Wall Lateral Force - IBC
Wall Lateral Force - IBC
CLIENT : DESIGN BY :
JOB NO. : DATE : REVIEW BY :
Lateral Force for One-Story Wall Based on IBC 2006
INPUT DATA
WALL THICKNESS t = 8 in
PARAPET HEIGHT hp = 4 ft
WALL HEIGHT h = 14 ft
TOTAL WALL DENSITY r = 150 pcf
SEISMIC PARAMETER SDS = 0.54 (ASCE 7-05 Sec 11.4.4)
SEISMIC DESIGN CATEGOR SDC = C
DIAPHRAGM FLEXIBLE ? (0=no, 1=yes) 1 Yes
SEISMIC IMPORTANCE FACTOR I = 1 (ASCE 7-05 Tab 11.5-1)
WIND IMPORTANCE FACTOR I = 1 (ASCE 7-05 Tab 6-1)
BASIC WIND SPEED V = 90 mph
EXPOSURE CATEGORY (B, C, D) = C
TOPOGRAPHIC FACTOR KZt = 1 Flat, (ASCE 6.5.7.2)
DESIGN SUMMARY
Out-of-plane force for wall design w1 = 22.5 psf (Wind governs)
Out-of-plane force for parapet design w2 = 61.7 psf (Wind governs)
Out-of-plane force for anchorage design Fanch = 440 plf (Horizontal direction)
(The governing seismic forces have been reduced by 0.7 for ASD)
WIND ANALYSIS
Out-of-plane wind force for wall design (ASCE 7-05, Eq.6-22)
h hp
F anch ,wind w1,w ind h p 1 w 2,wind = 440 plf (Horizontal)
2 2h
SEISMIC ANALYSIS
Out-of-plane seismic force for wall design (ASCE 7-05, Sec.12.11.1)
Out-of-plane seismic force for parapet design (ASCE 7-05, Sec. 13.3.1)
1.2a p S DS I pW p
w 2, seismic MAX 0.3S DS I pW p , MIN , 1.6 S DS I pW p 0.54
= 0.65 Wp = 64.8 psf
R p
Where : ap = 2.5 , Ip = 1.0 , Rp = 2.5
(ASCE Tab. 13.5-1) (ASCE Sec. 13.1.3) (ASCE Tab. 13.5-1)
h h p
2 2
hh p
F anch ,seismic MAX 0.4 S DS I W p , 0.1W p , 400 S DS I , F min 2.80 Wp =
2h 2h
280 plf (Horizontal)
(Not applicable)
Where : Fmin = 280 plf
(ASCE Sec. 12.11.2)
For seismic design category C and above, flexible diaphragm (ASCE 7-05 Sec. 12.11.2.1)
h h p
2 2
h h p
, 400 S DS I , F min
F anch , seismic MAX 0.8S DS I W p , 0.1W p
5.00 Wp =
2h 2h 500 plf (Horizontal)
(Applicable)
For seismic design category C and above, rigid diaphragm (ASCE 7-05 Sec. 12.11.2 & Sec. 13.3.1)
hh p
2
1.2a p S DS I p
F anch , seismic MAX MAX 0.3S DS I p , MIN , 1.6 S DS I p W p , 400 S DSI , F min
R p 2h
= 5.00 W = 500 plf (Horizontal)
p (Not applicable)
Where : ap = 1.0 Rp = 1.5
(ASCE Tab. 13.5-1) (1.5, ASCE 13.4.2 or 2.5, ASCE Tab 13.5-1)
PROJECT : PAGE :
CLIENT : DESIGN BY :
JOB NO. : DATE : REVIEW BY :
Lateral Force for One-Story Wall Based on IBC 2003
INPUT DATA
WALL THICKNESS t = 8 in
PARAPET HEIGHT hp = 4 ft
WALL HEIGHT h = 14 ft
TOTAL WALL DENSITY r = 150 pcf
SEISMIC PARAMETER SDS = 0.54 (IBC Sec.1615.1.3)
SEISMIC DESIGN CATEGOR SDC = C
DIAPHRAGM FLEXIBLE ? (0=no, 1=yes) 1 Yes
IMPORTANCE FACTOR Iw = 1 (IBC Tab. 1604.5)
BASIC WIND SPEED V = 90 mph
EXPOSURE CATEGORY (B, C, D) = C
TOPOGRAPHIC FACTOR KZt = 1 Flat, (ASCE Eq.6-3)
DESIGN SUMMARY
Out-of-plane force for wall design w1 = 22.5 psf (Wind governs)
Out-of-plane force for parapet design w2 = 61.7 psf (Wind governs)
Out-of-plane force for anchorage design Fanch = 440 plf (Horizontal direction)
