Specification sheet

Diesel Generator
set
QSK95 series
engine
2600 kVA-3750 kVA 50 Hz
Emissions regulated

Description
Cummins Power Generation commercial Control system - The PowerCommand® digital
generator sets are fully integrated power control is standard equipment and provides total
generation systems providing optimum genset system integration including automatic
performance, fuel economy, reliability and remote starting/stopping, precise frequency and
versatility for stationary standby, prime and voltage regulation, alarm and status message
continuous power applications. display, AmpSentry™ protective relay, output
metering and auto-shutdown.
Features Cooling system - Standard and enhanced
Cummins® heavy-duty engine - Rugged 4- integral set-mounted radiator systems, designed
cycle, industrial diesel delivers reliable power, and tested for rated ambient temperatures,
low emissions and fast response to load simplifies facility design requirements for rejected
changes. heat. Also optional remote cooled configuration
for non-factory supplied cooling systems.
Alternator - Several alternator sizes offer
selectable motor starting capability with low Warranty and service - Backed by a
reactance windings, low waveform distortion with comprehensive warranty and worldwide
non-linear loads and fault clearing short-circuit distributor network.
capability.
NFPA - The generator set accepts full rated load
in a single step in accordance with NFPA 110 for
Level 1 systems.

Standby rating Prime rating Continuous rating Emissions compliance Data sheets
50 Hz 50 Hz 50 Hz
Model kVA (kW) kVA (kW) kVA (kW) EPA and TA Luft 50 Hz
C3500 D5e 3500 (2800) 3125 (2500) 2600 (2080) 2g TA Luft NAD-5830-EN
C3500 D5e 3500 (2800) 3125 (2500) 2750 (2200) Tier 2 NAD-5938-EN
C3750 D5e 3750 (3000) 3350 (2680) 3000 (2400) Tier 2 NAD-5986-EN

Note: All ratings include radiator fan losses.

power.cummins.com
©2015 Cummins Power Generation Inc. | NAS-5829b-EN (8/15)
Generator set specifications
Governor regulation class ISO 8528 Part 1 Class G3
Voltage regulation, no load to full load ± 0.5%
Random voltage variation ± 0.5%
Frequency regulation Isochronous
Random frequency variation ± 0.25%
Emissions to EN 61000-6-4
EMC compatibility
Immunity to EN 61000-6-2

Engine specifications
Bore 190 mm (7.48 in)
Stroke 210 mm (8.27 in)
Displacement 95.3 litres (5815 in3)
Configuration Cast iron, V 16 cylinder
Battery capacity 6 x 1400 amps minimum at ambient temperature of -18 °C (0 °F)
Battery charging alternator 140 amps
Starting voltage 24 volt, negative ground
Fuel system Cummins Modular Common Rail System
On engine triple element, 5 micron primary filtration with water
Fuel filter separators, 3 micron/2 micron (filter in filter design) secondary
filtration
Fuel transfer pump Electronic variable speed priming and lift pump
Breather Cummins impactor breather system
Air cleaner type Unhoused dry replaceable element
Lube oil filter type(s) Spin-on combination full flow filter and bypass filters
Standard cooling system High ambient cooling system (ship loose)

Alternator specifications
Design Brushless, 4 pole, drip proof, revolving field
Stator Optimal
Rotor Two bearing, flexible coupling
Insulation system Class H on low and medium voltage, Class F on high voltage
Standard temperature rise 125 ºC standby / 105 ºC prime
Exciter type Optimal
Phase rotation A (U), B (V), C (W)
Alternator cooling Direct drive centrifugal blower fan
AC waveform total harmonic distortion < 5% no load to full linear load, < 3% for any single harmonic
Telephone influence factor (TIF) < 50 per NEMA MG1-22.43
Telephone harmonic factor (THF) <3
Anti-condensation heater 1400 watt

Available voltages
50 Hz line-neutral/line-line
 220/380  254/440  3464/6000  5775/10000
 230/400  400/690  3637/6300  6060/10500
 240/415  1905/3300  3810/6600  6350/11000
Note: Consult factory for other voltages.

