You are on page 1of 18

Machine Translated by Google

3/3 internal fire sockets (nozzles) systems

Chapter Three

Chapter Three

Internal fire outlets (nozzles) systems

January 2006 Requirements for firefighting and warning equipment - Part Two
Machine Translated by Google

3/3 internal fire sockets (nozzles) systems

Definition : 1/3/3
They are fire sockets (nozzles) distributed in the floors and parts of the building required to be protected to combat the

actual fire inside the building, and they are connected in the form of pipes fed with water from a suitable source, as will be mentioned later.

Systems are types 2/3/3


Internal fire alarms are divided into the following types:

The dry ascent system 1/2/3/3

starts from the ground floor B and consists of a main ascending pipe, devoid of water, installed in the
buildings and a (push pointintakes
to lead)
(nozzles)
the water
distributed
is pumped inby
thethe
floors
fire pumps,
and places
andrequired
feeds thetofire
assist

men Extinguishing in the delivery of control water to the upper floors, see ( 3/3-1 ) fig.

Figure ( 3/3-1 ) The dry riser system

January 2006 Requirements for firefighting and warning equipment - Part Two

175
Machine Translated by Google

3/3 internal fire sockets (nozzles) systems

The rising wet system consists 2/2/3/3

of a network of water extensions, engineered to feed the fire intakes distributed in parts and floors.

The building to be protected, and the network is supplied with water from a suitable water source in order to fight the fire by

firefighters or individuals trained for this purpose, and it is divided into two categories:

The fire outlet


accordance with the requirements of and hose shall have a diameter of 65 (A), which is for the use of firefighters only, in

licence.

millimeter (b) It is for the use of firefighters and trained personnel, so that the fire socket is 65 mm in diameter.

mm for the hose, in order to facilitate the use of the hose by the occupants of the building with a diameter adapter to 40

coaches.

Water sources The 3/3/3

water source must be suitable, in accordance with the design conditions and details contained in the general conditions for

water resources (Part Two - Chapter One).

system components 4/3/3

The dry riser system consists of the following components: 3/3/4/1

(a) The main ascending tube.

(b) a payment point .

(c) a non-return valve .

(D) Um. Take

(e) Air relief valve .

(f) An isolation valve.

January 2006 Requirements for firefighting and warning equipment - Part Two

176
Machine Translated by Google

3/3 internal fire sockets (nozzles) systems

The wet riser system consists of the following components: (a) 3/3/4/2

The components mentioned in the dry riser system.

(b) The source of the water.

(c) Flow switch .

(d) Valve wrench and equipment.

(E) Internal intake boxes.

(f) Pipes, their connections and accessories.

Materials Specifications 5/3/3


The components of the system shall be in accordance with the following specifications:

The pipes and their 1/5/3/3

accessories are in accordance with the specifications of the fire equipment materials (Part One - Chapter One) and can bear a pressure of 150 % of

operating pressure.

The fire socket is 2/5/3/3

the lid
made according to the specifications mentioned in Table C ( 3/3-1 ) . The connection shall be a quick female coupling with the

hem and the chain , see Figure (3/3-2 ). It is usually made for different positions, as in Figure ( 3/3-3).

Push point meets 3/5/3/3

The point consisted of


mm. And the fire socket specification, except that the connection is a 65 " male quick coupler .

mm and four holes if the riser tube has a diameter of two holes if the riser tube has a diameter of 100 as in Figure ( 3/3-4).

millimeter Combined with a non-return valve and a drain valve with a diameter of 25 150 mm

The hose 4/5/3/3

is a fabric lined with rubber according to the specifications of materials for fire equipment (Part One - Chapter One), and it has a diameter

millimeter . length of the hoseof


is 40
30 mm, or a length of 25 meters and a diameter of 65. The

Drop the sprinklers and connections 3/3/5/5

In accordance with the specifications of fire equipment materials (Part One - Chapter One).

