Professional Documents
Culture Documents
At the outset, we thank you for purchasing chiller manufactured and supplied by
KIRLOSKAR CHILLERS PRIVATE LIMITED. We are sure that our chiller will help you in
satisfying your chilling requirement.
This manual will guide you about the installation, Operation and maintenance of the system.
Please read this manual carefully and keep it in proper place in order to refer the same
whenever required. To prolong the life of your chiller and reduce maintenance cost, follow
the instructions given in this manual.
2. Installation ……………………………………………………………………………... 9
2.1. Space Requirement for Servicing …………………………………………………. 9
2.2. Unit Location ……………………………………………………………………… 9
2.3. Evaporator Water / Brine (Liquid) Piping ………………………………………… 10
2.4. Foundation and Anti-Vibration Mounts …………………………………………… 11
2.4.1. Foundation …………………………………………………………………… 11
2.4.2. Anti-Vibration Mounts ……………………………………………………… 12
2.5. Water Treatment / Quality ………………………………………………………… 12
2.6. Installation of Flow Switch……………………………….……………………….. 14
2.7. Installation Check Report for KAC Chiller Units ………………………………… 14
3. Operation ………………………………………………………………………………. 16
3.1. Liquid Chilling Systems - Principle ………………………………………………. 16
3.2. Components and Their Functions …………………………………………………. 17
3.3. Equipment Description and Cycle Operation ……………………………………… 18
3.3.1. Hermetic Type Scroll Compressor …………………………………………….. 19
3.3.2. Air Cooled Condenser …………………………………………………………. 20
3.3.3. Electronic Expansion Valve …………………………………………………… 21
3.3.4. Dry-Expansion Type Evaporator ……………………………………………… 21
3.3.5. Control Center …………………………………………………………………. 21
3.3.6. System Accessories ……………………………………………………………. 22
3.4. Preparing the System for Start-Up ………………………………………………… 22
3.5. Startup and Operation ……………………………………………………………... 23
3.6. Stop or Weekend or Temporary Shutdown ………………………………………. 24
3.7. Extended Shutdown ………………………………………………………………. 24
3.8. Recommended Log Format for KAC Units ………………………………………. 25
3.9. Sequence of Operation for Packaged Chiller Units ……………………………….. 26
3.10. Standard Controls ………………………………………………………………… 28
3.10.1. High Pressure Control ………………………………………………………... 28
3.10.2. Low Pressure Control ………………………………………………………… 28
3.10.3. Voltage Protection Device …………………………………………………… 29
4. System Maintenance…………………………………………………………………… 30
4. Maintenance Instruction……………………………………………………………… 30
4.1. Tips for Preventive Maintenance…………………………………………………… 30
4.2. System Service……………………………………………………………………… 32
4.2.1. Condenser and Evaporator……………………………………………………… 32
4.2.1.1. Air-Cooled Condensers …………………………………………………….. 32
4.2.1.2. Evaporator ………………………………………………………………….. 33
4.2.1.3. Testing Of Condenser and Evaporator Tube Leaks………………………… 33
4.2.2. Liquid Refrigerant Drier Replacement ………………………………………… 34
4.2.3. Refrigerants …………………………………………………………………….. 34
4.2.4. Vacuum / Dehydration Procedure ……………………………………………… 34
4.2.5. Refrigerant Properties …………………………………………………………. 35
4.2.5.1. Charging the Refrigerant…………………………………………………… 35
4.2.5.2. Adjusting the Refrigerant Charge…………………………………………. 36
4.2.5.3. Pressure Testing After Service or Repair or Major Leak ………………….. 36
Chapter 5 Troubleshooting 38
8. Annexures ……………………………………………………………………………... 58
8.1. Start-Up and Check Form …………………………………………………………. 58
Chiller Nomenclature
KA C 011 . 2 0
0- R-410A
No. of Compressors
Nominal capacity, TR
Scroll compressor
Operating Limits
Description Unit R-410A
KAC
Min leaving evaporator water ºC 3 ºC
temperature (without glycol) (ºF) ( 37.4 ºF)
Kirloskar Chillers make liquid chillers are designed for safe and reliable operation, when
operated within design limits. When operating this equipment, use good judgment and safety
precautions to avoid damage to equipment, property or injury to personnel. Be sure that you
understand and follow the procedure and safety precautions.
