EXTERNAL DIMENSIONS
760
2X5- 4.6 Hole
240
Control box •Pipe (ID9.52XOD12.7)···P250 1pc.
•Pipe (ID12.7XOD12.7)···P300 1pc.
•Pipe (ID12.7XOD9.52)···P300 1pc.
PUHY-P200,250,300YHA(-BS)
Intake Intake
2. EXTERNAL DIMENSIONS
1650
2.At brazing of pipes,wrap the refrigerant service valve
panel with wet cloth and keep the temperature of
1410
refrigerant service valve under 120°C.
Refrigerant service
valve <gas> 6
4 1
NO. Usage Specifications
72
Front through hole 102X72 Knockout hole
For pipes
54
B
Bottom through hole 150X92 Knockout hole
OUTDOOR UNITS
Front through hole
132 88
65 or 40 Knockout hole
90
For wires Front through hole 52 or 27 Knockout hole
55 25 25 55 3 204 98 Bottom through hole 52 Knockout hole
760 251 102 For transmission cables Front through hole 34 Knockout hole
Left side view Front view
Connecting pipe specifications
Position dimensions
221 150
for the refrigerant Connection specifications for 251 83 2X2-14X20 Oval hole
Model service valve the refrigerant service valve*1
186
86
Liquid
18
Gas
145
Liquid Gas
A B
131
145
PUHY-P200YHA(-BS) 170 9.52 Brazed 19.05 Brazed
142 9.52 Brazed
727)
92
PUHY-P250YHA(-BS) 5
( 12.7 Brazed)*3
172 22.2 Brazed 2 Refrigerant service
(760)
*1 Connect by using the connecting pipes (for bottom piping and front piping)
that are supplied.
*2 Indicates dimensions and connection specifications in the case the unit is 80 760 80
18
2 - 45
Y
Y
100 min.*
300 min.*
Wall <H> <To be left open>
100 min.*
Wall <H>
300 min.*
Front
Front
Front
Front
Front
450 min.*
Front
450 min.*
Front
PUHY-P200,250,300YHA(-BS)
Wall <H>
Wall <H>
450 min.*
450 min.*
<Top view> <Top view>
<Unit:mm> <To be left open>
When the height of the walls on the front, back or on the sides<H>
exceeds the wall height limit as defined below
add the height that exceeds the height limit <h> to the figures that
300 min.*
15 min.*
<Wall height limit> Front :Up to the unit height
h
Back :Up to 500mm from
the unit bottom
Side :Up to the unit height
H
Front
Front
Front
Front
Front
h
900 min.
900 min.
OUTDOOR UNITS
H
Front
Unit height
500
<To be left open>
2 - 46
760
2X5- 4.6 Hole
240
Control box
<Liquid> •Pipe (ID15.88XOD15.88)···P350,P400,P450 1pc.
•Pipe (ID15.88XOD12.7)···P350,P400 1pc.
PUHY-P350,400,450YHA(-BS)
Intake
2. EXTERNAL DIMENSIONS
Intake
Intake air air
air Refrigerant service Note1.Please refer to the next page for information
valve <liquid> regarding necessary spacing around the
Service unit and foundation work.
1650
panel 2.At brazing of pipes,wrap the refrigerant service valve
with wet cloth and keep the temperature of
1410
Refrigerant service
valve <gas> refrigerant service valve under 120°C.
