Professional Documents
Culture Documents
Evaporator + Expansion
units
Condensor + Compressor
the evaporator). Window AC’s ,Split AC’ s, Packaged Units(some of them) are examples of
DX units. In a split AC the evaporator with the expansion valve is present inside the room,
whereas the compressor & condensor components are present outside the room.
In case of Split AC, normally there can be no
provision for fresh air to enter the room. But in window AC there is a provision for letting
in fresh air. The amount of fresh air required by a person is 15 cfm (cubic feet /minute).
Package Unit :
R
Roollee ooff B
BMMS
S iinn D
DXX uunniittss C
Coonnttrrooll &
&MMoonniittoorriinngg::
♦ Time-Schedule based On/Off of DX units is possible.
♦ Common fault,blower status and heater status can also be monitored in case of
Precision AC’s
C
Ceennttrraalliisseedd S
Syysstteem
m::
This is for larger capacities of cooling requirements. It uses
a. A Chiller to produce the cooling centrally
b. Ahu’s ( Air Handling Units) to provide cooling locally, by using the cooling energy produced at the
Chiller.
The Chiller and it’s components are usually referred to as the ‘High’ side and the Ahu’s and the
components are referred to as ‘Low’ side of the HVAC contract.
C
Chhiilllleerr:: Each chiller is controlled by a microprocessor-based control panel. Each chiller has its own
evaporator, compressors, condenser and expansion components. (In other words an expanded room
air-conditioner, expanded multifold times.) The number of compressors in a Chiller is usually 2 but it
may also vary with the manufacturer & size of chiller. The water used in a chiller system is DM (de-
mineralized) water.
In a chiller the refrigerant cools water (called Chilled Water), by
using the same DX principle as that of a room air conditioner/split or packaged unit. The only difference
is that the capacity of the compressor is much more. This Chilled water is then pumped into the Heat
Exchanger of the AHU ‘s (called ‘Cooling coil’).
This Chilled water which is at a temperature of 5.5 degree centigrade to 6 degree centigrade
then cools the air from the conditioned space. Hence in a chiller system the refrigerant does
not directly cool the warm area.
♦ The cooling demand required to be produced by the chiller will depend on how much of chilled
water the chiller is producing is being used by the Ahu’s. A measure of the load condition is the
difference between the supply and return header temperatures. By measuring this difference, the
load can be determined and energy saving means adopted, as will be illustrated below:
♦ If there is only one chiller, the microprocessor of the chiller will receive inputs of the supply and
return header temperatures, ( apart from safety interlocks like water flow, refrigerant pressures etc)
and based on the difference, a decision on how many compressors can be switched on will be
determined.
♦ Example: Let us take the case of 2 chillers, each with it’s own microprocessor panel. In case of a
50% load ( meaning requirement of one chiller only), each chiller will operate with one compressor
each ( assuming two compressors per chiller). This is because the microprocessor of chiller 1 will
not know that there is another microprocessor panel of chiller 2 next to it. ( Assuming no BMS or
any other controls from Chiller manufacturer).
Each chiller will switch off one compressor, as both the chillers have received same supply and
return header temperature input.
Please Note: Whether BMS is there or not, the chiller manufacturer will use temperature sensors in
supply and return line of the chiller as inputs to the microprocessor. Panel.
Coming back to our above example:This creates a problem because, we have a situation where
two chillers are operating on 50% load conditions. Most chillers’ efficiency drop drastically if they
are operated below 80% load conditions.
So, we can use the BMS to switch off one Chiller and to make the other chiller run to cater to
50% load, which in this case would be operating both compressors of that particular chiller.
Also, one chilled water pump can also be shut down.The same example can be extended to
more number of chillers.
Please note: The decision to run the compressors of the chiller is taken by the
micrprocessor panel of Chiller and not by BMS. BMS will only decide whether one or more
chillers need to run.The operating of the compressors of the chiller, is referred to in HVAC
industry, as ‘loading’ and ‘unloading’ of the chiller.
♦ While switching off the chiller, The chiller is first switched off, then primary pumps and then the
butterfly valve is closed. When again switching on the chiller the reverse sequence is followed.