When working on the equipment, observe precautions in the literature, tags, stickers attached to
the equipment.
DO NOT CLIMB over the chiller or DO NOT STEP on refrigerant lines. Broken lines
can bang and release high-pressure refrigerant, causing personal injury.
USE platform, catwalk or staging. Follow safe practices when using ladders.
NEVER SHORT CIRCUIT any safety controls in the system.
Care in HANDLING & RIGGING; check weight before rigging any item. Always use
lifting hooks provided in the unit. Use suitable capacity crane to lift the unit
DO NOT ATTEMPT TO REMOVE pipefitting, flanges, covers etc., while chiller is
under pressure OR chiller is running. Ensure the pressure is at 0 kg/cm2g (0 psig) before
opening any refrigerant line OR connection.
WORK CAREFULLY, when working near OR in line with a compressed spring. Sudden
release of the spring can cause it and objects in its path to act as projectiles.
PERIODICALLY INSPECT all valves, fittings and piping for corrosion, rust, leaks OR
damages.
DRAIN WATER completely before loosening the bolts of water box / heat exchanger
dish ends.
USE ONLY DRY NITROGEN for pressure test. Use a regulating valve between the
Nitrogen cylinder and the system to regulate the pressure.
DO NOT USE OXYGEN or ACETYLENE to pressurize the refrigeration system.
Oxygen may react with oil and form an explosive chemical compound. Acetylene is an
explosive gas.
HANDLE THE CYLINDERS carefully. Do not drop the cylinder.
NEVER EXCEED specified TEST PRESSURE; verify the allowable test pressure by
checking the equipment nameplate. Contact Kirloskar Chillers if in doubt for further
details.
Refrigerant
Sharp Edges
The fins on the air-cooled condenser coils have sharp metal edges. Reasonable care should be
taken when working in contact with the coils to avoid the risk of minor abrasions and lacerations.
The use of gloves is recommended. Frame rails, brakes, and other components may also have
sharp edges. Reasonable care should be taken when working in contact with any components to
avoid risk of minor abrasions and lacerations.
Mechanical Strength
The unit is not designed to withstand loads or stresses from adjacent equipment, pipework or
structures. Additional components must not be mounted on the unit. Any such extraneous loads
may cause structural failure and may result in injury to the operator, or damage to the equipment.
The unit is intended for cooling water and is not suitable for purposes other than those specified
in these instructions. Any use of the equipment other than its intended use, or operation of the
equipment contrary to the relevant procedures may result in injury to the operator, or damage to
the equipment. The unit must not be operated outside the design parameters specified in this
manual.
Each KAC unit consists of air-cooled condensers with integral sub-cooler sections, multiple
hermetic compressors, direct expansion (Dx) type shell-and-tube evaporator, complete
refrigerant piping and control panel.
Refrigerant piping components include compressor suction and discharge, main liquid line, main
liquid line filter driers, electronic expansion valves. The control panel includes all safety and
operating controls necessary for dependable automatic operation. Compressors are fused in all
three phases and started by respective three-pole contactors.
A scroll compressor actually consists of two scrolls or spirals. One scroll is moving, whereas
the second one is fixed (attached to the compressor body). The first scroll orbits (rotates) in a
path defined by fixed scroll. The orbiting scroll is connected to the compressor's crankshaft. As a
result of the scroll's movement, gas pockets are formed between the two scrolls. At the outer part
of the scrolls, the pockets suck in gas and then move towards the center of the scroll, where the
compressed gas is discharged. As the gas moves into the continuously smaller internal pockets,
both its temperature and pressure are increased. Thus a desirable discharge pressure is achieved
by the motion of the compressor scrolls.
1.2.2. Reliability
Testing of all units ensures a trouble free start-up. Extensive tests make sure that all safety
controls are adjusted properly and operate correctly.
NOTE: DO THE LEAK CHECK BEFORE INSULATING THE CHILLED LIQUID PIPE.
h) Flow control devices such as balancing valves shall be mounted in the chilled liquid piping to
have the controlled and constant liquid flow. Refer design data sheet for the evaporator liquid
flow rate data.
