Professional Documents
Culture Documents
Comparison study on air flow and particle dispersion in a typical room with floor, skirt
boarding, and radiator heating systems
PII: S0360-1323(18)30084-2
DOI: 10.1016/j.buildenv.2018.02.018
Reference: BAE 5302
Please cite this article as: Dehghan MH, Abdolzadeh M, Comparison study on air flow and particle
dispersion in a typical room with floor, skirt boarding, and radiator heating systems, Building and
Environment (2018), doi: 10.1016/j.buildenv.2018.02.018.
This is a PDF file of an unedited manuscript that has been accepted for publication. As a service to
our customers we are providing this early version of the manuscript. The manuscript will undergo
copyediting, typesetting, and review of the resulting proof before it is published in its final form. Please
note that during the production process errors may be discovered which could affect the content, and all
legal disclaimers that apply to the journal pertain.
ACCEPTED MANUSCRIPT
Comparison study on air flow and particle dispersion in a typical room with floor, skirt
boarding, and radiator heating systems
PT
*
Corresponding author address: Department of Mechanical Engineering, Graduate University of
Advanced Technology, End of Haft Bagh Highway, Kerman, Iran, Email:
m.abdolzadeh@kgut.ac.ir, mo.abdolzadeh@gmail.com
RI
Abstract
In the present study, air flow and particle dispersion were simulated in a room using a three
SC
dimensional model when a thermal manikin was present in the room. The room was tested with
three heating systems: floor heating, skirt boarding heating, and radiator heating systems.
U
Airflow velocity and temperature distributions were obtained in terms of room’s height in
AN
different places of the room. Three particle sizes as well as two locations of particle injection
M
were studied. An Eulerian-Lagrangian model was used to predict the characteristics of air and
particle phases. In the Lagrangian particle model, the effects of drag, lift, thermophoretic, and
D
Brownian forces were considered. Results showed that the skirt boarding heating system due to
TE
uniform heat distribution and lower heat losses as well as providing a better thermal comfort
condition, has the best performance among all the studied heating systems. The results of
EP
particle phase showed that the skirt boarding heating system has the lowest particle concentration
in the breathing zone of the manikin. Furthermore, it was shown that due to the presence of
C
thermal sources in the room, the particles have a small tendency to leave the room and they
AC
mostly settled on walls and ceiling or stayed at lower heights of the room.
Keywords: Floor heating, Skirt boarding, Radiator, Breathing zone, Particle dispersion
1
ACCEPTED MANUSCRIPT
Introduction
Provision of standard thermal comfort conditions is very vital in places in which people spend
most of their daily time. Heat sources and heating systems undoubtedly create thermal plumes
that can affect the pattern of air ventilation and thermal comfort level. The flow and thermal
PT
distributions of air in indoor spaces are of great importance in term of indoor air quality
satisfaction. The numerical methods are very useful and inexpensive methods for checking
RI
whether the air quality is good or not. These methods provide a very valuable information in the
SC
shortest time which can help the designers select the best efficient HVAC system. So far,in this
regard many studies have been carried out. Spolink et al. studied the effect of different types of
U
heating systems (i.e. Electrically heated pews, hot air blow heating, and provisory electrical
AN
(infrared) heaters) on particulate air pollutant deposition: Their results showed that all the
heating systems re-suspend the particulate matter entered from outside [1] Ploski and Holemberg
M
studied heat emission from three hydronic skirting heating systems. They showed that the
D
thermal performance of the thermal skirting board with low temperature water supply must be
improved [2]. Zhong et al studied the effects of ventilation strategies and source locations on
TE
indoor particle deposition. They study two different ventilation strategies, including mixing
EP
ventilation (MV) and underfloor air distribution (UFAD) systems. They showed that in under
floor air distribution system, the location of the particle source highly effects on the particle
C
dispersion and particle removal efficiency [3]. Ploski and Holemberg numerically studied low-
AC
temperature baseboard heaters with integrated air supply. They indicated that the low
temperature baseboard heating system combined with air supply in the room can lead to a better
thermal comfort level as well as more energy saving [4]. HwaKang et al. studied numerical
simulation of VOC emission and sorption behaviors of adhesive-bonded materials under floor
heating condition. They mainly focused on the adhesive-bonded materials covering a large
2
ACCEPTED MANUSCRIPT
material. They showed that under the floor heating condition, the VOC emission becomes
significant [5]. Karabay et al. carried out a comparative study between floor heating system and
wall heating system. They investigated the air flow and heat transfer inside a room which is
PT
heated by floor heating and wall heating systems. They showed that the wall heating system is
RI
better than floor heating system as the wall heating system has a better comfort level [6].
Golkarfard and Talebizadeh studied the comparison of airborne particles deposition and
SC
dispersion in radiator and floor heating systems. They revealed that the floor and radiator heating
systems deposit the suspended particles on the ceiling and on the floor, respectively [7]. Maivel
U
et al. studied energy performance of radiators with parallel and serial connected panels. Their
AN
results showed that serial radiators have 0.3 to 0.7% less heat emission compared to the parallel
ones in a residential building [8]. Wang et al. retrofitted some houses with low temperature
M
heating (LTH) systems to achieve energy demand saving and thermal comfort. Their results
D
showed that combining LTH with external wall retrofitting has the highest effect on the
TE
operating temperature and the energy saving of the building [9]. Shin et al studied design of
radiant floor heating panel in view of floor surface temperatures. They designed the floor heating
EP
panel to keep the comfort level in the best condition. They showed that their design charts help
the designers to compare design alternative and this enhanced the flexibility of panel design [10].
C
Abdolzadeh et al. studied thermal skirting and floor heating systems from energy and energy
AC
point of views. They showed that the thermal skirting board heating system has less heat loss and
higher energy quality compared to floor heating system. They also showed that floor heating
system has 9% more energy consumption compared to the thermal skirt heating system [11].
