2.

EXTERNAL DIMENSIONS

760
2X5- 4.6 Hole

80 150 150 150 150


(Make hole at the plastic fan guard
for snow hood attachment) <Accessories>
18 884 18 Connecting pipe
<Snow hood attachment hole> 920 <Gas> •Elbow(ID19.05XOD19.05)···P200 1pc.
Discharge air •Elbow(ID25.4XOD25.4)···P250,P300 1pc.
Top view
•Pipe (ID25.4XOD22.2)···P250,P300 1pc.

<Liquid> •Pipe (ID9.52XOD9.52)···P200,P250 1pc.

240
Control box •Pipe (ID9.52XOD12.7)···P250 1pc.
•Pipe (ID12.7XOD12.7)···P300 1pc.
•Pipe (ID12.7XOD9.52)···P300 1pc.
PUHY-P200,250,300YHA(-BS)

Intake Intake
2. EXTERNAL DIMENSIONS

Intake air air


Note1.Please refer to the next page for information
air Refrigerant service regarding necessary spacing around the
valve <liquid> unit and foundation work.
Service

1650
2.At brazing of pipes,wrap the refrigerant service valve
panel with wet cloth and keep the temperature of

1410
refrigerant service valve under 120°C.
Refrigerant service
valve <gas> 6
4 1
NO. Usage Specifications

72
Front through hole 102X72 Knockout hole
For pipes

54
B
Bottom through hole 150X92 Knockout hole

OUTDOOR UNITS
Front through hole

132 88
65 or 40 Knockout hole

90
For wires Front through hole 52 or 27 Knockout hole
55 25 25 55 3 204 98 Bottom through hole 52 Knockout hole
760 251 102 For transmission cables Front through hole 34 Knockout hole
Left side view Front view
Connecting pipe specifications
Position dimensions
221 150
for the refrigerant Connection specifications for 251 83 2X2-14X20 Oval hole
Model service valve the refrigerant service valve*1
186
86

Liquid
18

Gas
145

Liquid Gas
A B

131
145
PUHY-P200YHA(-BS) 170 9.52 Brazed 19.05 Brazed
142 9.52 Brazed
727)

92

PUHY-P250YHA(-BS) 5
( 12.7 Brazed)*3
172 22.2 Brazed 2 Refrigerant service
(760)

9.52 Brazed Refrigerant service


PUHY-P300YHA(-BS) 143 valve <gas>
( 12.7 Brazed)*2 *4 valve <liquid>
724(721

*1 Connect by using the connecting pipes (for bottom piping and front piping)
that are supplied.
*2 Indicates dimensions and connection specifications in the case the unit is 80 760 80
18

used in combination with other outdoor units. (Mounting pitch)


*3 Total length >=90m Bottom view
Unit : mm

*4 Total length >=40m


DATA A3

2 - 45
Y
Y

1.Required space around the unit In case of collective installation


In case of single installation When multiple units are installed adjacent to each other, secure enough space to allow
for air circulation and walkway between groups of units as shown in the figures below.
Secure enough space around the unit as shown in the figure below. At least two sides must be left open.
• With a space of at least • With a space of at least As with the single installation, add the height that exceeds the height limit<h>
300mm to the wall on 100mm to the wall on to the figures that are marked with an asterisk.
the back of the unit the back of the unit If there is a wall at both the front and the rear of the unit, install up to six units
consecutively in the side direction and provide a space of 1000mm or more as inlet space/
passage space for each six units.

100 min.*
300 min.*
Wall <H> <To be left open>

100 min.*
Wall <H>

300 min.*
Front
Front
Front

Front
Front

450 min.*
Front

450 min.*
Front
PUHY-P200,250,300YHA(-BS)

Wall <H>
Wall <H>

15 min.* 15 min.* 50 min.* 50 min.*

<To be left open>


<To be left open>
<To be left open>

<To be left open>


Wall <H> 30 min.
Wall <H> 100 min.
2. EXTERNAL DIMENSIONS

450 min.* 450 min. 450 min. 100 min.*

450 min.*

450 min.*
<Top view> <Top view>
<Unit:mm> <To be left open>

When the height of the walls on the front, back or on the sides<H>
exceeds the wall height limit as defined below
add the height that exceeds the height limit <h> to the figures that
300 min.*

Wall <H> Wall<H>


300 min.*

are marked with an asterisk.


Wall <H>

15 min.*
<Wall height limit> Front :Up to the unit height

h
Back :Up to 500mm from
the unit bottom
Side :Up to the unit height

H
Front

Front
Front
Front
Front

h
900 min.
900 min.