2.4.1. Foundation
Kirloskar Chillers make KAC units have very minimum vibrations and do not require any special
type of mounts. These units can be set directly on the floor with the mounting pads supplied
along with the unit. For further details refer Fig. 2.4.1a.
a) Unit must be mounted on flat and level foundation, floor capable of supporting the entire
operating weight of the equipment. Refer the enclosed unit general arrangement drawing OR
physical data sheet for operating weight.
b) When floors are weak or of inadequate strength, supplementary structural OR concrete
supports must be provided. Such kind of supplementary supports must be designed to distribute /
transfer the unit weight to the nearest stronger beams.
If the unit is operating with a cooling tower (KAC units), clean and flush the cooling tower.
Make sure that the tower “blow-down” or “bleed-off” is operating. Atmospheric air contains
many contaminants, which increases the need for water treatment. This is also applicable for
liquid chiller / evaporator side.
The use of untreated water in cooling towers, closed water systems etc. frequently results in one
or more of the following:
KIRLOSKAR CHILLERS PRIVATE LIMITED
A Kirloskar Group Company IOM-KAC-ENG - Page 12
a) Scale formation
b) Corrosion or erosion
c) Slime and Algae formation and the growth of the bacterium Legionella pneumophila
(Legionnaires Disease).
It is therefore to the benefit of the end user to provide for proper water treatment to provide for
longer and more economical life of the equipment. The following recommendation is to
understand the condition of the water.
Flow switch installation: Mount individual flow switch in the leaving water line of the
evaporator and condenser. Refer Fig. 2.3a for flow switch installation.
SR PARTICULARS
No
1 UNIT:
1. In case of transit damage, has it been attended completely?
2. Is there any damage during installation?
3. If any damage as per #2, has it been attended?
4. Whether unit is mounted as per recommendations?
5. Is there free space available to attend compressor(s)?
3 AIR-COOLED CONDENSERS:
1. Sufficient space allowed for cleaning and replacing tubes.
2. Air vent and Water drain valves are provided.
3. Flow switch is mounted in the leaving water line
4. Service valves are provided for de-scaling / servicing
4 EVAPORATOR / CHILLER:
1. Sufficient space allowed for air entry & service facilities?
2. Coil guard provided
5 POWER AND CONTROL PANEL:
Sufficient space allowed for accessing and servicing the panel.
6 MISCELLANEOUS:
Sufficient space allowed to access and attend refrigerant liquid line valves,
Electronic expansion valves and moisture & liquid flow indicator.
Compressor
Condenser,
Evaporator
Refrigerant and
In cooler / evaporator, entering hot liquid (usually water) is cooled by the evaporating refrigerant
which is at a lower pressure and lower temperature. The evaporated refrigerant is drawn by the
compressor, which increases the temperature and pressure of the gas above ambient temperature
KIRLOSKAR CHILLERS PRIVATE LIMITED
A Kirloskar Group Company IOM-KAC-ENG - Page 16
in case of air-cooled and above entering water in case of water cooled, so that it may be
condensed at the higher temperature in the condenser.
The cooling medium is circulated through the condenser to condense the high pressure & high
temperature refrigerant vapors. The condensed liquid refrigerant then flows back to the
evaporator through an expansion device. A fraction of the liquid refrigerant flashes to vapor as
the pressure drops between the condenser pressure and the evaporator pressure at the expansion
valve. In evaporator the low pressure and low temperature liquid refrigerant evaporates and the
process continues.
b) CONDENSER in the vapor compression cycle is a heat exchanger, which rejects heat from
the refrigerant to the condensing medium. The function of condenser in a refrigeration system is
to de-superheat, condense and sub cool the discharged refrigerant vapor from compressor.
Condensers may be water-cooled type OR aircooled type OR evaporative type. Condenser in
water-cooled versions may be tube-in-tube, shell-and-coil, shell-and-tube or plate type heat
exchangers. Between air-cooled and evaporative type, air-cooled condensers are more common.
Less maintenance is required for air-cooled heat exchangers than the evaporative type.