Zheng at al. investigated the effect of non heating surface temperature on the heat output of a
3
ACCEPTED MANUSCRIPT
radiant floor heating system. They proposed a mathematical model to compute surface
temperature and heat output of a radiant floor heating system. They showed that the non-heating
surface temperature has a high impact on the heat output of the radiant floor [12]. Chu et al.
investigated air distribution and comfort of atrium with radiant floor heating. They studied the air
PT
flow behavior as well as thermal comfort level. They showed that the comfort condition in
RI
middle air supply is better than two side air supply [13]. Atienza et al. carried out comparison of
three heating systems: fan-coil, radiant floor, and combined fan-coil and radiant floor. They
SC
investigated the performance of the combined systems in terms of energy consumption and
comfort condition. Their results showed that in term of comfort, the combined system has the
U
best performance. The fan coils with fixed air velocity and inlet water temperature has the worst
AN
energy performance [14]. Rim and Novoselca studied ventilation effectiveness as an indicator of
occupant exposure to particles from indoor sources. Their results showed that the increase of
M
ventilation effectiveness decreases the occupant exposure for fine particles. They also showed
D
that airflow close to the pollutant sources as well as the location of sources are the major
TE
parameters which impact the human exposure [15]. Zhou et al. studied the effect of ventilation
and floor heating systems on the dispersion and deposition of fine particles in a room. They
EP
showed that the number of particles settled on the floor decreases with air velocity increase and
the floor temperature. They also showed that the higher inlet velocity leads to a faster reduction
C
The researches which used a manikin in their study are reviewed in the following. Wang and
Chow studied the influence of human walking on dispersion of expiratory droplets in an airborne
infection isolated room. They revealed that the human walking creates disturbance in the local
velocity field with wake formation and this reduces the number of suspended droplets in the
4
ACCEPTED MANUSCRIPT
room air [17]. Salmanzadeh et al. studied the buoyancy driven thermal plume near a sitting
heated manikin in a cubicle in turbulent flow using k-ε turbulent model. They showed that due to
the created thermal plume flow by the temperature gradient adjacent to the body high air velocity
and particle concentration are seen in the breathing zone of the manikin [18]. Hang et al. studied
PT
the influence of human walking on the flow and airborne transmission in a six-bed isolation
RI
room. They showed that the human walking effect is less important than ventilation design. They
also found that the surface heating of the human body produces a stronger thermal body plume
SC
and increases the turbulence near the human body [19]. Ansaripour et al. studied air flow
distribution and particle concentration emitted from a Laserjet printer in a ventilated room. They
U
used v2-f turbulent model to predict the turbulent characteristics. Their results showed that the
AN
particle concentration due to particle emission of the printer is significant in the breathing zone
of the manikin [20]. Bivolarova et al. studied the effect of airflow interaction in the breathing
M
convective flow created around the manikin, and the ventilation flow directed toward the
TE
manikin’s face. They showed that in case of exhalation through the nose, the exposure was
higher than the exhalation through the mouth. They also showed that air flows directed against
EP
the manikin face highly increases the exposure, [21]. Jian et al. studied an experimental study on
flow behavior of breathing activity produced by a thermal manikin. They obtained the temporal
C
and spatial distributions of breathing airflows with and without consideration of the convective
AC
boundary layer. They showed that the breathing flow has different behaviors during the breathing
process. They showed that the boundary layer has an important rule in developing the upward
spread and movement of exhaled contaminants of the manikin [22]. Zhuang et al. numerically
carried out a comparison of removal and deposition for fully-distributed particles in central and
5
ACCEPTED MANUSCRIPT
split-type air-conditioning rooms. They showed that the central-type air conditioner has a higher
particle removal efficiency compared to the split-type one. They also showed that high indoor air
supply velocity can improve the indoor air quality faster for a particle size range of 0.5 to 10 µm
[23]. Aliahmadi et al. studied air flow simulation of HVAC system in the compartment of a
PT
passenger coach. They showed that due to the inappropriate design of the compartment, the
RI
thermal comfort conditions do not evenly distribute in the compartment and this issue makes the
passengers uncomfortable, [24]. Tao et al. studied dynamic meshing modeling for particle
SC
resuspension caused by swinging manikin motion. The manikin has a swinging arm and leg
motions. Their results showed that the flow behavior is highly dependent to the manikin motion.
U
They provided a basis for particle re-suspension from the floor to the air using the flow
AN
streamlines. They showed that when the wake momentum dissipation gets higher the thermal
Based on the reviewed literature in above (with and without consideration of manikin), a
D
comprehensive comparison of low temperature heating systems, including skirt boarding and
TE
floor heating with high temperature heating system (radiator heating system) in terms of air flow
and particle dispersion has not been carried out yet. It seems these systems are still needed to
EP
study further in order to check out their thermal comfort conditions as well as indoor air quality
in enclosed spaces. This study investigated air flow and particle dispersion in three heating
C
systems, including floor heating, skirt boarding heating, and radiator heating systems in a typical
AC
room. The selected room was modeled when a heated manikin seated in the room’s middle. The
air flow was considered turbulent and the particle movement was modeled using the Langrngain
particle tracking method. Velocity and temperature of air were obtained in all the heating
systems and compared with each other. The particle dispersion for three particle sizes including
6
ACCEPTED MANUSCRIPT
0.1, 1, and 10 µm were calculated across the room in all the heating systems. The best system
form comfort level and particle dispersion point of views was determined. The particle
concentrations in the breathing zone of the manikin in all the studied systems were obtained and
compared with each other and the system with the lowest particle concentration in the breathing
PT
zone was introduced.
RI
2. System description
SC
Fig. 1 shows the schematic of the study room used in this research. A room with dimensions
of 4.8×2.4×2.7m was considered. The room has a door and window with dimensions of 2×1.2m
U
and 2.3×1.2m, respectively. Three heating systems, including floor heating, thermal skirting
AN
board, and radiator heating systems were studied in this room. Two registers on two walls of the
room were also considered in order to take into account the effect of air change on the air flow
M
and particle patterns. Dimensions of the registers are 0.24×0.14m and one of them is located at
2.28m height on the door’s wall and the other is located at 0.38m height on the window’s wall.
