You are on page 1of 13

Machine Translated by Google

3/2 reel rubber hose systems

Chapter Three

Chapter Two

Reel rubber hose systems

January 2006 Requirements for firefighting and alarm equipment - Part Two
Machine Translated by Google

3/2 reel rubber hose systems

definition 1/2/3

Rubber hose systems are a water network that feeds rubber hoses with a reel, distributed in the building to

be protected, fed from a suitable water source and is considered one of the primary means of combating

fire, and used by building users without the need for prior training.

Systems are types 2/2/3


Systems are divided in terms of pulley movement into two types:

(a) The fixed pulley, see fig . (1-2/3).

See figure (2-2/3) .


come on

(b) a ah a

Water sources The 3/2/3


water source must be appropriate, in accordance with the design conditions and details contained in the

Water Sources Conditions (Part Two - Chapter One).

system components 4/2/3

The rubber hose system consists of the following main components:

(a) The source of water.

(b) The pipe network and its accessories.

(c) Isolation valve .

(d) pulley .

(e) The rubber hose .

(f) Spray launcher .

January 2006 Requirements for firefighting and alarm equipment - Part Two
161
Machine Translated by Google

3/2 reel rubber hose systems

Figure (1-2/3 ) a hose with a fixed reel

Figure (2/2-3 ) a hose with a movable reel

January 2006 Requirements for firefighting and alarm equipment - Part Two
162
Machine Translated by Google

3/2 reel rubber hose systems

Material specification 5/2/3

The components must be in accordance with the

following specifications: The rubber hose is made of several layers of rubber and fabric according to the 3/2/5/1

specifications mentioned in Table C ( 2/3-1 ).

The shapes and dimensions of the hose storage boxes are shown in Figure (3/2-3 ) and (Figure (3/2-4 ) 3/2/5/2

according to the specifications mentioned in Table C ( 2/3-2).

The boxes 3/5/2/3

according to the specifications


arementioned
made of steel
in Table
or aluminum
C ( 2/3-3).sheets, with a thickness of not less than 5.1 mm,

Spraying 4/5/2/3

Launchers of approved types with a four-position control device, open and close, push operation, spray operation.

pulley 5/5/2/3

According to the specifications mentioned in Table C ( 4/2/3).

M M

Figure (3/2-3 ) The shape and dimensions of the hose storage box with the fixed reel

January 2006 Requirements for firefighting and alarm equipment - Part Two
163
Machine Translated by Google

3/2 reel rubber hose systems

Figure (2/3-4 ) the shape and dimensions of the hose storage box for the moving ball

Design principles 6/2/3

The quantity of the water source is calculated so that it is sufficient to supply two hoses as a minimum for a period of at least 30 minutes, 3/2/6/1

provided that the quantity is not less than 1900 meters in any case . to

The flow is calculated to give 140 d/L at a pressure as follows: 3/2/6/2

(a) Not more than 7 bar at the entrance of the hose.

millimeter . (b) Not less than 3 bar at the spray nozzle diameter 8.4

millimeter . (c) Not less than 5.1 bar at the spray nozzle diameter 35.6

January 2006 Requirements for firefighting and alarm equipment - Part Two
164
Machine Translated by Google

3/2 reel rubber hose systems

The distribution of hoses is taken into account to reach all parts of the building, so that the distance between the 3/2/6/3

sprayer and the furthest point is

be 25 mm in diameter and
not30more
mm than
in length
6 meters
. M . The hose should 3/2/6/4

millimeter .
or 35.6 millimeter
The diameter of the spray ejector hole should be 8.4 ". 3/2/6/5

T pipes according to the design calculations, so that the main feeding pipe must be a diameter of more than one 3/2/6/6

millimeter . hose less than 50

The pumps device for the hoses network must be composed of an integrated group consisting of two pumps and a 3/2/6/7

control panel according to the specifications of fire pumps (Chapter Two - Chapter Two), and it works automatically

when the pressure drops below a certain limit and closes automatically, in addition to a manual means of starting and stopping.

It is allowed to use one pump if it feeds two hoses at most. 3/2/6/8

In light-risk places, at the discretion of the competent authority, it is permissible to connect one hose to a water 3/2/6/9

source designated for other purposes (other than fire), provided that the necessary pressure and quantity are

available for operation for a period of at least 15 minutes.

technical equipments 7/2/3

m from the surface of the tile floor.than


The 3.1
height of the reel center is not less than 0.1 m and not more 3/2/7/1

The installation of hoses shall take into account their proximity to exits, stairs and protected places, and if this is not possible, 3/2/7/2

they shall be installed in corridors.