Capillary tubes
d) EVAPORATOR in the vapor compression cycle is a heat exchanger in which the heat is
rejected by the fluid to be cooled to the refrigerant. Principally the evaporators can be classified
as dry type and flooded type. As the name implies, flooded evaporators have submerged liquid
refrigerant coverage over the heat transfer surface. Dx type of evaporator are used in KAC
chillers. Evaporator in liquid-chilling versions may be either tube-in-tube, shell and-coil, shell-
and-tube or plate type heat exchangers.
e) REFRIGERANT is the working fluid, which absorbs heat from the fluid to be cooled and
rejects heat to the atmosphere, through evaporation and condensation. The refrigerant does not
undergo any chemical change as far as there is no contamination of moisture or air. It alternately
vaporizes from the liquid state to absorb heat in evaporator and by rejecting heat in condenser
where it condenses into a liquid for reuse in evaporator. The refrigerant should possess certain
chemical, physical and thermodynamic properties to make it safe and economical for use in the
refrigeration system.
f) CONTROL PANEL is the control center, which contains all the necessary switchgear
components and control section for safe operation of the refrigeration plant.
Control panel
In a Performer scroll compressor, the compression is performed by two scroll elements located in
the upper part of the compressor.
Suction gas enters the compressor at the suction connection. As all of the gas flows around and
through the electrical motor, thus ensuring complete motor cooling in all applications, oil
droplets separate and fall into the oil sump. After exiting the electrical motor, the gas enters the
scroll elements where compression takes place. Ultimately, the discharge gas leaves the
compressor at the discharge connection.
The figure below illustrates the entire compression process. The center of the orbiting scroll (in
grey) traces a circular path around the center of the fixed scroll (in black). This movement
creates symmetrical compression pockets between the two scroll elements. Low-pressure suction
gas is trapped within each crescent-shaped pocket as it gets formed; continuous motion of the
orbiting scroll serves to seal the pocket, which decreases in volume as the pocket moves towards
the center of the scroll set increasing the gas pressure. Maximum compression is achieved once a
pocket reaches the center where the discharge port is located; this stage occurs after three
complete orbits. Compression is a continuous process: the scroll movement is suction,
compression and discharge all at the same time.
Oil levels in the oil equalizing line sight glass should be between the bottom and the middle of
the sight glass with the system OFF. High oil levels may cause excessive oil carryover in the
system. High oil concentration in the system may cause nuisance trips resulting from incorrect
readings on the level sensor and temperature sensors. Temperature sensor errors may result in
poor liquid control and resultant liquid overfeed and subsequent damage to the compressor.
While running, a visible sign of oil splashing in the sight glass is normal.
Higher capacity scroll compressors come equipped with a sight glass which may be used to
determine the amount and condition of the oil contained within the sump.
Compressor Heaters
If power is OFF more than two hours, the crankcase heaters must be energized for 18 – 24 hours
prior to restarting a compressor. This will assure that liquid slugging and oil dilution does not
damage the compressors on start
All KAC units are equipped with compactly packed air-cooled condensers. These air-cooled
condensers are manufactured with the latest technology 9.53mm (3/8”) O.D internally enhanced
seamless copper tubes and super-slit aluminum fins. The copper tubes are precisely expanded
and brazed to the corresponding headers. These condensers are provided with the separate sub-
cooler circuit to get positive liquid subcooling of condensed high pressure liquid refrigerant.
The KAC systems are equipped with Electronic expansion valve (EXV). Every EXV will:
Expand the high pressure, high temperature liquid refrigerant to low pressure, low temperature
refrigerant and
Precisely feed the required quantity of expanded low pressure, low temperature liquid
refrigerant into the evaporator to maintain the constant super-heat at the evaporator outlet.
The “K-smart’ Controller will calculate the suction refrigerant vapor super-heat at the outlet of
the evaporator by sensing saturated evaporator temperature and suction line temperature through
temperature sensors. The controller will manage the opening of the electronic expansion valve
based on preset suction superheat value. The unit comes with factory-preset super-heat and
normally does not require any field adjustment.
The KAC units are equipped with compact shell-and-tube type dry expansion evaporators (U-
bundle design). These evaporators are manufactured with the latest technology 9.53 mm (3/8”)
O.D integrally grooved copper tubes having high heat transfer properties. These tubes are
precisely expanded into the tube-sheet to form leak tight joints. For high-performance and
minimum pressure drop values, all evaporators are provided with special pass partition assembly
on refrigerant side and special baffle assembly on liquid side.
KAC chillers consist of microprocessor based control section and power section.
a) Power section includes all necessary switchgear components for hermetic type compressor
motor.
b) Control section includes all necessary safety and operating controls necessary for dependable
automatic unit operations.
