FIELD INSPECTION REPORT No: VAL/SGS/MECH/BS/No.

92

Industry Division File No: IN/KOL/IND/201400172 Date: 05-11-2020

Projec:Scoop bath site. Client: M/s. VEDANTA, JHARSUGUDA


Supply intended for: Service Order No/PO No: Dated: 5600001417 Date.05.04.2019
Inspection ordered by: Placed with: SGS INDIA PVT.LTD.
Vedanta(Verbally)
Drawing No: Available

Name of work: Bucket elevator. QAP NO: Available.

Details of inspection carried out at site: The items marked offered for inspection at erection site and the offered items
checked randomly on visually accessible areas. Vendor: M/s.Wevin.
Completion
Comments Action By
Date
SL.No

1.

M/s.Wevin
Immediate

SCOOP BATH – Observation-Pre-Fabricated Bucket Elevator:


The bucket elevator is supposed to be erected on12 no’s foundation
bolts along with the nuts & washer fixed with it. But as per present
condition it had been erected on 6 no. foundation bolts along with
nuts& washer fixed with it only because among 12 no foundation
bolts at its base frame/plate 6 no bolts are fouling with the adjacent
vertical portion of the bucket elevator. The gap between those 6
bolts & edge of the vertical structure is not enough for fixing nut
along with the washer at those 6 positions. Now since the structure
of the bucket elevator is heavy so it is very much risky from safety
point of view to erect such heavy structure on 6 bolts instead of 12.
In this situation, we need the advice of the design department of
M/s.Wevin to resolve this issue ASAP. The painting of the bucket
elevator is found rusted also.
NOTE: We request the customer to respond/comment upon the doubt/dissatisfaction (if any) vis-à-vis above written observation(s) on or before 48 hours of its issuance, Alternatively, the report will be considered as “acknowledged”.

Severity Level- Major

Disclaimer:

This inspection has been carried out to the best of our knowledge & our responsibility is limited to the exercise of reasonable care. This Report reflects our findings at the time & place of inspection and is not intended to relieve the
seller from their contractual obligations. “In accordance with Client’s instructions, the Company’s involvement has been limited to witnessing/observing a third party’s intervention(s) at the third party’s laboratory/test house or other
facilities and installations used for the intervention(s). The Company’s sole responsibility was to be present at the time of the third party’s intervention(s) to forward the results, or confirm the occurrence, of the intervention(s). The
Company is not responsible for the condition or calibration of apparatus, instruments and measuring devices used, the analysis methods applied the qualifications, actions or omissions of the third party’s personnel or the analysis results.
This document is issued by the Company under its General Conditions of Service accessible at http://www.sgsgroup.in/en-GB/Terms-and-Conditions.aspx . Attention is drawn to the limitation of liability, indemnification and
jurisdiction issues defined therein. Any holder of this document is advised that information contained hereon reflects the company’s findings at the time of it’s intervention only and within the limits of client’s instructions, if any. The
company’s sole responsibility is to its client and this document(s) does not exonerate parties to a transaction from exercising all their rights and obligations under the transaction document. Any unauthorized alteration, forgery or
falsification of the content or appearance of this document is unlawful and offenders may be prosecuted to the fullest extent of the law.” “The information stated in the Report is derived from the results of inspection or testing
procedures carried out in accordance with the instruction of our clients and / or our assessment of such results on the basis of any technical standards, trade custom or practice, or other circumstances which should in our professional
opinion be taken into account”

BAPI SEN
05.11.2020
Client’s Signature & Date Inspector’s Sign & Date

You might also like