January 2006 Requirements for firefighting and warning equipment - Part Two

177
Machine Translated by Google

3/3 internal fire sockets (nozzles) systems

Figure ( 2-3/3 ) Figure A (take the nozzle) of the fire

Figure ( 3/ 3-3) Different shapes of internal fire sockets (nozzles).

January 2006 Requirements for firefighting and warning equipment - Part Two

178
Machine Translated by Google

3/3 internal fire sockets (nozzles) systems

Figure ( 3/3-4 ) Push point with two or four holes

Design Principles The 6/3/3


following must be taken into account when designing and calculating the fire intake system of both types:

Dry upward system 1/6/3/3

(a) The number of rising main pipes shall be determined according to the floor area and at a rate of not less than one main pipe

2 per 1000
m.

(B) The number of fire outlets in the floor shall be determined so that the distance between any outlet and the farthest point in the floor does not exceed

20 . M

(c) The diameter of the riser pipe feeding one outlet on the floor shall not be less than 100 mm, which feeds

millimeter .
More than one floor socket for 150

(d) When changing the direction of the pipe path, elbows of large diameter should be used to reduce friction losses .

January 2006 Requirements for firefighting and warning equipment - Part Two

179
Machine Translated by Google

3/3 internal fire sockets (nozzles) systems

(e) The air relief valve shall be installed at the highest point of the ascending pipe, preferably in the air

outside on the surface. The

rising wet system (a) the 2/6/3/3

factors mentioned in the previous paragraph (1/6/3/3).

To be used in simple fires and according to conditions license.


(b) A rubber fire hose of 25 mm diameter may be added to the

Q. (c) The amount of water must be sufficient for 1

(D) The required flow must be 2000 LD /L for each riser pipe, with an increment of 1000 LD /L regardless of the number of

rising tubes.

(e) In the event that another firefighting system is involved with the wet riser system, when calculating the amount of flow, the

need for both systems is taken into account, and when calculating the pressure, the network is designed on the basis of the

higher pressure of the two networks, provided that the other system is provided with means to reduce the pressure.

(f) The pressure required to be available in the water source is calculated on the basis that the minimum pressure at the

farthest outlet is 5.4 bar at a flow of 950 d/L, in addition to the pressure loss due to the effect of friction and the height difference.

The floors of the building can be divided into low pressure areas (g) in buildings whose height is more than 80 for the lower

floors, and high pressure areas for the upper floors, and each area must be fed by an independent main riser pipe , as in Figure

( 3/3-5).

(h) In buildings with a large floor area and divided into separate fire zones , each fire shall be fed

Sector with an independent ascending main tube.

mm if it is 150 M and its height is more than 30 mm. (i) The diameter of the rising pipe shall not be less than 100 mm if

(j) The diameter of the main pipe directly connected to the pump must be greater than the diameter of the riser pipe or any

other pipe branching from it.

(k) The diameter of the pipe must be suitable for flow and supply, according to Table ( 1-3/3).

January 2006 Requirements for firefighting and warning equipment - Part Two

180
Machine Translated by Google

3/3 internal fire sockets (nozzles) systems

exceed 40 m, so that the (l)


launchers
The distance
of spraying
betweenhoses
each( two
30 mconsecutive
long hose ) outlets
reach aon
distance
the same
notfloor
exceeding
should10
not
m

from the farthest point on the floor.

Figure (3/3-5 ) A model of internal fire intakes and fire sprinkler systems

January 2006 Requirements for firefighting and warning equipment - Part Two

181
Machine Translated by Google

3/3 internal fire sockets (nozzles) systems

Table (3/3-1 ) Diameter of the rising tube The

diameter of the tube

()

pipe length mm tube length tube length Flow (d/

more than 30 ( m) up to (30 m) up to (15 m) l) 1520

150 100 150 100 150 2280

150 150 200 150 200 3040

200

200
more than 3040

licensing schemes 3/6/3/3

When submitting a license application, the following drawings and data must be attached to it:

(a) The design diagrams showing vertical and horizontal projections showing the locations of payment points and sockets in each

floor as well as relief and isolation valves .