Generator set options and accessories


Engine Alternator Control panel Generator set
 400 V thermostatically controlled  80 C rise  Multiple language support  Battery
coolant heater for ambient above  105 C rise  Ground fault indication  Battery charger
4.5 C (40 F)  125 C rise  Remote annunciator panel  LV and MV entrance box
 Heavy duty air cleaner  150 C rise  Paralleling and shutdown alarm  Spring isolators
 Redundant fuel filter  Differential current relay package  Factory witness tests
 Air starter transformers  Floor mounted pedestal installed  IBC and IEEE seismic
 Redundant electric starting Cooling system control panel certification
 Eliminator oil filter system  Enhanced high ambient Warranty
 Lube oil make up cooling system (ship loose)  3, 5 or 10 years for standby
 Coalescing breather filter  Remote cooled configuration including parts (labor and travel
optional)
 2 or 3 years for prime including
parts, labor and travel
Note: Some options may not be available on all models - consult factory for availability.
power.cummins.com
©2015 Cummins Power Generation Inc. | NAS-5829b-EN (8/15)
PowerCommand 3.3 Control System
Engine data
 DC voltage
 Engine speed
 Lube oil pressure and temperature
 Coolant temperature
 Comprehensive FAE data (where applicable)
Other data
 Genset model data
 Start attempts, starts, running hours, kW hours
 Load profile (operating hours at % load in 5% increments)
 Fault history
An integrated microprocessor based generator set control
 Data logging and fault simulation (requires InPower)
system providing voltage regulation, engine protection, alternator
 Air cleaner restriction indication
protection, operator interface and isochronous governing. Refer
to document S-1570 for more detailed information on the control.  Exhaust temperature in each cylinder
AmpSentry – Includes integral AmpSentry protection, which Standard control functions
provides a full range of alternator protection functions that are Digital governing
matched to the alternator provided.  Integrated digital electronic isochronous governor
Power management – Control function provides battery  Temperature dynamic governing
monitoring and testing features and smart starting control Digital voltage regulation
system.  Integrated digital electronic voltage regulator
Advanced control methodology – Three phase sensing, full  3-phase, 4-wire line-to-line sensing
wave rectified voltage regulation, with a PWM output for stable  Configurable torque matching
operation with all load types.
AmpSentry AC protection
Communications interface – Control comes standard with
 AmpSentry protective relay
PCCNet and Modbus interface.
Regulation compliant – Prototype tested: UL, CSA and CE  Over current and short circuit shutdown
compliant.  Over current warning
Service - InPower™ PC-based service tool available for detailed  Single and three phase fault regulation
diagnostics, setup, data logging and fault simulation.  Over and under voltage shutdown
Easily upgradeable – PowerCommand controls are designed  Over and under frequency shutdown
with common control interfaces.  Overload warning with alarm contact
Reliable design – The control system is designed for reliable  Reverse power and reverse var shutdown
operation in harsh environment.  Field overload shutdown
Multi-language support Engine protection
 Battery voltage monitoring, protection and testing
Operator panel features  Overspeed shutdown
Operator/display functions  Low oil pressure warning and shutdown
 Displays paralleling breaker status  High coolant temperature warning and shutdown
 Provides direct control of the paralleling breaker  Low coolant level warning or shutdown
 320 x 240 pixels graphic LED backlight LCD  Low coolant temperature warning
 Auto, manual, start, stop, fault reset and lamp test/panel lamp  Fail to start (overcrank) shutdown
switches  Fail to crank shutdown
 Alpha-numeric display with pushbuttons  Cranking lockout
 LED lamps indicating genset running, remote start, not in  Sensor failure indication
auto, common shutdown, common warning, manual run
 Low fuel level warning or shutdown
mode, auto mode and stop
 Fuel-in-rupture-basin warning or shutdown
Paralleling control functions  Full authority electronic engine protection
 First Start Sensor System selects first genset to close to bus
Control functions
 Phase Lock Loop Synchronizer with voltage matching
 Time delay start and cool down
 Sync check relay
 Real time clock for fault and event time stamping
 Isochronous kW and kVar load sharing
 Exerciser clock and time of day start/stop
 Load govern control for utility paralleling
 Data logging
 Extended Paralleling (baseload/peak shave) Mode
 Cycle cranking
 Digital power transfer control, for use with a breaker pair to
 Load shed
provide open transition, closed transition, ramping closed
 Configurable inputs and outputs (20)
transition, peaking and base load functions.
 Remote emergency stop
Other control features
 150 watt anti-condensation heater
 DC distribution panel
 AC auxiliary distribution panel
Alternator data
 Line-to-neutral and line-to-line AC volts
 3-phase AC current
 Frequency
 kW, kvar, power factor kVA (three phase and total)
 Winding temperature
 Bearing temperature

