You are on page 1of 2

ASI Controls ASIC/1-8655

Packaged Air Conditioner Controller

The ASIC/1-8655 is a pre-programmed digital controller for use in the


ASIC/1-8655 Features control of Packaged Air Conditioner units for both new construction
and retrofit applications. This controller maintains the space
• Sequences include: temperature by turning on and off stages of heating or cooling. The
1& 2 Stage Heat Pumps controller has personalities for one and two stage heat pumps and up to
Up to 4 Stage Air Conditioners four stage air conditioning units.
• 8 Form C (NO,NC) relay The controller monitors zone temperature through the WS-0X1 Wall
outputs with isolated return. Sensor. It calculates the cooling or heating requirement for the space
based upon comparing this temperature with the cooling and heating
• 2 Analog Outputs 0-10 Vdc setpoints. The WS-051 Digital Display Wall Sensor can be used with
this controller. Control of the indoor fan is included. It also has
• 2-Part Screw Terminals optional auxiliary cooling and auxiliary electric or gas heat. The
• Compatible with WS-051 optional modulating economizer can be based on discharge air or
Digital Wall Sensor mixed air temperature. The optional changeover analog output can be
used for hydronic heating or cooling.
• Other Features include: The ASIC/1-8655 controls compressors, and electric or gas heat. An
Modulating Economizer optional modulating-economizer is controlled as the first stage of
CO2 Demand Ventilation cooling. It has 8 N.O./N.C. relays with isolated return, so that no
Auxiliary Heating / Cooling interposing relays are necessary. It has two analog outputs, 0 to 10 Vdc,
Lighting Control 5 mA, that can be assigned to heating, cooling, modulating economizer,
Changeover Analog Output or changeover heating/cooling. The controller is mounted on a steel
• Compatible with ASI WebLink base, and has an optional steel top cover.
& ASI Data Server Products No user programming or calibration is necessary. The pre-configured
controller allows newly installed zones to be started up quickly and
efficiently. A pre-tuned PI algorithm means that controllers can
accurately maintain space temperature.
The controllers include after-hours override, and user temperature
adjustment. Afterhours usage is automatically stored at each unit.
Time-based features such as scheduled changes in setpoints may be
used when the controller is connected in a network that can synchronize
the ASIC/1 internal software clock by broadcasting a time message.
The ASIC/1-8655 can operate-
stand alone or as part of a
larger communicating control
network with other ASI
controllers. Communication at
speeds up to 19,200 baud
means rapid access to
information. This enables
integrated control of the
complete mechanical system to
ensure optimum building
performance. Temperatures,
setpoints, and other controller
information may be easily
reported to ASI WebLink, or
any Windows based software
that is a client for OLE for
Process Control (OPC).
The ASIC/1-8655 has flash
programming. The firmware
can be upgraded over the local
RS-485 communications bus.

DOC-1565 (2006-05-31) 2202 Camino Ramon, San Ramon, CA 94583 925 866-8808
http://www.asicontrols.com
ASI Controls ASIC/1-8655
Packaged Air Conditioner Controller

Specifications
Control Power 2 A Fuse Power

L1
Fuse
Supply Voltage: 24 Vac/Vdc +/- 15%, 50/60 Hz,

R29
Power Consumption: 12 VA (plus loads)

NEU HOT
24 Vac/dc
D2
Fuse: 2 A. 24 Vac

BT1

L2
Power
Outputs 10

C1
Binary Output: 8 Form C Relays, NO/NC

D3
24 Vac

24 Vac, 5 A, Pilot Duty

C2
2 groups of 4 outputs with
U9

OUTPUTS U8

common return

TB2
Return

R
Analog Output: 2, 0-10 Vdc, 5 mA, 8 bit.

NC NO NC NO NC NONC NO
OUT1 OUT2 OUT3 OUT4

DS1
LED
Relay Relay
Inputs 8

ASI Controls ASIC/1-8655


Type: Universal Analog/Binary

DS2
LED

Range: 0 to 5 Vdc Relay


Outputs Relay Relay

DS3
LED
Resolution: 10 bit, 0.1% full scale
Common
Accuracy: 1%

DS4
LED

Temperature Sensor: WS-0X1


Relay Relay

R
3 kohm at 77 oF (25 oC) thermistor. Return

R
Communications

NC NONC NO NC NO NC NO
OUT5 OUT6 OUT7 OUT8

DS5
LED
Format: RS-485 1/2 duplex Relay Relay
Protection: 100 mA polyswitch fuse, TVS

DS6
LED

Baud Rate: up to 19,200 baud Relay


Outputs
Repeater: ASI Converter/Repeater

DS7
LED

every 32 devices
DS8
LED
J3
Connections
Power and I/O: 2 part screw terminals Return
R

OUTPUTS
Communications: 3 Position screw terminals WS-0xx

J1

WS-0XX
P4

U12
Zone Sensor: 8 position, modular jack, INPUTS
P5 Wall Sensor
for use with ASI cable, SCP-0XX
C

Rx
LED LED

TB6 Tx
Other
C8051F000

IN1
U1

Indication: LEDs, 1 Power, IN2

C
P3
IN3
RS-485
8 Output, 2 RS-485
Y1

-
IN4 P2
Dimensions: 3.25" x 9.50" x 1.50" Universal
C52

C53

+
Inputs IN5
83 mm x 241 mm x 38 mm
PWR

LED
IN6
U11

Steel Base: 4.5" x 9.7" x 0.70" (WxLxH) IN7


114 mm x 246 mm x 18 mm
JTAG

IN8
J2

with mounting holes on center


C

VR7
VR6

P6 P1
6.7" x 3.95" (170 mm x 100 mm ) INPUTS
AO1
AO2

Weight with base: 1.34 lb (0.61 kg) Analog


C

C
AOut

Pull-up
Outputs
Resistors
Environmental Pull-ups R8 R7 R6 R5 R4 R3 R2 R1

Operating: -22 to +122 oF (-30 to 50 oC)


10 to 95% rh non-condensing
Storage: -40 to +167 oF (–40 to 75 oC)
5 to 95% rh non-condensing How to Order: Order Number
UL Listing & CE Packaged AC Controller ASIC/1-8655
Rated as a Class 2 Device, Pilot Duty
UL916, Open Energy Management
Accessories: Order Number
Wall Temperature Sensor WS-0XX
E123287 11PK
Sensor Cable SCP-0XX
ASIC/1-8655
Top Cover Kit CE-8655

Meets CE requirements. Software & Documentation: Order Number


ASI Expert Configuration Software ASI Expert
ASIC/1-8655 User Manual 8655 Manual

DOC-1565 (2006-05-31) 2202 Camino Ramon, San Ramon, CA 94583 925 866-8808
http://www.asicontrols.com

You might also like