D
The radiator is located on the door’s wall and its dimensions are 1.2×0.55m and its distances
TE
from the ground and the wall are 0.1m and 0.055m, respectively. The thermal skirting board is
EP
placed in the periphery of the room. Its dimensions are 17.1×0.2m and it is located at 0.02m from
the ground. The area of floor heating system is 11.52m2.A seated female manikin faced to the
C
window was placed at the middle of the room. The door material is wood and its thickness is
AC
5cm. The window glass thickness is 3cm. The thickness of the side walls is 30cm and made
from gypsum.
7
ACCEPTED MANUSCRIPT
PT
RI
U SC
AN
Fig. 1: Sketch of the study room with the heated manikin in its middle
M
solved using the Reynolds Averaged Navier–Stokes (RANS) equations as well as the energy
equation. To analyze the flow, the v2-f turbulence model was used [26, 27]. The model
EP
_ _ _
∂φ _
∂φ ∂ ∂φ
ρ +ρuj − Γφ , eff = Sφ (1)
∂x j ∂ x j ∂x j
AC
∂t
Where φ represents the independent flow variables, Γ φ , eff the effective diffusion coefficient,
Sφ the source term, ρ the flow density and the bars denote the Reynolds averaging. In Table 1
the mathematical form of each transport equation of the v2-f model are summarized. p is the air
8
ACCEPTED MANUSCRIPT
_
pressure, µ t the turbulent viscosity, S the rate of strain, f a part of the v '2 source term and T the
PT
equation nt flow diffusion Sφ
variable coefficient
_ Γφ ,eff
φ
RI
Continuity 1 0 0
X-Component of u υt + υ −
1 ∂p
+
∂
(υ t
∂u
)+
∂
(υ t
∂v
)+
∂
(υ t
∂w
)
momentum ρ ∂x ∂x ∂x ∂y ∂x ∂z ∂z
Y-Component of v υt + υ 1 ∂p ∂ ∂u ∂ ∂v ∂ ∂w
+ (υt )+ (υt ) + (υt
SC
− )
momentum ρ ∂y ∂x ∂x ∂y ∂y ∂z ∂z
Z- Component of w υt + υ −
1 ∂p
momentum ρ ∂z
U
∂ ∂v ∂ ∂u ∂ ∂w
− β g (T − T∞ ) + (υt ) + (υt ) + (υt )
∂y ∂y ∂x ∂y ∂z ∂z
AN
T λ f + υ t /σT 0
Energy
Turbulent kinetic k υt / σ k ,t + υ Gk − ε
M
energy(k)
Turbulent kinetic energy ε υt / σ ε ,t + υ ( C ε' 1 G k − C ε 2 ε ) / T l
dissipation rate(ε)
Wall normal turbulence υt /σ ϕ + υ ∂k ∂ϕ
D
_ 2 p
fluctuation of kinetic energy ( v '2 / k ) (α υ + υt / σ k,t ) + Sϕ
k ∂x j ∂x j
( ϕ)
TE
L2 ∆α − α = −1 , Gk = υt S , S = Sij Sij
2
, Sϕ = (1 − α p ) f w + α p f h − G k ϕ / k
k ν
ϕε
fh = −
1 G Tl = max , CT
( C 1 − 1 + k )( ϕ − 2 / 3 ) , fw = −
Tl ε ε ε
k
EP
k3/ 2 υ3 / 4
_
L = CL max , Cη 1/ 4 , Pk = 2Cµ v '2 TSij2
ε ε
p 1
C
The appropriate boundary conditions of turbulence variables near the walls are as follows:
k
k = v '2 = 0, ε = 2υ (2)
y 2p
yp is the distance from the cell center to the wall.
The equation used to solve the solid wall temperature is as follows:
9
ACCEPTED MANUSCRIPT
∂ 2 Tw ∂ 2Tw ∂ 2 Tw
+ 2 + =0 (3)
∂x 2 ∂y ∂z 2
Tw is the walls’ temperature. It should be mentioned that it was assumed that the heat transfer
in the walls is happening under the steady state condition and there is no heat generation inside
PT
the room’s wall.
The utilized boundary conditions for solving the governing equations are given in Table 2.
RI
The wall boundary condition on the outside of the walls which are in contact with the
SC
surrounding air is as follows:
U
h is convection heat transfer coefficient on the exterior walls, Two is the exterior wall
AN
temperature, and Tamb is ambient temperature. It should be pointed out that the heat transfer due
to radiation heat transfer to the sky is ignored and the simulation was performed at night times
M
thus solar energy on the walls was not considered. It also should be mentioned the heat transfer
D
coefficients on the walls were obtained based on the equation given in the appendix. The
TE
∂Tair ∂T (5)
k air = kw w
∂n ∂n inner side of wall
EP
kair is the air conductivity coefficient, Tair is room temperature, Tw is the wall temperature.
C
Turbulent intensity, temperature, and velocity were considered 30%, 20°C, and 0.2 m/s,
AC
respectively, at the air inlet register. The temperature of the manikin’s body was taken 32.2°C and
the buoyancy movement due to the generated thermal plume was taken into account in the
particle distribution calculation. It should be mentioned this temperature is the manikin’s body
temperature with clothes [18, 20]. The pressure outlet boundary condition was given at the outlet
registers of the room. An unstructured grid (tetrahedral cell topology) was applied for
10
ACCEPTED MANUSCRIPT
surrounding air of the manikin as well as the solid walls (See Fig. 2). To resolve the boundary
layer around the manikin, fine meshes were created at the surface of the manikin with an initial
height of 0:2 mm, and an increase mesh size of 1.13. The unstructured mesh and the finite
volume method as well as the SIMPLE algorithm were used to solve the governing equations.
