JOB n° Rev. 00 Sheet 1/1 ELECTRICAL TEST REPORT OPT ROLLING MILL [amNT RoeM PRESSURE TEST ON MEDIUM VOLTAGE 33KV CABLES [Desexiption Job: Medium Voltage Cable connections 33 KV Reference DWG: [Nominal Tension Uo/UKV 33KV 50 Hz TEC 298 International Saree Cenc: WOE’ S08iae 1Mia- SECTION& | VOLTAGESET | TIME CABLE IDENTIFICATION | -ryPH of CABER|| _‘TESTI(ASEY) RESULT INCOMING 4x 500 x3 Té i 4x 300-3 13 GaN 1 Min. oo 2)D01 E10 + PTRO4 ls. )p01 E10-+ PFROZ 13 "GaN Min. oe ‘TEST EQUIPMENT -HEGGER KYoRITSU-K3125 (sav) Date: Hoe /2o45 C\s epi \ Deng SROM MLV Cable SK JOB n° ELECTRICAL TEST REPORT ies gh Ne ee ee ee eae Rev. 00 Sheet 1/1 "ORC! ROLLING MILL SENT BSRM PRESSURE TEST ON MEDIUM VOLTAGE 33KV CABLES Description Job: ‘Medium Voltage Cable connections 33 KV Reference DWG: ‘Nominal Tension Uo/UKV 33KV 50 Hz TEC 298 Taieratonal Sndard- Pressure test _70KV_50H2_1Min. SECTION & | VOLTAGESET | TIME ‘TYPE of CABLE | __TEST (33 Kv) TEST. CABLE IDENTIFICATION RESULT Li INCOMING T6 =)D0{ E40 + PTROY l=)po4 210+ PTROS ‘TEST EQUIPMENT HEGGER KyoRITSU-K3125 (Sov) ee Bs — 5 0 Rey F Hee /2o45 Ce gi \ Daa MLV ales wat SK doe JOB n° Rev 00 Sheet 1/1 ELECTRICAL TEST REPORT ROR’ ROLLING MILL. ues RgRME PRESSURE TEST ON MEDIUM VOLTAGE 33KV CABLES Description Job: ‘Medium Voltage Cable connections 33 KV Reference DWG: ‘Nominal Tension Uo/UKV 33KV 50 Hz TEC 298 Iniersational Standard - Prestute test OKV 50H2 IMin. SECTION& | VOLTAGESET | TIME CARIE IDEN TICS TION: | IVER of GAMER |" TESECASKY) ‘TEST RESULT =)D01E40+4 PTROZ =)DO1 E40+ PTROT Ie ArO4 E404 PTROL T3 1x306x3 ‘TEST EQUIPMENT a HEGGER KyoRITsD- K325 (Sd00V ) cs ~ BmeL BsRM 8 Bae etfee/215 €\ tien api Dest BSAA MEV Cables a BK ee TRASFORMER TEST | 7/02/2015 . Panel TRReference | _Title Notes Results . Terre Toomosee Ima ima ry 2a 2 [Ohm [Secondary 2.9) 3 [Megger Test _[Prim/Seo. infinite 4] last [Ohm [Primary zal 3 [Ohm [Seconda a7] Gi [Megger Test |Prim/Sec. — infinite 7| laorer [ohm Primary al 3] [Ohm [Secondary, 02] 9] IMegger Test _[Prim/Sec. infin i) lao [ohm [Primary transformer cores show a slight oxidation caused by humidity, which does not involve any inconvenience for the functionality | transformers, BSRM Group ‘Sub-Station tenance Report Name of Sub-Station/Installation: - Equipment: - Transformer: 4500 _KVA/MVA, Manufacturer: - JB0f1E10 PTR OF Date of Maintenance:- BXARED) EVA si. Items | Condition Remarks no 01 | Overall leaning Cleaned( ) ~~ Not cleaned (7) Claaned popeky 4 Oil level tow() | High() | Normal(/) | Defective indicator ( ) Oil Leak Yes(_) No (V) __| Oil condition Good (Vv) Not Good ( ) (Visual) 04 | Temp. Meter Good Defective {a)oil W () (b) Winding () HE) 05 | Color of SiticaGel_| Color: ] Ok(/) | NotOk() ] Changed( ) 06 | Tap changing Manual Auto: Ok Not Ok devise wv |) 3) O) 07 | Bushing Good | Cracked Punched Others: “1 O a 08 | Buchholz Relay Good () Defective ( ) (09 | Continuity test RYB. ry-bn ‘Ok (Yj | Not ok OK(_) Not ok 10 | Test of oll Oil sample Test result Di-electric strength Tal Not abbeetad , A” | cen a) eee 1) 11 | Insulation test ‘Applied | insulation value at- °C AF ‘Specification of Position Volt insulation tester: 15sec. | 30sec. | 60sec. | R60/R30 R6O/R15 HTLTG |r eee 3000 32.684, Analogy i ial 5000 Stee Digit stow Datel _[ EFATS ]3500 46S ‘Comment:- ~ BSRM Group Sub-Station Maintenance Report Name of Sub-Station/Installation:- JDO{E40 — Pre{ Equipment: - Transformer: 4000 _KVA/MVA, Manufacturer: - Date of Maintenance:- sl. Items Condition Remarks no 01 | Overall cleaning leaned (4 Not cleaned ( ) 02 | Oillevel tow( ) | High( ) | Normal (7) Defective indicator ( ) 03 | Oil Leak Yes() No Oil condition Good (Vf Not Good ( ) (Visual) ‘04 | Temp. Meter Good Defective (aout wv Q (6) Winding ) {) 05 | Color of Silica Gel Color: Ok(A Not Ok( ) Changed( ) 06 "| Tap changing Manual | Auto Ok Not Ok : devise (i () () () 07 | Bushing Good | Cracked | Punched Others 7) O O oO 08 | Buchholz Relay Good (i Defective ( ) ‘09 | Continuity test RYB rybn Ok (Yj | Not ok oK(_) Not ok 10 | Test of off Ol sample Test result Di-electric strength - ‘Taken ‘Not a (| taken os () 1 | insulation test ‘Applied | insulation value at- ___ °C AF Specification of Position | Volt insulation tester: 15sec. | 30sec. | 60sec. | RGO/RIO R6O/RI5 HT-LTG 0 hs 5000 At G| — HLT | So00 #23 est| Analog/Digital TG 13500 B32 cal ‘Comment:- My we BSRM Group Sub-Station Maintenance Report Name of Sub-Station/Installation:- PO{E19 PTROZ Equipment: - Transformer: 4.000_KkVA/MVA, Manufacturer: - Date of Maintenance:- sl. Items Condition Remarks MO} 01 | Overall cleaning Cleaned (4 Not cleaned( ) 02 | Oillevel Low( ) | High( ) | Normal (A Defective indicator (_) 03 | Oilteak Yes( ) No (J Oil condition Good (4 Not Good ( ) (Visual) (04 | Temp. Meter (Good Defective _ {ajou _ oO (b) Winding we 05 | Color of Silica Gel Changed( ) 06 | Tap changing Not Ok devise me) 07 | Bushing Others () 08 | Buchholz Relay Good (4 Defective ( ) (09. | Continuity test RY-B yb ~| Ok (i | Notok ‘Ok(_) Not ok 10 | Test of oil Oil sample ‘Test result Di-electric strength |— + Taken | Not Quprd abeehed . ( taken . () 11 | insulati t ‘Applied | insulation value at-___ °C Specification of Position Volt ianidation tatters 15sec. | 30sec. | 60sec. | R60/R30 R6O/R15, on HEUTE | 5000 3,65 6x v. ce aeeee ||Enata| oo 688 cal Analog/Digital | THT |DE0O 3 af asl a - ‘Comment:- Le z So , 6 BSRM Group Sub-Station Maintenance Report Name of Sub-Station/installation:- IDOL EXO PTROZ Equipment: - Transformer: _4600_KVA/MVA, Manufacturer: - Date of Maintenance: Items Condition Remarks ‘Overall cleaning leaned (4 Not cleaned () ~ Oillevel tow() | High() | Normal(7) |” Defective indicator ( ) ‘Oil Leak Yes( ) No (4 ‘ll condition Good ‘Not Good ( ) (Visual) (04 [ Temp. Meter ‘Good Defective {ajoi (2) () {b) Winding () () 05 | Color of SilicaGel | Color: ] Ok(i) | NotOk() | Changed( ) (06 | Tap changing ‘Manual | Auto Ok Not Ok devise WV. () () () 07 | Bushing Good | Cracked | Punched Others ” a) WO O ‘08 | Buchholz Relay Good (4 Defective ) 09 | Continuity test RYB rybn ‘Ok (Vf |_Notok Ok(_) Not ok Test of oll il sample Test result Drelectrc strength Fran] Not ‘Qypk arbeccled . “ taken . () 7 Insulation test ‘Applied | insulation value at-___ °C AF Se Volt | Gece. | Sosec. | 60sec. | R6O7RI0 R60/RI5 ae ATLTE |5900 14,5068 eS RFT [5000 525 esl igital Analog! Diatal THIS [D505 Bical ‘Comment:- Ux, Equipment: - Transformer: 4 BSRM Group Sub-Station Maintenance Report ‘Name of Sub-Station/installation:- JDO4 E10. PrRog © _KVA/MVA, Manufacturer: - Date of Maintenance:- Items Condition ‘Overall cleaning Cleaned (V) Not cleaned ( ) Oil level Low( ) | High( ) Normal (\/) Defective indicator ( ) 03 | Oil Leak Yes(_) No (“f_ Oil condition Good (4 Not Good) {Visual) 04 | Temp. Meter Good Defective (2)0H wi () (b) Winding ) ) 05 | Color of Silica Gel | Color: | Oxi Not Ok() | Changed( ) 06 | Tap changing Manual Auto: Ok Not Ok devise of | i) QO 07 | Bushing Good | Cracked Punched Others janet) oO) a 08 | Buchholz Relay Good (4 Defective ( ) 09° | Continuity test RYB ryba Ok (4 [Not ok Ok{_) Not ok 10 | Test of olf Oil sample Test result Drelectrc strength | — at 4 ( taken . () 31 _| insulation test ‘Applied | insulation value at- °c Specification of Position Volt insulation tester:e 15sec. | 30sec. | 60sec. RGO/RIS HTATe ne 5000 443 Go| TUT | 5000 6,62 GU Analog/ Digital mee Petal arATE [60m 293 os ‘Comment:- Wy. NN IA ISP LLL BSRM Group Sub-Station Maintenance Report Name of Sub-Station/installation:- § TF. Equipment: - Transformer: 1500 _ KVA/MVA, Manufacturer: - Date of Maintenance:- Items Condition Remarks Overall cleaning Cleaned (VJ Not cleaned ( ) Oil level tow( ) | High( ) |” Normal(“f~ | Defective indicator ( ) Oil Leak Yes(_) No WY Oil condition Good (Vf Not Good () (Visual) Temp. Meter Good Defective (a)oil O () (b) Winding () HE) Color of Silica Gel) “Color: | Ok( ) | Not Ok() | Changed (Wf Tap changing Manual Auto Ok Not Ok devise | ) O Bushing Good | Cracked Punched Others “1 oO a) Buchholz Relay Good (fF Defective ( ) Continuity test R-Y-B ry-b-n Ok (Vf | Notok | ox) Not ok Test of olf (il sample Test result Di-electric strength r Taken | Not eed. yn | oe + | QRpek athe () | Insulation test Applied | insulation value at-___ °C AF Hil cen ostion | volt iSsec. | 30sec. | 60sec. | R6O/RIO REO/RIS | HTLTe ae 5000 S42Gn tra [5000 6,25 Gx U-HTG 2500 05 BSRM Group Sub-Station Maintenance Report Name of Sub-Station/Installation: - Tie Date of Maintenance:- Sl. Items Condition Remarks no 01 | Overall cleaning Cleaned (~f Not cleaned( ) 02 | Oiliever tow () High () | Normal ( Defective