The cuts or furnishings in the building do not conflict with the use of hoses. If this is not possible due to the 3/2/7/3

entire area of the building


necessitytoof
beusing
protected.
the building, the number of hoses must be increased so that it covers the

mm on the pipe immediately before connecting it to the hose, with an isolation valve with a diameter of 25 installed 3/2/7/4

for each hose.

January 2006 Requirements for firefighting and alarm equipment - Part Two
165
Machine Translated by Google

3/2 reel rubber hose systems

Hoses must be installed within the walls, and in cases where this is not possible architecturally, they are installed 3/2/7/5

on the face of the walls inside boxes with a door of a metal frame and a face of reinforced glass, opening a full

opening at an angle of 180 degrees so as not to be an obstacle to the passages and it is permissible for architectural reasons to be a cover

The door is made of iron

sheets. Hose reels must be installed to rotate counterclockwise with


an arrow for the direction of rotation. 3/2/7/6

A guiding sign shall be fixed on the face of the box on which the phrase (FIRE) is written, and another 3/2/7/7

guiding sign shall be placed on the hose reel or inside the box indicating the operating method

instructions, such as opening the valve, withdrawing the hose, opening the spray gun , etc.

During the network installation works, the parts that are to be installed must be checked first to ensure that 3/2/7/8

there are no leakages from the joints and valves at the highest operating pressure.

The boxes shall be large enough to accommodate and handle the hoses and any other equipment that may be placed 3/2/7/9

within it.

It is preferred that the network pipe extensions be visible and not buried in the concrete or under the 3/2/7/10

tiles. The boxes must be installed properly, so that they are not affected by external weather factors.

3/2/7/11

Ensure that the location of the fireboxes in projects with large areas such as warehouses is free of any 3/2/7/12

obstacles obstructing their view, and if this is not possible, guiding signs and arrows should be installed at a higher level

to denote it.

The pumps must be attached to a tank (air / water) for pumps that feed more than 3 hoses. 3/2/7/13

When feeding rubber hoses from a high-pressure water source, suitable pressure relief valves must be 3/2/7/14

installed , and the appropriate number of isolation valves and filters must be installed on the network in all

cases.

January 2006 Requirements for firefighting and alarm equipment - Part Two
166
Machine Translated by Google

3/2 reel rubber hose systems

and examination test 8/2/3

The following checks and tests shall be carried out at the end of implementation:

Examine the system components according to their pressures according to the specifications mentioned in 3/2/8/1

Table C ( 5-2/3).

The net must be completely emptied and pressurized with water to clean it of any impurities or sediment. 3/2/8/2

The network pressurizes the water up to 150 % of the operating pressure for two hours to ensure that there is no water 3/2/8/3

Leak .

The nearest hose to the water source is examined, where the hose is fully pulled out, and the spray ejector is opened on that 3/2/8/4

on the farthest hose as well, in order to measure the pressure and flow, and the extent ofposition,
the spraying andejection
and the then propelling
is carried out

so that it is not less than 0.8 . M. It should be ensured that the sprayer is closed well after the end of the examination.

Isolation valves diameter of 25 mm are opened and closed when the hose sprayers are open, then the valves 3/2/8/5

are opened again to ensure their operation.

The pumps shall be checked manually and automatically for performance in terms of pressure and flow. In the 3/2/8/6

case of two pumps, they are checked alternately, by turning on one and cutting off the current from the other, and vice versa.

periodic maintenance 9/2/3

Maintenance work must be carried out in accordance with the principles of the profession, provided that it is not less than the following:

Maintenance weekly 1/9/2/3

Verify the amount of water source. (a) must

Ensure that the hose is wound in the correct manner on the reel and that there is no defect (b) that must be

observed, and that the boxes are free of any other materials.

Ensure that there are no obstacles in front of the hoses that prevent their use. (c) must

January 2006 Requirements for firefighting and alarm equipment - Part Two
167
Machine Translated by Google

3/2 reel rubber hose systems

monthly maintenance 2/9/2/3

Ensure the condition of the isolation valves, lubricate them, and ensure that there is no leakage. (a) must

(b) The hoses shall be turned on and the spray launchers shall be ensured that the sprayers are working , that they are secured , and that the hoses are emptied of water.

Close the valves after testing.

Ensure that the network pipes are well installed. (c) must

(d) The operation of the pumps and their connection and performance shall be tested according to the fire pumps (Section

II - Chapter Two).