PT
Grid dependency analysis of the computational domain was carried out and a computational
RI
mesh containing about 2 ×106 cells showed a sufficient accuracy for continuing the analysis. In
this study, a program with user-defined scalar (UDS) is compiled by commercial CFD software,
SC
FLUENT (version 6.2) to predict the airflow turbulence features.
U
AN
M
D
TE
EP
11
ACCEPTED MANUSCRIPT
The verification of air flow phase simulation was performed in two cases: with and without
the presence of the manikin. The first case of the verification is an experimental study which has
been carried out by Olsen et al. [28]. The studied geometry of this research is shown in Fig. 3.
The detail characteristics of the experimental study and the present study are given in Table 4. It
PT
should be mentioned, the studied system in this research has been selected based on Olesen et al.
RI
study.
U SC
AN
M
Comfort Temperature
Room Air change 0 and 0.8Ach 1Ach
The Langragian point of view was used to model particle transport in the air. The following
= (6)
12
ACCEPTED MANUSCRIPT
. . /"
( . )
) + ( ()) +
#
( − ) + ( −
$ ( %& &% ) /'
9πµυ d p 1
*1 − - ./ − ∇Tait
(7)
, T air kf
2+
kp
PT
Where = 10 + ′
which 10 is the mean flow velocity at the particle location, ′
is the flow
fluctuation velocity, is the velocity of particles at the center of the particles, xi is the particle
RI
position, t is time, dp is the particle diameter, S is the ratio of particle density to fluid density, and
SC
gi is the gravitational acceleration. 23 = 4 − 4 5/6 is the particle Reynolds number based
on the flow-particle slip velocity. The first term on the right-hand side of Eq. 7 stands for the
< .
:; = 1 + (2.514 + .@@ ⁄A ) (9)
TE
The second term on the right right-hand side of Eq. 7 presents the contribution of the Saffman
lift force. The third term in Eq. 7, nj(t), represents the stochastic phenomenon of the Brownian
EP
diffusion. This force is modeled by a Gaussian random number with zero-mean, unit variance,
Gi, as [30]
C
E F H K
( ()) = C/ × ( IJ ) /E
AC
G @$"8 ∆
(10)
9
The fourth term in Eq. 7 is the particle gravitational force. The fifth term in Eq. 7 is the
To calculate the particle concentration in the room as well as the concentration in the
breathing zone of the manikin due to the released particles, plane and volume averaged particle
13
ACCEPTED MANUSCRIPT
number concentrations are obtained. The particle number concentration equation used in this
∑O
: M = #P #
(11)
QK
PT
Where n is the number of particles that move across the measurement volume V, and ti is the
particle residence time in the measurement volume, and T is the sampling time. The plane
RI
averaged particle number concentration, Cpa, is calculated as follows:
∑O
#P ( / # )
SC
: M = (12)
RK
Where n is the number of particles that move across the plane having an area of A with a
U
normal velocity vp. It should be stated that, the average concentration at the inlet was used to
AN
normalize the calculated concentrations in the breathing zone. The normalized volume averaged
∑O # /Q
: ∗M = (T/R
#P
U (13)
#O #O )
D
: ∗M = U ) (14)
(T/R#O #O
Where N is number of injected particles and vP is the particle velocity at the inlet register with
EP
an area of Ain.
The particles were released from the inlet register as well as a surface located in the front of
C
the manikin in the room. The particle phase characteristics are given in Table 5. The injection
AC
type is surface injection and the particles were released with an initial velocity of 0.25m/s. The
selected particle sizes are 0.1, 1, and 10µm. Three particle numbers were tested in the room in
order to find the steady state condition of particle concentration. This study selected three
particle numbers, including 4×104, 7×104, and 9×104 to test the steady state condition. The
results of the this test showed that 7×104 particles have sufficient accuracy for reaching the
14
ACCEPTED MANUSCRIPT
steady state condition. It should be mentioned that the particle injection was performed in 700s
and the room reached a steady state condition after 640s. This steady time was approximately the
same in all the injection numbers. The obtained results in this study all are in the steady state
time condition.
PT
Table 5: Characteristics of particle phase
Injection Type Surface Injection
RI
Vparticle (m/s) 0.25
( s)
n& p # 7×104
SC
dp (μm) 0.1-1-10
3
ρ (kg/m ) 2000
The particle equation of motion was solved using the discrete phase of FLUENT software.
U
The concentration equations listed above were solved using a home made computer code written
AN
in MATLAB. This code was later linked to the discrete phase model of FLUENT to obtain the
M
Fig. 4 shows the temperature distribution of three studied systems, including floor heating
system, the radiator heating system, and skirt boarding heating system. This figure also shows
EP
the comparison between the present study and the experimental study [28]. As shown in this
figure, the present simulation predicts the experimental data with a reasonable accuracy in all the
C
cases. It should be mentioned that some differences are seen between the present simulation and
AC
Olsen et al. study in some points of the measurement. This is mainly due to the difference
between the air change of the present study and the Olesen et al. study. Fig. 5 shows the
comparison of air flow velocities above the manikin head calculated in the present study with
two computational studies [18, 20] and an experimental study [33]. As shown in this figure, the
15
ACCEPTED MANUSCRIPT
present study predicts the air flow velocity above the manikin’s head with a good accuracy.