indicator ( ) 03 | Oil teak Yes(_) No (Uy Oil condition Good (Vf Not Good ( ) (Visual) 04” [ Temp. Meter Good Defective (a)oit ) () (bo) Winding () () 05 | Color of Silica Gel | “Color: | Ok() | Not Ok() ‘Changed (j~ 06 | Tap changing Manyal | Auto Ok Not Ok devise tl () () () 07 | Bushing Good | Cracked | Punched Others () () () () 08 | Buchholz Relay Good ( ) Defective ( ) NA 09 | Continuity test RY rybn Ok (4 | Notok ‘Ok( ) Not ok 10 | Test of oll il sample Test result Di-electric strength a Taken | Not wh” | atom 1 | Rapak alread . () 21 | Insulation test ‘Applied | insulation value at-___ °C AF eae Position | Wot re sone 60sec. | REO/R30 R6O/RIS wre ow. 3200 SF en ara T5000 51560. Analog Distal ate Tpeqp) 13 Ga ‘Comment:- MW OSes BSRM Group Sub-Station Maintenance Report ‘Name of Sub-Station/Installation:- — T Equipment: - Transformer: 2000 _KVA/MVA, Manufacturer: - Date of Maintenance:- si. Items Condition no 01 | Overall cleaning ‘Cleaned (J Not cleaned ( ) 02 | Oillevel Low( ) | High( )| Normal( ) Defective indicator (_ ) 03 | Oil Leak Yes(_) No( Oil condition Good (Vf Not Good ( ) (Visual) 04 | Temp. Meter Good Defective (joi O O (6) Winding () () 05 | Color of Sitica Gel | “Color: | Ok( ) | NotOk(W” | Changed(~ Tap changing Manual Auto Ok Not Ok devise ( ) fe) () 07 Bushing Good | Cracked Punched Others: wv | 0) O oO 08 | Buchholz Relay Good (4 Defective ( ) 09 | Continuity test R-Y-B rybn Ok (4 [Not ok Ok(_) Not ok 10 | Test of oll, Oll sample Test result : Taken Not uU taken : ay 3a) insulation test ‘Appited | Insulation value at ———°C if folt Sess [On| sae [ame Pee wow. (tts {5000 10 6.2. 7 HrtT 15000 St Gu Analog/ Distal TiraTs [DE0p Gil Gal ‘Comment:- BSRM Group Sub-Station Maintenance Report Name of Sub-Station/Installation:- T1O(TR FURNACE ) Equipment: - Transformer: 2000 KVA/MVA, Manufacturer: - Date of Maintenance:- Sl. Items Condition Remarks no oe 01 | Overall cleaning Cleaned (“f Not cleaned ( ) 02 | Olllevel Low( ) | High()| Normal(~f | Defective indicator ( ) 03 | Oil Leak ‘Yes(_) Noy Oil condition Good (J Not Good ( ) (Visual) 7 04 | Temp. Meter Good Defective {a)oit _ () () = (b) Winding =o) : 05 | Color of SificaGel | Color: | Ok() | NotOk() | Changed( (06 | Tap changing Manual | Auto ‘Ok Not Ok devise i ) ce) () 07 | Bushing Good | Cracked Punched Others: M10 Oo oO (08 | Buchholz Relay Good (4 Defective ( 09 | Continuity test RYB ry-bn [ok (7 [Not ok Okt) Not ok 10 | Test of ol! il sample Test result Di-electric strength Taken | Not 4 taken . Repo . () = 11 | insulation test ‘Applied | Insulation value at-___ °C AF Specificatior tic jolt —_ pecineationet | aston) 15sec. [ 30sec. | GOsec | ROO/RIO | REO/RLS ew [ |5000 Bronk Analog/Digital dial 25 Os alog/ Digital ; — = mer _[ Bets [2500 Had oo Name of Sub-Station/Installation: - Tl (vuTP BSRM Group Equipment: - Transformer: 4000 KVA/MVA, Manufacturer: - Date