The control section will automatically control the unit based on the load requirement of the
secondary system, the leaving chilled liquid temperature. Refer the controller operation manual
for details.
a) Compressor Isolation & Liquid Line Valves: Every hermetic type scroll compressor is
provided with ball valves in the liquid line. For easy service access in refrigerant side; service
valves are mounted at each suction, discharge and liquid lines. The Electronic expansion valve is
mounted on liquid line after the filter drier.
b) Liquid Line Filter Drier: The Filter drier assembly is provided on liquid line. This Filter drier
removes moisture as well as foreign particles.
The maximum voltage deviation is the largest difference between a voltage measurement
across two legs and the average across all three legs. Example:
a) Supply Voltage is 415 V, 3 Ph, 50 Hz Voltage across RY = 410V Voltage across YB =
419V Voltage across BR = 405V Average = 411.33V
b) Maximum deviation from average voltage: RY = 1.33V; YB = 7.67V; BR = 6.33V
Hence, maximum deviation is 7.67V
g) The unit might have been shipped from factory with the liquid line valves closed.
Open the refrigerant line valve.
h) Check and inspect all evaporator liquid piping. Make sure that the flow direction is
correct and piping is made to correct water nozzle connections on the respective heat
exchangers and open the isolation valves of secondary side.
i) Start manually evaporator liquid pumps. Check all piping for leaks. Vent the air from
the evaporator liquid header / from the entire secondary system.
j) The secondary circuit in the evaporator side should contain clean, non-corrosive
liquid.
k) Set the required liquid flow with the help of balancing valve(s) or any other flow
measuring device, the flow rate data is given in the unit design and physical data sheet.
l) Ensure that adequate load is available for initial start-up.
a) Turn the RUN/STOP circuit switches to STOP position. Each circuit will pump-down
and the respective compressor to STOP position.
b) After the circuits have been pumped down stop the evaporator / chiller liquid pump(s).
NOTE: FOR TEMPORARY SHUTDOWNS, KEEP THE UNIT’S
POWER SUPPLY ON.
NOTE:
a) This is a sample recommended log sheet format given only for guidance. Customer shall have
a detailed log than the sample shown here.
b) Operational data of the unit shall be recorded for minimum interval of two hours of operation.
d) It is customer’s responsibility to send the log readings once in fortnight to Kirloskar Chillers
Pvt. Ltd., Service department at Head Office. This may help KCPL to keep continuous
monitoring of unit for its trouble free operation
This is a manual reset type pressure controlled electromechanical device used as safety cutout
against high discharge pressure. When the discharge pressure OR saturated condensing pressure
increases beyond the high-pressure set point, this control opens the compressor motor power
circuit, causing the compressor to stop. Press manual reset button for resetting the controller.
Refer controls, setting and functions section for set point details.
Checking Control Operation - (This test has to be performed only in presence of Kirloskar
Chillers authorized service personal)
b) When the discharge pressure rises above the control cut-out set point, the control should stop
the compressor.
This is an auto reset type pressure controlled electromechanical device used as safety cutout
against low discharge pressure.
When the suction pressure OR saturated evaporation pressure decreases below the low pressure
set point, this control opens the compressor motor power circuit, causing the compressor to stop.
Refer controls, setting and functions section for set point details.
Checking Control Operation - (This test has to be performed only in presence of Kirloskar
Chillers authorized service personal)
a) To check the control, either close the liquid line shut off valve or switch off the pilot solenoid
valve, which in-turn close the electronic expansion valve.
c) When the suction pressure drops lower than the control set point, the control should stop the
compressor.
The KAC liquid chilling package unit comes along with voltage protection device, having
manual reset. The VPD is incorporated in the unit to safe-guard the hermetic compressor motor
failure from:
Under & over voltage on any of the above fault condition, the VPD will trip the compressor
with the indication in the panel.