Maintenance procedures for fire water pumps and water sources must be carried out in accordance with the 3/2/9/3

Chapters One andconditions


Chapter Two).
for water sources and fire pumps (Part Two -

proofreading models 10/2/3

3/2/10/1 The network of rubber hoses (design stage and executive plans), see model ( 3/ 2-1 ) fire hose (suggested

by illustrated evidence), look at model ( 3/2-2.) 3/2/10 /2

Location detection of the rubber hose system, see Exhibit ( 3/2-3). 3/2/10/3

Maintenance of rubber hoses, see form ( 4-2/3). 3/2/10/4

January 2006 Requirements for firefighting and alarm equipment - Part Two
168
Machine Translated by Google

3/2 reel rubber hose systems

Model (2/3-1 ) Checking the rubber hose network (design stage and executive plans)

Notes Details item


..........................
1 number of hoses

M ( ) Within 40 ( )
2 The distance between the hoses
M Greater than 40

( ) Suitable
3 diameters of pipes in the net
( ) Not suitable

( ) Swinging
4 hose type
( ) Fixed

( ) Pump ( )
5 source of water
High tank ( )

Sufficient
6 Water source capacity
( ) Insufficient

()
7 Pressure available for furthest hose
Sufficient ( )

Insufficient ( ) Next to
8 Hose installation location
the outlets ( ) Away

from the outlets ( ) the hose


9 firebox
inside the box ( ) the hose

without a box ( )
10 extinguishers
with the

hose ( )
11 Dimensions of the firebox
separated ( ) suitable ( ) unsuitable

January 2006 Requirements for firefighting and alarm equipment - Part Two
169
Machine Translated by Google

3/2 reel rubber hose systems

Form (2/ 3-2) Fire Hose Check - (Suggested with illustrated evidence)

Notes Details item


.......................... 1
manufacturer (brand)

..........................
2 agent

( ) approved
3 accreditation
( ) not supported
..........................
4 diameter

( ) 2 modes
Sprayer modes
5
only ( ) 3
open - close - spray - push
modes ( ) 4

modes ( )
6
Hose quality

Oscillating
7 operating
( ) Fixed ( ) Manual ( ) Auto
.......................... 8
Pipe quality

..........................
9 quality of connections

..........................
10 pipe specifications

..........................
11 connector specifications

..........................
12 quality valves

..........................
13 fuse specifications

January 2006 Requirements for firefighting and alarm equipment - Part Two
170
Machine Translated by Google

3/2 reel rubber hose systems

Form (3/2-3) On- site audit of the rubber hose system

Notes Details item


(As approved)
1
Hose quality
Contrary to

approved
2 Install the hose
(correctly)

Wrong way)
3 in place of Khartoum
As per plan

(contrary
4 Install the valve
to plan)

Correct
Hose run (thrust pressure) 5
(Incorrect)

Appropriate
Sprayer modes
6

open - close - spray - push

(Inappropriate) 2 modes
7 Leakage
only ( 3 modes) 4

modes (No noticeable


8 action valves
leakage) There is a large

leakage) It works Run the auxiliary pump


9

properly (Does not (If any)

work
10 Water source capacity
properly)

Works
11 firebox
properly

(Does not Pump room protection


12
work properly) Appropriate (Inappropriate)(IfAppropriate
any) (Inappropriate) There is protection (T
( ( ( ( ( ( ( ( ( ( ( ( ( ( ( ( ( ( ( ( ( ( ( ( (

January 2006 Requirements for firefighting and alarm equipment - Part Two
171
Machine Translated by Google

3/2 reel rubber hose systems

Form (3/ 2-4) Maintenance audit of rubber hoses

Notes Details item


weekly maintenance

( ) available 1 ) The water supply contains the

( ) not available ( ) required quantity.

leakage ( ) no leakage 2 ) Leakage from the valves or hose

( ) obstruction ( ) no
1
obstruction ( )
(3 ) The presence of obstacles in front of Khartoum
correctly ( ) incorrectly

( ) working ( ) not
(4 ) Put the hose on the reel
working

(5 ) Turn on the pumps

Monthly maintenance

( ) operated properly ( ) did not


(1 ) Turn the hoses on and off
operate as required ( ) installed well ( )

some were not


(2 ) Install the pipes and accessories
installed ( ) functioned
2
properly ( ) did not function
(3 ) Operation and maintenance of pumps
properly ( ) suitable ( ) unsuitable

()
(4 ) Hose boxes case
maintenance was

done ( ) no work was done (5 ) Hose sprayer, lubrication

maintenance and maintenance

January 2006 Requirements for firefighting and alarm equipment - Part Two
172

You might also like