♦ Present study
▲ Present study
- - - - Experiment (0ach) [28]
- - - - Experiment (0ach) [28]
Experiment (0.8ach) [28]
Experiment (0.8ach) [28]
PT
RI
SC
(a) (b)
U
Present study
- - - - Experiment (0ach) [28]
AN
Experiment (0.8ach) [28]
M
D
TE
(c)
Fig. 4: Comparison of temperature distribution across the room height in the present study
with Olsen et al.[28] study for floor heating (a), skirt boarding (b), radiator heating systems (c)
C EP
AC
(a) (b)
16
ACCEPTED MANUSCRIPT
PT
RI
SC
(c) (d)
Fig.5: Comparison of the air flow velocity above the manikin’s head (a) computational study
(Fig.6 in article [18]) (b) computational study(Fig.7 in article [20]), (c) present study, and (d)
U
experimental study (Fig. 6 in article [33]) ,
AN
Now the results of the present study are described in following. Figure 6 shows the study
system (a) and some selected planes (b) in that in order to show the flow characteristics all over
M
the room. Elevens planes are shown in Fig. 6b as well as detailed information about their
D
positions. Fig. 6c also shows some selected points in the room in order to show the flow and
TE
(a)
17
ACCEPTED MANUSCRIPT
PT
RI
SC
(b)
U
AN
M
D
(c)
Fig. 6: The room (a) with defined planes (b) and lines (c) to show the present study results
TE
Figure 7 shows temperature and velocity distributions in plane 10 crossed the manikin’s body in
EP
all the heating systems. This figure states that the floor heating system and the radiator heating
system have the highest and lowest air velocities, respectively, around the manikin among all the
C
heating systems. This figure also states that the air velocity in the manikin breathing zone in the
AC
floor heating is higher than that of the other two systems. The air velocity in the floor heating
system is 2.9 times larger than the radiator system. This figure further state that the air
temperature in the radiator heating system is higher than that of the two other heating systems.
The air temperatures in the floor heating system and the skirt boarding system evenly distribute
in the room while the radiator heating system does not have this advantage.
18
ACCEPTED MANUSCRIPT
PT
RI
(a)
U SC
AN
(b)
M
D
TE
EP
(c)
Fig. 7: Air flow velocity, vector velocity, and air temperature distributions in Plane 10, Floor heating system(a), Skirt
C
The velocity and temperature distributions in plane 3 are shown in Fig. 8. This figure also says
that the air velocity in the floor heating system is still higher than that of the two other heating
systems. The radiator heating system has the lowest air velocity in the room. The skirt boarding
heating system in plane 3 experiences a much lower air velocity than the floor heating system in
comparison with plane 10. The mean air velocity of skirt boarding and the radiator heating
19
ACCEPTED MANUSCRIPT
systems in plane 3 is 205% and 460%, respectively, smaller than that of the floor heating system.
It should be mentioned that the mean air velocity of floor heating system is in the range of
comfort velocity. The temperature distribution in Fig. 8 shows that like plane 10, the highest air
temperature belongs to the radiator heating system and also non uniform temperature distribution
PT
is seen in this system. Fig. 9 shows the velocity and temperature distributions across the lines
RI
shown in Fig. 6c. As shown in Fig. 6c, line 1 is close to the door, line 5 is close to the window,
lines 2 and 4 are in the back and front of the manikin, respectively, and lines 6 and 7 are in the
SC
right and left sides of the manikin, respectively. It should be mentioned that the symmetry
condition in the room does not exist. Fig. 9 shows that the air velocity changes in lines 1 and 5
U
for the floor and the radiator heating systems are the same. However, the air velocities in the
AN
skirt boarding heating system on these two lines are not the same. The difference is mainly due
to the door and window which are close to these lines. The temperature distributions on these
M
two lines show that the floor and skirt boarding heating systems have evenly distributed
D
temperature across the room’s height. This figure also shows that the air temperature across the
TE
room height in the radiator heating system changes and is not constant. The velocity distributions
on lines 6 and 7 show that due to non symmetry condition of the front and back of the manikin,
EP
the velocity trend is not the same specially for the floor heating system. Fig. 9 also show that the
temperature distribution is like other lines and the skirt boarding heating system has the most
C
20
ACCEPTED MANUSCRIPT
PT
RI
SC
(a)
U
AN
M
D
TE
(b)
C EP
AC
(c)
Fig. 8: Air flow velocity, vector velocity, and air temperature distributions in plane 3, Floor heating(a),
Skirt boarding heating system (b), and radiator heating system (c)
21
ACCEPTED MANUSCRIPT
PT
RI
Line 1 Line 5
U SC
AN
M
Line 2 Line 5
D
TE
C EP
Line 6 Line 7
AC
Fig. 9: Air flow and temperature distributions across different lines in the room for all the heating systems
Table 6 shows the mean values of the air temperature and velocity for all the studied systems in
all the planes shown in Fig. 9. Fig.10 shows the mean values of air temperature as well as
velocity for all the investigated systems in the room. This figure states that the mean air velocity
in the floor heating system and the skirt boarding system is 266% and 133%, respectively, larger
22
ACCEPTED MANUSCRIPT
than the radiator heating system. This figure also states that the air mean temperature in the
radiator heating system is higher than the floor heating and skirt boarding heating systems. This
difference is about 0.25K. It should be mentioned that the air distributions in the floor heating
and the skirt boarding heating systems are quite uniform through the room while the radiator
PT
heating system suffers from the nonuniform temperature distribution in the room.
RI
Table 5: Mean air flow properties in planes 1-11 for floor, skirt boarding, and radiator heating systems.
Floor Skirt boarding Radiator
Vm(m/s) Tm(K) Vm(m/s) Tm(K) Vm(m/s) Tm(K)
SC
Plane 1 0.11 292.8 0.109 294.51 0.0708 297.39
Plane 2 0.22 294.35 0.138 294.56 0.073 296.32
Plane 3 0.29 295.87 0.141 295.73 0.063 296.83
Plane 4 0.17 294 0.138 294.63 0.071 296.21
U
Plane 5 0.135 293.5 0.135 294.5 0.042 295.3
Plane 6 0.12 294.47 0.123 295.33 0.069 298.35 2
AN
Plane 7 0.11 293.95 0.12 295.21 `0.052 296.1
Plane 8 0.11 294.18 0.116 295.13 0.038 294.25
Plane 9 0.13 294.15 0.141 295.01 0.037 296.68
Plane 10 0.125 294.19 0.123 294.32 0.043 296.3 2
M
Fig. 10: Comparison of mean air temperature and velocity in the room for all the studied heating systems
AC
It is first needed to verify the particle model performance. For checking out this, the plane
average concentration in the breathing zone of the manikin was obtained and compared with two
other numerical studies performed in the past [18,20] as well as experimental studies [34, 35].