OUTDOOR UNITS
H

Front

Unit height
500
<To be left open>

450 min. 450 min.


<To be left open>
<To be left open>

<Side view> <To be left open>


Wall <H> 1000 min.*
Corner of the
300 min.*

2.Foundation work installation leg


30mm max.

Take into consideration the surface strength, water drainage route,


piping route, and wiring route when preparing the installation site.
<Note that the drain water comes out of the unit during operation.>
Build the foundation in such way that the corner of the installation leg is M10 anchor bolt
securely supported as shown in the right figure.(Fig.A) <field supply required>
When using a rubber isolating cushion, please ensure it is large enough
to cover the entire width of each of the unit's legs. Fig.A
The protrusion length of the anchor bolt must not exceed 30mm.(Fig.A) Fixing plate
Use four fixing plates as shown in the right figure <field supply required> <field supply required>
when using post-installed anchor bolts.(Fig.B)
To prevent small animals and water and snow from entering the unit and damaging its parts, Fig.B
close the gap around the edges of through holes for pipes and wires with
filler plates <field supply required>.
When the pipes or cables are routed at the bottom of the unit,
make sure that the through hole at the base of the unit does not get blocked
with the installation base.
Refer to the Installation Manual when installing units on an installation base.
Unit : mm
DATA A3

2 - 46
760
2X5- 4.6 Hole

80 150 150 150 150


(Make hole at the plastic fan guard
for snow hood attachment) 18 1184 18
<Snow hood attachment hole>
1220
Discharge air
Top view
<Accessories>
Connecting pipe
<Gas> •Elbow(ID28.6XOD28.6)···P350,P400,P450 1pc.

240
Control box
<Liquid> •Pipe (ID15.88XOD15.88)···P350,P400,P450 1pc.
•Pipe (ID15.88XOD12.7)···P350,P400 1pc.
PUHY-P350,400,450YHA(-BS)

Intake
2. EXTERNAL DIMENSIONS

Intake
Intake air air
air Refrigerant service Note1.Please refer to the next page for information
valve <liquid> regarding necessary spacing around the
Service unit and foundation work.

1650
panel 2.At brazing of pipes,wrap the refrigerant service valve
with wet cloth and keep the temperature of

1410
Refrigerant service
valve <gas> refrigerant service valve under 120°C.

6
4 1

72

54

OUTDOOR UNITS
B
Usage

A
NO. Specifications

132 88
Front through hole 102X72 Knockout hole
For pipes

90
Bottom through hole 150X94 Knockout hole
55 25 25 55 3 254 98 Front through hole 65 or 40 Knockout hole
760 301 102 For wires Front through hole 52 or 27 Knockout hole
Left side view Bottom through hole 65 Knockout hole
Front view
271 150 For transmission cables Front through hole 34 Knockout hole
301 83 2X2-14X20 Oval hole

84
Connecting pipe specifications 216

142
18

Position dimensions Connection specifications for


for the refrigerant

131
the refrigerant service valve *1

145
Model service valve
Liquid Gas
Liquid Gas
94

A B 5
PUHY-P350YHA(-BS) 12.7 Brazed 2 Refrigerant service
(760)

12.7 Brazed Refrigerant service valve <gas>


PUHY-P400YHA(-BS) 158 172
724(721 727)

( 15.88 Brazed) 28.58 Brazed valve <liquid>


(Mounting pitch)

*2
PUHY-P450YHA(-BS) 15.88 Brazed
18

*1 Connect by using the connecting pipes (for bottom piping and front piping)
that are supplied. 80 1060 80
*2 Indicates dimensions and connection specifications in the case the unit is (Mounting pitch)
used in combination with other outdoor units. Bottom view
Unit : mm
DATA A3

2 - 47
Y
Y

1.Required space around the unit


In case of collective installation
In case of single installation When multiple units are installed adjacent to each other, secure enough space to allow
for air circulation and walkway between groups of units as shown in the figures below.
Secure enough space around the unit as shown in the figure below. At least two sides must be left open.
• With a space of at least • With a space of at least As with the single installation, add the height that exceeds the height limit<h>
300mm to the wall on 100mm to the wall on to the figures that are marked with an asterisk.
the back of the unit the back of the unit If there is a wall at both the front and the rear of the unit, install up to six units
consecutively in the side direction and provide a space of 1000mm or more as inlet space/
passage space for each six units.

