Professional Documents
Culture Documents
Chapter-2 Reel Rubber Hose-Page-161-171
Chapter-2 Reel Rubber Hose-Page-161-171
Chapter Three
Chapter Two
January 2006 Requirements for firefighting and alarm equipment - Part Two
Machine Translated by Google
definition 1/2/3
Rubber hose systems are a water network that feeds rubber hoses with a reel, distributed in the building to
be protected, fed from a suitable water source and is considered one of the primary means of combating
fire, and used by building users without the need for prior training.
(b) a ah a
(d) pulley .
January 2006 Requirements for firefighting and alarm equipment - Part Two
161
Machine Translated by Google
January 2006 Requirements for firefighting and alarm equipment - Part Two
162
Machine Translated by Google
following specifications: The rubber hose is made of several layers of rubber and fabric according to the 3/2/5/1
The shapes and dimensions of the hose storage boxes are shown in Figure (3/2-3 ) and (Figure (3/2-4 ) 3/2/5/2
Spraying 4/5/2/3
Launchers of approved types with a four-position control device, open and close, push operation, spray operation.
pulley 5/5/2/3
M M
Figure (3/2-3 ) The shape and dimensions of the hose storage box with the fixed reel
January 2006 Requirements for firefighting and alarm equipment - Part Two
163
Machine Translated by Google
Figure (2/3-4 ) the shape and dimensions of the hose storage box for the moving ball
The quantity of the water source is calculated so that it is sufficient to supply two hoses as a minimum for a period of at least 30 minutes, 3/2/6/1
provided that the quantity is not less than 1900 meters in any case . to
millimeter . (b) Not less than 3 bar at the spray nozzle diameter 8.4
millimeter . (c) Not less than 5.1 bar at the spray nozzle diameter 35.6
January 2006 Requirements for firefighting and alarm equipment - Part Two
164
Machine Translated by Google
The distribution of hoses is taken into account to reach all parts of the building, so that the distance between the 3/2/6/3
be 25 mm in diameter and
not30more
mm than
in length
6 meters
. M . The hose should 3/2/6/4
millimeter .
or 35.6 millimeter
The diameter of the spray ejector hole should be 8.4 ". 3/2/6/5
T pipes according to the design calculations, so that the main feeding pipe must be a diameter of more than one 3/2/6/6
The pumps device for the hoses network must be composed of an integrated group consisting of two pumps and a 3/2/6/7
control panel according to the specifications of fire pumps (Chapter Two - Chapter Two), and it works automatically
when the pressure drops below a certain limit and closes automatically, in addition to a manual means of starting and stopping.
In light-risk places, at the discretion of the competent authority, it is permissible to connect one hose to a water 3/2/6/9
source designated for other purposes (other than fire), provided that the necessary pressure and quantity are
The installation of hoses shall take into account their proximity to exits, stairs and protected places, and if this is not possible, 3/2/7/2
The cuts or furnishings in the building do not conflict with the use of hoses. If this is not possible due to the 3/2/7/3
mm on the pipe immediately before connecting it to the hose, with an isolation valve with a diameter of 25 installed 3/2/7/4
January 2006 Requirements for firefighting and alarm equipment - Part Two
165
Machine Translated by Google
Hoses must be installed within the walls, and in cases where this is not possible architecturally, they are installed 3/2/7/5
on the face of the walls inside boxes with a door of a metal frame and a face of reinforced glass, opening a full
opening at an angle of 180 degrees so as not to be an obstacle to the passages and it is permissible for architectural reasons to be a cover
A guiding sign shall be fixed on the face of the box on which the phrase (FIRE) is written, and another 3/2/7/7
guiding sign shall be placed on the hose reel or inside the box indicating the operating method
instructions, such as opening the valve, withdrawing the hose, opening the spray gun , etc.
During the network installation works, the parts that are to be installed must be checked first to ensure that 3/2/7/8
there are no leakages from the joints and valves at the highest operating pressure.
The boxes shall be large enough to accommodate and handle the hoses and any other equipment that may be placed 3/2/7/9
within it.
It is preferred that the network pipe extensions be visible and not buried in the concrete or under the 3/2/7/10
tiles. The boxes must be installed properly, so that they are not affected by external weather factors.
3/2/7/11
Ensure that the location of the fireboxes in projects with large areas such as warehouses is free of any 3/2/7/12
obstacles obstructing their view, and if this is not possible, guiding signs and arrows should be installed at a higher level
to denote it.
The pumps must be attached to a tank (air / water) for pumps that feed more than 3 hoses. 3/2/7/13
When feeding rubber hoses from a high-pressure water source, suitable pressure relief valves must be 3/2/7/14
installed , and the appropriate number of isolation valves and filters must be installed on the network in all
cases.
