You are on page 1of 2

DSE86xx MKI to DSE86xx MKII

Conversion
1 DESCRIPTION

NOTE: This document is intended as a wiring conversion guide and assumes that the individual
following it understands that the DSE86xx MKII may require configuring to suit the requirements of the
application. For further information on module configuration refer to DSE Publications: 057-119 DSE8600
Configuration Suite Software Manual and 057-238 DSE8610 MKII Configuration Suite PC Software Manual or
057-257 DSE 8660 MKII Configuration Suite PC Software Manual.

This document describes how to convert the existing wiring connections for a DSE86xx MKI module to suit the
DSE86xx MKII module. The panel cutout is the same size, the only changes required are to the controller wiring and
module configuration.

Always refer to the source of the module configuration and system wiring diagram to confirm the below listed
connections are suitable for the application.

2 WIRING CHANGES
Terminal number assignment differs considerably between the DSE86xx MKI and DSE86xx MKII modules. Despite
this the physical locations and pin-out of the majority of terminals and connectors remain the same, with the addition
of a small number of inputs and outputs for the DSE86xx MKII. This is illustrated by the below images:

DSE8610 MKI DSE8610 MKII

D) 39 to 46 E) 47 to 50 F) 51 to 57 G) 60 to 70 D) 40 to 47 E) 48 to 51 F) 52 to 58 G) 59 to 70

H)

H) 71-76

A) 1 to 13 B) 15 to 19 C) 22 to 38 A) 1 to 14 B) 15 to 22 C) 23 to 39

Author: J.Z. Page 1 of 2 056-089 ISSUE: 3


3 TERMINAL NUMBER ASSIGNMENT
The following tables detail the differences in terminal number assignment between the DSE86xx MKI and DSE86xx
MKII modules. Each table corresponds to a specific connector on the module. The connectors have been labelled A to
H. This is not a DSE standard for connector labelling, and has simply been included for ease of reference.

NOTE: Not every terminal listed below is NOTE: The designation of CT common and
applicable to all DSE86xx modules. For further earth fault CT terminals may change depending on
information refer to the relevant DSE Operator system requirements. For further information refer
Manual. to DSE publication: 056-019 Earth Fault Protection.

Connector A Connector D
DSE86xx Description DSE86xx DSE86xx Description DSE86xx
MKI Pin No. MKII Pin No. MKI Pin No. MKII Pin No.
1 DC Supply Negative 1 39 Normally Closed Volt-Free Relay 40
2 DC Supply Positive 2 40 Output C 41
3 Emergency Stop 3 41 Normally Open Volt-Free Relay 42
4 Fuel Output 4 42 Output D 43
5 Starter Output 5 43 V1 L1 44
6 Charge Alternator 6 44 V1 L2 45
7 Earth N/C 45 V1 L3 46
8 Digital Output E 7 46 V1 N 47
9 Digital Output F 8
10 Digital Output G 9 Connector E
11 Digital Output H 10 DSE86xx Description DSE86xx
12 Digital Output I 11 MKI Pin No. MKII Pin No.
13 Digital Output J 12 47 V2 L1 48
N/A Digital Output K 13 48 V2 L2 49
N/A Digital Output L 14 49 V2 L3 50
50 V2 N 51
Connector B
DSE86xx Description DSE86xx Connector F
MKI Pin No. MKII Pin No. DSE86xx Description DSE86xx
15 Analogue Input Common 15 MKI Pin No. MKII Pin No.
16 Analogue Input A 16 51 L1 CT S1 52
17 Analogue Input B 17 52 L2 CT S1 53
18 Analogue Input C 18 53 L3 CT S1 54
19 Analogue Input D 19 54 See note above 55
N/A CAN H 20 55 See note above 56
N/A CAN L 21 56 L1 Bus/Load Current S1 57
N/A CAN Screen 22 57 L1 Bus/Load Current S2 58

Connector C Connector G
DSE86xx Description DSE86xx DSE86xx Description DSE86xx
MKI Pin No. MKII Pin No. MKI Pin No. MKII Pin No.
22 MPU Negative 23 60 Digital Input A 59
23 MPU Positive 24 61 Digital Input B 60
24 MPU Screen 25 62 Digital Input C 61
25 ECU Port H 26 63 Digital Input D 62
26 ECU Port L 27 64 Digital Input E 63
27 ECU Screen 28 65 Digital Input F 64
28 DSENet® B 29 66 Digital Input G 65
29 DSENet® A 30 67 Digital Input H 66
30 DSENet® Screen 31 68 Digital Input I 67
31 MSC H 32 69 Digital Input J 68
70 Digital Input K 69
32 MSC L 33
N/A Digital Input L 70
33 MSC Screen 34
34 Governor B 35
Connector H
35 Governor A 36
DSE86xx Description DSE86xx
36 Not Connected 37
MKI Pin No. MKII Pin No.
37 AVR B 38
Screen RS485 Port 1 Screen 71
38 AVR A 39
B RS485 Port 1 A 72
A RS485 Port 1 B 73
N/A RS485 Port 2 Screen 74
N/A RS485 Port 2 A 75
N/A RS485 Port 2 B 76

056-089 ISSUE: 3 Page 2 of 2 Author: J.Z.