power.cummins.com
©2015 Cummins Power Generation Inc. | NAS-5829b-EN (8/15)
Ratings definitions
Emergency standby power (ESP):
Applicable for supplying power to varying electrical
loads for the duration of power interruption of a reliable
utility source. Emergency Standby Power (ESP) is in
accordance with ISO 8528. Fuel Stop power in
accordance with ISO 3046, AS 2789, DIN 6271 and
BS 5514.
Limited-time running power (LTP):
Applicable for supplying power to a constant electrical
load for limited hours. Limited Time Running Power
(LTP) is in accordance with ISO 8528.
Prime power (PRP):
Applicable for supplying power to varying electrical
loads for unlimited hours. Prime Power (PRP) is in
accordance with ISO 8528. Ten percent overload
capability is available in accordance with ISO 3046,
AS 2789, DIN 6271 and BS 5514.
Base load (continuous) power (COP):
Applicable for supplying power continuously to a
This outline drawing is for reference only. See PowerSuite
constant electrical load for unlimited hours. Continuous Library for specific model outline drawing number.
Power (COP) in accordance with ISO 8528, ISO 3046,
AS 2789, DIN 6271 and BS 5514. Do not use for installation design
No sustained overload capability is available at this rating.
Dim “A”* Dim “B”* Dim “C”* Set Weight* Set Weight*
Model mm (in.) mm (in.) mm (in.) dry kg (lbs) wet kg (lbs)
C3500 D5e 7902 (311) 3028 (119) 3663 (144) 29526 (65092) 31194 (68771)
C3750 D5e 7902 (311) 3028 (119) 3663 (144) 29526 (65092) 31194 (68771)
* Weights and dimensions represent a set with standard features and alternator frame P80X.
See outline drawings for weights and dimensions of other configurations.

Codes and standards


Codes or standards compliance may not be available with all model configurations – consult factory for availability.
This generator set is designed in facilities
This generator set is available with CE
certified to ISO 9001 and manufactured in
certification.
facilities certified to ISO 9001 or ISO 9002.
All models are CSA certified to product class This generator set has been designed to
4215-01.
ISO8528 comply with ISO8528 regulation.

Engine certified to Stationary Emergency U.S. The engine used in this generator set complies
EPA New Source Performance Standards, with TA Luft Standards of 2g/nm3
U.S. EPA 40 CFR 60 subpart IIII Tier 2 exhaust emission (4.8g/bhp-hr) NOx at prime rating corrected to
levels. 5% oxygen content and measured in
accordance with ISO 8178.

Cummins Power Generation

Europe, CIS, Middle East and Africa Americas Asia Pacific


Manston Park Columbus Ave. 1400 73rd Avenue N.E. 10 Toh Guan Road #07-01
Manston, Ramsgate Minneapolis, MN 55432 USA Singapore 608838
Kent CT12 5BF United Kingdom Phone 763 574 5000 Phone 65 6417 2388
Phone 44 1843 255000 Fax 763 574 5298 Fax 65 6417 2399
Fax 44 1843 255902

Warning: Back feed to a utility system can cause electrocution and/or property damage. Do not connect to any building’s electrical system
except through an approved device or after building main switch is open.

©2015 Cummins Power Generation Inc. All rights reserved.


Cummins Power Generation and Cummins are registered trademarks of Cummins Inc. PowerCommand, AmpSentry, InPower
and “Our energy working for you.” are trademarks of Cummins Power Generation. Other company, product, or service names
may be trademarks or service marks of others. Specifications are subject to change without notice.