REPORT FOR PRECISION AIR CONDITIONING SYSTEM

Customer Model
Date Time Serial Number
Status Maintenance ( ) On Call ( ) Start Up & Commissioning ( ) Warranty ( )

ITEM CHECKED SPEC. RANGE* ACTUAL CHECKED REMARKS


ELECTRICAL POWER SUPPLY
1 Voltage line to Neural Ground 220 + 10% L1/L2/L3 =…………………………………….V
2 Voltage line to line 380 + 10% L1L2/L2L3/L1L3=…………………………………….V
3 Frequency 50 + 10% F =…………………………………….Hz
4 Fuses & Cable Connection Ok or No ………………………………………………………………………………
FILTERS SECTION
1 Check Filters Condition Clean or Dirty ………………………………………………………………………………
2 Check Filters Clog Switch Ok or No ………………………………………………………………………………
Blower 1
BLOWER SECTION Blower 2 Blower 3
1 Motor Mounting Ok or No
2 Fan Belt Ok or No
3 Fan Safety Switch Ok or No
4 Bearing Ok or No
5 Pulley Ok or No
6 Current FLA =……………………….A
COMPRESSOR SECTION
1 Check Current Comp 1 & 2 OA…………………………..A
2 Suction Pressure 55 - 90 PsiG
3 Discharge Pressure 200 - 90 PsiG
4 Oil Level Ok or No
5 Leakage No or Yes
SIGHT GLASS Ok or No Circuit 1( ) Circuit 2 ( ) Circuit 3 ( )
REHEAT
1 Check Current Element Operation FLA =……………………….A L1/L2/L3 = Amp
HUMIDIFIER
1 Make Up Water Valve Ok or No ………………………………………………………………………………
2 Water Level Sensor Ok or No ………………………………………………………………………………
3 Infra Red / Steam Current FLA =……………………….A L1/L2/L3 = Amp
AIR COOLED CONDENSOR
1 Check Condensor Coil Clean or Dirty ………………………………………………………………………………
2 Bearing Ok or No ………………………………………………………………………………
3 Check Current Element Operation FLA =……………………….A L1/L2/L3 = Amp
4 Condition Arround Area Condensor Ok or No
WATER COOLED / CHILED WATER
1 Water Temperature / Pressure In …...….……0C.……...…Psi …...….……0C.……...…Psi
2 Water Temperature / Pressure Out …...….…… C.……...…Psi
0
…...….……0C.……...…Psi
GENERAL FUNCTION
1 Cooling Test Ok or No ………………………………………………………………………………
2 Hesting Test Ok or No ………………………………………………………………………………
3 Humidification Test Ok or No ………………………………………………………………………………
4 Dehumidification Test Ok or No ………………………………………………………………………………
5 Alarm Test Ok or No ………………………………………………………………………………
ROOM CONDITION Set Point/Sensitivity Aktual
1 Temperature …..…………………………….. C 0
…..……………………………..0C
2 Humidity ……..…………………………...% ……..…………………………...%

Note By PT Solusi Mandiri Sejahtera : Note By Customer :

Dibuat oleh : Mengetahui :


Technician / Engineer Customer Acknowledgement

Nama Nama
Tanggal Tanggal
1.Keuangan SMS (Putih) 2.Customer (Merah) 3.Teknisi SMS (Kuning)