing the following
protection and other types of protections. factors: the voltage at the connection point, the action of
When a fault occurs within the protected area, the main grid protective relays, the protective relay action of
main protection will detect the fault in around 20 ms, and connection point and the configuration of anti-islanding
trip circuit breaker to isolate the fault. If the fault does not protection. The analysis results are shown in Tab. 1.
disappear after 500 ms, overcurrent protection is
progressively in action according to the principles of the
Table 1 Stability analysis of MG with external fault Table 2 Stability analysis of micro-grid when internal fault
Stability analysis of migro- Stability analysis of migro-
grid grid
The new The new The new
The action The The new
The The action energy energy The energy
of the main- action of The action of energy
voltage of of PCC sources use source does voltage source do not
grid the MG PCC protection sources use
PCC protection fast trip anti- not use fast of PCC use fast trip
protection protection fast trip anti-
islanding trip anti- anti-
islanding
protection islanding islanding
protection
protection protection
External Internal Internal Fault
Grid- Grid-
protection or protection protection isolation
Fault No act connected connected
PCC does not act, does not act, time <
isolation mode mode
protection MG turns MG turns 100 ms
time < 100
tripped the into isolated into isolated The low voltage MG
ms The anti-
PCC circuit operation. operation. protection or protection
islanding
breaker over-current acts
protection of
External The anti- Internal protection of Microgrid
DG acts, and
protection islanding protection PCC tripped the turns into
100 ms < 100 ms < MG lost
orpcc protection of does not act, PCC circuit islanding
Fault Fault stablity
< 0,5 pu protection DG acts, and MG turns breaker mode.
isolation isolation
trips the MG loses into isolated The anti-
time < 2 s < 0,5 pu time < 2 s
PCC circuit stablity operation islanding
MG
breaker protection of
No act protection
The low The anti- The anti- DG acts, and
acts.
voltage islanding islanding MG lost
Fault protection of protection of protection of stablity
isolation PCC trips DG acts, and DG acts, and The low voltage
The anti- The anti-
time>2s the PCC MG loses MG loses protection or
islanding islanding
circuit stablity stablity Fault over-current
protection of protection of
breaker isolation protection of
DG acts, and DG acts, and
External Internal Internal time>2s PCC tripped the
MG lost MG lost
protection protection protection PCC circuit
stablity stablity
Fault orpcc does not act, does not act, breaker
isolation protection MG turns MG turns Fault Grid- Grid-
time>2s trips the into isolated into isolated isolation No act connected connected
PCC circuit operation operation time < 2 s mode mode
breaker The anti- The anti-
> 0,5 pu
The low The anti- The anti- > 0,5 pu The low voltage islanding islanding
Fault
voltage islanding islanding protection of protection of protection of
isolation
Fault protection of protection of protection of PCC tripped the DG acts, and DG acts, and
time > 2 s
isolation PCC trips DG acts, and DG acts, and PCC breaker MG lost MG lost
time > 2 s the PCC MG loses MG loses stablity stablity
circuit stablity stablity
breaker
threat to the protective devices in the MG.
3) At the connection point, the voltage protection and
4.2 The action of internal fault frequency protection are used to isolate the fault
within the main grid and the MG.
When the fault occurs within the MG, the stability of
4) The anti-islanding protection configuration of the
the MG is tested by observing the following factors: the
new energy source inverter is set according to the
voltage at the connection point, the action of master grid,
requirement of local grid corporation. Unless there
the protection action of connection point and the
are special requirements, it is suggested that the fast
configuration of anti-islanding protection. The analysis
anti-islanding protection shall be disabled, and the
results are shown in Tab. 2.
action time of low voltage protection and over-
frequency/under-frequency protection set at 2,0 s.
4.3 The protection configuration principle of MG 5) If the fault occurs within the main grid, the
automation system of the main grid will trip the
Through the analyzing of the MG stability in different
circuit breaker through remote tripping. After the
scenarios, it can be seen that the key to keep the stability
power supply in the main grid is restored, the MG
of the MG is to ensure the fast action of main grid
energy management system (the mode controller) will
protection in the case of internal fault and the fast action
restore the mode from isolated operation to connected
of distributed network in the case of external fault.
operation, thus restarting the connected MG.
1) The MGusess the multi-stage timing coordinated
6) In order to guarantee the reliable operation of MG, it
protection scheme, which combines the fast trip
is required that the new energy sources in the MG
protection (optical fiber differential protection and
shall possess the function of low voltage ride through
directional pilot protection for example) and back-up
and it is suggested adopting the new energy sources
protection (overcurrent protection and low voltage
generating equipment with zero voltage ride through
protection).
capability.
2) The communication channel between the MG and the
main grid uses the optical fiber differential relay as
fast protection, which ensures that the fault in the
main grid can be tripped rapidly and will not pose any