6
4 1
72
54
OUTDOOR UNITS
B
Usage
A
NO. Specifications
132 88
Front through hole 102X72 Knockout hole
For pipes
90
Bottom through hole 150X94 Knockout hole
55 25 25 55 3 254 98 Front through hole 65 or 40 Knockout hole
760 301 102 For wires Front through hole 52 or 27 Knockout hole
Left side view Bottom through hole 65 Knockout hole
Front view
271 150 For transmission cables Front through hole 34 Knockout hole
301 83 2X2-14X20 Oval hole
84
Connecting pipe specifications 216
142
18
131
the refrigerant service valve *1
145
Model service valve
Liquid Gas
Liquid Gas
94
A B 5
PUHY-P350YHA(-BS) 12.7 Brazed 2 Refrigerant service
(760)
*2
PUHY-P450YHA(-BS) 15.88 Brazed
18
*1 Connect by using the connecting pipes (for bottom piping and front piping)
that are supplied. 80 1060 80
*2 Indicates dimensions and connection specifications in the case the unit is (Mounting pitch)
used in combination with other outdoor units. Bottom view
Unit : mm
DATA A3
2 - 47
Y
Y
100 min.*
300 min.*
Wall <H> <To be left open>
100 min.*
Wall <H>
300 min.*
Front
Front
Front
Front
Front
450 min.*
Front
450 min.*
Front
PUHY-P350,400,450YHA(-BS)
Wall <H>
Wall <H>
30 min.
450 min.* 450 min. 450 min. 100 min.*
450 min.*
450 min.*
<Top view> <Top view>
<Unit:mm> <To be left open>
When the height of the walls on the front, back or on the sides<H>
exceeds the wall height limit as defined below
add the height that exceeds the height limit <h> to the figures that
300 min.*
15 min.*
<Wall height limit> Front :Up to the unit height
h
Back :Up to 500mm from
the unit bottom
Side :Up to the unit height
H
Front
Front
Front
Front
h
Front
900 min.
OUTDOOR UNITS
900 min.
Front
Unit height
500
<To be left open>
<Side view>
<To be left open>
Wall <H> 1000 min.*
Corner of the
300 min.*
2 - 48
760 920 30 920
1650
Intake Intake
Intake air air
air
OUTDOOR UNITS
e a
Left view c To indoor unit
Twinning pipe connection size Liquid Twinning pipe<optional parts>
Package unit name PUHY-P500YSHA(-BS) PUHY-P550YSHA(-BS) f b
Outdoor unit 1 PUHY-P250YHA(-BS) PUHY-P300YHA(-BS) d To indoor unit
Component unit name
Outdoor unit 2 PUHY-P250YHA(-BS) PUHY-P250YHA(-BS) Liquid Gas Gas Twinning pipe<optional parts>
Unit model Front view
Outdoor Twinning Kit(optional parts) CMY-Y100VBK2 c or e d or f
Liquid a 15.88 P250 9.52 22.2
Indoor unit Twinning pipe Twinning pipe Outdoor unit
Gas b 28.58 P300 12.7 22.2
Note 1.Connect the pipes as shown in the figure above. Refer to the table above for pipe size.
2.Twinning pipes should not be tilted more than 15 degrees from the ground.
Be sure to see the Installation Manual for details of Twinning pipe installation.
3.The pipe section before the Twinning pipe (sections "a" and "b" in the figure) must have at least 500mm of straight section
(*including the straight pipe that is supplied with the Twinning pipe).
4.Only use the Twinning pipe by Mitsubishi (optional parts).
Unit : mm
DATA A3
2 - 49
Y
Y
1650
Intake Intake Intake
air air air
OUTDOOR UNITS
e a
Left view c To indoor unit
Liquid Twinning pipe<optional parts>
Twinning pipe connection size f
d b To indoor unit
Package unit name PUHY-P600YSHA(-BS) PUHY-P650YSHA(-BS)
Liquid Gas Gas Twinning pipe<optional parts>
Component unit name Outdoor unit 1 PUHY-P350YHA(-BS) PUHY-P350YHA(-BS) Unit model
Outdoor unit 2 PUHY-P250YHA(-BS) PUHY-P300YHA(-BS) c or e d or f Front view
Outdoor Twinning Kit(optional parts) CMY-Y100VBK2 P250 9.52 22.2
Liquid a 15.88 Twinning pipe Outdoor unit P300 12.7 22.2
Indoor unit Twinning pipe
Gas b 28.58 P350 12.7 28.58
Note 1.Connect the pipes as shown in the figure above. Refer to the table above for pipe size.
2.Twinning pipes should not be tilted more than 15 degrees from the ground.