23
ACCEPTED MANUSCRIPT
Fig. 11 shows the comparison between the present study and the other studied carried out in the
past. As shown in this figure, the present study predicts the plane concentration with a good
accuracy when it is compared with the numerical and experimental studies. It also has a better
accuracy than Salmanzadeh et al. study [18]. It should be mentioned that the differnce between
PT
the present study results and the experiment results becomes higher at distances larger than 5cm,
RI
because in the present study the manikin was simulated without breathing while in the
experimental study [35] the manikin has nose breathing (30° with respect to vertical plane)
SC
M a r r ( E x p e r im e n t a l S t u d y )
S a lm a n z a d e h ( C o m p u t a t in a l S t u d y )
1 .5 A n s a r ip o u r ( C o m p u t a t in a l S t u d y )
U
P resen t S tu d y
Plane Averaged Concentration
AN
1
M
● Present study
■ Experiment [34, 35]
0 .5
▲♦ Computation [18, 20]
D
0 5 10 15
D is t a n c e ( c m )
TE
Fig. 11: Comparison of plane concentration in the breathing zone of the manikin in the present study with
the experimental [34, 35] and numerical [18, 20] studies
EP
Fig.12 shows the dimensionless particle concentration in plane 10 in all the studied systems for
particle size of 0.1µm. The particles are released from the inlet vent. It is clear that the particle
C
concentration has the maximum value in the radiator heating system and the second maximum is
AC
happening in the floor heating system. The skirt boarding heating system has the minimum
concentration among all the studied systems. The particle concentration in plane 3 also states that
the maximum particle concentration belongs to the radiator heating system and the minimum
24
ACCEPTED MANUSCRIPT
PT
RI
C C C
) mean = 0.06 ) mean = 0.046 ) mean = 0.074
C0 C0
C0
(a)
U SC
AN
M
C C C
) mean = 0.026 )mean = 0.007 )mean = 0.053
C0 C0 C0
(b)
D
Fig. 12: Normal particle concentration in planes 10 (a) and 3 (b) for all the studied heating systems, injection from inlet
register and do=0.1µm
TE
Fig.13 shows the particle concentration in planes 10 and 3 when particles are released from
the plane placed in front of the manikin. In this case also the maximum particle concentration is
EP
seen in plane 10 in the floor heating system and the particle concentration in the skirt boarding
C
and the radiator heating systems in this plane are the same. In plane 3, the maximum and
AC
minimum particle concentrations are again seen in the floor heating system and the skirt board
25
ACCEPTED MANUSCRIPT
PT
RI
C
SC
C C ) m e a n = 0 .0 1 5
) mean = 0.021 ) mean = 0.015 C0
C0 C0
U
AN
M
D
C C C
) m ean = 0 .0 0 7
) m e a n = 0 .0 1 8 C0 ) m e a n = 0 .0 1 4
C0 C0
Fig. 13: Normal particle concentration in planes 10 (a) and 3(b) for all the studied heating systems, injection from the manikin
TE
Fig. 14 shows the particle deposition fraction settled on the walls of the room when the particles
EP
are released from the air inlet vent. This figure shows that the maximum particle deposition in all
the systems is happening on the walls and in this case the maximum and minimum particle
C
depositions belong to the floor heating and the skirt board heating systems. On the ceiling, the
AC
maximum and minimum particle depositions belong to the floor and the radiator heating systems.
The particle deposition on the floor has the minimum value in the floor heating system and the
26
ACCEPTED MANUSCRIPT
PT
RI
SC
Fig. 14: Particle deposition fractions on the room components in all the studied heating systems,
injection from inlet register and dp=0.1µm
Fig. 15 shows the fraction of particle deposition in the room for all the heating systems in
U
three particle sizes (i.e. 0.1, 1, and 10µm). This figure depicts the particle fraction for the two
AN
locations in which the particles were released. As shown in this figure, the maximum and
minimum particle deposition fractions in the room for the entire particle sizes are happening in
M
the floor heating and the radiator heating systems, respectively, when the particles are injected
D
from the inlet air vent. This means that the floor heating and the skirt boarding heating systems
TE
have a good performance to remove the particle from the air in the room. It should be mentioned
that the dominant forces which controls the particle motions in smaller particle sizes (0.1 and
EP
1µm) are Brownian, thermophoretic and lift forces. For the large particle size (10µm), the
Fig. 15 also shows that when the particles are released from the plane in front of the manikin, the
AC
particle removal efficiencies of all the studied systems are lower (i.e. 5-10%) than that of the
case of injection particle from the inlet air vent. This figure also states that the maximum and the
minimum particle depositions in the case of particle release from the injection plane are
happening on the floor and skirt boarding heating systems, respectively. Fig. 15 shows that in
case of different particle sizes, the removal efficiencies for particles entered from the air inlet in
27
ACCEPTED MANUSCRIPT
all the particle sizes are quite the same. However, in the case of particle injection from the
manikin front, for smaller particle sizes the skirt boarding and radiator heating systems have
lower particle removal efficiencies compared to that for larger particle sizes.
