Platform Tuning
References
Smart Platform 700 Installation and Maintenance 101764-004
Smart Platform 1200 Installation and Maintenance 101764-003
Platform Tuning also requires a measuring tape
Follow the book exactly! Failure to do so can produce a platform that will remove body
parts, especially if the torque pot V/F is set to high on Fincor/Lovejoy Motor controllers.
Use the SP 700 manual, since platform tuning is identical for both platforms, except for
the Wrap Around dimension.
Open the manual to Page 75, Section 5 Platform Tuning
Turn to page 76
Check the Health Reports [E] Electronics page. Look at the top right hand corner of any
health report page. Make sure the variable Safety Interrupt is reset.
If it is set use the information on the Electronics page to correct the fault.
Check for alarms while tuning the frame. Refer to Section 11, page 247 for the following
alarms.
Motor Stopped by Obstacle - usually the Fincor motor controller is set up incorrectly. The
torque pot V/F is set too low. The difference between scanning and not scanning can be the
width of a screw driver blade, on either side of the correct setting.
Head Speed Inconsistency - usually results from improper setup of Minimum Velocity
Setup of the Motor controller and Basic Smart Platform Tuning -Head Position Calibration
and Automatic Motor Controller tuning are the only parts of ft, that needs to be performed
as part of tuning.
All other entries can be made using the Health Pages on the Smart Platform Service Work
Station.
4-3
C232 AccuRay Smart Platform Maintenance Course
1 2
MODIFY DISPLAY
1 2 3 4 5 6 7 8
CURRENT
SCANNER
POSITION
2
1 CURRENT
2
HEAD POSITION
MOTOR
3 CURRENT
CONTROLLER
SCANNER
4 REVIEW * *
* MOTOR 5
CONTROLLER
CURRENT
6 ENGINEERING
SCANNER
SCANNER/SHEET
POSITION
CURRENT CURRENT
SERVO AEOS
VALUES
SCANNER
SPEED
SCANNING
SCANNER
AUTO EDGE
SETUP 1
1 Scanning Monitor
2 Servo Global Data
3 Servo State Data
MANUAL
4 Servo Timing Data
SERVO
5 Servo Trajectory Data
6 Servo Tuning Data
7 Frame Data
4-4
4 - Platform Tuning
4-5
C232 AccuRay Smart Platform Maintenance Course
4-6
4 - Platform Tuning
Verify the value by splitting the heads. Leave the upper head alone, move the lower head.
The tac is connected to the upper head
measure the distance, end column to center of the window. The value should be with in.25
mm or .01 inch.
If the value is correct enter n
Step 9. The software will ask if you want to use automatic or manual tuning. Say m, for
manual
Automatic mode never stops in the same place twice. Where the head stops depends on
how fast it was going when it hit the limit switch
Press enter when the head package is positioned at the far end column
Read the value at the service work station and verify by measuring
Say n to complete this part of the setup.
Step 10. The software asks about a centerline. This feature is only for Tetra-Pak Scanners.
Paper Scanners do not use this feature. Type n
Step 14. Move the head package to the center of the platform, before Step 14.
If the head is left sitting on a limit switch it will not move! The platform will abort
automatic servo tune process
If you have an ACS-110 drive controller, go to page 4 of the F -frame health report,
set slow dac to 40.This is a more realistic number, for the new controller, since it is more
sensitive and capable of slower speeds.
At the completion of the tuning process the software will perform automatic gstores.
Step 18, page 98, the Vmin Self-tuning flag is accessed by selecting the F- Frame health
report
Press F6 until you have the Servo Setup parameters.
Use The TAB key and arrow keys to select DDC Vmin Self-Tuning. Turn on, by pressing
the space bar.
The platform should be scanning for this feature to work. When the heas is scanning turn
on Vmin Self-tuning for four scans. After four scans turn the flag off. The software will
select a value for Vmin that ensures proper scanning.
Beginning at Page 98, to the end of the Section, all entries are made using the [F] - Frame
Health report.
Use the position values, on the next page. These are example values, for laboratory use
only. Actual values for an individual smart Platform will be determined by sheet position
on the paper machine.