(b) Detailed drawings for the installation of sockets, payment points and fire boxes.

(c) Executive drawings and hydraulic calculations according to the form prepared for that, in addition to the illustrated guide to the

for the source


payment points and the rest of the
And materials.

January 2006 Requirements for firefighting and warning equipment - Part Two

182
Machine Translated by Google

3/3 internal fire sockets (nozzles) systems

technical equipments 7/3/3

Dry rising system The 1/7/3/3

technical installation works must be carried out in accordance with the principles of the profession and the instructions of the manufacturer, in addition to the conditions

next :

(a) Installing the main rising pipe in the skylight near the place of the outlet, so that it is visible outside the walls, and is

in the floors, and the air vent valve at the highest point connected to the payment point and all the outlets

.from him

m of tile floor on all floors and roof. (b) Installing the outlet at a height from 0.1 m to 3.1 m

Boxes inside the walls according to the specifications mentioned in Y (C) Maintaining the intakes - in Table C

( 2-3/3) , or inside the firefighting equipment box.

(d) The outlet must be installed within the protected staircase space or the protected staircase, and if this is not possible,

it must be close to the escape exits as approved by the competent authority.

(e) The pipes must be securely fixed with appropriate and approved tools and anchors, not less than one on each floor,

and a fulcrum at the bottom that bears the weight of the pipe.

(f) If the pipes extend to a large distance, they must be provided with means of protection against expansion.

(g) Pipes and joints shall be coated with a base coat of anti-corrosion followed by a final coat of red paint.

(H) When installing the payment point , the following conditions

must be observed: 1 ) It shall be in a visible location at the entrance of the building facing the

than 0.1 mm from the ground


nearest
surface
place
. The
toopening main
which the
of thestreet.
fire engine2can
) Itsreach.4
drain valve height
shall beshall
)at not
It the
shall be more
bottom
not beof
more
the

than 18 meters away.5 ) An indicative sign indicating its

use shall be affixed to it.

(i) An approved non-return valve must be installed after the payment point at an appropriate distance, even if the payment

point contains a non-return valve, and it is prohibited to install any other valve on the payment point.

(j) The sockets and push points shall be provided with their respective covers and rubber gaskets .

January 2006 Requirements for firefighting and warning equipment - Part Two

183
Machine Translated by Google

3/3 internal fire sockets (nozzles) systems

(k) An indicative sign must be put on it (dry outlet for firefighters use only).

(l) The network must be connected to an earth line in accordance with the specifications approved in the country.

(m) The installation of the ascending pipe must be started during implementation, so that it rises with the height of the building, in

order to use it for control during implementation, if the project is not provided with a temporary network for this purpose.

Wet upward system 2/7/3/3

(A) The conditions mentioned in the previous paragraph, the dry ascent system - Paragraph (1/7/3/3 ).

(B) Installing outlets inside boxes containing fire hoses of the appropriate diameter with hose holders, spray ejectors, connections

and any other equipment according to the terms of the license, Figure ( 6-3/3).

(C) A line shall be installed to check the performance of the pumps (if any) from the feeding line to the reservoir, and its diameter shall be equal

diameter of the feed line.

(D) A non-return valve and an approved isolation valve shall be installed at the water source, in addition to the existing valve at the water source

payment point .

installed at
(e)an
If appropriate
the water source
distance
feeds
from
more
thethan
building,
one network
as well as
in approved
on the main
buildings,
pipe connecting
a standing
thevalve
same with
building.
an indicator must be

(f) An approved pressure gauge must be installed at the water source suitable for the network pressure.

(g) If the pressure is greater than 7 bar, the outlet valve shall have a pressure regulator as shown in

( 3/3-7 ) fig

Valves of the types that show the direction of opening, closing, and flow by means of arrows (h) All metal must be prominent on

the valve or the opening hand .

(i) The inlet valves shall be provided with a drain hole to remove the deposited dirt so that it does not seep into

Khartoum .