January 2006 Requirements for firefighting and alarm equipment - Part Two
166
Machine Translated by Google
The following checks and tests shall be carried out at the end of implementation:
Examine the system components according to their pressures according to the specifications mentioned in 3/2/8/1
Table C ( 5-2/3).
The net must be completely emptied and pressurized with water to clean it of any impurities or sediment. 3/2/8/2
The network pressurizes the water up to 150 % of the operating pressure for two hours to ensure that there is no water 3/2/8/3
Leak .
The nearest hose to the water source is examined, where the hose is fully pulled out, and the spray ejector is opened on that 3/2/8/4
on the farthest hose as well, in order to measure the pressure and flow, and the extent ofposition,
the spraying andejection
and the then propelling
is carried out
so that it is not less than 0.8 . M. It should be ensured that the sprayer is closed well after the end of the examination.
Isolation valves diameter of 25 mm are opened and closed when the hose sprayers are open, then the valves 3/2/8/5
The pumps shall be checked manually and automatically for performance in terms of pressure and flow. In the 3/2/8/6
case of two pumps, they are checked alternately, by turning on one and cutting off the current from the other, and vice versa.
Maintenance work must be carried out in accordance with the principles of the profession, provided that it is not less than the following:
Ensure that the hose is wound in the correct manner on the reel and that there is no defect (b) that must be
observed, and that the boxes are free of any other materials.
Ensure that there are no obstacles in front of the hoses that prevent their use. (c) must
January 2006 Requirements for firefighting and alarm equipment - Part Two
167
Machine Translated by Google
Ensure the condition of the isolation valves, lubricate them, and ensure that there is no leakage. (a) must
(b) The hoses shall be turned on and the spray launchers shall be ensured that the sprayers are working , that they are secured , and that the hoses are emptied of water.
Ensure that the network pipes are well installed. (c) must
(d) The operation of the pumps and their connection and performance shall be tested according to the fire pumps (Section
II - Chapter Two).
Maintenance procedures for fire water pumps and water sources must be carried out in accordance with the 3/2/9/3
3/2/10/1 The network of rubber hoses (design stage and executive plans), see model ( 3/ 2-1 ) fire hose (suggested
Location detection of the rubber hose system, see Exhibit ( 3/2-3). 3/2/10/3
January 2006 Requirements for firefighting and alarm equipment - Part Two
168
Machine Translated by Google
Model (2/3-1 ) Checking the rubber hose network (design stage and executive plans)
M ( ) Within 40 ( )
2 The distance between the hoses
M Greater than 40
( ) Suitable
3 diameters of pipes in the net
( ) Not suitable
( ) Swinging
4 hose type
( ) Fixed
( ) Pump ( )
5 source of water
High tank ( )
Sufficient
6 Water source capacity
( ) Insufficient
()
7 Pressure available for furthest hose
Sufficient ( )
Insufficient ( ) Next to
8 Hose installation location
the outlets ( ) Away
without a box ( )
10 extinguishers
with the
hose ( )
11 Dimensions of the firebox
separated ( ) suitable ( ) unsuitable
January 2006 Requirements for firefighting and alarm equipment - Part Two
169
Machine Translated by Google
Form (2/ 3-2) Fire Hose Check - (Suggested with illustrated evidence)
..........................
2 agent
( ) approved
3 accreditation
( ) not supported
..........................
4 diameter
( ) 2 modes
Sprayer modes
5
only ( ) 3
open - close - spray - push
modes ( ) 4
modes ( )
6
Hose quality
Oscillating
7 operating
( ) Fixed ( ) Manual ( ) Auto
.......................... 8
Pipe quality
..........................
9 quality of connections
..........................
10 pipe specifications
..........................
11 connector specifications
..........................
12 quality valves
..........................
13 fuse specifications
January 2006 Requirements for firefighting and alarm equipment - Part Two
170
Machine Translated by Google
approved
2 Install the hose
(correctly)
Wrong way)
3 in place of Khartoum
As per plan
(contrary
4 Install the valve
to plan)
Correct
Hose run (thrust pressure) 5
(Incorrect)
Appropriate
Sprayer modes
6
(Inappropriate) 2 modes
7 Leakage
only ( 3 modes) 4
work
10 Water source capacity
properly)
Works
11 firebox
properly
January 2006 Requirements for firefighting and alarm equipment - Part Two
171
Machine Translated by Google
( ) obstruction ( ) no
1
obstruction ( )
(3 ) The presence of obstacles in front of Khartoum
correctly ( ) incorrectly
( ) working ( ) not
(4 ) Put the hose on the reel
working
Monthly maintenance
()
(4 ) Hose boxes case
maintenance was
January 2006 Requirements for firefighting and alarm equipment - Part Two
172