Professional Documents
Culture Documents
Intouch - IO Drivers Configuration
Intouch - IO Drivers Configuration
1. Start the driver from the “Start > All Programs” Windows menù.
2. It is necessary that the driver starts before inTouch application and that it remains active
during supervision service: to do this go in “Configure > Settings” and activate the “Run
as a windows service” option.
3. Define the adapter card, using “Simatic menu > Configurator Console”:
4. Select “CP_H1_1:” and choose for this access point the adapter card with “(Auto)”
option.
5. After this operation open PG/PC interface from SIMATIC menu to verify that the
selected application access point is correct. If it is not, select the right one:
6. In S5TI500 driver window, select “Configure > Adapter Card Setting”:
7. To insert the right Adapter Card press “Automatic” button, select “CP_H1_1:” and then
press “Add” button. If nothing appears close and open again the “Adapter Card
Settings” window.
8. Insert the adapter card settings and add the desired topics through “Configure > Topic
Definition”
9. Press the “New…” button to add a new Topic:
10.
11. Complete this window with topic name (retracable in inTouch Maker), MAC or IP
address and TSAP. At last select “CP_H1_1:” in the “NetBIOS Adapter Card” field
When communication is started in the driver main window will appear the list of all topics along with their
communication status, number of read items, errors and write statuses.
Driver for RSLogix: DASABCIP
DASABCIP is the driver used to communicate with RSLogix PLCs. The IO server must be configured directly
on DASABCIP application.
7. Insert all the active PLC topics: their names can be retraced in inTouch Maker
8. Repeat the above operations 3-7 for all the necessary PLCs
Driver for Mitsubishi: DASMTEthernet
DASMTEthernet is the driver used to communicate with Mitsubishi PLCs. The IO server must be configured
directly on DASMTEthernet application.
Here, only the master HMI, when the variable that identifies the measure status
(.._TP_MEAS_STAT) indicates that a new measure is arrived(status: 4), all values are transferred to
PLC.
The function is a DataChangeScript, so it is called every time the MEAS_STAT variable values
changes.