100 min.*
300 min.*
Wall <H> <To be left open>

100 min.*
Wall <H>

300 min.*
Front
Front
Front

Front
Front

450 min.*
Front

450 min.*
Front
PUHY-P350,400,450YHA(-BS)

Wall <H>
Wall <H>

15 min.* 15 min.* 50 min.* 50 min.*

<To be left open>


<To be left open>
<To be left open>

<To be left open>


Wall <H> Wall <H> 100 min.
2. EXTERNAL DIMENSIONS

30 min.
450 min.* 450 min. 450 min. 100 min.*

450 min.*

450 min.*
<Top view> <Top view>
<Unit:mm> <To be left open>

When the height of the walls on the front, back or on the sides<H>
exceeds the wall height limit as defined below
add the height that exceeds the height limit <h> to the figures that
300 min.*

Wall <H> Wall<H>


300 min.*

are marked with an asterisk.


Wall <H>

15 min.*
<Wall height limit> Front :Up to the unit height

h
Back :Up to 500mm from
the unit bottom
Side :Up to the unit height

H
Front

Front
Front
Front

h
Front
900 min.

OUTDOOR UNITS
900 min.

Front

Unit height
500
<To be left open>

450 min. 450 min.


<To be left open>
<To be left open>

<Side view>
<To be left open>
Wall <H> 1000 min.*
Corner of the
300 min.*

2.Foundation work installation leg


30mm max.

Take into consideration the surface strength, water drainage route,


piping route, and wiring route when preparing the installation site.
<Note that the drain water comes out of the unit during operation.>
Build the foundation in such way that the corner of the installation leg is M10 anchor bolt
securely supported as shown in the right figure.(Fig.A) <field supply required>
When using a rubber isolating cushion, please ensure it is large enough
to cover the entire width of each of the unit's legs. Fig.A
The protrusion length of the anchor bolt must not exceed 30mm.(Fig.A) Fixing plate
Use four fixing plates as shown in the right figure <field supply required> <field supply required>
when using post-installed anchor bolts.(Fig.B)
To prevent small animals and water and snow from entering the unit and damaging its parts, Fig.B
close the gap around the edges of through holes for pipes and wires with
filler plates <field supply required>.
When the pipes or cables are routed at the bottom of the unit,
make sure that the through hole at the base of the unit does not get blocked
with the installation base.
Refer to the Installation Manual when installing units on an installation base.
Unit : mm
DATA A3

2 - 48
760 920 30 920

Discharge air Outdoor unit 1 Outdoor unit 2


PUHY-P500,550YSHA(-BS)
2. EXTERNAL DIMENSIONS

1650
Intake Intake
Intake air air
air

OUTDOOR UNITS
e a
Left view c To indoor unit
Twinning pipe connection size Liquid Twinning pipe<optional parts>
Package unit name PUHY-P500YSHA(-BS) PUHY-P550YSHA(-BS) f b
Outdoor unit 1 PUHY-P250YHA(-BS) PUHY-P300YHA(-BS) d To indoor unit
Component unit name
Outdoor unit 2 PUHY-P250YHA(-BS) PUHY-P250YHA(-BS) Liquid Gas Gas Twinning pipe<optional parts>
Unit model Front view
Outdoor Twinning Kit(optional parts) CMY-Y100VBK2 c or e d or f
Liquid a 15.88 P250 9.52 22.2
Indoor unit Twinning pipe Twinning pipe Outdoor unit
Gas b 28.58 P300 12.7 22.2

Note 1.Connect the pipes as shown in the figure above. Refer to the table above for pipe size.
2.Twinning pipes should not be tilted more than 15 degrees from the ground.
Be sure to see the Installation Manual for details of Twinning pipe installation.
3.The pipe section before the Twinning pipe (sections "a" and "b" in the figure) must have at least 500mm of straight section
(*including the straight pipe that is supplied with the Twinning pipe).
4.Only use the Twinning pipe by Mitsubishi (optional parts).
Unit : mm
DATA A3

2 - 49
Y
Y

760 1220 30 920

Discharge air Outdoor unit 1 Outdoor unit 2


PUHY-P600,650YSHA(-BS)
2. EXTERNAL DIMENSIONS

1650
Intake Intake Intake
air air air

OUTDOOR UNITS
e a
Left view c To indoor unit
Liquid Twinning pipe<optional parts>
Twinning pipe connection size f
d b To indoor unit
Package unit name PUHY-P600YSHA(-BS) PUHY-P650YSHA(-BS)
Liquid Gas Gas Twinning pipe<optional parts>
Component unit name Outdoor unit 1 PUHY-P350YHA(-BS) PUHY-P350YHA(-BS) Unit model
Outdoor unit 2 PUHY-P250YHA(-BS) PUHY-P300YHA(-BS) c or e d or f Front view
Outdoor Twinning Kit(optional parts) CMY-Y100VBK2 P250 9.52 22.2
Liquid a 15.88 Twinning pipe Outdoor unit P300 12.7 22.2
Indoor unit Twinning pipe
Gas b 28.58 P350 12.7 28.58