4. Maintenance Instructions
A conscientiously administered inspection and maintenance program will enhance the value of
the package chiller by:
Under normal conditions, the packaged chiller will require nothing more than periodic thorough
visual inspections to assure operation at maximum performance. Maintenance and inspections
shall be handled by qualified service person. If the operator of the package unit has limited
refrigeration and electrical maintenance knowledge, he should confine his maintenance of the
equipment to periodic inspection, filter service and cleaning of condenser coils (in air-cooled
units) only.
a) Record readings as detailed earlier and maintain the ‘LOG-BOOK’ in plant room.
b) Maintain history of parts used with date and reason for replacement.
e) Keep the condenser coil surface clean. If required, perform the cleaning operation.
f) Safety guards must be in place after any service and before operation.
h) Use correct chiller parts as per our recommendation. Always mention correct part number /
description, refer spare part manual for details.
j) Check the oil level. Oil level should cover one half of the oil sight glass.
k) Never close valves on pressure, never close liquid lines during normal operation, and never
close valves before safety devices.
l) Tighten the cables and electrical connections every month. Study the wiring diagram before
attending any service on control panel.
n) If liquid flood back occurs in compressor, do not run the compressor. Investigate and rectify
the defects.
WARNING:
The warranty becomes void if the wiring is not in accordance with Kirloskar Chillers
specifications.
The warranty is void if the settings on any of the protection devices are altered.
A blown fuse or tripped protector indicates a short ground or overload. Before replacing the
fuse or restarting the compressor, the cause must be found and corrected. Unqualified tampering
with the controls can cause serious damage to equipment and void the warranty.
Maintain history of service and any type of work done, including refrigerant charging, filter
drier changing, strainer cleanup / changing, compressor overhaul, electrical component failure
replacement etc.
In case of any failure, these details will enable us to approach the problem in correct path.
The KAC units are mounted with air-cooled condensers. Generally, no maintenance is required
except the occasional removal of dirt and debris from the outside surface of the fins. We
recommend the use of foaming coil cleaners available at air conditioning supply outlets. Care
should be taken not to damage the fins during cleaning.
The evaporator is of the direct expansion shell-and-tube type U bundle design, the tubes are
precisely expanded into the tube-sheets to form leak tight joints. In dry expansion type
evaporators, refrigerant flows through the tubes and water flowing through the shell over the
tubes. Normally no service work is required on this type of evaporator.
There may be instances where a tube leak in evaporator may result in refrigerant leak into the
waterside of the system or vice versa depending on the pressure levels. The tube leak may be due
to any of these reasons:
Once the tube leak is established in evaporator, the old tube shall be plugged. Follow the steps
involved in plugging a failed tube:
iv) Open the refrigerant head covers and close the water nozzle with dummy flanges.
v) Gradually increase the pressure level with the help of dry nitrogen on the shell side and check
for the probable leak at the tube joints.
vi) The tubes are mechanically expanded to the tube sheets at the ends. Identify the leaking tubes
and gradually reduce the pressure on shell side.
vii) In cases where only one or two tubes leak, the problem can be solved by plugging the tube at
both ends. If no of failed tubes are more then, it is recommended to replace complete evaporator.
viii) Reassemble the evaporator, perform the leak test with dry Nitrogen gas and once the
exchanger passes pressure test, vacuum the evaporator, break vacuum with refrigerant and hook
up the evaporator with system.
CAUTION: THE BOND PRODUCED BY EXPANSION MUST BE
REFRIGERANT TIGHT. THIS BOND SHALL BE PRODUCED BY
APPLYING LOCKTITE (GRADE 638) OVER THE OUTER SURFACE OF
THE TUBE AND ROLLING IT INTO THE TUBE SHEET.
KAC units are equipped with high capacity replaceable filter drier in liquid line. The purpose of
the filter drier is to keep the refrigeration circuit clean of solid contaminants, water and acid.
Contamination can cause corrosion and ice building as well as malfunction of the unit. The filter
drier cartridge is specially made out of Molecular sieves and Activated alumina. To change the
filter drier follow the procedure given below:
i) Isolate the filter drier by closing ball valve and 100% closing EEV
ii) Drain out the liquid refrigerant available in the filter drier area.
v) For injection line, replace the existing drier with the new drier. Use wet clothe on both side to
avoid heat dissipation.
vi) Vacuum the isolated line. Break the vacuum with refrigerant and connect the filter drier
assembly to the system.