January 2006 Requirements for firefighting and warning equipment - Part Two

184
Machine Translated by Google

3/3 internal fire sockets (nozzles) systems

(J) In tall buildings with large areas, more than one outlet must be installed , according to the conditions

licence.

Each system (k), if the water source feeds other fire systems in addition to the intake system, must have an

independent payment point attached to a plate on which the type of system associated with it is written.

(l) The connection of the water source with the intake network must be at the lowest level of the pipe

the main .

(m) Any curvature in the path of the pipes must be avoided so that air does not get trapped inside the network

Any inverted connection (siphon) an air vent must be installed .

(n) The network pipes must not pass through potentially dangerous or unprotected areas, and they must be far from

.
any potential external influences

Figure (3/3-6 ) an internal socket box with all its equipment

January 2006 Requirements for firefighting and warning equipment - Part Two

185
Machine Translated by Google

3/3 internal fire sockets (nozzles) systems

Figure ( 3/3-7 ) an internal outlet with a pressure regulator

Examination and testing


3/3/8
Inspections must be conducted in accordance with the principles of the profession, provided that they are not less than the following:

Dry upward system 1/8/3/3

(a) Examine the network under 15 bar pressure or at 150 % of the operating pressure for at least two hours.

(b) The implementing contractor or the supervising body shall prepare the testing equipment, including pressure and flow gauges

Occasion .

Ensure that the relief valve is valid . (c) The nearest outlet and the furthest outlet from the payment point shall be examined as well

(d) Ensure that there are no leakages or blockages in the sockets on all floors, and that the leakage is at the payment point,

within acceptable limits after operation.

January 2006 Requirements for firefighting and warning equipment - Part Two

186
Machine Translated by Google

3/3 internal fire sockets (nozzles) systems

Wet upward system 2/8/3/3

(A) The conditions mentioned in the previous paragraph, the dry ascent system - Paragraph (1/8/3/3).

(b) The operation of the flow switches must be checked by means of special tools for this purpose.

(c) The gauges and switches of all valves must be checked and the alarm signal reached on the panel

control .

(D) The inlet is opened at the highest level, and the pressure difference in both cases is noted, and it is matched with the design.

(e) Flow and pressure shall be checked at the water source and outlets.

(f) Examination of pillars , ties and anchors to ensure their suitability.

periodic maintenance 9/3/3

Maintenance works must be carried out in accordance with the principles of the profession, provided that they are not less than the following conditions

Weekly Maintenance (a) 1/9/3/3

Ensure that the main valve is always open except for the maintenance period.

(b) Ensure that the water is drained from the non-return valve to the push point .

(c) Ensure that the valves of the outlets are closed, test their operation, and that the rubber gaskets and covers of the outlets are

present, and that there is no leakage.

(d) Ensure that the plates are located at the locations of the intakes and payment points, clean them and, if necessary, rewrite them.

(e) Ensure the water level in the tank in the case of a wet riser system .

Ensure that the electric current is connected to the pumps in the case of a wet riser system. (and) should

January 2006 Requirements for firefighting and warning equipment - Part Two

187
Machine Translated by Google

3/3 internal fire sockets (nozzles) systems

Monthly maintenance 2/9/3/3

(a) Testing and cleaning the intakes in the case of a dry riser system .

(b) Clean the outlets and ensure the integrity of the hoses and place them in the box in an appropriate manner, and

not connect the hose in the outlets in the case of a wet riser system.

(c) Operate pumps and monitor control panels and gauges in the case of a wet riser system.

(d) Ensure the validity of the air relief valve .

annual maintenance 3/9/3/3

(A) Changing the water in the case of a wet riser system and maintenance in accordance with the conditions of water sources (Part Two).

chapter one.)

(b) Carrying out the necessary maintenance for the pumps and electrical panels in the case of the wet riser system, according to the conditions

Fire pumps (Part Two - Chapter Two).

(c) Ensure the position of the network, pipe extensions , anchors and pillars, and note any leakage and repair it.

n audit forms 3/3/10

3/3/10/1 Design and executive provisions (internal fire sockets), see form ( 3/3-1).