(The governing seismic forces have been reduced by 0.7 for ASD)
WIND ANALYSIS
Out-of-plane wind force for wall design (ASCE 7-02, Eq.6-22)
h hp
F anch ,wind w1,w ind h p 1 w 2,wind = 440 plf (Horizontal)
2 2h
SEISMIC ANALYSIS
Out-of-plane seismic force for wall design (IBC 2003, Sec.1620.2.7)
Out-of-plane seismic force for parapet design (ASCE 7-02, Sec. 9.6.1.3)
hh p
2 2
h h p
, 400 S DS I E , F min
F anch, seismic MAX 0.4 S DS I EW p , 0.1W p
2.80 Wp =
2h 2h 280 plf (Horizontal)
(Not applicable)
Where : Fmin = 280 plf
(IBC Sec.1604.8.2)
For seismic design category C and above, flexible diaphragm (IBC 2003, Sec.1604.8.2 ,1620.2.7, & 1620.3.1)
h h p
2 2
h h p
MAX 0.8 , 0.1W , 400 S DS I E , F min
F anch ,seismic S DS I EW p
5.00 Wp =
2h
p
2h 500 plf (Horizontal)
(Applicable)
For seismic design category C and above, rigid diaphragm (IBC 2003, Sec.1604.8.2 ,1620.2.7, & ASCE Sec. 9.6.1.3)
2
1.2a p S DS I p h h p
F anch , seismic MAX MAX 0.3S DS I p , MIN , 1.6 S DS I p W p , 400 S DS I E , F min
R p 2h
= 3.00 W = 300 plf (Horizontal)
p (Not applicable)
Where : ap = 1.0
(ASCE Tab.9.6.2.2)
PROJECT : PAGE :
CLIENT : DESIGN BY :
JOB NO. : DATE : REVIEW BY :
Lateral Force for One-Story Wall Based on IBC 2000
INPUT DATA
WALL THICKNESS t = 8 in
PARAPET HEIGHT hp = 4 ft
WALL HEIGHT h = 14 ft
TOTAL WALL DENSITY r = 150 pcf
SEISMIC PARAMETER SDS = 0.54 (IBC Sec.1615.1.3)
SEISMIC DESIGN CATEGOR SDC = C
DIAPHRAGM FLEXIBLE ? (0=no, 1=yes) 1 Yes
IMPORTANCE FACTOR Iw = 1 (IBC Tab. 1604.5)
BASIC WIND SPEED V = 90 mph
EXPOSURE CATEGORY (B, C, D) = C
TOPOGRAPHIC FACTOR KZt = 1 Flat, (ASCE Eq.6-1)
DESIGN SUMMARY
Out-of-plane force for wall design w1 = 23.9 psf (Wind governs)
Out-of-plane force for parapet design w2 = 61.7 psf (Wind governs)
Out-of-plane force for anchorage design Fanch = 450 plf (Horizontal direction)
(The governing seismic forces have been reduced by 0.7 for ASD)
WIND ANALYSIS
Out-of-plane wind force for wall design (ASCE 7-98, Eq.6-18)
h hp
F anch ,wind w1,wind h p 1 w 2,wind = 450 plf (Horizontal)
2 2h
SEISMIC ANALYSIS
Out-of-plane seismic force for wall design (IBC 2000, Sec.1620.1.7)
Out-of-plane seismic force for parapet design (IBC 2000, Sec. 1621.1.4)
hh p
2 2
hh p
, 400 S DS I E , F min
F anch ,seismic MAX 0.4 S DS I EW p , 0.1W p
2.50 Wp =
2h 2h 250 plf (Horizontal)
(Not applicable)
Where : Fmin = 200 plf
(IBC Sec.1604.8.2)
For seismic design category C and above, flexible diaphragm (IBC 2000, Sec.1604.8.2 ,1620.1.7, & 1620.2.1)
h h p
2 2
hh p
, 400S DS I E , F min
F anch ,seismic MAX 0.8S DS I EW p , 0.1W p
5.00 Wp =
2h 2h 500 plf (Horizontal)
(Applicable)
For seismic design category C and above, rigid diaphragm (IBC 2000, Sec.1604.8.2 ,1620.1.7, & 1621.1.4)
2
hh p
1.2a p S DS I p
F anch , seismic MAX MAX 0.3S DS I p , MIN , 1.6 S DS I p W p , 400 S DS I E , F min
Rp 2h
= 3.00 W =p 300 plf (Horizontal) (Not applicable)
Where : ap = 1.0
(IBC Tab.1621.2)