PT
RI
U SC
Fig. 15: Particle deposition fractions in the room for three particle sizes, dp=0.1, 1, and 10 µm
AN
in all the studied heating systems, injection from the inlet register and the manikin front
M
D
TE
C EP
AC
Fig. 16: Normal Particle concentration in the breathing zone of the manikin for two
particle sizes, dp=0.1, and 10 µm in all the studied heating systems, injection from the inlet
register and the manikin front
Fig. 16 shows the particle concentration in the breathing zone of the manikin for two particle
sizes and the two locations of particle injection. This figure shows that the radiator heating
system has the maximum particle concentration in the breathing zone among all the studied
28
ACCEPTED MANUSCRIPT
systems for particle size of 10µm with particle injection from the both locations. At this size, the
floor heating and the skirt boarding heating systems with injection form the manikin’s front have
the most particle concentration in the breathing zone. For small particle size (dp=0.1µm), the
PT
radiator heating system with particle injection from the manikin’s front has the maximum
RI
particle concentration in the breathing zone. The floor heating and the skirt boarding heating
systems with the same injection plane have the second and third most particle concentrations,
SC
respectively, in the breathing zone. At this size, when the injection is from the inlet register, the
U
maximum particle concentration belongs to the floor heating systems and the particle
AN
concentration of the breathing zone in the radiator and the skirt boarding heating systems are
M
Fig.17 shows the particle concentration in different lines shown in Fig. 6c for 0.1µm particle
D
size when they were released from the inlet air register. The particle concentration in the studied
TE
heating systems on line 1 shows that the radiator heating system has the lowest and highest
EP
particle concentrations close to the floor and ceiling, respectively. These changes are confirmed
by the velocity and temperature distributions shown in Fig. 9 as the lowest and the highest
C
velocities are seen close to the floor and ceiling, respectively. The particle concentration on line
AC
1 for the skirt boarding heating system also shows that this system has the highest and lowest
particle concentrations close to the floor and ceiling, respectively. The floor heating system has
the maximum particle concentration between the height of 0.5 and 1.4m, among all the studied
systems. The particle concentration close to the window (line 5) shows that the maximum
particle concentration on this line belongs to the radiator heating system with the highest value
29
ACCEPTED MANUSCRIPT
close to the ceiling. The floor heating system has the same particle concentration as the skirt
boarding heating system close to the ceiling. The particle concentration distributions of floor
heating and the skirt boarding heating systems on line 2 are qualitatively and quantitatively the
same. It is still observed that the radiator heating system has the maximum concentration even in
PT
the lowest height of the room. On the line located in the manikin front (line 4), the particle
RI
concentration of the floor heating is different with the particle concentration of the skirt boarding
heating system at the middle heights of the room. Lines 6 and 7 have the same particle
SC
concentration distributions in all the studied heating systems. On these lines, the maximum
particle concentration belongs to the radiator heating system. The skirt boarding heating system
U
and the floor heating system has the same particle distribution.
AN
M
D
TE
EP
Line 1 Line 5
C
AC
Line 2 Line 4
30
ACCEPTED MANUSCRIPT
PT
RI
Line 6 Line 7
Fig. 17: Normal particle concentrations across different lines in the room for
SC
all the heating systems, dp=0.1µm and injection from the inlet register
To check out the effect of particle size on the normal particle concentration, the results of the
U
two selected sizes are brought close each other to assess the particle size effect. Fig. 18 shows
AN
the normal particle concentration changes for two particle sizes (0.1and 10µm) across line 2. As
shown in this figure, 10µm particle size has a larger particle concentration at the heights below
M
1.2m and a lower concentration above 1.2 m in the floor and skirt boarding heating systems. This
D
figure also shows that the particle concentration in the radiator heating system is larger than the
TE
two other systems and 10µm particle size below 1.75m height has a higher particle concentration
compared to 0.1 µm. It means that the radiator heating system disperses a larger particle size in
EP
31
ACCEPTED MANUSCRIPT
Fig. 18:Normal particle concentration across line 2 for two particle sizes, 0.1 and 10µm, in all the studied heating
systems, particle injection from the inlet register
5. Conclusions
In this study, air flow and particle dispersion of three heating systems, including floor heating,
skirt boarding heating, and radiator heating systems were investigated and compared with one
PT
another in a typical room with a seated heated manikin. The airflow was considered turbulent
and it was solved using v2-f turbulent model. The air flow study showed that the radiator heating
RI
system has a lower air velocity across the room height compared to other studied systems and the
SC
mean air velocity in the radiator heating system was 2 to 5 times smaller compared to that in the
floor and skirt boarding heating systems. The air temperature distributions of floor and skirt
highest concentration in the breathing zone of the manikin in the selected large particle size was
M
seen in the radiator heating system in the two cases of particle injection locations (i.e. Inlet
D
register and manikin’s front). It was also shown that in the case of particle injection from the
TE
manikin’s front, the particle concentration has still the maximum value in the radiator heating
system for the small particle size. This study found the skirt boarding heating system is the best
EP
heating system with the lowest particle concentration in the breathing zone and the highest
References
[1]. Spolnik Z, Worobiec A, Samek L, Bencs L, Belikov K and Van Grieken R, Influence of
different types of heating systems on particulate air pollutant deposition: The case of churches
situated in a cold climate, Journal of Cultural Heritage, 2007, 8, 7-12
[2] Ploskić A and Holmberg S, Heat emission from thermal skirting boards, Building and
Environment, 2010, 45, 1123-1133.
32
ACCEPTED MANUSCRIPT
[3] Zhong K, Yang X and Kang Y, Effects of ventilation strategies and source locations on
indoor particle deposition, Building and Environment, 2010, 45, 655-662.
[4]. Ploskić A and Holmberg S, Low-temperature baseboard heaters with integrated air supply–
An analytical and numerical investigation, Building and Environment, 2011, 46, 176-186.
PT
[5]. Dong HwaKang, Dong HeeChoi, Yoon-BokSeong, Myoung SoukYeo, Kwang WooKim, A
numerical simulation of VOC emission and sorption behaviors of adhesive-bonded materials
RI
under floor heating condition. Building and Environment, 2013, 68, 193-201
1. [6] Hasan Karabay, Müslüm Arıcı, Murat Sandık, A numerical investigation of fluid flow and
SC
heat transfer inside a room for floor heating and wall heating systems, Energy and Buildings,
2013, 67, 471-478
2.