of Maintenance: sl. Items Condition Remarks no 01 | Overall cleaning Cleaned (4 Not cleaned ( ) 02 | Oillevel ‘tow( ) | High( )| Normal (4 Defective = indicator ( ) 03 | Oil Leak Yes( ) No ‘Oil condition Good (J Not Good ( ) (Visual) 04 [ Temp. Meter Good. Defective (ajo FT O {b) Winding i) () 05 | Color ofsitiea Gel [~Color: | Ok( ) | NotOk() | Changed( q-| ‘06 | Tap changing Manual| Auto | Ok Not Ok devise ¢ () () () 07 | Bushing “Good _| Cracked | Punched Others ( Mele HED Key 08 | Buchholz Relay Good (4 Defective ( ) 09 | Continuity test RY reba Ok (Ff | Notok ‘OK ) ‘Not ok 10_| Test of oil il sample Test result Di-clectric strength Taken [Not akbeehed « (| taken . | Pepe () ‘11 | Insulation test ‘Applied | insulation value at-___ °C AF Specification of |_| Pesition ve 15sec. | 30sec. | 60sec. | REO/RO REOPRIS tow ets [5000 C24 Gu _ ret [5000 72 Gx Analog/ Distal FEATS [9500 4 Gal ‘Comment:- 7 UD a BSRM Group Sub-Station Maintenance Report ‘Name of Sub-Station/Installation: - Té Date of Maintenance:- 38/0 ev Sl. Items Condition Remarks no 01 | Overall cleaning Cleaned (J Not cleaned( ) 02 [Oillevel tow( ) | High() | Normal(vf | Defective _ indicator ( ) 03 | OllLeak Yes( ) Not Oil condition Good ( Not Good ( ) (Visual) 04 | Temp. Meter Good Defective (joi a O {b) Winding () () 05 | Color of SilicaGel | Color: | Ok( ) | NotOk(4 | Changed(-7 | 06 | Tap changing. Manual Auto Ok ‘Not Ok |__| devise ia) a) O 07 | Bushing Good | Cracked Pur Others: M | Uy) ey oO 08 | Buchholz Relay Good (Vr Defective ( ) 09 | Continuity test RY-B ry-b-n ‘Ok ( Not ok ‘Ok(_) Not ok 10 | Test of olf Oil sample ‘Test result Di-electric strength ~ Taken Not ie ted ti taken 7 Dapot Ke) | Insulation text ‘Appiled | insulation value at- ___ °C AF erase cece (ceca | a |B ver | 90 once ec | euro [i nears wow tts [5000 34 64 frit | S000 42 60 Analogy Digital UPHTS [5000 39 Gal ‘Comment:- BSRM Group ib-s ‘Name of Sub-Station/Installation: - Equipment: - Transformer: 3500 KVA/MVA, Manufacturer: - Date of Maintenance:~ Si. Items Condition no 01 | Overall cleaning Cleaned (7) Not cleaned ( ) ‘02 | Oillevel Low( ) | High() | Normal (4 Defective indicator (_) 03 | Oilteak Yes(_) No Oil condition Good (Vf Not Good ( ) (Visual) 04 | Temp. Meter Good Defective (a)oit ¢ O (b) Winding QO ( 05 | Color of SilicaGel | Color: | Ok(/f | NotOk() | Changed( ) 06 | Tap changing Manual Auto Ok Not Ok devise ( () Ke) () 07 | Bushing Good | Cracked Punched Others: ea) a O 08 | Buchholz Relay Good (J Defective ( ) (09 | Continuity test RY-B rybn ‘Ok (Vf | Notok Ok(_) Not ok 10 | Test of off Oil sample Test result a ie Taken Not 4 taken . () ‘11 | insulation test ‘Applied | insulation value at-___ °C AF Specificatic Position feaapel Wor [asec [ 30sec. | 60sec. R6O/RAS to ke HT-LTG S000 FF su sow Dea! HTT 15000 382 cn Analog/Digital Tate [3500 93 es ‘Comment:-

You might also like