Be sure to see the Installation Manual for details of Twinning pipe installation.
3.The pipe section before the Twinning pipe (sections "a" and "b" in the figure) must have at least 500mm of straight section
(*including the straight pipe that is supplied with the Twinning pipe).
4.Only use the Twinning pipe by Mitsubishi (optional parts).
Unit : mm
DATA A3
2 - 50
760 1220 30 1220
1650
Intake Intake Intake
air air
PUHY-P700,750,800,850,900YSHA(-BS)
air
OUTDOOR UNITS
e a
Left view c To indoor unit
Liquid Twinning pipe<optional parts>
f b
d To indoor unit
Twinning pipe connection size Gas Twinning pipe<optional parts>
Package unit name PUHY-P700YSHA(-BS) PUHY-P750YSHA(-BS) PUHY-P800YSHA(-BS) PUHY-P850YSHA(-BS) PUHY-P900YSHA(-BS)
Front view
Outdoor unit 1 PUHY-P350YHA(-BS) PUHY-P400YHA(-BS) PUHY-P450YHA(-BS) PUHY-P450YHA(-BS) PUHY-P450YHA(-BS) Liquid Gas
Component unit name Unit model
Outdoor unit 2 PUHY-P350YHA(-BS) PUHY-P350YHA(-BS) PUHY-P350YHA(-BS) PUHY-P400YHA(-BS) PUHY-P450YHA(-BS) c or e d or f
Outdoor Twinning Kit(optional parts) CMY-Y200VBK2 P350 12.7 28.58
Liquid a 19.05 Twinning pipe Outdoor unit P400 15.88 28.58
Indoor unit Twinning pipe
Gas b 34.93 41.28 P450 15.88 28.58
Note 1.Connect the pipes as shown in the figure above. Refer to the table above for pipe size.
2.Twinning pipes should not be tilted more than 15 degrees from the ground.
Be sure to see the Installation Manual for details of Twinning pipe installation.
3.The pipe section before the Twinning pipe (sections "a" and "b" in the figure) must have at least 500mm of straight section
(*including the straight pipe that is supplied with the Twinning pipe).
4.Only use the Twinning pipe by Mitsubishi (optional parts).
Unit : mm
DATA A3
2 - 51
Y
Y
Intake
Intake
1650
air
2. EXTERNAL DIMENSIONS
Intake air
air
g i a
OUTDOOR UNITS
e c To indoor unit
Left view
Liquid Twinning pipe 1 <optional parts> Liquid Twinning pipe 2 <optional parts>
h j b
f d To indoor unit
Twinning pipe connection size Gas Twinning pipe 1 <optional parts> Gas Twinning pipe 2 <optional parts>
Package unit name PUHY-P950YSHA(-BS) PUHY-P1000YSHA(-BS)
Outdoor unit 1 PUHY-P400YHA(-BS) PUHY-P400YHA(-BS) Front view
Component unit name Outdoor unit 2 PUHY-P300YHA(-BS) PUHY-P300YHA(-BS)
Outdoor unit 3 PUHY-P250YHA(-BS) PUHY-P300YHA(-BS)
Outdoor Twinning Kit(optional parts) CMY-Y300VBK2 Unit model
Liquid Gas
a 19.05 e or g or i f or h or j
Indoor unit Twinning pipe 2 Liquid
Gas b 41.28 P250 9.52 22.2
Liquid c 19.05 Twinning pipe Outdoor unit P300 12.7 22.2
Twinning pipe 1 Twinning pipe 2
Gas d 34.93 P400 15.88 28.58
Note 1.Connect the pipes as shown in the figure above. Refer to the table above for pipe size.
2.Twinning pipes should not be tilted more than 15 degrees from the ground.
Be sure to see the Installation Manual for details of Twinning pipe installation.
3.The pipe section before the Twinning pipe (sections "a", "b", "c" and "d" in the figure) must have at least 500mm of straight section
(*including the straight pipe that is supplied with the Twinning pipe).
4.Only use the Twinning pipe by Mitsubishi (optional parts).