Suggested materials (dry riser system and wet riser system), see form ( 3/3-2). 3/3/10/2

3/3/10/3 Location detection - (dry riser system and wet riser system), see form ( 3/3-3).

January 2006 Requirements for firefighting and warning equipment - Part Two

188
Machine Translated by Google

3/3 internal fire sockets (nozzles) systems

From Form ( 3/ 3-1) (review of design and implementation provisions - (internal fire sockets) details

Notes item
( ) Appropriate
The location of the payment point in relation to the location of
1

( ) inappropriate
the building and the closest place to the street

( ) Exists ( )
2 non-return valve
Not present ( )

Appropriate
3 Elevation of the payment point
( ) Not appropriate

( ) Next to the exit


4 place sockets
( ) away from the exit

( ) Appropriate
5 socket height
( ) inappropriate

( ) sufficient
6 the number of sockets in the floor
( ) insufficient ( )

correct The location of the relief valve is


7

( ) Incorrect ( ) at the top of the net

Correct ( )
8
Location of the isolation valve

Incorrect ( )

Reservoir ( )
9 Water source (wet riser system)
Upper reservoir ( )

Enough
10 Water source capacity
( ) not enough

( ) sufficient
11 available pressure

( ) insufficient ( )

true
12 hydraulic calculations
( ) Incorrect

January 2006 Requirements for firefighting and warning equipment - Part Two

189
Machine Translated by Google

3/3 internal fire sockets (nozzles) systems

Form ( 3/ 3-2) (review of the proposed materials - (the dry riser system and the wet riser

Notes system) B details item


Internal fire sockets

1 ) Manufacturer (Brand) 2 )

Make (Model) 3 )

Dealer 4 )

Authorized according to specifications


1

( ) oblique vertical

( ) straight upright
(5 (Fig
( ) oblique

upright ( ) oblique horizontal

6 ) The materials from which

the payment

point is made 1 ) The manufacturer

(brand) 2 ) The make (model)

2
3 ) The agent 4 )

Approved according to the specifications

( ) double
(5 (Fig
( ) quadruple

pipes

3
Type ( 1)

(2 )

Specifications Non-

return valve

(1 ) for type (2 ) (make 4

(model) 3 )

(specification )

(4 ) agent

(isolation

5
valve ) (1 ) (specification )

(2 ) (model (model)

3 ) (specification (4) (agent

January 2006 Requirements for firefighting and warning equipment - Part Two

190
Machine Translated by Google

3/3 internal fire sockets (nozzles) systems

Form ( 3/3-3 ) Checking the on-site detection (dry riser system and RH riser system) Notes for details

item
( ) appropriately
1 Install the payment point and its parts
( ) Inappropriate

( ) approved by the catalog


2 quality payment point
( ) Not of approved quality ( )

According to the scheme ( ) Contrary to the scheme


3 place the payment point

( ) Appropriately ( )
4 Installation of sockets and their parts
Inappropriate ( )

Approved by the catalog


5 quality sockets
( ) Not approved by quality ( )

Against the plan ( ) According to the plan 6 place sockets

( ) Not Found ( ) Available


7 Install the non-return valve
( ) inappropriate ( ) Appropriate

( ) Not Found ( ) Available Install the relief valve at


8

( ) inappropriate ( ) Appropriate the top of the network

( ) is a valid place Isolation valve


9

( ) incorrect installation (wet riser system only)

( ) not available ( ) present


10 Pay Point Indication Panel
( ) Inappropriate ( ) Suitable

( ) According to plan
11 Installation of pipes and fittings
( ) Not according to plan

( ) Properly ( )

Incorrect ( ) Dyed
12 Installation of tubes and accessories
red ( ) Not dyed ( ) Leakage ( ) No

leakage ( M) Fit ( ) Not

fit
13 Choosing the system

14 pressure

January 2006 Requirements for firefighting and warning equipment - Part Two

191

You might also like