Note 1.Connect the pipes as shown in the figure above. Refer to the table above for pipe size.
2.Twinning pipes should not be tilted more than 15 degrees from the ground.
Be sure to see the Installation Manual for details of Twinning pipe installation.
3.The pipe section before the Twinning pipe (sections "a" and "b" in the figure) must have at least 500mm of straight section
(*including the straight pipe that is supplied with the Twinning pipe).
4.Only use the Twinning pipe by Mitsubishi (optional parts).
Unit : mm
DATA A3

2 - 50
760 1220 30 1220

Discharge air Outdoor unit 1 Outdoor unit 2


2. EXTERNAL DIMENSIONS

1650
Intake Intake Intake
air air
PUHY-P700,750,800,850,900YSHA(-BS)

air

OUTDOOR UNITS
e a
Left view c To indoor unit
Liquid Twinning pipe<optional parts>
f b
d To indoor unit
Twinning pipe connection size Gas Twinning pipe<optional parts>
Package unit name PUHY-P700YSHA(-BS) PUHY-P750YSHA(-BS) PUHY-P800YSHA(-BS) PUHY-P850YSHA(-BS) PUHY-P900YSHA(-BS)
Front view
Outdoor unit 1 PUHY-P350YHA(-BS) PUHY-P400YHA(-BS) PUHY-P450YHA(-BS) PUHY-P450YHA(-BS) PUHY-P450YHA(-BS) Liquid Gas
Component unit name Unit model
Outdoor unit 2 PUHY-P350YHA(-BS) PUHY-P350YHA(-BS) PUHY-P350YHA(-BS) PUHY-P400YHA(-BS) PUHY-P450YHA(-BS) c or e d or f
Outdoor Twinning Kit(optional parts) CMY-Y200VBK2 P350 12.7 28.58
Liquid a 19.05 Twinning pipe Outdoor unit P400 15.88 28.58
Indoor unit Twinning pipe
Gas b 34.93 41.28 P450 15.88 28.58

Note 1.Connect the pipes as shown in the figure above. Refer to the table above for pipe size.
2.Twinning pipes should not be tilted more than 15 degrees from the ground.
Be sure to see the Installation Manual for details of Twinning pipe installation.
3.The pipe section before the Twinning pipe (sections "a" and "b" in the figure) must have at least 500mm of straight section
(*including the straight pipe that is supplied with the Twinning pipe).
4.Only use the Twinning pipe by Mitsubishi (optional parts).
Unit : mm
DATA A3

2 - 51
Y
Y

760 1220 30 920 30 920

Discharge air Outdoor unit 1 Outdoor unit 2 Outdoor unit 3 PUHY-P950,1000YSHA(-BS)

Intake
Intake

1650
air
2. EXTERNAL DIMENSIONS

Intake air
air

g i a

OUTDOOR UNITS
e c To indoor unit
Left view
Liquid Twinning pipe 1 <optional parts> Liquid Twinning pipe 2 <optional parts>
h j b
f d To indoor unit
Twinning pipe connection size Gas Twinning pipe 1 <optional parts> Gas Twinning pipe 2 <optional parts>
Package unit name PUHY-P950YSHA(-BS) PUHY-P1000YSHA(-BS)
Outdoor unit 1 PUHY-P400YHA(-BS) PUHY-P400YHA(-BS) Front view
Component unit name Outdoor unit 2 PUHY-P300YHA(-BS) PUHY-P300YHA(-BS)
Outdoor unit 3 PUHY-P250YHA(-BS) PUHY-P300YHA(-BS)
Outdoor Twinning Kit(optional parts) CMY-Y300VBK2 Unit model
Liquid Gas
a 19.05 e or g or i f or h or j
Indoor unit Twinning pipe 2 Liquid
Gas b 41.28 P250 9.52 22.2
Liquid c 19.05 Twinning pipe Outdoor unit P300 12.7 22.2
Twinning pipe 1 Twinning pipe 2
Gas d 34.93 P400 15.88 28.58