Unit : mm
DATA A3
2 - 52
760 1220 30 1220 30 920
Intake Intake
1650
air Intake
2. EXTERNAL DIMENSIONS
air air
OUTDOOR UNITS
Left view g i a
e c To indoor unit
Liquid Twinning pipe 2 <optional parts>
Liquid Twinning pipe 1 <optional parts>
j
Twinning pipe connection size h d b
f To indoor unit
Package unit name PUHY-P1050YSHA(-BS) Gas Twinning pipe 2 <optional parts>
Outdoor unit 1 PUHY-P400YHA(-BS) Gas Twinning pipe 1 <optional parts>
Component unit name Outdoor unit 2 PUHY-P350YHA(-BS) Front view
Outdoor unit 3 PUHY-P300YHA(-BS)
Outdoor Twinning Kit(optional parts) CMY-Y300VBK2 Liquid Gas
Unit model
Liquid a 19.05 e or g or i f or h or j
Indoor unit Twinning pipe 2
Gas b 41.28 P300 12.7 22.2
Liquid c 19.05 Twinning pipe Outdoor unit P350 12.7 28.58
Twinning pipe 1 Twinning pipe 2
Gas d 34.93 P400 15.88 28.58
Note 1.Connect the pipes as shown in the figure above. Refer to the table above for pipe size.
2.Twinning pipes should not be tilted more than 15 degrees from the ground.
Be sure to see the Installation Manual for details of Twinning pipe installation.
3.The pipe section before the Twinning pipe (sections "a", "b", "c" and "d" in the figure) must have at least 500mm of straight section
(*including the straight pipe that is supplied with the Twinning pipe).
4.Only use the Twinning pipe by Mitsubishi (optional parts).
Unit : mm
DATA A3
2 - 53
Y
Y
Intake Intake
1650
air Intake
air air
2. EXTERNAL DIMENSIONS
PUHY-P1100,1150,1200,1250YSHA(-BS)
g i a
e c To indoor unit
Left view
OUTDOOR UNITS
Liquid Twinning pipe 1 <optional parts> Liquid Twinning pipe 2 <optional parts>
h j b
f d To indoor unit
Twinning pipe connection size Gas Twinning pipe 2 <optional parts>
Gas Twinning pipe 1 <optional parts>
Package unit name PUHY-P1100YSHA(-BS) PUHY-P1150YSHA(-BS) PUHY-P1200YSHA(-BS) PUHY-P1250YSHA(-BS)
Outdoor unit 1 PUHY-P400YHA(-BS) PUHY-P450YHA(-BS) PUHY-P450YHA(-BS) PUHY-P450YHA(-BS) Front view
Component unit name Outdoor unit 2 PUHY-P350YHA(-BS) PUHY-P350YHA(-BS) PUHY-P400YHA(-BS) PUHY-P450YHA(-BS)
Outdoor unit 3 PUHY-P350YHA(-BS) PUHY-P350YHA(-BS) PUHY-P350YHA(-BS) PUHY-P350YHA(-BS)
Outdoor Twinning Kit(optional parts) CMY-Y300VBK2 Liquid Gas
Unit model
Liquid a 19.05 e or g or i f or h or j
Indoor unit Twinning pipe 2
Gas b 41.28 P350 12.7 28.58
Liquid c 19.05 Twinning pipe Outdoor unit P400 15.88 28.58
Twinning pipe 1 Twinning pipe 2
Gas d 34.93 P450 15.88 28.58
Note 1.Connect the pipes as shown in the figure above. Refer to the table above for pipe size.
2.Twinning pipes should not be tilted more than 15 degrees from the ground.
Be sure to see the Installation Manual for details of Twinning pipe installation.
3.The pipe section before the Twinning pipe (sections "a", "b", "c" and "d" in the figure) must have at least 500mm of straight section
(*including the straight pipe that is supplied with the Twinning pipe).
4.Only use the Twinning pipe by Mitsubishi (optional parts).
Unit : mm
DATA A3
2 - 54