4.2.3. Refrigerants
Kirloskar Chillers make KAC units are designed to work with refrigerant R-410A. All units shall
be shipped factory charged. For details of approximate refrigerant charge, refer the design data
sheet. In case, if moisture is noticed in the system, remove the refrigerant from the system,
evacuate the system and charge the refrigerant through the high capacity filter drier cores to
eliminate cause of trouble. Contact Kirloskar Chillers for further details.
After performing leak test, the chiller OR part OR equipment shall be subjected to vacuum and
dehydration
A suitable calibrated vacuum micron gauge OR a mercury manometer shall be connected to the
system. For vacuuming, follow the steps given hereunder:
1. Evacuate the system to a pressure of 500 μm Hg( 0.5 mm of Hg) /(0.67 mbar) absolute.
R-410A is highly efficient nearly azeotropic mixture (gases evaporate at nearly the same
temperatures) of two gasses ideally suited for replacing R-22 in scroll compressor packages. R-
410A will not damage the ozone and has a significantly higher vapor pressure than R-22.These
refrigerants are practically odorless. Refrigerants are non-combustible at atmospheric pressure.
Read the ‘Material Safety Data Sheet (MSDS) and the latest ASHRAE Safety Guide for
Mechanical Refrigeration’ to know more about safe handling of these refrigerants.
Refrigerant R410A
Compressor type 11 TR 22 TR
Working pressure range high side [bar(g)] 15.8 – 44.5 13.5 – 44.7
Working pressure range low side [bar(g)] 1.9 – 10.8 1.7 – 11.6
If it becomes necessary to charge the refrigerant at site, follow the procedure given below:
a) Connect the refrigerant cylinder with a connecting pipe to the charging valve provided in the
liquid line.
b) Open the valves and allow the refrigerant to flow into the refrigeration system. Refrigerant
will get charged till the pressures are equalized.
d) Check the moisture and liquid indicator, it should show the bubble free liquid refrigerant flow,
also check the refrigerant vapor suction super-heat and liquid refrigerant sub-cool temperature
details for concluding the correct charge of refrigerant.
To recover it, use empty, clean and dry cylinders OR refrigerant storage vessel. The liquid
refrigerant recovery can be performed with the help of the valve provided on the liquid line. To
facilitate the recovery of refrigerant, place the receiver / cylinder inside a container full of ice.
Weigh the bottle frequently to avoid excessive filling of the containers (70 ~ 80% max by
volume can be stored in the containers). If it is necessary to top-up the refrigerant follow the
same procedure. Before toping-up the refrigerant, find out and attend the cause of refrigerant
loss.
If it becomes necessary to adjust the refrigerant charge to obtain optimum chiller performance,
operate the chiller at design load and then add or remove refrigerant slowly until the refrigeration
parameters reaches design conditions. DO NOT OVERCHARGE. Refrigerant may be added
either through the storage vessel OR directly into the chiller.
After attending the repair, the chiller OR equipment OR part of the equipment must be
pressurized and leak tested. Pressurize the system with dry nitrogen and use a soap solution to
determine if leaks are present. The leak test has to be performed only after evacuating the
complete refrigerant from the part OR equipment OR chiller.
d) Observe the pressure gauge on the chiller OR part OR the equipment and close the regulating
valve when the pressure reaches test level. Refer recommended leak pressure test values
mentioned in technical specification of chillers or concern Kirloskar Chillers Pvt. Ltd.
e) Close the charging valve on the chiller OR part OR the equipment. Remove the copper tube if
no longer required.
g) Bring the chiller back to atmospheric pressure, repair any leaks found, and retest.
h) After retesting and finding no leak, vacuum and dehydrate the chiller OR part OR equipment.
POSSIBLE CORRECTIVE
PROBLEM POSSIBLE CAUSES
STEPS
Main switch open. Close switch.
A.
Determine type and cause of
COMPRESSOR WILL
System shut down on safety. shutdown and correct it before
NOT START
restart.
H.
Expansion valve not opening /
LOW SUCTION Check wiring connections of EXV.
malfunctioning.