A
Aiirr H
Haannddlliinngg U
Unniitt:: The filter in the AHU filters the dust particles in the air from the return air
duct and fresh air supply. This air then passes across a cooling coil inside which cold water
is running (from the chiller, through the pumps). Heat exchange occurs between the air and
the chilled water in the cooling coil. The cooled air is then circulated into the supply air duct
by means of a fan. Using ducts this cooled air is distributed to the various areas where this
AHU is catering to.
Return Air
Supply Fan
Filter
R
Roollee ooff B
BMMS
S iinn A
AHHU
UCCoonnttrrooll &
&MMoonniittoorriinngg::
♦ The filter status is monitored to find out if any clogging has occurred. A differential pressure switch
connected across the filter is used to give a digital output when the filter is clogged.
♦ A differential pressure switch is used to monitor the functioning of the fan
♦ The AHU can also be operated on time schedule basis. For e.g.. The AHU can be switched on from
9.00 am to 9.30 p.m.
♦ The return air temperature of each AHU is used to monitor the opening and closing of the valve
connected at the outlet of the chilled water line (cooling coils) . If the return air temperature is high
then the valve is opened wide . If the return air temperature is low, then the valve is closed
allowing only little water flow.
AHU :
V
Vaarriiaabbllee A
Aiirr V
Voolluum
mee U
Unniittss:: VAV is used to control the amount of cool air flowing into each room or
zone. The air enters each room via a damper system. Each zone will have varying temperature and
pressure requirements. This requirement is met by varying the closing and opening of the damper
which in turn controls the amount of cool air flowing into the zone.
A VAV unit :
Comparing the AHU, VAV combination with the water
system we have at home and offices, the AHU is similar to the overhead water tank. The VAV’s are
similar to the taps in each of the rooms. The water available in the overhead tank can be used in the
rooms as per each room’s requirement by variably opening and closing the taps.
R
Roollee ooff B
BMMS
S iinn V
VAAV
VCCoonnttrrooll &
&MMoonniittoorriinngg::
♦
♦ A temperature sensor is placed in the supply air duct from the AHU. This temperature is monitored
while using VAV.
♦
♦ A pressure sensor is installed at 2/3 rd distance of the supply air duct serving the various zones. If
the pressure is too high a Variable frequency drive is used to lower the speed of the AHU fan.
R
Reedduucciinngg R
RHH ooff aa rroooom
m: In pharma and textile industries a specific RH has to be maintained. While
monitoring RH using an RH sensor there may be situations where we need to reduce the RH. To
reduce RH we increase the cooling. Increased cooling leads to dehumidification. Due to
dehumidification the water content in the air reduces. Thus the RH of the room is reduced.
After this process if the temperature of the room has to be
increased a little then we can switch on the heater.
G
Glloossssaarryy::
Humidity: It is the measure of moisture content in a substance. Air is never 100 % dry. Air always
exists in the form of a mixture of dry air and water vapour.
Relative Humidity: The ratio of the actual moisture content of air at a given condition to the moisture
condition that would have been present at saturated conditions for the same temperature.
Dew point temperature: It is the temperature at which air can no longer hold the moisture and when
condensation commences.
Boiling point: We can alter the boiling points of liquids by changing the pressure. When pressure
increases the boiling point increases. In other words the temperature of the liquid increases when we
increase the pressure.
Anamolous Expansion of water: Between 0 deg centigrade and 4 deg centigrade water actually
contracts. Hence care should be taken that the water flowing in chiller never reaches this temperature.
Heat Exchange : Exchange of heat happens from a higher temperature area to a lower temperature
area.
Btu/hr : The abbreviation for British thermal units. The amount of heat required to raise one pound of
water to one degree Fahrenheit per hour, a common measure of heat transfer rate.
Tonnage(TR) : The unit of measure used in air conditioning to describe the cooling capacity of a
system. One ton of cooling is based on the amount of heat needed to melt one ton (2000 lbs.) of ice in a
24 hour period. One ton of cooling is equal to 12,000 Btu/hr.
**************************************