Note 1.Connect the pipes as shown in the figure above. Refer to the table above for pipe size.
2.Twinning pipes should not be tilted more than 15 degrees from the ground.
Be sure to see the Installation Manual for details of Twinning pipe installation.
3.The pipe section before the Twinning pipe (sections "a", "b", "c" and "d" in the figure) must have at least 500mm of straight section
(*including the straight pipe that is supplied with the Twinning pipe).
4.Only use the Twinning pipe by Mitsubishi (optional parts).
Unit : mm
DATA A3

2 - 52
760 1220 30 1220 30 920

Discharge air Outdoor unit 1 Outdoor unit 2 Outdoor unit 3


PUHY-P1050YSHA(-BS)

Intake Intake

1650
air Intake
2. EXTERNAL DIMENSIONS

air air

OUTDOOR UNITS
Left view g i a
e c To indoor unit
Liquid Twinning pipe 2 <optional parts>
Liquid Twinning pipe 1 <optional parts>
j
Twinning pipe connection size h d b
f To indoor unit
Package unit name PUHY-P1050YSHA(-BS) Gas Twinning pipe 2 <optional parts>
Outdoor unit 1 PUHY-P400YHA(-BS) Gas Twinning pipe 1 <optional parts>
Component unit name Outdoor unit 2 PUHY-P350YHA(-BS) Front view
Outdoor unit 3 PUHY-P300YHA(-BS)
Outdoor Twinning Kit(optional parts) CMY-Y300VBK2 Liquid Gas
Unit model
Liquid a 19.05 e or g or i f or h or j
Indoor unit Twinning pipe 2
Gas b 41.28 P300 12.7 22.2
Liquid c 19.05 Twinning pipe Outdoor unit P350 12.7 28.58
Twinning pipe 1 Twinning pipe 2
Gas d 34.93 P400 15.88 28.58

Note 1.Connect the pipes as shown in the figure above. Refer to the table above for pipe size.
2.Twinning pipes should not be tilted more than 15 degrees from the ground.
Be sure to see the Installation Manual for details of Twinning pipe installation.
3.The pipe section before the Twinning pipe (sections "a", "b", "c" and "d" in the figure) must have at least 500mm of straight section
(*including the straight pipe that is supplied with the Twinning pipe).
4.Only use the Twinning pipe by Mitsubishi (optional parts).
Unit : mm
DATA A3

2 - 53
Y
Y

760 1220 30 1220 30 1220

Discharge air Outdoor unit 1 Outdoor unit 2 Outdoor unit 3

Intake Intake

1650
air Intake
air air
2. EXTERNAL DIMENSIONS

PUHY-P1100,1150,1200,1250YSHA(-BS)

g i a
e c To indoor unit
Left view

OUTDOOR UNITS
Liquid Twinning pipe 1 <optional parts> Liquid Twinning pipe 2 <optional parts>
h j b
f d To indoor unit
Twinning pipe connection size Gas Twinning pipe 2 <optional parts>
Gas Twinning pipe 1 <optional parts>
Package unit name PUHY-P1100YSHA(-BS) PUHY-P1150YSHA(-BS) PUHY-P1200YSHA(-BS) PUHY-P1250YSHA(-BS)
Outdoor unit 1 PUHY-P400YHA(-BS) PUHY-P450YHA(-BS) PUHY-P450YHA(-BS) PUHY-P450YHA(-BS) Front view
Component unit name Outdoor unit 2 PUHY-P350YHA(-BS) PUHY-P350YHA(-BS) PUHY-P400YHA(-BS) PUHY-P450YHA(-BS)
Outdoor unit 3 PUHY-P350YHA(-BS) PUHY-P350YHA(-BS) PUHY-P350YHA(-BS) PUHY-P350YHA(-BS)
Outdoor Twinning Kit(optional parts) CMY-Y300VBK2 Liquid Gas
Unit model
Liquid a 19.05 e or g or i f or h or j
Indoor unit Twinning pipe 2
Gas b 41.28 P350 12.7 28.58
Liquid c 19.05 Twinning pipe Outdoor unit P400 15.88 28.58
Twinning pipe 1 Twinning pipe 2
Gas d 34.93 P450 15.88 28.58

Note 1.Connect the pipes as shown in the figure above. Refer to the table above for pipe size.
2.Twinning pipes should not be tilted more than 15 degrees from the ground.
Be sure to see the Installation Manual for details of Twinning pipe installation.
3.The pipe section before the Twinning pipe (sections "a", "b", "c" and "d" in the figure) must have at least 500mm of straight section
(*including the straight pipe that is supplied with the Twinning pipe).
4.Only use the Twinning pipe by Mitsubishi (optional parts).
Unit : mm
DATA A3

2 - 54