PRESSURE
2) Program Memory 9MB (2MB BIOS + 7MB application program), 4MB logs
4) Parameter memory 32 KB
1) Suction Pressure
2) Discharge Pressure
C) Safeties: Following safeties are directly sensed by the controller & acted upon
3) Antifreeze Trip
D) Other safeties which are sensed by other devices, but action is taken by the controller
E) Other Features:
1) Battery backup for memory and clock to take care of power failures
4) Alarm History :- Logging of last 99 alarms with 4 Variables (critical parameters) which
can be viewed with display
3. Additional power supply for the terminal and 0 to 5 V ratio metric probes;
6. 0 to 10 V analogue outputs;
9. Connector for the display panel (external panel with direct signals);
10. Connector for all standard PCO series terminals and for downloading the application
program;
Technical specifications:
Display:
Type: FSTN graphic
Backlighting: white LED
Graphic resolution: 132x64 pixels
Text mode: 8 rows x 22 columns (font sizes 6x8pixels) 4
rows x 11 columns (font size 12x16 pixels) or
mixed modes
Character height: 2 mm (font sizes 6x8pixels)
4 mm (font size 12x16 pixels)
Size of active area: 36.94*15.98mm
Size of display area: 38.9*19.4mm
Power supply:
Voltage: pLAN Port: power supply from pCO through
telephone cable(18…30Vdc Class II only);
Maximum power input: 0.5 W
Maximum distances:
Maximum pLAN length: 500 m with AWG22 twisted pair cable
pCO terminal distance: 50m with telephone cable 500m with AWG22
twisted pair cable and TCONN6J000 Note: to
These terminals have been designed for panel installation; the drilling template measures
71x29mm.
a) Connect the telephone cable; Insert the terminal, with the front frame removed, into the
opening, and fasten the device to the panel using the flush-head screws, supplied in the
packaging, as shown in Fig. Finally, fit the click-on frame.
b) Electrical connection - Connect the telephone cable (code S90CONN00*) from the PCO
board to the connector provided (RJ12) on the rear of the terminal.
c) Configuring the address - The address of the terminal can be configured only after having
connected the power supply, using the RJ12 telephone jack (the factory default value is 32).
To access configuration mode, press the buttons together and hold them for at least
5seconds; the screen shown in Fig below will displayed.
address setting), press the button once: the cursor will move to the address field (nn). Use the
buttons to select the desired value, and confirm by pressing again. If the value
selected is not the same as the one saved previously, the screen shown in Fig. below
will be displayed, and the new value will be saved to the permanent memory. Protocol (not
pLAN) and the field “I/O Board address:xx” will not be displayed, as it has no meaning.
d) Fault signals: - If the terminal detects the off-line status of the pCO board it is associated with,
the display shows the message: I/O Board xx fault. On the other hand, if the terminal receives no
signal from the network, the display shows the following message: NO LINK.
After entering the Supervisory password we can able to access user level parameters also. Only
after entering the supervisor level password we can change the tripping parameters of the
pressures, tripping parameters of the temperatures, all alarm delays, anti-recycle timers etc. The
authorization code is a special four-character code that enables access in to the CAREL
controller system. The code must be numeric with values between 1 and 9 if it is to be entered
from the Keypad/Display. Each system can have three different authorization levels & for each
level there are different passwords. This provides the capability of issuing different codes to
different people if desired. The authorization code cannot display. The authorization codes must
be protected and remain confidential, if they are compromised unauthorized personnel can gain
access to the system.
6.6. Troubleshooting:
Problem Check points
1. The mains power supply;
2. 24 Vac/Vdc is available downstream of the power
The unit does not start (power
transformer;
LED off)
3. The 24 Vac/Vdc power connecter is plugged in correctly;
1. The analogue inputs used for the probes are not connected
Pressure probes: if errors occur in as per wiring diagram (in the application program);
the reading of these probes 2. The probe capillary is not blocked.
1. The analogue inputs used for the probes are not connected
Temperature probes: if errors
as per wiring diagram (in the application program);
occur in the reading of these
2. The probe capillary is not blocked.
probes
C = {(5/9) x (F-32)} F = {((9/5) x C) + 32}, 1 bar = 105 Pascal = 105 N/mm2 = 14.504 psi 1
psi = 0.68948 x 105 N/m2 = 68.948 mbar = 2.0360” Hg = 51.7149 torr (mmHg)
After start-up :
Send one copy to ‘Kirloskar Chillers Head Office’ within one week from the date of
commissioning; otherwise warranty claim may not be applicable.
Contact Details
Head Office:
Pune - 411005
- Phone: +91–20–66859800
- Fax: +91–20–66859802
- Email: pune@kcpl.net.in