[7]. Golkarfard V and Talebizadeh P, Numerical comparison of airborne particles deposition and
U
dispersion in radiator and floor heating systems, Advanced Powder Technology, 2014, 25, 389-
397.
AN
[8] Maivel, M, Konzelmann, M., Kurnitski, J.Energy performance of radiators with parallel and
serial connected panels, Energy and Buildings, 2015, 86, 745-753
M
energy-demand savings and thermal comfort, 2015 Energy and Buildings 109, 217-229
TE
1. [10]. Mi Su Shin, Kyu Nam Rhee, Seong Ryong Ryu, Myoung Souk Yeo, Kwang Woo Kim ,
Design of radiant floor heating panel in view of floor surface temperatures, Building and
Environment, 2015, 92, 559-577
EP
http://dx.doi.org/10.1061/(ASCE)EY.1943-7897.0000385, 2016.
AC
[12]. Xuejing Zheng, Yong Han, Huan Zhang, Wandong Zheng, Dehui Kong, Numerical study
on impact of non-heating surface temperature on the heat output of radiant floor heating system,
Energy and Buildings, 2017, 155, 198-206
[13]. Guangming Chu, YanghongSun, TongJing, YanSun, YongliSun, A Study on Air
Distribution and Comfort of Atrium with Radiant Floor Heating, Procedia Engineering, 2017,
205, 3316-3322
[14]. AntonioAtienza, MárquezJosé Manuel, Cejudo LópezFrancisco,Fernández Hernández,
33
ACCEPTED MANUSCRIPT
PT
[16]. Zhou, Y., Deng, Y., Wu, P. Cao, S. The effects of ventilation and floor heating systems on
the dispersion and deposition of fine particles in an enclosed environment, Building and
Environment, 2017,125, 192-205
RI
[17]. Wang, J and Chow T. Numerical investigation of influence of human walking on dispersion and
SC
deposition of expiratory droplets in airborn infection isolation room. Building and Environment, 2011, 46,
1993-2002.
U
[18] Salmanzadeh, M.; Zahedi, G.; Ahmadi, G.; Marr, D.R.; and Glauser, M. Computational
modeling of effects of thermal plume adjacent to the body on the indoor airflow and particle
AN
transport. Journal of Aerosol Science, 53, 29–39, 2012.
[19] Hang, J. Li. Y., Jin, R. The influence of human walking on the flow and airborne
M
transmission in a six-bed isolation room: Tracer gas simulation, Building and Environment,
2014, 77, 2014, Pages 119-134
D
2017, 125,216-226
AC
2
[22]. JiangNan, Shi-yongYao, Lian-yuanFeng, He-jiangSun, Jun-jieLiu Experimental study on
flow behavior of breathing activity produced by a thermal manikin, Building and Environment
2017, 123, 200-210
[23] Zhuang, C., et al., Numerical comparison of removal and deposition for fully-distributed
particles in central- and split-type air-conditioning rooms. Building & Environment, 2017. 112:
p. 17-28.
34
ACCEPTED MANUSCRIPT
[25] Tao Y, Inthavong , Tu , Dynamic meshing modelling for particle resuspension caused by
PT
swinging manikin motion, Building and Environment, 2017, 123, 529-54
[26]. Lien F., Kalitzin G., Computations of transonic flow with the v2-f turbulence model.
RI
International Journal of Heat and Fluid Flow 22, 53–61.
[27] Davidson L., Nielsen, P.V., Sveningsson A.,. Modification of the V2F model for
SC
computing the flow in a 3D wall jet. Turbulence Heat and Mass Transfer , 4, 577–584 2003.
U
[29] Hinds William , Aerosol Technology Properties, Behavior, and Measurement of Airborne
AN
Particles. Wiley, New York, 1982.
[30]. Li A., Ahmadi G., Dispersion and deposition of spherical particles from point sources in
turbulent channel flow, Aerosol Science and Technology, 16 , 209–226, (1992)
M
[31] L. Talbot, R.K. Cheng, R.W. Schefer, D.R. Willis, Thermophoresis of particles in
a heated boundary layer, J. Fluid Mech. 101 (1980) 737-758
D
[32] Zhu, J., Rudoff, R., Bachalo, E., & Bachalo, W. (1993). Number density and mass flux
TE
measurements using the phase Doppler particle analyzer in reacting and non-reacting swirling
flows. In: AIAA, Aerospace sciences meeting.
EP
[33]. Marr D, Velocity Measurements in Breathing Zone of a Moving Thermal Manikin within
the Indoor Environment Ph.D. Thesis,Syracuse University,New York, 2007,
[34]. Spitzer, I.M. (2006). Experimental Aerosol Characterization in the Indoor Environment
C
[35] Spitzer, I.M., Marr, D.M., & Glauser, M.N. (2010). Impact of manikin motion on particle
transport in the breathing zone. Journal of Aerosol Science, 41, 373–383.
[36] Liu J, Heidarinejad M, Gracik S and Srebric J, The impact of exterior surface convective
heat transfer coefficients on the building energy consumption in urban neighborhoods with
different plan area densities, Energy and Buildings, 2015, 86, 449-463.
35
ACCEPTED MANUSCRIPT
Appendix
The following equations have been used to predict the heat transfer coefficient around the
building [36].
( 3.39 − 5.03λ p )U loc ( )
2 2
hCwindward = 0.94
+ 1.52 ∆ T 0.36
; R 2 = 0.94 (A1)
PT
RI
( 3.57 − 1.72 λ p ) U loc ( )
2 2
hCRoof = 0.94
+ 1.55 ∆ T 0.36
; R 2 = 0.91 (A3)
SC
Uc is the wind speed, ∆T is the temperature difference between the indoor and outdoor
temperatures of the room, and λp is the compression coefficient of the residential zone.
U
AN
M
D
TE
C EP
AC
36
ACCEPTED MANUSCRIPT
Highlights
PT
RI
U SC
AN
M
D
TE
C EP
AC